DANFOSS - FCD 300 Configuration for Conveyor M6 / Beer Fil

PNU # Display Text Operation and Display


001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 018 019 020 024 025 026 100 101 102 103 104 105 106 107 108 109 117 119 120 121 122 123 126 127 128 130 131 132 133 134 135 136 137 138 139 140 142 144 146 LANGUAGE OPERATION SITE LOCAL REFERENCE ACTIVE SETUP EDIT SETUP SETUP COPY LCP COPY FREQUENCY SCALE DISPLAY LINE 2 DISPLAY LINE 1.1 DISPLAY LINE 1.2 DISPLAY LINE 1.3 LOC CTRL/CONFIG. LOCAL STOP LOCAL JOGGING LOCAL REVERSING LOCAL RESET DATA CHANGE LOCK POWER UP ACTION HAND OPERATION USER QUICKMENU QUICK MENU SETUP LED STATUS

Parameter Description
Language Local/Remote Operation Local reference Active Setup Programming Setup Setup copying LCP copy Display scaling of output frequency Large display readout Small display line 1.1 Small display line 1.2 Small display line 1.3 Local Control Local Stop Local Jog Local reversing Local reset of trip Lock for data change Operating mode at Power-up, local operation Userdefined Quick Menu Quick Menu setup LED Status [0] [0] [1] [5] [0] [0] [4] [1] [6] [8] [4] [1] [0] [0] [1] [0] [1] [0] [0] [0] [1]

User-set value
ENGLISH REMOTE 20.000 Hz SETUP 1 ACTIVE SETUP NO COPY NO COPY 1.00 FREQUENCY [Hz] REFERENCE [%] MOTOR CURRENT [A] POWER [kW] LOC+DIG CTRL/AS P100 ENABLE DISABLE DISABLE ENABLE NOT LOCKED LOCAL = STOP DISABLE DISABLE [1] 000 OVERLOAD SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz 10% 18.000 OHM 1.30 OFF

Load and motor


CONFIG. MODE Configuration TORQUE CHARACT Torque characteristics MOTOR POWER Motor Power PM,N MOTOR VOLTAGE Motor Voltage UM,N MOTOR FREQUENCY Motor Frequency fM,N MOTOR CURRENT Motor Current IM,N MOTOR NOM. SPEED Rated Motor Speed AUTO MOTOR TUN. Automatic motor tuning, ATM STATOR RESISTAN Stator resistance RS STATOR REACTANCE Stator reactance XS RESONANCE DAMP. Resonance dampening HIGH START TORQ. High start torque START DELAY Start delay START FUNCTION Start function FUNCTION AT STOP Function at stop MIN.F. FUNC.STOP Min. frequency for activating of function at stop DC BRAKING TIME DC braking time DC BRAKE CUT-IN DC brake cut-in frequency MOT.THERM PROTECT Thermal motor protection START FREQUENCY Start frequency INITIAL VOLTAGE Initial voltage DC BRAKE VOLTAGE DC brake voltage START VOLTAGE Start voltage LOAD COMPENSATIO Load compensation U/F RATIO U/f-ratio SLIP COMP. Slip compensation DC HOLD VOLTAGE DC hold voltage BRAKE CUT OUT Brake cut out value BRAKE CUT IN Brake cut in frequency CURRENT MIN VAL Current, minimum value LEAK. REACTANCE Leakage reactance XL GAIN AC BRAKE Gain AC brake RESET VECTOR Reset voltage vector

[0]

[2] [0]

[4]

[0]

148 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 221 223 224 225 226 227 228 229 230 231 302 303 304 305 307 308 309 310 314 315 316 317 318 319 323 327 328 341 342 343 344 349 400 405 406 409 411 413 414

MOTOR TYPE OUT FREQ RNG/ROT MIN. OUTPUT FREQ. MAX, OUTPUT FREQ. REFERENCE RANGE MIN. REFERENCE MAX. REFERENCE RAMP TYPE RAMP UP TYPE 1 RAMP DOWN TIME 1 RAMP UP TYPE 2 RAMP DOWN TIME 2 JOG RAMP TIME Q STOP RAMP TIME JOG FREQUENCY REF FUNCTION PRESET REF. 1 PRESET REF. 2 PRESET REF. 3 PRESET REF. 4 CATCH UP/SLW DWN CURRENT LIMIT WARN. CURRENT LO WARN. CURRENT HI WARN. FREQ. LOW WARN. FREQ. HIGH WARN. FEEDB. LOW WARN. FEEDB HIGH FREQ BYPASS B.W. FREQ. BYPASS 1 FREQ. BYPASS 2 DIGITAL INPUT 18 DIGITAL INPUT 19 DIGITAL INPUT 27 DIGITAL INPUT 29 DIGITAL INPUT 33 AI [V] 53 FUNCT. AI 53 SCALE LOW AI 53 SCALE HIGH AI [MA] 60 FUNCT. AI 60 SCALE LOW AI 60 SCALE HIGH LIVE ZERO TIME 0 LIVE ZERO FUNCT. AO 42 FUNCT. RELAY 1-3 FUNCT. PULSE MAX 33 PULSE MAX 29 DO 46 FUNCTION DO 46 MAX. PULS PRECISE STOP PULSE COUNT PRE SPEED COMP DELAY BRAKE FUNCTION RESET MODE AUTORESTART TIME TRIP DELAY CUR. SWITCH FREQ. OVERMODULLATION MIN. FEEDBACK Output frequency range Output frequency low limit (FMIN) Output frequency high limit (FMAX) Reference range Minimum reference, RefMIN Maximum reference, RefMAX Ramp type Ramp-up time 1 Ramp-down time 1 Ramp-up time 2 Ramp-down time 2 Jog ramp time Quick stop ramp-down time Jog frequency Reference function Preset reference 1 Preset reference 2 Preset reference 3 Preset reference 4 Catch up/slow down reference Current limit. ILIM Warning: Low current, ILOW Warning: High current, IHIGH Warning: Low frequency, fLOW Warning: High frequency, fHIGH Warning: Low feedback, FBLOW Warning: High feedback, FBHIGH Frequency bypass, bandwidth Frequency bypass 1 Frequency bypass 2 Terminal 18, input Terminal 19, input Terminal 27, input Terminal 29, input Terminal 33, input Terminal 53, analogue input voltage Terminal 53, min. scaling Terminal 53, max. scaling Terminal 60, analogue input current Terminal 60, min. scaling Terminal 604, max. scaling Time out Function after time out Analogue output terminal 42 Relay output 1-3 Pulse Max. 33 Pulse Max. 29 Digital output terminal 46 Terminal 46, max. pulse scaling Precise stop function Counter value Speed comp delay Brake function Reset function Automatic restart time Trip delay overcurrent. ILIM Switching frequency Overmodulation function Minimum feedback, FBMIN [0]

GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 50.000 Hz LINEAR 1.00 sec 0.50 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% 0 Hz (OFF) 0.0 Hz 0.0 Hz NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz UNIT READY 5000 Hz NORMAL 100000 pulses OFF OFF MANUAL RESET 5 sec OFF (61 sec.) 4.5 kHz ON 0.000

References and limits

[0]

[0]

[0]

Inputs and outputs


[0] [0] [0] [0] [0] [1]

[0]

[0] [7] [0]

[1] [0]

Special functions
[0] [0]

[1]

415 416 445 456 500 501 502 503 504 505 506 507 508 509 510 512 513 514 535 600 601 602 603 604 605 615 616 617 618 619 620 621 624 625 626 627 628 630 632 634 635 640 641 642 643 645 646 678 800 801 803 804 805 832 833 834 835 836

MAX. FEEDBACK REF/FEEDB. UNIT FLYING START BRAKE VOL REDUCE BUS ADDRESS BAUDRATE COASTING SELECT Q STOP SELECT DC BRAKE SELECT START SELECT REVERSING SELECT SETUP SELECT PRES.REF. SELECT BUS JOG 1 FREQ. BUS JOG 2 FREQ. TELEGRAM PROFILE BUS TIMEOUT TIME BUS TIMEOUT FUNC BUS FEEDBACK 1 OPERATING HOURS RUNNING HOURS KWH COUNTER POWER UP's OVER TEMP's OVER VOLTS F.LOG: ERROR COD F.LOG: TIME F.LOG: VALUE RESET KWH COUNT RESET RUN. HOUR OPERATION MODE VLT TYPE SOFTWARE VERSION LCP ID NO PARAM DB ID POWER UNIT DB ID APP. OPTION COM. OPTION

Maximum feedback, FBMAX Process units Flying start Brake voltage reduce Address Baudrate Coasting Quick-stop DC-brake Start Reversing Selection of Setup Selection of speed Bus jog 1 Bus jog 2 Telegram profile Bus time interval Bus time interval function

[0] [0]

1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 444.6 h 229.8 h 31.2 kWh 64 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.176 NOT USED 1.44 2.06 1.5 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex

Serial communication
[5] [3] [3] [3] [3] [3] [3] [0]

[0]

Technical functions
Operating hours Hours run kWh counter No. of cut-ins No. of overtemps No. of overvoltages Fault log : Error code Fault log : Time Fault log : Value Reset of kWh counter Reset of hours-run counter Operating mode VLT Type Software version number LCP identification number Database identification number Power section identification number Application option type Communication option type BMC software identification Unit identification for communication Software parts no. Software version BMC software identification Power card identification

[0] [0] [0]

UPDATE VLT COMM OPTION SW APPL OPTION SW Configure Control Card PROTOCOL SELECT BAUD RATE SELECT BUS TIME OUT TIME OUT FUNCT. BIT 10 FUNCTION BUS OFF INT. BEH. FIELDBUS ENABLE COS FILTER 1 COS FILTER 2 COS FILTER 3 Protocol select Baud rate select Bus time out Bus time out function Bit 10 function Bus Off Interrupt Behavior Fieldbus enable Filter Mask for status word Filter Mask for main actual value Filter Mask PCD 1 [0] [1] [2] [2] [20]

837 838 850 851 852 904 915 916 918 970 971 980 981 982 990 991 992

COS FILTER 4 EDS DATA TYPES TRANSMIT ERROR C RECEIVE ERROR C BUS OFF ERROR C PPO TYPE SELECT PCD CONFIG WRITE PCD CONFIG READ STATION ADDRESS EDIT SETUP SELECT STORE DATA VALUE DEFINED PARAM. 1 DEFINED PARAM. 2 DEFINED PARAM. 3 MODIFI. PARAM. 1 MODIFI. PARAM. 2 MODIFI. PARAM. 3

Filter Mask PCD 2 EDS Data Types Readout Transmit Error Counter Readout Receive Error Counter Readout Bus Off Counter PPO Selection PCD write configuration PCD read configuration Station address/MAC ID Parameter setup selection Save data values Defined parameter 1 Defined parameter 2 Defined parameter 3 Modified parameter 1 Modified parameter 2 Modified parameter 3 [5] [0] [13] [1]

FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 006 ACTIVE SETUP OFF [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

CD 300 Configuration for Conveyor M6 / Beer Filler


Note (Setting range)

Remote control

Value : 0.01 - 100.00

Remote-operated control as parameter 100 Active Not active Not active Active Forced stop, use saved ref. Not active Value : [index 1 - 20] Value : 0 - 999 Overload Speed control, open loop Constant torque Value : 0.18 - 4 kW Value : 50 - 999 V Value : 24 - 1000 Hz Value : 0.01 - IMAX Value : 100 - fM,N x 60 (max. 60000 rpm) Optimisation off Value : 0.000 - x.xxx Ohm Value : 0.00 - x.xx Ohm Value : 0 - 100 % Value : 0.0 - 0.5 sec. Value : 0.0 - 10.0 sec. Coasting during start delay time Coasting Value : 0.1 - 10 Hz Value : 0 - 60 sec. Value : 0.0 (OFF) - parameter 202 ETR trip 1 Value : 0.0 - 10.0 Hz Value : 0.0 - 200.0 V Value : 0 - 100 % of max. DC brake voltage Value : 0.0 - 100.00 V Value : 0.0 - 300.0 % Value : 0.00 - 20.00 V/Hz Value : -500 - +500% of rated slip compensation Value : 0 - 100% of max. DC hold voltage Value : 0.5 - 132.0/1000.0 Hz Value : 0.5 - 132.0/1000.0 Hz Value : 0 % of Inom - 100 % of Inom Value : 0.000 - xxx,xxx Ohm Value : 1.00 - 1.50 Off

Only clockwise, 0-132 Hz Value : 0.0 - fMAX Value : fMIN - 132/1000 Hz (parameter 200) Value : Min. reference - Max. reference Value : -100,000.000 - par. 205 RefMAX Value : par. 204 ReMIN - 100,000.000 Linear Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.0 - par. 202 Value : -100.00 % - +100.00 % Value : -100.00 % - +100.00 % Value : -100.00 % - +100.00 % Value : -100.00 % - +100.00 % Value : 0.00 - 100 % of the given reference Value : 0 - xxx.x % of par. 105 Value : 0.0 - par. 224 Value : par. 223 - IMAX Value : 0.0 - par. 226 Value : par. 225 - 132 Hz Value : -100,000.000 - par. 228 Value : par. 227 - 100,000.000 Value : 0 (OFF) - 100 Hz Value : 0 - 1000 Hz Value : 0 - 1000 Hz No function No function No function No function No function Reference Value : 0.0 - 10.0 Volt Value : 0.0 - 10.0 Volt No function Value : 0.0 - 20.0 mA Value : 0.0 - 20.0 mA Value : 0 - 99 sec. No operation Output current 0 - IMAX 0 - 20 mA No function Value : 150 - 67600 Hz Value : 150 - 67600 Hz Drive ready Value : 150 - 10000 Hz Normal ramp stop Value : 1 - 999999 Value : 0 ms - 100 ms Off Manual reset Value : 0 - 10 sec. Value : 0 - 60 sec. (61 = OFF) Value : 3000 - 14000 Hz Value : -100,000.000 - Par. 415 FBMAX

Value : Par. 414 FBMIN - 100,000.000 Off Value : 0 - 50 V Value : 1 - 126 9600 Baud Logic or Logic or Logic or Logic or Digital input Logic or Logic or Value : 0.0 - nparameter 202 Value : 0.0 - nparameter 202 Value : 1 - 99 sec. Off

Range : 0 - 130,000.0 Range : 0 - 130,000.0 Range : 0 - 9999 Range : 0 - 9999 Range : 0 - 9999 Range : 0 - 9999 Value : [Index 1 - 10] Error code 0 - 44 Value : [Index 1 - 10] Value : [Index 1 - 10] No reset No reset Normal Operation

Devicenet 125 kbps Value : 1 - 99 sec. Stop with auto restart This parameter is read only Ho;d the device in bus-off state Value : 0000 - FFFF Hex Value : 0000 - FFFF Hex Value : 0000 - FFFF Hex

Value : 0000 - FFFF Hex Errata 2

Value : Sub index 1 (PCD 1) Sub index 2 (PCD 2) Value : Sub index 1 (PCD 1) Sub index 2 (PCD 2) Value : 0 - 63 Active set up Not active Read only Read only Read only Read only Read only Read only

[Par. Number] [Par. Number] [Par. Number] [Par. Number]

DANFOSS - FCD 300 Configuration for Input Conveyors M1, M2, M3, M4, M5, M6 / Beer Filler
PNU # Display Text KEYB. & DISPLAY
001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 018 019 020 024 025 026 100 101 102 103 104 105 106 107 108 109 117 119 120 121 122 123 126 127 128 130 131 132 133 134 135 136 137 138 139 LANGUAGE OPERATION SITE LOCAL REFERENCE ACTIVE SETUP EDIT SETUP SETUP COPY LCP COPY FREQUENCY SCALE DISPLAY LINE 2 DISPLAY LINE 1.1 DISPLAY LINE 1.2 DISPLAY LINE 1.3 LOC CTRL/CONFIG. LOCAL STOP LOCAL JOGGING LOCAL REVERSING LOCAL RESET DATA CHANGE LOCK POWER UP ACTION HAND OPERATION USER QUICKMENU QUICK MENU SETUP LED STATUS

Parameter Description
Language Local/Remote Operation Local reference Active Setup Programming Setup Setup copying LCP copy Display scaling of output frequency Large display readout Small display line 1.1 Small display line 1.2 Small display line 1.3 Local Control Local Stop Local Jog Local reversing Local reset of trip Lock for data change Operating mode at Power-up, local operation Userdefined Quick Menu Quick Menu setup LED Status [0] [0] [1] [5] [0] [0] [4] [1] [6] [8] [4] [1] [0] [0] [1] [0] [1] [0] [0] [0] [1]

M1

M2

M3

M4

M5

User-set value M6

ENGLISH ENGLISH ENGLISH ENGLISH ENGLISH ENGLISH REMOTE REMOTE REMOTE REMOTE REMOTE REMOTE 20.000 Hz 20.000 Hz 20.000 Hz 20.000 Hz 20.000 Hz 20.000 Hz SETUP 1 SETUP 1 SETUP 1 SETUP 1 SETUP 1 SETUP 1 ACTIVE SETUP ACTIVE SETUP ACTIVE SETUP ACTIVE SETUP ACTIVE SETUP ACTIVE SETUP NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY 1.00 1.00 1.00 1.00 1.00 1.00 FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] REFERENCE [%] REFERENCE [%] REFERENCE [%] REFERENCE [%] REFERENCE [%] REFERENCE [%] MOTOR CURRENT [A] MOTOR CURRENT [A] MOTOR CURRENT [A] MOTOR CURRENT [A] MOTOR CURRENT [A] MOTOR CURRENT [A] POWER [kW] POWER [kW] POWER [kW] POWER [kW] POWER [kW] POWER [kW] LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE NOT LOCKED NOT LOCKED NOT LOCKED NOT LOCKED NOT LOCKED NOT LOCKED LOCAL = STOP LOCAL = STOP LOCAL = STOP LOCAL = STOP LOCAL = STOP LOCAL = STOP DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE [1] 000 [1] 000 [1] 000 [1] 000 [1] 000 [1] 000 OVERLOAD OVERLOAD OVERLOAD OVERLOAD OVERLOAD OVERLOAD SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz

Load and motor


CONFIG. MODE Configuration TORQUE CHARACT Torque characteristics MOTOR POWER Motor Power PM,N MOTOR VOLTAGE Motor Voltage UM,N MOTOR FREQUENCY Motor Frequency fM,N MOTOR CURRENT Motor Current IM,N MOTOR NOM. SPEED Rated Motor Speed AUTO MOTOR TUN. Automatic motor tuning, ATM Stator resistance RS STATOR RESISTAN STATOR REACTANCE Stator reactance XS RESONANCE DAMP. Resonance dampening HIGH START TORQ. High start torque START DELAY Start delay START FUNCTION Start function FUNCTION AT STOP Function at stop MIN.F. FUNC.STOP Min. frequency for activating of function at stop DC BRAKING TIME DC braking time DC BRAKE CUT-IN DC brake cut-in frequency MOT.THERM PROTECT Thermal motor protection START FREQUENCY Start frequency INITIAL VOLTAGE Initial voltage DC BRAKE VOLTAGE DC brake voltage START VOLTAGE Start voltage LOAD COMPENSATIO Load compensation U/F RATIO U/f-ratio SLIP COMP. Slip compensation DC HOLD VOLTAGE DC hold voltage BRAKE CUT OUT Brake cut out value BRAKE CUT IN Brake cut in frequency

[0]

[2] [0]

[4]

DANFOSS - FCD 300 Configuration for Input Conveyors M1, M2, M3, M4, M5, M6 / Beer Filler
PNU # Display Text
140 142 144 146 148 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 221 223 224 225 226 227 228 229 230 231 302 303 304 305 307 308 309 310 314 315 316 317 318 319 323 327 328 CURRENT MIN VAL LEAK. REACTANCE GAIN AC BRAKE RESET VECTOR MOTOR TYPE OUT FREQ RNG/ROT MIN. OUTPUT FREQ. MAX, OUTPUT FREQ. REFERENCE RANGE MIN. REFERENCE MAX. REFERENCE RAMP TYPE RAMP UP TYPE 1 RAMP DOWN TIME 1 RAMP UP TYPE 2 RAMP DOWN TIME 2 JOG RAMP TIME Q STOP RAMP TIME JOG FREQUENCY REF FUNCTION PRESET REF. 1 PRESET REF. 2 PRESET REF. 3 PRESET REF. 4 CATCH UP/SLW DWN CURRENT LIMIT WARN. CURRENT LO WARN. CURRENT HI WARN. FREQ. LOW WARN. FREQ. HIGH WARN. FEEDB. LOW WARN. FEEDB HIGH FREQ BYPASS B.W. FREQ. BYPASS 1 FREQ. BYPASS 2 DIGITAL INPUT 18 DIGITAL INPUT 19 DIGITAL INPUT 27 DIGITAL INPUT 29 DIGITAL INPUT 33 AI [V] 53 FUNCT. AI 53 SCALE LOW AI 53 SCALE HIGH AI [MA] 60 FUNCT. AI 60 SCALE LOW AI 60 SCALE HIGH LIVE ZERO TIME 0 LIVE ZERO FUNCT. AO 42 FUNCT. RELAY 1-3 FUNCT. PULSE MAX 33 PULSE MAX 29

Parameter Description
Current, minimum value Leakage reactance XL Gain AC brake Reset voltage vector

M1
10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 0.02 sec 0.02 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz

M2
10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 0.50 sec 0.50 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz

M3
10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 1.00 sec 1.00 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz

M4
10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 85.000 Hz LINEAR 1.00 sec 1.00 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz

M5
10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 1.00 sec 1.00 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz

User-set value M6
10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 50.000 Hz LINEAR 1.00 sec 0.50 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz

[0]

References and limits


Output frequency range Output frequency low limit (FMIN) Output frequency high limit (FMAX) Reference range Minimum reference, RefMIN Maximum reference, RefMAX Ramp type Ramp-up time 1 Ramp-down time 1 Ramp-up time 2 Ramp-down time 2 Jog ramp time Quick stop ramp-down time Jog frequency Reference function Preset reference 1 Preset reference 2 Preset reference 3 Preset reference 4 Catch up/slow down reference Current limit. ILIM Warning: Low current, ILOW Warning: High current, IHIGH Warning: Low frequency, fLOW Warning: High frequency, fHIGH Warning: Low feedback, FBLOW Warning: High feedback, FBHIGH Frequency bypass, bandwidth Frequency bypass 1 Frequency bypass 2 Terminal 18, input Terminal 19, input Terminal 27, input Terminal 29, input Terminal 33, input Terminal 53, analogue input voltage Terminal 53, min. scaling Terminal 53, max. scaling Terminal 60, analogue input current Terminal 60, min. scaling Terminal 604, max. scaling Time out Function after time out Analogue output terminal 42 Relay output 1-3 Pulse Max. 33 Pulse Max. 29 [0]

[0]

[0]

[0]

Inputs and outputs


[0] [0] [0] [0] [0] [1]

[0]

[0] [7] [0]

DANFOSS - FCD 300 Configuration for Input Conveyors M1, M2, M3, M4, M5, M6 / Beer Filler
PNU # Display Text
341 342 343 344 349 400 405 406 409 411 413 414 415 416 445 456 500 501 502 503 504 505 506 507 508 509 510 512 513 514 535 600 601 602 603 604 605 615 616 617 618 619 620 621 624 625 626 627 628 630 632 DO 46 FUNCTION DO 46 MAX. PULS PRECISE STOP PULSE COUNT PRE SPEED COMP DELAY BRAKE FUNCTION RESET MODE AUTORESTART TIME TRIP DELAY CUR. SWITCH FREQ. OVERMODULLATION MIN. FEEDBACK MAX. FEEDBACK REF/FEEDB. UNIT FLYING START BRAKE VOL REDUCE BUS ADDRESS BAUDRATE COASTING SELECT Q STOP SELECT DC BRAKE SELECT START SELECT REVERSING SELECT SETUP SELECT PRES.REF. SELECT BUS JOG 1 FREQ. BUS JOG 2 FREQ. TELEGRAM PROFILE BUS TIMEOUT TIME BUS TIMEOUT FUNC BUS FEEDBACK 1 OPERATING HOURS RUNNING HOURS KWH COUNTER POWER UP's OVER TEMP's OVER VOLTS F.LOG: ERROR COD F.LOG: TIME F.LOG: VALUE RESET KWH COUNT RESET RUN. HOUR OPERATION MODE VLT TYPE SOFTWARE VERSION LCP ID NO PARAM DB ID POWER UNIT DB ID APP. OPTION COM. OPTION BMC-SOFTWARE ID

Parameter Description
Digital output terminal 46 Terminal 46, max. pulse scaling Precise stop function Counter value Speed comp delay Brake function Reset function Automatic restart time Trip delay overcurrent. ILIM Switching frequency Overmodulation function Minimum feedback, FBMIN Maximum feedback, FBMAX Process units Flying start Brake voltage reduce Address Baudrate Coasting Quick-stop DC-brake Start Reversing Selection of Setup Selection of speed Bus jog 1 Bus jog 2 Telegram profile Bus time interval Bus time interval function [1] [0]

M1
NO OPERATION 5000 Hz NORMAL 100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 492.1 h 229.8 h 15.9 kWh 56 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06

M2
NO OPERATION 5000 Hz NORMAL 100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 492.9 h 222.9 h 12.0 kWh 56 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06

M3
NO OPERATION 5000 Hz NORMAL 100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 492.5 h 226.5 h 30.6 h 59 0 0 [1] 13 [1] 988 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06

M4
NO OPERATION 5000 Hz NORMAL 100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 486.3 h 227.5 h 74.1 kWh 55 0 0 [1] 13 [1] 1182 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06

M5
NO OPERATION 5000 Hz NORMAL 100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 489.1 h 229.7 h 31.2 kWh 65 0 0 [1] 13 [1] 988 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06

User-set value M6
UNIT READY 5000 Hz NORMAL 100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 444.6 h 229.8 h 31.2 kWh 64 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06

Special functions
[0] [0]

[1]

[0] [0]

Serial communication
[5] [3] [3] [3] [3] [3] [3] [0]

[0]

Technical functions
Operating hours Hours run kWh counter No. of cut-ins No. of overtemps No. of overvoltages Fault log : Error code Fault log : Time Fault log : Value Reset of kWh counter Reset of hours-run counter Operating mode VLT Type Software version number LCP identification number Database identification number Power section identification number Application option type Communication option type BMC software identification

[0] [0] [0]

DANFOSS - FCD 300 Configuration for Input Conveyors M1, M2, M3, M4, M5, M6 / Beer Filler
PNU # Display Text
634 635 640 641 642 643 645 646 678 800 801 803 804 805 832 833 834 835 836 837 838 850 851 852 904 915 916 918 970 971 980 981 982 990 991 992 UNIT ID SW. PART NO. SOFTWARE VERSION BMC2 ID POWER ID UPDATE VLT COMM OPTION SW APPL OPTION SW CONFIG CTRL CARD PROTOCOL SELECT BAUD RATE SELECT BUS TIME OUT TIME OUT FUNCT. BIT 10 FUNCTION BUS OFF INT. BEH. FIELDBUS ENABLE COS FILTER 1 COS FILTER 2 COS FILTER 3 COS FILTER 4 EDS DATA TYPES TRANSMIT ERROR C RECEIVE ERROR C BUS OFF ERROR C PPO TYPE SELECT PCD CONFIG WRITE PCD CONFIG READ STATION ADDRESS EDIT SETUP SELECT STORE DATA VALUE DEFINED PARAM. 1 DEFINED PARAM. 2 DEFINED PARAM. 3 MODIFI. PARAM. 1 MODIFI. PARAM. 2 MODIFI. PARAM. 3

Parameter Description
Unit identification for communication Software parts no. Software version BMC software identification Power card identification

M1
ID 007.099.187 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS [2] [20] [2] [0] [1] DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex [1] ERRATA 2 000000000 000000000 000000000 [13] INSTANCE 101 / 151 [1] 000 [1] 528 001 [5] [0] ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

M2
ID 007.099.171 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 002 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

M3
ID 007.099.173 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 003 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

M4
ID 007.038.252 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 004 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

M5
ID 007.099.164 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 005 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

User-set value M6
ID 007.099.176 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 006 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

Configure Control Card Protocol select Baud rate select Bus time out Bus time out function Bit 10 function Bus Off Interrupt Behavior Fieldbus enable Filter Mask for status word Filter Mask for main actual value Filter Mask PCD 1 Filter Mask PCD 2 EDS Data Types Readout Transmit Error Counter Readout Receive Error Counter Readout Bus Off Counter PPO Selection PCD write configuration PCD read configuration Station address/MAC ID Parameter setup selection Save data values Defined parameter 1 Defined parameter 2 Defined parameter 3 Modified parameter 1 Modified parameter 2 Modified parameter 3

DANFOSS - FCD 300 Configuration for Outlet Conveyors M7, M8, M9, M10 / Beer
PNU # Display Text Operation and Display
001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 018 019 020 024 025 026 100 101 102 103 104 105 106 107 108 109 117 119 120 121 122 123 126 127 128 LANGUAGE OPERATION SITE LOCAL REFERENCE ACTIVE SETUP EDIT SETUP SETUP COPY LCP COPY FREQUENCY SCALE DISPLAY LINE 2 DISPLAY LINE 1.1 DISPLAY LINE 1.2 DISPLAY LINE 1.3 LOC CTRL/CONFIG. LOCAL STOP LOCAL JOGGING LOCAL REVERSING LOCAL RESET DATA CHANGE LOCK POWER UP ACTION HAND OPERATION USER QUICKMENU QUICK MENU SETUP LED STATUS CONFIG. MODE TORQUE CHARACT MOTOR POWER MOTOR VOLTAGE MOTOR FREQUENCY MOTOR CURRENT MOTOR NOM. SPEED AUTO MOTOR TUN. STATOR RESISTAN STATOR REACTANCE RESONANCE DAMP. HIGH START TORQ. START DELAY START FUNCTION FUNCTION AT STOP MIN.F. FUNC.STOP DC BRAKING TIME DC BRAKE CUT-IN MOT.THERM PROTECT

Parameter Description
Language Local/Remote Operation Local reference Active Setup Programming Setup Setup copying LCP copy Display scaling of output frequency Large display readout Small display line 1.1 Small display line 1.2 Small display line 1.3 Local Control Local Stop Local Jog Local reversing Local reset of trip Lock for data change Operating mode at Power-up, local operation Userdefined Quick Menu Quick Menu setup LED Status Configuration Torque characteristics Motor Power PM,N Motor Voltage UM,N Motor Frequency fM,N Motor Current IM,N Rated Motor Speed Automatic motor tuning, ATM Stator resistance RS Stator reactance XS Resonance dampening High start torque Start delay Start function Function at stop Min. frequency for activating of function at stop DC braking time DC brake cut-in frequency Thermal motor protection [0] [0] [1] [5] [0] [0] [4] [1] [6] [8] [4] [1] [0] [0] [1] [0] [1] [0] [0] [0] [1]

M8
ENGLISH REMOTE 20.000 Hz SETUP 1 ACTIVE SETUP NO COPY NO COPY 1.00 FREQUENCY [Hz] REFERENCE [%] MOTOR CURRENT [A] POWER [kW] LOC+DIG CTRL/AS P100 ENABLE DISABLE DISABLE ENABLE NOT LOCKED LOCAL = STOP DISABLE DISABLE [1] 000 OVERLOAD SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1

M9
ENGLISH REMOTE 20.000 Hz SETUP 1 ACTIVE SETUP NO COPY NO COPY 1.00 FREQUENCY [Hz] REFERENCE [%] MOTOR CURRENT [A] POWER [kW] LOC+DIG CTRL/AS P100 ENABLE DISABLE DISABLE ENABLE NOT LOCKED LOCAL = STOP DISABLE DISABLE [1] 000 OVERLOAD SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1

M10
ENGLISH REMOTE 20.000 Hz SETUP 1 ACTIVE SETUP NO COPY NO COPY 1.00 FREQUENCY [Hz] REFERENCE [%] MOTOR CURRENT [A] POWER [kW] LOC+DIG CTRL/AS P100 ENABLE DISABLE DISABLE ENABLE NOT LOCKED LOCAL = STOP DISABLE DISABLE [1] 000 OVERLOAD SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1

Load and motor

[0]

[2] [0]

[4]

DANFOSS - FCD 300 Configuration for Outlet Conveyors M7, M8, M9, M10 / Beer
PNU # Display Text 130 START FREQUENCY Operation and Display
131 132 133 134 135 136 137 138 139 140 142 144 146 148 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 221 223 224 225 226 227 228 229 230 INITIAL VOLTAGE DC BRAKE VOLTAGE START VOLTAGE LOAD COMPENSATIO U/F RATIO SLIP COMP. DC HOLD VOLTAGE BRAKE CUT OUT BRAKE CUT IN CURRENT MIN VAL LEAK. REACTANCE GAIN AC BRAKE RESET VECTOR MOTOR TYPE OUT FREQ RNG/ROT MIN. OUTPUT FREQ. MAX, OUTPUT FREQ. REFERENCE RANGE MIN. REFERENCE MAX. REFERENCE RAMP TYPE RAMP UP TYPE 1 RAMP DOWN TIME 1 RAMP UP TYPE 2 RAMP DOWN TIME 2 JOG RAMP TIME Q STOP RAMP TIME JOG FREQUENCY REF FUNCTION PRESET REF. 1 PRESET REF. 2 PRESET REF. 3 PRESET REF. 4 CATCH UP/SLW DWN CURRENT LIMIT WARN. CURRENT LO WARN. CURRENT HI WARN. FREQ. LOW WARN. FREQ. HIGH WARN. FEEDB. LOW WARN. FEEDB HIGH FREQ BYPASS B.W. FREQ. BYPASS 1

Parameter Description
Start frequency Initial voltage DC brake voltage Start voltage Load compensation U/f-ratio Slip compensation DC hold voltage Brake cut out value Brake cut in frequency Current, minimum value Leakage reactance XL Gain AC brake Reset voltage vector

M8
0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% 0 Hz (OFF) 0.0 Hz

M9
0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% 0 Hz (OFF) 0.0 Hz

M10
0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz 3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% 0 Hz (OFF) 0.0 Hz

[0]

References and limits


Output frequency range Output frequency low limit (FMIN) Output frequency high limit (FMAX) Reference range Minimum reference, RefMIN Maximum reference, RefMAX Ramp type Ramp-up time 1 Ramp-down time 1 Ramp-up time 2 Ramp-down time 2 Jog ramp time Quick stop ramp-down time Jog frequency Reference function Preset reference 1 Preset reference 2 Preset reference 3 Preset reference 4 Catch up/slow down reference Current limit. ILIM Warning: Low current, ILOW Warning: High current, IHIGH Warning: Low frequency, fLOW Warning: High frequency, fHIGH Warning: Low feedback, FBLOW Warning: High feedback, FBHIGH Frequency bypass, bandwidth Frequency bypass 1 [0]

[0]

[0]

[0]

DANFOSS - FCD 300 Configuration for Outlet Conveyors M7, M8, M9, M10 / Beer
PNU # Display Text 231 FREQ. BYPASS 2 Operation and Display Inputs and outputs
302 303 304 305 307 308 309 310 314 315 316 317 318 319 323 327 328 341 342 343 344 349 400 405 406 409 411 413 414 415 416 445 456 500 501 502 503 504 505 506 507 DIGITAL INPUT 18 DIGITAL INPUT 19 DIGITAL INPUT 27 DIGITAL INPUT 29 DIGITAL INPUT 33 AI [V] 53 FUNCT. AI 53 SCALE LOW AI 53 SCALE HIGH AI [MA] 60 FUNCT. AI 60 SCALE LOW AI 60 SCALE HIGH LIVE ZERO TIME 0 LIVE ZERO FUNCT. AO 42 FUNCT. RELAY 1-3 FUNCT. PULSE MAX 33 PULSE MAX 29 DO 46 FUNCTION DO 46 MAX. PULS PRECISE STOP PULSE COUNT PRE SPEED COMP DELAY BRAKE FUNCTION RESET MODE AUTORESTART TIME TRIP DELAY CUR. SWITCH FREQ. OVERMODULLATION MIN. FEEDBACK MAX. FEEDBACK REF/FEEDB. UNIT FLYING START BRAKE VOL REDUCE BUS ADDRESS BAUDRATE COASTING SELECT Q STOP SELECT DC BRAKE SELECT START SELECT REVERSING SELECT SETUP SELECT

Parameter Description
Frequency bypass 2 Terminal 18, input Terminal 19, input Terminal 27, input Terminal 29, input Terminal 33, input Terminal 53, analogue input voltage Terminal 53, min. scaling Terminal 53, max. scaling Terminal 60, analogue input current Terminal 60, min. scaling Terminal 604, max. scaling Time out Function after time out Analogue output terminal 42 Relay output 1-3 Pulse Max. 33 Pulse Max. 29 Digital output terminal 46 Terminal 46, max. pulse scaling Precise stop function Counter value Speed comp delay Brake function Reset function Automatic restart time Trip delay overcurrent. ILIM Switching frequency Overmodulation function Minimum feedback, FBMIN Maximum feedback, FBMAX Process units Flying start Brake voltage reduce Address Baudrate Coasting Quick-stop DC-brake Start Reversing Selection of Setup [0] [0] [0] [0] [0] [1]

M8
0.0 Hz NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL 100000 pulses OFF OFF MANUAL RESET 5 sec OFF (61 sec.) 4.5 kHz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR

M9
0.0 Hz NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL 100000 pulses OFF OFF MANUAL RESET 5 sec OFF (61 sec.) 4.5 kHz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR

M10
0.0 Hz NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL 100000 pulses OFF OFF MANUAL RESET 5 sec OFF (61 sec.) 4.5 kHz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR

[0]

[0] [7] [0]

[1] [0]

Special functions
[0] [0]

[1]

[0] [0]

Serial communication
[5] [3] [3] [3] [3] [3] [3]

DANFOSS - FCD 300 Configuration for Outlet Conveyors M7, M8, M9, M10 / Beer
PNU # Display Text 508 PRES.REF. SELECT Operation and Display
509 510 512 513 514 535 600 601 602 603 604 605 615 616 617 618 619 620 621 624 625 626 627 628 630 632 634 635 640 641 642 643 645 646 678 800 801 803 804 805 832 BUS JOG 1 FREQ. BUS JOG 2 FREQ. TELEGRAM PROFILE BUS TIMEOUT TIME BUS TIMEOUT FUNC BUS FEEDBACK 1 OPERATING HOURS RUNNING HOURS KWH COUNTER POWER UP's OVER TEMP's OVER VOLTS F.LOG: ERROR COD F.LOG: TIME F.LOG: VALUE RESET KWH COUNT RESET RUN. HOUR OPERATION MODE VLT TYPE SOFTWARE VERSION LCP ID NO PARAM DB ID POWER UNIT DB ID APP. OPTION COM. OPTION

Parameter Description
Selection of speed Bus jog 1 Bus jog 2 Telegram profile Bus time interval Bus time interval function [0]

M8
DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 489.5 h 223.4 h 46.2 kWh 63 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 315 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.203 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s [2] [0] STOP BIT 10 = 1 > CTW ACT HOLD CAN

M9
DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 489.6 h 218.7 h 54.2 kWh 67 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.168 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN

M10
DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 488.5 h 215.4 h 50.2 kWh 69 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.167 NOT USED 1.44 2.06 1.50 NO 0.00 0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN

[0]

Technical functions
Operating hours Hours run kWh counter No. of cut-ins No. of overtemps No. of overvoltages Fault log : Error code Fault log : Time Fault log : Value Reset of kWh counter Reset of hours-run counter Operating mode VLT Type Software version number LCP identification number Database identification number Power section identification number Application option type Communication option type BMC software identification Unit identification for communication Software parts no. Software version BMC software identification Power card identification

[0] [0] [0]

UPDATE VLT COMM OPTION SW APPL OPTION SW Configure Control Card PROTOCOL SELECT BAUD RATE SELECT BUS TIME OUT TIME OUT FUNCT. BIT 10 FUNCTION BUS OFF INT. BEH. Protocol select Baud rate select Bus time out Bus time out function Bit 10 function Bus Off Interrupt Behavior [2] [20]

DANFOSS - FCD 300 Configuration for Outlet Conveyors M7, M8, M9, M10 / Beer
PNU # Display Text 833 FIELDBUS ENABLE Operation and Display
834 835 836 837 838 850 851 852 904 915 916 918 970 971 980 981 982 990 991 992 COS FILTER 1 COS FILTER 2 COS FILTER 3 COS FILTER 4 EDS DATA TYPES TRANSMIT ERROR C RECEIVE ERROR C BUS OFF ERROR C PPO TYPE SELECT PCD CONFIG WRITE PCD CONFIG READ STATION ADDRESS EDIT SETUP SELECT STORE DATA VALUE DEFINED PARAM. 1 DEFINED PARAM. 2 DEFINED PARAM. 3 MODIFI. PARAM. 1 MODIFI. PARAM. 2 MODIFI. PARAM. 3

Parameter Description
Fieldbus enable Filter Mask for status word Filter Mask for main actual value Filter Mask PCD 1 Filter Mask PCD 2 EDS Data Types Readout Transmit Error Counter Readout Receive Error Counter Readout Bus Off Counter PPO Selection PCD write configuration PCD read configuration Station address/MAC ID Parameter setup selection Save data values Defined parameter 1 Defined parameter 2 Defined parameter 3 Modified parameter 1 Modified parameter 2 Modified parameter 3 [5] [0] [13] [1] [1]

M8
ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 008 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

M9
ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 009 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

M10
ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 010 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

DANFOSS - FCD 300 Configuration for Conveyor M1, M2, M3, M4, M5, M6,
PNU # Display Text Operation and Display
001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 018 019 020 024 025 026 100 101 102 103 104 105 106 107 108 109 117 119 120 121 122 123 126 127 128 130 131 132 133 134 135 136 137 138 LANGUAGE OPERATION SITE LOCAL REFERENCE ACTIVE SETUP EDIT SETUP SETUP COPY LCP COPY FREQUENCY SCALE DISPLAY LINE 2 DISPLAY LINE 1.1 DISPLAY LINE 1.2 DISPLAY LINE 1.3 LOC CTRL/CONFIG. LOCAL STOP LOCAL JOGGING LOCAL REVERSING LOCAL RESET DATA CHANGE LOCK POWER UP ACTION HAND OPERATION USER QUICKMENU QUICK MENU SETUP LED STATUS

Parameter Description
Language Local/Remote Operation Local reference Active Setup Programming Setup Setup copying LCP copy Display scaling of output frequency Large display readout Small display line 1.1 Small display line 1.2 Small display line 1.3 Local Control Local Stop Local Jog Local reversing Local reset of trip Lock for data change Operating mode at Power-up, local operation Userdefined Quick Menu Quick Menu setup LED Status

M1
ENGLISH REMOTE 20.000 Hz SETUP 1 ACTIVE SETUP NO COPY NO COPY 1.00 FREQUENCY [Hz] REFERENCE [%] MOTOR CURRENT [A] POWER [kW] LOC+DIG CTRL/AS P100 ENABLE DISABLE DISABLE ENABLE NOT LOCKED LOCAL = STOP DISABLE DISABLE [1] 000 OVERLOAD SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz

CONFIG. MODE Configuration TORQUE CHARACT Torque characteristics MOTOR POWER Motor Power PM,N MOTOR VOLTAGE Motor Voltage UM,N MOTOR FREQUENCY Motor Frequency fM,N MOTOR CURRENT Motor Current IM,N MOTOR NOM. SPEED Rated Motor Speed AUTO MOTOR TUN. Automatic motor tuning, ATM STATOR RESISTAN Stator resistance RS STATOR REACTANCE Stator reactance XS RESONANCE DAMP. Resonance dampening HIGH START TORQ. High start torque START DELAY Start delay START FUNCTION Start function FUNCTION AT STOP Function at stop MIN.F. FUNC.STOP Min. frequency for activating of function at stop DC BRAKING TIME DC braking time DC BRAKE CUT-IN DC brake cut-in frequency MOT.THERM PROTECT Thermal motor protection START FREQUENCY Start frequency INITIAL VOLTAGE Initial voltage DC BRAKE VOLTAGE DC brake voltage START VOLTAGE Start voltage LOAD COMPENSATIO Load compensation U/F RATIO U/f-ratio SLIP COMP. Slip compensation DC HOLD VOLTAGE DC hold voltage BRAKE CUT OUT Brake cut out value

139 140 142 144 146 148 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 221 223 224 225 226 227 228 229 230 231 302 303 304 305 307 308 309 310 314 315 316 317 318 319 323 327 328 341 342 343

BRAKE CUT IN CURRENT MIN VAL LEAK. REACTANCE GAIN AC BRAKE RESET VECTOR MOTOR TYPE OUT FREQ RNG/ROT MIN. OUTPUT FREQ. MAX, OUTPUT FREQ. REFERENCE RANGE MIN. REFERENCE MAX. REFERENCE RAMP TYPE RAMP UP TYPE 1 RAMP DOWN TIME 1 RAMP UP TYPE 2 RAMP DOWN TIME 2 JOG RAMP TIME Q STOP RAMP TIME JOG FREQUENCY REF FUNCTION PRESET REF. 1 PRESET REF. 2 PRESET REF. 3 PRESET REF. 4 CATCH UP/SLW DWN CURRENT LIMIT WARN. CURRENT LO WARN. CURRENT HI WARN. FREQ. LOW WARN. FREQ. HIGH WARN. FEEDB. LOW WARN. FEEDB HIGH FREQ BYPASS B.W. FREQ. BYPASS 1 FREQ. BYPASS 2 DIGITAL INPUT 18 DIGITAL INPUT 19 DIGITAL INPUT 27 DIGITAL INPUT 29 DIGITAL INPUT 33 AI [V] 53 FUNCT. AI 53 SCALE LOW AI 53 SCALE HIGH AI [MA] 60 FUNCT. AI 60 SCALE LOW AI 60 SCALE HIGH LIVE ZERO TIME 0 LIVE ZERO FUNCT. AO 42 FUNCT. RELAY 1-3 FUNCT. PULSE MAX 33 PULSE MAX 29 DO 46 FUNCTION DO 46 MAX. PULS PRECISE STOP

Brake cut in frequency Current, minimum value Leakage reactance XL Gain AC brake Reset voltage vector

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 0.02 sec 0.02 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL

References and limits


Output frequency range Output frequency low limit (FMIN) Output frequency high limit (FMAX) Reference range Minimum reference, RefMIN Maximum reference, RefMAX Ramp type Ramp-up time 1 Ramp-down time 1 Ramp-up time 2 Ramp-down time 2 Jog ramp time Quick stop ramp-down time Jog frequency Reference function Preset reference 1 Preset reference 2 Preset reference 3 Preset reference 4 Catch up/slow down reference Current limit. ILIM Warning: Low current, ILOW Warning: High current, IHIGH Warning: Low frequency, fLOW Warning: High frequency, fHIGH Warning: Low feedback, FBLOW Warning: High feedback, FBHIGH Frequency bypass, bandwidth Frequency bypass 1 Frequency bypass 2 Terminal 18, input Terminal 19, input Terminal 27, input Terminal 29, input Terminal 33, input Terminal 53, analogue input voltage Terminal 53, min. scaling Terminal 53, max. scaling Terminal 60, analogue input current Terminal 60, min. scaling Terminal 604, max. scaling Time out Function after time out Analogue output terminal 42 Relay output 1-3 Pulse Max. 33 Pulse Max. 29 Digital output terminal 46 Terminal 46, max. pulse scaling Precise stop function

Inputs and outputs

344 349 400 405 406 409 411 413 414 415 416 445 456 500 501 502 503 504 505 506 507 508 509 510 512 513 514 535 600 601 602 603 604 605 615 616 617 618 619 620 621 624 625 626 627 628 630 632 634 635 640 641 642 643 645

PULSE COUNT PRE SPEED COMP DELAY BRAKE FUNCTION RESET MODE AUTORESTART TIME TRIP DELAY CUR. SWITCH FREQ. OVERMODULLATION MIN. FEEDBACK MAX. FEEDBACK REF/FEEDB. UNIT FLYING START BRAKE VOL REDUCE BUS ADDRESS BAUDRATE COASTING SELECT Q STOP SELECT DC BRAKE SELECT START SELECT REVERSING SELECT SETUP SELECT PRES.REF. SELECT BUS JOG 1 FREQ. BUS JOG 2 FREQ. TELEGRAM PROFILE BUS TIMEOUT TIME BUS TIMEOUT FUNC BUS FEEDBACK 1 OPERATING HOURS RUNNING HOURS KWH COUNTER POWER UP's OVER TEMP's OVER VOLTS F.LOG: ERROR COD F.LOG: TIME F.LOG: VALUE RESET KWH COUNT RESET RUN. HOUR OPERATION MODE VLT TYPE SOFTWARE VERSION LCP ID NO PARAM DB ID POWER UNIT DB ID APP. OPTION COM. OPTION BMC-SOFTWARE ID UNIT ID SW. PART NO. SOFTWARE VERSION BMC2 ID POWER ID UPDATE VLT COMM OPTION SW

Counter value Speed comp delay Brake function Reset function Automatic restart time Trip delay overcurrent. ILIM Switching frequency Overmodulation function Minimum feedback, FBMIN Maximum feedback, FBMAX Process units Flying start Brake voltage reduce Address Baudrate Coasting Quick-stop DC-brake Start Reversing Selection of Setup Selection of speed Bus jog 1 Bus jog 2 Telegram profile Bus time interval Bus time interval function

100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 492.1 h 229.8 h 15.9 kWh 56 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.187 NOT USED 1.44 2.06 1.50 NO 0.00

Special functions

Serial communication

Technical functions
Operating hours Hours run kWh counter No. of cut-ins No. of overtemps No. of overvoltages Fault log : Error code Fault log : Time Fault log : Value Reset of kWh counter Reset of hours-run counter Operating mode VLT Type Software version number LCP identification number Database identification number Power section identification number Application option type Communication option type BMC software identification Unit identification for communication Software parts no. Software version BMC software identification Power card identification

646 678 800 801 803 804 805 832 833 834 835 836 837 838 850 851 852 904 915 916 918 970 971 980 981 982 990 991 992

APPL OPTION SW CONFIG CTRL CARD PROTOCOL SELECT BAUD RATE SELECT BUS TIME OUT TIME OUT FUNCT. BIT 10 FUNCTION BUS OFF INT. BEH. FIELDBUS ENABLE COS FILTER 1 COS FILTER 2 COS FILTER 3 COS FILTER 4 EDS DATA TYPES TRANSMIT ERROR C RECEIVE ERROR C BUS OFF ERROR C PPO TYPE SELECT PCD CONFIG WRITE PCD CONFIG READ STATION ADDRESS EDIT SETUP SELECT STORE DATA VALUE DEFINED PARAM. 1 DEFINED PARAM. 2 DEFINED PARAM. 3 MODIFI. PARAM. 1 MODIFI. PARAM. 2 MODIFI. PARAM. 3

Configure Control Card Protocol select Baud rate select Bus time out Bus time out function Bit 10 function Bus Off Interrupt Behavior Fieldbus enable Filter Mask for status word Filter Mask for main actual value Filter Mask PCD 1 Filter Mask PCD 2 EDS Data Types Readout Transmit Error Counter Readout Receive Error Counter Readout Bus Off Counter PPO Selection PCD write configuration PCD read configuration Station address/MAC ID Parameter setup selection Save data values Defined parameter 1 Defined parameter 2 Defined parameter 3 Modified parameter 1 Modified parameter 2 Modified parameter 3

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 001 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

or M1, M2, M3, M4, M5, M6, M8, M9, M10 / Beer Filler
M2 M3 M4 M5 M6

ENGLISH ENGLISH ENGLISH ENGLISH ENGLISH REMOTE REMOTE REMOTE REMOTE REMOTE 20.000 Hz 20.000 Hz 20.000 Hz 20.000 Hz 20.000 Hz SETUP 1 SETUP 1 SETUP 1 SETUP 1 SETUP 1 ACTIVE SETUP ACTIVE SETUP ACTIVE SETUP ACTIVE SETUP ACTIVE SETUP NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY 1.00 1.00 1.00 1.00 1.00 FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] REFERENCE [%] REFERENCE [%] REFERENCE [%] REFERENCE [%] REFERENCE [%] MOTOR CURRENT [A] MOTOR CURRENT [A] MOTOR CURRENT [A] MOTOR CURRENT [A] MOTOR CURRENT [A] POWER [kW] POWER [kW] POWER [kW] POWER [kW] POWER [kW] LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 ENABLE ENABLE ENABLE ENABLE ENABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE ENABLE ENABLE ENABLE ENABLE ENABLE NOT LOCKED NOT LOCKED NOT LOCKED NOT LOCKED NOT LOCKED LOCAL = STOP LOCAL = STOP LOCAL = STOP LOCAL = STOP LOCAL = STOP DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE [1] 000 [1] 000 [1] 000 [1] 000 [1] 000 OVERLOAD OVERLOAD OVERLOAD OVERLOAD OVERLOAD

Load and motor


SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 0.50 sec 0.50 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000% 4000.000% OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 1.00 sec 1.00 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000 4000.000 OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 85.000 Hz LINEAR 1.00 sec 1.00 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000 4000.000 OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 1.00 sec 1.00 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000 4000.000 OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 50.000 Hz LINEAR 1.00 sec 0.50 sec 0.02 sec 0.02 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160.0% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000 4000.000 OFF OFF OFF NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz UNIT READY 5000 Hz NORMAL

100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 492.9 h 222.9 h 12.0 kWh 56 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.171 NOT USED 1.44 2.06 1.50 NO 0.00

100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 492.5 h 226.5 h 30.6 h 59 0 0 [1] 13 [1] 988 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.173 NOT USED 1.44 2.06 1.50 NO 0.00

100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 486.3 h 227.5 h 74.1 kWh 55 0 0 [1] 13 [1] 1182 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.038.252 NOT USED 1.44 2.06 1.50 NO 0.00

100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 489.1 h 229.7 h 31.2 kWh 65 0 0 [1] 13 [1] 988 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.164 NOT USED 1.44 2.06 1.50 NO 0.00

100000 OFF OFF MANUAL RESET 5 sec OFF 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 444.6 h 229.8 h 31.2 kWh 64 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.176 NOT USED 1.44 2.06 1.50 NO 0.00

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 002 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 003 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 004 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 005 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 006 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

M8

M9

M10

Note (Setting range)

ENGLISH ENGLISH ENGLISH REMOTE REMOTE REMOTE 20.000 Hz 20.000 Hz 20.000 Hz SETUP 1 SETUP 1 SETUP 1 ACTIVE SETUP ACTIVE SETUP ACTIVE SETUP NO COPY NO COPY NO COPY NO COPY NO COPY NO COPY 1.00 1.00 1.00 FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] REFERENCE [%] REFERENCE [%] REFERENCE [%] MOTOR CURRENT [A] MOTOR CURRENT [A] MOTOR CURRENT [A] POWER [kW] POWER [kW] POWER [kW] LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 LOC+DIG CTRL/AS P100 ENABLE ENABLE ENABLE DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE ENABLE ENABLE ENABLE NOT LOCKED NOT LOCKED NOT LOCKED LOCAL = STOP LOCAL = STOP LOCAL = STOP DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE [1] 000 [1] 000 [1] 000 OVERLOAD OVERLOAD OVERLOAD SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz SPEED OPEN LOOP CONSTANT TORQUE 1.10 kW 400 V 50 Hz 2.80 A 1420 RPM AMT OFF 6.000 OHM 180.00 OHM 0% OFF (0.0 sec) 0.0 sec COAST/DELAY TIME COAST 0.1 Hz 10 sec 0.0 Hz (OFF) ETR TRIP 1 0.0 Hz 0.0 Volt 0 % (OFF) 12.67 V 100% 7.56 100% 0% 3.0 Hz

Remote control

Value : 0.01 - 100.00

Remote-operated control as parameter 100 Active Not active Not active Active Forced stop, use saved ref. Not active Value : [index 1 - 20] Value : 0 - 999 Overload Speed control, open loop Constant torque Value : 0.18 - 4 kW Value : 50 - 999 V Value : 24 - 1000 Hz Value : 0.01 - IMAX Value : 100 - fM,N x 60 (max. 60000 rpm) Optimisation off Value : 0.000 - x.xxx Ohm Value : 0.00 - x.xx Ohm Value : 0 - 100 % Value : 0.0 - 0.5 sec. Value : 0.0 - 10.0 sec. Coasting during start delay time Coasting Value : 0.1 - 10 Hz Value : 0 - 60 sec. Value : 0.0 (OFF) - parameter 202 ETR trip 1 Value : 0.0 - 10.0 Hz Value : 0.0 - 200.0 V Value : 0 - 100 % of max. DC brake voltage Value : 0.0 - 100.00 V Value : 0.0 - 300.0 % Value : 0.00 - 20.00 V/Hz Value : -500 - +500% of rated slip compensation Value : 0 - 100% of max. DC hold voltage Value : 0.5 - 132.0/1000.0 Hz

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000 4000.000 0 Hz (OFF) 0.0 Hz 0.0 Hz NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000 4000.000 0 Hz (OFF) 0.0 Hz 0.0 Hz NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL

3.0 Hz 10% 18.000 OHM 1.30 OFF GENERAL 132 Hz CLOCK WISE 0.0 Hz 132.0 Hz MIN - MAX 0.000 Hz 60.000 Hz LINEAR 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 3.00 sec 10.0 Hz SUM 0.00% 0.00% 0.00% 0.00% 0.00% 160% 0.0 A 2.8 A 0.0 Hz 132.0 Hz -4000.000 4000.000 0 Hz (OFF) 0.0 Hz 0.0 Hz NO OPERATION NO OPERATION NO OPERATION NO OPERATION NO OPERATION REFERENCE 0.0 Volt 10.0 Volt NO OPERATION 0.0 mA 20.0 mA 10 sec OFF 0 - IMAX = 0 - 20 mA NO OPERATION 5000 Hz 5000 Hz NO OPERATION 5000 Hz NORMAL

Value : 0.5 - 132.0/1000.0 Hz Value : 0 % of Inom - 100 % of Inom Value : 0.000 - xxx,xxx Ohm Value : 1.00 - 1.50 Off

Only clockwise, 0-132 Hz Value : 0.0 - fMAX Value : fMIN - 132/1000 Hz (parameter 200) Value : Min. reference - Max. reference Value : -100,000.000 - par. 205 RefMAX Value : par. 204 ReMIN - 100,000.000 Linear Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.02 - 3600.00 sec. Value : 0.0 - par. 202 Value : -100.00 % - +100.00 % Value : -100.00 % - +100.00 % Value : -100.00 % - +100.00 % Value : -100.00 % - +100.00 % Value : 0.00 - 100 % of the given reference Value : 0 - xxx.x % of par. 105 Value : 0.0 - par. 224 Value : par. 223 - IMAX Value : 0.0 - par. 226 Value : par. 225 - 132 Hz Value : -100,000.000 - par. 228 Value : par. 227 - 100,000.000 Value : 0 (OFF) - 100 Hz Value : 0 - 1000 Hz Value : 0 - 1000 Hz No function No function No function No function No function Reference Value : 0.0 - 10.0 Volt Value : 0.0 - 10.0 Volt No function Value : 0.0 - 20.0 mA Value : 0.0 - 20.0 mA Value : 0 - 99 sec. No operation Output current 0 - IMAX 0 - 20 mA No function Value : 150 - 67600 Hz Value : 150 - 67600 Hz Drive ready Value : 150 - 10000 Hz Normal ramp stop

100000 OFF OFF MANUAL RESET 5 sec OFF (61 sec.) 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 489.5 h 223.4 h 46.2 kWh 63 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 315 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.203 NOT USED 1.44 2.06 1.50 NO 0.00

100000 OFF OFF MANUAL RESET 5 sec OFF (61 sec.) 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 489.6 h 218.7 h 54.2 kWh 67 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.168 NOT USED 1.44 2.06 1.50 NO 0.00

100000 OFF OFF MANUAL RESET 5 sec OFF (61 sec.) 4500 Hz ON 0.000 1500.000 NO UNIT DISABLE 0 1 9600 BAUD LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR LOGIC OR DIGITAL INPUT 10.0 Hz 10.0 Hz FC PROFILE 1 sec OFF 0 488.5 h 215.4 h 50.2 kWh 69 0 0 [1] 0 [1] 0 [1] 0 DO NOT RESET DO NOT RESET NORMAL OPERATION FCD 311 380 V - 480 V V 1.44 / 2.00 ID 2.00 2 Kb ID 1.07 ID 1.50 NONE DEVICENET ID 2.06 ID 007.099.167 NOT USED 1.44 2.06 1.50 NO 0.00

Value : 1 - 999999 Value : 0 ms - 100 ms Off Manual reset Value : 0 - 10 sec. Value : 0 - 60 sec. (61 = OFF) Value : 3000 - 14000 Hz Value : -100,000.000 - Par. 415 FBMAX Value : Par. 414 FBMIN - 100,000.000 Off Value : 0 - 50 V Value : 1 - 126 9600 Baud Logic or Logic or Logic or Logic or Digital input Logic or Logic or Value : 0.0 - nparameter 202 Value : 0.0 - nparameter 202 Value : 1 - 99 sec. Off

Range : 0 - 130,000.0 Range : 0 - 130,000.0 Range : 0 - 9999 Range : 0 - 9999 Range : 0 - 9999 Range : 0 - 9999 Value : [Index 1 - 10] Error code 0 - 44 Value : [Index 1 - 10] Value : [Index 1 - 10] No reset No reset Normal Operation

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 008 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 009 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000

0.00 CANBUS DEVICENET 125 KBAUD 10 s STOP BIT 10 = 1 > CTW ACT HOLD CAN ENABLE FFFF hex FFFF hex FFFF hex FFFF hex ERRATA 2 000000000 000000000 000000000 INSTANCE 101 / 151 [1] 000 [1] 528 010 ACTIVE SETUP NO ACTION [1] 001 [1] 415 [1] 904 [1] 003 [1] 000 [1] 000 Value : Sub index 1 (PCD 1) Sub index 2 (PCD 2) Value : Sub index 1 (PCD 1) Sub index 2 (PCD 2) Value : 0 - 63 Active set up Not active Read only Read only Read only Read only Read only Read only [Par. Number] [Par. Number] [Par. Number] [Par. Number] Value : 0000 - FFFF Hex Value : 0000 - FFFF Hex Value : 0000 - FFFF Hex Value : 0000 - FFFF Hex Errata 2 Devicenet 125 kbps Value : 1 - 99 sec. Stop with auto restart This parameter is read only Ho;d the device in bus-off state