Section One
Descriptions of Battery Model
Example :T12V100SE/A
T 12 V 100 SE / A
Identity number differences of batteries expressed by A,B,C....... no default)
Structure expressed by 1-3 bits capital letters, see the explanations below Capacity(rated capacity for Telion series, it is C10 for UPStar series, it is C20) Voltage rated voltage of battery, not default value Series number English capital letters T stands for Telion series U stands for UPStar series
Note The structure is expressed by 1-3 bits of capital letters and the definitions are given below: Fire retardant Front access S F (Security); defined as default if the battery is not fire retardant (Front Access); Front access is defined as default
Gas collection E (Environmental); No gas collection is defined as default Old battery model is kept in the brackets, such as T2V200E/A GFM-200
Section Two
1 Select the batteries with the reference to the tables in the rear part according to the following rules and the battery capacity calculated
through power supply selection (The Telion series batteries for selection include: 6V100Ah, 12V40Ah, 12V50Ah, 12V65Ah, 12V80Ah, 12V100Ah; 2V200Ah, 2V300Ah, 2V400Ah, 2V500Ah, 2V650Ah, 2V800Ah, 2V1000Ah, 2V1600Ah, 2V2000Ah, and 2V3000Ah). (1) Two 48V battery strings connected in parallel are the main configuration, other configurations are subordination selections; (2) Select 2V battery for the capacity above 48V400Ah (2 battery strings in parallel should be given the top priority, 1 string or less than 6 strings in parallel is the auxiliary configuration) ; (3) Select 12V battery for the capacity below 48V300Ah (2 battery strings in parallel is the main configuration, 1 string or 3 strings in parallel is the auxiliary configuration) ; 2V battery can also be selected (1 battery string of 48V200Ah or 48V300Ah) , among them, 2 battery strings in parallel is the preferable scheme. (4) Cautions for configuring battery capacity 1) Configuration of battery strings: For important telecom station, the batteries should be configured in 1+1 redundancy mode. Under other conditions, the designing capacity should be halved or only one battery string is selected. 2) Upper limit of battery capacity: Cmax 50Iload
Step
2 Determine the battery installation mode according to battery capacity and field reconnaissance data of battery room
(1) Field reconnaissance data of battery room include bearing capacity of floor (if the equipment is installed in 2nd floor or above), space of machine room, anti-shock requirements and so on; (2) User can also select the installation mode designed by ENP, which is much more widely applied; (3) Battery installation mode should be defined clearly if special design is required according to actual machine room layout.
Section Two
2. Installation illustrations and parameters of batteries used for communication power system
2.1. Installation illustrations and parameters of 48V100Ah battery
Single layer single row installation illustration of 48V100Ah battery Capacity of battery strings 48V100Ah Quantity (PCS) 4 Battery installation sizes (L 796 W 452 H) 298 Total weight (Kg) 200
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.
2-layer 2-row installation illustration of 48V200Ah Capacity of battery strings 48V200Ah battery model T2V200E/A (GFM-200 ) Quantity (PCS) 24 Battery installation sizes (L 662 874 W 450 400 H) 1122 1006
6-layer flat-laying installation illustration of 48V200Ah Total weight (Kg) 410 422 Remark 2-layer 2-row battery rack 6-layer flat-laying battery rack
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.
Section Two
2-layer 2-row installation illustration of 48V300Ah Capacity of battery strings 48V300Ah Quantity (PCS) ) 24 Battery installation sizes (L 932 874 W 450 400 H) 1122 1276
6-layer flat-laying installation illustration of 48V300Ah Total weight (Kg) 630 643 Remark 2-layer 2-row battery rack 6-layer flat-laying battery rack
Note:
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.
2-layer 2-row installation illustration of 48V400Ah Capacity of battery strings 48V400Ah battery model T2V400E/A (GFM-400 ) Quantity (PCS) 24 Battery installation sizes (L 1058 1284 W 446 370 H) 1116 1010
4-layer flat-laying installation illustration of 48V400Ah Total weight (Kg) 733 748 Remark 2-layer 2-row battery rack 4-layer flat-laying battery rack
Note:
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.
Section Two
2-layer 2-row installation illustration of 48V500Ah Capacity of battery strings 48V500Ah battery model T2V500E/A (GFM-500 ) Quantity (PCS) 24 Battery installation sizes (L 1148 1542 W 518 370 H) 1125 1010
4-layer flat-laying installation illustration of 48V500Ah Total weight (Kg) 1015 1035 Remark 2-layer 2-row battery rack 4-layer flat-laying battery rack
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.
2-layer 2-row installation illustration of 48V650Ah Capacity of battery strings 48V650Ah Quantity (PCS) 24 Battery installation sizes (L 11148 1840 W 640 400 H) 1126 1022
Note:
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.
Section Two
4-layer flat-laying installation illustration of 48V800Ah Capacity of battery strings 48V800Ah Quantity (PCS) 24 Battery installation sizes (L 1580 W 493 H) 1450 Total weight (Kg) 1524
Note:
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.
4-layer flat-laying installation illustration of 48V1000Ah Capacity of battery strings 48V1000Ah Quantity (PCS) ) 24 Battery installation sizes (L 1580 W 493 H) 1450 Total weight (Kg) 1836
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.
Section Two
single layer 2-row installation illustration of 48V1600Ah Capacity of battery strings 48V1600Ah Quantity (PCS) 24 Battery installation sizes (L 4432 W 784 H) 540 Total weight (Kg) 3000
Note:
Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock
single layer 2-row installation illustration of 48V2000Ah Capacity of battery strings 48V2000Ah Quantity (PCS) 24 Battery installation sizes (L 4432 W 968 H) 540 Total weight (Kg) 3700
Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on)
Section Two
Quantity (PCS) 24
Note:
Battery installation mode can be designed according to reconnaissance data (space of machine room, bearing capacity of floor and anti-shock
Section Three
Selection of batteries used for UPS
1 Select the batteries with the reference to the tables in the rear part according to the following rules and the battery capacity calculated through
power supply selection. 1 2 3 4 5 Telion 2V series battery 400Ah 3000Ah should be used when the capacity of battery strings exceeds 400Ah; Generally, the number of battery strings in parallel is 2 or 3; One battery string is the main configuration mode if the required voltage is high 240V or above , others are subordinate configuration; Telion series battery should be preferably selected if the backup time is required to be longer than 8h; UPStar series battery(low price) should be preferably selected if the cost is the main considerations. 6V100Ah 12V40Ah, 12V50Ah, 12V65Ah, 12V80Ah, 12V100Ah 2V200Ah, 12V24Ah, 12V38Ah,
Two battery series can be selected Telion series 12V65Ah, 12V100Ah, and 6V200Ah .
2V300Ah, 2V400Ah, 2V500Ah, 2V650Ah, 2V800Ah, 2V1000Ah, 2V1600Ah, 2V2000Ah, and 2V3000Ah; UPStar series
Step
2 Determine the battery installation mode according to battery capacity and field reconnaissance data of battery room
1 2 3 above , space of machine room, anti-shock requirements and so on; User can also select the installation mode designed by ENP, which is much more widely applied;
Field reconnaissance data of battery room include bearing capacity of floor if the equipment is installed in 2nd floor or
Battery installation mode should be defined clearly if special design is required according to actual machine room layout.
Section Three
Selection of batteries used for UPS
2.1 Installation illustrations and parameters of batteries with 36V rated voltage
Quantity (PCS) 3 3 6 6
Battery installation sizes (L W H, mm) 410 432 864 864 230 290 290 290 battery cabinet: 450 battery cabinet 655 battery cabinet 655
Remark suitable for 1KVA UPS with backup time of 1h suitable for 1KVA UPS with backup time of 2h suitable for 1KVA UPS with backup time of 4h suitable for 1KVA UPS with backup time of 8h
Section Three
Selection of batteries used for UPS
2.2 Installation illustrations and parameters of batteries with 96V rated voltage
single battery string(96V) installation illustration Capacity of battery strings 96V38Ah 96V65Ah 96V100Ah 96V200Ah battery model U12V38/A U12V65/A U12V100/A U12V100/A Quantity (PCS) 8 8 8 16 Number of battery strings 1-string 1-string 1-string
2 battery strings(96V) in parallel installation illustration Battery installation sizes (L W H, mm) 450 450 450 900 630 630 630 630 battery cabinet: 450 battery cabinet 800 battery cabinet 800 Total weight (Kg) 132 207 327.2 654.4
Remark suitable for 2KVA UPS with backup time of 1h suitable for 2KVA UPS with backup time of 2h suitable for 2KVA UPS with backup time of 4h suitable for 2KVA UPS with backup time of 8h
Section Three
Selection of batteries used for UPS
2.3 Installation illustrations and parameters of batteries with 120V rated voltage
single battery string (120V) installation illustration Capacity of battery strings 120V38Ah 120V65Ah 120V100Ah 120V200Ah battery model U12V38/A U12V65/A U12V100/A U12V100/A Quantity (PCS) 10 10 10 20 Number of battery strings 1-string 1-string 1-string
2 battery strings(120V) in parallel installation illustration Battery installation sizes (L W H, mm) 450 450 450 900 530 900 900 900 battery cabinet: 620 battery cabinet 800 battery cabinet 800 Total weight (Kg) 158.2 261 411.3 822.6
Remark suitable for 3KVA UPS with backup time of 1h suitable for 3KVA UPS with backup time of 2h suitable for 3KVA UPS with backup time of 4h suitable for 3KVA UPS with backup time of 8h
Section Three
Selection of batteries used for UPS
2.4 Installation illustrations and parameters of batteries with 240V rated voltage
240V38Ah installation illustration Capacity of battery strings 240V38Ah 240V65Ah 240V100Ah 240V200Ah 240V400Ah battery model U12V38/A U12V65/A U12V100/A U12V100/A U12V100/A Quantity (PCS) 20 20 20 40 80
1 battery string(240V) installation illustration Number of battery strings 1-string 1-string 1-string 2-string of 240V100Ah in parallel 4-string of 240V100Ah in parallel
2 battery strings(240V) in parallel Total weight (Kg) 900 1245 1245 1245 total 1245 total 301.3 502 802 1604 3208
Battery installation sizes (L W H, mm) 450 450 450 450 450 battery cabinet 800 battery cabinet 980 battery cabinet 980 battery cabinet 980 2PCS battery cabinet 980 4PCS
Remark suitable for 6KVA UPS with backup time of 1h suitable for 6KVA UPS with backup time of 2h or 10KVA UPS with backup time of 1h suitable for 6KVA UPS with backup time of 4h or 10KVA UPS with backup time of 2h suitable for 6KVA UPS with backup time of 8h or 10KVA UPS with backup time of 4h suitable for 10KVA UPS with backup time of 8h
Section Three
Selection of batteries used for UPS
2.5 Installation illustrations and parameters of batteries with 480V rated voltage
single battery string(480V) installation illustration Capacity of battery strings 480V24Ah 480V38Ah 480V65Ah 480V100Ah 480V130Ah 480V200Ah 480V300Ah battery model U12V24/A U12V38/A U12V65/A U12V100/A U12V65/A U12V100/A U12V100/A Quantity (PCS) 40 40 40 40 80 80 120 Number of battery strings 1-string 1-string 1-string 1-string 2-string of 480V65Ah in parallel 2-string of 480V100Ah in parallel 3-string of 480V100Ah in parallel 980 980 980 800 800 980 980
2 battery strings(480V) in parallel Battery installation sizes (L W H, mm) 900 total 2PCS 900 total 2PCS 1245 total 2PCS 1245 total 2PCS 1245 total 4PCS 1245 total 4PCS 1245 total 6PCS battery cabinet 450 450 450 450 450 450 450 battery cabinet battery cabinet battery cabinet battery cabinet battery cabinet battery cabinet Total weight (Kg) 430.6 602.6 1004 1604 2008 3208 4812
3 battery strings(480V) in parallel Remark suitable for 10KVA UPS with backup time of 1h or 15KVA UPS with backup time of 30min suitable for 15KVA UPS with backup time of 1h or 20KVA UPS with backup time of 30min suitable for 10KVA UPS with backup time of 2h or 20KVA UPS with backup time of 1h suitable for 10KVA UPS with backup time of 4h or 15KVA/20KVA UPS with backup time of 2h suitable for 15KVA UPS with backup time of 4h suitable for 10KVA/15KVA UPS with backup time of 8h or 20KVA UPS with backup time of 4h suitable for 20KVA UPS with backup time of 8h
Section Three
Selection of batteries used for UPS
2.6 Installation illustrations and parameters of batteries with 360V rated voltage
650Ah cell)
1000Ah cell)
Section Three
Selection of batteries used for UPS
Quantity (PCS) 30
Battery installation sizes (L W H, mm) One 20PCS-battery cabinet (800 900) and one 10PCS-battery cabinet (620 450 530)
Remark suitable for 20KVA UPS with backup time of 10min suitable for 20KVA UPS with backup time of 15min; or 30KVA UPS with backup time of 10min suitable for 30KVA UPS with backup time of 15min suitable for 20KVA/30KVA UPS with backup time
One 20PCS-battery cabinet (800 360V38Ah U12V38/A 30 1-string 2-string of 360V24Ah in parallel 1-string 800 450 900) and one 10PCS-battery cabinet (620 360V48Ah U12V24/A 60 450 450 530) 646 battery cabinet: 900 total 3PCS 460
360V65Ah
U12V65/A
30
815
of 30min; or 40KVA UPS with backup time of 10min/15min; or 60KVA with backup time of 10min suitable for 20KVA UPS with backup time of 1h;
360V100Ah
U12V100/A
30
1325
or 40KVA UPS with backup time of 30min; or 60KVA UPS with backup time of 15min; suitable for 20KVA UPS with backup time of 2h; or 30KVA UPS with backup time of 1h; suitable for 20KVA UPS with backup time of 3h; or 30KVA UPS with backup time of 2h; or 40KVA UPS with backup time of 1h; or 60KVA UPS with backup time of 30min suitable for 20KVA UPS with backup time of 4h/5h;
360V130Ah
U12V65/A
60
1630
360V200Ah
U12V100/A
60
2650
360V300Ah
U12V100/A
90
3975
or 30KVA UPS with backup time of 3h/4h; or 40KVA UPS with backup time of 2h; or 60KVA UPS with backup time of 1h
Section Three
Selection of batteries used for UPS
battery model
Quantity (PCS)
360V400Ah
T2V400E/A
180
1-string
400
1010
5610
or 30KVA UPS with backup time of 5h; or 40KVA UPS with backup time of 3h; or 60KVA UPS with backup time of 2h suitable for 30KVA UPS with backup time of 6h; or 40KVA UPS with backup time of 4h suitable for 30KVA UPS with backup time of 8h; or 40KVA UPS with backup time of 5h/6h; or 60KVA UPS with backup time of 3h/4h suitable for 40KVA UPS with backup time of 8h; or 60KVA UPS with backup time of 5h Used for 60KVA UPS with backup time of 6h Used for 60KVA UPS with backup time of 8h
360V500Ah
T2V500E/A
180
1-string
400
1010
7762
360V650Ah
T2V650/A
180
1-string
400
1022
9157
2.7 Installation illustrations and parameters of batteries with 384V rated voltage
Section Three
Selection of batteries used for UPS
1 battery string(384V) installation illustration (2V400Ah Capacity of battery strings 384V100Ah battery model U12V100/A Quantity (PCS) 32 Number of battery strings 1-string
600Ah cell)
2 battery strings (384V) installation illustration (2V800Ah Battery installation sizes (L 1500 W H, mm) 480 1190 415 975 battery rack: Total weight (Kg) 1232
1000Ah cell)
Remark suitable for 80KVA UPS with backup time of 15min or 120KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 30min; or 160KVA UPS with backup time of 15min; or 200KVA UPS with backup time of 10min; suitable for 160/200KVA UPS with backup time of 15min; or 300KVA UPS with backup time of 10min; suitable for 120KVA UPS with backup time of 30min; or 300KVA UPS with backup time of 15min; or 400KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 1h; or 160/200KVA UPS with backup time of 30min; or 400KVA UPS with backup time of 15min; or 600KVA UPS with backup time of 10min
384V130Ah
U12V65/A
64
1500
384V200Ah
U12V100/A
64
2464
384V300Ah
U12V100/A
96
total 3PCS
3696
384V400Ah
T2V400E/A
192
1-string
5984
Section Three
Selection of batteries used for UPS
or 600KVA UPS with backup time of 15min; or 800KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 2h;
384V800Ah
T2V800/A
192
1-string
493
1450
12192
or 160KVA UPS with backup time of 1h; or 300KVA UPS with backup time of 30min suitable for 80KVA UPS with backup time of 3h/4h; or 120/160KVA UPS with backup time of 2h;
384V1000Ah
T2V1000/A
192
1-string
14688
or 200KVA UPS with backup time of 1h; or 400KVA UPS with backup time of 30min; or 800KVA UPS with backup time of 15min suitable for 300KVA UPS with backup time of 1h; or 600KVA UPS with backup time of 30min suitable for 200KVA UPS with backup time of 2h suitable for 120/160KVA UPS with backup time of 3h/4h; or 400KVA UPS with backup time of 1h; or 800KVA UPS with backup time of 30min suitable for 200KVA UPS with backup time of 3h;
battery rack: 14720 800 1022 986 1450 battery rack: 12640
384V3000Ah
T2V3000/A
192
44480
or 300KVA UPS with backup time of 2h; or 600KVA UPS with backup time of 1h
384V4000Ah
T2V2000/A
384
59200
Appendix A
1. Telion series
SN Product Photo Product Model Specification Outline Dimensions L W H(mm) Weight (Kg) Remark
T6V100/A (3-GFM-100)
6V100Ah
205
177
300
27.0
T12V50/A (6-GFM-50)
12V50Ah
357
178
221
28.0
T12V65SE/A (6-GFM-65N)
12V65Ah
356
178
230
33.0
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
T12V80/A (6-GFM-80)
12V80Ah
400
177
300
46.0
T12V100/A (6-GFM-100)
12V100Ah
400
177
300
54.0
T12V100SE/A (6-GFM-100N)
12V100Ah
360
177
265
43.5
T12V100SE/B (6-GFM-10019N)
12V100Ah
407
173
225
42.0
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
T12V100SEF/A (6-GFM-100PS)
12V100Ah
520
105
253
42.0
10
T2V200E/A (GFM-200
2V200Ah
98
178
385
16.0
11
T2V300E/A (GFM-300
2V300Ah
143
178
385
24.5
12
T2V400E/A (GFM-400
2V400Ah
164
178
385
27.0
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
13
T2V500E/A (GFM-500
2V500Ah
214
180
385
38.0
14
T2V650/A (GFM-650)
2V650Ah
261
180
385
46.0
15
T2V800/A (GFM-800
2V800Ah
254
210
512
61.0
16
T2V1000/A (GFM-1000
2V1000Ah
254
210
521
74.0
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
17
T2V1600/A (GFM-1600)
2V1600Ah
355
332
387
130.0
18
T2V2000/A (GFM-2000)
2V2000Ah
425
357
387
155.0
19
T2V3000/A (GFM-3000)
2V3000Ah
616
358
388
243.0
Main features 1 Long life in telecom level Designing according to special telecom requirements with 15-year designing life. 2 New generation grid alloy: The battery has strong anti-corrosion and anti-distortion capabilities because its grid uses special alloy made of Pb-Ca-Sn-Al low percent of Ca, high percent of Sn , which ensures the long life of the battery. Besides, the level of negative pole is improved, which can suppress the generation of hydrogen to prevent the water in the electrolyte from decomposing. 3 High reliable sealing The terminals are sealed reliably. They are coated with a layer of heat-shrinking tube that can act as a protection coat after being heated. An O shape sealing ring is installed around the tube and the ring is the second sealing protection layer. The upper part of the terminal is sealed with imported resin that can act as a third sealing protection coat. Thus these three protection coat guarantee the battery have no leakage, so the leakage problem is solved completely. 4 Excellent deep-discharging recovery function: Perform short circuit test on the batteries. The battery capacity can maintain at 95% or above after 5 times of cycle discharge test. 5 Anti heat-failure function If the battery is charged with constant voltage at 75 ambient temperature, the charging current will not increase abnormally, which indicates that the battery has a strong temperature adaptability. 6 Patented gas collection device The device collects the gas(mainly hydrogen) generated in charging process(such as high temperature and sealing environment) and the possible acid fog, process them and then expel the waste gases, thus gas accumulation is avoided and the adaptability of the battery to environment is improved. Suitable for: Mobile station outdoor, network access(integrated cabinet) and other precise equipment. 7 UL and CE safety certification: Product using safety is fully guaranteed.
Appendix A
U12V24/A
12V24Ah
165
125
181
8.7
U12V38/A
12V38Ah
196
165
176
13
U12V65/A
12V65Ah
322
167
175
22
U12V100/A
12V100Ah
407
173
220
37
Appendix A
SN
Product Photo
Product Model
Specification
Weight (Kg)
Remark
Launch to 5 UH12V370/A 370W/cell @ 15min 341 172 240 36 market in Dec, 2002
Launch to 6 UH6V740/A 740W/cell @ 15min 341 172 240 36 market in Dec, 2002
Main features 1 Simple maintenance: Sealing technology is used, so there is no necessity of adding water or acid periodically in the whole life of the battery. 2 Safe & Reliable No abundant electrolyte, anti-explosion design 3 Small self-discharging: Self discharging each day is below 0.1% 4 Reliable sealing Multi-sealing technology is used to guarantee no leakage of the battery 5 Small internal resistance: Good discharging performance at big current 6 Long life: 10-year designing float-charging life
Query table of battery model used for telecom power system, installation rack/cabinet and the total weight
Appendix B
48V100Ah 48V100Ah
48V100Ah 48V100Ah
Query table of battery model used for telecom power system, installation rack/cabinet and the total weight
Appendix B
48V200Ah, 48V300Ah, 48V400Ah, 48V500Ah, 48V650Ah, 48V800Ah, 48V1000Ah, 48V1600Ah, 48V2000Ah, 48V3000Ah, 48V200Ah, 48V300Ah, 48V400Ah, 48V500Ah, 48V650Ah, 48V800Ah, 48V1000Ah,
24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS
Appendix C
tte glo aries and abb viatio bbr Batter y glossaries and abbreviations
Close Circuit Voltage Open Circuit Voltage Unit of battery capacity Float Charging Voltage 10h rate rated capacity 3h rate rated capacity 1h rate rated capacity Ah Ah Ah the value is 1.00 C10 the value is 0.75 C10 the value is 0.55 C10 which is the value obtained at 25 basic temperature Ah
by multiplying the discharging current I(A) with the discharging time t(h) 10h rate discharging current, the value is 1.00I10(A) 3h rate discharging current, the value is 2.50I10(A) 1h rate discharging current, the value is 5.50I10(A)