Sunteți pe pagina 1din 30

CONTENT

Section One Section Two Section Three Appendix A Appendix B Appendix C


Descriptions of Battery Model Selection of batteries used for communication power supplies Selection of batteries used for UPS Emerson battery series Query table of battery model used for telecom power system, installation rack/cabinet and the total weight Battery glossaries and abbreviations

Section One
Descriptions of Battery Model

Example :T12V100SE/A
T 12 V 100 SE / A
Identity number differences of batteries expressed by A,B,C....... no default)

Structure expressed by 1-3 bits capital letters, see the explanations below Capacity(rated capacity for Telion series, it is C10 for UPStar series, it is C20) Voltage rated voltage of battery, not default value Series number English capital letters T stands for Telion series U stands for UPStar series

Note The structure is expressed by 1-3 bits of capital letters and the definitions are given below: Fire retardant Front access S F (Security); defined as default if the battery is not fire retardant (Front Access); Front access is defined as default

Gas collection E (Environmental); No gas collection is defined as default Old battery model is kept in the brackets, such as T2V200E/A GFM-200

Section Two

Selection of batteries used for communication power supplies

1. Procedures for selecting battery


Step

1 Select the batteries with the reference to the tables in the rear part according to the following rules and the battery capacity calculated
through power supply selection (The Telion series batteries for selection include: 6V100Ah, 12V40Ah, 12V50Ah, 12V65Ah, 12V80Ah, 12V100Ah; 2V200Ah, 2V300Ah, 2V400Ah, 2V500Ah, 2V650Ah, 2V800Ah, 2V1000Ah, 2V1600Ah, 2V2000Ah, and 2V3000Ah). (1) Two 48V battery strings connected in parallel are the main configuration, other configurations are subordination selections; (2) Select 2V battery for the capacity above 48V400Ah (2 battery strings in parallel should be given the top priority, 1 string or less than 6 strings in parallel is the auxiliary configuration) ; (3) Select 12V battery for the capacity below 48V300Ah (2 battery strings in parallel is the main configuration, 1 string or 3 strings in parallel is the auxiliary configuration) ; 2V battery can also be selected (1 battery string of 48V200Ah or 48V300Ah) , among them, 2 battery strings in parallel is the preferable scheme. (4) Cautions for configuring battery capacity 1) Configuration of battery strings: For important telecom station, the batteries should be configured in 1+1 redundancy mode. Under other conditions, the designing capacity should be halved or only one battery string is selected. 2) Upper limit of battery capacity: Cmax 50Iload

Step

2 Determine the battery installation mode according to battery capacity and field reconnaissance data of battery room
(1) Field reconnaissance data of battery room include bearing capacity of floor (if the equipment is installed in 2nd floor or above), space of machine room, anti-shock requirements and so on; (2) User can also select the installation mode designed by ENP, which is much more widely applied; (3) Battery installation mode should be defined clearly if special design is required according to actual machine room layout.

Section Two

Selection of batteries used for communication power supplies

2. Installation illustrations and parameters of batteries used for communication power system
2.1. Installation illustrations and parameters of 48V100Ah battery

Single layer single row installation illustration of 48V100Ah battery Capacity of battery strings 48V100Ah Quantity (PCS) 4 Battery installation sizes (L 796 W 452 H) 298 Total weight (Kg) 200

battery model T12V100SE/B (6-GFM-10019N)

Remark Single layer single row battery rack

Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.

2.2 Installation illustrations and parameters of 48V200Ah battery

2-layer 2-row installation illustration of 48V200Ah Capacity of battery strings 48V200Ah battery model T2V200E/A (GFM-200 ) Quantity (PCS) 24 Battery installation sizes (L 662 874 W 450 400 H) 1122 1006

6-layer flat-laying installation illustration of 48V200Ah Total weight (Kg) 410 422 Remark 2-layer 2-row battery rack 6-layer flat-laying battery rack

Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.

Section Two

Selection of batteries used for communication power supplies

2.3 Installation illustrations and parameters of 48V300Ah battery

2-layer 2-row installation illustration of 48V300Ah Capacity of battery strings 48V300Ah Quantity (PCS) ) 24 Battery installation sizes (L 932 874 W 450 400 H) 1122 1276

6-layer flat-laying installation illustration of 48V300Ah Total weight (Kg) 630 643 Remark 2-layer 2-row battery rack 6-layer flat-laying battery rack

battery model T2V300E/A (GFM-300

Note:

Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.

requirements and so on)

2.4 Installation illustrations and parameters of 48V400Ah

2-layer 2-row installation illustration of 48V400Ah Capacity of battery strings 48V400Ah battery model T2V400E/A (GFM-400 ) Quantity (PCS) 24 Battery installation sizes (L 1058 1284 W 446 370 H) 1116 1010

4-layer flat-laying installation illustration of 48V400Ah Total weight (Kg) 733 748 Remark 2-layer 2-row battery rack 4-layer flat-laying battery rack

Note:

Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.

requirements and so on)

Section Two

Selection of batteries used for communication power supplies

2.5 Installation illustrations and parameters of 48V500Ah

2-layer 2-row installation illustration of 48V500Ah Capacity of battery strings 48V500Ah battery model T2V500E/A (GFM-500 ) Quantity (PCS) 24 Battery installation sizes (L 1148 1542 W 518 370 H) 1125 1010

4-layer flat-laying installation illustration of 48V500Ah Total weight (Kg) 1015 1035 Remark 2-layer 2-row battery rack 4-layer flat-laying battery rack

Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.

2.6 Installation illustrations and parameters of 48V650Ah

2-layer 2-row installation illustration of 48V650Ah Capacity of battery strings 48V650Ah Quantity (PCS) 24 Battery installation sizes (L 11148 1840 W 640 400 H) 1126 1022

4-layer flat-laying installation illustration of 48V650Ah Total weight Kg 1200 1221

battery model T2V650E/A (GFM-650)

Remark 2-layer 2-row battery rack 4-layer flat-laying battery rack

Note:

Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.

requirements and so on)

Section Two

Selection of batteries used for communication power supplies

2.7 Installation illustrations and parameters of 48V800Ah

4-layer flat-laying installation illustration of 48V800Ah Capacity of battery strings 48V800Ah Quantity (PCS) 24 Battery installation sizes (L 1580 W 493 H) 1450 Total weight (Kg) 1524

battery model T2V800/A (6-GFM-10019N)

Remark 4-layer flat-laying battery rack

Note:

Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock Please refer to Appendix B if battery cabinet is used.

requirements and so on)

2.8 Installation illustrations and parameters of 48V1000Ah

4-layer flat-laying installation illustration of 48V1000Ah Capacity of battery strings 48V1000Ah Quantity (PCS) ) 24 Battery installation sizes (L 1580 W 493 H) 1450 Total weight (Kg) 1836

battery model T2V1000/A (GFM-1000

Remark 4-layer flat-laying battery rack

Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on) Please refer to Appendix B if battery cabinet is used.

Section Two

Selection of batteries used for communication power supplies

2.9 Installation illustrations and parameters of 48V1600Ah

single layer 2-row installation illustration of 48V1600Ah Capacity of battery strings 48V1600Ah Quantity (PCS) 24 Battery installation sizes (L 4432 W 784 H) 540 Total weight (Kg) 3000

battery model T2V1600/A (GFM-1600)

Remark single laying 2-row battery rack

Note:

Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock

requirements and so on)

2.10 Installation illustrations and parameters of 48V2000Ah

single layer 2-row installation illustration of 48V2000Ah Capacity of battery strings 48V2000Ah Quantity (PCS) 24 Battery installation sizes (L 4432 W 968 H) 540 Total weight (Kg) 3700

battery model T2V2000/A (GFM-2000)

Remark single laying 2-row battery rack

Note: Battery installation mode can be designed according to reconnaissance data(space of machine room, bearing capacity of floor and anti-shock requirements and so on)

Section Two

Selection of batteries used for communication power supplies

2.11 Installation illustrations and parameters of 48V3000Ah

single layer 2-row installation illustration of 48V3000Ah

Capacity of battery strings 48V3000Ah

battery model T2V3000/A (GFM-3000)

Quantity (PCS) 24

Battery installation sizes (L 4432 W 1348 H) 540

Total weight (Kg) 5560

Remark single laying 2-row battery rack

Note:

Battery installation mode can be designed according to reconnaissance data (space of machine room, bearing capacity of floor and anti-shock

requirements and so on)

Section Three
Selection of batteries used for UPS

1. Procedures for selecting battery


Step

1 Select the batteries with the reference to the tables in the rear part according to the following rules and the battery capacity calculated through
power supply selection. 1 2 3 4 5 Telion 2V series battery 400Ah 3000Ah should be used when the capacity of battery strings exceeds 400Ah; Generally, the number of battery strings in parallel is 2 or 3; One battery string is the main configuration mode if the required voltage is high 240V or above , others are subordinate configuration; Telion series battery should be preferably selected if the backup time is required to be longer than 8h; UPStar series battery(low price) should be preferably selected if the cost is the main considerations. 6V100Ah 12V40Ah, 12V50Ah, 12V65Ah, 12V80Ah, 12V100Ah 2V200Ah, 12V24Ah, 12V38Ah,

Two battery series can be selected Telion series 12V65Ah, 12V100Ah, and 6V200Ah .

2V300Ah, 2V400Ah, 2V500Ah, 2V650Ah, 2V800Ah, 2V1000Ah, 2V1600Ah, 2V2000Ah, and 2V3000Ah; UPStar series

Step

2 Determine the battery installation mode according to battery capacity and field reconnaissance data of battery room
1 2 3 above , space of machine room, anti-shock requirements and so on; User can also select the installation mode designed by ENP, which is much more widely applied;

Field reconnaissance data of battery room include bearing capacity of floor if the equipment is installed in 2nd floor or

Battery installation mode should be defined clearly if special design is required according to actual machine room layout.

Section Three
Selection of batteries used for UPS

2. Installation illustration and parameters of UPS batteries

2.1 Installation illustrations and parameters of batteries with 36V rated voltage

single battery string(36V) installation illustration

2 battery strings(36V) in parallel installation illustration

Capacity of battery strings 36V38Ah 36V65Ah 36V130Ah 36V200Ah

battery model U12V38/A U12V65/A U12V65/A U12V100/A

Quantity (PCS) 3 3 6 6

Number of battery strings 1-string 1-string 2-string of 36V65Ah in parallel

Battery installation sizes (L W H, mm) 410 432 864 864 230 290 290 290 battery cabinet: 450 battery cabinet 655 battery cabinet 655

Total weight (Kg) 50 82 164 255

Remark suitable for 1KVA UPS with backup time of 1h suitable for 1KVA UPS with backup time of 2h suitable for 1KVA UPS with backup time of 4h suitable for 1KVA UPS with backup time of 8h

2-string of 36V100Ah in parallel battery cabinet 655

Section Three
Selection of batteries used for UPS

2.2 Installation illustrations and parameters of batteries with 96V rated voltage

single battery string(96V) installation illustration Capacity of battery strings 96V38Ah 96V65Ah 96V100Ah 96V200Ah battery model U12V38/A U12V65/A U12V100/A U12V100/A Quantity (PCS) 8 8 8 16 Number of battery strings 1-string 1-string 1-string

2 battery strings(96V) in parallel installation illustration Battery installation sizes (L W H, mm) 450 450 450 900 630 630 630 630 battery cabinet: 450 battery cabinet 800 battery cabinet 800 Total weight (Kg) 132 207 327.2 654.4

Remark suitable for 2KVA UPS with backup time of 1h suitable for 2KVA UPS with backup time of 2h suitable for 2KVA UPS with backup time of 4h suitable for 2KVA UPS with backup time of 8h

2-string of 96V100Ah in parallel battery cabinet 800

Section Three
Selection of batteries used for UPS

2.3 Installation illustrations and parameters of batteries with 120V rated voltage

single battery string (120V) installation illustration Capacity of battery strings 120V38Ah 120V65Ah 120V100Ah 120V200Ah battery model U12V38/A U12V65/A U12V100/A U12V100/A Quantity (PCS) 10 10 10 20 Number of battery strings 1-string 1-string 1-string

2 battery strings(120V) in parallel installation illustration Battery installation sizes (L W H, mm) 450 450 450 900 530 900 900 900 battery cabinet: 620 battery cabinet 800 battery cabinet 800 Total weight (Kg) 158.2 261 411.3 822.6

Remark suitable for 3KVA UPS with backup time of 1h suitable for 3KVA UPS with backup time of 2h suitable for 3KVA UPS with backup time of 4h suitable for 3KVA UPS with backup time of 8h

2-string of 120V100Ah in parallel battery cabinet 800

Section Three
Selection of batteries used for UPS

2.4 Installation illustrations and parameters of batteries with 240V rated voltage

240V38Ah installation illustration Capacity of battery strings 240V38Ah 240V65Ah 240V100Ah 240V200Ah 240V400Ah battery model U12V38/A U12V65/A U12V100/A U12V100/A U12V100/A Quantity (PCS) 20 20 20 40 80

1 battery string(240V) installation illustration Number of battery strings 1-string 1-string 1-string 2-string of 240V100Ah in parallel 4-string of 240V100Ah in parallel

2 battery strings(240V) in parallel Total weight (Kg) 900 1245 1245 1245 total 1245 total 301.3 502 802 1604 3208

4 battery strings(240V) in parallel

Battery installation sizes (L W H, mm) 450 450 450 450 450 battery cabinet 800 battery cabinet 980 battery cabinet 980 battery cabinet 980 2PCS battery cabinet 980 4PCS

Remark suitable for 6KVA UPS with backup time of 1h suitable for 6KVA UPS with backup time of 2h or 10KVA UPS with backup time of 1h suitable for 6KVA UPS with backup time of 4h or 10KVA UPS with backup time of 2h suitable for 6KVA UPS with backup time of 8h or 10KVA UPS with backup time of 4h suitable for 10KVA UPS with backup time of 8h

Section Three
Selection of batteries used for UPS

2.5 Installation illustrations and parameters of batteries with 480V rated voltage

single battery string(480V) installation illustration Capacity of battery strings 480V24Ah 480V38Ah 480V65Ah 480V100Ah 480V130Ah 480V200Ah 480V300Ah battery model U12V24/A U12V38/A U12V65/A U12V100/A U12V65/A U12V100/A U12V100/A Quantity (PCS) 40 40 40 40 80 80 120 Number of battery strings 1-string 1-string 1-string 1-string 2-string of 480V65Ah in parallel 2-string of 480V100Ah in parallel 3-string of 480V100Ah in parallel 980 980 980 800 800 980 980

2 battery strings(480V) in parallel Battery installation sizes (L W H, mm) 900 total 2PCS 900 total 2PCS 1245 total 2PCS 1245 total 2PCS 1245 total 4PCS 1245 total 4PCS 1245 total 6PCS battery cabinet 450 450 450 450 450 450 450 battery cabinet battery cabinet battery cabinet battery cabinet battery cabinet battery cabinet Total weight (Kg) 430.6 602.6 1004 1604 2008 3208 4812

3 battery strings(480V) in parallel Remark suitable for 10KVA UPS with backup time of 1h or 15KVA UPS with backup time of 30min suitable for 15KVA UPS with backup time of 1h or 20KVA UPS with backup time of 30min suitable for 10KVA UPS with backup time of 2h or 20KVA UPS with backup time of 1h suitable for 10KVA UPS with backup time of 4h or 15KVA/20KVA UPS with backup time of 2h suitable for 15KVA UPS with backup time of 4h suitable for 10KVA/15KVA UPS with backup time of 8h or 20KVA UPS with backup time of 4h suitable for 20KVA UPS with backup time of 8h

Section Three
Selection of batteries used for UPS

2.6 Installation illustrations and parameters of batteries with 360V rated voltage

1 battery string(360V) (12V cell)

2 battery strings(360V) in parallel (12V cell)

3 battery strings (360V) in parallel (12V cell)

1 battery string(360V) installation illustration (2V400Ah

650Ah cell)

1 battery string (360V) installation illustration(2V800Ah

1000Ah cell)

Section Three
Selection of batteries used for UPS

Capacity of battery strings 360V24Ah

battery model U12V24/A

Quantity (PCS) 30

Number of battery strings 1-string 450

Battery installation sizes (L W H, mm) One 20PCS-battery cabinet (800 900) and one 10PCS-battery cabinet (620 450 530)

Total weight (Kg) 330.5

Remark suitable for 20KVA UPS with backup time of 10min suitable for 20KVA UPS with backup time of 15min; or 30KVA UPS with backup time of 10min suitable for 30KVA UPS with backup time of 15min suitable for 20KVA/30KVA UPS with backup time

One 20PCS-battery cabinet (800 360V38Ah U12V38/A 30 1-string 2-string of 360V24Ah in parallel 1-string 800 450 900) and one 10PCS-battery cabinet (620 360V48Ah U12V24/A 60 450 450 530) 646 battery cabinet: 900 total 3PCS 460

360V65Ah

U12V65/A

30

battery cabinet: 820 821.5 1400

815

of 30min; or 40KVA UPS with backup time of 10min/15min; or 60KVA with backup time of 10min suitable for 20KVA UPS with backup time of 1h;

360V100Ah

U12V100/A

30

1-string 2-string of 360V65Ah in parallel 2-string of 360V100Ah in parallel 1000

battery cabinet: 1000 800 1800

1325

or 40KVA UPS with backup time of 30min; or 60KVA UPS with backup time of 15min; suitable for 20KVA UPS with backup time of 2h; or 30KVA UPS with backup time of 1h; suitable for 20KVA UPS with backup time of 3h; or 30KVA UPS with backup time of 2h; or 40KVA UPS with backup time of 1h; or 60KVA UPS with backup time of 30min suitable for 20KVA UPS with backup time of 4h/5h;

360V130Ah

U12V65/A

60

battery cabinet: 1640 821.5 1400

1630

360V200Ah

U12V100/A

60

battery cabinet: 800 1800 total 2PCS

2650

360V300Ah

U12V100/A

90

3-string of 360V100Ah in parallel 1000

battery cabinet: 800 1800 total 3PCS

3975

or 30KVA UPS with backup time of 3h/4h; or 40KVA UPS with backup time of 2h; or 60KVA UPS with backup time of 1h

Section Three
Selection of batteries used for UPS

Capacity of battery strings

battery model

Quantity (PCS)

Number of battery strings

Battery installation sizes (L W H, mm)

Total weight (Kg)

Remark suitable for 20KVA UPS with backup time of 6h/8h;

360V400Ah

T2V400E/A

180

1-string

battery rack: 9630

400

1010

5610

or 30KVA UPS with backup time of 5h; or 40KVA UPS with backup time of 3h; or 60KVA UPS with backup time of 2h suitable for 30KVA UPS with backup time of 6h; or 40KVA UPS with backup time of 4h suitable for 30KVA UPS with backup time of 8h; or 40KVA UPS with backup time of 5h/6h; or 60KVA UPS with backup time of 3h/4h suitable for 40KVA UPS with backup time of 8h; or 60KVA UPS with backup time of 5h Used for 60KVA UPS with backup time of 6h Used for 60KVA UPS with backup time of 8h

360V500Ah

T2V500E/A

180

1-string

battery rack: 11560

400

1010

7762

360V650Ah

T2V650/A

180

1-string

battery rack: 13800

400

1022

9157

360V800Ah 360V1000Ah 360V1300Ah

T2V800/A T2V1000/A T2V650/A

180 180 360

1-string 1-string 2-string of 360V650Ah in parallel

battery rack: 11850 battery rack: 11850 battery rack: 13800

493 493 800

1450 1450 1022

11430 13770 13770

2.7 Installation illustrations and parameters of batteries with 384V rated voltage

1 battery string(384V) installation illustration(12V cell)

2 battery strings(384V) in parallel installation illustration(12V cell)

Section Three
Selection of batteries used for UPS

1 battery string(384V) installation illustration (2V400Ah Capacity of battery strings 384V100Ah battery model U12V100/A Quantity (PCS) 32 Number of battery strings 1-string

600Ah cell)

2 battery strings (384V) installation illustration (2V800Ah Battery installation sizes (L 1500 W H, mm) 480 1190 415 975 battery rack: Total weight (Kg) 1232

1000Ah cell)

Remark suitable for 80KVA UPS with backup time of 15min or 120KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 30min; or 160KVA UPS with backup time of 15min; or 200KVA UPS with backup time of 10min; suitable for 160/200KVA UPS with backup time of 15min; or 300KVA UPS with backup time of 10min; suitable for 120KVA UPS with backup time of 30min; or 300KVA UPS with backup time of 15min; or 400KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 1h; or 160/200KVA UPS with backup time of 30min; or 400KVA UPS with backup time of 15min; or 600KVA UPS with backup time of 10min

384V130Ah

U12V65/A

64

2-string of 384V65Ah in parallel 2-string of 384V100Ah in parallel 3-string of 384V100Ah in parallel

battery rack: 1485

total 2PCS battery rack: 1500 480 1190

1500

384V200Ah

U12V100/A

64

total 2PCS battery rack: 1500 480 1190

2464

384V300Ah

U12V100/A

96

total 3PCS

3696

384V400Ah

T2V400E/A

192

1-string

battery rack: 10272 400 1010

5984

Section Three
Selection of batteries used for UPS

Capacity of battery strings 384V600Ah

battery model T2V300E/A

Quantity (PCS) 384

Number of battery strings 2-string of 384V300Ah in parallel

Battery installation sizes (L W H, mm) 800 1276

Total weight (Kg) 10288

Remark suitable for 120KVA UPS with backup time of 1h;

battery rack: 6992

or 600KVA UPS with backup time of 15min; or 800KVA UPS with backup time of 10min suitable for 80KVA UPS with backup time of 2h;

384V800Ah

T2V800/A

192

1-string

battery rack: 12640

493

1450

12192

or 160KVA UPS with backup time of 1h; or 300KVA UPS with backup time of 30min suitable for 80KVA UPS with backup time of 3h/4h; or 120/160KVA UPS with backup time of 2h;

384V1000Ah

T2V1000/A

192

1-string

battery rack: 12640 493 1450

14688

or 200KVA UPS with backup time of 1h; or 400KVA UPS with backup time of 30min; or 800KVA UPS with backup time of 15min suitable for 300KVA UPS with backup time of 1h; or 600KVA UPS with backup time of 30min suitable for 200KVA UPS with backup time of 2h suitable for 120/160KVA UPS with backup time of 3h/4h; or 400KVA UPS with backup time of 1h; or 800KVA UPS with backup time of 30min suitable for 200KVA UPS with backup time of 3h;

384V1300Ah 384V1600Ah 384V2000Ah

T2V650/A T2V800/A T2V1000/A

384 384 384

2-string of 384V650Ah in 2-string of 384V800Ah in parallel 2-string of 384V1000Ah in parallel

battery rack: 14720 800 1022 986 1450 battery rack: 12640

19536 24384 29376

battery rack: 12640 986 1450

384V3000Ah

T2V3000/A

192

1-string 2-string of 384V2000Ah in parallel

battery rack: 8864 8300 540 11244 540

44480

or 300KVA UPS with backup time of 2h; or 600KVA UPS with backup time of 1h

384V4000Ah

T2V2000/A

384

battery rack: 8864

59200

suitable for 800KVA UPS with backup time of 1h

Appendix A

Emerson battery series

1. Telion series
SN Product Photo Product Model Specification Outline Dimensions L W H(mm) Weight (Kg) Remark

T6V100/A (3-GFM-100)

6V100Ah

205

177

300

27.0

Launch to 2 T12V40SEF/A 12V40Ah 274 105 220 15.0 market in Nov,2002

T12V50/A (6-GFM-50)

12V50Ah

357

178

221

28.0

T12V65SE/A (6-GFM-65N)

12V65Ah

356

178

230

33.0

Appendix A

Emerson battery series

SN

Product Photo

Product Model

Specification

Outline Dimensions L W H(mm)

Weight (Kg)

Remark

T12V80/A (6-GFM-80)

12V80Ah

400

177

300

46.0

T12V100/A (6-GFM-100)

12V100Ah

400

177

300

54.0

T12V100SE/A (6-GFM-100N)

12V100Ah

360

177

265

43.5

T12V100SE/B (6-GFM-10019N)

12V100Ah

407

173

225

42.0

Appendix A

Emerson battery series

SN

Product Photo

Product Model

Specification

Outline Dimensions L W H(mm)

Weight (Kg)

Remark

T12V100SEF/A (6-GFM-100PS)

12V100Ah

520

105

253

42.0

10

T2V200E/A (GFM-200

2V200Ah

98

178

385

16.0

11

T2V300E/A (GFM-300

2V300Ah

143

178

385

24.5

12

T2V400E/A (GFM-400

2V400Ah

164

178

385

27.0

Appendix A

Emerson battery series

SN

Product Photo

Product Model

Specification

Outline Dimensions L W H(mm)

Weight (Kg)

Remark

13

T2V500E/A (GFM-500

2V500Ah

214

180

385

38.0

14

T2V650/A (GFM-650)

2V650Ah

261

180

385

46.0

15

T2V800/A (GFM-800

2V800Ah

254

210

512

61.0

16

T2V1000/A (GFM-1000

2V1000Ah

254

210

521

74.0

Appendix A

Emerson battery series

SN

Product Photo

Product Model

Specification

Outline Dimensions L W H(mm)

Weight (Kg)

Remark

17

T2V1600/A (GFM-1600)

2V1600Ah

355

332

387

130.0

18

T2V2000/A (GFM-2000)

2V2000Ah

425

357

387

155.0

19

T2V3000/A (GFM-3000)

2V3000Ah

616

358

388

243.0

Main features 1 Long life in telecom level Designing according to special telecom requirements with 15-year designing life. 2 New generation grid alloy: The battery has strong anti-corrosion and anti-distortion capabilities because its grid uses special alloy made of Pb-Ca-Sn-Al low percent of Ca, high percent of Sn , which ensures the long life of the battery. Besides, the level of negative pole is improved, which can suppress the generation of hydrogen to prevent the water in the electrolyte from decomposing. 3 High reliable sealing The terminals are sealed reliably. They are coated with a layer of heat-shrinking tube that can act as a protection coat after being heated. An O shape sealing ring is installed around the tube and the ring is the second sealing protection layer. The upper part of the terminal is sealed with imported resin that can act as a third sealing protection coat. Thus these three protection coat guarantee the battery have no leakage, so the leakage problem is solved completely. 4 Excellent deep-discharging recovery function: Perform short circuit test on the batteries. The battery capacity can maintain at 95% or above after 5 times of cycle discharge test. 5 Anti heat-failure function If the battery is charged with constant voltage at 75 ambient temperature, the charging current will not increase abnormally, which indicates that the battery has a strong temperature adaptability. 6 Patented gas collection device The device collects the gas(mainly hydrogen) generated in charging process(such as high temperature and sealing environment) and the possible acid fog, process them and then expel the waste gases, thus gas accumulation is avoided and the adaptability of the battery to environment is improved. Suitable for: Mobile station outdoor, network access(integrated cabinet) and other precise equipment. 7 UL and CE safety certification: Product using safety is fully guaranteed.

Appendix A

Emerson battery series

2. UPStar 12V series


SN Product Photo Product Model Specification Outline Dimensions L W H(mm) Weight (Kg) Remark

U12V24/A

12V24Ah

165

125

181

8.7

U12V38/A

12V38Ah

196

165

176

13

U12V65/A

12V65Ah

322

167

175

22

U12V100/A

12V100Ah

407

173

220

37

Appendix A

Emerson battery series

SN

Product Photo

Product Model

Specification

Outline Dimensions L W H(mm)

Weight (Kg)

Remark

Launch to 5 UH12V370/A 370W/cell @ 15min 341 172 240 36 market in Dec, 2002

Launch to 6 UH6V740/A 740W/cell @ 15min 341 172 240 36 market in Dec, 2002

Main features 1 Simple maintenance: Sealing technology is used, so there is no necessity of adding water or acid periodically in the whole life of the battery. 2 Safe & Reliable No abundant electrolyte, anti-explosion design 3 Small self-discharging: Self discharging each day is below 0.1% 4 Reliable sealing Multi-sealing technology is used to guarantee no leakage of the battery 5 Small internal resistance: Good discharging performance at big current 6 Long life: 10-year designing float-charging life

Query table of battery model used for telecom power system, installation rack/cabinet and the total weight

Appendix B

1.1 TELION 12V series


battery rack/cabinet size SN 1 2 3 4 battery capacity and quantity 12V50Ah, 12V65Ah, 72V65Ah, 12V100Ah, 1PCS 1PCS 6PCS 1PCS battery model installation mode Width mm Total Remark Code of single battery Code of single battery 8PCS can be placed in ONUF01B Used for microwave base station Code of single battery 4PCS can be placed in ONU512A, 8PCS can be placed in ONU512C 2PCS can be placed in BTS30A 5 6 7 8 9 10 11 12 12V100Ah, 48V100Ah, 48V200Ah, (2 (3 48V300Ah, 48V100Ah, 48V200Ah, (2 (3 48V300Ah, 1PCS 4PCS 8PCS ) ) 12PCS 4PCS 8PCS ) ) 12PCS T12V100SE/B(6-GFM-10019N) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) T12V100/A(6-GFM-100) cabinet for 2-layer 1 row cabinet for 3-layer 1 row Rack for single layer single row rack for 2-layer 1-row rack for 2-layer flat-laying rack for 2-layer 3-row Cabinet for single layer single row 810 445 930 930 860 860 860 445 418 465 653 450 450 450 340 540 1200 1200 475 875 1275 223 450 670 256 502 658 Under condition that 12V cell is selected Under condition that 12V cell is selected Code of single battery ONUF01A, 4PCS can be placed in F02A Under condition that 12V cell is selected Under condition that 12V cell is selected Depth Height Weight Kg mm mm

T12V50SE/A(6-GFM-50) T12V65SE/A(6-GFM-65N) T12V65SE/A(6-GFM-65N) T12V100SE/A(6-GFM-100N)

48V100Ah 48V100Ah

48V100Ah 48V100Ah

Query table of battery model used for telecom power system, installation rack/cabinet and the total weight

Appendix B

1.2 TELION 2V series


SN 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 battery capacity and quantity battery rack/cabinet size battery model installation mode Width mm T2V200E/A (GFM-200 T2V300E/A (GFM-300 T2V400E/A (GFM-400 T2V500E/A (GFM-500 T2V650/A (GFM-650) T2V800/A (GFM-800 T2V1000/A (GFM-1000 T2V1600/A (GFM-1600) T2V2000/A (GFM-2000) T2V3000/A (GFM-3000) T2V200E/A (GFM-200 T2V300E/A (GFM-300 T2V400E/A (GFM-400 T2V500E/A (GFM-500 T2V650/A (GFM-650) T2V800/A (GFM-800 T2V1000/A (GFM-1000 ) ) ) ) ) ) ) ) ) ) ) ) rack for 6-layer flat-laying rack for 2-layer 2-row rack for 6-layer flat-laying rack for 2-layer 2-row rack for 4-layer flat-laying rack for 2-layer 2-row rack for 4-layer flat-laying rack for 2-layer 2-row rack for 4-layer flat-laying rack for 2-layer 2-row rack for 4-layer flat-laying rack for 4-layer flat-laying rack for single layer 2-row rack for single layer 2-row rack for single layer 2-row cabinet for 6-layer flat-laying cabinet for 8-layer flat-laying cabinet for 8-layer flat-laying cabinet for 8-layer flat-laying cabinet for 8-layer flat-laying cabinet for 4-layer flat-laying cabinet for 4-layer flat-laying 874 752 874 1022 1290 1058 1550 1148 1800 1148 1580 1580 4432 4432 4432 600 600 600 800 1000 1600 1600 Depth mm 400 459 400 459 400 446 400 518 400 640 493 493 784 968 1348 550 550 550 550 550 600 600 Height mm 1006 1200 1276 1200 1006 1116 1014 1125 1018 1126 1450 1450 540 540 540 2000 2000 2000 2000 2000 1500 1500 Total Weight Kg 422 410 643 630 748 733 1035 1015 1221 1200 1524 1836 3000 3700 5560 564 768 852 1092 1284 1764 2076 Remark flat-laying vertical laying flat-laying vertical laying flat-laying vertical laying flat-laying vertical laying flat-laying vertical laying

48V200Ah, 48V300Ah, 48V400Ah, 48V500Ah, 48V650Ah, 48V800Ah, 48V1000Ah, 48V1600Ah, 48V2000Ah, 48V3000Ah, 48V200Ah, 48V300Ah, 48V400Ah, 48V500Ah, 48V650Ah, 48V800Ah, 48V1000Ah,

24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS 24PCS

Appendix C
tte glo aries and abb viatio bbr Batter y glossaries and abbreviations

VRLA battery CCV OCV Ah Vf C10 C3 C1 Ct Ce I10 I3 I1

Valve Regulated Lead-Acid battery

Close Circuit Voltage Open Circuit Voltage Unit of battery capacity Float Charging Voltage 10h rate rated capacity 3h rate rated capacity 1h rate rated capacity Ah Ah Ah the value is 1.00 C10 the value is 0.75 C10 the value is 0.55 C10 which is the value obtained at 25 basic temperature Ah

Actual measured capacity of battery Ah Actual measured capacity of battery Ah

by multiplying the discharging current I(A) with the discharging time t(h) 10h rate discharging current, the value is 1.00I10(A) 3h rate discharging current, the value is 2.50I10(A) 1h rate discharging current, the value is 5.50I10(A)