Reinforced Concrete Masonry Lintel Design example

Design code:
ACI 530 - 05 Building Code Requirements for Masonry Structures

Design data:
Design load: W = 1000 lb/ft Length of lintel opening: L = 8 ft Depth of lintel: D = 24 in Thickness of wall: 8 inch nominal Compressive strength of masonry: f'm = 1500 psi Yield strength of steel reinforcement: fy = 60000 psi

Requirement:

Requirement:
Design reinforcement for masonry lintel

Solution:
1. Design flexural reinforcement Calculate design moment: M = WL2/8 = 8000 lb-ft Actual Thickness of wall: b = 7.625 in. Effective depth: d = 24 in -7.625 in /2 = 20.187 in Elastic modulus of concrete masonry: Em = 900 f'm = (900)(1500 psi)/1000 = 1350 ksi Elastic modulus of steel: Es = 29000 ksi Transformation factor: n = Es / Em = 21.5 Try one #5 bar, reinforcement area, As = 0.3 in2. Reinforcement ratio r = As /bd = (0.3)/(7.625)(20.187) = 0.002 Calculate Factor, k = [2 r n + (r n)2 ] - r n = 0.251 Calculate Factor j = 1 - k/3 = 0.916 Check Tensile stress in steel, fs = M / (As j d )= 17.3 ksi Allowable tensile stress: Fs = 24000 psi O.K.

Check Stress in masonry: fc = 2 M / (bd2jk) = 269 psi Allowable stress in masonry: Fc = f'm /3 = 500 psi O.K.

Check shear stress:


Calculate shear force: V = W L /2 = 4100 lbs Shear stress: fv = V/bd = 26 psi Allowable shear stress, Fv = f'm = 38.7 psi O.K. Disclaimer: The content of this website was obtained and edited from various resources. The editor made reasonable effort of editing. Nevertheless, the editor does not warrant, and assume no liability for accuracy and completeness of its content. The viewer shall use his/her professional knowledge and judgment in use of the web content. Webmaster: www.ce-ref.com