DF001
This drawing and design is the property of AREVA and must not be copied or lent without prior permission in writing
Name Date Name Date Name Date Name Date SDA 25.02.09 Name Date SDA 25.02.09
Name Date Name Date Name Date Name Date Name Date NGS 25.02.09
0
REV.
FIRST ISSUE
DESCRIPTION
Name Date
SIGN.
SIGN.
DRAWN
CHECKED
APPROVED
CLIENT :
CONSULTANT :
PROJECT :
LOA No.:
DOCUMENT No.
TOTAL SH.
SH. No.
REV.
PEI-7602PN063-4-CON-024
001
PEI-7602PN063-4-CON-024
SIGN.
AIR-CONDISIONED KIOSK-DIA-1
5CX2.5 5CX2.5
CONTROL, DI, DO, I/L R Ph CB 400KV 4-2 TIE CB LCC CONTROL, DI, DO, I/L Y Ph CB AUX. SUPPLY
5CX10
4-1EMVT EMVT
2CX2.5 2CX2.5 2CX2.5 2CX2.5 2CX2.5 2CX2.5 4-3BMK CONTROL, DI, DO, I/L B Ph CB 400KV GT PANEL1 Relay & BCU CONTROL, DI, DO, I/L R Ph ISO CONTROL, DI, DO, I/L AUX. SUPPLY STUB PROTECTION RELAY 400KV ISO A MB CONTROL, DI, DO, I/L Y Ph ISO LINE EMVTJB
(FOR METERING IN BCU,SYNCH CHECK) (FOR DISTANCE MAIN 1 PROT.,59) (FOR BUSBAR MAIN1& 2 PROT.) (FOR DISTANCE MAIN 1 PROT.) (FOR DISTANCE MAIN 2 PROT.) 5CX2.5 (FOR STUB PROT.) 19CX2.5 (FOR TRIP COIL 1 , PROTECTION TRIP1, TC SUPERVISION, CONTROL) 19CX2.5 (FOR TRIP COIL 2 , PROTECTION TRIP2, TC SUPERVISION, CONTROL) DI, DO, CONTROL CIRCUIT., AUX. SUPPLY
LINE PANEL MAIN 1 RELAY AND BCU PANEL AND PERIPHERAL UNIT FOR BUSBAR PROTECTION
4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 4CX2.5 BAY BUS 1 CTJB PLCC PANEL
CONTROL, DI, DO, I/L R Ph ISO CONTROL, DI, DO, I/L AUX. SUPPLY AUX. SUPPLY CONTROL, DI, DO, I/L B Ph ISO 19CX2.5 (FOR TRIP COIL 1 , PROTECTION TRIP1, TC SUPERVISION, CONTROL) 19CX2.5 (FOR TRIP COIL 2 , PROTECTION TRIP2, TC SUPERVISION, CONTROL) 400KV ES. AE CONTROL, DI, DO, I/L MB 400KV ISO B MB CONTROL, DI, DO, I/L Y Ph ISO
(FOR 21L1 FROM TIE CT MB) (FOR 21L2 FROM TIE CT MB) (FOR BCU METERING FROM TIE CT MB)
400KV GT PANEL 2
CONTROL, DI, DO, I/L R Ph CB 400KV 4-1 CB LCC CONTROL, DI, DO, I/L Y Ph CB BAY MARSHALLING KIOSK CONTROL, DI, DO, I/L B Ph CB AUX. SUPPLY 4-1BMK
5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 BAY BUS 1 CTJB 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5
DC1(DCDB) R Ph ISO CONTROL, DI, DO, I/L 400KV ISO A MB CONTROL, DI, DO, I/L AUX. SUPPLY 3PH 415V AC SUPPLY FROM ACDB CONTROL, DI, DO, I/L B Ph ISO
DC2(DCDB)
RTCC Panel
R Ph ISO CONTROL, DI, DO, I/L 400KV ISO. B MB CONTROL, DI, DO, I/L
FROM TIE CT MB FOR METERING (FOR OVERHEAD DIFF FROM TIE CT MB) (FOR OVERALL DIFF FROM TIE CT MB)
CONTROL, DI, DO, I/L B Ph ISO CONTROL, DI, DO, I/L 400KV ES. AE MB TIE BAY CR PANEL TIE CTJB-A TO BAY CT MB 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 5CX2.5 R 4-2CTA TIE CT
400KV ES BE MB
5CX2.5 Note: 1. CORE CROSS SECTION SIZES IN Sq. mm 2.Cable supply is not in AREVA's Scope
3. Cable supply and laying not in AREVA's SCOPE
4-2CTB TIE CT
5CX2.5
5CX2.5
TO BAY CTMB
4.All cable sizes taken optimally subject to approval by the client. 5.One BMK is considerd for each breaker section 6. The cable sizes will be finalised after approval of I/O List which will be submitted after receiving the inputs required for auxiliary signal list.
PEI-7602PN063-4-CON-024
Page 2 of 2