Sunteți pe pagina 1din 286

PCS-9611 Feeder Relay Instruction Manual

NR Electric Co., Ltd.

Preface

Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide full information on safe handling, commissioning and testing of this equipment. Documentation for equipment ordered from NR Electric Co., Ltd. is dispatched separately from manufactured goods and may not be received at the same time. Therefore this guide is provided to ensure that printed information normally present on equipment is fully understood by the recipient. Before carrying out any work on the equipment, the user should be familiar with the contents of this manual and read relevant chapters carefully. This chapter describes the safety precautions recommended when using the equipment. Before installing and using the equipment, this chapter must be thoroughly read and understood.

Health and Safety


The information in this chapter of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition. When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the equipment must be isolated. Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate the equipment. Qualified personnel are individuals who: Are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected; Are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorized to energize and de-energize equipment and to isolate, ground, and label it; Are trained in the care and use of safety apparatus in accordance with safety engineering practices; Are trained in emergency procedures (first aid).

PCS-9611 Feeder Relay Date: 2011-08-29

Preface

Instructions and Warnings


The following indicators and standard definitions are used: DANGER means that death, severe personal injury, or considerable equipment damage will occur if safety precautions are disregarded. means that death, severe personal, or considerable equipment damage could occur if safety precautions are disregarded. means that light personal injury or equipment damage may occur if safety precautions are disregarded. This particularly applies to damage to the device and to resulting damage of the protected equipment.

WARNING

CAUTION

WARNING! The firmware may be upgraded to add new features or enhance/modify existing features, please make sure that the version of this manual is compatible with the product in your hand. WARNING! During operation of electrical equipment, certain parts of these devices are under high voltage. Severe personal injury or significant equipment damage could result from improper behavior. Only qualified personnel should work on this equipment or in the vicinity of this equipment. These personnel must be familiar with all warnings and service procedures described in this manual, as well as safety regulations. In particular, the general facility and safety regulations for work with high-voltage equipment must be observed. Noncompliance may result in death, injury, or significant equipment damage. DANGER! Never allow the current transformer (CT) secondary circuit connected to this equipment to be opened while the primary system is live. Opening the CT circuit will produce a dangerously high voltage. WARNING! Exposed terminals Do not touch the exposed terminals of this equipment while the power is on, as the high voltage generated is dangerous. Residual voltage Hazardous voltage can be present in the DC circuit just after switching off the power supply. It takes a few seconds for the voltage to discharge.
II
Date: 2011-08-29 PCS-9611 Feeder Relay

Preface

CAUTION! Earthing The earthing terminal of the equipment must be securely earthed. Operating environment The equipment must only be used within the range of ambient environment detailed in the specification and in an environment free of abnormal vibration. Ratings Before applying AC voltage and current or the power supply to the equipment, check that they conform to the equipment ratings. Printed circuit board Do not attach and remove printed circuit boards when the power supply to the equipment is on, as this may cause the equipment to malfunction. External circuit When connecting the output contacts of the equipment to an external circuit, carefully check the supply voltage used in order to prevent the connected circuit from overheating. Connection cable Carefully handle the connection cable without applying excessive force.

Typographic and Graphical Conventions


The following symbols are used in drawings: Input signal of a function block, such as a logic setting, a blocking signal or a analog comparator signal etc. Input inversion signal of a function block, such as a logic setting, a blocking signal or a analog comparator signal etc.

AND gate: all the input signals are 1, then the output is 1

OR gate: anyone the input signals is 1, then the output is 1

RS flipflop (static memory): setting input (S), resetting input (R), output (Q) and inverted output (Q)

PCS-9611 Feeder Relay Date: 2011-08-29

III

Preface

Timer: pickup with delay t, dropout without delay

Timer: pickup without delay, dropout with delay t

Timer: pickup with delay t1, dropout with delay t2

Junction (connection point)

Copyright
Version: 1.01 NR ELECTRIC CO., LTD. 69 Suyuan Avenue. Jiangning, Nanjing 211102, China P/N: EN_DYBH5301.0086.0002 Tel: +86-25-87178185, Fax: +86-25-87178208

Website: www.nrelect.com, www.nari-relays.com Copyright NR 2011. All rights reserved Email: nr_techsupport@nari-relays.com

We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination to third parties is strictly forbidden except where expressly authorized. The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated. We reserve the rights to make technical improvements without notice.

IV
Date: 2011-08-29

PCS-9611 Feeder Relay

Preface

Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set of instructions for the relays use and application. The chapter contents are summarized as below:

1 Introduction
Briefly introduce the application, functions and features about this relay.

2 Technical Data
Introduce the technical data about this relay, such as electrical specifications, mechanical specifications, ambient temperature and humidity range, communication port parameters, type tests, setting ranges and accuracy limits and the certifications that our products have passed.

3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.

4 Supervision
Introduce the automatic self-supervision function of this relay.

5 Management Function
Introduce the management functions (such as metering, control and recording etc.) of this relay.

6 Hardware
Introduce the main function carried out by each module of this relay and providing the definition of pins of each module.

7 Settings
List of all the settings and their ranges and step sizes, together with a brief explanation of each setting and some notes about the setting application.

8 Human Machine Interface


Introduce the hardware of the human machine interface (HMI) module and a detailed guide for the user how to use this relay through the HMI. It also lists all the information which can be view through the HMI, such as settings, measurements, all kinds of reports etc.

9 Configurable Function
Introduce the configurable function (such as protection function configuration, LED configuration, binary input configuration and binary output configuration etc.) of this relay.

10 Communication
Introduce the communication port and protocol which this relay can support, the IEC60870-5-103, IEC61850 and DNP3.0 protocols are introduced in details.
PCS-9611 Feeder Relay Date: 2011-08-29

Preface

11 Installation
Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A guide to the mechanical and electrical installation of this relay is also provided, incorporating earthing recommendations. A typical wiring connection to this relay is indicated.

12 Commissioning
Introduce how to commission this relay, comprising checks on the calibration and functionality of this relay.

13 Maintenance
A general maintenance policy for this relay is outlined.

14 Decommissioning and Disposal


A general decommissioning and disposal policy for this relay is outlined.

15 Manual Version History


List the instruction manual version and the modification history records.

VI
Date: 2011-08-29

PCS-9611 Feeder Relay

1 Introduction

1 Introduction
Table of Contents
1.1 Application ........................................................................................................1-1 1.2 Functions ..........................................................................................................1-1 1.3 Features ............................................................................................................1-3

List of Figures
Figure 1.1-1 Functional diagram of PCS-9611 ........................................................................ 1-1

PCS-9611 Feeder Relay Date: 2011-08-29

1-a

1 Introduction

1-b
Date: 2011-08-29

PCS-9611 Feeder Relay

1 Introduction

1.1 Application
The PCS-9611 relay is a protection, control and monitoring unit for various primary equipments (such as overhead line, underground cable and transformer etc.) on solidly grounded, impedance grounded, Peterson coil grounded and ungrounded system. This relay is suitable for wall surface mounted indoors or outdoors or flush mounted into a control panel. This relay can sample the analog values from the traditional instrument transformers, or receive the sampled values from the electronic current and voltage transformers (via a merging unit). The binary inputs and outputs of this relay can be configured according to the demands of a practical engineering through the PCS-PC configuration tool auxiliary software, which can meet some special requirements of protection and control functions. This relay can fully support the IEC61850 communication protocol and GOOSE function, and can completely meet the demands of a modern digitalized substation. The function diagram of this relay is shown in Figure 1.1-1.

Figure 1.1-1 Functional diagram of PCS-9611

1.2 Functions
The functions of this relay include protective functions, management functions and auxiliary testing functions, and the functions of this relay are listed in the following tables. Protective functions
1-1
Date: 2011-08-29

PCS-9611 Feeder Relay

1 Introduction Protective Functions 50P 51P 67P 50G 51G 67G 51SG 67SG 27 59 47 59G 49 46 46BC 81U 81O 81R 50BF 79 25 SOTF MR AI Instantaneous overcurrent protection Time overcurrent protection Directional overcurrent protection Instantaneous zero sequence overcurrent protection Time zero sequence overcurrent protection Directional zero sequence overcurrent protection Sensitive earth fault protection Directional sensitive earth fault protection Undervoltage protection Overvoltage protection Negative sequence overvoltage protection Zero sequence overvoltage protection Thermal overload protection Negative sequence overcurrent protection Broken conductor protection Under-frequency protection Over-frequency protection Frequency rate-of-change protection Breaker failure Protection Three-pole auto-recloser (Up to 4 shots) Synchronism check function Switch onto fault logic Mechanical protection Analog inputs Voltage and current drift auto adjustment Self supervision VTS CTS Voltage transformer supervision Current transformer supervision Binary inputs Binary outputs

Management functions
Management Functions Metering Circuit breaker status monitoring 2 TCS Circuit breaker control Tripping circuit supervision Multiple setting groups Control inputs 64 Protection operation reports 1024 Supervision alarm records 1024 Control operation records

1-2
Date: 2011-08-29

PCS-9611 Feeder Relay

1 Introduction 1024 User operation records FDR SOE 64 Fault and disturbance records 1024 latest SOE records, latest records of the following elements state changing: operating abnormality alarm elements, supervision alarm elements, protection elements and binary input elements. Rear communication ports: Ethernet, RS-485, Printer port Time synchronization port: RS-485

Auxiliary testing functions


Auxiliary Testing Functions Virtual tripping report generation and communication testing Virtual self-supervision report generation and communication testing Virtual binary input state change report generation and communication testing Virtual metering values generation and communication testing

1.3 Features
This device is based on a 32-bit high performance dual-core processor, internal high speed bus and intelligent I/O ports, and the hardware is in module design and can be configured flexibly, featuring interchangeability and easy extension and maintenance. Modularized hardware design makes this relay be easily upgraded or repaired by a qualified service person. Various function optional modules can satisfy various situations according to the different requirements of the users. The adoption of 16-bit A/D converter and the dual-channel sampling technology can ensure the accuracy and reliability of protection sampling and the correctness of protection operation. It is also provides dedicated current transformers for metering, and ensures the high accuracy of telemetering with 48-point high speed sampling rate per cycle. This device can sample the analog values from the traditional instrument transformers, or receive the sampled values from the electronic transformers. It can support the protocol IEC60044-8, IEC61850-9-2 and GOOSE. Various algorithms for protection and measurement have been completed in this device for the feature of electronic transformer sampling, such as the error prevention method of multi-algorithms data anomaly for the digital channels, to realize high accuracy and reliability under various conditions of network faults or communication interruption. This device has powerful GOOSE functions, and the connection and cooperation between some devices can be realized without using electrical cables, to facilitate the realization of such functions as simple bus differential protection, overload interlock shedding function and backup automatic transfer function etc. This device has fully realized the technology to integrate six functions into one device: protection, measurement, control, remote signaling, merging unit function and remote module

PCS-9611 Feeder Relay Date: 2011-08-29

1-3

1 Introduction

functions, to improve the reliability. Various methods of GPS time synchronization are supported in this relay, including SNTP, IEEE1588 (V2), pulse per second (PPS) and IRIG-B synchronization. The protection modules are completely separated from other modules, and are independent in both hardware and software. The protection functions do not depend on the communication network, so the failure of communication network will not affect the normal operation of the protection functions. Mature protection configuration, fast speed and high security performance can meet the practical requirements. Each protective element is independent, so it is very convenient for whether adopting the selected protective element. This device constantly measures and calculates a large amount of analog quantities, such as phase voltage, phase-to-phase voltage, neutral voltage, phase current, neutral current, active power, reactive power, power factor and frequency etc. The human machine interface (HMI) with a small control module (a 240128-dot LCD, a 9-key keypad and 20 LED indicators) on the front panel is very friendly and convenient to the user. This device can communicate with a SAS or RTU via different communication intermediates: Ethernet network, RS-485 serial ports. The communication protocol of this device is optional: IEC61850, IEC60870-5-103 or DNP3.0. This device can detect the tripping circuit of the circuit breaker and monitor the operation (close or trip) time of a circuit breaker by checking the auxiliary contacts of the circuit breaker. Complete event recording function is provided: 64 latest protection operation reports, 1024 latest supervision records, 1024 latest control operation records, 1024 latest user operation records and 1024 latest records of time tagged sequence of event (SOE) can be recorded. Powerful fault and disturbance recording function is supported: 64 latest fault or disturbance waves, the duration of a wave recording is configurable.

1-4
Date: 2011-08-29

PCS-9611 Feeder Relay

2 Technical Data

2 Technical Data
Table of Contents
2.1 General Specification.......................................................................................2-1
2.1.1 Electrical Specifications ..................................................................................................... 2-1 2.1.2 Mechanical Specifications.................................................................................................. 2-2 2.1.3 Ambient Temperature and Humidity ................................................................................... 2-2 2.1.4 Communication Interfaces ................................................................................................. 2-3 2.1.5 Type Test ........................................................................................................................... 2-4

2.2 Protective Functions ........................................................................................2-6


2.2.1 Overcurrent Protection....................................................................................................... 2-6 2.2.2 Voltage Control Element .................................................................................................... 2-6 2.2.3 Phase Directional Element................................................................................................. 2-6 2.2.4 IDMT Overcurrent Protection ............................................................................................. 2-6 2.2.5 Zero Sequence Overcurrent Protection ............................................................................. 2-6 2.2.6 Zero Sequence Directional Element .................................................................................. 2-7 2.2.7 Zero Sequence IDMT Overcurrent Protection.................................................................... 2-7 2.2.8 Sensitive Earth Fault Protection......................................................................................... 2-7 2.2.9 Sensitive Earth Fault Directional Element.......................................................................... 2-7 2.2.10 Sensitive Earth Fault IDMT Protection ............................................................................. 2-8 2.2.11 Negative Sequence Overcurrent Protection..................................................................... 2-8 2.2.12 Thermal Overload Protection ........................................................................................... 2-8 2.2.13 Undervoltage Protection .................................................................................................. 2-8 2.2.14 Overvoltage Protection .................................................................................................... 2-9 2.2.15 Zero Sequence Overvoltage Protection ........................................................................... 2-9 2.2.16 Negative Sequence Overvoltage Protection .................................................................... 2-9 2.2.17 Frequency Protection....................................................................................................... 2-9 2.2.18 Frequency Rate-of-change Protection ........................................................................... 2-10 2.2.19 SOTF Overcurrent Protection ........................................................................................ 2-10
PCS-9611 Feeder Relay Date: 2011-08-29

2-a

2 Technical Data

2.2.20 Zero Sequence SOTF Overcurrent Protection ...............................................................2-10 2.2.21 Breaker Failure Protection..............................................................................................2-10 2.2.22 Broken Conductor Protection ......................................................................................... 2-11

2.3 Management Functions................................................................................. 2-11


2.3.1 Metering Scope and Accuracy.......................................................................................... 2-11 2.3.2 Control Performance ........................................................................................................ 2-11 2.3.3 Clock Performance ...........................................................................................................2-12 2.3.4 Fault and Disturbance Recording .....................................................................................2-12 2.3.5 Binary Input Signal ...........................................................................................................2-12 2.3.6 Transient Overreach .........................................................................................................2-12

2.4 Certification.................................................................................................... 2-12

2-b
Date: 2011-08-29

PCS-9611 Feeder Relay

2 Technical Data

2.1 General Specification


2.1.1 Electrical Specifications
2.1.1.1 Power Supply
Standard Rated voltage Variation Permissible ripple voltage Burden Traditional AC inputs Digital AC inputs IEC60255-11: 2008 110/125Vdc, 220/250Vdc, 220Vac 80% ~ 120% Max 15% of the rated voltage (DC power supply) < 10W @ Quiescent condition; < 15W @ Operating condition < 15W @ Quiescent condition; < 20W @ Operating condition

2.1.1.2 Analog Current Input Ratings


Phase rotation Rated frequency (fn) Nominal range Application object Rated current (In) Linear to Thermal withstand capability Burden (@ In) continuously for 10s for 1s for half a cycle 30In 3In 30In 100In 250In < 0.10VA/phase 1A 30In 3In 30In 100In 250In < 0.20VA/phase ABC 50Hz, 60Hz fn 5Hz For protection 5A 2In 2In 12In 30In 75In < 0.20VA/phase 1A 2In 2In 12In 30In 75In < 0.40VA/phase For metering 5A

2.1.1.3 Analog Voltage Input Ratings


Phase rotation Rated frequency (fn) Nominal range Rated voltage (Un) Linear to Thermal withstand capability Burden continuously 10s 1s ABC 50Hz, 60Hz fn 5Hz 100V ~ 130V (phase-to-phase voltage) 130V 130V 200V 250V < 0.10VA / phase

2.1.1.4 Binary Input


Binary input number Rated voltage Rated current Pickup voltage Dropout voltage Up to 38 24V 1.20mA 48V 2.40mA 110V 1.10mA 125V 1.25mA 220V 2.20mA 250V 2.50mA

55% ~ 70% rated voltage 55% rated voltage

PCS-9611 Feeder Relay Date: 2011-08-29

2-1

2 Technical Data Maximum permitted voltage High voltage withstand Resolving time for logic input 120% rated voltage 2000Vac, 2800Vdc < 1ms

2.1.1.5 Binary Output


Item Binary output number Output model Max system voltage Voltage across open contact Continuous carry Short duration current Breaking capacity Pickup time Dropout time Bounce time Durability loaded contact unloaded contact Up to 25 Potential-free contact 380Vac, 250Vdc 1000V RMS for 1min 5.0A @ 380Vac; 5.0A @ 250Vdc 6A for 3000ms; 15A for 500ms 0.6A @ 48Vdc, L/R=40ms 0.1A @ 110Vdc, L/R=40ms 0.05A @ 220Vdc, L/R=40ms < 8ms < 5ms 1ms 100,000 operations minimum 10,000,000 operations minimum Tripping output Up to 10 Potential-free contact 380Vac, 250Vdc 1200V RMS for 1min 8.0A @ 380Vac; 8.0A @ 250Vdc 10A for 3000ms; 20A for 500ms 0.6A @ 48Vdc, L/R=40ms 0.3A @ 110Vdc, L/R=40ms 0.2A @ 220Vdc, L/R=40ms < 10ms < 8ms 1ms 100,000 operations minimum 10,000,000 operations minimum Signal output

2.1.2 Mechanical Specifications


Enclosure dimensions Trepanning dimensions Mounting way Weight per device Local control panel Display language Housing material Housing color Location of terminals Protection class 225.00177.00224.80 (WHD, unit: mm) 226.00178.00, M5 screw (WH, unit: mm) Flush mounted Approx. 7.0kg (fully equipped) Small control module: a 240128-dot LCD, a 9-key keypad and 20 LEDs Optional: Chinese, English Aluminum Silver grey Rear panel of the device Front side: IP40, up to IP51 IEC60225-1: 2009 Rear side, connection terminals: IP20 Other Sides: IP30

2.1.3 Ambient Temperature and Humidity


Standard Operating temperature range Transport and storage temperature range Permissible humidity Altitude IEC60225-1: 2009 -40C ~ +70C -40C ~ +70C 5% ~ 95%, condensation not permissible < 3000m

2-2
Date: 2011-08-29

PCS-9611 Feeder Relay

2 Technical Data

2.1.4 Communication Interfaces


2.1.4.1 Ethernet Port for RTU/SCADA
Medium Port number Connector type Transmission rate Electrical Transmission standard Transmission distance Protocol Safety level Ethernet Port number Connector type Transmission rate Optical Transmission standard Optical fiber type Wavelength Transmission distance Protocol Parameters 2 or 4 RJ-45 100Mbits/s 100Base-TX < 100m IEC60870-5-103:1997 or IEC61850 Isolation to ELV level 2 SC 100Mbits/s 100Base-FX Multi-mode 1300nm < 1500m IEC60870-5-103:1997 or IEC61850

2.1.4.2 Serial Port for RTU/SCADA


Medium Port number Baud rate RS-485 (EIA) Transmission distance Maximal capacity Protocol Safety level Parameters 0 or 2 4800 ~ 115200bps < 1000m @ 4800bps 32 IEC60870-5-103:1997 or DNP3.0 Isolation to ELV level

2.1.4.3 Serial Port for Printer


Medium Port number RS-232 (EIA) Baud rate Printer type Safety level 1 4800 ~ 115200bps EPSON LQ-300K Isolation to ELV level Parameters

2.1.4.4 Serial Port for Time Synchronization


Medium Port number Transmission distance RS-485 (EIA) Maximal capacity Timing standard Safety level 1 < 500m 32 PPS, IRIG-B Isolation to ELV level Parameters

PCS-9611 Feeder Relay Date: 2011-08-29

2-3

2 Technical Data

2.1.4.5 Ethernet Port for Debugging


Medium Port number Connector type Electrical Ethernet (in front panel) Transmission rate Transmission standard Transmission distance Safety level 1 RJ-45 100Mbits/s 100Base-TX < 100m Isolation to ELV level Parameters

2.1.4.6 Process Level Interface


Medium Optical fiber material Optical fiber type Connector type Optical Ethernet Wavelength Transmission distance Minimum transmission power Reception sensitivity Parameters Glass fiber Multi-mode LC 1310nm < 2000m -20dBm -30dBm ST 820nm

2.1.5 Type Test


2.1.5.1 Environmental Tests
Dry cold test Dry heat test Damp heat test Cyclic temperature with humidity test IEC60068-2-1: 2007, 16h at -25C IEC60068-2-2: 2007, 16h at +55C IEC60068-2-78: 2001, 10 days, 93%RH, +55C IEC60068-2-30: 2005, six (12+12hours) cycles, 95%RH, low temperature +25C, high temperature +55C

2.1.5.2 Electrical Tests


Dielectric test Impulse voltage test Overvoltage category Insulation measurement Pollution degree IEC60255-27: 2005, test voltage: 2kV, 50Hz, 1min IEC60255-5: 2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50s, source energy 0.5J IEC60255-5: 2000, Class III IEC60255-5: 2000, insulation resistance >100M @ 500Vdc IEC60225-1: 2009, Class II

2.1.5.3 Electromagnetic Compatibility


1MHz burst disturbance tests - Common mode - Differential mode Electrostatic discharge tests - For contact discharge - For air discharge IEC60255-22-1: 2007, Class III 2.5kV 1.0kV IEC60255-22-2: 2008, Class IV 8.0kV 15.0kV

2-4
Date: 2011-08-29

PCS-9611 Feeder Relay

2 Technical Data Radio frequency interference tests - Frequency sweep - Radiated amplitude-modulated - Spot frequency - Radiated amplitude-modulated - Radiated pulse-modulated Fast transient disturbance tests - Power supply, I/O & Earth terminals - Communication terminals Surge immunity tests - Power supply, AC inputs, I/O terminals 10Vm(RMS), f=80/160/450/900MHz 10Vm(RMS), f=900MHz IEC60255-22-4: 2008, Class IV 4kV, 2.5kHz, 5/50ns 2kV, 5.0kHz, 5/50ns IEC60255-22-5: 2008, Class IV 1.2/50us, 4kV, line-to-ground 2kV, line-to-line Conducted RF electromagnetic disturbance - Power supply, AC, I/O, Comm. terminals Power frequency field immunity IEC60255-22-6: 2001, Class III 10V(RMS), 150kHz~80MHz IEC60255-22-7: 2003, Class A 10s 300V, line-to-ground 150V, line-to-line Conducted emission limits Radiated emission limits Auxiliary power supply performance - Voltage dips - Voltage short interruptions Power frequency magnetic field immunity IEC60255-25: 2000, Class A IEC60255-25: 2000, Class A IEC60255-11: 2008 Up to 500ms for dips to 40% of rated voltage without reset 100ms for interruption without rebooting IEC61000-4-8: 2001, Class V 100A/m for 1min 1000A/m for 3s Pulse magnetic field immunity Damped oscillatory magnetic field immunity Ring wave immunity - Power supply, I/O terminals IEC61000-4-9: 2001, Class V 6.4/16us, 1000A/m for 3s IEC61000-4-10: 2001, Class V 100kHz & 1MHz 100A/m IEC61000-4-12: 2006, Class III 1MHz 2kV, line-to-ground 1kV, line-to-line 10V/m(RMS), f=801000MHz IEC60255-22-3: 2007, Class III

2.1.5.4 Mechanical Tests


Vibration test Shock test Bump test Seismic test IEC60255-21-1:1988, Class I IEC60255-21-2:1988, Class I IEC60255-21-2:1988, Class I IEC60255-21-3:1988, Class I

PCS-9611 Feeder Relay Date: 2011-08-29

2-5

2 Technical Data

2.2 Protective Functions


2.2.1 Overcurrent Protection
Current setting Pickup current Dropout current Tolerance of current setting Time setting Pickup time Dropout time Tolerance of time setting 0.05In ~ 30.0In 1.00Setting 0.95Setting 2.5% Setting or 0.01In, whichever is greater 0.00s ~ 100.00s 35ms 35ms 1% Setting + 35ms

2.2.2 Voltage Control Element


Negative overvoltage element setting Undervoltage element setting Tolerance of voltage setting Operating time 2.00V ~ 70.00V 2.00V ~ 120.00V 2.5% Setting or 0.10V, whichever is greater 35ms

2.2.3 Phase Directional Element


Directionality Characteristic angle Boundary and angle accuracy Block logic Operating time Optional: Forward, Reverse Configurable: -180~179, step is 1 3 Permission or block selectable by setting 35ms

2.2.4 IDMT Overcurrent Protection


Current threshold setting Pickup current Dropout current Tolerance of current threshold setting Time multiplier setting Pickup time Dropout time Tolerance of trip time for 1.2 < I/Ip < 30 0.05In ~ 4.0In 1.00Setting 0.95Setting 2.5% Setting or 0.01In, whichever is greater 0.05 ~ 100.00 35ms 35ms 5% of reference (calculated) value + 2.5% current tolerance or 35ms, whichever is greater

2.2.5 Zero Sequence Overcurrent Protection


Current setting Pickup current Dropout current Tolerance of current setting 0.05In ~ 30.0In 1.00Setting 0.95Setting 2.5% Setting or 0.01In, whichever is greater

2-6
Date: 2011-08-29

PCS-9611 Feeder Relay

2 Technical Data Time setting Pickup time Dropout time Tolerance of time setting 0.00s ~ 100.00s 35ms 35ms 1% Setting + 35ms

2.2.6 Zero Sequence Directional Element


Directionality Characteristic angle Boundary and angle accuracy Block logic Operating time Optional: Forward, Reverse Configurable: -180~179, step is 1 3 Permission or block selectable by setting 35ms

2.2.7 Zero Sequence IDMT Overcurrent Protection


Current threshold setting Pickup current Dropout current Tolerance of current threshold setting Time multiplier setting Pickup time Dropout time Tolerance of trip time for 1.2 < I/Ip < 30 0.05In ~ 4.0In 1.00Setting 0.95Setting 2.5% Setting or 0.01In, whichever is greater 0.05 ~ 100.00 35ms 35ms 5% of reference (calculated) value + 2.5% current tolerance or 35ms, whichever is greater

2.2.8 Sensitive Earth Fault Protection


Current setting Pickup current Dropout current Tolerance of current setting Time setting Pickup time Dropout time Tolerance of time setting 0.005A ~ 0.400A, dedicated CT 1.00Setting 0.95Setting 1.5% Setting or 1mA, whichever is greater 0.00s ~ 100.00s 35ms 35ms 1% Setting + 35ms

2.2.9 Sensitive Earth Fault Directional Element


Directionality Characteristic angle Boundary and angle accuracy Block logic Operating time Optional: Forward, Reverse Configurable: -180~179, step is 1 3 Permission or block selectable by setting 35ms

PCS-9611 Feeder Relay Date: 2011-08-29

2-7

2 Technical Data

2.2.10 Sensitive Earth Fault IDMT Protection


Current threshold setting Pickup current Dropout current Tolerance of current threshold setting Time multiplier setting Pickup time Dropout time Tolerance of trip time for 1.2 < I/Ip < 30 0.005A ~ 0.400A, dedicated CT 1.00Setting 0.95Setting 1.5% Setting or 1mA, whichever is greater 0.05 ~ 100.00 35ms 35ms 5% of reference (calculated) value + 1.5% current tolerance or 35ms, whichever is greater

2.2.11 Negative Sequence Overcurrent Protection


Current setting Pickup current Dropout current Tolerance of current setting Time setting Pickup time Dropout time Tolerance of time setting 0.05In ~ 4.0In 1.00Setting 0.95Setting 2.5% Setting or 0.01In, whichever is greater 0.00s ~ 100.00s 50ms 50ms 1% Setting + 50ms

2.2.12 Thermal Overload Protection


Reference current setting Pickup current Dropout current Tolerance of reference current setting Time constant setting Pickup time Dropout time Tolerance of trip time for 1.2 < I/(kIb) < 20 0.05In ~ 3.0In 1.00Setting 0.98Setting 2.5% Setting or 0.01In, whichever is greater 0.01s ~ 6000.00s 35ms 35ms 5% of reference (calculated) value + 2.5% current tolerance or 35ms, whichever is greater

2.2.13 Undervoltage Protection


Voltage setting Pickup voltage Dropout voltage Tolerance of voltage setting Time setting Pickup time Dropout time Tolerance of time setting 2.00V ~ 120.00V 1.00Setting Configurable: 1.03Setting ~ 3.00Setting 2.5% Setting or 0.10V, whichever is greater 0.00s ~ 100.00s 80ms 80ms 1% Setting + 80ms

2-8
Date: 2011-08-29

PCS-9611 Feeder Relay

2 Technical Data

2.2.14 Overvoltage Protection


Voltage setting Pickup voltage Dropout voltage Tolerance of voltage setting Time setting Pickup time Dropout time Tolerance of time setting 57.70V ~ 200.00V 1.00Setting Configurable: 0.93Setting ~ 0.97Setting 2.5% Setting or 0.10V, whichever is greater 0.00s ~ 100.00s 50ms 50ms 1% Setting + 50ms

2.2.15 Zero Sequence Overvoltage Protection


Voltage setting Pickup voltage Dropout voltage Tolerance of voltage setting Time setting Pickup time Dropout time Tolerance of time setting 2.00V ~ 160.00V 1.00Setting 0.95Setting 2.5% or 0.10V, whichever is greater 0.00s ~ 100.00s 50ms 50ms 1% Setting + 50ms

2.2.16 Negative Sequence Overvoltage Protection


Voltage setting Pickup voltage Dropout voltage Tolerance of voltage setting Time setting Pickup time Dropout time Tolerance of time setting 2.00V ~ 120.00V 1.00Setting 0.95Setting 2.5% or 0.10V, whichever is greater 0.00s ~ 100.00s 50ms 50ms 1% Setting + 50ms

2.2.17 Frequency Protection


Under-frequency setting Over-frequency setting Pickup frequency Dropout frequency Tolerance of frequency setting Time setting Pickup time Dropout time Tolerance of time setting Blocking element Undervoltage blocking setting 10.00V ~ 120.00V 45.00Hz ~ 60.00Hz 50.00Hz ~ 65.00Hz 1.00Setting 1.00Setting 0.01Hz 0.00s ~ 100.00s 50ms 50ms 1% Setting + 50ms

PCS-9611 Feeder Relay Date: 2011-08-29

2-9

2 Technical Data Operating time Tolerance of undervoltage blocking setting 35ms 2.5% Setting or 0.10V, whichever is greater

2.2.18 Frequency Rate-of-change Protection


Frequency Rate-of-change setting Pickup frequency rate-of-change Dropout frequency rate-of-change Tolerance of frequency rate-of-change setting Time setting Pickup time Dropout time Tolerance of time setting -10.00Hz/s ~ 10.00Hz/s 1.00Setting 1.00Setting 0.20Hz/s 0.00s ~ 100.00s 50ms 50ms 1% Setting + 50ms

2.2.19 SOTF Overcurrent Protection


Current setting Pickup current Dropout current Tolerance of current setting Time setting Pickup time Dropout time Tolerance of time setting 0.05In ~ 30.0In 1.00Setting 0.97Setting 2.5% Setting or 0.01In, whichever is greater 0.00s ~ 100.00s 35ms 35ms 1% Setting + 35ms

2.2.20 Zero Sequence SOTF Overcurrent Protection


Current setting Pickup current Dropout current Tolerance of current setting Time setting Pickup time Dropout time Tolerance of time setting 0.05In ~ 30.0In 1.00Setting 0.97Setting 2.5% Setting or 0.01In, whichever is greater 0.00s ~ 100.00s 35ms 35ms 1% Setting + 35ms

2.2.21 Breaker Failure Protection


Current setting Pickup current Dropout current Tolerance of current setting Time setting Pickup time Dropout time Tolerance of time setting 0.05In ~ 5.0In 1.00Setting 0.90Setting 2.5% Setting or 0.01In, whichever is greater 0.00s ~ 100.00s 35ms 35ms 1% Setting + 35ms

2-10
Date: 2011-08-29

PCS-9611 Feeder Relay

2 Technical Data

2.2.22 Broken Conductor Protection


I2/I1 Ratio setting Pickup ratio Dropout ratio Tolerance of current setting Time setting Pickup time Dropout time Tolerance of time setting 0.10 ~ 1.00 1.00Setting 0.95Setting 2.5% Setting 0.00s ~ 200.00s 70ms 70ms 1% Setting + 70ms

2.3 Management Functions


2.3.1 Metering Scope and Accuracy
Metering Item Phase range Frequency Current Voltage Active power (W) Reactive Power (Vars) Apparent Power (VA) Energy (Wh) Energy (Varh) Current Voltage Active power (W) Reactive Power (Vars) Apparent Power (VA) Energy (Wh) Energy (Varh) 0 ~ 360 35.00Hz ~ 70.00Hz 0.05 ~ 1.40In 0.05 ~ 1.40Un 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.05 ~ 1.40In 0.05 ~ 1.40Un 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.20 ~ 1.40Un, 0.05 ~ 1.40In 0.20 ~ 1.40Un, 0.05 ~ 1.40In Range 0.5% or 1 0.01Hz 0.2% of reading 0.5% of reading 0.5% of reading at unity power factor 0.5% of reading at zero power factor 0.5% of reading 0.5% of reading at unity power factor 0.5% of reading at zero power factor 2.0% of reading 0.5% of reading 3.0% of reading at unity power factor 3.0% of reading at zero power factor 3.0% of reading 3.0% of reading at unity power factor 3.0% of reading at zero power factor Accuracy

Currents from dedicated metering current transformers

Currents from protection measurement current transformers

2.3.2 Control Performance


Control mode Accuracy of local control Accuracy of remote control Local or remote 1s 3s

PCS-9611 Feeder Relay Date: 2011-08-29

2-11

2 Technical Data

2.3.3 Clock Performance


Real time clock accuracy Accuracy of GPS synchronization External time synchronization 3s/day 1ms IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol

2.3.4 Fault and Disturbance Recording


Magnitude and relative phases Maximum duration Recording position 2.5% of applied quantities 10000 sampled points (24 sampled points per cycle) 5 cycles before pickup of trigger element

2.3.5 Binary Input Signal


Resolution of binary input signal Binary input mode Resolution of SOE 1ms Potential-free contact 2ms

2.3.6 Transient Overreach


Transient overreach (DC offset) 5% for X/R 100

2.4 Certification
ISO9001: 2000 ISO14001: 2004 OHSAS18001: 1999 ISO10012: 2003 CMMI L4 EMC: 89/336/EEC, EN50263: 2000 Products safety(PS): 73/23/EEC, EN61010-1: 2001, EN60950: 2002

2-12
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

3 Operation Theory
Table of Contents
3.1 Overview ...........................................................................................................3-1 3.2 Fault Detectors .................................................................................................3-1 3.3 Overcurrent Protection ....................................................................................3-4
3.3.1 Definite Time Overcurrent Protection................................................................................. 3-4 3.3.2 Inverse Definite Minimum Time Overcurrent Protection..................................................... 3-6 3.3.3 Voltage Control Element for Overcurrent Protection .......................................................... 3-8 3.3.4 Directional Element for Overcurrent Protection.................................................................. 3-9 3.3.5 Harmonic Blocking Element for Overcurrent Protection....................................................3-11 3.3.6 Overcurrent Protection Settings....................................................................................... 3-12

3.4 Thermal Overload Protection ........................................................................3-14


3.4.1 Thermal Overload Protection Theory ............................................................................... 3-14 3.4.2 Thermal Overload Protection Settings ............................................................................. 3-16

3.5 Zero Sequence Overcurrent Protection........................................................3-16


3.5.1 Definite Time Zero Sequence Overcurrent Protection ..................................................... 3-16 3.5.2 IDMT Zero Sequence Overcurrent Protection.................................................................. 3-18 3.5.3 Directional Element for Zero Sequence Overcurrent Protection ...................................... 3-19 3.5.4 Harmonic Blocking Element for ROC Protection.............................................................. 3-20 3.5.5 Zero Sequence Overcurrent Protection Settings ............................................................. 3-21

3.6 Sensitive Earth Fault Protection ...................................................................3-24


3.6.1 Definite Time Sensitive Earth Fault Protection................................................................. 3-24 3.6.2 IDMT Sensitive Earth Fault Protection ............................................................................. 3-25 3.6.3 Directional Element for Sensitive Earth Fault Protection ................................................. 3-26 3.6.4 Sensitive Earth Fault Protection Settings......................................................................... 3-27

3.7 Negative Sequence Overcurrent Protection ................................................3-28


3.7.1 Definite Time Negative Sequence Overcurrent Protection............................................... 3-28 3.7.2 IDMT Negative Sequence Overcurrent Protection ........................................................... 3-29
PCS-9611 Feeder Relay Date: 2011-08-29

3-a

3 Operation Theory

3.7.3 Negative Sequence Overcurrent Protection Settings .......................................................3-30

3.8 Broken Conductor Protection....................................................................... 3-31


3.8.1 Broken Conductor Protection Theory ...............................................................................3-31 3.8.2 Broken Conductor Protection Settings..............................................................................3-31

3.9 Breaker Failure Protection ............................................................................ 3-32


3.9.1 Breaker Failure Protection Theory....................................................................................3-32 3.9.2 Breaker Failure Protection Settings ..................................................................................3-34

3.10 Switch Onto Fault (SOTF) Protection......................................................... 3-34


3.10.1 SOTF Protection Theory.................................................................................................3-34 3.10.2 SOTF Protection Settings...............................................................................................3-36

3.11 Cold Load Pickup Logic .............................................................................. 3-36


3.11.1 Cold Load Pickup Logic Theory ......................................................................................3-36 3.11.2 Cold Load Pickup Logic Settings ....................................................................................3-37

3.12 Undervoltage Protection ............................................................................. 3-39


3.12.1 Undervoltage Protection Theory .....................................................................................3-39 3.12.2 Undervoltage Protection Settings ...................................................................................3-40

3.13 Overvoltage Protection ............................................................................... 3-41


3.13.1 Overvoltage Protection Theory .......................................................................................3-41 3.13.2 Overvoltage Protection Settings .....................................................................................3-42

3.14 Zero Sequence Overvoltage Protection ..................................................... 3-43


3.14.1 Zero Sequence Overvoltage Protection Theory..............................................................3-43 3.14.2 Zero Sequence Overvoltage Protection Settings............................................................3-44

3.15 Negative Sequence Overvoltage Protection.............................................. 3-44


3.15.1 Negative Sequence Overvoltage Protection Theory.......................................................3-44 3.15.2 Negative Sequence Overvoltage Protection Settings .....................................................3-45

3.16 Frequency Protection .................................................................................. 3-45


3.16.1 Under-frequency Protection............................................................................................3-46 3.16.2 Over-frequency Protection..............................................................................................3-46 3.16.3 Frequency Rate-of-change Protection............................................................................3-47 3.16.4 Frequency Protection Settings .......................................................................................3-48
3-b
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

3.17 Auto-recloser ................................................................................................3-51


3.17.1 Auto-recloser Theory...................................................................................................... 3-51 3.17.2 Auto-recloser Ready Conditions .................................................................................... 3-53 3.17.3 Auto-recloser Startup Condition ..................................................................................... 3-54 3.17.4 Auto-recloser Check Mode............................................................................................. 3-55 3.17.5 Auto-recloser Blocking Logic.......................................................................................... 3-57 3.17.6 Auto-recloser Settings.................................................................................................... 3-57

3.18 Manual Closing Function.............................................................................3-59


3.18.1 Manual Closing Theory .................................................................................................. 3-59 3.18.2 Check Mode for Manual Closing Function ..................................................................... 3-60 3.18.3 Manual Closing Function Settings ................................................................................. 3-62

3.19 Mechanical Protection .................................................................................3-63


3.19.1 Mechanical Protection Theory ....................................................................................... 3-63 3.19.2 Mechanical Protection Settings...................................................................................... 3-63

List of Figures
Figure 3.3-1 Demonstration characteristic of the overcurrent protection ........................... 3-5 Figure 3.3-2 Logic diagram of the stage 1 overcurrent protection ....................................... 3-5 Figure 3.3-3 Logic diagram of the stage 4 overcurrent protection ....................................... 3-7 Figure 3.3-4 Logic diagram of the OC1 phase A voltage control element ........................... 3-9 Figure 3.3-5 Operation characteristic of the OC directional element ................................. 3-10 Figure 3.3-6 Logic diagram of the OC1 phase A directional element ................................. 3-10 Figure 3.3-7 Logic diagram of the OC1 phase A harmonic blocking element ....................3-11 Figure 3.4-1 Characteristic curve of the thermal overload model ...................................... 3-15 Figure 3.4-2 Logic diagram of the thermal overload protection ......................................... 3-15 Figure 3.5-1 Logic diagram of the No.1 zero sequence overcurrent protection................ 3-17 Figure 3.5-2 Logic diagram of the No.1 zero sequence IDMT overcurrent protection ...... 3-18 Figure 3.5-3 Operation characteristic of the ROC directional element .............................. 3-19 Figure 3.5-4 Logic diagram of the directional element for the No.1 ROC1 protection...... 3-20 Figure 3.5-5 Logic diagram of the No.1 ROC1 harmonic blocking element....................... 3-20

PCS-9611 Feeder Relay Date: 2011-08-29

3-c

3 Operation Theory

Figure 3.6-1 Logic diagram for the stage 1 sensitive earth fault protection ......................3-25 Figure 3.6-2 Logic diagram of the IDMT sensitive earth fault protection ...........................3-25 Figure 3.6-3 Operation characteristic of the SEF directional element ................................3-26 Figure 3.6-4 Logic diagram of the directional element for the stage 1 SEF protection.....3-27 Figure 3.7-1 Logical diagram of the stage 1 NOC protection...............................................3-29 Figure 3.7-2 Logic diagram of the IDMT negative sequence overcurrent protection ........3-30 Figure 3.8-1 Logic diagram of the broken conductor protection ........................................3-31 Figure 3.9-1 Logic diagram of the breaker failure protection ..............................................3-33 Figure 3.9-2 Timing for a typical breaker failure scenario ...................................................3-33 Figure 3.10-1 Logic diagram of the SOTF protection ...........................................................3-35 Figure 3.11-1 Logic diagram of the cold load pickup function ............................................3-37 Figure 3.12-1 Logic diagram of the system lost voltage for the UV1 protection................3-39 Figure 3.12-2 Logic diagram of the stage 1 undervoltage protection .................................3-40 Figure 3.13-1 Logic diagram of the stage 1 overvoltage protection ...................................3-42 Figure 3.14-1 Logic diagram of the stage 1 ROV protection................................................3-43 Figure 3.15-1 Logic diagram of the NOV protection .............................................................3-45 Figure 3.16-1 Logic diagram of the stage 1 under-frequency protection ...........................3-46 Figure 3.16-2 Logic diagram of the stage 1 over-frequency protection..............................3-47 Figure 3.16-3 Logic diagram of the stage 1 frequency rate-of-change protection.............3-47 Figure 3.17-1 Timing diagram for a successful second reclosing ......................................3-52 Figure 3.17-2 Timing diagram for an unsuccessful one-shot reclosing .............................3-52 Figure 3.17-3 Logic diagram of the auto-recloser ................................................................3-53 Figure 3.17-4 Logic diagram of the auto-recloser ready conditions ...................................3-54 Figure 3.17-5 Logic diagram of the synchronism check element for AR ...........................3-55 Figure 3.17-6 Logic diagram of the dead check element for AR .........................................3-56 Figure 3.18-1 Logic diagram of the manual closing function ..............................................3-59 Figure 3.18-2 Logic diagram of the synchronism check element for manual closing.......3-60 Figure 3.18-3 Logic diagram of the dead check element for manual closing ....................3-61 Figure 3.19-1 Logic diagram of the No.1 mechanical protection ........................................3-63

3-d
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

3.1 Overview
The PCS-9611 relay is a microprocessor based relay which can provide mature protection for various primary equipments (such as overhead line, underground cable and transformer etc.). The following sections detail the individual protection functions of this relay. NOTE! In each functional element, the signal input [XXXX.En1] is used for inputting the enabling signals; and the signal input [XXXX.Blk] is used for inputting the blocking signals. The XXXX is the name code of the functional element (such as 50/51P1, 49, 50/51G2 etc.). They can be configured through PCS-PC configuration tool auxiliary software. If the signal input [XXXX.En1] is not used, its default value is 1; and if the signal input [XXXX.Blk] is not used, its default value is 0.

3.2 Fault Detectors


The fault detector will operate if any of the following conditions is satisfied. 1. The startup conditions of the auto-recloser are satisfied if the auto-recloser is enabled and ready for operating. Any one of the phase currents is in excess of the setting of the stage 1 overcurrent protection multiplied by 0.95 if the stage 1 overcurrent protection is enabled. Any one of the phase currents is in excess of the setting of the stage 2 overcurrent protection multiplied by 0.95 if the stage 2 overcurrent protection is enabled. Any one of the phase currents is in excess of the setting of the stage 3 overcurrent protection multiplied by 0.95 if the stage 3 overcurrent protection is enabled. Any one of the phase currents is in excess of the setting of the stage 4 overcurrent protection multiplied by 0.95 if the stage 4 overcurrent protection is enabled. The No.1 zero sequence current is in excess of the setting of the stage 1 of the No.1 zero sequence overcurrent protection multiplied by 0.95 if the stage 1 of the No.1 zero sequence overcurrent protection is enabled. The No.1 zero sequence current is in excess of the setting of the stage 2 of the No.1 zero sequence overcurrent protection multiplied by 0.95 if the stage 2 of the No.1 zero sequence overcurrent protection is enabled. The No.1 zero sequence current is in excess of the setting of the stage 3 of the No.1 zero sequence overcurrent protection multiplied by 0.95 if the stage 1 of the No.3 zero sequence overcurrent protection is enabled. The No.1 zero sequence current is in excess of the setting of the stage 4 of the No.1 zero sequence overcurrent protection multiplied by 0.95 if the stage 1 of the No.4 zero sequence overcurrent protection is enabled.
3-1
Date: 2011-08-29

2.

3.

4.

5.

6.

7.

8.

9.

PCS-9611 Feeder Relay

3 Operation Theory

10. The No.2 zero sequence current is in excess of the setting of the stage 1 of the No.2 zero sequence overcurrent protection multiplied by 0.95 if the stage 1 of the No.2 zero sequence overcurrent protection is enabled. 11. The No.2 zero sequence current is in excess of the setting of the stage 2 of the No.2 zero sequence overcurrent protection multiplied by 0.95 if the stage 2 of the No.2 zero sequence overcurrent protection is enabled. 12. The No.2 zero sequence current is in excess of the setting of the stage 3 of the No.2 zero sequence overcurrent protection multiplied by 0.95 if the stage 3 of the No.2 zero sequence overcurrent protection is enabled. 13. The No.2 zero sequence current is in excess of the setting of the stage 4 of the No.2 zero sequence overcurrent protection multiplied by 0.95 if the stage 4 of the No.2 zero sequence overcurrent protection is enabled. 14. The negative sequence current is in excess of the setting of the stage 1 negative sequence overcurrent protection multiplied by 0.95 if the stage 1 negative sequence overcurrent protection is enabled. 15. The negative sequence current is in excess of the setting of the stage 2 negative sequence overcurrent protection multiplied by 0.95 if the stage 2 negative sequence overcurrent protection is enabled. 16. The sensitive earth fault current is in excess of the current setting of the stage 1 sensitive earth fault protection multiplied by 0.95 if the stage 1 sensitive earth fault protection is enabled. 17. The sensitive earth fault current is in excess of the current setting of the stage 2 sensitive earth fault protection multiplied by 0.95 if the stage 2 sensitive earth fault protection is enabled. 18. The sensitive earth fault current is in excess of the current setting of the stage 3 sensitive earth fault protection multiplied by 0.95 if the stage 3 sensitive earth fault protection is enabled. 19. The sensitive earth fault current is in excess of the current setting of the stage 4 sensitive earth fault protection multiplied by 0.95 if the stage 4 sensitive earth fault protection is enabled. 20. Any one of the phase currents is in excess of the setting of the SOTF overcurrent protection multiplied by 0.97 if the SOTF overcurrent protection is enabled. 21. The No.1 zero sequence current is in excess of the setting of the zero sequence SOTF overcurrent protection multiplied by 0.97 if the zero sequence SOTF overcurrent protection is enabled. 22. Any one of the phase currents is in excess of [49.K_Trp][49.Ib_Set] if the thermal overload protection is enabled. 23. The ratio of negative to positive phase sequence current (I2/I1) is in excess of the ratio setting
3-2
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

of the broken conductor protection multiplied by 0.95 if the broken conductor protection is enabled. 24. Any one of the initiation signals of the breaker failure protection is detected if the breaker failure protection is enabled. 25. The voltages are less than the setting of the stage 1 undervoltage protection multiplied by the dropout coefficient setting of the stage 1 undervoltage protection if the stage 1 undervoltage protection is enabled. 26. The voltages are less than the setting of the stage 2 undervoltage protection multiplied by the dropout coefficient setting of the stage 2 undervoltage protection if the stage 1 undervoltage protection is enabled. 27. The voltages are greater than the setting of the stage 1 overvoltage protection multiplied by the dropout coefficient setting of the stage 1 overvoltage protection if the stage 1 overvoltage protection is enabled. 28. The voltages are greater than the setting of the stage 2 overvoltage protection multiplied by the dropout coefficient setting of the stage 2 overvoltage protection if the stage 2 overvoltage protection is enabled. 29. The zero sequence voltage is greater than the setting of the stage 1 zero sequence overvoltage protection multiplied by 0.95 if the stage 1 zero sequence overvoltage protection is enabled. 30. The zero sequence voltage is greater than the setting of the stage 2 zero sequence overvoltage protection multiplied by 0.95 if the stage 2 zero sequence overvoltage protection is enabled. 31. The negative sequence voltage is greater than the setting of the negative sequence overvoltage protection multiplied by 0.95 if the negative sequence overvoltage protection is enabled. 32. The frequency is less than the setting of the stage 1 under-frequency protection and all the phase-to-phase voltages are greater than the voltage setting of the voltage blocking element of the frequency protection if the stage 1 under-frequency protection is enabled and ready for operating. 33. The frequency is less than the setting of the stage 2 under-frequency protection and all the phase-to-phase voltages are greater than the voltage setting of the voltage blocking element of the frequency protection if the stage 2 under-frequency protection is enabled and ready for operating. 34. The frequency is less than the setting of the stage 3 under-frequency protection and all the phase-to-phase voltages are greater than the voltage setting of the voltage blocking element of the frequency protection if the stage 3 under-frequency protection is enabled and ready for operating. 35. The frequency is less than the setting of the stage 4 under-frequency protection and all the

PCS-9611 Feeder Relay Date: 2011-08-29

3-3

3 Operation Theory

phase-to-phase voltages are greater than the voltage setting of the voltage blocking element of the frequency protection if the stage 4 under-frequency protection is enabled and ready for operating. 36. The frequency is greater than the setting of the stage 1 over-frequency protection and all the phase-to-phase voltages are greater than the voltage setting of the voltage blocking element of the frequency protection if the stage 1 over-frequency protection is enabled and ready for operating. 37. The frequency is greater than the setting of the stage 2 over-frequency protection and all the phase-to-phase voltages are greater than the voltage setting of the voltage blocking element of the frequency protection if the stage 2 over-frequency protection is enabled and ready for operating. 38. The rate-of-change of frequency is greater than the setting of the stage 1 frequency rate-of-change protection if the stage 1 frequency rate-of-change protection is enabled. 39. The rate-of-change of frequency is greater than the setting of the stage 2 frequency rate-of-change protection if the stage 2 frequency rate-of-change protection is enabled. 40. The rate-of-change of frequency is greater than the setting of the stage 3 frequency rate-of-change protection if the stage 3 frequency rate-of-change protection is enabled. 41. The rate-of-change of frequency is greater than the setting of the stage 4 frequency rate-of-change protection if the stage 4 frequency rate-of-change protection is enabled. 42. If anyone the binary inputs of the mechanical protections is energized if the corresponding mechanical protection is enabled. The FD (Fault Detector) element will reset to normal operation status 10s later if the auto-recloser is enabled or 500ms later if the auto-recloser is disabled, after the last one of the above items is reverted.

3.3 Overcurrent Protection


3.3.1 Definite Time Overcurrent Protection
The overcurrent protection in this relay provides a four-stage phase overcurrent protection with independent definite time characteristics. Each stage can be enabled or disabled independently by the logic settings respectively. All overcurrent element, directional element, voltage control element and harmonic blocking element settings apply to all three phases but are independent for each of the four stages. Configuring the relevant settings can enable or disable the corresponding protection. The first three stages of overcurrent protection only have definite time characteristics, and they have the same protective functional logic. The stage 4 overcurrent protection can be set as either definite time (DT) or inverse definite minimum time (IDMT). The demonstration characteristic figure of the DT overcurrent protection and IDMT overcurrent protection is shown as below.

3-4
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory
tDelay DT OC tDelay IDMT OC

50/51P2.t_Op

50/51P1.t_Op

50/51P2.I_Set

50/51P1.I_Set

Inom

Inom

Figure 3.3-1 Demonstration characteristic of the overcurrent protection

The logic diagram of the stage 1 overcurrent protection is shown in Figure 3.3-2. The overcurrent block is a level detector that detects whether the current magnitude is above the threshold. The stage 2 overcurrent protection and the stage 3 overcurrent protection have the same logic diagrams with the stage 1 overcurrent protection, but the operation thresholds are [50/51P2.I_Set] and [50/51P3.I_Set] respectively. The logic diagram of the stage 4 overcurrent protection with definite time characteristic is shown in Figure 3.3-3, if the setting [50/51P4.Opt_Curve] is set as 0.

Figure 3.3-2 Logic diagram of the stage 1 overcurrent protection

Where: [50/51P1.I_Set] is the current setting of the stage 1 overcurrent protection; tOC1 is the setting [50/51P1.t_Op], the time setting of the stage 1 overcurrent protection; [50/51P1.En] is the logic setting of the stage 1 overcurrent protection; [50/51P1.En1] is the binary signal for enabling the stage 1 overcurrent protection; [50/51P1.Blk] is the binary signal for blocking the stage 1 overcurrent protection; 50/51P1.VCE_x (x: A, B, C) denotes the state of the voltage control element of the stage 1 overcurrent protection, see Section 3.3.3 for more details about the voltage control element;
PCS-9611 Feeder Relay Date: 2011-08-29

3-5

3 Operation Theory

50/51P1.Dir_x (x: A, B, C) denotes the state of the directional element of the stage 1 overcurrent protection, see Section 3.3.4 for more details about the directional element; 50/51P1.HmBlk_x (x: A, B, C) denotes the harmonic blocking element of the stage 1 overcurrent protection, see Section 3.3.5 for more details about the harmonic blocking element.

3.3.2 Inverse Definite Minimum Time Overcurrent Protection


The stage 4 overcurrent protection also can be used as inverse definite minimum time (IDMT) overcurrent protection if the setting [50/51P4.Opt_Curve] is not set as 0. Various methods are available to achieve correct relay coordination on a system; by means of time alone, current alone or a combination of both time and current. Grading by means of current is only possible where there is an appreciable difference in fault level between the two relay locations. Grading by time is used by some utilities but can often lead to excessive fault clearance times at or near source substations where the fault level is highest. For these reasons the most commonly applied characteristic in coordinating overcurrent relays is the IDMT type. The inverse time delayed characteristics comply with the following formula (based on IEC60255-3 and IEEE Std C37.112-1996 standard).

k + C Tp t = ( I / I ) 1 p
Where: k = Constant, the setting [50/51P4.K]. = Constant, the setting [50/51P4.Alpha]. C = Constant, the setting [50/51P4.C]. t = Operation time. I = Measured phase current. Ip is the current threshold setting; the current setting of the stage 4 overcurrent [50/51P4.I_Set] is used as the Ip in this relay. If the stage 4 overcurrent protection is used as IDMT overcurrent protection, the range of the setting [50/51P4.I_Set] is 0.05In ~ 4In. Tp is the time multiplier setting; the multiplier setting of the IDMT overcurrent protection [50/51P4.TMS] is used as Tp in this relay. If the stage 4 overcurrent protection is used as IDMT overcurrent protection, the range of the setting [50/51P4.TMS] is 0.05 ~ 100.00. Some recommended types of IDMT characteristic curves are applied in this relay. It is also can be programmed according to the demand of the special practical application through the PCS-PC configuration tool auxiliary software. The setting [50/51P4.Opt_Curve] can be used to select the expected curve.

3-6
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory Setting Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 IEC IEC IEC IEC IEC IEEE (ANSI) IEEE (ANSI) IEEE (ANSI) IEEE (ANSI) IEEE (ANSI) IEEE (ANSI) IEEE (ANSI) Standard Time Characteristic Definite Time Standard Inverse Very Inverse Extremely Inverse Short Time Inverse Long Time Inverse Extremely Inverse Very Inverse Inverse Moderately Inverse Long Time Extremely Inverse Long Time Very Inverse Long Time Inverse User Programmable k 0.14 13.5 80.0 0.05 120.0 28.20 19.61 0.0086 0.0515 64.07 28.55 0.086 0.02 1.00 2.00 0.04 1.00 2.00 2.00 0.02 0.02 2.00 2.00 0.02 C 0.00 0.00 0.00 0.00 0.00 0.1217 0.491 0.0185 0.114 0.25 0.712 0.185

If the setting [50/51P4.Opt_Curve] is set as 1 to 12, these settings [50/51P4.K], [50/51P4.Alpha] and [50/51P4.C] do not need to be set, and this relay will use these values as listed in above table. The logic diagram of the stage 4 overcurrent protection is shown in Figure 3.3-3. The overcurrent block is a level detector that detects whether the current magnitude is above the threshold.

Figure 3.3-3 Logic diagram of the stage 4 overcurrent protection

Where: [50/51P4.I_Set] is the current setting of the stage 4 overcurrent protection; tOC4 is the setting [50/51P4.t_Op], the time setting of the stage 4 overcurrent protection; [50/51P4.En] is the logic setting of the stage 4 overcurrent protection; [50/51P4.En1] is the binary signal for enabling the stage 4 overcurrent protection;

PCS-9611 Feeder Relay Date: 2011-08-29

3-7

3 Operation Theory

[50/51P4.Blk] is the binary signal for blocking the stage 4 overcurrent protection; [50/51P4.Opt_Curve] is the setting for selecting the inverse time characteristic curve; 50/51P4.VCE_x (x: A, B, C) denotes the state of the voltage control element of the stage 4 overcurrent protection, see Section 3.3.3 for more details about the voltage control element; 50/51P4.Dir_x (x: A, B, C) denotes the state of the directional element of the stage 4 overcurrent protection, see Section 3.3.4 for more details about the directional element; 50/51P4.HmBlk_x (x: A, B, C) denotes the harmonic blocking element of the stage 4 overcurrent protection, see Section 3.3.5 for more details about the harmonic blocking element.

3.3.3 Voltage Control Element for Overcurrent Protection


If the current detected by a local relay for a remote fault condition is below its overcurrent setting, a voltage controlled overcurrent (VCO) element may be used to increase the relay sensitivity to such faults. In this case, a reduction in system voltage will occur; this may then be used to reduce the pick up level of the overcurrent protection. The VCO function can be selectively enabled on the four stages of the main overcurrent element, which was described in Section 3.3.1. When the VCO is enabled, the overcurrent setting can be modified just to be in excess of the maximum value of the load current.
Overcurrent Element Ia> Ib> Ic> Voltage for Controlling Uab< or Uca< or U2> Ubc< or Uab< or U2> Uca< or Ubc< or U2>

Note that the voltage dependent overcurrent relays are more often applied in practical protection applications in order to give adequate overcurrent relay sensitivity for close up fault conditions. The fault characteristic of this protection must then coordinate with any of the downstream overcurrent relays that are responsive to the current decrement condition. It therefore follows that if this relay is to be applied on an outgoing feeder from a generator station, the use of voltage controlled overcurrent protection in the feeder relay may allow better coordination with the VCO relay on the generator. For the operation accuracy of the VCO protection, it is necessary to take the status of the voltage transformer into account. If the voltage transformer has a fault, the numerical relay will issue an [VTS.Alm] signal and block all the elements that relate to the voltage measurement. The logic diagram of the voltage control overcurrent protection is shown in Figure 3.3-2. Each stage of the overcurrent protection can be set with voltage control by its relevant independent setting respectively. The detailed logic diagram for the voltage control element of phase A for the stage 1 overcurrent protection is shown as below. The logic diagrams for voltage control elements of phase B and phase C can be gotten on the analogy of this.

3-8
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

Figure 3.3-4 Logic diagram of the OC1 phase A voltage control element

Where: [50/51P.Upp_VCE] is the voltage setting of the undervoltage control element; [50/51P.U2_VCE] is the voltage setting of the negative sequence overvoltage control element; [VTS.En] is the logic setting of the protection voltage transformer supervision function; [50/51P1.En_VCE] is the logic setting of the voltage control element for the OC1 protection; [50/51P.En_VTS_Blk] is the logic setting of the function which can block all the OC protective elements that relate to the voltage measurement when the voltage transformer is failed; [VTS.Alm] is the alarm signal of the protection voltage transformer supervision.

3.3.4 Directional Element for Overcurrent Protection


The phase fault elements of this relay are internally polarized by the quadrature phase-to-phase voltages, as shown in the table below:
Phase of Protection A Phase B Phase C Phase Operate Current Ia Ib Ic Polarizing Voltage Ubc Uca Uab

Under system fault conditions, the fault current vector will lag its nominal phase voltage by an angle dependent upon the system X/R ratio. It is therefore a requirement that the relay operates with maximum sensitivity for currents lying in this region. This is achieved by means of the relay characteristic angle (RCA) setting; this defines the angle by which the current applied to the relay must be displaced from the voltage applied to the relay to obtain maximum relay sensitivity. For a close up three-phase fault, all three voltages will collapse to zero and no healthy phase voltages will be present. For this reason, the relay includes a synchronous polarization feature that stores the pre-fault positive sequence voltage information and continues to apply it to the directional overcurrent elements for a time period of 25 fundamental wave cycles, after which, it will keep the result of the directional element, this ensures that either the instantaneous or the time delayed directional overcurrent elements will be allowed to operate, even with a three-phase voltage collapse. The relay characteristic angle (RCA) is configurable through the setting [50/51P.RCA]. A directional check is performed based on the following criteria:

PCS-9611 Feeder Relay Date: 2011-08-29

3-9

3 Operation Theory

Directional forward -90 < (angle(U) - angle(I) - RCA) < 90 Directional reverse -90 > (angle(U) - angle(I) - RCA) > 90
Reverse

RCA I Forward

Figure 3.3-5 Operation characteristic of the OC directional element

The setting [50/51Px.Opt_Dir] (x: 1~4) is used to select the directional mode for the stage x (x: 1~4) overcurrent protection respectively.
Setting Value Directional Mode 0 Non-directional 1 Forward directional 2 Reverse directional

Any of the four overcurrent stages may be configured to be directional. When the element is selected as directional, a VTS block option is available. When the relevant setting is set as 1, operation of the voltage transformer supervision (VTS) will block the stage if the relevant directional element is in service. When the relevant setting is set as 0, the stage will revert to non-directional upon operation of the VTS. The logic diagram of the phase directional overcurrent protection is shown in Figure 3.3-2. Each stage of the overcurrent protection can be set with directional element control by its relevant independent setting respectively. The detailed logic diagram for the phase A directional element for the stage 1 overcurrent protection is shown as below. The logic diagrams of voltage control elements of phase B and phase C can be gotten on the analogy of this.
[50/51P.En_VTS_Blk] [VTS.En] [VTS.Alm] Ia (present measure) Ubc(present measure) Ubc(in memory) [50/51P1.Opt_Dir] 0 Phase A Direction Check

&
50/51P1.Dir_A

Figure 3.3-6 Logic diagram of the OC1 phase A directional element

Where: [50/51P1.Opt_Dir] is the setting which is used to select the directional mode (non-directional, forward, reverse) of the directional element for the stage 1 overcurrent protection;

3-10
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

[VTS.En] is the logic setting of the protection voltage transformer supervision function; [50/51P.En_VTS_Blk] is the logic setting of the function which can block all the OC protective elements that relate to the voltage measurement when the voltage transformer is failed; [VTS.Alm] is the alarm signal of the protection voltage transformer supervision.

3.3.5 Harmonic Blocking Element for Overcurrent Protection


To prevent maloperation of the overcurrent protection when the transformer is energized without any load, this relay provides a 2nd harmonic blocking function for resolving such a problem. The percent threshold of the 2nd harmonic blocking element to the fundamental wave can be set through the setting [50/51P.K_Hm2]. The harmonic blocking mode can be selected through the setting [50/51P.Opt_Hm_Blk].

Setting Value 1 2 3 Phase blocking Cross blocking Maximum blocking

Harmonic Blocking Criterion Phase A Ia2/ Ia1 > Max(Ia2, Ib2, Ic2)/ Ia1 > Phase B Ib2/ Ib1 > Max(Ia2, Ib2, Ic2)/ Ib1 > Phase C Ic2/ Ic1 > Max(Ia2, Ib2, Ic2)/ Ic1 >

(Ia2/ Ia1 >) or (Ib2/ Ib1 >) or (Ic2/ Ic1 >)

When the fundamental current is greater than the setting [50/51P.I_Rls_HmBlk], the harmonic blocking element of the corresponding phase is released. The following figure shows the logic diagram of the harmonic blocking element of phase A for the stage 1 overcurrent protection. The logic diagrams of the harmonic blocking elements of phase B and phase C can be gotten on the analogy of this.

Figure 3.3-7 Logic diagram of the OC1 phase A harmonic blocking element

Where: [50/51P1.En_HarmBlk] is the logic setting of the harmonic blocking element of the stage 1 overcurrent protection; [50/51P.K_Hm2] is the percent setting of the harmonic blocking element for OC protection; [50/51P.I_Rls_HmBlk] is the current setting for releasing the harmonic blocking element; [50/51P.Opt_Hm_Blk] is the setting for selecting the harmonic blocking criterion;

PCS-9611 Feeder Relay Date: 2011-08-29

3-11

3 Operation Theory

Ix1 (x: a, b or c) is the fundamental current; Ix2 (x: a, b or c) is the 2nd harmonic current; Imax is the maximum phase current; Imax2 is the maximum 2nd harmonic current.

3.3.6 Overcurrent Protection Settings


All the settings of the overcurrent protection are listed in following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 Menu text 50/51P.U2_VCE 50/51P.Upp_VCE 50/51P.RCA Explanation The voltage setting of the negative sequence voltage blocking element (phase voltage) The voltage setting of the low voltage blocking element (phase-to-phase voltage) The relay characteristic angle for the directional overcurrent protection The logic setting of the function which can block 4 50/51P.En_VTS_Blk the OC protection related voltage measurement when the voltage transformer is failed 5 6 7 8 9 10 50/51P.K_Hm2 50/51P.I_Rls_HmBlk 50/51P.Opt_Hm_Blk 50/51P1.I_Set 50/51P1.t_Op 50/51P1.En_VCE The percent setting of the harmonic blocking element for OC protection The current setting for releasing the harmonic blocking element of the OC protection The setting is used to select the harmonic blocking mode of the OC protection The current setting of the stage 1 overcurrent protection The time setting of the stage 1 overcurrent protection The logic setting of the voltage control element for the stage 1 overcurrent protection The setting is used to select the directional mode 11 50/51P1.Opt_Dir for the stage 1 overcurrent protection, see Section 3.3.4 12 13 14 15 16 50/51P1.En_Hm_Blk 50/51P1.En 50/51P1.OutMap 50/51P2.I_Set 50/51P2.t_Op The logic setting of the harmonic blocking element for the stage 1 overcurrent protection The logic setting of the stage 2 overcurrent protection The output matrix setting of the stage 1 overcurrent protection The current setting of the stage 2 overcurrent protection The time setting of the stage 2 overcurrent protection 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 1 1 1 0.001A 0.001s 0~2 1 0.05~1.00 0.05In~30In 1~3 0.05In~30In 0~100s 0~1 0.001 0.001A 1 0.001A 0.001s 1 0~1 1 Range 2~70V 2~120V -180~179 Step 0.001V 0.001V 1

3-12
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory 17 50/51P2.En_VCE The logic setting of the voltage control element for the stage 2 overcurrent protection The setting is used to select the directional mode 18 50/51P2.Opt_Dir for the stage 2 overcurrent protection, see Section 3.3.4 19 20 21 22 23 24 50/51P2.En_Hm_Blk 50/51P2.En 50/51P2.OutMap 50/51P3.I_Set 50/51P3.t_Op 50/51P3.En_VCE The logic setting of the harmonic blocking element for the stage 2 overcurrent protection The logic setting of the stage 2 overcurrent protection The output matrix setting of the stage 2 overcurrent protection The current setting of the stage 3 overcurrent protection The time setting of the stage 3 overcurrent protection The logic setting of the voltage control element for the stage 3 overcurrent protection The setting is used to select the directional mode 25 50/51P3.Opt_Dir for the stage 3 overcurrent protection, see Section 3.3.4 26 27 28 29 30 31 50/51P3.En_Hm_Blk 50/51P3.En 50/51P3.OutMap 50/51P4.I_Set 50/51P4.t_Op 50/51P4.En_VCE The logic setting of the harmonic blocking element for the stage 3 overcurrent protection The logic setting of the stage 3 overcurrent protection The output matrix setting of the stage 3 overcurrent protection The current setting of the stage 4 overcurrent protection The time setting of the stage 4 overcurrent protection The logic setting of the voltage control element for the stage 4 overcurrent protection The setting is used to select the directional mode 32 50/51P4.Opt_Dir for the stage 4 overcurrent protection, see Section 3.3.4 33 34 35 36 50/51P4.En_Hm_Blk 50/51P4.En 50/51P4.OutMap 50/51P4.Opt_Curve The logic setting of the harmonic blocking element for the stage 4 overcurrent protection The logic setting of the stage 4 overcurrent protection The output matrix setting of the stage 4 overcurrent protection The setting is for selecting the inverse time characteristic curve for OC4 protection 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 1 1 1 1 0~2 1 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~1 1 1 1 0.001A 0.001s 1 0~2 1 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~1 1 1 1 0.001A 0.001s 1 0~2 1 0~1 1

PCS-9611 Feeder Relay Date: 2011-08-29

3-13

3 Operation Theory 37 38 39 40 41 50/51P4.TMS 50/51P4.tmin 50/51P4.K 50/51P4.C 50/51P4.Alpha The time multiplier setting of the IDMT overcurrent protection The minimum operation time setting of the IDMT overcurrent protection Constant k for the IDMT overcurrent protection, see Section 3.3.2 Constant C for the IDMT overcurrent protection, see Section 3.3.2 Constant for the IDMT overcurrent protection, see Section 3.3.2 0.05~100.0 0~100s 0.001~120.0 0.00~1.00 0.01~3.00 0.001 0.001s 0.0001 0.0001 0.0001

3.4 Thermal Overload Protection


3.4.1 Thermal Overload Protection Theory
The relay incorporates a current based thermal replica, using load current to model heating and cooling of the protected plant. The heat generated within an item of the plant, such as a cable or a transformer, is the resistive loss (2Rt). Thus, heating is directly proportional to current squared. The thermal time characteristic used in the relay is therefore based on current squared, integrated over time. The relay automatically uses the largest phase current for input to the thermal model. Equipment is designed to operate continuously at a temperature corresponding to its full load rating, where heat generated is balanced with heat dissipated by radiation etc. This relay provides a thermal overload model which is based on the IEC60255-8 standard. The thermal overload formulas are shown as below. Criterion of cooling start characteristic:

T = ln
Criterion of hot start characteristic:

I2 I 2 (k I B ) 2

T = ln
Where: T = Time to trip (in seconds);

2 I2 Ip

I 2 (k I B ) 2

= Thermal time constant of the equipment to be protected, the setting [49.Tau];


IB = Full load current rating, the setting [49.Ib_Set]; I = The RMS value of the largest phase current;
3-14
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

IP = Steady state pre-loading before application of the overload; k = Factor associated to the thermal state formula, the setting [49.K_Trp] and [49.K_Alm]. The characteristic curve of thermal overload model is shown in Figure 3.4-1.

Figure 3.4-1 Characteristic curve of the thermal overload model

The 1st ~ 7th harmonics of the phase current is taken into account in the calculation of the RMS value of the largest phase current. The input signal [49.Clr] (it can be led from a binary input of this relay) can clear the thermal accumulation without blocking the thermal overload protection, if it is energized. The thermal overload protection also can be used to issue an alarm signal [49.Alm], if the logic setting [49.En_Alm] is set as 1. The logic diagram of the thermal overload protection is shown as below.

Figure 3.4-2 Logic diagram of the thermal overload protection

Where: Imax_rms is the maximum RMS phase current; [49.K_Trp] is the factor setting of the thermal overload protection; [49.Ib_Set] is the reference current setting of the thermal overload protection;

PCS-9611 Feeder Relay Date: 2011-08-29

3-15

3 Operation Theory

[49.K_Alm] is the factor setting of the thermal overload alarm element; [49.En_Trp] is the logic setting of the thermal overload protection; [49.En_Alm] is the logic setting of the thermal overload alarm element; [49.En1] is the binary signal for enabling the thermal overload protection; [49.Blk] is the binary signal for blocking the thermal overload protection; [49.Clr] is the binary signal for clearing the thermal accumulation.

3.4.2 Thermal Overload Protection Settings


All the settings of the thermal overload protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 Menu text 49.Ib_Set 49.Tau Explanation The reference current setting of the thermal overload protection The time constant setting of the IDMT overload protection The factor setting of the thermal overload 3 49.K_Trp protection which is associated to the thermal state formula The factor setting of the thermal overload alarm 4 49.K_Alm element which is associated to the thermal state formula 5 6 7 49.En_Trp 49.En_Alm 49.OutMap The logic setting of the thermal overload protection for tripping The logic setting of the thermal overload protection for alarming The output matrix setting of the thermal overload protection 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 1 1 1 1.0~3.0 0.001 1.0~3.0 0.001 Range 0.05In~3.0In 10~6000s Step 0.001A 0.001s

3.5 Zero Sequence Overcurrent Protection


3.5.1 Definite Time Zero Sequence Overcurrent Protection
The zero sequence overcurrent protection in this relay provides two groups of four-stage zero sequence overcurrent protections with independent definite time delay characteristics. Each stage can be enabled or disabled independently by the corresponding logic setting respectively, and can be controlled with the directional element, harmonic blocking element respectively. The zero sequence current of the No.1 zero sequence overcurrent protection can be led from one dedicated zero sequence current transformer or be self-calculated (through the setting [Opt_3I0]), and the zero sequence current of the No.2 zero sequence overcurrent protection only can be led from another dedicated zero sequence current transformer.

3-16
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

When this relay is used in non-effective grounding (such as the delta side of a transformer) or small current grounding system, the grounding zero sequence current during earth fault is basically small capacitive current. Correct selection of faulty phase in zero sequence protection can not be ensured by detection of such a current. Since all protection equipments are connected with each other via network and information resource can be shared in the substation automation system, so the faulty feeder can be identified firstly by comparing information from various feeders which are connected to the same busbar and then decided finally by trial tripping of the circuit breaker of the selected feeder. In this case, the zero sequence current has to be led from a zero sequence current transformer. When this relay is used in small resistance grounding system, the grounding zero sequence current during earth fault is larger and can be used for tripping directly. All stages are equipped for the zero sequence current protection. In this case, the zero sequence current for tripping can be calculated or directly led from a zero sequence current transformer. Here, take the No.1 zero sequence overcurrent protection as an example to explain the operation theory of the zero sequence overcurrent protection. The operation theory of the No.2 zero sequence overcurrent protection can be gotten on the analogy of this. The following figure shows the logic diagram of the No.1 zero sequence protection. The No.2 zero sequence protection has the same logic diagram with the No.1 zero sequence protection.

Figure 3.5-1 Logic diagram of the No.1 zero sequence overcurrent protection

Where:

PCS-9611 Feeder Relay Date: 2011-08-29

3-17

3 Operation Theory

[50/51Gx.3I0_Set] (x: 1~4) is the current setting of the stage x (x: 1~4) zero sequence overcurrent protection; tROCx (x: 1~4) is the setting [50/51Gx.t_Op] (x: 1~4), the time setting of the stage x (x: 1~4) zero sequence overcurrent protection; [50/51Gx.En] (x: 1~4) is the logic setting of the stage x (x: 1~4) zero sequence overcurrent protection; [50/51Gx.En1] (x: 1~4) is the binary signal for enabling the stage x (x: 1~4) zero sequence overcurrent protection; [50/51Gx.Blk] (x: 1~4) is the binary signal for blocking the stage x (x: 1~4) zero sequence overcurrent protection; [50/51G4.Opt_Curve] is the setting for selecting the inverse time characteristic curve; 50/51Gx.Dir (x: 1~4) denotes the status of the zero sequence directional element, see Section 3.5.3 for more details about the directional element; 50/51Gx.HmBlk (x: 1~4) denotes the status of the harmonic blocking element, see Section 3.5.4 for more details about the harmonic blocking element.

3.5.2 IDMT Zero Sequence Overcurrent Protection


The stage 4 zero sequence overcurrent protection also can be used as zero sequence inverse definite minimum time (IDMT) overcurrent protection. It has the same inverse time characteristic with the IDMT overcurrent protection (see Section 3.3.2), and the setting [50/51G4.Opt_Curve] can be used to select the expected curve. The logic diagram of the No.1 zero sequence IDMT overcurrent protection is shown as below. The zero sequence overcurrent block is a level detector that detects whether the current magnitude is above the threshold.

Figure 3.5-2 Logic diagram of the No.1 zero sequence IDMT overcurrent protection

Where: [50/51G4.3I0_Set] is the current setting of the No.1 stage 4 ROC protection; [50/51G4.En] is the logic setting of the No.1 stage 4 ROC protection; [50/51G4.En1] is the binary signal for enabling the stage 4 ROC protection; [50/51G4.Blk] is the binary signal for blocking the stage 4 ROC protection;
3-18
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

[50/51G4.Opt_Curve] is the setting for selecting the inverse time characteristic curve; 50/51G4.Dir denotes the status of the zero sequence directional element for the No.1 stage 4 zero sequence overcurrent protection, see Section 3.5.3 for more details about the directional element; 50/51G4.HmBlk denotes the status of the harmonic blocking element for the No.1 stage 4 zero sequence overcurrent protection, see Section 3.5.4 for more details about the harmonic blocking element.

3.5.3 Directional Element for Zero Sequence Overcurrent Protection


The residual voltage is used to polarize the directional earth fault (DEF) protection. With earth fault protection, the polarizing signal is required to be a representative of the earth fault condition. As residual voltage is generated during earth fault conditions, this quantity is commonly used to polarize DEF elements. This relay internally derives this voltage from the 3-phase voltage input that must be supplied from three single-phase voltage transformers. These types of VT design allow the passage of residual flux and consequently permit the relay to derive the required residual voltage. In addition, the primary star point of the VT must be earthed. It is possible that small levels of residual voltage will be present under normal system conditions due to system imbalances, VT inaccuracies, relay tolerances etc. The zero sequence relay characteristic angle (ZS-RCA) is configurable through the setting [50/51G.RCA]. A directional check is performed based on the following criteria: Directional forward -90 < (angle(U0) - angle(I01) - ZS-RCA) < 90 Directional reverse -90 > (angle(U0) - angle(I01) - ZS-RCA) > 90

Figure 3.5-3 Operation characteristic of the ROC directional element

The setting [50/51Gx.Opt_Dir] (x: 1~4) is used to select the directional mode for the stage x (x: 1~4) zero sequence overcurrent protection respectively.

PCS-9611 Feeder Relay Date: 2011-08-29

3-19

3 Operation Theory Setting Value Directional Mode 0 Non-directional 1 Forward directional 2 Reverse directional

When the element is selected as directional, a VTS block option is available. When the relevant setting is set as 1, operation of the voltage transformer supervision (VTS) will block the stage if the relevant directional element is in service. When the relevant setting is set as 0, the stage will revert to non-directional upon operation of the VTS. The detailed logic diagram of the zero sequence directional element of the stage 1 zero sequence overcurrent protection is shown as below.

Figure 3.5-4 Logic diagram of the directional element for the No.1 ROC1 protection

Where: [50/51G1.Opt_Dir] is the setting which is used to select the directional mode (non-directional, forward, reverse) of the directional element for the stage 1 ROC protection; [VTS.En] is the logic setting of the protection voltage transformer supervision function; [50/51G.En_VTS_Blk] is the logic setting of the function which blocks all the 1ROC protective elements that relate to the voltage measurement when the voltage transformer is failed; [VTS.Alm] is the alarm signal of the protection voltage transformer supervision.

3.5.4 Harmonic Blocking Element for ROC Protection


To prevent maloperation of the zero sequence overcurrent protection when the transformer is energized without any load, this relay provides a 2nd harmonic blocking function for resolving such a problem. The percent threshold of the 2nd harmonic blocking element to the fundamental wave can be set through the setting [50/51G.K_Hm2]. When the fundamental current is greater than the setting [50/51G.3I0_Rls_HmBlk], the harmonic blocking element for the zero sequence protection is released. The following figure shows the logic diagram of the harmonic blocking element for the stage 1 zero sequence overcurrent protection.

Figure 3.5-5 Logic diagram of the No.1 ROC1 harmonic blocking element

3-20
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

Where: [50/51G1.En_Hm_Blk] is the logic setting of the harmonic blocking element; [50/51G.K_Hm2] is the percent setting of the harmonic blocking element; [50/51G.3I0_Rls_HmBlk] is the current setting for releasing the harmonic blocking element; I01 is the No.1 zero sequence current; I012 is the 2nd harmonic of the No.1 zero sequence current.

3.5.5 Zero Sequence Overcurrent Protection Settings


For the information about the common explanation of the settings, see Section 7.3. All the settings of the No.1 zero sequence overcurrent protection are listed in the following table.
No. 1 Menu text 50/51G.RCA Explanation The relay characteristic angle for the No.1 directional zero sequence overcurrent protection The logic setting of the function which blocks the 2 50/51G.En_VTS_Blk 1ROC protection related voltage measurement when the voltage transformer is failed 3 4 5 6 7 8 9 10 11 12 13 14 50/51G.K_Hm2 50/51G.3I0_Rls_HmBlk 50/51G1.3I0_Set 50/51G1.t_Op 50/51G1.Opt_Dir 50/51G1.En_Hm_Blk 50/51G1.En 50/51G1.OutMap 50/51G2.3I0_Set 50/51G2.t_Op 50/51G2.Opt_Dir 50/51G2.En_Hm_Blk The percent setting of the harmonic blocking element for the No.1 ROC protection The current setting for releasing the harmonic blocking element of the No.1 ROC protection The current setting of the No.1 stage 1 zero sequence overcurrent protection The time setting of the No.1 stage 1 zero sequence overcurrent protection The setting is used to select the directional mode for the No.1 ROC1 protection, see Section 3.5.3 The logic setting of the harmonic blocking element for the No.1 ROC1 protection The logic setting of the No.1 stage 1 zero sequence overcurrent protection The output matrix setting of the No.1 stage 1 zero sequence overcurrent protection The current setting of the No.1 stage 2 zero sequence overcurrent protection The time setting of the No.1 stage 2 zero sequence overcurrent protection The setting is used to select the directional mode for the No.1 ROC2 protection, see Section 3.5.3 The logic setting of the harmonic blocking element for the No.1 ROC2 protection 0.05~1.00 0.05In~30In 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0.001 0.001A 0.001A 0.001s 1 1 1 1 0.001A 0.001s 1 1 0~1 1 Range -180~179 Step 1

PCS-9611 Feeder Relay Date: 2011-08-29

3-21

3 Operation Theory 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 50/51G2.En 50/51G2.OutMap 50/51G3.3I0_Set 50/51G3.t_Op 50/51G3.Opt_Dir 50/51G3.En_Hm_Blk 50/51G3.En 50/51G3.OutMap 50/51G4.3I0_Set 50/51G4.t_Op 50/51G4.Opt_Dir 50/51G4.En_Hm_Blk 50/51G4.En 50/51G4.OutMap 50/51G4.Opt_Curve 50/51G4.TMS 50/51G4.tmin 50/51G4.K 50/51G4.C 50/51G4.Alpha The logic setting of the No.1 stage 2 zero sequence overcurrent protection The output matrix setting of the No.1 stage 2 zero sequence overcurrent protection The current setting of the No.1 stage 3 zero sequence overcurrent protection The time setting of the No.1 stage 3 zero sequence overcurrent protection The setting is used to select the directional mode for the No.1 ROC3 protection, see Section 3.5.3 The logic setting of the harmonic blocking element for the No.1 ROC3 protection The logic setting of the No.1 stage 3 zero sequence overcurrent protection The output matrix setting of the No.1 stage 3 zero sequence overcurrent protection The current setting of the No.1 stage 4 zero sequence overcurrent protection The time setting of the No.1 stage 4 zero sequence overcurrent protection The setting is used to select the directional mode for the No.1 ROC4 protection, see Section 3.5.3 The logic setting of the harmonic blocking element for the No.1 ROC4 protection The logic setting of the No.1 stage 4 zero sequence overcurrent protection The output matrix setting of the No.1 stage 4 zero sequence overcurrent protection The setting is for selecting the inverse time characteristic curve for the No.1 ROC4 protection The time multiplier setting of the No.1 zero sequence IDMT overcurrent protection The minimum operation time setting of the No.1 zero sequence IDMT overcurrent protection Constant k for the No.1 zero sequence IDMT overcurrent protection, see Section 3.5.2 Constant C for the No.1 zero sequence IDMT overcurrent protection, see Section 3.5.2 Constant for the No.1 zero sequence IDMT overcurrent protection, see Section 3.5.2 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s 0.001~120.0 0.00~1.00 0.01~3.00 1 1 0.001A 0.001s 1 1 1 1 0.001A 0.001s 1 1 1 1 1 0.001 0.001s 0.0001 0.0001 0.0001

3-22
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

All the settings of the No.2 zero sequence overcurrent protection are listed in the following table.
No. 1 Menu text A.50/51G.RCA Explanation The relay characteristic angle for the No.2 directional zero sequence overcurrent protection The logic setting of the function which blocks the 2 A.50/51G.En_VTS_Blk 2ROC protection related voltage measurement when the voltage transformer is failed 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 A.50/51G.K_Hm2 A.50/51G.3I0_Rls_HmBlk A.50/51G1.3I0_Set A.50/51G1.t_Op A.50/51G1.Opt_Dir A.50/51G1.En_Hm_Blk A.50/51G1.En A.50/51G1.OutMap A.50/51G2.3I0_Set A.50/51G2.t_Op A.50/51G2.Opt_Dir A.50/51G2.En_Hm_Blk A.50/51G2.En A.50/51G2.OutMap A.50/51G3.3I0_Set A.50/51G3.t_Op A.50/51G3.Opt_Dir A.50/51G3.En_Hm_Blk The percent setting of the harmonic blocking element for the No.2 ROC protection The current setting for releasing the harmonic blocking element of the No.2 ROC protection The current setting of the No.2 stage 1 zero sequence overcurrent protection The time setting of the No.2 stage 1 zero sequence overcurrent protection The setting is used to select the directional mode for the No.2 ROC1 protection The logic setting of the harmonic blocking element for the No.2 ROC1 protection The logic setting of the No.2 stage 1 zero sequence overcurrent protection The output matrix setting of the No.2 stage 1 zero sequence overcurrent protection The current setting of the No.2 stage 2 zero sequence overcurrent protection The time setting of the No.2 stage 2 zero sequence overcurrent protection The setting is used to select the directional mode for the No.2 ROC2 protection The logic setting of the harmonic blocking element for the No.2 ROC2 protection The logic setting of the No.2 stage 2 zero sequence overcurrent protection The output matrix setting of the No.2 stage 2 zero sequence overcurrent protection The current setting of the No.2 stage 3 zero sequence overcurrent protection The time setting of the No.2 stage 3 zero sequence overcurrent protection The setting is used to select the directional mode for the No.2 ROC3 protection The logic setting of the harmonic blocking element for the No.2 ROC3 protection 0.05~1.00 0.05In~30In 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0.001 0.001A 0.001A 0.001s 1 1 1 1 0.001A 0.001s 1 1 1 1 0.001A 0.001s 1 1 0~1 1 Range -180~179 Step 1

PCS-9611 Feeder Relay Date: 2011-08-29

3-23

3 Operation Theory 21 22 23 24 25 26 27 28 29 30 31 32 33 34 A.50/51G3.En A.50/51G3.OutMap A.50/51G4.3I0_Set A.50/51G4.t_Op A.50/51G4.Opt_Dir A.50/51G4.En_Hm_Blk A.50/51G4.En A.50/51G4.OutMap A.50/51G4.Opt_Curve A.50/51G4.TMS A.50/51G4.tmin A.50/51G4.K A.50/51G4.C A.50/51G4.Alpha The logic setting of the No.2 stage 3 zero sequence overcurrent protection The output matrix setting of the No.2 stage 3 zero sequence overcurrent protection The current setting of the No.2 stage 4 zero sequence overcurrent protection The time setting of the No.2 stage 4 zero sequence overcurrent protection The setting is used to select the directional mode for the No.2 ROC4 protection The logic setting of the harmonic blocking element for the No.2 ROC4 protection The logic setting of the No.2 stage 4 zero sequence overcurrent protection The output matrix setting of the No.2 stage 4 zero sequence overcurrent protection The setting is for selecting the inverse time characteristic curve for the No.2 ROC4 protection The time multiplier setting of the No.2 zero sequence IDMT overcurrent protection The minimum operation time setting of the No.2 zero sequence IDMT overcurrent protection Constant k for the No.2 zero sequence IDMT overcurrent protection, see Section 3.5.2 Constant C for the No.2 zero sequence IDMT overcurrent protection, see Section 3.5.2 Constant for the No.2 zero sequence IDMT overcurrent protection, see Section 3.5.2 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s 0.001~120.0 0.00~1.00 0.01~3.00 1 1 0.001A 0.001s 1 1 1 1 1 0.001 0.001s 0.0001 0.0001 0.0001

3.6 Sensitive Earth Fault Protection


3.6.1 Definite Time Sensitive Earth Fault Protection
This relay provides a four-stage sensitive earth fault protection with independent definite time delay characteristics. Each stage can be enabled or disabled independently by the corresponding logic setting respectively, and can be controlled by the directional element respectively. The stage 4 SEF also can be set with inverse definite minimum time (IDMT) characteristic. Each stage can be used for tripping or alarming through the PCS-PC and the default is for tripping. When this relay is used in non-effective grounding (such as the delta side of a transformer) or small current grounding system, the grounding zero sequence current during earth fault is basically small capacitive current. Correct selection of faulty phase in zero sequence protection can not be ensured by detection of such a current. One current transformer input is dedicated to the sensitive earth fault (SEF) protection. The input CT is designed specially to operate at very low
3-24
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

current magnitudes. The following figure shows the stage 1 sensitive earth fault protection logic diagram, other stage has the same logic diagram.

Figure 3.6-1 Logic diagram for the stage 1 sensitive earth fault protection

Where: [50/51SEF1.3I0_Set] is the current setting of the stage 1 sensitive earth fault protection; tSEF1 is the setting [50/51SEF1.t_Op], the time setting of the SEF1 protection; [50/51SEF1.En] is the logic setting of the stage 1 sensitive earth fault protection; [50/51SEF1.En1] is the binary signal for enabling the stage 1 sensitive earth fault protection; [50/51SEF1.Blk] is the binary signal for blocking the stage 1 sensitive earth fault protection; 50/51SEF1.Dir denotes the status of the directional element for the stage 1 sensitive earth fault protection, see Section 3.6.3 for more details about the directional element.

3.6.2 IDMT Sensitive Earth Fault Protection


The stage 4 sensitive earth fault protection also can be used as inverse definite minimum time (IDMT) sensitive earth fault protection. It has the same inverse time characteristic with the IDMT overcurrent protection (see Section 3.3.2), and the setting [50/51SEF4.Opt_Curve] can be used to select the expected curve. The logic diagram of the IDMT sensitive earth fault protection is shown as below. The sensitive earth fault current block is a level detector that detects whether the current magnitude is above the threshold.

Figure 3.6-2 Logic diagram of the IDMT sensitive earth fault protection

Where: [50/51SEF4.3I0_Set] is the current setting of the stage 4 sensitive earth fault protection; [50/51SEF4.En] is the logic setting of the stage 4 sensitive earth fault protection;
PCS-9611 Feeder Relay Date: 2011-08-29

3-25

3 Operation Theory

[50/51SEF4.En1] is the binary signal for enabling the stage 4 sensitive earth fault protection; [50/51SEF4.Blk] is the binary signal for blocking the stage 4 sensitive earth fault protection; [50/51SEF4.Opt_Curve] is the setting for selecting the inverse time characteristic curve; 50/51SEF4.Dir denotes the status of the directional element for the stage 4 sensitive earth fault protection, see Section 3.6.3 for more details about the directional element.

3.6.3 Directional Element for Sensitive Earth Fault Protection


The residual voltage is used to polarize the directional element for the SEF protection. With earth fault protection, the polarizing signal is required to be a representative of the earth fault condition. As residual voltage is generated during earth fault conditions, this quantity is commonly used to polarize directional elements. The residual voltage is also derived from the 3-phase voltage input, which are same with the directional element for the zero sequence overcurrent protection. The sensitive earth fault relay characteristic angle (SEF-RCA) is configurable through the setting [50/51SEF.RCA]. A directional check is performed based on the following criteria: Directional forward -90 < (angle(U0) - angle(I0S) - SEF-RCA) < 90 Directional reverse -90 > (angle(U0) - angle(I0S) - SEF-RCA) > 90

Figure 3.6-3 Operation characteristic of the SEF directional element

The setting [50/51SEFx.Opt_Dir] (x: 1~4) is used to select the directional mode for the stage x (x: 1~4) sensitive earth fault protection respectively.
Setting Value Directional Mode 0 Non-directional 1 Forward directional 2 Reverse directional

When the element is selected as directional, a VTS block option is available. When the relevant setting is set as 1, operation of the voltage transformer supervision (VTS) will block the stage if the relevant directional element is in service. When the relevant setting is set as 0, the stage will revert to non-directional upon operation of the VTS. The detailed logic diagram of the directional element of the stage 1 sensitive earth fault protection
3-26
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

is shown as below.

Figure 3.6-4 Logic diagram of the directional element for the stage 1 SEF protection

Where: [50/51SEF1.Opt_Dir] is the setting which is used to select the directional mode (non-directional, forward, reverse) of the directional element for the stage 1 SEF protection; [VTS.En] is the logic setting of the protection voltage transformer supervision function; [50/51SEF.En_VTS_Blk] is the logic setting of the function which can block all the SEF protection that relate to the voltage measurement when the voltage transformer is failed; [VTS.Alm] is the alarm signal of the protection voltage transformer supervision.

3.6.4 Sensitive Earth Fault Protection Settings


All the settings of the sensitive earth fault protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 Menu text 50/51SEF.RCA Explanation The relay characteristic angle for the directional sensitive earth fault protection The logic setting of the function which blocks the 2 50/51SEF.En_VTS_Blk SEF protection related voltage measurement when the voltage transformer is failed 3 4 5 6 7 8 9 50/51SEF1.3I0_Set 50/51SEF1.t_Op 50/51SEF1.Opt_Dir 50/51SEF1.En 50/51SEF1.OutMap 50/51SEF2.3I0_Set 50/51SEF2.t_Op The current setting of the stage 1 sensitive earth fault protection The time setting of the stage 1 sensitive earth fault protection The setting is used to select the directional mode for the stage 1 SEF protection, see Section 3.6.3 The logic setting of the stage 1 sensitive earth fault protection The output matrix setting of the stage 1 sensitive earth fault protection The current setting of the stage 2 sensitive earth fault protection The time setting of the stage 2 sensitive earth fault protection 0.005~0.4A 0~100s 0~2 0~1 0x00000000 ~ 0x7FFFFFFF 0.005~0.4A 0~100s 0.001A 0.001s 1 1 1 0.001A 0.001s 0~1 1 Range -180~179 Step 1

PCS-9611 Feeder Relay Date: 2011-08-29

3-27

3 Operation Theory 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 50/51SEF2.Opt_Dir 50/51SEF2.En 50/51SEF2.OutMap 50/51SEF3.3I0_Set 50/51SEF3.t_Op 50/51SEF3.Opt_Dir 50/51SEF3.En 50/51SEF3.OutMap 50/51SEF4.3I0_Set 50/51SEF4.t_Op 50/51SEF4.Opt_Dir 50/51SEF4.En 50/51SEF4.OutMap 50/51SEF4.Opt_Curve 50/51SEF4.TMS 50/51SEF4.tmin 50/51SEF4.K 50/51SEF4.C 50/51SEF4.Alpha The setting is used to select the directional mode for the stage 2 SEF protection, see Section 3.6.3 The logic setting of the stage 2 sensitive earth fault protection The output matrix setting of the stage 2 sensitive earth fault protection The current setting of the stage 3 sensitive earth fault protection The time setting of the stage 3 sensitive earth fault protection The setting is used to select the directional mode for the stage 3 SEF protection, see Section 3.6.3 The logic setting of the stage 3 sensitive earth fault protection The output matrix setting of the stage 3 sensitive earth fault protection The current setting of the stage 4 sensitive earth fault protection The time setting of the stage 4 sensitive earth fault protection The setting is used to select the directional mode for the stage 4 SEF protection, see Section 3.6.3 The logic setting of the stage 4 sensitive earth fault protection The output matrix setting of the stage 4 sensitive earth fault protection The setting is for selecting the inverse time characteristic curve for SEF4 protection The time multiplier setting of the IDMT sensitive earth fault protection The minimum operation time setting of the IDMT sensitive earth fault protection Constant k for the IDMT sensitive earth fault protection, see Section 3.6.2 Constant C for the IDMT sensitive earth fault protection, see Section 3.6.2 Constant for the IDMT sensitive earth fault protection, see Section 3.6.2 0~2 0~1 0x00000000 ~ 0x7FFFFFFF 0.005~0.4A 0~100s 0~2 0~1 0x00000000 ~ 0x7FFFFFFF 0.005~0.4A 0~100s 0~2 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s 0.001~120.0 0.00~1.00 0.01~3.00 1 1 1 0.001A 0.001s 1 1 1 0.001A 0.001s 1 1 1 1 0.001 0.001s 0.0001 0.0001 0.0001

3.7 Negative Sequence Overcurrent Protection


3.7.1 Definite Time Negative Sequence Overcurrent Protection
The application of negative sequence overcurrent protection to motors has a special significance.
3-28
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

Unbalanced loads create counter-rotating fields in three-phase induction motors, which act on the rotor at double frequency. Eddy currents are induced on the rotor surface, which causes local overheating in rotor end zones and the slot wedges. This especially goes for motors which are tripped via vacuum contactors with fuses connected in series. With single phasing due to operation of a fuse, the motor only generates small and pulsing torques such that it soon is thermally strained assuming that the torque required by the machine remains unchanged. In addition, the unbalanced supply voltage introduces the risk of thermal overload. Due to the small negative sequence reactance even small voltage asymmetries lead to large negative sequence currents. This relay provides a two-stage negative sequence overcurrent protection with definite time delay characteristics. Each stage can be enabled or disabled by scheme logic settings independently. The two stages have same protection logics if they are set with definite time characteristics. The logic diagram for the stage 1 negative sequence overcurrent protection is shown as below. The negative sequence overcurrent block is a level detector that detects whether the negative sequence current magnitude is above the threshold.

Figure 3.7-1 Logical diagram of the stage 1 NOC protection

Where: [50/51Q1.I2_Set] is the current setting of the stage 1 negative sequence overcurrent protection; tNOC1 is the setting [50/51Q1.t_Op], the time setting of the stage 1 negative sequence overcurrent protection; [50/51Q1.En] is the logic setting of the stage 1 negative sequence overcurrent protection; [50/51Q1.En1] is the binary signal for enabling the NOC1 protection; [50/51Q1.Blk] is the binary signal for blocking the NOC1 protection.

3.7.2 IDMT Negative Sequence Overcurrent Protection


The stage 2 negative sequence overcurrent protection also can be set with inverse definite minimum time (IDMT) characteristic. It has the same inverse time characteristic with the IDMT overcurrent protection (see Section 3.3.2), and the setting [50/51Q2.Opt_Curve] can be used to select the expected curve. The logic diagram of the negative sequence overcurrent protection is shown as below. The negative sequence current block is a level detector that detects whether the current magnitude is above the threshold.

PCS-9611 Feeder Relay Date: 2011-08-29

3-29

3 Operation Theory

Figure 3.7-2 Logic diagram of the IDMT negative sequence overcurrent protection

Where: [50/51Q2.I2_Set] is the current setting of the stage 2 negative sequence overcurrent protection; [50/51Q2.En] is the logic setting of the stage 2 negative sequence overcurrent protection; [50/51Q2.Opt_Curve] is the setting for selecting the inverse time characteristic curve; [50/51Q2.En1] is the binary signal for enabling the NOC2 protection; [50/51Q2.Blk] is the binary signal for blocking the NOC2 protection.

3.7.3 Negative Sequence Overcurrent Protection Settings


All the settings of the negative sequence overcurrent protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 4 5 6 7 8 9 10 11 Menu text 50/51Q1.I2_Set 50/51Q1.t_Op 50/51Q1.En 50/51Q1.OutMap 50/51Q2.I2_Set 50/51Q2.t_Op 50/51Q2.En 50/51Q2.OutMap 50/51Q2.Opt_Curve 50/51Q2.TMS 50/51Q2.tmin Explanation The current setting of the stage 1 negative sequence overcurrent protection The time setting of the stage 1 negative sequence overcurrent protection The logic setting of the stage 1 negative sequence overcurrent protection The output matrix setting of the stage 1 negative sequence overcurrent protection The current setting of the stage 2 negative sequence overcurrent protection The time setting of the stage 2 negative sequence overcurrent protection The logic setting of the stage 2 negative sequence overcurrent protection The output matrix setting of the stage 2 negative sequence overcurrent protection The setting is for selecting the inverse time characteristic curve for the NOC2 protection The time multiplier setting of the negative sequence IDMT overcurrent protection The minimum operation time setting of the negative sequence IDMT overcurrent protection Range 0.05In~4In 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~4In 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s Step 0.001A 0.001s 1 1 0.001A 0.001s 1 1 1 0.001 0.001s

3-30
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory 12 13 14 50/51Q2.K 50/51Q2.C 50/51Q2.Alpha Constant k for the negative sequence IDMT overcurrent protection, see Section 3.7.2 Constant C for the negative sequence IDMT overcurrent protection, see Section 3.7.2 Constant for the negative sequence IDMT overcurrent protection, see Section 3.7.2 0.001~120.0 0.00~1.00 0.01~3.00 0.0001 0.0001 0.0001

3.8 Broken Conductor Protection


3.8.1 Broken Conductor Protection Theory
The relay incorporates an element which measures the ratio of negative to positive phase sequence current (2/1). This will be affected to a lesser extent than the measurement of negative sequence current alone, since the ratio is approximately constant with variations in load current. Hence, a more sensitive setting may be achieved. At the moment when the circuit breaker is closed, because the three poles of the circuit breaker are discrepant for a very short time, and if the broken conductor protection is enabled, it is easy to make the broken conductor protection pick up, and it will restore after the load current is stable. The logic diagram is as shown below. The ratio of I2/I1 is calculated and is compared with the threshold and if the threshold is exceeded then the delay timer is initiated.

Figure 3.8-1 Logic diagram of the broken conductor protection

Where: [50BC.I2/I1_Set] is the ratio setting of the broken conductor protection; tBCP is the setting [50BC.t_Op], the time setting of the broken conductor protection; [50BC.En] is the logic setting of the broken conductor protection; [50BC.En1] is the binary signal for enabling the broken conductor protection; [50BC.Blk] is the binary signal for blocking the broken conductor protection.

3.8.2 Broken Conductor Protection Settings


All the settings of the broken conductor protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 Menu text 50BC.I2/I1_Set protection Explanation The ratio setting for the broken conductor Range 0.10~1.00 Step 0.001

PCS-9611 Feeder Relay Date: 2011-08-29

3-31

3 Operation Theory 2 3 4 50BC.t_Op 50BC.En 50BC.OutMap The time setting for the broken conductor protection The logic setting for the broken conductor protection The output matrix setting of the broken conductor protection 0~200s 0~1 0x00000000 ~ 0x7FFFFFFF 0.001s 1 1

3.9 Breaker Failure Protection


3.9.1 Breaker Failure Protection Theory
The circuit breaker failure protection is specially for re-tripping the circuit breaker, when the relay has transmitted the tripping command to the circuit breaker, but it also can detect the fault is still existed in the system or the circuit breaker is still closed after an appointed time delay. The breaker failure protection in this relay has two independent definite time delay characteristics. It is controlled by the external initiation signal 50BF.In_BFP1 (such as the external binary input trigger signal) or the inner initiation signal 50BF.In_BFP2 (such as the relay tripping operation signal). The signal 50BF.In_BFP1 and 50BF.In_BFP2 can be configured through the PCS-PC software. For some special faults (for example, mechanical protection or overvoltage protection operating), maybe the faulty current is very small and the current criterion of the breaker failure protection can not be satisfied, in order to make the breaker failure protection can operate in such a situation, the auxiliary contact of the circuit breaker can be taken into account. So this relay provides four criteria logics to meet different requirements. Four criteria logics based on the phase currents and the circuit breaker state (based on the binary input [BI_52b]) are selectable through the setting [50BF.Opt_LogicMode]. The criteria conditions are list as below: (A) the maximum phase current is greater than the setting [50BF.I_Set]; (B) the circuit breaker is still closed ([BI_52b] = 0).
Setting Value 1 2 3 4 Ipmax > [50BF.I_Set] NOT([BI_52b]) (Ipmax > [50BF.I_Set]) OR (NOT([BI_52b])) (Ipmax > [50BF.I_Set]) AND (NOT([BI_52b])) Criteria Condition Logic Only A Only B A OR B A AND B

The logic diagram of the breaker failure protection is shown as below.

3-32
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory
Ia > [50BF.I_Set] Ib > [50BF.I_Set] Ic > [50BF.I_Set] [BI_52b] [50BF.Opt_LogicMode] 50BF.In_BFP1 50BF.In_BFP2 [50BF.En] [50BF.En1] [50BF.En_ReTrp] tBFP2 0 B A 1 ONLY A 2 ONLY B 3 A OR B 4 A AND B

[50BF.St]

&

tBFP1

[50BF.Op]

&

[50BF.ReTrp]

Figure 3.9-1 Logic diagram of the breaker failure protection

Where: [50BF.I_Set] is the current setting of the breaker failure protection; tBFP1 is the setting [50BF.t_Op], the time setting of the breaker failure protection; tBFP2 is the setting [50BF.t_ReTrp] is the re-trip time setting of the breaker failure protection; [50BF.En] is the logic setting of the breaker failure protection; [50BF.En1] is the binary signal for enabling the breaker failure protection; [50BF.En_ReTrp] is the logic setting of re-trip function the breaker failure protection; [50BF.Opt_LogicMode] is the setting for selecting the BFP criterion logic; [BI_52b] is the binary input from the auxiliary normal close contact of the circuit breaker; 50BF.In_BFP1 is the external initiation signal such as the external binary input trigger signal, and the external binary input which is used to initiate the breaker failure protection can be configured through the PCS-PC configuration tool auxiliary software. 50BF.In_BFP2 is the inner initiation signal such as the relay tripping operation signal, and the tripping elements which are used to initiate the breaker failure protection can be configured through the PCS-PC configuration tool auxiliary software. The time setting of the breaker failure protection should be based on the maximum circuit breaker operating time plus the dropout time of the current flow monitoring element plus a safety margin which takes into consideration the tolerance of the time delay.

Figure 3.9-2 Timing for a typical breaker failure scenario

PCS-9611 Feeder Relay Date: 2011-08-29

3-33

3 Operation Theory

3.9.2 Breaker Failure Protection Settings


All the settings of the breaker failure protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 4 5 6 7 8 Menu text 50BF.I_Set 50BF.t_Op 50BF.t_ReTrp 50BF.Opt_LogicMode 50BF.En 50BF.En_ReTrp 50BF.OutMap 50BF.OutMap_ReTrp protection The time setting of the breaker failure protection The re-trip time setting of the breaker failure protection The setting for selecting the criteria logic of the breaker failure protection The logic setting of the breaker failure protection The logic setting of the re-trip function of the breaker failure protection The output matrix setting of the breaker failure protection The output matrix setting of the re-trip function of the breaker failure protection Explanation The current setting of the breaker failure Range 0.05In~5.0In 0~100s 0~100s 1~4 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0x00000000 ~ 0x7FFFFFFF Step 0.001A 0.001s 0.001s 1 1 1 1 1

3.10 Switch Onto Fault (SOTF) Protection


3.10.1 SOTF Protection Theory
In some feeder applications, three-pole fast tripping may be required if a fault is present on the feeder when it is energized. Such faults may be due to a fault condition not having been removed from the feeder, or due to earthing clamps having been left on the following maintenance. In either case, it may be desirable to clear the fault condition in an accelerated time, rather than waiting for the time delay associated with overcurrent protection. Switch onto fault overcurrent protection and zero sequence accelerated overcurrent protection are equipped in this equipment. Acceleration before or after tripping can be configured by setting the logic setting [SOTF.Opt_Mode]. Acceleration after tripping includes accelerated tripping for manual switching-onto-fault or automatic reclosing-onto-fault. Current settings and delays of these two accelerated tripping protections can be configured independently. If acceleration after tripping is selected, the SOTF element is enabled for the predefined time [SOTF.t_En] after the auto-recloser operates. And the SOTF element is enabled for the predefined time [SOTF.t_En] fixedly after manual closing signal is issued, and the typical value is 3s. The logic diagram of the switch onto fault protection is shown as below.

3-34
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory
Ia > [50PSOTF.I_SetF] Ib > [50PSOTF.I_SetF] Ic > [50PSOTF.I_SetF] [50PSOTF.En] [50PSOTF.En1] [50PSOTF.Blk] [79.Ready] [SOTF.Opt_Mode] [79.Close_3PSx] (x:1~4) SOTF.ManClsCB I10 > [50GSOTF.3I0_Set] [50GSOTF.En] [50GSOTF.En1] [50GSOTF.Blk]

& & & &


0 tEnSOTF tSOTFOC 0

[50PSOTF.St] [50PSOTF.Op]

[50GSOTF.St]

& &

tSOTFROC

[50GSOTF.Op]

Figure 3.10-1 Logic diagram of the SOTF protection

Where: [50PSOTF.I_Set] is the current setting of the SOTF overcurrent protection; tSOTFOC is the setting [50PSOTF.t_Op], the time setting of the SOTF overcurrent protection; [50PSOTF.En] is the logic setting of the SOTF overcurrent protection; [50PSOTF.En1] is the binary signal for enabling the SOTF overcurrent protection; [50PSOTF.Blk] is the binary signal for blocking the SOTF overcurrent protection; [50GSOTF.3I0_Set] is the current setting of the zero sequence SOTF overcurrent protection; tSOTFROC is the setting [50GSOTF.t_Op], the time setting of the zero sequence SOTF overcurrent protection; [50GSOTF.En] is the logic setting of the zero sequence SOTF overcurrent protection; [50GSOTF.En1] is the binary signal for enabling the zero sequence SOTF overcurrent protection; [50GSOTF.Blk] is the binary signal for blocking the zero sequence SOTF overcurrent protection; [SOTF.Opt_Mode] is the setting for selecting the acceleration mode of the SOTF protection; tEnSOTF is the setting [SOTF.t_En], the enabling time setting of the SOTF protection; [79.Ready] is used to denote the auto-recloser is ready for operating; [79.Close_3PSx] (x:1~4) means that the auto-recloser operates; SOTF.ManClsCB denotes the circuit breaker is closed manually (local or remote), for example, the circuit breaker is closed by the remote closing command from the SAS or SCADA, or by pressing the closing button on the control panel.

PCS-9611 Feeder Relay Date: 2011-08-29

3-35

3 Operation Theory

3.10.2 SOTF Protection Settings


All the settings of the SOTF protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 4 5 6 7 8 9 10 Menu text SOTF.t_En SOTF.Opt_Mode 50PSOTF.I_Set 50PSOTF.t_Op 50PSOTF.En 50PSOTF.OutMap 50GSOTF.3I0_Set 50GSOTF.t_Op 50GSOTF.En 50GSOTF.OutMap Explanation The enabling time setting of the SOTF protection The setting for selecting the acceleration tripping mode of the SOTF protection The current setting of the SOTF overcurrent protection The time setting of the SOTF overcurrent protection The logic setting of the SOTF overcurrent protection The output matrix setting of the SOTF overcurrent protection The current setting of the zero sequence SOTF overcurrent protection The time setting of the zero sequence SOTF overcurrent protection The logic setting of the zero sequence SOTF overcurrent protection The output matrix setting of the zero sequence SOTF overcurrent protection Range 0~100s 0~1 0.05In~30In 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF Step 0.001s 1 0.001A 0.001s 1 1 0.001A 0.001s 1 1

3.11 Cold Load Pickup Logic


3.11.1 Cold Load Pickup Logic Theory
The cold load pickup (CLP) logic which is included within this relay serves to either inhibit the selected protective elements for an appointed duration, or to raise the settings of the selected protective elements. Therefore, it allows the protection settings to be set closer to the load profile by automatically increasing them following circuit energization. The CLP logic thus provides stability, whilst maintaining protection during starting. The CLP function acts upon the overcurrent protection and the No.1 group of zero sequence overcurrent protection. The output signal of the CLP logic also can be used as a blocking signal for a selected protective element through the PCS-PC configuration tool software. The logic diagram of the cold load pickup function is shown in Figure 3.11-1. The cold load pickup logic operates when the circuit breaker remains open for a time greater than [CLP.t_Cold] and is subsequently closed. The CLP operation is applied after [CLP.t_Cold] and remains for a time delay [CLP.t_Rst] after the circuit breaker is closed. The status of the circuit breaker is provided either by means of the load current ([CLP.LogicMode] = 1) or by means of the
3-36
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

CB auxiliary contact ([CLP.LogicMode] = 2). The signal [CLP.OnLoad] can be gotten from the signal Prot.OnLoad through the PCS-PC. If the CLP output CLP.St is 1, the CLP settings are enabled for the overcurrent protection and the No.1 group of zero sequence overcurrent protection respectively. After the delay [CLP.t_Rst] has elapsed, the normal protection settings are applied. And if a fast resetting signal is received, the normal protection settings are applied after the delay [CLP.t_ShortRst].
[CLP.OnLoad] [CLP.Opt_LogicMode] = 1 [BI_52b] [CLP.Opt_LogicMode] = 2

&
tCold 0

&
tRst 0

S R

Q Q

[CLP.ShortRst] [CLP.St_50/51] [CLP.Init] [CLP.En] [CLP.Blk]

&

tShortRst

& &
[CLP.St]

Figure 3.11-1 Logic diagram of the cold load pickup function

Where: [CLP.OnLoad] is the signal denotes anyone of the phase currents is greater than 0.04In; [CLP.LogicMode] is used for selecting the cold load condition mode; [BI_52b] is the binary input for inputting the normal close contact of the circuit breaker; [CLP.ShortRst] is the binary signal of the short resetting function; [CLP.St_50/51] is the binary signal which denotes anyone of the selected protective elements picked up; [CLP.Init] is the binary signal for initiating the cold load pickup logic function (for example, a binary input signal from other relevant relay); [CLP.En] is the logic setting of the cold load pickup logic function; [CLP.Blk] is the binary signal for blocking the cold load pickup logic function; tCold is the setting [CLP.t_Cold], the time setting for ensuring the cold load condition is met; tRst is the setting [CLP.t_Rst], the time setting for resetting the cold load pickup logic function; tShortRst is the setting [CLP.t_ShortRst], the time setting for fast resetting the cold load pickup logic function.

3.11.2 Cold Load Pickup Logic Settings


All the settings of the cold load pickup logic are listed in the following table. For the information
PCS-9611 Feeder Relay Date: 2011-08-29

3-37

3 Operation Theory

about the common explanation of the settings, see Section 7.3.


No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Menu text CLP.Opt_LogicMode CLP.t_Cold CLP.t_Rst CLP.t_ShortRst CLP.En 50/51P1.CLP.IMult 50/51P1.CLP.t_Op 50/51P2.CLP.IMult 50/51P2.CLP.t_Op 50/51P3.CLP.IMult 50/51P3.CLP.t_Op 50/51P4.CLP.IMult 50/51P4.CLP.t_Op 50/51P4.CLP.TMS 50/51G1.CLP.IMult 50/51G1.CLP.t_Op 50/51G2.CLP.IMult 50/51G2.CLP.t_Op 50/51G3.CLP.IMult 50/51G3.CLP.t_Op 50/51G4.CLP.IMult Explanation The setting for selecting the cold load condition The time setting for ensuring the cold load condition is met The time setting for resetting the cold load pickup logic The time setting for fast resetting the cold load pickup logic The logic setting of the cold load pickup logic function The multiple setting of the stage 1 overcurrent protection when CLP is active The time setting of the stage 1 overcurrent protection when CLP is active The multiple setting of the stage 2 overcurrent protection when CLP is active The time setting of the stage 2 overcurrent protection when CLP is active The multiple setting of the stage 3 overcurrent protection when CLP is active The time setting of the stage 3 overcurrent protection when CLP is active The multiple setting of the stage 4 overcurrent protection when CLP is active The time setting of the stage 4 overcurrent protection when CLP is active The time multiplier setting of the IDMT overcurrent protection when CLP is active The multiple setting of the stage 1 zero sequence overcurrent protection when CLP is active The time setting of the stage 1 zero sequence overcurrent protection when CLP is active The multiple setting of the stage 2 zero sequence overcurrent protection when CLP is active The time setting of the stage 2 zero sequence overcurrent protection when CLP is active The multiple setting of the stage 3 zero sequence overcurrent protection when CLP is active The time setting of the stage 3 zero sequence overcurrent protection when CLP is active The multiple setting of the stage 4 zero sequence overcurrent protection when CLP is active 1~2 0~4000s 0~4000s 0~600s 0~1 1.00~10.00 0~100s 1.00~10.00 0~100s 1.00~10.00 0~100s 1.00~10.00 0~100s 0.05~100.0 1.00~10.00 0~100s 1.00~10.00 0~100s 1.00~10.00 0~100s 1.00~10.00 Range 1 0.001s 0.001s 0.001s 1 0.001 0.001s 0.001 0.001s 0.001 0.001s 0.001 0.001s 0.001 0.001 0.001s 0.001 0.001s 0.001 0.001s 0.001 Step

3-38
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory 22 23 50/51G4.CLP.t_Op 50/51G1.CLP.TMS The time setting of the stage 4 zero sequence overcurrent protection when CLP is active The time multiplier setting of the zero sequence IDMT overcurrent protection when CLP is active 0~100s 0.05~100.0 0.001s 0.001

3.12 Undervoltage Protection


3.12.1 Undervoltage Protection Theory
This relay provides a two-stage undervoltage protection with definite time delay characteristics. The two stages have same protection logics. Each stage can be used for tripping or alarming through the PCS-PC and the default is for tripping. This protection can support all kinds of VT connection: three phase voltage (Ua, Ub, Uc), three phase-to-phase voltages (Uab, Ubc, Uca), two phase-to-phase voltages (Uab, Ubc), anyone of three phase voltages or anyone of three phase-to-phase voltages. Two methods are used to check the undervoltage condition by the setting [27P.Opt_1P/3P]. If setting [27P.Opt_1P/3P] is set as 0, and all of the three voltage values are less than the voltage setting, the undervoltage protection will operates after the appointed time delay; and if the setting [27P.Opt_1P/3P] is set as 1, and anyone of the three voltage values is less than the voltage setting, the undervoltage protection will operates after the appointed time delay. The setting [27P.Opt_Up/Upp] is used to decide the voltage input mode. If it is set as 1, the input voltage is phase-to-phase voltage; and if it is set as 0, the input voltage is phase voltage. So the voltage setting must be set in accordance with the setting [27P.Opt_Up/Upp]; i.e. if the setting [27P.Opt_Up/Upp] is set as 1, the voltage setting is set according to phase-to-phase voltage; and if the setting [27P.Opt_Up/Upp] is set as 0, the voltage setting is set according to phase voltage. The circuit breaker state (based on the binary input [BI_52b]) is taken into account in the undervoltage protection logic; when the circuit breaker is opened ([BI_52b] = 1), the undervoltage protection is not in service. If the system voltage is lost, the undervoltage protection is blocked. The criterion of the system voltage lost detects that all the three phase voltages are less than 15V, and the load current can be taken into account according to the application demands through [27P1.OnLoad] which denotes whether there has load current (anyone of the three phase currents is greater than 0.04In). The signal [27P1.OnLoad] can be gotten from the signal Prot.OnLoad through the PCS-PC.

Figure 3.12-1 Logic diagram of the system lost voltage for the UV1 protection

The following figure shows the logic diagram of the stage 1 undervoltage protection.

PCS-9611 Feeder Relay Date: 2011-08-29

3-39

3 Operation Theory

Figure 3.12-2 Logic diagram of the stage 1 undervoltage protection

Where: [27P1.U_Set] is the voltage setting of the stage 1 undervoltage protection; tUV1 is the setting [27P1.t_Op], the time setting of the stage 1 undervoltage protection; [27P.Opt_1P/3P] is the logic setting for selecting the undervoltage calculation method; [27P.Opt_Up/Upp] is the logic setting for deciding the voltage input mode; [27P1.En] is the logic setting of the stage 1 undervoltage protection; [27P1.En1] is the binary signal for enabling the stage 1 undervoltage protection; [27P1.Blk] is the binary signal for blocking the stage 1 undervoltage protection; [BI_52b] is the binary input from the auxiliary normal close contact of the circuit breaker; 27P1.LostVolt denotes whether the system voltage is lost.

3.12.2 Undervoltage Protection Settings


All the settings of the undervoltage protections are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 Menu text 27P.Opt_1P/3P 27P.Opt_Up/Upp 27P1.U_Set The setting for Explanation selecting the undervoltage protection calculation method The setting for selecting the voltage input mode for the undervoltage protection The voltage setting of the stage 1 undervoltage protection 0~1 0~1 2~120V Range 1 1 0.001V Step

3-40
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory 4 5 6 7 8 9 10 11 12 27P1.t_Op 27P1.K_DropOut 27P1.En 27P1.OutMap 27P2.U_Set 27P2.t_Op 27P2.K_DropOut 27P2.En 27P2.OutMap The time setting of the stage 1 undervoltage protection The dropout coefficient setting of the stage 1 undervoltage protection The logic setting of the stage 1 undervoltage protection The output matrix setting of the stage 1 undervoltage protection The voltage setting of the stage 2 undervoltage protection The time setting of the stage 2 undervoltage protection The dropout coefficient setting of the stage 2 undervoltage protection The logic setting of the stage 2 undervoltage protection The output matrix setting of the stage 2 undervoltage protection 0~100s 1.03~3.0 0~1 0x00000000 ~ 0x7FFFFFFF 2~120V 0~100s 1.03~3.0 0~1 0x00000000 ~ 0x7FFFFFFF 0.001s 0.001 1 1 0.001V 0.001s 0.001 1 1

If the voltage is greater than [27Px.U_Set][27Px.K_DropOut] (x: 1~2), the corresponding undervoltage protection will drop out. The dropout coefficient [27Px.K_DropOut] (x: 1~2) for setting the dropout value of the corresponding undervoltage protection, and its typical value is 1.03.

3.13 Overvoltage Protection


3.13.1 Overvoltage Protection Theory
This relay provides a two-stage overvoltage protection with definite time delay characteristics. The two stages have same protection logics. Each stage can be used for tripping or alarming through the PCS-PC and the default is for tripping. This protection can support all kinds of VT connection: three phase voltage (Ua, Ub, Uc), three phase-to-phase voltages (Uab, Ubc, Uca), two phase-to-phase voltages (Uab, Ubc), anyone of three phase voltages or anyone of three phase-to-phase voltages. Two methods are used to check the overvoltage condition by the setting [59P.Opt_1P/3P]. If setting [59P.Opt_1P/3P] is set as 0, and all of the three voltage values are greater than the voltage setting, the overvoltage protection will operates after the appointed time delay; and if the setting [59P.Opt_1P/3P] is set as 1, and anyone of the three voltage values is greater than the voltage setting, the overvoltage protection will operates after the appointed time delay. The setting [59P.Opt_Up/Upp] is used to decide the voltage input mode. If it is set as 1, the input voltage is phase-to-phase voltage; and if it is set as 0, the input voltage is phase voltage. So the voltage setting must be set in accordance with the setting [59P.Opt_Up/Upp]; i.e. if the setting [59P.Opt_Up/Upp] is set as 1, the voltage setting is set according to phase-to-phase voltage; and if the setting [59P.Opt_Up/Upp] is set as 0, the voltage setting is set according to phase voltage.
PCS-9611 Feeder Relay Date: 2011-08-29

3-41

3 Operation Theory

The following figure shows the logic diagram of the stage 1 overvoltage protection.

Figure 3.13-1 Logic diagram of the stage 1 overvoltage protection

Where: [59P1.U_Set] is the voltage setting of the stage 1 overvoltage protection; tOV1 is the setting [59P1.t_Op], the time setting of the stage 1 overvoltage protection; [59P.Opt_1P/3P] is the logic setting for selecting the overvoltage calculation method; [59P.Opt_Up/Upp] is the logic setting for deciding the voltage input mode; [59P1.En] is the logic setting of the stage 1 overvoltage protection; [59P1.En1] is the binary signal for enabling the stage 1 overvoltage protection; [59P1.Blk] is the binary signal for blocking the stage 1 overvoltage protection.

3.13.2 Overvoltage Protection Settings


All the settings of the overvoltage and undervoltage protections are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 4 5 Menu text 59P.Opt_1P/3P 59P.Opt_Up/Upp 59P1.U_Set 59P1.t_Op 59P1.K_DropOut The setting for Explanation selecting the overvoltage protection calculation method The setting for selecting the voltage input mode for the overvoltage protection The voltage setting of the stage 1 overvoltage protection The time setting of the stage 1 overvoltage protection The dropout coefficient setting of the stage 1 overvoltage protection 0~1 0~1 57.7~200V 0~100s 0.93~0.97 Range 1 1 0.001V 0.001s 0.001 Step

3-42
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory 6 7 8 9 10 11 12 59P1.En 59P1.OutMap 59P2.U_Set 59P2.t_Op 59P2.K_DropOut 59P2.En 59P2.OutMap The logic setting of the stage 1 overvoltage protection The output matrix setting of the stage 1 overvoltage protection The voltage setting of the stage 2 overvoltage protection The time setting of the stage 2 overvoltage protection The dropout coefficient setting of the stage 2 overvoltage protection The logic setting of the stage 2 overvoltage protection The output matrix setting of the stage 2 overvoltage protection 0~1 0x00000000 ~ 0x7FFFFFFF 57.7~200V 0~100s 0.93~0.97 0~1 0x00000000 ~ 0x7FFFFFFF 1 1 0.001V 0.001s 0.001 1 1

If the voltage is less than [59Px.U_Set][59Px.K_DropOut] (x: 1~2), the corresponding overvoltage protection will drop out. The dropout coefficient [59Px.K_DropOut] (x: 1~2) for setting the dropout value of the corresponding overvoltage protection, and its typical value is 0.97.

3.14 Zero Sequence Overvoltage Protection


3.14.1 Zero Sequence Overvoltage Protection Theory
On a healthy three-phase power system, the addition of each of the three-phase to earth voltages is nominally zero. However, when an earth fault occurs on the primary system, the balance is upset and a residual voltage is produced. Hence, a zero sequence overvoltage protection can be used to offer earth fault protection on such a system. The residual voltage could be measured at the secondary terminals of a voltage transformer having a broken delta secondary connection, or it can be calculated from the three phase voltages; which is decided by the setting [Opt_3U0]. This relay provides a two-stage zero sequence overvoltage protection with definite time delay characteristics. The two stages have same protection logics. The following figure shows the logic diagram of the stage 1 zero sequence overvoltage protection.

Figure 3.14-1 Logic diagram of the stage 1 ROV protection

Where: [59G1.3U0_Set] is the voltage setting of the stage 1 zero sequence overvoltage protection;

PCS-9611 Feeder Relay Date: 2011-08-29

3-43

3 Operation Theory

tROV1 is the setting [59G1.t_Op], the time setting of the stage 1 zero sequence overvoltage protection; [59G1.En] is logic setting of the stage 1 zero sequence overvoltage protection. [59G1.En1] is the binary signal for enabling the stage 1 zero sequence overvoltage protection; [59G1.Blk] is the binary signal for blocking the stage 1 zero sequence overvoltage protection.

3.14.2 Zero Sequence Overvoltage Protection Settings


All the settings of the zero sequence overvoltage protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 4 5 6 7 8 Menu text 59G1.3U0_Set 59G1.t_Op 59G1.En 59G1.OutMap 59G2.3U0_Set 59G2.t_Op 59G2.En 59G2.OutMap Explanation The voltage setting of the stage 1 zero sequence overvoltage protection The time setting of the stage 1 zero sequence overvoltage protection The logic setting of the stage 1 zero sequence overvoltage protection The output matrix setting of the stage 1 zero sequence overvoltage protection The voltage setting of the stage 2 zero sequence overvoltage protection The time setting of the stage 2 zero sequence overvoltage protection The logic setting of the stage 2 zero sequence overvoltage protection The output matrix setting of the stage 2 zero sequence overvoltage protection Range 2~160V 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 2~160V 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF Step 0.001V 0.001s 1 1 0.001V 0.001s 1 1

3.15 Negative Sequence Overvoltage Protection


3.15.1 Negative Sequence Overvoltage Protection Theory
On a healthy three-phase power system, the negative sequence voltage is nominally zero. However, when an unbalance situation occurs on the primary system, the negative sequence voltage is produced. This relay provides a one-stage negative sequence overvoltage protection with definite time delay characteristic. The negative sequence voltage is self-calculated. The following figure shows the logic diagram of the negative sequence overvoltage protection.

3-44
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

Figure 3.15-1 Logic diagram of the NOV protection

Where: [59Q.U2_Set] is the voltage setting of the negative sequence overvoltage protection; tNOV is the setting [59Q.t_Op], the time setting of the negative sequence overvoltage protection; [59Q.En] is logic setting of the negative sequence overvoltage protection. [59Q.En1] is the binary signal for enabling the negative sequence overvoltage protection; [59Q.Blk] is the binary signal for blocking the negative sequence overvoltage protection.

3.15.2 Negative Sequence Overvoltage Protection Settings


All the settings of the negative sequence overvoltage protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 4 Menu text 59Q.U2_Set 59Q.t_Op 59Q.En 59Q.OutMap Explanation The voltage setting of the negative sequence overvoltage protection The time setting of the negative sequence overvoltage protection The logic setting of the negative sequence overvoltage protection The output matrix setting of the negative sequence overvoltage protection Range 2~120V 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF Step 0.001V 0.001s 1 1

3.16 Frequency Protection


The frequency protection detects abnormally high and low frequencies in the power system or in electrical machines. If the frequency is out of the allowable range, the appropriate actions are initiated, such as load shedding or separating a generator from the system. A decrease in system frequency occurs when the system experiences an increase in the real power demand, or when a malfunction occurs with a generator governor or automatic generation control (AGC) system. The frequency protection function is also used for generators, which (for a certain time) operate to an island network. This is due to the fact that the reverse power protection cannot operate in case of a drive power failure. The generator can be disconnected from the power system using the frequency decrease protection. An increase in system frequency occurs, e.g. when large blocks of load (island network) are
PCS-9611 Feeder Relay Date: 2011-08-29

3-45

3 Operation Theory

removed from the system, or again when a malfunction occurs with a generator governor. This entails risk of self-excitation for generators feeding long lines under no-load conditions.

3.16.1 Under-frequency Protection


The feeder relay includes under-frequency protection to facilitate load shedding and subsequent restoration. It provides a four-stage under-frequency protection with independent definite time delay characteristics in this relay, and the four stages have same protection logics. This protection can be enabled after 100ms only when the frequency is greater than the frequency setting [81Ux.f_Set] (x: 1~4) and three phase-to-phase voltages are greater than the setting [81.Upp_VCE]. Meanwhile, this protection will be blocked when the system frequency is less than 35.00Hz or greater than 70.00Hz and this situation keeps for longer than 200ms. The logic diagram of the stage 1 under-frequency protection is shown as below.

Figure 3.16-1 Logic diagram of the stage 1 under-frequency protection

Where: [81U1.f_Set] is the frequency setting of the stage 1 under-frequency protection; tUF1 is the setting [81U1.t_Op], the time setting of the stage 1 under-frequency protection; [81.Upp_VCE] is the under voltage blocking setting of the frequency protection; [81U1.En] is the logic setting of the stage 1 under-frequency protection; [81U1.En1] is the binary signal for enabling the stage 1 under-frequency protection; [81U1.Blk] is the binary signal for blocking the stage 1 under-frequency protection.

3.16.2 Over-frequency Protection


The feeder relay provides a two-stage over-frequency protection with independent definite time delay characteristics, and the two stages have same protection logics. This protection can be enabled after 100ms only when the frequency is less than the frequency setting [81Ox.f_Set] (x: 1~4) and three phase-to-phase voltages are greater than the setting [81.Upp_VCE]. Meanwhile, this protection will be blocked when the power frequency is less than 35.00Hz or greater than 70.00Hz and this situation keeps for longer than 200ms. The logic diagram of the stage 1 over-frequency protection is shown as below.

3-46
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

Figure 3.16-2 Logic diagram of the stage 1 over-frequency protection

Where: [81O1.f_Set] is the frequency setting of the stage 1 over-frequency protection; tOF1 is the setting [81O1.t_Op], the time setting of the stage 1 over-frequency protection; [81.Upp_VCE] is the under voltage blocking setting of the frequency protection; [81O1.En] is the logic setting of the stage 1 over-frequency protection; [81O1.En1] is the binary signal for enabling the stage 1 over-frequency protection; [81O1.Blk] is the binary signal for blocking the stage 1 over-frequency protection.

3.16.3 Frequency Rate-of-change Protection


This relay provides a four-stage rate-of-change of frequency protection with independent definite time delay characteristic, and the four stages have same protection logics. Depending upon whether the rate-of-change of frequency threshold is set above or below zero, each stage can respond to either rising or falling rate-of-change of frequency conditions: if the setting [81Rx.df/dt_Set] (x: 1~4) is less than zero, the corresponding rate-of-change of frequency protection is used as falling rate-of-change of frequency protection; and if the setting [81Rx.df/dt_Set] (x: 1~4) is greater than zero, the corresponding rate-of-change of frequency protection is used as rising rate-of-change of frequency protection. The logic diagram of the stage 1 frequency rate-of-change protection is shown as below.

Figure 3.16-3 Logic diagram of the stage 1 frequency rate-of-change protection

Where: [81R1.df/dt_Set] is the setting of the stage 1 frequency rate-of-change protection;


PCS-9611 Feeder Relay Date: 2011-08-29

3-47

3 Operation Theory

tFRCP1 is the setting [81R1.t_Op], the time setting of the stage 1 frequency rate-of-change protection; [81R1.f_Pkp] is the pickup frequency setting of the stage 1 frequency rate-of-change protection; [81R1.En] is the logic setting of the stage 1 frequency rate-of-change protection; [81R1.En1] is the binary signal for enabling the stage 1 frequency rate-of-change protection; [81R1.Blk] is the binary signal for blocking the stage 1 frequency rate-of-change protection. The calculation of the rate-of-change of frequency is based on the voltage sampled values. How many cycles of the voltage sampled values are adopted for the calculation of the rate-of-change of frequency is decided by the setting [81R.dt_Set] (range: 3 ~ 8). For example, if the setting [81R.dt_Set] is set as 4, it means that the 4 cycles of the voltage sampled values are adopted for the calculation of the rate-of-change of frequency.

3.16.4 Frequency Protection Settings


All the settings of the frequency protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 4 5 6 7 8 9 10 11 12 Menu text 81.Upp_VCE 81U1.f_Set 81U1.t_Op 81U1.En 81U1.OutMap 81U2.f_Set 81U2.t_Op 81U2.En 81U2.OutMap 81U3.f_Set 81U3.t_Op 81U3.En Explanation The setting of the low voltage blocking element of the frequency protection (phase-to-phase voltage) The frequency setting of the stage 1 under-frequency protection The time setting of the stage 1 under-frequency protection The logic setting of the stage 1 under-frequency protection The output matrix setting of the stage 1 under-frequency protection The frequency setting of the stage 2 under-frequency protection The time setting of the stage 2 under-frequency protection The logic setting of the stage 2 under-frequency protection The output matrix setting of the stage 2 under-frequency protection The frequency setting of the stage 3 under-frequency protection The time setting of the stage 3 under-frequency protection The logic setting of the stage 3 under-frequency protection Range 10~120V 45~60Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 45~60Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 45~60Hz 0~100s 0~1 Step 0.001V 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1

3-48
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 81U3.OutMap 81U4.f_Set 81U4.t_Op 81U4.En 81U4.OutMap 81O1.f_Set 81O1.t_Op 81O1.En 81O1.OutMap 81O2.f_Set 81O2.t_Op 81O2.En 81O2.OutMap 81O3.f_Set 81O3.t_Op 81O3.En 81O3.OutMap 81O4.f_Set 81O4.t_Op 81O4.En 81O4.OutMap 81R.dt_Set The output matrix setting of the stage 3 under-frequency protection The frequency setting of the stage 4 under-frequency protection The time setting of the stage 4 under-frequency protection The logic setting of the stage 4 under-frequency protection The output matrix setting of the stage 4 under-frequency protection The frequency setting of the stage 1 over-frequency protection The time setting of the stage 1 over-frequency protection The logic setting of the stage 1 over-frequency protection The output matrix setting of the stage 1 over-frequency protection The frequency setting of the stage 2 over-frequency protection The time setting of the stage 2 over-frequency protection The logic setting of the stage 2 over-frequency protection The output matrix setting of the stage 2 over-frequency protection The frequency setting of the stage 3 over-frequency protection The time setting of the stage 3 over-frequency protection The logic setting of the stage 3 over-frequency protection The output matrix setting of the stage 3 over-frequency protection The frequency setting of the stage 4 over-frequency protection The time setting of the stage 4 over-frequency protection The logic setting of the stage 4 over-frequency protection The output matrix setting of the stage 4 over-frequency protection The cycle number for the calculation of the frequency rate-of-change protection 0x00000000 ~ 0x7FFFFFFF 45~60Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 50~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 50~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 50~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 50~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 3~8 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 1

PCS-9611 Feeder Relay Date: 2011-08-29

3-49

3 Operation Theory 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 81R1.df/dt_Set 81R1.f_Pkp 81R1.t_Op 81R1.En 81R1.OutMap 81R2.df/dt_Set 81R2.f_Pkp 81R2.t_Op 81R2.En 81R2.OutMap 81R3.df/dt_Set 81R3.f_Pkp 81R3.t_Op 81R3.En 81R3.OutMap 81R4.df/dt_Set 81R4.f_Pkp 81R4.t_Op 81R4.En 81R4.OutMap The setting of the stage 1 frequency -10~10Hz/s 45~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF stage 2 frequency -10~10Hz/s 45~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF stage 3 frequency -10~10Hz/s 45~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF stage 4 frequency -10~10Hz/s 45~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0.001 Hz/s 0.001Hz 0.001s 1 1 0.001 Hz/s 0.001Hz 0.001s 1 1 0.001 Hz/s 0.001Hz 0.001s 1 1 0.001 Hz/s 0.001Hz 0.001s 1 1

rate-of-change protection The pickup frequency setting of the stage 1 frequency rate-of-change protection The time setting of the stage 1 frequency rate-of-change protection The logic setting of the stage 1 frequency rate-of-change protection The output matrix setting of the stage 1 frequency rate-of-change protection The setting of the rate-of-change protection The pickup frequency setting of the stage 2 frequency rate-of-change protection The time setting of the stage 2 frequency rate-of-change protection The logic setting of the stage 2 frequency rate-of-change protection The output matrix setting of the stage 2 frequency rate-of-change protection The setting of the rate-of-change protection The pickup frequency setting of the stage 3 frequency rate-of-change protection The time setting of the stage 3 frequency rate-of-change protection The logic setting of the stage 3 frequency rate-of-change protection The output matrix setting of the stage 3 frequency rate-of-change protection The setting of the rate-of-change protection The pickup frequency setting of the stage 4 frequency rate-of-change protection The time setting of the stage 4 frequency rate-of-change protection The logic setting of the stage 4 frequency rate-of-change protection The output matrix setting of the stage 4 frequency rate-of-change protection

3-50
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory

3.17 Auto-recloser
3.17.1 Auto-recloser Theory
This relay can support up to 4-shot auto-recloser. This relay will initiate the auto-recloser for fault clearance by the phase overcurrent protection, the earth fault protection etc. (which can be configured through PCS-PC). An auto-reclosing cycle can be internally initiated by operation of a protection element or externally by a separate protection device, provided the circuit breaker (CB) is closed until the instant of protection operation. At the end of the dead time of each shot, if all the auto-reclosing conditions are satisfied, a circuit breaker close signal is given. The auto-reclosing output time pulse width is configurable through the setting [79.t_DDO_AR]. The system conditions to be met for closing are that the system voltages are in synchronism or dead line/live busbar or live line/dead busbar conditions exist, indicated by the internal check synchronism element and that the circuit breaker closing spring, or other energy source, is fully charged indicated from the binary input [BI_LowPres_Cls]. The CB close signal is cut-off when the circuit breaker is closed. If the CB position check function is enabled (the setting [79.En_FailChk] is set as 1), the auto-recloser detects the CB position in the period [79.t_Fail] after the auto-reclosing command is issued. If the CB closed position condition is not met in the period [79.t_Fail], the auto-recloser can not operate successfully, and the signal [79.Fail] will be issued. When the auto-reclosing command is issued, the reclaim timer starts. If the circuit breaker does not trip again, the auto-recloser resets at the end of the reclaim time. If the protection operates during the reclaim time delay [79.t_Reclaim], this relay either advances to the next shot in the programmed auto-reclosing cycle, or it goes to lockout if all programmed reclose attempts have been made. The reclaim time should be set long enough to allow this relay to operate when the circuit breaker is automatically closed onto a fault. If any blocking condition is met in the process of the auto-recloser, the auto-recloser will be blocked at once. And if any shot of the auto-recloser can not operate successfully, the signal [79.Fail] will be issued. Single-shot Reclosing When a trip signal is programmed to initiate the automatic reclosing system, the appropriate automatic reclosing program will be executed. Once the circuit breaker has opened, a dead time interval in accordance with the type of fault is started. Once the dead time interval has elapsed, a closing signal is issued to reclose the circuit breaker. If the fault is cleared, the reclaim time expires and the automatic reclosing is reset in anticipation of a future fault. The fault is cleared. If the fault is not cleared, then a final tripping signal is initiated by one or more protective elements. Multi-shot Reclosing

PCS-9611 Feeder Relay Date: 2011-08-29

3-51

3 Operation Theory

This relay permits up to 4 shots of reclosing. The shot number of reclosing can be set. The first reclose cycle is, in principle, the same as the single-shot auto-reclosing. If the first reclosing attempt is unsuccessful, this does not result in a final trip, but in a reset of the reclaim time interval and start of the next reclose cycle with the next dead time. This can be repeated until the shot number of reclosing has been reached. If one of the reclosing attempts is successful, i.e. the fault disappeared after reclosing, the reclaim time expires and the automatic reclosing system is reset. The fault is terminated. If none of the reclosing attempts is successful, then a final circuit breaker trip will take place after the last allowable reclosing attempt has been performed by the protection function. All reclosing attempts were unsuccessful. After the final circuit breaker trip, the automatic reclosing system is dynamically blocked. An example of a timing diagram for a successful second reclosing is shown as below.

Figure 3.17-1 Timing diagram for a successful second reclosing

An example of a timing diagram for an unsuccessful one-shot reclosing is shown as below.

Figure 3.17-2 Timing diagram for an unsuccessful one-shot reclosing 3-52


Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

The logic diagram of the auto-recloser is shown in Figure 3.17-3.


[79.En] [79.En1] [79.Ready] [79.Blk] 25A.Ok_SynChk [79.En_SynChk] 25A.Ok_DdChk [79.En_DdChk] [79.OnLoad] [79.Init]

[79.Inprog]

&

& & & & &


tAR1 0

[79.N_Rcls] = 1

[79.Close_3PS1]

tAR2

[79.N_Rcls] = 2

[79.Close_3PS2]

tAR3

[79.N_Rcls] = 3

[79.Close_3PS3]

tAR4

[79.N_Rcls] = 4

[79.Close_3PS4]

Figure 3.17-3 Logic diagram of the auto-recloser

Where: tARX (x: 1~4) is the setting [79.t_3PSx] (x: 1~4), the time setting of the auto-recloser; [79.En] is the logic setting of the auto-recloser; [79.N_Rcls] is the shot number of the auto-recloser; [79.Ready] denotes that the auto-recloser is ready for operation; [79.En1] is the binary signal for enabling the auto-recloser; [79.Blk] is the binary signal for blocking the auto-recloser; [79.En_SynChk] is the logic setting of the synchronism check mode of the auto-recloser; [79.En_DdChk] is the logic setting of the dead check mode of the auto-recloser; 25A.Ok_SynChk is the result of the synchronism check of the auto-recloser; 25A.Ok_DdChk is the result of the dead check of the auto-recloser; [79.OnLoad] denotes that anyone of the phase currents is greater than 0.04In, which can be gotten the signal Prot.OnLoad through the PCS-PC; [79.Init] is the auto-recloser initiation signal which can be configured through the PCS-PC.

3.17.2 Auto-recloser Ready Conditions


When the auto-recloser is enabled, and if all the following cases are ready in normal operation situation, the auto-recloser will be in service automatically after the predefined time setting.
PCS-9611 Feeder Relay Date: 2011-08-29

3-53

3 Operation Theory

1. 2.

The CB is closed manually (local or remote) and the CB normal close contact (BI_52b) is 0. Any protection element is not in startup status; i.e. the fault detector does not operate: when the CB is closed, if the fault detector is operated, it means that the CB is closed onto an abnormal system or a fault system. The blocking signal of the auto-recloser 79.Blk is 0; that is no blocking auto-recloser condition is met. The binary input of the operation circuit status of the CB (BI_LowPres_Cls) is 0; i.e. the CB is ready for reclosing.

3.

4.

If the auto-recloser is ready, there is a full charged battery sign on the right bottom of LCD. The logic diagram of the auto-recloser ready conditions is shown as below.
[BI_52b] [FD.Pkp] [BI_LowPres_Cls] [79.Blk] [79.En] [79.En1] tCBRdy 0 0 tPWBlk tCBCls 100ms

& & &


79.Ready

Figure 3.17-4 Logic diagram of the auto-recloser ready conditions

Where: [79.En] is the logic setting of the auto-recloser; [79.En1] is the binary signal for enabling the auto-recloser; [BI_52b] is the binary input for inputting the normal close contact of the circuit breaker; [FD.Pkp] means that the fault detector is operated; [BI_LowPres_Cls] is the binary input for inputting the CB closing low pressure signal; [79.Blk] is the binary signal for blocking the auto-recloser; tCBCls is the setting [79.t_CBClsd] of the minimum time delay for ensuring the CB is closed; tCBRdy is the setting [79.t_CBReady] of the time delay for ensuring the CB is ready; tPWBlk is the setting [79.t_DDO_BlkAR] of the pulse width for ensuring the AR blocking signal.

3.17.3 Auto-recloser Startup Condition


The startup condition of the auto-recloser is that anyone of the protective elements (for example, the overcurrent protection, zero sequence overcurrent protection etc.) which are configured for initiating the auto-recloser through the PCS-PC configuration tool auxiliary software has operated successfully. The auto-reclosing startup logic diagram is shown in Figure 3.17-3. To prevent the auto-reclosing
3-54
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

startup element from undesired operation, this relay takes the currents into account (the signal [79.OnLoad]). Only when the circuit breaker has tripped completely, the auto-recloser will be put into service.

3.17.4 Auto-recloser Check Mode


Three check modes are adopted in this relay: synchronism check mode, dead check mode and non-check mode. Each mode can be selected through a corresponding logic setting. Synchronism check mode The following conditions must be satisfied in the synchro check auto-reclosing function. 1. 2. 3. The protection voltage is greater than the setting [25.U_Lv]; The synchro-check voltage is greater than [25.U_Lv] / [25.U_Comp]; The voltage difference between the protection voltage and the synchro-check voltage (U = |UProt - USyn [25.U_Comp]|) is less than the setting [25A.U_Diff]; The frequency of protection voltage and the frequency of synchro-check voltage are in the range fn 5Hz (fn: the rated system frequency); The frequency difference between the protection voltage and the synchro-check voltage (f = |fProt - fSyn|) is less than the setting [25A.f_Diff]; The phase angle difference between the protection voltage and the synchro-check voltage ( = |Prot (Syn + [25.phi_Comp])|) is less than the setting [25A.phi_Diff].

4.

5.

6.

For the details about the settings [25.U_Comp] and [25.phi_Comp], see Section 7.4.1. If the above conditions are satisfied at the same time for longer than [25A.t_SynChk], the signal of the synchronism check of the auto-recloser 25A.Ok_SynChk is issued. When the reclosing operation is executed, this relay checks the synchronism check closing conditions in the period of the setting [25A.t_Wait]. If the synchro check closing conditions are satisfied, this relay will issue the reclosing command. The logic diagram of the synchronism check element for the auto-recloser is shown as below.

Figure 3.17-5 Logic diagram of the synchronism check element for AR

Where: UProt is the protection voltage value; USyn is the synchro-check voltage; U is the voltage difference of the protection voltage and the synchro-check voltage;
PCS-9611 Feeder Relay Date: 2011-08-29

3-55

3 Operation Theory

f is the frequency difference of the protection voltage and the synchro-check voltage; is the angle difference of the protection voltage and the synchro-check voltage; [25.U_Lv] is the voltage setting of the live voltage; [25A.U_Diff] is the voltage difference setting of the synchronism check function for the auto-recloser; [25A.f_Diff] is the frequency difference setting of the synchronism check function for the auto-recloser; [25A.phi_Diff] is the phase angle difference setting of the synchronism check function for the auto-recloser; tARSynChk is the setting [25A.t_SynChk], the time setting of the synchronism check function for the auto-recloser. Dead check mode In dead check mode case, the relay checks the protection voltage and synchro-check voltage. There are several kinds of dead check modes which are supported in this relay and the dead check mode can be selected according to the demands of a practical engineering by the setting [25A.Opt_DdChk]. The relationship between the setting [25A.Opt_DdChk] and the dead check mode is listed in following table.
[25A.Opt_DdChk] 1 2 3 4 5 6 7 Description of Dead Check Mode The protection voltage is dead, and the synchro-check voltage is dead. The protection voltage is dead, and the synchro-check voltage is live. The protection voltage is live, and the synchro-check voltage is dead. The protection voltage is dead, the synchro-check voltage is live or dead. The synchro-check voltage is dead, the protection voltage is live or dead. One of the two voltages is live, another one is dead. One of the two voltages is dead, another one is live or dead.

The logic diagram of the dead check element for the auto-recloser is shown as below.

Figure 3.17-6 Logic diagram of the dead check element for AR

Where: UProt is the protection voltage value;


3-56
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

USyn is the synchro-check voltage value; [25.U_Dd] the voltage setting for denoting whether the system is dead; [25.U_Lv] the voltage setting for denoting whether the system is live; tARDdChk is the setting [25A.t_DdChk], the time setting of the dead check function for the auto-recloser; [25A.Opt_DdChk] is the setting for selecting the dead check mode of the auto-recloser. Non-check mode In non-check mode case, the reclosing is permitted without taking the value, phase angle and frequency of the two voltages into account. After the reclosing delay time, this relay will issue a reclosing signal, if all the other reclosing conditions are ready. If the two settings [79.En_SynChk] and [79.En_DdChk] are set as 0, the non-check mode will be in service. If one of the two settings [79.En_SynChk] and [79.En_DdChk] is set as 1, the relevant reclosing check mode will be in service. If the two settings [79.En_SynChk] and [79.En_DdChk] are set as 1 together, the two reclosing check modes will be in service; and if anyone of the reclosing check modes is met, the corresponding check output is for the auto-reclosing.

3.17.5 Auto-recloser Blocking Logic


After the auto-recloser is put into service successfully, and if anyone of the following cases occurs at anytime in normal operation situation, the relay will block the auto-recloser automatically at once. 1. 2. 3. Open the circuit breaker by manual tripping. Open the circuit breaker by remote tripping. The VT failure occurs and it is detected by the relay ([VTS.Alm_SynVT] = 1 or [VTS.Alm] = 1), if the reclosing check mode is dead check mode. The blocking signal of the auto-recloser 79.Blk is 1; that is at least one of the blocking auto-recloser conditions is met. The blocking auto-recloser conditions can be configured for blocking the auto-recloser through the PCS-PC configuration tool auxiliary software The binary input of the closing operation circuit status of the CB (BI_LowPres_Cls) is 1; i.e. the CB is not ready for reclosing ([BI_LowPres_Cls] = 1). The last auto-reclosing command has been issued successfully.

4.

5.

6.

If the auto-recloser is blocked, there is an empty battery sign on the right bottom of LCD.

3.17.6 Auto-recloser Settings


All the settings of the auto-recloser are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.

PCS-9611 Feeder Relay Date: 2011-08-29

3-57

3 Operation Theory No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Menu text 79.t_CBClsd 79.t_DDO_BlkAR 79.t_CBReady 79.t_Fail 79.t_3PS1 79.t_3PS2 79.t_3PS3 79.t_3PS4 79.t_Reclaim 79.t_DDO_AR 79.N_Rcls 79.En_SynChk 79.En_DdChk 79.En_FailChk 79.En 79.OutMap Explanation The time setting of the minimum time delay for ensuring the CB is closed The time pulse width for ensuring the AR blocking signal The time setting of the time delay for ensuring the CB is ready The time setting of the time delay for checking the CB position The time setting of the 1st shot auto-recloser The time setting of the 2
nd rd th

Range 0.01~600s 0.01~600s 0.01~600s 0.01~600s 0~600s 0~600s 0~600s 0~600s 0~600s 0-4.00s 1~4 0~1 0~1 0~1 0~1 0x00000000 ~ 0x7FFFFFFF

Step 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 1 1 1 1 1 1

shot auto-recloser

The time setting of the 3 shot auto-recloser The time setting of the 4 shot auto-recloser The reclaim time setting of the auto-recloser The pulse width of the auto-recloser The shot number setting of the auto-recloser The logic setting of the synchronism check function of the auto-recloser The logic setting of the dead check function of the auto-recloser The logic setting of the CB position check function of the auto-recloser The logic setting of the auto-recloser The output matrix setting of the auto-recloser

The settings about the check function of the auto-recloser are listed in the following table. For the information about the common explanation of the settings, see Section 7.4.
No. 1 2 3 4 5 6 7 8 Menu text 25.U_Dd 25.U_Lv 25.U_Comp 25.phi_Comp 25.Opt_Usyn 25.t_ClsCB 25A.U_Diff 25A.f_Diff Explanation The voltage setting of the system dead check The voltage setting of the system live check The compensation coefficient setting of the synchro-check voltage The compensation phase angle setting of the synchro-check voltage The voltage type setting of the synchronism check closing function The circuit breaker closing time setting of the closing synchronism check function The voltage difference setting of the auto-closing synchronism check function The frequency difference setting of the auto-closing synchronism check function Range 2~120V 2~120V 0.2~5.0 0~360 0~5 0.02~1.00s 2~120V 0~2Hz Step 0.001V 0.001V 0.001 1 1 0.001s 0.001V 0.001Hz

3-58
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory 9 10 11 12 13 25A.phi_Diff 25A.t_Wait 25A.Opt_DdChk 25A.t_DdChk 25A.t_SynChk The phase angle difference setting of the auto-closing synchronism check function The waiting time setting of the auto-closing synchronism check function The setting for selecting the dead check mode of the auto-closing synchronism check function The time setting of the dead check function of the auto-closer The time setting of the synchronism check function of the auto-closer 0~60 0.01~60s 1~7 0.01~25s 0.01~25s 1 0.001s 1 0.001s 0.001s

3.18 Manual Closing Function


3.18.1 Manual Closing Theory
This relay supports manual closing function (local or remote closing). The manual closing can be initiated a local input signal (through a binary input or the control panel) or remote closing signal from a supervision and control system (SAS, SCADA). Three check modes described below can be selected for the manual closing function. The logic diagram of the manual closing function is shown as below.

Figure 3.18-1 Logic diagram of the manual closing function

Where: ManCls_Cmd is the manual closing command; 25M.Ok_SynChk is the result of the synchronism check of the manual closing function; 25M.Ok_DdChk is the result of the dead check of the manual closing function; 25M.BI_EnSynChk is the binary input for enabling the synchronism check mode, and it can be configured through the PCS-PC configuration tool auxiliary software; 25M.BI_EnDdChk is the binary input for enabling the dead check mode, and it can be configured through the PCS-PC configuration tool auxiliary software; [25M.En_SynChk] is the logic setting of the synchronism check of the manual closing; [25M.En_DdChk] is the logic setting of the dead check of the manual closing.

PCS-9611 Feeder Relay Date: 2011-08-29

3-59

3 Operation Theory

3.18.2 Check Mode for Manual Closing Function


This relay provides three check modes for the manual closing function (local or remote closing): synchronism check mode, dead check mode and non-check mode. Each mode can be selected through the relevant logic settings. Synchronism check mode The following conditions must be satisfied in the synchro check manual closing function. 1. 2. 3. The protection voltage is greater than the setting [25.U_Lv]; The synchro-check voltage is greater than [25.U_Lv] / [25.U_Comp]; The voltage difference between the protection voltage and the synchro-check voltage (U = |UProt - USyn [25.U_Comp]|) is less than the setting [25M.U_Diff]; The frequency of protection voltage and the frequency of synchro-check voltage are in the range fn 5Hz (fn: the rated system frequency); The frequency difference between the protection voltage and the synchro-check voltage (f = |fProt - fSyn|) is less than the setting [25M.f_Diff]; The rate-of-change of the frequency difference (df/dt) is less than the setting [25M.df/dt] to decrease the disturbance to the power system when the CB is closed; The phase angle difference between the protection voltage and the synchro-check voltage ( = |Prot (Syn + [25.phi_Comp])|) is less than the setting [25M.phi_Diff].

4.

5.

6.

7.

For the details about the settings [25.U_Comp] and [25.phi_Comp], see Section 7.4.1. If the above conditions are satisfied at the same time, the signal of the synchronism check of the manual closing 25M.Ok_SynChk is issued. When the manual closing operation is executed, this relay checks synchronism check closing conditions in the period of the setting [25M.t_Wait]. If the synchro check closing conditions are satisfied, this relay will issue the closing command. The logic diagram of the manual closing synchronism check element is shown as below.

Figure 3.18-2 Logic diagram of the synchronism check element for manual closing

Where: UProt is the protection voltage value; USyn is the synchro-check voltage value;
3-60
Date: 2011-08-29 PCS-9611 Feeder Relay

3 Operation Theory

U is the voltage difference of the protection voltage and the synchro-check voltage; f is the frequency difference of the protection voltage and the synchro-check voltage; df/dt is the rate-of-change of the frequency difference; is the angle difference of the protection voltage and the synchro-check voltage; [25.U_Lv] is the voltage setting of the live voltage; [25M.U_Diff] is the voltage difference setting of the synchronism check function for the manual closing; [25M.f_Diff] is the frequency difference setting of the synchronism check function for the manual closing; [25M.df/dt] is the frequency rate-of-change setting of the synchro check closing function for the manual closing; [25M.phi_Diff] is the phase angle difference setting of the synchronism check function for the manual closing. Dead check mode In dead check mode case, the relay checks the protection voltage and synchro-check voltage. There are several kinds of dead check modes which are supported in this relay and the dead check mode can be selected according to the demands of a practical engineering by the setting [25M.Opt_DdChk]. The relationship between the setting [25M.Opt_DdChk] and the dead check mode is listed in following table.
[25M.Opt_DdChk] 1 2 3 4 5 6 7 Description of Dead Check Mode The protection voltage is dead, and the synchro-check voltage is dead. The protection voltage is dead, and the synchro-check voltage is live. The protection voltage is live, and the synchro-check voltage is dead. The protection voltage is dead, the synchro-check voltage is live or dead. The synchro-check voltage is dead, the protection voltage is live or dead. One of the two voltages is live, another one is dead. One of the two voltages is dead, another one is live or dead.

The logic diagram of the manual closing dead check element is shown as below.

Figure 3.18-3 Logic diagram of the dead check element for manual closing

Where:

PCS-9611 Feeder Relay Date: 2011-08-29

3-61

3 Operation Theory

Ubus is the protection voltage value; Uline_comp is the synchro-check voltage value; [25.U_Dd] the voltage setting for denoting whether the system is dead; [25.U_Lv] the voltage setting for denoting whether the system is live; [25M.Opt_DdChk] is the setting for selecting the dead check mode of the manual closing. Non-check mode In non-check mode case, the manual closing is permitted without taking the value, phase angle and frequency of the two voltages into account. If all the other manual closing conditions are ready, this relay will issue a manual closing signal. If the two settings [25M.En_SynChk] and [25M.En_DdChk] are set as 0, the non-check mode will be in service. If one of the two settings [25M.En_SynChk] and [25M.En_DdChk] is set as 1, the relevant manual closing check mode will be in service. If the two settings [25M.En_SynChk] and [25M.En_DdChk] are set as 1 together, the two manual closing check modes will be in service; and if anyone of the manual closing check modes is met, the corresponding check output is for the manual closing.

3.18.3 Manual Closing Function Settings


All the settings of the closing synchronism check function are listed in the following table. For the information about the common explanation of the settings, see Section 7.4.
No. 1 2 3 4 5 6 7 8 9 10 11 Menu text 25.U_Dd 25.U_Lv 25.U_Comp 25.phi_Comp 25.Opt_Usyn 25.t_ClsCB 25M.U_Diff 25M.f_Diff 25M.df/dt 25M.phi_Diff 25M.t_Wait Explanation The voltage setting of the system dead check The voltage setting of the system live check The compensation coefficient setting of the synchro-check voltage The compensation phase angle setting of the synchro-check voltage The voltage type setting of the synchronism check closing function The circuit breaker closing time setting of the closing synchronism check function The voltage difference setting of the manual closing synchronism check function The frequency difference setting of the manual closing synchronism check function The frequency rate-of-change setting of the manual closing synchronism check function The phase angle difference setting of the manual closing synchronism check function The waiting time setting of the manual closing synchronism check function Range 2~120V 2~120V 0.2~5.0 0~360 0~5 0.02~1.00s 2~120V 0~2Hz 0~3Hz/s 0~60 0.01~60s Step 0.001V 0.001V 0.001 1 1 0.001s 0.001V 0.001Hz 0.001 Hz/s 1 0.001s

3-62
Date: 2011-08-29

PCS-9611 Feeder Relay

3 Operation Theory 12 13 14 25M.Opt_DdChk 25M.En_SynChk 25M.En_DdChk The setting for selecting the dead check mode of the manual closing function The logic setting of the synchronism check function of the manual closing function The logic setting of the dead check function of the manual closing function 1~7 0~1 0~1 1 1 1

3.19 Mechanical Protection


3.19.1 Mechanical Protection Theory
This relay can provide up to 4 programmable binary inputs for mechanical protection. If a binary input which is used as a mechanical protection input is energized, this relay will issue an operation signal after a predefined time delay. The following figure shows the logic diagram of the No.1 mechanical protection. Other mechanical protections have the same functional logic with the No.1 mechanical protection.

Figure 3.19-1 Logic diagram of the No.1 mechanical protection

Where: [MR1.Input] is the mechanical protection input signal which can be from a binary input; tMR1 is the setting [MR1.t_Op], the time setting of the No.1 mechanical protection; [MR1.En] is the logic setting of the No.1 mechanical protection; [MR1.En1] is the binary signal for enabling the No.1 mechanical protection; [MR1.Blk] is the binary signal for blocking the No.1 mechanical protection.

3.19.2 Mechanical Protection Settings


All the settings of the mechanical protection are listed in the following table. For the information about the common explanation of the settings, see Section 7.3.
No. 1 2 3 Menu text MR1.t_MR MR1.En MR1.OutMap The time protection The logic setting of the No.1 mechanical protection The output matrix setting of the No.1 mechanical protection Explanation setting of the No.1 mechanical Range 0~4000s 0~1 0x00000000 ~ 0x7FFFFFFF Step 0.001s 1 1

PCS-9611 Feeder Relay Date: 2011-08-29

3-63

3 Operation Theory 4 5 6 7 8 9 10 11 12 MR2.t_MR MR2.En MR2.OutMap MR3.t_MR MR3.En MR3.OutMap MR4.t_MR MR4.En MR4.OutMap The time setting of the No.2 mechanical 0~4000s 0~1 0x00000000 ~ 0x7FFFFFFF setting of the No.3 mechanical 0~4000s 0~1 0x00000000 ~ 0x7FFFFFFF setting of the No.4 mechanical 0~4000s 0~1 0x00000000 ~ 0x7FFFFFFF 0.001s 1 1 0.001s 1 1 0.001s 1 1

protection The logic setting of the No.2 mechanical protection The output matrix setting of the No.2 mechanical protection The time protection The logic setting of the No.3 mechanical protection The output matrix setting of the No.3 mechanical protection The time protection The logic setting of the No.4 mechanical protection The output matrix setting of the No.4 mechanical protection

3-64
Date: 2011-08-29

PCS-9611 Feeder Relay

4 Supervision

4 Supervision
Table of Contents
4.1 Overview ...........................................................................................................4-1 4.2 Supervision Functions.....................................................................................4-1
4.2.1 Device Hardware Supervision............................................................................................ 4-1 4.2.2 Board Configuration Error Supervision .............................................................................. 4-1 4.2.3 Setting Supervision ............................................................................................................ 4-1 4.2.4 Program Version Supervision ............................................................................................ 4-2 4.2.5 Tripped Position Contact Supervision ................................................................................ 4-2 4.2.6 Low Pressure Binary Input Supervision ............................................................................. 4-2 4.2.7 VT Circuit Supervision ....................................................................................................... 4-2 4.2.8 CT Circuit Supervision ....................................................................................................... 4-4 4.2.9 Thermal Overload Supervision .......................................................................................... 4-5 4.2.10 Time Synchronization Supervision................................................................................... 4-5 4.2.11 Auxiliary Communication Testing Supervision .................................................................. 4-5 4.2.12 Device Maintenance Supervision..................................................................................... 4-5 4.2.13 Reserved Programmable Alarm Supervision ................................................................... 4-5 4.2.14 Tripping Circuit Supervision ............................................................................................. 4-5

List of Figures
Figure 4.2-1 Logic diagram of the 52b contact supervision element ................................... 4-2 Figure 4.2-2 Logic diagram of the protection VTS element................................................... 4-3 Figure 4.2-3 Logic diagram of the synchro-check VTS element........................................... 4-4 Figure 4.2-4 Logic diagram of the CTS element..................................................................... 4-4 Figure 4.2-5 Principle of the TCS function with two binary inputs ....................................... 4-6

PCS-9611 Feeder Relay Date: 2011-08-29

4-a

4 Supervision

4-b
Date: 2011-08-29

PCS-9611 Feeder Relay

4 Supervision

4.1 Overview
Though the protection system is in non-operating state under normal conditions, it is waiting for a power system fault to occur at any time and must operate for the fault without fail. When the equipment is in energizing process before the LED HEALTHY is on, the equipment needs to be checked to ensure there are no errors. Therefore, the automatic supervision function, which checks the health of the protection system during startup and normal operation procedure, plays an important role. The numerical relay based on the microprocessor operations has the capability for implementing this automatic supervision function of the protection system. In case a fatal fault is detected during automatic supervision, the equipment will be blocked out. It means that this relay is out of service. Therefore you must re-energize the relay or even replace a module to make this relay back into service.

4.2 Supervision Functions


4.2.1 Device Hardware Supervision
The MCU, RAM, ROM chips in this relay are monitored continuously to ensure whether they are damaged or have some errors. If any one of them is detected damaged or having error, this relay will be blocked, the alarm signal [Fail_Device] will be issued, and the LED indicator HEALTHY will be off at the same time.

4.2.2 Board Configuration Error Supervision


If the board configuration of this relay does not comply with the program software of this relay, the alarm signals [Fail_Device] and [Fail_BoardConfig] will be issued, and the LED indicator HEALTHY will be off at the same time.

4.2.3 Setting Supervision


This relay has 10 setting groups, but only one is active at any time. The settings of active setting group are checked continuously. If anyone of the active settings is confirmed to be modified, this relay will be blocked, the alarm signals [Fail_Device] and [Fail_Setting] will be issued; meanwhile, if the modified setting is out of the appointed range, the alarm signal [Fail_Setting_OvRange] will be issued at the same time. The LED indicator HEALTHY will be off at the same time. If anyone of the items of the setting file is changed (the program of this relay is updated), the alarm signal [Fail_SettingItem_Chgd] will be issued. The LED indicator HEALTHY will be off at the same time. The items of the setting include the setting number, the setting name, the setting range, the setting step etc.

PCS-9611 Feeder Relay Date: 2011-08-29

4-1

4 Supervision

If the settings which are from the HMI module to the main CPU module are not in accordance with the current settings of the main CPU module, the alarm signal [Alm_Setting_MON] will be issued. The LED indicator ALARM will be on at the same time. If the setting group number which is indicated through the dedicated binary inputs is not in accordance with the current setting group number, the alarm signal [Alm_BI_SettingGrp] will be issued. The LED indicator ALARM will be on at the same time.

4.2.4 Program Version Supervision


If the relay detects that the current program version is not in accordance with the program version which is defined by the manufacturer, the alarm signal [Alm_Version] will be issued. The LED indicator ALARM will be on at the same time.

4.2.5 Tripped Position Contact Supervision


If the relay detects that the tripped auxiliary contact position is on (i.e., the value of [BI_52b] is 1.), meanwhile any phase current is greater than 0.04In, and such a condition keeps for longer than 10 seconds, the alarm signals [Alm_Device] and [Alm_52b] will be issued, and the LED indicator ALARM will be on at the same time. The logic diagram of the tripped position contact supervision function is shown as below.
Ia > 0.04In Ib > 0.04In Ic > 0.04In Prot.OnLoad [BI_52b]

Prot.OnLoad

&

10s

[Alm_52b]

Figure 4.2-1 Logic diagram of the 52b contact supervision element

4.2.6 Low Pressure Binary Input Supervision


This relay has two binary inputs [BI_LowPres_Cls] and [BI_LowPres_Trp] which are used to indicate the state of the circuit breaker mechanism. If the binary input [BI_LowPres_Cls] is energized for longer than 15s, this relay will issue the alarm signals [Alm_Device] and [Alm_LowPres_Cls]; and the LED indicator ALARM will be on at the same time. The auto-recloser and the first remote closing output functions are blocked. If the binary input [BI_LowPres_Trp] is energized for longer than 5s, this relay will issue the alarm signals [Alm_Device] and [Alm_LowPres_Trp] 5s later, and the LED indicator ALARM will be on at the same time. The first remote tripping output function is blocked.

4.2.7 VT Circuit Supervision


The voltage transformer supervision (VTS) feature is used to detect failure of the AC voltage input circuit of this relay. The VTS logic in the relay is designed to detect the voltage failure and automatically adjust the configuration of protective elements whose stability would otherwise be compromised. A time
4-2
Date: 2011-08-29 PCS-9611 Feeder Relay

4 Supervision

delay alarm output is also available. Protection VT supervision If this relay detects any one of the following two conditions is satisfied, it means that the protection VT is in abnormal status. (1) The negative phase sequence voltage is greater than 8V. (2) The positive phase sequence voltage is less than 30V, and any of the phase currents is greater than 0.04In. Then the alarm signals [Alm_Device] and [VTS.Alm] are issued 10s later, and the LED ALARM will be on at the same time. When the protection VT status returns to normal condition, the alarm will restore automatically 1.25s later. In case the protection VT circuit is failed, these protective elements dependent on voltage will be blocked. If the fast VT failure is detected, the internal signal VTS.InstAlm will be 1 without any time delay. In the fast VTS element, the phase current or the negative sequence current must be taken into account. The logic diagram of the protection VTS element is shown as below.

Figure 4.2-2 Logic diagram of the protection VTS element

Where: Prot.OnLoad is the signal for denoting the system is on load state; [VTS.En] is the logic setting of the protection VTS function; [VTS.I_Set] is the phase current setting of the protection VTS function; [VTS.I2_Set] is the negative sequence current setting of the protection VTS function; [Sig_MCB_VTS] is the VT supervision input from VTs miniature circuit breaker (MCB) auxiliary contact which shows the MCB whether is opened. Synchro-check VT supervision This function is used to supervise the synchro-check voltage transformer circuit. When the setting [VTS.En_SynVT] is set as 1, if the difference between the measured synchro-check voltage (Ux) and the setting [Syn.U2n] is greater than 15V for longer than 10s, the alarm

PCS-9611 Feeder Relay Date: 2011-08-29

4-3

4 Supervision

signals [Alm_Device] and [VTS.Alm_SynVT] will be issued, and the LED ALARM will be on at the same time. When the status of the synchro-check VT returns to normal condition, the alarm will restore automatically 1.25s later.
[79.En_SynChk] [79.En_DdChk] |Ux [Syn.U2n]| > 15V [VTS.En_SynVT]

&

10s

[VTS.Alm_SynVT]

Figure 4.2-3 Logic diagram of the synchro-check VTS element

Where: [VTS.En_SynVT] is the logic setting of the synchro-check VTS function; [79.En_SynChk] is the logic setting of the synchronism check mode of the auto-recloser; [79.En_DdChk] is the logic setting of the dead check mode of the auto-recloser.

4.2.8 CT Circuit Supervision


The main purpose of the current transformer supervision (CTS) function is to detect faults in the secondary circuits of the current transformer and avoid influence on the operation of relevant protection functions. This current transformer supervision (CTS) function will be in operation at any time, whether the general fault detection picks up or not. The criteria of the CTS element are: 1. 2. The calculated zero sequence current is greater than the setting [CTS.3I0_Set]; The calculated zero sequence voltage is less than the setting [CTS.3U0_Set].

If a CT circuit failure is detected, the alarm signals [Alm_Device] and [CTS.Alm] will be issued, and the LED indicator ALARM will be on at the same time. If the fast CT circuit failure is detected, the internal signal [CTS.InstAlm] will be 1 without any time delay. The logic diagram of the CTS element is shown as below.

Figure 4.2-4 Logic diagram of the CTS element

Where: [CTS.3I0_Set] is the threshold current setting of the CTS element; [CTS.3U0_Set] is the threshold voltage setting of the CTS element; [CTS.En] is the logic setting of the CTS element.
4-4
Date: 2011-08-29 PCS-9611 Feeder Relay

4 Supervision

If there has no phase current to be led to this relay, the setting [CTS.En] must be set as 0.

4.2.9 Thermal Overload Supervision


See Section 3.4 for the details. When the thermal overload alarm situation is detected, the alarm signals [Alm_Device] and [49.Alm] will be issued, and the LED indicator ALARM will be on at the same time.

4.2.10 Time Synchronization Supervision


If the time synchronization function is enabled in this relay, but this relay detects the time synchronization is not correct, the alarm signals [Alm_Device] and [Alm_TimeSync] will be issued and the LED indicator ALARM will be on at the same time.

4.2.11 Auxiliary Communication Testing Supervision


If this relay is in the auxiliary communication testing of binary signal or metering, the alarm signals [Alm_Device] and [Alm_CommTest] will be issued and the LED indicator ALARM will be on at the same time.

4.2.12 Device Maintenance Supervision


If this relay is in the maintenance situation (the binary input which is used for denoting maintenance situation is energized), the alarm signals [Alm_Device] and [Alm_Maintenance] will be issued and the LED indicator ALARM will be on at the same time.

4.2.13 Reserved Programmable Alarm Supervision


The relay provides several reserved programmable alarm signals which can be programmed through the PCS-PC configuration tool auxiliary software according to the engineering demands. When the relay detects anyone of the reserved programmable alarms is trigged, the alarm signals [Alm_Device] and [Alm_ResvX] (X: a number; 1, 2 etc.) will be issued and the LED indicator ALARM will be on at the same time.

4.2.14 Tripping Circuit Supervision


The tripping circuit supervision function can be realized by program the logic function of this device through the PCS-PC configuration tool auxiliary software according to the practical application experience of the user. In this manual, a scheme which uses two independent binary inputs to supervise the tripping circuit is recommended. The following figure show the recommended scheme for tripping circuit supervision and the logic diagram of the TCS function.

PCS-9611 Feeder Relay Date: 2011-08-29

4-5

4 Supervision

Figure 4.2-5 Principle of the TCS function with two binary inputs

Where: BTJ is the protection tripping output contact; TC is the tripping coil of the circuit breaker; [B07.BI_01] is the binary input which is parallel connected with BTJ; [B07.BI_02] is the binary input which is serial connected with the 52b contact.

4-6
Date: 2011-08-29

PCS-9611 Feeder Relay

5 Management Function

5 Management Function
Table of Contents
5.1 Overview ...........................................................................................................5-1 5.2 Measurement ....................................................................................................5-1
5.2.1 Protection Sampling........................................................................................................... 5-1 5.2.2 Metering............................................................................................................................. 5-1

5.3 Circuit Breaker Control ....................................................................................5-1 5.4 Signaling ...........................................................................................................5-2 5.5 Event Recording...............................................................................................5-2 5.6 Fault and Disturbance Recording ...................................................................5-3 5.7 Setting Group Switch Function.......................................................................5-3

List of Figures
Figure 5.3-1 Demonstration diagram of the control function................................................ 5-2

PCS-9611 Feeder Relay Date: 2011-08-29

5-a

5 Management Function

5-b
Date: 2011-08-29

PCS-9611 Feeder Relay

5 Management Function

5.1 Overview
The relay provides some management functions, such as protection sampling, metering, remote control, signaling, event recording and fault & disturbance recording etc. All these functions can ensure this relay meets the requirements of a modern power grid.

5.2 Measurement
This relay produces a variety of both directly and calculated power system quantities. There are two kinds of measurements are supported in this relay: protection sampling and metering. All these measurands also can be transmitted to the SAS or RTU through communication. See Chapter 10 for more information about the communication and protocols.

5.2.1 Protection Sampling


This relay samples the protection related values with 24-point sampling rate per cycle. These protection sampled values are being updated per 0.5s and can be viewed in the submenu Measurement1 of this relay or via relay communication. See Section 8.2.3 for more details about the protection measurands.

5.2.2 Metering
This relay samples the metering values with 48-point sampling rate per cycle. These metering values are being undated per 0.5s and can be viewed in the submenu Measurement2 of this relay or via relay communication. See Section 8.2.3 for more details about the metering values.

5.3 Circuit Breaker Control


This relay can receive the control commands to trip or close the circuit breaker. Up to 5 groups of output relays in this relay can be configured as control outputs (closing and tripping). And only the first closing output (local or remote) can be configured with synchronism check or dead check. The control function includes local control and remote control. The local control command can be gotten through the binary inputs or the submenu Control (see Section 8.2.8.4). The remote control command can be from the substation automatic system through the communication. Before executing a remote control command, it is necessary to put the control switch at the Remote position to make the binary signal [Ctrl.Sig_EnCtrl] be 1. Each control output can be control with an interlock module (which can be configured through the PCS-PC) if the corresponding interlock logic setting (see Section 7.4.3) is set as 1. If it makes the control outputs without interlock control in such a situation, the binary signal [Ctrl.Sig_Unblock] should be 1. The remote control commands include remote tripping command, remote closing command etc. See Chapter 10 for more information about the communication and protocols.
PCS-9611 Feeder Relay Date: 2011-08-29

5-1

5 Management Function

The demonstration diagram of the control function is shown as below.

Figure 5.3-1 Demonstration diagram of the control function

5.4 Signaling
This relay has some programmable binary inputs which are used to monitor the contact positions of the corresponding bay, or be used in protection logics or for releasing or blocking the relevant protective element, or be used in supervision logics calculation for supervision alarm elements The binary inputs can be configured according to the engineering demands through the PCS-PC configuration tool auxiliary software. The binary input state change confirmation time of each binary input is configurable according to practical application through the PCS-PC configuration tool auxiliary software, and the default binary input state change confirmation time of the binary inputs is 10ms. See Section 8.2.4 for more details about the binary inputs.

5.5 Event Recording


This relay supports the event recording functions which can record all the events happened in this relay. So it is very convenient for the user to view the history records. The following event information can be recorded. 64 latest protection operation reports 1024 latest supervision alarm records 1024 latest control operation records 1024 latest user operation records 1024 latest reports of time tagged sequence of event (SOE)
5-2
Date: 2011-08-29

PCS-9611 Feeder Relay

5 Management Function

5.6 Fault and Disturbance Recording


This relay provides the fault and disturbance recording facility for recording the sampled values of the fault and disturbance wave when a fault is occurred in the power system. The 64 latest fault and disturbance records can be recorded in this relay, and each wave record includes 5 cycles of pre-fault sampled data and most 150 cycles fault sampled data. The current and voltage sampled values, the binary input signals and the protection operation signals are contained in the fault and disturbance wave record, and the analog value sampling rate is 24 points per cycle. The format of the wave complies with the COMTRADE standard. There are several conditions which can trigger the fault and disturbance recording of this relay. The fault detector picks up. Anyone of the protective elements operates. Any shot of the auto-recloser operates. The binary input [BI_TrigDFR] is energized. The submenu Trig Oscillograph is executed. Each waveform includes the wave recording data both before and after the fault. Each trigger element operation will extend the wave recording time, until the appointed time delay is over after the trigger element restores, or until the maximum number of wave recording points is reached.

5.7 Setting Group Switch Function


This relay can switch the setting group number if this relay is in normal operation situation. Two fixed methods for switching the setting group number which are described in Section 8.2.6.4. Another method for changing the setting group number through two binary inputs can be supported by this relay, if this function is enabled. Two general binary inputs can be configured as signal inputs for switching the setting group number through PCS-PC configuration tool auxiliary software. This method only can switch four group of settings (1 ~ 4).
Binary Code Setting Group Number 00 1 01 2 10 3 11 4

PCS-9611 Feeder Relay Date: 2011-08-29

5-3

5 Management Function

5-4
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware

6 Hardware
Table of Contents
6.1 Overview ...........................................................................................................6-1 6.2 Basic Enclosure ...............................................................................................6-3 6.3 Human Machine Interface Module (NR4856) ..................................................6-3 6.4 Power Supply Module (NR4304)......................................................................6-3 6.5 Main CPU Module (NR4106).............................................................................6-5 6.6 Analog Input Module (NR4412)........................................................................6-7
6.6.1 Connection Examples ........................................................................................................ 6-9 6.6.2 Current Transformer Requirements ................................................................................. 6-10

6.7 Binary Output Module (NR4521) ...................................................................6-12 6.8 Binary Input Module (NR4502/NR4503/NR4504) ..........................................6-14 6.9 Network DSP Module (NR4136/NR4126).......................................................6-17 6.10 Optical Interface Extension Module (NR4202) ...........................................6-17

List of Figures
Figure 6.1-1 Hardware structure of the this relay .................................................................. 6-1 Figure 6.1-2 Front panel of the this relay................................................................................ 6-2 Figure 6.1-3 Rear panel of the this relay ................................................................................. 6-2 Figure 6.2-1 Rack, back plane and slot allocation of this relay ............................................ 6-3 Figure 6.4-1 View of the power supply module ...................................................................... 6-4 Figure 6.5-1 View of the main CPU module ............................................................................ 6-6 Figure 6.6-1 View of the analog input module........................................................................ 6-7 Figure 6.6-2 Current connection examples ............................................................................ 6-9 Figure 6.6-3 Voltage connection examples........................................................................... 6-10 Figure 6.7-1 View of the binary output module .................................................................... 6-12 Figure 6.8-1 View of the binary input module....................................................................... 6-15 Figure 6.9-1 View of the network DSP module ..................................................................... 6-17
PCS-9611 Feeder Relay Date: 2011-08-29

6-a

6 Hardware

Figure 6.10-1 View of the optical interface extension module.............................................6-18

6-b
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware

6.1 Overview
The modular design of this relay allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is hinged to allow easy access to the configurable modules, and back-plugging structure design makes it easy to repair or replace any modules. There are several types of hardware modules in this relay; each module takes a different part in this relay. The relevant modules can be selected according to the practical engineering demands. These modules which are supported in this relay and their module codes are listed as below.
No. 1 2 3 4 5 6 7 8 Module Description Human machine interface module Power supply module Main CPU module Analog input module Binary output module Binary input module Network DSP module Optical interface extension module Module Code NR4856 NR4304 NR4106 NR4412 NR4521 NR4502/NR4503/ NR4504 NR4136/NR4126 NR4202 Configuration Mandatory Mandatory Mandatory Optional Optional Optional Optional Optional

The hardware structure of this relay is shown as below.

Figure 6.1-1 Hardware structure of the this relay

These modules can be freely equipped in the basic enclosure of this relay (see Section 6.2), and the relationship between the module and the slot number is listed as below.
Module Description Power supply module Main CPU module Analog input module Binary output module Binary input module Network DSP module Optical interface extension module Must be in the No.9 slot. Must be in the No.1 slot. Must be in the No.4 and No.5 slots, if it is selected. Any slot if the slot is not occupied, default is the No.6 slot. Any slot if the slot is not occupied, default is the No.7 slot. Must be in the No.2 slot, if it is selected. Must be in the No.3 slot, if it is selected. Slot Number

PCS-9611 Feeder Relay Date: 2011-08-29

6-1

6 Hardware

The following two figures show the front panel and the rear panel of this device.

Figure 6.1-2 Front panel of the this relay

Figure 6.1-3 Rear panel of the this relay

NOTE! The hardware module configuration in above figure is only a demonstration for explaining how the hardware module is configured. The hardware module configuration can be different according to the different engineering demands, and the hardware module configuration of a practical engineering should be taken as final and binding. NOTE! The No.8 slot is reserved for some special demands, if the present hardware configuration can not meet the special demands.

6-2
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware

6.2 Basic Enclosure


The basic enclosure of this relay is an electronic equipment rack (see Figure 6.2-1) with an adequate number of slots for all these modules. The basic rack is equipped with a back plane (mother board), and the back plane provides some back plane lines for distributing signals within the enclosure. The rack, back plane and the slot allocation of this relay is shown as below. The hardware module configuration is in accordance with the Figure 6.1-3.

Slot:

NR4136/NR4126

NR4106

NR4202

NR4412

NR4521

NR4503

Figure 6.2-1 Rack, back plane and slot allocation of this relay

6.3 Human Machine Interface Module (NR4856)


The human machine interface (HMI) module is installed on the front panel of this device. It is used to observe the running status and event information on the LCD, and configure the protection settings and device operation mode. It can help the user to know the status of this relay and detailed event information easily, and provide convenient and friendly access interface for the user. Please see Chapter 8 for further details about how to access the human machine interface.

6.4 Power Supply Module (NR4304)


The power supply module is a power supply converter with electrical insulation between input and output, and a maximum output power of 30W. The power supply module has an input voltage range as described in Section 2.1.1.1. The standardized output DC voltages are +3.3V, +5V, 12V and +24V. The tolerances of the output voltages are continuously monitored. The +3.3Vdc output provides power supply for the microchip processors, and the +5Vdc output provides power supply for all the electrical elements that need +5Vdc power supply in this relay. The 12Vdc output provides power supply for A/D conversion circuits in this device, and the +24Vdc output provides power supply for the static relays of this device. The use of an external miniature circuit breaker is recommended. The miniature circuit breaker must be in the on position when the device is in operation and in the off position when the device is in cold reserve.

NR4304

PCS-9611 Feeder Relay Date: 2011-08-29

6-3

6 Hardware

The power supply module also provides binary outputs which are used to send out some necessary binary output signals according to the relevant commands from the CPU module, and these binary outputs only can be used as tripping and closing (protection, auto-recloser or remote control) outputs by setting the relevant settings. The view of the power supply module is shown in Figure 6.4-1.

NR4304 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 PWR+ 21 PWR22 GND

NR4304A

Figure 6.4-1 View of the power supply module

A 22-pin connector is fixed on the front side of this module. The terminal definition of the connector is described as below. Pin connections on the 22-pin connector of the power supply module NR4304A:
Pin No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 SIG_COM BO_Fail_Device BO_Alm_Device BO_01 BO_02 BO_03 BO_04 BO_05 BO_06 BO_07 Sign Failure signal output Alarming signal output The No.1 programmable tripping and closing binary output. It is also a self-latched output contact. The No.2 programmable tripping and closing binary output. It is also a self-latched output contact. The No.3 programmable tripping and closing binary output. The No.4 programmable tripping and closing binary output. The No.5 programmable tripping and closing binary output. The No.6 programmable tripping and closing binary output. The No.7 programmable tripping and closing binary output. Description Signal common output terminal

6-4
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware 18 19 20 21 22 BO_08 PSW+ PSWGND The No.8 programmable tripping and closing binary output. DC power supply positive input DC power supply negative input Grounded terminal

6.5 Main CPU Module (NR4106)


The main CPU module is the central part of this equipment, and contains a powerful microchip processor and some necessary electronic elements. This powerful processor performs all of the functions for the relay: the protection functions, the communication management functions. There are several A/D conversion circuits on this module, which are used to convert the AC analog signals to corresponding DC signals for fulfilling the demand of the electrical level standard. A high-accuracy clock chip is contained in this module, it provide accurate current time for this relay. The functional details of the main CPU module are listed as below: Protection calculations The main CPU module can calculate protective elements (such as overcurrent element, zero sequence overcurrent etc.) on the basis of the analog sampled values (voltages and currents) and binary inputs, and then decides whether the device needs to trip or close. Communication management The main CPU module can effectively manage all communication procedures, and reliably send out some useful information through its various communication interfaces. These interfaces are used to communicate with a SAS or a RTU. It also can communicate with the human machine interface module. If an event is occurred (such as SOE, protective tripping event etc.), this module will send out the relevant event information through these interfaces, and make it be easily observed by the user. Auxiliary calculations Based on the voltage and current inputs, the main CPU module also can calculate out the metering values, such as active power, reactive power and power factor etc. All these values can be sent to a SAS or a RTU through the communication interfaces. Time Synchronization This module has a local clock chip and an interface to receive time synchronized signals from external clock source. These signals include PPS (pulse per second) signal and IRIG-B signal. Basing on the timing message (from SAS or RTU) and the PPS signal, or basing on the IRIG-B signal, this module can synchronize local clock with the standard clock. There are three types of main CPU modules, and the view of the main CPU module is shown in Figure 6.5-1.

PCS-9611 Feeder Relay Date: 2011-08-29

6-5

6 Hardware

Figure 6.5-1 View of the main CPU module

A 16-pin or 7-pin connector is fixed on the front side of the module. The terminal definition of the connector is described as below. Pin connections on the connector of the main CPU module NR4106A and NR4106C:
Pin No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 485-1A 485-1B SGND FGND 485-2A 485-2B SGND FGND SYN+ SYNSGND FGND RTS TXD SGND Sign Not used The No.1 EIA RS-485 standardized interface for connecting with a SAS or a RTU. The grounded terminal. The No.2 EIA RS-485 standardized interface for connecting with a SAS or a RTU. The grounded terminal. The EIA RS-485 standardized interface for time synchronization, PPS and IRIG-B signals are permitted. The grounded terminal. The interface for connecting with a printer, the EPSON LQ-300K printer is recommended. Description

Pin connections on the connector of the main CPU module NR4106B:


Pin No. 01 02 03 04 Sign SYN+ SYNSGND FGND Description The EIA RS-485 standardized interface for time synchronization, PPS and IRIG-B signals are permitted. The grounded terminal.

6-6
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware 05 06 07 RTS TXD SGND The interface for connecting with a printer, the EPSON LQ-300K printer is recommended.

6.6 Analog Input Module (NR4412)


The analog input module can transform high AC input values to relevant low AC output value, which are suited to the analog inputs of the main CPU module. The transformers are used both to step-down the currents and voltages to levels appropriate to the relays electronic circuitry and to provide effective isolation between the relay and the power system. A low pass filter circuit is connected to each transformer (CT or VT) secondary circuit for reducing the noise of each analog AC input signal. NOTE! The rated value of the current transformer is optional: 1A or 5A. The rated value of the CT must be definitely declared in the technical scheme and the contract. NOTE! Because the rated value of the current transformer is optional, it is necessary to check whether the rated value of the current transformer inputs is according to the demand of the engineering scheme before the device is put into operation. DANGER! Never allow the current transformer (CT) secondary circuit connected to this relay to be opened while the primary system is energized. The opened CT secondary circuit will produce a dangerously high voltage. If this safety precaution is disregarded, personal death, severe personal injury or considerable equipment damage will occur. There are two types of analog input modules: NR4412 with 26 pins and NR4412 with 24 pins. The view of the analog input module is shown in Figure 6.6-1.

NR4412

NR4412

01

02

01

02

03

04

03

04

05

06

05

06

07

08

07

08

09

10

09

10

11

12

11

12

13

14

13

14

15

16

15

16

17

18

17

18

19

20

19

20

21

22

21

22

23

24

23

24

25

26

26-pin

24-pin

Figure 6.6-1 View of the analog input module

PCS-9611 Feeder Relay Date: 2011-08-29

6-7

6 Hardware

A 26-pin or 24-pin connector is fixed on the front side of this module. The terminal definition of the connector is described as below. Pin connections on the connector of the analog input module NR4412 with 26 pins:
Pin No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Ua Ub Uc Un Ux Uxn U0 U0n I02 I02n Ia Ian Ib Ibn Ic Icn I01 I01n I0s I0sn Iam Iamn Ibm Ibmn Icm Icmn The synchro-check voltage input. The zero sequence voltage input. The input of the No.2 zero sequence current. The input of the current of the A phase for protection. The input of the current of the B phase for protection. The input of the current of the C phase for protection. The input of the No.1 zero sequence current. The input of the sensitive zero sequence current. The input of the current of the A phase for metering. The input of the current of the B phase for metering. The input of the current of the C phase for metering. The three voltage inputs with inner star connection (Y) for protection and metering. Sign Description

Pin connections on the connector of the analog input module NR4412 with 24 pins:
Pin No. 01 02 03 04 05 06 07 08 6-8
Date: 2011-08-29

Sign Ua Ub Uc Un Ux Uxn U0 U0n

Description The three voltage inputs with inner star connection (Y) for protection and metering.

The synchro-check voltage input. The zero sequence voltage input.

PCS-9611 Feeder Relay

6 Hardware 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 I02 I02n Ia Ian Ib Ibn Ic Icn I01 I01n I0s I0sn The input of the No.2 zero sequence current. The input of the current of the A phase for protection. The input of the current of the B phase for protection. The input of the current of the C phase for protection. The input of the No.1 zero sequence current. The input of the sensitive zero sequence current. Not used Not used Not used Not used

6.6.1 Connection Examples


Some connection examples of the current transformers and voltage transformers which are supported by this relay are shown in this section. If one of the analog inputs has no input in a practical engineering, the relevant input terminals should be disconnected. 1. Current connections examples

Figure 6.6-2 Current connection examples

PCS-9611 Feeder Relay Date: 2011-08-29

6-9

6 Hardware

Where: (1) Current connections to three current transformers with a star-point connection for ground current (zero sequence current or residual current). (2) Current connections to three current transformers with a separate ground current transformer (summation current transformer or core balance current transformer). (3) Current connections to two current transformers with a separate ground current transformer (summation current transformer or core balance current transformer), only for ungrounded or compensated networks. (4) Current connection to a core balance neutral current transformer for sensitive ground fault detection, only for ungrounded or compensated networks. (5) Current connection to a separate ground current transformer (summation current transformer or core balance current transformer) for the No.2 zero sequence current input of this relay. 2. Voltage connections examples
A B C A B C

05 52 52 52 05 06 Ux Uxn 52 52 52 06

Ux Uxn

01 02 03 04 07 08 (1)

Ua Ub Uc Un U0 U0n (2)

01 02 03 04 07 08

Ua Ub Uc Un U0 U0n

Figure 6.6-3 Voltage connection examples

Where: (1) Voltage connections to three star-connected voltage transformers with open-delta windings and additionally to any phase voltage (for synchronism check). (2) Voltage connections to three star-connected voltage transformers with open-delta windings and additionally to any phase-to-phase voltage (for synchronism check).

6.6.2 Current Transformer Requirements


CT Requirements -Rated primary current Ipn:

6-10
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware

According to the rated current or maximum load current of primary apparatus -Rated continuous thermal current Icth: According to the maximum load current -Rated short-time thermal current Ith and rated dynamic current Idyn: According to the maximum fault current --Rated secondary current Isn Accuracy limit factor Kalf:
Ipn Icth Ith Idyn Isn Kalf Ipal Rated primary current (amps) Rated continuous thermal current (amps) Rated short-time thermal current (amps) Rated dynamic current (amps) Rated secondary current (amps) Accuracy limit factor: Kalf = Ipal / Ipn Rated accuracy limit primary current (amps)

Performance Verification Esl > Esl


Esl Esl Kalf k Ipal Ipcf Ipn Isn Rct Rbn Sbn Rb Rc RL Rr Rated secondary limiting e.m.f (volts): Esl = kalf Isn (Rct + Rbn) Required secondary limiting e.m.f (volts): Esl = k Ipcf Isn (Rct + Rb) / Ipn Accuracy limit factor: Kalf = Ipal / Ipn Stability factor: k = 2 Rated accuracy limit primary current (amps) Protective checking factor current (amps): same as the maximum prospective fault current Rated primary current (amps) Rated secondary current (amps) Current transformer secondary winding resistance (ohms) Rated resistance burden (ohms): Rbn = Sbn / Isn2 Rated burden (VAs) Real resistance burden (ohms): Rb = Rr + 2RL + Rc Contact resistance, 0.05~0.10 (ohms) Resistance of a single lead from relay to the CT (ohms) Impedance of relay phase current input (ohms)

Example Kalf = 30.00, Isn = 5A, Rct = 1.00, Sbn = 60VA

PCS-9611 Feeder Relay Date: 2011-08-29

6-11

6 Hardware

Esl = kalf Isn (Rct + Rbn) = kalf Isn (Rct + Sbn / Isn2) So, Esl = 30 5 (1 + 60 / 52) = 510V Ipcf = 40000A, RL = 0.50, Rr = 0.10, Rc = 0.10, Ipn = 2000A

Esl = k Ipcf Isn (Rct + Rb) / Ipn = k Ipcf Isn (Rct + (Rr + 2RL + Rc)) / Ipn So, Esl = 2 40000 5 (1 + (0.1 + 2 0.5 + 0.1)) / 2000 = 440V It can meet the requirement: Esl > Esl.

6.7 Binary Output Module (NR4521)


The binary output module consists of some necessary contact outputs, and the binary outputs are used as tripping and closing (protection, auto-recloser or remote control) outputs or signal outputs. It can receive tripping commands or closing commands from the main CPU module, and then act according to these commands. It also can output some alarm signals from the main CPU module. There are three types of binary output modules: NR4521A, NR4521C and NR4521D. The view of the binary output module is shown in Figure 6.7-1.

Figure 6.7-1 View of the binary output module

A 22-pin connector is fixed on the front side of this module. The terminal definition of the connector is described as below. Pin connections on the 22-pin connector of the binary output module NR4521A:
Pin No. 01 02 03 04 BO_01 BO_02 Sign Description The No.1 programmable tripping and closing binary output. The No.2 programmable tripping and closing binary output.

6-12
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 BO_03 BO_04 BO_05 BO_06 BO_07 BO_08 BO_09 BO_10 BO_11 The No.3 programmable tripping and closing binary output. The No.4 programmable tripping and closing binary output. The No.5 programmable tripping and closing binary output. The No.6 programmable tripping and closing binary output. The No.7 programmable tripping and closing binary output. The No.8 programmable tripping and closing binary output. The No.9 programmable tripping and closing binary output. The No.10 programmable tripping and closing binary output. The No.11 programmable tripping and closing binary output.

Pin connections on the 22-pin connector of the binary output module NR4521C:
Pin No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 BO_01 BO_02 BO_03 BO_04 BO_05 BO_06 BO_07 BO_08 BO_09 BO_10 BO_11 Sign Description The No.1 programmable tripping and closing binary output. The No.2 programmable tripping and closing binary output. The No.3 programmable tripping and closing binary output. The No.4 programmable tripping and closing binary output. The No.5 programmable tripping and closing binary output. The No.6 programmable tripping and closing binary output. The No.1 programmable signal binary output. The No.2 programmable signal binary output. The No.3 programmable signal binary output. The No.4 programmable signal binary output. The No.5 programmable signal binary output.

PCS-9611 Feeder Relay Date: 2011-08-29

6-13

6 Hardware

Pin connections on the 22-pin connector of the binary output module NR4521D:
Pin No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 BO_01 BO_02 BO_03 BO_04 BO_05 BO_06 BO_07 BO_08 BO_09 BO_10 BO_11 Sign Description The No.1 programmable tripping and closing binary output. The No.2 programmable tripping and closing binary output. The No.3 programmable tripping and closing binary output. The No.4 programmable tripping and closing binary output. The No.5 programmable tripping and closing binary output. The No.6 programmable tripping and closing binary output. The No.7 programmable tripping and closing binary output. The No.8 programmable tripping and closing binary output. The No.9 programmable tripping and closing binary output. The No.10 programmable tripping and closing binary output. The No.11 programmable tripping and closing binary output.

6.8 Binary Input Module (NR4502/NR4503/NR4504)


The binary input module contains some binary inputs which are used to monitor the contact positions of the corresponding bay, and all the binary inputs are configurable through PCS-PC configuration tool. Some of them are used as general purpose binary inputs, and others are used as special purpose binary inputs. These binary inputs are all optical isolated binary inputs. The regular optical isolated binary inputs are used to monitor the position of the regular binary signals; the special optical isolated binary inputs are used to monitor the position of the special binary signals, which must be taken into account in the protection and interlock logic calculations of the main CPU module. There are three types of binary input modules: NR4502, NR4503 and NR4504. The view of the binary input module is shown in Figure 6.8-1.

6-14
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware

Figure 6.8-1 View of the binary input module

A 22-pin connector is fixed on the front side of this module. The terminal definition of the connector is described as below. Pin connections on the 22-pin connector of the binary input module NR4502:
Pin No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 BI_01+ BI_01BI_02+ BI_02BI_03+ BI_03BI_04+ BI_04BI_05+ BI_05BI_06+ BI_06BI_07+ BI_07BI_08+ BI_08BI_09+ BI_09BI_10+ BI_10BI_11+ BI_11Sign Description The No.1 programmable binary input The No.2 programmable binary input The No.3 programmable binary input The No.4 programmable binary input The No.5 programmable binary input The No.6 programmable binary input The No.7 programmable binary input The No.8 programmable binary input The No.9 programmable binary input The No.10 programmable binary input The No.11 programmable binary input

Pin connections on the 22-pin connector of the binary input module NR4503:
PCS-9611 Feeder Relay Date: 2011-08-29

6-15

6 Hardware Pin No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 BI_01+ BI_01BI_02+ BI_02BI_03 BI_04 BI_05 BI_06 BI_07 BI_08 BI_09 BI_10 BI_11 BI_12 BI_13 BI_14 BI_15 BI_16 BI_17 BI_18 BI_19 BI_OptoSign Description The No.1 programmable binary input. The No.2 programmable binary input. The No.3 programmable binary input. The No.4 programmable binary input. The No.5 programmable binary input. The No.6 programmable binary input. The No.7 programmable binary input. The No.8 programmable binary input. The No.9 programmable binary input. The No.10 programmable binary input. The No.11 programmable binary input. The No.12 programmable binary input. The No.13 programmable binary input. The No.14 programmable binary input. The No.15 programmable binary input. The No.16 programmable binary input. The No.17 programmable binary input. The No.18 programmable binary input. The No.19 programmable binary input. The common negative connection of the BI_03 to BI_19.

Pin connections on the 22-pin connector of the binary input module NR4504:
Pin No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 BI_01 BI_02 BI_Opto1BI_03 BI_04 BI_Opto2BI_05 BI_06 BI_Opto3BI_07 BI_08 BI_Opto4BI_09 BI_10 BI_Opto5BI_11 BI_12 Sign Description The No.1 programmable binary input. The No.2 programmable binary input. The common negative connection of the BI_01 and BI_02. The No.3 programmable binary input. The No.4 programmable binary input. The common negative connection of the BI_03 and BI_04. The No.5 programmable binary input. The No.6 programmable binary input. The common negative connection of the BI_05 and BI_06. The No.7 programmable binary input. The No.8 programmable binary input. The common negative connection of the BI_07 and BI_08. The No.9 programmable binary input. The No.10 programmable binary input. The common negative connection of the BI_09 and BI_10. The No.11 programmable binary input. The No.12 programmable binary input.

6-16
Date: 2011-08-29

PCS-9611 Feeder Relay

6 Hardware 18 19 20 21 22 BI_Opto6BI_13 BI_14 BI_Opto7The common negative connection of the BI_11 and BI_12. The No.13 programmable binary input. The No.14 programmable binary input. The common negative connection of the BI_13 and BI_14. Not used

6.9 Network DSP Module (NR4136/NR4126)


The network DSP module is applied in a digitalized substation for leading the current and voltage from the electronic transformer through a merging unit, and it also can receive or transmit the GOOSE information. There are two kinds of network DSP module: NR4126 and NR4136. The network DSP module NR4136 provides up to 6 optical Ethernet ports which can supports the protocol IEC61850-9-2, GOOSE and IEEE1588. It also provides an optical Ethernet port for the IEC60044-8 data reception, and an optical Ethernet port for the time synchronization. The network DSP module NR4126 provides 2 optical Ethernet ports which only can supports the GOOSE protocol. The view of the network DSP module is shown in Figure 6.9-1.

Figure 6.9-1 View of the network DSP module

6.10 Optical Interface Extension Module (NR4202)


The optical interface extension module is applied in a digitalized substation to extend the optical interfaces for the module NR4106 and the module NR4136. It is only can support the reception or transmission of the protocol IEC60044-8. The view of the optical interface extension module is shown in Figure 6.10-1.

PCS-9611 Feeder Relay Date: 2011-08-29

6-17

6 Hardware

Figure 6.10-1 View of the optical interface extension module

6-18
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings

7 Settings
Table of Contents
7.1 Overview ...........................................................................................................7-1 7.2 System Settings ...............................................................................................7-1 7.3 Protection Settings ..........................................................................................7-2
7.3.1 Overcurrent Protection Settings......................................................................................... 7-3 7.3.2 Zero Sequence Overcurrent Protection Settings ............................................................... 7-6 7.3.3 Negative Sequence Overcurrent Protection Settings......................................................... 7-9 7.3.4 Sensitive Earth Fault Protection Settings......................................................................... 7-10 7.3.5 Breaker Failure Protection Settings ................................................................................. 7-12 7.3.6 Broken Conductor Protection Settings ............................................................................. 7-13 7.3.7 Cold Load Pickup Settings............................................................................................... 7-13 7.3.8 SOTF Protection Settings ................................................................................................ 7-14 7.3.9 Thermal Overload Protection Settings ............................................................................. 7-15 7.3.10 Overvoltage and Undervoltage Protection Settings ....................................................... 7-16 7.3.11 Negative Sequence Overvoltage Protection Settings..................................................... 7-17 7.3.12 Zero Sequence Overvoltage Protection Settings ........................................................... 7-17 7.3.13 Frequency Protection Settings....................................................................................... 7-18 7.3.14 Auto-recloser Settings.................................................................................................... 7-21 7.3.15 Mechanical Protection Settings...................................................................................... 7-21 7.3.16 Supervision Element Settings ........................................................................................ 7-22 7.3.17 Binary Output Matrix Settings ........................................................................................ 7-23

7.4 Monitor and Control Settings ........................................................................7-23


7.4.1 Closing Synchronism Check Settings .............................................................................. 7-23 7.4.2 Manual Control Settings................................................................................................... 7-25 7.4.3 Interlock Settings ............................................................................................................. 7-26

7.5 Logic Link Settings ........................................................................................7-27


7.5.1 Function Link Settings ..................................................................................................... 7-27
PCS-9611 Feeder Relay Date: 2011-08-29

7-a

7 Settings

7.5.2 GOOSE Link Settings.......................................................................................................7-27 7.5.3 SV Link Settings ...............................................................................................................7-27 7.5.4 Spare Link Settings...........................................................................................................7-27

7.6 Device Related Settings ................................................................................ 7-28


7.6.1 Device Settings ................................................................................................................7-28 7.6.2 Communication Settings...................................................................................................7-28

7.7 Copy Settings................................................................................................. 7-31

7-b
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings

7.1 Overview
The settings are used to determine the characteristic of each protective element and operation mode of the relay. It is necessary to configure the settings of this relay according to engineering demands before putting this relay into service. If the settings are not configured correctly, this relay maybe works abnormally (such as communication interruption, printing out unexpected codes etc.), it also can lead to much more serious accident (such as unwanted operation, missing operation) sometimes. The settings of this relay include system settings, protection settings, communication settings and miscellaneous settings. The user can configure these settings or parameters manually (see Section 8.2.6.2). Remote modification is also supported (IEC61850, IEC60870-5-103 or DNP3.0 interface, see Chapter 10 for the details about these protocols). NOTE! If a CPU module is replaced, it is necessary to configure all the settings again according to the configuration of the CPU module which is replaced.

7.2 System Settings


The system settings (in the submenu System Settings) are mainly used to set the rated value of VT and CT. The following table lists all the system parameters.
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Menu text Active_Grp Opt_SysFreq PrimaryEquip_Name Prot.I1n Prot.I2n Measmt.I1n Measmt.I2n Neu1.I1n Neu1.I2n Neu2.I1n Neu2.I2n SEF.I1n SEF.I2n Prot.U1n Prot.U2n Syn.U1n Syn.U2n Delt.U1n Explanation The active setting group number Select the rated system frequency: 0, 50Hz; 1, 60Hz The name of the protected primary equipment Rated primary value of protection phase CT Rated secondary value of protection phase CT Rated primary value of metering phase CT Rated secondary value of metering phase CT Rated primary value of the No.1 zero sequence CT Rated secondary value of the No.1 zero sequence CT Rated primary value of the No.2 zero sequence CT Rated secondary value of the No.2 zero sequence CT Rated primary value of sensitive zero sequence CT Rated secondary value of sensitive zero sequence CT Rated primary value of protection VT Rated secondary value of protection VT Rated primary value of synchro-check VT Rated secondary value of synchro-check VT Rated primary value of zero sequence VT 0~1 1~7 characters 0~20000A 1/5A 0~20000A 1/5A 0~20000A 1/5A 0~20000A 1/5A 0~20000A 1/5A 0.1~500.0kV 100~200V 0.1~500.0kV 10~200V 0.1~500.0kV 1A 4A 1A 4A 1A 4A 1A 4A 1A 4A 0.001kV 0.001V 0.001kV 0.001V 0.001kV Range 1 ~ 10 1 1 Step

PCS-9611 Feeder Relay Date: 2011-08-29

7-1

7 Settings 19 20 21 22 Delt.U2n Opt_3I0 Opt_3U0 Opt_PwrDir Rated secondary value of zero sequence VT Zero sequence current is self calculated 0:from neutral CT 1:self calculated Zero sequence voltage is self calculated 0:from neutral VT 1:self calculated Power Measurement Mode 10~200V 0~1 0~1 0~3 0.001V 1 1 1

NOTE! 1. The system settings is related to the protection activities, thus it is necessary to configure theses settings according to actual conditions. The setting [Opt_3I0] is used to select the No.1 zero sequence current source. Setting the value of [Opt_3I0] as 1 means that the No.1 zero sequence current is self-calculated, and setting the value as 0 means that the No.1 zero sequence current is derived from specific zero sequence CT. The default value is 0 when the equipment is delivered. The setting [Opt_3U0] is used to select the zero sequence voltage source. Setting the value of [Opt_3U0] as 1 means that zero sequence voltage is self-calculated, and setting the value as 0 means that zero sequence voltage is derived from specific broken delta VT. The setting [Opt_PwrDir] is used to select the power measurement mode.
[Opt_PwrDir] 0 1 2 3 Active Power To line +W -W +W -W To busbar -W +W -W +W Lagging reactive power To line +Var +Var -Var -Var To busbar -Var -Var +Var +Var

2.

3.

4.

7.3 Protection Settings


The protection settings (in the submenu Prot Settings) are used to decide the characteristics of the protective elements. There are up to 10 groups of protection settings in this relay. NOTE! Following items should be considered before modifying the protection settings. 1. 2. Before configuring the settings, the setting group must be configured first. When a certain setting is of no use, in case of over-elements (such as overcurrent, residual overcurrent), set the value as upper limit; in case of under-elements (such as under frequency, under voltage), set the value as lower limit; set the corresponding time as 100s and disable corresponding protection element and de-energize the corresponding binary input. In general, for switch onto fault protection and accelerated protection, it is necessary to set a time delay from decades to 100ms. Thanks to there is no 100ms time delay in the numerical

3.

7-2
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings

protection equipment as there in the traditional protection equipment in the past, thus it can not avoid surge current when CB is closing if the time is set as 0.00s. For residual overcurrent when switch onto fault and residual accelerate protection, there is zero sequence surge current when CB is closing. 4. To a certain protection element, only when the logic setting and the state of enabling input signal are 1, and the state of the blocking input signal is 0 at the same time, then the corresponding protection element is enabled, otherwise it is disabled. The setting [XXXX.OutMap] is used to select the binary outputs of the module NR4304 and the module NR4521 to send the related protection tripping or closing signal to the circuit breaker. Each bit can control an output, and if it is set as 1, the related protection tripping or closing signal can be sent to the circuit breaker through the selected binary output.
Bit No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Corresponding Binary Output The No.1 programmable binary output of the module NR4304 (B09.BO_01) The No.2 programmable binary output of the module NR4304 (B09.BO_02) The No.3 programmable binary output of the module NR4304 (B09.BO_03) The No.4 programmable binary output of the module NR4304 (B09.BO_04) The No.5 programmable binary output of the module NR4304 (B09.BO_05) The No.6 programmable binary output of the module NR4304 (B09.BO_06) The No.7 programmable binary output of the module NR4304 (B09.BO_07) The No.8 programmable binary output of the module NR4304 (B09.BO_08) The No.1 programmable binary output of the module NR4521 (B06.BO_01) The No.2 programmable binary output of the module NR4521 (B06.BO_02) The No.3 programmable binary output of the module NR4521 (B06.BO_03) The No.4 programmable binary output of the module NR4521 (B06.BO_04) The No.5 programmable binary output of the module NR4521 (B06.BO_05) The No.6 programmable binary output of the module NR4521 (B06.BO_06) The No.1 programmable binary output of the module NR4521 (B03.BO_01) The No.2 programmable binary output of the module NR4521 (B03.BO_02) The No.3 programmable binary output of the module NR4521 (B03.BO_03) The No.4 programmable binary output of the module NR4521 (B03.BO_04) The No.5 programmable binary output of the module NR4521 (B03.BO_05) The No.6 programmable binary output of the module NR4521 (B03.BO_06)

5.

Some of the protective elements have a setting (just like [XXXX.OutMap], XXXX is the abbreviation of a protective element, such as 50/51P1, 50/51G1, 59P1 etc.) to configure the outputs, and they have the same meanings described here. Please refer the content here for the output matrix setting of each protective element.

7.3.1 Overcurrent Protection Settings


The overcurrent protection settings (in the submenu OC Settings) are used to determine the characteristic of the overcurrent protection. All the settings of the overcurrent protection are listed in the following table.
PCS-9611 Feeder Relay Date: 2011-08-29

7-3

7 Settings No. 1 2 3 Menu text 50/51P.U2_VCE 50/51P.Upp_VCE 50/51P.RCA Explanation The voltage setting of the negative sequence voltage blocking element (phase voltage) The voltage setting of the low voltage blocking element (phase-to-phase voltage) The relay characteristic angle for the directional overcurrent protection The logic setting of the function which can block 4 50/51P.En_VTS_Blk the OC protection related voltage measurement when the voltage transformer is failed 5 6 7 8 9 10 50/51P.K_Hm2 50/51P.I_Rls_HmBlk 50/51P.Opt_Hm_Blk 50/51P1.I_Set 50/51P1.t_Op 50/51P1.En_VCE The percent setting of the harmonic blocking element for OC protection The current setting for releasing the harmonic blocking element of OC protection The setting is used to select the harmonic blocking mode of OC protection The current setting of the stage 1 overcurrent protection The time setting of the stage 1 overcurrent protection The logic setting of the voltage control element for the stage 1 overcurrent protection The setting is used to select the directional mode 11 50/51P1.Opt_Dir for the stage 1 overcurrent protection, see Section 3.3.4 12 13 14 15 16 17 50/51P1.En_Hm_Blk 50/51P1.En 50/51P1.OutMap 50/51P2.I_Set 50/51P2.t_Op 50/51P2.En_VCE The logic setting of the harmonic blocking element for the stage 1 overcurrent protection The logic setting of the stage 2 overcurrent protection The output matrix setting of the stage 1 overcurrent protection The current setting of the stage 2 overcurrent protection The time setting of the stage 2 overcurrent protection The logic setting of the voltage control element for the stage 2 overcurrent protection The setting is used to select the directional mode 18 50/51P2.Opt_Dir for the stage 2 overcurrent protection, see Section 3.3.4 19 20 50/51P2.En_Hm_Blk 50/51P2.En The logic setting of the harmonic blocking element for the stage 2 overcurrent protection The logic setting of the stage 2 overcurrent protection 0~1 0~1 1 1 0~2 1 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~1 1 1 1 0.001A 0.001s 1 0~2 1 0.05~1.00 0.05In~30In 1~3 0.05In~30In 0~100s 0~1 0.001 0.001A 1 0.001A 0.001s 1 0~1 1 Range 2~70V 2~120V -180~179 Step 0.001V 0.001V 1

7-4
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings 21 22 23 24 50/51P2.OutMap 50/51P3.I_Set 50/51P3.t_Op 50/51P3.En_VCE The output matrix setting of the stage 2 overcurrent protection The current setting of the stage 3 overcurrent protection The time setting of the stage 3 overcurrent protection The logic setting of the voltage control element for the stage 3 overcurrent protection The setting is used to select the directional mode 25 50/51P3.Opt_Dir for the stage 3 overcurrent protection, see Section 3.3.4 26 27 28 29 30 31 50/51P3.En_Hm_Blk 50/51P3.En 50/51P3.OutMap 50/51P4.I_Set 50/51P4.t_Op 50/51P4.En_VCE The logic setting of the harmonic blocking element for the stage 3 overcurrent protection The logic setting of the stage 3 overcurrent protection The output matrix setting of the stage 3 overcurrent protection The current setting of the stage 4 overcurrent protection The time setting of the stage 4 overcurrent protection The logic setting of the voltage control element for the stage 4 overcurrent protection The setting is used to select the directional mode 32 50/51P4.Opt_Dir for the stage 4 overcurrent protection, see Section 3.3.4 33 34 35 36 37 38 39 40 41 50/51P4.En_Hm_Blk 50/51P4.En 50/51P4.OutMap 50/51P4.Opt_Curve 50/51P4.TMS 50/51P4.tmin 50/51P4.K 50/51P4.C 50/51P4.Alpha The logic setting of the harmonic blocking element for the stage 4 overcurrent protection The logic setting of the stage 4 overcurrent protection The output matrix setting of the stage 4 overcurrent protection The setting is for selecting the inverse time characteristic curve for OC4 protection The time multiplier setting of the IDMT overcurrent protection The minimum operation time setting of the IDMT overcurrent protection Constant k for the IDMT overcurrent protection, see Section 3.3.2 Constant C for the IDMT overcurrent protection, see Section 3.3.2 Constant for the IDMT overcurrent protection, see Section 3.3.2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s 0.001~120.0 0.00~1.00 0.01~3.00 1 1 1 1 0.001 0.001s 0.0001 0.0001 0.0001 0~2 1 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~1 1 1 1 0.001A 0.001s 1 0~2 1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~1 1 0.001A 0.001s 1

PCS-9611 Feeder Relay Date: 2011-08-29

7-5

7 Settings

NOTE! 1. The setting [50/51Px.Opt_Dir] (x: 1~4) is used to select the directional mode for the stage x (x: 1~4) overcurrent protection respectively. 0 is the non-directional mode; 1 is the forward directional mode; and 2 is the reverse directional mode.

7.3.2 Zero Sequence Overcurrent Protection Settings


The No.1 zero sequence overcurrent protection settings (in the submenu EF1 Settings) are used to determine the characteristic of the No.1 zero sequence overcurrent protection. The No.2 zero sequence overcurrent protection settings (in the submenu EF2 Settings) are used to determine the characteristic of the No.2 zero sequence overcurrent protection. All the settings of the No.1 zero sequence overcurrent protection are listed in the following table.
No. 1 Menu text 50/51G.RCA Explanation The relay characteristic angle for the No.1 directional zero sequence overcurrent protection The logic setting of the function which blocks the 2 50/51G.En_VTS_Blk 1ROC protection related voltage measurement when the voltage transformer is failed 3 4 5 6 7 8 9 10 11 12 13 14 50/51G.K_Hm2 50/51G.3I0_Rls_HmBlk 50/51G1.3I0_Set 50/51G1.t_Op 50/51G1.Opt_Dir 50/51G1.En_Hm_Blk 50/51G1.En 50/51G1.OutMap 50/51G2.3I0_Set 50/51G2.t_Op 50/51G2.Opt_Dir 50/51G2.En_Hm_Blk The percent setting of the harmonic blocking element for the No.1 ROC protection The current setting for releasing the harmonic blocking element of the No.1 ROC protection The current setting of the No.1 stage 1 zero sequence overcurrent protection The time setting of the No.1 stage 1 zero sequence overcurrent protection The setting is used to select the directional mode for the No.1 ROC1 protection, see Section 3.5.3 The logic setting of the harmonic blocking element for the No.1 ROC1 protection The logic setting of the No.1 stage 1 zero sequence overcurrent protection The output matrix setting of the No.1 stage 1 zero sequence overcurrent protection The current setting of the No.1 stage 2 zero sequence overcurrent protection The time setting of the No.1 stage 2 zero sequence overcurrent protection The setting is used to select the directional mode for the No.1 ROC2 protection, , see Section 3.5.3 The logic setting of the harmonic blocking element for the No.1 ROC2 protection 0.05~1.00 0.05In~30In 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0.001 0.001A 0.001A 0.001s 1 1 1 1 0.001A 0.001s 1 1 0~1 1 Range -180~179 Step 1

7-6
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 50/51G2.En 50/51G2.OutMap 50/51G3.3I0_Set 50/51G3.t_Op 50/51G3.Opt_Dir 50/51G3.En_Hm_Blk 50/51G3.En 50/51G3.OutMap 50/51G4.3I0_Set 50/51G4.t_Op 50/51G4.Opt_Dir 50/51G4.En_Hm_Blk 50/51G4.En 50/51G4.OutMap 50/51G4.Opt_Curve 50/51G4.TMS 50/51G4.tmin 50/51G4.K 50/51G4.C 50/51G4.Alpha The logic setting of the No.1 stage 2 zero sequence overcurrent protection The output matrix setting of the No.1 stage 2 zero sequence overcurrent protection The current setting of the No.1 stage 3 zero sequence overcurrent protection The time setting of the No.1 stage 3 zero sequence overcurrent protection The setting is used to select the directional mode for the No.1 ROC3 protection, see Section 3.5.3 The logic setting of the harmonic blocking element for the No.1 ROC3 protection The logic setting of the No.1 stage 3 zero sequence overcurrent protection The output matrix setting of the No.1 stage 3 zero sequence overcurrent protection The current setting of the No.1 stage 4 zero sequence overcurrent protection The time setting of the No.1 stage 4 zero sequence overcurrent protection The setting is used to select the directional mode for the No.1 ROC4 protection, see Section 3.5.3 The logic setting of the harmonic blocking element for the No.1 ROC4 protection The logic setting of the No.1 stage 4 zero sequence overcurrent protection The output matrix setting of the No.1 stage 4 zero sequence overcurrent protection The setting is for selecting the inverse time characteristic curve for the No.1 ROC4 protection The time multiplier setting of the No.1 zero sequence IDMT overcurrent protection The minimum operation time setting of the No.1 zero sequence IDMT overcurrent protection Constant k for the No.1 zero sequence IDMT overcurrent protection, see Section 3.5.2 Constant C for the No.1 zero sequence IDMT overcurrent protection, see Section 3.5.2 Constant for the No.1 zero sequence IDMT overcurrent protection, see Section 3.5.2 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s 0.001~120.0 0.00~1.00 0.01~3.00 1 1 0.001A 0.001s 1 1 1 1 0.001A 0.001s 1 1 1 1 1 0.001 0.001s 0.0001 0.0001 0.0001

NOTE! 1. The setting [50/51Gx.Opt_Dir] (x: 1~4) is used to select the directional mode for the No.1
7-7
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings

stage x (x: 1~4) zero sequence overcurrent protection respectively. 0 is the non-directional mode; 1 is the forward directional mode; and 2 is the reverse directional mode. All the settings of the No.2 zero sequence overcurrent protection are listed in the following table.
No. 1 Menu text A.50/51G.RCA Explanation The relay characteristic angle for the No.2 directional zero sequence overcurrent protection The logic setting of the function which blocks the 2 A.50/51G.En_VTS_Blk 2ROC protection related voltage measurement when the voltage transformer is failed 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 A.50/51G.K_Hm2 A.50/51G.3I0_Rls_HmBlk A.50/51G1.3I0_Set A.50/51G1.t_Op A.50/51G1.Opt_Dir A.50/51G1.En_Hm_Blk A.50/51G1.En A.50/51G1.OutMap A.50/51G2.3I0_Set A.50/51G2.t_Op A.50/51G2.Opt_Dir A.50/51G2.En_Hm_Blk A.50/51G2.En A.50/51G2.OutMap A.50/51G3.3I0_Set A.50/51G3.t_Op A.50/51G3.Opt_Dir The percent setting of the harmonic blocking element for the No.2 ROC protection The current setting for releasing the harmonic blocking element of the No.2 ROC protection The current setting of the No.2 stage 1 zero sequence overcurrent protection The time setting of the No.2 stage 1 zero sequence overcurrent protection The setting is used to select the directional mode for the No.2 ROC1 protection The logic setting of the harmonic blocking element for the No.2 ROC1 protection The logic setting of the No.2 stage 1 zero sequence overcurrent protection The output matrix setting of the No.2 stage 1 zero sequence overcurrent protection The current setting of the No.2 stage 2 zero sequence overcurrent protection The time setting of the No.2 stage 2 zero sequence overcurrent protection The setting is used to select the directional mode for the No.2 ROC2 protection The logic setting of the harmonic blocking element for the No.2 ROC2 protection The logic setting of the No.2 stage 2 zero sequence overcurrent protection The output matrix setting of the No.2 stage 2 zero sequence overcurrent protection The current setting of the No.2 stage 3 zero sequence overcurrent protection The time setting of the No.2 stage 3 zero sequence overcurrent protection The setting is used to select the directional mode for the No.2 ROC3 protection 0.05~1.00 0.05In~30In 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0.001 0.001A 0.001A 0.001s 1 1 1 1 0.001A 0.001s 1 1 1 1 0.001A 0.001s 1 0~1 1 Range -180~179 Step 1

7-8
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 A.50/51G3.En_Hm_Blk A.50/51G3.En A.50/51G3.OutMap A.50/51G4.3I0_Set A.50/51G4.t_Op A.50/51G4.Opt_Dir A.50/51G4.En_Hm_Blk A.50/51G4.En A.50/51G4.OutMap A.50/51G4.Opt_Curve A.50/51G4.TMS A.50/51G4.tmin A.50/51G4.K A.50/51G4.C A.50/51G4.Alpha The logic setting of the harmonic blocking element for the No.2 ROC3 protection The logic setting of the No.2 stage 3 zero sequence overcurrent protection The output matrix setting of the No.2 stage 3 zero sequence overcurrent protection The current setting of the No.2 stage 4 zero sequence overcurrent protection The time setting of the No.2 stage 4 zero sequence overcurrent protection The setting is used to select the directional mode for the No.2 ROC4 protection The logic setting of the harmonic blocking element for the No.2 ROC4 protection The logic setting of the No.2 stage 4 zero sequence overcurrent protection The output matrix setting of the No.2 stage 4 zero sequence overcurrent protection The setting is for selecting the inverse time characteristic curve for the No.2 ROC4 protection The time multiplier setting of the No.2 zero sequence IDMT overcurrent protection The minimum operation time setting of the No.2 zero sequence IDMT overcurrent protection Constant k for the No.2 zero sequence IDMT overcurrent protection, see Section 3.5.2 Constant C for the No.2 zero sequence IDMT overcurrent protection, see Section 3.5.2 Constant for the No.2 zero sequence IDMT overcurrent protection, see Section 3.5.2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~2 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s 0.001~120.0 0.00~1.00 0.01~3.00 1 1 1 0.001A 0.001s 1 1 1 1 1 0.001 0.001s 0.0001 0.0001 0.0001

NOTE! 1. The setting [A.50/51Gx.Opt_Dir] (x: 1~4) is used to select the directional mode for the No.2 stage x (x: 1~4) zero sequence overcurrent protection respectively. 0 is the non-directional mode; 1 is the forward directional mode; and 2 is the reverse directional mode.

7.3.3 Negative Sequence Overcurrent Protection Settings


The negative sequence overcurrent protection settings (in the submenu NegOC Settings) are used to determine the characteristic of the negative sequence overcurrent protection. All the settings of the negative sequence overcurrent protection are listed in the following table.

PCS-9611 Feeder Relay Date: 2011-08-29

7-9

7 Settings No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Menu text 50/51Q1.I2_Set 50/51Q1.t_Op 50/51Q1.En 50/51Q1.OutMap 50/51Q2.I2_Set 50/51Q2.t_Op 50/51Q2.En 50/51Q2.OutMap 50/51Q2.Opt_Curve 50/51Q2.TMS 50/51Q2.tmin 50/51Q2.K 50/51Q2.C 50/51Q2.Alpha Explanation The current setting of the stage 1 negative sequence overcurrent protection The time setting of the stage 1 negative sequence overcurrent protection The logic setting of the stage 1 negative sequence overcurrent protection The output matrix setting of the stage 1 negative sequence overcurrent protection The current setting of the stage 2 negative sequence overcurrent protection The time setting of the stage 2 negative sequence overcurrent protection The logic setting of the stage 2 negative sequence overcurrent protection The output matrix setting of the stage 2 negative sequence overcurrent protection The setting is for selecting the inverse time characteristic curve for the NOC2 protection The time multiplier setting of the negative sequence IDMT overcurrent protection The minimum operation time setting of the negative sequence IDMT overcurrent protection Constant k for the negative sequence IDMT overcurrent protection, see Section 3.7.2 Constant C for the negative sequence IDMT overcurrent protection, see Section 3.7.2 Constant for the negative sequence IDMT overcurrent protection, see Section 3.7.2 Range 0.05In~4In 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~4In 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s 0.001~120.0 0.00~1.00 0.01~3.00 Step 0.001A 0.001s 1 1 0.001A 0.001s 1 1 1 0.001 0.001s 0.0001 0.0001 0.0001

7.3.4 Sensitive Earth Fault Protection Settings


The sensitive earth fault protection settings (in the submenu SEF Settings) are used to determine the characteristic of the sensitive earth fault protection. All the settings of the sensitive earth fault protection are listed in the following table.
No. 1 Menu text 50/51SEF.RCA Explanation The relay characteristic angle for the directional sensitive earth fault protection The logic setting of the function which blocks the 2 50/51SEF.En_VTS_Blk SEF protection related voltage measurement when the voltage transformer is failed 3 50/51SEF1.3I0_Set The current setting of the stage 1 sensitive earth fault protection 0.005~0.4A 0.001A 0~1 1 Range -180~179 Step 1

7-10
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 50/51SEF1.t_Op 50/51SEF1.Opt_Dir 50/51SEF1.En 50/51SEF1.OutMap 50/51SEF2.3I0_Set 50/51SEF2.t_Op 50/51SEF2.Opt_Dir 50/51SEF2.En 50/51SEF2.OutMap 50/51SEF3.3I0_Set 50/51SEF3.t_Op 50/51SEF3.Opt_Dir 50/51SEF3.En 50/51SEF3.OutMap 50/51SEF4.3I0_Set 50/51SEF4.t_Op 50/51SEF4.Opt_Dir 50/51SEF4.En 50/51SEF4.OutMap 50/51SEF4.Opt_Curve 50/51SEF4.TMS 50/51SEF4.tmin The time setting of the stage 1 sensitive earth fault protection The setting is used to select the directional mode for the stage 1 SEF protection, see Section 3.6.3 The logic setting of the stage 1 sensitive earth fault protection The output matrix setting of the stage 1 sensitive earth fault protection The current setting of the stage 2 sensitive earth fault protection The time setting of the stage 2 sensitive earth fault protection The setting is used to select the directional mode for the stage 2 SEF protection, see Section 3.6.3 The logic setting of the stage 2 sensitive earth fault protection The output matrix setting of the stage 2 sensitive earth fault protection The current setting of the stage 3 sensitive earth fault protection The time setting of the stage 3 sensitive earth fault protection The setting is used to select the directional mode for the stage 3 SEF protection, see Section 3.6.3 The logic setting of the stage 3 sensitive earth fault protection The output matrix setting of the stage 3 sensitive earth fault protection The current setting of the stage 4 sensitive earth fault protection The time setting of the stage 4 sensitive earth fault protection The setting is used to select the directional mode for the stage 4 SEF protection, see Section 3.6.3 The logic setting of the stage 4 sensitive earth fault protection The output matrix setting of the stage 4 sensitive earth fault protection The setting is for selecting the inverse time characteristic curve for SEF4 protection The time multiplier setting of the IDMT sensitive earth fault protection The minimum operation time setting of the IDMT sensitive earth fault protection 0~100s 0~2 0~1 0x00000000 ~ 0x7FFFFFFF 0.005~0.4A 0~100s 0~2 0~1 0x00000000 ~ 0x7FFFFFFF 0.005~0.4A 0~100s 0~2 0~1 0x00000000 ~ 0x7FFFFFFF 0.005~0.4A 0~100s 0~2 0~1 0x00000000 ~ 0x7FFFFFFF 0~13 0.05~100.0 0~100s 0.001s 1 1 1 0.001A 0.001s 1 1 1 0.001A 0.001s 1 1 1 0.001A 0.001s 1 1 1 1 0.001 0.001s

PCS-9611 Feeder Relay Date: 2011-08-29

7-11

7 Settings 26 27 28 50/51SEF4.K 50/51SEF4.C 50/51SEF4.Alpha Constant k for the IDMT sensitive earth fault protection, see Section 3.6.2 Constant C for the IDMT sensitive earth fault protection, see Section 3.6.2 Constant for the IDMT sensitive earth fault protection, see Section 3.6.2 0.001~120.0 0.00~1.00 0.01~3.00 0.0001 0.0001 0.0001

NOTE! 1. The setting [50/51SEFx.Opt_Dir] (x: 1~4) is used to select the directional mode for the stage x (x: 1~4) sensitive earth fault protection respectively. 0 is the non-directional mode; 1 is the forward directional mode; and 2 is the reverse directional mode.

7.3.5 Breaker Failure Protection Settings


The breaker failure protection settings (in the submenu BFP Settings) are used to determine the characteristic of the breaker failure protection. All the settings of the breaker failure protection are listed in the following table.
No. 1 2 3 4 5 6 7 8 Menu text 50BF.I_Set 50BF.t_Op 50BF.t_ReTrp 50BF.Opt_LogicMode 50BF.En 50BF.En_ReTrp 50BF.OutMap 50BF.OutMap_ReTrp protection The time setting of the breaker failure protection The re-trip time setting of the breaker failure protection The setting for selecting the criteria logic of the breaker failure protection The logic setting of the breaker failure protection The logic setting of the re-trip function of the breaker failure protection The output matrix setting of the breaker failure protection The output matrix setting of the re-trip function of the breaker failure protection Explanation The current setting of the breaker failure Range 0.05In~5.0In 0~100s 0~100s 1~4 0~1 0~1 0x00000000 ~ 0x7FFFFFFF 0x00000000 ~ 0x7FFFFFFF Step 0.001A 0.001s 0.001s 1 1 1 1 1

NOTE! 1. The setting [50BF.Opt_LogicMode] is used to select the criteria logic of the breaker failure protection. Four criteria logics based on the phase currents and the circuit breaker state (based on the binary input [BI_52b]) are supported in this relay. The two criteria conditions are list as below: (A) The maximum phase current is greater than the setting [50BF.I_Set]. (B) The circuit breaker is still closed ([BI_52b] = 0).
7-12
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings Setting Value 1 2 3 4 NOT([BI_52b]) (Ipmax > [50BF.I_Set]) OR (NOT([BI_52b])) (Ipmax > [50BF.I_Set]) AND (NOT([BI_52b])) Criteria Condition Logic Ipmax > [50BF.I_Set] Only A Only B A OR B A AND B

7.3.6 Broken Conductor Protection Settings


The broken conductor protection settings (in the submenu BrknCond Settings) are used to determine the characteristic of the broken conductor protection. All the settings of the broken conductor protection are listed in the following table.
No. 1 2 3 4 Menu text 50BC.I2/I1_Set 50BC.t_Op 50BC.En 50BC.OutMap protection The time setting for the broken conductor protection The logic setting for the broken conductor protection The output matrix setting of the broken conductor protection Explanation The ratio setting for the broken conductor Range 0.10~1.00 0~200s 0~1 0x00000000 ~ 0x7FFFFFFF Step 0.001 0.001s 1 1

7.3.7 Cold Load Pickup Settings


The cold load pickup logic settings (in the submenu CLP Settings) are used to determine the characteristic of the cold load pickup logic. All the settings of the cold load pickup logic are listed in the following table
No. 1 2 3 4 5 6 7 8 Menu text CLP.Opt_LogicMode CLP.t_Cold CLP.t_Rst CLP.t_ShortRst CLP.En 50/51P1.CLP.IMult 50/51P1.CLP.t_Op 50/51P2.CLP.IMult Explanation The setting for selecting the cold load condition The time setting for ensuring the cold load condition is met The time setting for resetting the cold load pickup logic The time setting for fast resetting the cold load pickup logic The logic setting of the cold load pickup logic function The multiple setting of the stage 1 overcurrent protection when CLP is active The time setting of the stage 1 overcurrent protection when CLP is active The multiple setting of the stage 2 overcurrent protection when CLP is active 1~2 0~4000s 0~4000s 0~600s 0~1 1.00~10.00 0~100s 1.00~10.00 Range 1 0.001s 0.001s 0.001s 1 0.001 0.001s 0.001 Step

PCS-9611 Feeder Relay Date: 2011-08-29

7-13

7 Settings 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 50/51P2.CLP.t_Op 50/51P3.CLP.IMult 50/51P3.CLP.t_Op 50/51P4.CLP.IMult 50/51P4.CLP.t_Op 50/51P4.CLP.TMS 50/51G1.CLP.IMult 50/51G1.CLP.t_Op 50/51G2.CLP.IMult 50/51G2.CLP.t_Op 50/51G3.CLP.IMult 50/51G3.CLP.t_Op 50/51G4.CLP.IMult 50/51G4.CLP.t_Op 50/51G1.CLP.TMS The time setting of the stage 2 overcurrent protection when CLP is active The multiple setting of the stage 3 overcurrent protection when CLP is active The time setting of the stage 3 overcurrent protection when CLP is active The multiple setting of the stage 4 overcurrent protection when CLP is active The time setting of the stage 4 overcurrent protection when CLP is active The time multiplier setting of the IDMT overcurrent protection when CLP is active The multiple setting of the stage 1 zero sequence overcurrent protection when CLP is active The time setting of the stage 1 zero sequence overcurrent protection when CLP is active The multiple setting of the stage 2 zero sequence overcurrent protection when CLP is active The time setting of the stage 2 zero sequence overcurrent protection when CLP is active The multiple setting of the stage 3 zero sequence overcurrent protection when CLP is active The time setting of the stage 3 zero sequence overcurrent protection when CLP is active The multiple setting of the stage 4 zero sequence overcurrent protection when CLP is active The time setting of the stage 4 zero sequence overcurrent protection when CLP is active The time multiplier setting of the zero sequence IDMT overcurrent protection when CLP is active 0~100s 1.00~10.00 0~100s 1.00~10.00 0~100s 0.05~100.0 1.00~10.00 0~100s 1.00~10.00 0~100s 1.00~10.00 0~100s 1.00~10.00 0~100s 0.05~100.0 0.001s 0.001 0.001s 0.001 0.001s 0.001 0.001 0.001s 0.001 0.001s 0.001 0.001s 0.001 0.001s 0.001

7.3.8 SOTF Protection Settings


The SOTF protection settings (in the submenu SOTF Settings) are used to determine the characteristic of the SOTF protection. All the settings of the SOTF protection are listed in the following table.
No. 1 2 3 Menu text SOTF.t_En SOTF.Opt_Mode 50PSOTF.I_Set Explanation The enabling time setting of the SOTF protection The setting for selecting the acceleration tripping mode of the SOTF protection The current setting of the SOTF overcurrent protection Range 0~100s 0~1 0.05In~30In Step 0.001s 1 0.001A

7-14
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings 4 5 6 7 8 9 10 50PSOTF.t_Op 50PSOTF.En 50PSOTF.OutMap 50GSOTF.3I0_Set 50GSOTF.t_Op 50GSOTF.En 50GSOTF.OutMap The time setting of the SOTF overcurrent protection The logic setting of the SOTF overcurrent protection The output matrix setting of the SOTF overcurrent protection The current setting of the zero sequence SOTF overcurrent protection The time setting of the zero sequence SOTF overcurrent protection The logic setting of the zero sequence SOTF overcurrent protection The output matrix setting of the zero sequence SOTF overcurrent protection 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0.05In~30In 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0.001s 1 1 0.001A 0.001s 1 1

NOTE! 1. The setting [SOTF.t_En] is used to enable the SOTF protection for the appointed time delay, when the enabling conditions are satisfied (See Section 3.10). The setting [SOTF.Opt_Mode] is used for selecting the acceleration tripping mode of the SOTF protection. Setting as 1 means accelerated tripping before auto-reclosing; and setting as 0 means accelerated tripping after auto-reclosing.

2.

7.3.9 Thermal Overload Protection Settings


The thermal overload protection settings (in submenu ThOvLd Settings) are used to determine the characteristic of the thermal overload protection. All the settings of the thermal overload protection are listed in the following table.
No. 1 2 Menu text 49.Ib_Set 49.Tau Explanation The reference current setting of the thermal overload protection The time constant setting of the IDMT overload protection The factor setting of the thermal overload 3 49.K_Trp protection which is associated to the thermal state formula The factor setting of the thermal overload alarm 4 49.K_Alm element which is associated to the thermal state formula 5 6 49.En_Trp 49.En_Alm The logic setting of the thermal overload protection for tripping The logic setting of the thermal overload protection for alarming 0~1 0~1 1 1 1.0~3.0 0.001 1.0~3.0 0.001 Range 0.05In~3.0In 10~6000s Step 0.001A 0.001s

PCS-9611 Feeder Relay Date: 2011-08-29

7-15

7 Settings 7 49.OutMap The output matrix setting of the thermal overload protection 0x00000000 ~ 0x7FFFFFFF 1

7.3.10 Overvoltage and Undervoltage Protection Settings


The overvoltage and undervoltage protection settings (in the submenu Voltage Settings) are used to determine the characteristic of the overvoltage and undervoltage protections. All the settings of the overvoltage and undervoltage protections are listed in the following table.
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Menu text 27P.Opt_1P/3P 27P.Opt_Up/Upp 27P1.U_Set 27P1.t_Op 27P1.K_DropOut 27P1.En 27P1.OutMap 27P2.U_Set 27P2.t_Op 27P2.K_DropOut 27P2.En 27P2.OutMap 59P.Opt_1P/3P 59P.Opt_Up/Upp 59P1.U_Set 59P1.t_Op 59P1.K_DropOut The setting for Explanation selecting the undervoltage protection calculation method The setting for selecting the voltage input mode for the undervoltage protection The voltage setting of the stage 1 undervoltage protection The time setting of the stage 1 undervoltage protection The dropout coefficient setting of the stage 1 undervoltage protection The logic setting of the stage 1 undervoltage protection The output matrix setting of the stage 1 undervoltage protection The voltage setting of the stage 2 undervoltage protection The time setting of the stage 2 undervoltage protection The dropout coefficient setting of the stage 2 undervoltage protection The logic setting of the stage 2 undervoltage protection The output matrix setting of the stage 2 undervoltage protection The setting for selecting the overvoltage protection calculation method The setting for selecting the voltage input mode for the overvoltage protection The voltage setting of the stage 1 overvoltage protection The time setting of the stage 1 overvoltage protection The dropout coefficient setting of the stage 1 overvoltage protection 0~1 0~1 2~120V 0~100s 1.03~3.0 0~1 0x00000000 ~ 0x7FFFFFFF 2~120V 0~100s 1.03~3.0 0~1 0x00000000 ~ 0x7FFFFFFF 0~1 0~1 57.7~200V 0~100s 0.93~0.97 Range 1 1 0.001V 0.001s 0.001 1 1 0.001V 0.001s 0.001 1 1 1 1 0.001V 0.001s 0.001 Step

7-16
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings 18 19 20 21 22 23 24 59P1.En 59P1.OutMap 59P2.U_Set 59P2.t_Op 59P2.K_DropOut 59P2.En 59P2.OutMap The logic setting of the stage 1 overvoltage protection The output matrix setting of the stage 1 overvoltage protection The voltage setting of the stage 2 overvoltage protection The time setting of the stage 2 overvoltage protection The dropout coefficient setting of the stage 2 overvoltage protection The logic setting of the stage 2 overvoltage protection The output matrix setting of the stage 2 overvoltage protection 0~1 0x00000000 ~ 0x7FFFFFFF 57.7~200V 0~100s 0.93~0.97 0~1 0x00000000 ~ 0x7FFFFFFF 1 1 0.001V 0.001s 0.001 1 1

NOTE! 1. See Section 3.12 and Section 3.13 for more details about the settings [27P.Opt_1P/3P], [27P.Opt_Up/Upp], [59P.Opt_1P/3P] and [59P.Opt_Up/Upp].

7.3.11 Negative Sequence Overvoltage Protection Settings


The negative sequence overvoltage protection settings (in the submenu NegOV Settings) are used to determine the characteristic of the negative sequence overvoltage protection. All the settings of the negative sequence overvoltage protection are listed in the following table.
No. 1 2 3 4 Menu text 59Q.U2_Set 59Q.t_Op 59Q.En 59Q.OutMap Explanation The voltage setting of the negative sequence overvoltage protection The time setting of the negative sequence overvoltage protection The logic setting of the negative sequence overvoltage protection The output matrix setting of the negative sequence overvoltage protection Range 2~120V 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF Step 0.001V 0.001s 1 1

7.3.12 Zero Sequence Overvoltage Protection Settings


The zero sequence overvoltage protection settings (in the submenu ROV Settings) are used to determine the characteristic of the zero sequence overvoltage protection. All the settings of the zero sequence overvoltage protection are listed in the following table.
No. 1 Menu text 59G1.3U0_Set Explanation The voltage setting of the stage 1 zero sequence overvoltage protection Range 2~160V Step 0.001V

PCS-9611 Feeder Relay Date: 2011-08-29

7-17

7 Settings 2 3 4 5 6 7 8 59G1.t_Op 59G1.En 59G1.OutMap 59G2.3U0_Set 59G2.t_Op 59G2.En 59G2.OutMap The time setting of the stage 1 zero sequence overvoltage protection The logic setting of the stage 1 zero sequence overvoltage protection The output matrix setting of the stage 1 zero sequence overvoltage protection The voltage setting of the stage 2 zero sequence overvoltage protection The time setting of the stage 2 zero sequence overvoltage protection The logic setting of the stage 2 zero sequence overvoltage protection The output matrix setting of the stage 2 zero sequence overvoltage protection 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 2~160V 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 0.001s 1 1 0.001V 0.001s 1 1

7.3.13 Frequency Protection Settings


The frequency protection settings (in the submenu FreqProt Settings) are used to determine the characteristic of the frequency protection. All the settings of the frequency protection are listed in the following table.
No. 1 2 3 4 5 6 7 8 9 10 11 Menu text 81.Upp_VCE 81U1.f_Set 81U1.t_Op 81U1.En 81U1.OutMap 81U2.f_Set 81U2.t_Op 81U2.En 81U2.OutMap 81U3.f_Set 81U3.t_Op Explanation The setting of the low voltage blocking element of the frequency protection (phase-to-phase voltage) The frequency setting of the stage 1 under-frequency protection The time setting of the stage 1 under-frequency protection The logic setting of the stage 1 under-frequency protection The output matrix setting of the stage 1 under-frequency protection The frequency setting of the stage 2 under-frequency protection The time setting of the stage 2 under-frequency protection The logic setting of the stage 2 under-frequency protection The output matrix setting of the stage 2 under-frequency protection The frequency setting of the stage 3 under-frequency protection The time setting of the stage 3 under-frequency protection Range 10~120V 45~60Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 45~60Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 45~60Hz 0~100s Step 0.001V 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s

7-18
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 81U3.En 81U3.OutMap 81U4.f_Set 81U4.t_Op 81U4.En 81U4.OutMap 81O1.f_Set 81O1.t_Op 81O1.En 81O1.OutMap 81O2.f_Set 81O2.t_Op 81O2.En 81O2.OutMap 81O3.f_Set 81O3.t_Op 81O3.En 81O3.OutMap 81O4.f_Set 81O4.t_Op 81O4.En 81O4.OutMap The logic setting of the stage 3 under-frequency protection The output matrix setting of the stage 3 under-frequency protection The frequency setting of the stage 4 under-frequency protection The time setting of the stage 4 under-frequency protection The logic setting of the stage 4 under-frequency protection The output matrix setting of the stage 4 under-frequency protection The frequency setting of the stage 1 over-frequency protection The time setting of the stage 1 over-frequency protection The logic setting of the stage 1 over-frequency protection The output matrix setting of the stage 1 over-frequency protection The frequency setting of the stage 2 over-frequency protection The time setting of the stage 2 over-frequency protection The logic setting of the stage 2 over-frequency protection The output matrix setting of the stage 2 over-frequency protection The frequency setting of the stage 3 over-frequency protection The time setting of the stage 3 over-frequency protection The logic setting of the stage 3 over-frequency protection The output matrix setting of the stage 3 over-frequency protection The frequency setting of the stage 4 over-frequency protection The time setting of the stage 4 over-frequency protection The logic setting of the stage 4 over-frequency protection The output matrix setting of the stage 4 over-frequency protection 0~1 0x00000000 ~ 0x7FFFFFFF 45~60Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 50~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 50~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 50~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 50~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1 0.001Hz 0.001s 1 1

PCS-9611 Feeder Relay Date: 2011-08-29

7-19

7 Settings 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 81R.dt_Set 81R1.df/dt_Set 81R1.f_Pkp 81R1.t_Op 81R1.En 81R1.OutMap 81R2.df/dt_Set 81R2.f_Pkp 81R2.t_Op 81R2.En 81R2.OutMap 81R3.df/dt_Set 81R3.f_Pkp 81R3.t_Op 81R3.En 81R3.OutMap 81R4.df/dt_Set 81R4.f_Pkp 81R4.t_Op 81R4.En 81R4.OutMap The cycle number for the calculation of the frequency rate-of-change protection The setting of the stage 1 frequency rate-of-change protection The pickup frequency setting of the stage 1 frequency rate-of-change protection The time setting of the stage 1 frequency rate-of-change protection The logic setting of the stage 1 frequency rate-of-change protection The output matrix setting of the stage 1 frequency rate-of-change protection The setting of the stage 2 frequency rate-of-change protection The pickup frequency setting of the stage 2 frequency rate-of-change protection The time setting of the stage 2 frequency rate-of-change protection The logic setting of the stage 2 frequency rate-of-change protection The output matrix setting of the stage 2 frequency rate-of-change protection The setting of the stage 3 frequency rate-of-change protection The pickup frequency setting of the stage 3 frequency rate-of-change protection The time setting of the stage 3 frequency rate-of-change protection The logic setting of the stage 3 frequency rate-of-change protection The output matrix setting of the stage 3 frequency rate-of-change protection The setting of the stage 4 frequency rate-of-change protection The pickup frequency setting of the stage 4 frequency rate-of-change protection The time setting of the stage 4 frequency rate-of-change protection The logic setting of the stage 4 frequency rate-of-change protection The output matrix setting of the stage 4 frequency rate-of-change protection 3~8 -10~10Hz/s 45~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF -10~10Hz/s 45~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF -10~10Hz/s 45~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF -10~10Hz/s 45~65Hz 0~100s 0~1 0x00000000 ~ 0x7FFFFFFF 1 0.001 Hz/s 0.001Hz 0.001s 1 1 0.001 Hz/s 0.001Hz 0.001s 1 1 0.001 Hz/s 0.001Hz 0.001s 1 1 0.001 Hz/s 0.001Hz 0.001s 1 1

7-20
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings

7.3.14 Auto-recloser Settings


The auto-recloser settings (in submenu AR Settings) are used to determine the characteristic of the auto-recloser. All the settings of the auto-recloser are listed in the following table.
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Menu text 79.t_CBClsd 79.t_DDO_BlkAR 79.t_CBReady 79.t_Fail 79.t_3PS1 79.t_3PS2 79.t_3PS3 79.t_3PS4 79.t_Reclaim 79.t_DDO_AR 79.N_Rcls 79.En_SynChk 79.En_DdChk 79.En_FailChk 79.En 79.OutMap Explanation The time setting of the minimum time delay for ensuring the CB is closed The time pulse width for ensuring the AR blocking signal The time setting of the time delay for ensuring the CB is ready The time setting of the time delay for checking the CB position The time setting of the 1st shot auto-recloser The time setting of the 2
nd rd th

Range 0.01~600s 0.01~600s 0.01~600s 0.01~600s 0~600s 0~600s 0~600s 0~600s 0~600s 0-4.00s 1~4 0~1 0~1 0~1 0~1 0x00000000 ~ 0x7FFFFFFF

Step 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 1 1 1 1 1 1

shot auto-recloser

The time setting of the 3 shot auto-recloser The time setting of the 4 shot auto-recloser The reclaim time setting of the auto-recloser The pulse width of the auto-recloser The shot number setting of the auto-recloser The logic setting of the synchronism check function of the auto-recloser The logic setting of the dead check function of the auto-recloser The logic setting of the CB position check function of the auto-recloser The logic setting of the auto-recloser The output matrix setting of the auto-recloser

NOTE! 1. If the settings [79.En_SynChk] and [79.En_DdChk] are both set as 0, it means that the non-check mode is applied in the auto-reclosing logic.

7.3.15 Mechanical Protection Settings


The auto-recloser settings (in submenu MR Prot Settings) are used to determine the characteristic of the mechanical protection. All the settings of the mechanical protection are listed in the following table.

PCS-9611 Feeder Relay Date: 2011-08-29

7-21

7 Settings No. 1 2 3 4 5 6 7 8 9 10 11 12 Menu text MR1.t_MR MR1.En MR1.OutMap MR2.t_MR MR2.En MR2.OutMap MR3.t_MR MR3.En MR3.OutMap MR4.t_MR MR4.En MR4.OutMap The time protection The logic setting of the No.1 mechanical protection The output matrix setting of the No.1 mechanical protection The time setting of the No.2 mechanical protection The logic setting of the No.2 mechanical protection The output matrix setting of the No.2 mechanical protection The time setting of the No.3 mechanical protection The logic setting of the No.3 mechanical protection The output matrix setting of the No.3 mechanical protection The time setting of the No.4 mechanical protection The logic setting of the No.4 mechanical protection The output matrix setting of the No.4 mechanical protection Explanation setting of the No.1 mechanical Range 0~4000s 0~1 0x00000000 ~ 0x7FFFFFFF 0~4000s 0~1 0x00000000 ~ 0x7FFFFFFF 0~4000s 0~1 0x00000000 ~ 0x7FFFFFFF 0~4000s 0~1 0x00000000 ~ 0x7FFFFFFF Step 0.001s 1 1 0.001s 1 1 0.001s 1 1 0.001s 1 1

7.3.16 Supervision Element Settings


The supervision element settings (in the submenu Superv Settings) are used to determine the parameters of the supervision element. All the settings of the supervision element are listed in the following table.
No. 1 2 3 4 5 6 7 Menu text CTS.3I0_Set CTS.3U0_Set CTS.En VTS.I_Set VTS.I2_Set VTS.En VTS.En_SynVT Explanation The threshold current setting of the CTS element The threshold voltage setting of the CTS element The logic setting of the CTS element The phase current setting of the protection VTS element The negative sequence current setting of the protection VTS element The logic setting of the protection VTS element The logic setting of the synchro-check VTS element Range 0.05In~30In 0.01~120V 0~1 0.05In~30In 0.05In~30In 0~1 0~1 Step 0.001A 0.001V 1 0.001A 0.001A 1 1

7-22
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings

7.3.17 Binary Output Matrix Settings


The binary output matrix settings (in the submenu CfgBO Settings) are used to determine the parameters of the last eight binary outputs in module NR4304 and NR4521. All the settings of the binary outputs are listed in the following table.
No. 1 2 3 4 5 6 7 8 9 10 11 12 Menu text B09.BO_03.t_Dwell B09.BO_04.t_Dwell B09.BO_05.t_Dwell B09.BO_06.t_Dwell B09.BO_07.t_Dwell B09.BO_08.t_Dwell B06.BO_01.t_Dwell B06.BO_02.t_Dwell B06.BO_03.t_Dwell B06.BO_04.t_Dwell B06.BO_05.t_Dwell B06.BO_06.t_Dwell Explanation The dwell time of the output B09.BO_03 The dwell time of the output B09.BO_04" The dwell time of the output B09.BO_05 The dwell time of the output B09.BO_06 The dwell time of the output B09.BO_07 The dwell time of the output B09.BO_08 The dwell time of the output B06.BO_01 The dwell time of the output B06.BO_02 The dwell time of the output B06.BO_03 The dwell time of the output B06.BO_04 The dwell time of the output B06.BO_05 The dwell time of the output B06.BO_06 Range 0~100s 0~100s 0~100s 0~100s 0~100s 0~100s 0~100s 0~100s 0~100s 0~100s 0~100s 0~100s Step 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s 0.001s

NOTE! 1. The setting [Bxx.BO_xx.t_Dwell] (x: a number; 1, 2 etc.) is used to set the dwell time of the relevant binary output in module NR4304 and NR4521.

7.4 Monitor and Control Settings


The monitor and control settings (in the submenu Mon\Ctrl Settings) are used to determine the parameters of the monitor and control function of this relay.

7.4.1 Closing Synchronism Check Settings


The closing synchronism check settings (in the submenu Syn Settings) are used to determine the settings of the closing synchronism check function. All the settings of the closing synchronism check function are listed in the following table.
No. 1 2 3 4 Menu text 25.U_Dd 25.U_Lv 25.U_Comp 25.phi_Comp Explanation The voltage setting of the system dead check The voltage setting of the system live check The compensation coefficient setting of the synchro-check voltage The compensation phase angle setting of the synchro-check voltage Range 2~120V 2~120V 0.2~5.0 0~360 Step 0.001V 0.001V 0.001 1

PCS-9611 Feeder Relay Date: 2011-08-29

7-23

7 Settings 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 25.Opt_Usyn 25.t_ClsCB 25M.U_Diff 25M.f_Diff 25M.df/dt 25M.phi_Diff 25M.t_Wait 25M.Opt_DdChk 25M.En_SynChk 25M.En_DdChk 25A.U_Diff 25A.f_Diff 25A.phi_Diff 25A.t_Wait 25A.Opt_DdChk 25A.t_DdChk 25A.t_SynChk The voltage type setting of the synchronism check closing function The circuit breaker closing time setting of the closing synchronism check function The voltage difference setting of the manual closing synchronism check function The frequency difference setting of the manual closing synchronism check function The frequency rate-of-change setting of the manual closing synchronism check function The phase angle difference setting of the manual closing synchronism check function The waiting time setting of the manual closing synchronism check function The setting for selecting the dead check mode of the manual closing function The logic setting of the synchronism check function of the manual closing function The logic setting of the dead check function of the manual closing function The voltage difference setting of the auto-closing synchronism check function The frequency difference setting of the auto-closing synchronism check function The phase angle difference setting of the auto-closing synchronism check function The waiting time setting of the auto-closing synchronism check function The setting for selecting the dead check mode of the auto-closing synchronism check function The time setting of the dead check function of the auto-closer The time setting of the synchronism check function of the auto-closer 0~5 0.02~1.00s 2~120V 0~2Hz 0~3Hz/s 0~60 0.01~60s 1~7 0~1 0~1 2~120V 0~2Hz 0~60 0.01~60s 1~7 0.01~25s 0.01~25s 1 0.001s 0.001V 0.001Hz 0.001 Hz/s 1 0.001s 1 1 1 0.001V 0.001Hz 1 0.001s 1 0.001s 0.001s

NOTE! 1. The settings [25.U_Comp] and [25.phi_Comp] are used to compensate the synchro-check voltage, and make the compensated synchro-check voltage is equal to the corresponding protection voltage in normal operation situation. The settings [25.U_Comp] and [25.phi_Comp] can be set according to following formula.

7-24
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings

[25.U _ Comp] = U Pr ot _ Normal U Syn _ Normal [25. phi _ Comp ] = Pr ot _ Normal Syn _ Normal
In general application, the setting [25.U_Comp] is set as 1.000, and the setting [25.phi_Comp] is set as 0. For example, the synchro-check voltage and the protection are gotten from different sides of a power transformer respectively. Synchro-check VT: 400kV Primary, 110V Secondary Protection VT: 200kV Primary, 100V Secondary Power transformer: 400kV / 200kV, vector group Yd11 The synchro-check VT supplies 110V secondary rated voltage while the protection VT supplies 100V secondary rated voltage. Therefore, this difference must be balanced: [25.U_Comp] = 100V / 110V = 0.91 The transformer vector group is defined from the high voltage side to the low voltage side. In this example, the synchro-check voltage is one of the voltages of the high voltage side, i.e. the compensation angle setting is 30 (according to the vector group): [25.phi_Comp] = 30 2. The setting [25.Opt_Usyn] is used to select the synchro-check voltage source of the synchronism check element, and this relay can use the corresponding protection voltage for the synchronism check element.
Setting Value Voltage Type 0 Ua 1 Ub 2 Uc 3 Uab 4 Ubc 5 Uca

7.4.2 Manual Control Settings


The manual control settings (in the submenu Control Settings) are used to determine the parameters of the manual control function (local or remote closing and tripping). All the settings of the manual control are listed in the following table.
No. 1 2 3 4 Menu text Ctrl1.t_PW_Opn Ctrl1.t_PW_Cls Ctrl1.OutMap_Opn Ctrl1.OutMap_Cls tripping element The output pulse width of the No.1 manual closing element The output matrix setting of the No.1 manual tripping element The output matrix setting of the No.1 manual closing element Explanation The output pulse width of the No.1 manual Range 0.1~99.0s 0.1~99.0s 0x00000000 ~ 0x7FFFFFFF 0x00000000 ~ 0x7FFFFFFF Step 0.001s 0.001s 1 1

PCS-9611 Feeder Relay Date: 2011-08-29

7-25

7 Settings 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Ctrl2.t_PW_Opn Ctrl2.t_PW_Cls Ctrl2.OutMap_Opn Ctrl2.OutMap_Cls Ctrl3.t_PW_Opn Ctrl3.t_PW_Cls Ctrl3.OutMap_Opn Ctrl3.OutMap_Cls Ctrl4.t_PW_Opn Ctrl4.t_PW_Cls Ctrl4.OutMap_Opn Ctrl4.OutMap_Cls Ctrl5.t_PW_Opn Ctrl5.t_PW_Cls Ctrl5.OutMap_Opn Ctrl5.OutMap_Cls The output pulse width of the No.2 manual tripping element The output pulse width of the No.2 manual closing element The output matrix setting of the No.2 manual tripping element The output matrix setting of the No.2 manual closing element The output pulse width of the No.3 manual tripping element The output pulse width of the No.3 manual closing element The output matrix setting of the No.3 manual tripping element The output matrix setting of the No.3 manual closing element The output pulse width of the No.4 manual tripping element The output pulse width of the No.4 manual closing element The output matrix setting of the No.4 manual tripping element The output matrix setting of the No.4 manual closing element The output pulse width of the No.5 manual tripping element The output pulse width of the No.5 manual closing element The output matrix setting of the No.5 manual tripping element The output matrix setting of the No.5 manual closing element 0.1~99.0s 0.1~99.0s 0x00000000 ~ 0x7FFFFFFF 0x00000000 ~ 0x7FFFFFFF 0.1~99.0s 0.1~99.0s 0x00000000 ~ 0x7FFFFFFF 0x00000000 ~ 0x7FFFFFFF 0.1~99.0s 0.1~99.0s 0x00000000 ~ 0x7FFFFFFF 0x00000000 ~ 0x7FFFFFFF 0.1~99.0s 0.1~99.0s 0x00000000 ~ 0x7FFFFFFF 0x00000000 ~ 0x7FFFFFFF 0.001s 0.001s 1 1 0.001s 0.001s 1 1 0.001s 0.001s 1 1 0.001s 0.001s 1 1

7.4.3 Interlock Settings


The interlock settings (in the submenu Interlock Settings) are used to determine whether the interlock check of the manual control function (local or remote closing and tripping) is enabled. All the settings of the interlock check function are listed in the following table.
No. 1 2 Menu text Interlock1.En_BlkOpn Interlock1.En_BlkCls Explanation The logic setting of the interlock check of the No.1 manual tripping element The logic setting of the interlock check of the No.1 manual closing element 0~1 0~1 Range 1 1 Step

7-26
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings 3 4 5 6 7 8 9 10 Interlock2.En_BlkOpn Interlock2.En_BlkCls Interlock3.En_BlkOpn Interlock3.En_BlkCls Interlock4.En_BlkOpn Interlock4.En_BlkCls Interlock5.En_BlkOpn Interlock5.En_BlkCls The logic setting of the interlock check of the No.2 manual tripping element The logic setting of the interlock check of the No.2 manual closing element The logic setting of the interlock check of the No.3 manual tripping element The logic setting of the interlock check of the No.3 manual closing element The logic setting of the interlock check of the No.4 manual tripping element The logic setting of the interlock check of the No.4 manual closing element The logic setting of the interlock check of the No.5 manual tripping element The logic setting of the interlock check of the No.5 manual closing element 0~1 0~1 0~1 0~1 0~1 0~1 0~1 0~1 1 1 1 1 1 1 1 1

NOTE! 1. The interlock check function can be programmed through the PCS-PC configuration tool auxiliary software.

7.5 Logic Link Settings


The logic link settings (in the submenu Logic Links) are used to determine whether the relevant function of this relay is enabled or disabled. If this relay supports the logic link function, it will have a corresponding submenu in the submenu Logic Links for the logic link settings.

7.5.1 Function Link Settings


The function link settings (in the submenu Function Links) are used to determine whether the relevant functional elements are enabled or disabled.

7.5.2 GOOSE Link Settings


The GOOSE link settings (in the submenu GOOSE Links) are used to determine whether the relevant GOOSE elements are enabled or disabled. See the GOOSE related instruction manual for the more information and details.

7.5.3 SV Link Settings


The SV (sampled value) link settings (in the submenu SV Links) are used to determine whether the SV elements are enabled or disabled.

7.5.4 Spare Link Settings


The spare link settings (in the submenu Spare Links) are used for future application. It can be
PCS-9611 Feeder Relay Date: 2011-08-29

7-27

7 Settings

defined as one of above three link settings through the PCS-PC configuration tool.

7.6 Device Related Settings


The device related settings (in the submenu Device Setup) are used for setting the operation parameters and communication parameters of this device.

7.6.1 Device Settings


The device settings (in the submenu Device Settings) are used for setting the operation parameters of this device. The following table lists all the communication parameters.
No. 1 2 3 Menu text HDR_EncodeMode Opt_Caption_103 B07.Un_BinaryInput Explanation The encoding type of the HDR waveform file, it is only reserved for the manufacturer The language of the group caption when the IEC60870-5-103 is adopted The rated voltage value of the binary input 0~1 0~1 0~3 Range 1 1 1 Step

NOTE! 1. The setting [Opt_Caption_103] is used for selecting the language of the group caption when the IEC60870-5-103 protocol is adopted. If it is set as 0, the group caption language is English; and if it is set as 1, the group caption language is Chinese. The setting [B07.Un_BinaryInput] is used for selecting the rated voltage of the binary input.
Setting Value Rated Voltage 0 24V 1 48V 2 110V 3 220V

2.

7.6.2 Communication Settings


The communication settings (in the submenu Comm Settings) are used for communication with substation monitoring system, substation controlling system or remote SCADA. The following table lists all the communication parameters.
No. 1 2 3 4 5 6 7 8 7-28
Date: 2011-08-29

Menu text IP_LAN1 Mask_LAN1 IP_LAN2 Mask_LAN2 En_LAN2 IP_LAN3 Mask_LAN3 En_LAN3

Explanation The IP address of the No.1 Ethernet port The mask code of the No.1 Ethernet port The IP address of the No.2 Ethernet port The mask code of the No.2 Ethernet port The logic setting of the No.2 Ethernet network The IP address of the No.3 Ethernet port The mask code of the No.3 Ethernet port The logic setting of the No.3 Ethernet network

Range 000.000.000.000 ~255.255.255.255 000.000.000.000 ~255.255.255.255 0~1 000.000.000.000 ~255.255.255.255 0~1

PCS-9611 Feeder Relay

7 Settings 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 IP_LAN4 Mask_LAN4 En_LAN4 Gateway En_Broadcast Addr_RS485A Baud_RS485A Protocol_RS485A Addr_RS485B Baud_RS485B Protocol_RS485B Threshold_Measmt Period_Measmt Format_Measmt Baud_Printer En_AutoPrint Opt_TimeSyn IP_Server_SNTP OffsetHour_UTC OffsetMinute_UTC En_DaulNet_GOOSE The IP address of the No.4 Ethernet port The mask code of the No.4 Ethernet port The logic setting of the No.4 Ethernet network The IP address of the network gateway of this device The logic setting of the UDP broadcast function when the IEC60870-5-103 protocol is adopted The communication address of the serial port A The communication baud rate of the serial port A The communication protocol of the serial port A The communication address of the serial port B The communication baud rate of the serial port B The communication protocol of the serial port B The metering value change differentiate percent for uplink communication The time setting of circularly sending metering for the IEC60870-5-103 protocol The metering data format for the IEC60870-5-103 protocol The baud rate of the print port The logic setting of the auto-printing function The time synchronization mode The IP address of the SNTP server The hour code of the time zone The minute code of the time zone The logic setting of the dual-network GOOSE function 000.000.000.000 ~255.255.255.255 0~1 000.000.000.000 ~255.255.255.255 0~1 0 ~ 255 0~5 0~2 0 ~ 255 0~5 0~2 0 ~ 100 (%) 0 ~ 65535s 0~1 0~5 0~1 0~3 000.000.000.000 ~255.255.255.255 -12 ~ 12 0 ~ 60 0~1

NOTE! 1. Above table listed all the communication settings, the device delivered to the user maybe only show some settings of them according to the communication interface configuration. If only the Ethernet ports are applied, the settings about the serial ports (port A and port B) are not listed in this submenu. And the settings about the Ethernet ports only listed in this submenu according to the actual number of Ethernet ports. The standard arrangement of the Ethernet port is two, at most four (predetermined when ordering). Set the IP address according to actual arrangement of Ethernet numbers and the un-useful port/ports need not be configured. If the PCS-PC configuration tool auxiliary software is connected with this device through the Ethernet, the IP address of the PCS-PC must be set as one of the available IP address of this device. The setting [En_Broadcast] is used to enable or disable this relay to transmit the UDP broadcast messages when the IEC60870-5-103 protocol is adopted. If it is set as 0, this
7-29
Date: 2011-08-29

2.

3.

PCS-9611 Feeder Relay

7 Settings

relay does not transmit any UDP broadcast message; and if it is set as 1, this relay can transmit UDP broadcast messages. 4. The setting [Addr_RS485A] and [Addr_RS485B] are used to set the communication address of the serial ports (port A and port B); if a protocol over serial communication is adopted. The settings [Baud_RS485A], [Baud_RS485B] and [Baud_Printer] are respectively used to set the communication baudrate of each serial port (port A, port B and print port).
Setting Value 0 4800 1 9600 2 19200 3 38400 4 57600 5 115200

5.

Baudrate (bsp) 6.

The settings [Protocol_RS485A] and [Protocol_RS485B] are respectively used to set the communication protocol of each serial port (port A and port B).
Setting Value 0 2 Protocol IEC60870-5-103 Modbus Setting Value 1 Other Protocol Reserved Not available

7.

The setting [Threshold_Measmt] is used to decide whether the present metering value is sends forward. Only the change percent of a metering value is greater than this setting, the relevant metering value can be sent forward. The circle time for sending telemetering [Period_Measmt]: It represents the time period when this device sends metering data forward. When this setting is set as 0, it means that the equipment will not send metering data forward at a fixed time (the inquiry issued by SCADA still can be responded during this period). This setting may be set according to actual field condition and can be set as 0 when the communication function is not used. The default value is 0 when the equipment is delivered. The setting [Format_Measmt] is used to select the metering data format in the GDD (Generic Data Description) message when the IEC60870-5-103 protocol is adopted. If it is set as 0, the metering data format type is 12 (Measurand with Quality Descriptor); and if it is set as 1, the metering data format type is 7 (R32.23, IEEE 754).

8.

9.

10. The setting [Opt_TimeSyn] is used to select the external time synchronization source.
Setting Value 0 1 2 3 External Time Synchronization Mode Electrical signal time synchronization mode: PPS signal (RS-485), IRIG-B signal (RS-485), PPM signal (Binary input), PPS signal (Binary input) Message time synchronization mode: SNTP protocol (unicast or broadcast), other SAS time synchronization message (such as IEC60870-5-103) etc. Extension module time synchronization mode: IEEE1588 protocol, PPS signal (Optical interface), IRIG-B signal (Optical interface) No external time synchronization source

If this setting is set as 1, if this device does not receive time synchronization message or receives error time synchronization message, it will alarm; and if this setting is set as 0 or 2, if this device does not receive the time synchronization signal, it will alarm and switch to

7-30
Date: 2011-08-29

PCS-9611 Feeder Relay

7 Settings

message time synchronization mode automatically. 11. The setting [IP_Server_SNTP] is used to set the IP address of the SNTP server, if this relay adopts the SNTP time synchronization. If the SNTP time synchronization is not adopted, it is recommended to set as 000.000.000.000. 12. If the IEC61850 protocol is adopted in substations, the time tags of communication messages are required according to UTC (Universal Time Coordinated) time. The setting [OffsetHour_UTC] is used to set the hour offset of the current time zone to the GMT (Greenwich Mean Time) zone; for example, if a relay is applied in China, the time zone of China is east 8th time zone, so this setting is set as 8. The setting [OffsetMinute_UTC] is used to set the minute offset of the current time zone to the GMT zone.
Time zone Setting Time zone Setting Time zone Setting Time zone Setting GMT zone 0 East 6 6 East/West 12 -12/12 West 6 -6
th th th

East 1st 1 East 7 7 West 1 -1 West 7 -7


th st th

East 2nd 2 East 8 8 West 2 -2 West 8 -8


th nd th

East 3rd 3 East 9 9 West 3 -3 West 9 -9


th rd th

East 4th 4 East 10 10 West 4 -4 West 10 -10


th th th

East 5th 5 East 11 11 West 5th -5 West 11th -11


th

13. The setting [En_DualNet_GOOSE] is used to enable or disable the dual-network GOOSE function if the GOOSE function is supported in this relay. If it is set as 1, the dual-network GOOSE function is adopted; otherwise, the single-network GOOSE function is adopted.

7.7 Copy Settings


It (the submenu Copy Settings) is used to copy the active settings to another group, see Section 8.2.6.3 for more details.

PCS-9611 Feeder Relay Date: 2011-08-29

7-31

7 Settings

7-32
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

8 Human Machine Interface


Table of Contents
8.1 Overview ...........................................................................................................8-1
8.1.1 Design................................................................................................................................ 8-1 8.1.2 Functionality....................................................................................................................... 8-1 8.1.3 Keypad and Keys............................................................................................................... 8-1 8.1.4 LED indications.................................................................................................................. 8-2

8.2 Understand the HMI Menu Tree .......................................................................8-3


8.2.1 Overview............................................................................................................................ 8-3 8.2.2 Default Display under Normal Operation Condition ........................................................... 8-3 8.2.3 Submenu of Measurements ............................................................................................ 8-5 8.2.4 Submenu of Status .......................................................................................................... 8-8 8.2.5 Submenu of Records..................................................................................................... 8-12 8.2.6 Submenu of Settings ..................................................................................................... 8-15 8.2.7 Submenu of Print........................................................................................................... 8-19 8.2.8 Submenu of Local Cmd ................................................................................................. 8-21 8.2.9 Submenu of Information ................................................................................................ 8-24 8.2.10 Submenu of Test ......................................................................................................... 8-25 8.2.11 Submenu of Clock ....................................................................................................... 8-27 8.2.12 Submenu of Language ................................................................................................ 8-28

8.3 Understand the LCD Display .........................................................................8-29


8.3.1 Display When Tripping ..................................................................................................... 8-29 8.3.2 Display under Abnormal Condition................................................................................... 8-32

8.4 Password Protection......................................................................................8-34

List of Figures
Figure 8.1-1 Keypad on the front panel................................................................................... 8-2 Figure 8.1-2 LED indicators ..................................................................................................... 8-2
PCS-9611 Feeder Relay Date: 2011-08-29

8-a

8 Human Machine Interface

Figure 8.2-1 Default display in normal situation.....................................................................8-3 Figure 8.2-2 Main menu display of this relay ..........................................................................8-4 Figure 8.2-3 Tree diagram of total command menu................................................................8-4 Figure 8.2-4 LCD display of the protection secondary measurement values ......................8-6 Figure 8.2-5 LCD display of the status of the general binary inputs.....................................8-9 Figure 8.2-6 History fault report on LCD ...............................................................................8-13 Figure 8.2-7 History alarm report on LCD .............................................................................8-13 Figure 8.2-8 History binary state change report on LCD .....................................................8-14 Figure 8.2-9 History user operation report on LCD ..............................................................8-15 Figure 8.2-10 History control report on LCD.........................................................................8-15 Figure 8.2-11 LCD display of the selection of setting group number .................................8-17 Figure 8.2-12 LCD display of the selected protection settings ...........................................8-18 Figure 8.2-13 LCD display of the change of active group....................................................8-19 Figure 8.2-14 Control object and command selection interfaces .......................................8-23 Figure 8.2-15 Control execution check and interlock selection interfaces ........................8-23 Figure 8.2-16 Control type selection interface and execution result interface ..................8-23 Figure 8.2-17 LCD display of the software version...............................................................8-25 Figure 8.2-18 LCD display of the board information ............................................................8-25 Figure 8.2-19 Clock modification interface ...........................................................................8-28 Figure 8.2-20 Language modification interface ....................................................................8-28 Figure 8.3-1 LCD display of trip report ..................................................................................8-29 Figure 8.3-2 Information of alarm report on the LCD ...........................................................8-32 Figure 8.4-1 Password input interface for control operation...............................................8-35 Figure 8.4-2 Password input interface for modifying settings ............................................8-35

8-b
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

8.1 Overview
Human machine interface (HMI) is an important component of the equipment. It is a convenient facility to access the relay from the front local control panel of this relay to view desired information, such as measurement quantity or binary inputs state or program version etc. or modify some system settings or protection settings. This function is very helpful during commissioning before putting the equipment into service. Furthermore, all above functions can be realized in a remote terminal with special software through a communication bus via a RS-485 port or an Ethernet port. This chapter will describe human machine interface (HMI), menu tree and LCD display of the equipment. In addition, how to input settings using keypad is described in detail.

8.1.1 Design
The human machine interface consists of a human machine interface (HMI) module which allows the communication as simple as possible for the user. The HMI module includes: A 240128-dot matrix backlight LCD visible in dim lighting conditions for monitoring status, fault diagnostics and setting etc. Twenty LED indicators on the front panel of this relay for denoting the status of this protection operation, the color and trigger condition of each LED can be configured through PCS-PC. A 9-key keypad on the front panel of the device for full access to the device. An Ethernet interface special for the PCS-PC configuration tool; for more details, see the PCS-PC online help brochure or the PCS-PC configuration tool instruction manual. The front panel of the device is shown in Figure 6.1-2.

8.1.2 Functionality
The HMI module helps to draw your attention to something that has occurred which may activate a LED or a report display on the LCD. You as the operator may have own interest to view a certain data. Use menus navigate through menu commands and to locate the data of interest.

8.1.3 Keypad and Keys


The keypad and keys on the front panel of the equipment provide convenience to the operator to view a certain data or change the devices setting. The keypad contains nine keys, and each key has different function to the other one.
Key Sign , , , +, ENT
PCS-9611 Feeder Relay Date: 2011-08-29

Description Move between selectable branches of the menu tree. Change parameters or settings. Confirm/Execute present operation. 8-1

8 Human Machine Interface GRP ESC Fast change the setting group number. Exit the present level menu to main menu, or cancel present operation.

The following figure shows the keypad and keys.


GR P

Figure 8.1-1 Keypad on the front panel

8.1.4 LED indications


There are twenty LED indicators, which can indicate the operation state of the device. The LED_03 to LED_20 is configurable through the PCS-PC configuration tool auxiliary software, and the following figure shows the default LED configuration on the front panel of the device.

Figure 8.1-2 LED indicators Label HEALTHY Off Steady Green ALARM TRIP RECLOSE CB OPEN CB CLOSE Off Steady Yellow Off Steady Red Off Steady Red Off Steady Red Off Steady Green Display during self-supervision. When this relay is in service and ready for operation. When this relay is in normal operating situation. When any abnormality alarm is issued. When this relay is in normal operating situation. When any protection element is operated. When this relay is in normal operating situation. When the auto-recloser operates. When the circuit breaker is closed state. When the circuit breaker is opened state. When the circuit breaker is opened state. When the circuit breaker is closed state. Remarks When this relay is not energized or any hardware defect is detected

NOTE!

8-2
Date: 2011-08-29

ESC

PCS-9611 Feeder Relay

8 Human Machine Interface

The HEALTHY LED can only be turned on by supplying power to this device again or rebooting this device. The ALARM LED is turned on as long as alarm exists. When alarm signals disappear, it will be turned off. The TRIP LED is turned on once any protection element operates and keeps being on even after the trip command goes off. The RECLOSE LED is turned on once auto-recloser operates and remains keeps being on even after the auto-reclosing command goes off. The CB OPEN LED is turned on once when the circuit breaker is in open position. The CB CLOSE LED is turned on once when the circuit breaker is in closing position. The TRIP and RECLOSE LEDs and relevant latched binary outputs can be reset by pressing the key ENT+ESC, by energizing the binary input [BI_RstTarg] or by executing the submenu Reset Target.

8.2 Understand the HMI Menu Tree


8.2.1 Overview
In this section, the main layout of the menu which is shown on the LCD of the local human machine interface (HMI) will be described in detail.

8.2.2 Default Display under Normal Operation Condition


The default display on the LCD is shown as below when the device is in normal situation.

Figure 8.2-1 Default display in normal situation

The first line shows the time synchronization state and the current time of this relay. The sign S on left-top side means this relay receive the clock synchronization signal correctly; if there has nothing on left-top side, it means the time synchronization is not correct. The current time format of this relay is yyyy-mm-dd hh:mm:ss. The middle part of the LCD shows the measurement for the protection. The last line shows the last section of the IP address and the setting group number. The battery sign on the left-bottom is used to indicate the ready state of the auto-recloser. When the battery
PCS-9611 Feeder Relay Date: 2011-08-29

8-3

8 Human Machine Interface

sign is solid ( ), it means that the auto-recloser is ready; when the battery sign is empty ( ), it means that the auto-recloser is blocked; and when the battery sign is half solid ( ), it means that the auto-recloser is in reclaiming procedure. When the default screen is being shown, press key to enter the main menu of this relay.

Figure 8.2-2 Main menu display of this relay

The following figure shows the menu tree structure of this device.

Figure 8.2-3 Tree diagram of total command menu

Press key , , or to select a submenu and the press key ENT to show the details. NOTE! This manual introduces all the submenus and their functions which maybe can be supplied by this relay. Some submenus are not configured if the relevant functions are not supported in this relay. So the practical submenus of this relay should be taken as final and binding.

8-4
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

8.2.3 Submenu of Measurements


Purpose: This menu is used to view the measured values including current, voltage, phase angle and other calculated quantities. Access approach: Move cursor to the item Measurements and press key ENT to enter its submenu after entering the main menu of this device. Submenu structure tree: The submenu Measurements has following submenus.
No. 1 2 Item Measurements1 Measurements2 Description To display the measurement values for protection To display the measurement values for metering

The submenu Measurements1 has following submenus.


No. 1 2 Item Primary Values Secondary Values Description To display the primary measurement values for protection To display the secondary measurement values for protection

The submenu Measurements2 has following submenus.


No. 1 2 3 4 5 Item Primary Values Secondary Values Primary Power Secondary Power Synchrocheck Description To display the primary measurement values for metering To display the secondary measurement values for metering To display the primary power values for metering To display the secondary power values for metering To display the closing synchronism check state

8.2.3.1 View Measurements Here take viewing the secondary protection measurement values as an example to introduce the operating steps of viewing the measurements. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Measurements and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Measurements1 and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Secondary Values and press key ENT to enter this submenu.

3.

4.

PCS-9611 Feeder Relay Date: 2011-08-29

8-5

8 Human Machine Interface

5.

Press key or to view the expected measured values.

Figure 8.2-4 LCD display of the protection secondary measurement values

The following tables show all the measurement values of this relay. Protection measurement values
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Ia Ib Ic I1 I2 3I0_Cal 3I0_Ext1 3I0_Ext2 3I0_SEF Ua Ub Uc Uab Ubc Uca U1 U2 3U0_Cal 3U0_Ext Ux f Ang(Ia-Ib) Ang(Ib-Ic) Ang(Ic-Ia) Ang(Ua-Ia) Ang(Ub-Ib) Ang(Uc-Ic) Ang(Ua-Ub) Symbol Current value of the phase A Current value of the phase B Current value of the phase C Positive sequence current value Negative sequence current value Self-calculated zero sequence current value The No.1 external zero sequence current value The No.2 external zero sequence current value Sensitive zero sequence current value Voltage value of phase A Voltage value of phase B Voltage value of phase C Voltage value of phase A to phase B Voltage value of phase B to phase C Voltage value of phase C to phase A Positive sequence voltage value Negative sequence voltage value Self-calculated zero sequence voltage value External zero sequence voltage value Synchro-check voltage value System frequency value Angle of phase A current and phase B current Angle of phase B current and phase C current Angle of phase C current and phase A current Angle of phase A voltage and phase A current Angle of phase B voltage and phase B current Angle of phase C voltage and phase C current Angle of phase A voltage and phase B voltage Description

8-6
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface 29 30 31 32 Ang(Ub-Uc) Ang(Uc-Ua) Ang(Uab-Ux) Ang(3U0-3I0_Cal) Angle of phase B voltage and phase C voltage Angle of phase C voltage and phase A voltage Angle of phase-to-phase voltage Uab and synchro-check voltage Angle of the self-calculated zero sequence voltage and current

Metering measurement values


No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Ia Ib Ic 3I0_Ext1 Ua Ub Uc Uab Ubc Uca f Ang(Ia-Ib) Ang(Ib-Ic) Ang(Ic-Ia) Ang(Ua-Ia) Ang(Ub-Ib) Ang(Uc-Ic) Ang(Ua-Ub) Ang(Ub-Uc) Ang(Uc-Ua) Symbol Current value of the phase A Current value of the phase B Current value of the phase C The No.1 external zero sequence current value Voltage value of phase A Voltage value of phase B Voltage value of phase C Voltage value of phase A to phase B Voltage value of phase B to phase C Voltage value of phase C to phase A System frequency value Angle of phase A current and phase B current Angle of phase B current and phase C current Angle of phase C current and phase A current Angle of phase A voltage and phase A current Angle of phase B voltage and phase B current Angle of phase C voltage and phase C current Angle of phase A voltage and phase B voltage Angle of phase B voltage and phase C voltage Angle of phase C voltage and phase A voltage Description

Power measurement values


No. 1 2 3 4 5 6 7 P Q COS KWH_Out KVAH_Out KWH_In KVAH_In Symbol Active power Reactive power Power factor Outgoing active energy Outgoing reactive energy Incoming active energy Incoming reactive energy Description

Closing synchronism check data


No. 1 2 3 Symbol 25M.U_Diff 25M.f_Diff 25M.phi_Diff Description The voltage difference of the manual closing function The frequency difference of the manual closing function The angle difference of the manual closing function

PCS-9611 Feeder Relay Date: 2011-08-29

8-7

8 Human Machine Interface 4 5 6 25A.U_Diff 25A.f_Diff 25A.phi_Diff The voltage difference of the auto-closing function The frequency difference of the auto-closing function The angle difference of the auto-closing function

8.2.4 Submenu of Status


Purpose: This menu is used to view the state of the binary inputs, binary outputs and supervision alarm elements of this relay. Access approach: Move cursor to the item Status and press key ENT to enter its submenu after entering the main menu of this device. Submenu structure tree: The submenu Status has following submenus.
No. 1 2 3 Inputs Outputs Superv State Item Description To display the state of the binary inputs To display the state of the binary outputs To display the state of supervision alarm signals

The submenu Inputs has following submenus.


No. 1 2 3 4 Item Contact Inputs GOOSE Inputs Prot Inputs Interlock Status Description To display the state of the general binary inputs To display the state of the GOOSE binary inputs To display the state of the protection binary inputs To display the state of the interlocking signals for remote control

The submenu Outputs has following submenus.


No. 1 2 Item Contact Outputs GOOSE Outputs Description To display the state of the general binary outputs To display the state of the GOOSE binary outputs

The submenu Superv State has following submenus.


No. 1 2 Prot Superv GOOSE Superv Item Description To display the state of the protection supervision alarm elements To display the state of the GOOSE supervision alarm elements

8.2.4.1 View Status Here take viewing the status of the general binary inputs as an example to introduce the operating steps of viewing the status. Operating steps:

8-8
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

1. 2.

Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Status and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Inputs and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Contact Inputs and press key ENT to enter this submenu. Press key or to view the expected binary inputs.

3.

4.

5.

Figure 8.2-5 LCD display of the status of the general binary inputs

The following tables show all the binary signal status of this relay. General binary input status
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Symbol B07.BI_01 B07.BI_02 B07.BI_03 B07.BI_04 B07.BI_05 B07.BI_06 B07.BI_07 B07.BI_08 B07.BI_09 B07.BI_10 B07.BI_11 B07.BI_12 B07.BI_13 B07.BI_14 B07.BI_15 B07.BI_16 B07.BI_17 B07.BI_18 B07.BI_19 Description The status of the No.1 general binary input The status of the No.2 general binary input The status of the No.3 general binary input The status of the No.4 general binary input The status of the No.5 general binary input The status of the No.6 general binary input The status of the No.7 general binary input The status of the No.8 general binary input The status of the No.9 general binary input The status of the No.10 general binary input The status of the No.11 general binary input The status of the No.12 general binary input The status of the No.13 general binary input The status of the No.14 general binary input The status of the No.15 general binary input The status of the No.16 general binary input The status of the No.17 general binary input The status of the No.18 general binary input The status of the No.19 general binary input 8-9
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

The signal symbol of a binary input is B0x.BI_yy; x is the sequence number of the binary input module location in the rack of this relay, and yy is the sequence number of the binary input at the binary input module. For the details about the binary inputs, see Section 6.8. GOOSE binary input status
No. 1 2 3 GBI_001 GBI_002 Symbol Description The status of the No.1 GOOSE binary input The status of the No.2 GOOSE binary input

See the GOOSE related instruction manual for the more information and details. Protection binary input status
No. 1 2 3 4 5 6 7 8 9 10 11 12 BI_52b BI_52a Ctrl.Sig_EnCtrl Ctrl.Sig_Unblock Ctrl1. Sig_ManSynChk Ctrl1. Sig_ManDdChk 79.Blk 79.Ready BI_LowPres_Trp BI_LowPres_Cls BI_TrigDFR BI_RstTarg Symbol Description The binary input of the state of the CB normal close contact signal The binary input of the state of the CB normal open contact signal The binary input of the enabling remote control function signal The binary input of the interlock unlocking function signal The binary input of the enabling synchronism check for manual closing The binary input of the enabling dead check for manual closing The binary input of the blocking auto-recloser signal A virtual binary input of indicating the auto-recloser is ready The binary input of the tripping low pressure signal The binary input of the closing low pressure signal The binary input of the triggering oscillography signal The binary input of the signal resetting signal

Interlock input status


No. 1 2 3 4 5 6 7 8 9 10 Symbol Interlock1.Sig_Opn Interlock1.Sig_Cls Interlock2.Sig_Opn Interlock2.Sig_Cls Interlock3.Sig_Opn Interlock3.Sig_Cls Interlock4.Sig_Opn Interlock4.Sig_Cls Interlock5.Sig_Opn Interlock5.Sig_Cls Description The interlock check status of the No.1 manual tripping element The interlock check status of the No.1 manual closing element The interlock check status of the No.2 manual tripping element The interlock check status of the No.2 manual closing element The interlock check status of the No.3 manual tripping element The interlock check status of the No.3 manual closing element The interlock check status of the No.4 manual tripping element The interlock check status of the No.4 manual closing element The interlock check status of the No.5 manual tripping element The interlock check status of the No.5 manual closing element

General binary output status


No. 1 2 8-10
Date: 2011-08-29

Symbol B09.BO_01 B09.BO_02

Description The status of the binary output B09.BO_01 The status of the binary output B09.BO_02
PCS-9611 Feeder Relay

8 Human Machine Interface 3 4 5 6 7 8 9 B09.BO_03 B09.BO_04 B09.BO_05 B09.BO_06 B09.BO_07 B09.BO_08 The status of the binary output B09.BO_03 The status of the binary output B09.BO_04 The status of the binary output B09.BO_05 The status of the binary output B09.BO_06 The status of the binary output B09.BO_07 The status of the binary output B09.BO_08

The signal symbol of a binary output is B0x.BO_yy; x is the sequence number of the binary output module location in the rack of this relay, and yy is the sequence number of the binary output at the binary output module. For the details about the binary outputs, see Section 6.4 and Section 6.7. GOOSE binary output status
No. 1 2 3 4 5 6 Symbol GBO_Act01 GBO_Act02 GBO_01 GBO_02 Description The status of the No.1 GOOSE operation output The status of the No.2 GOOSE operation output The status of the No.1 GOOSE general output The status of the No.2 GOOSE general output

See the GOOSE related instruction manual for the more information and details. Supervision alarm element status
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Symbol Fail_Device Fail_BoardConfig Fail_Setting Fail_Setting_OvRange Fail_SettingItem_Chgd Alm_Device Alm_Setting_MON Alm_Version Alm_BI_SettingGrp Alm_52b VTS.Alm_SynVT VTS.Alm CTS.Alm 49.Alm Alm_CommTest Alm_TimeSync Alm_Maintenance Alm_LowPres_Trp Description The status of the alarm signal Fail_Device The status of the alarm signal Fail_BoardConfig The status of the alarm signal Fail_Setting The status of the alarm signal Fail_Setting_OvRange The status of the alarm signal Fail_SettingItem_Chgd The status of the alarm signal Alm_Device The status of the alarm signal Alm_Setting_MON The status of the alarm signal Alm_Version The status of the alarm signal Alm_BI_SettingGrp The status of the alarm signal Alm_52b The status of the alarm signal VTS.Alm_SynVT The status of the alarm signal VTS.Alm The status of the alarm signal CTS.Alm The status of the alarm signal 49.Alm The status of the alarm signal Alm_CommTest The status of the alarm signal Alm_TimeSync The status of the alarm signal Alm_Maintenance The status of the alarm signal Alm_LowPres_Trp

PCS-9611 Feeder Relay Date: 2011-08-29

8-11

8 Human Machine Interface 19 20 Alm_LowPres_Cls Alm_ResvX The status of the alarm signal Alm_LowPres_Cls The status of the alarm signal Alm_ResvX (X: a number; 1, 2 etc.)

For the details about the supervision alarm element, see Section 4.2. GOOSE alarm element status
No. 1 2 3 4 5 Symbol goose_netstorm_warning_1 goose_netstorm_warning_2 Link0goose_link_down_a Link0goose_link_down_b Link0goose_cfg_err Description The status of the alarm signal goose_netstorm_warning_1 The status of the alarm signal goose_netstorm_warning_2 The status of the alarm signal Link0goose_link_down_a The status of the alarm signal Link0goose_link_down_b The status of the alarm signal Link0goose_cfg_err

See the GOOSE related instruction manual for the more information and details.

8.2.5 Submenu of Records


Purpose: This menu is used to view all kinds of history records, such as the protection tripping reports, the supervision alarm records and the binary state change records etc. Access approach: Move cursor to the item Records and press key ENT to enter its submenu after entering the main menu of this device. Submenu structure tree: The submenu Records has following submenus.
No. 1 2 3 4 5 Item Disturb Records Superv Events IO Events Device Logs Control Logs To display the fault reports To display the supervision alarm records To display the records of binary state change records To display the device operation reports To display the local/remote control records Description

NOTE! Press the key +, -, +, - and ENT in sequence to enter the submenu for clearing the history reports. 8.2.5.1 View History Fault Report The history fault report stores the trip elements, trip time and waveform of a selected trip report. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Records and press key ENT to enter this submenu.
PCS-9611 Feeder Relay Date: 2011-08-29

8-12

8 Human Machine Interface

3.

Press key or to locate the cursor on the submenu Disturb Records and press key ENT to enter this submenu. If there is no report in the selected submenu, it will show No Report! on the LCD. Press key + or - to view the expected history fault report.

4.

Figure 8.2-6 History fault report on LCD

The first line shows the report title and the sequence number of the history trip report, and the second line shows the operation time of the history trip report. Other lines show the protection elements and fault information one by one according to the relative time sequence. The fault information includes fault phase, maximum fault value and minimum fault value. For more information about the protection elements and fault information, see Section 8.3.1. 8.2.5.2 View History Alarm Report The history alarm report stores the alarm elements and alarm time. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Records and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Superv Events and press key ENT to enter this submenu. If there is no report in the selected submenu, it will show No Report! on the LCD. Press key + or - to view the expected history alarm report.

3.

4.

Figure 8.2-7 History alarm report on LCD

The first line shows the report title and the sequence number of the history alarm report, and the

PCS-9611 Feeder Relay Date: 2011-08-29

8-13

8 Human Machine Interface

second line shows the alarm time of the history alarm report. Other lines show the alarm elements and state change information one by one. For more information about the alarm elements, see Section 8.3.2. 8.2.5.3 View History Binary State Change Report The history binary state change report stores the binary signal name and state change time. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Records and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu IO Events and press key ENT to enter this submenu. If there is no report in the selected submenu, it will show No Report! on the LCD. Press key + or - to view the expected history binary state change report.

3.

4.

Figure 8.2-8 History binary state change report on LCD

The first line shows the report title and the sequence number of the history binary input state change report, and the second line shows the binary state change time of the history binary state change report. Other lines show the binary state change information one by one. For more information about the binary signals, see Section 8.2.4. 8.2.5.4 View History User Operation Report The history user operation report stores the user operation information and user operation time. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Records and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Device Logs and press key ENT to enter this submenu. Press key + or - to view the expected history user operation report.

3.

4.

8-14
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

Figure 8.2-9 History user operation report on LCD

The first line shows the report title and the sequence number of the history user operation report, and the second line shows the user operation time of the history user operation report. Other lines show the user operation information. 8.2.5.5 View History Control Report The history control report stores the control information and control time. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Records and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Control Logs and press key ENT to enter this submenu. Press key + or - to view the expected history control report.

3.

4.

Figure 8.2-10 History control report on LCD

The first line shows the report title and the sequence number of the history control report, and the second line shows the control time of the history control report. Other lines show the control information.

8.2.6 Submenu of Settings


Purpose: The menu is used to view and modify the settings and parameters of this device. Please read Chapter 7 for the details about the all the settings.

PCS-9611 Feeder Relay Date: 2011-08-29

8-15

8 Human Machine Interface

Access approach: Move cursor to the item Settings and press key ENT to enter its submenu after entering the main menu of this device. The submenu Settings has following submenus.
No. 1 2 3 4 5 6 Item System Settings Prot Settings Mon/Ctrl Settings Logic Links Device Setup Copy Settings Description To view and modify the system settings To view and modify the protection settings To view and modify the monitor and control settings To view and modify the virtual enabling binary input settings To view and modify the device and communication settings To copy a group of setting to other group

The submenu Prot Settings has following submenus.


No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Item OC Settings NegOC Settings EF1 Settings EF2 Settings SEF Settings BFP Settings BrknCond Settings SOTF Settings ThOvLd Settings Voltage Settings NegOV Settings ROV Settings FreqProt Settings AR Settings CLP Settings MR Prot Settings Superv Settings CfgBO Settings Description To view and modify the settings of the OC protection To view and modify the settings of the NOC protection To view and modify the settings of the No.1 ROC protection To view and modify the settings of the No.2 ROC protection To view and modify the settings of the SEF protection To view and modify the settings of the BFP protection To view and modify the settings of the BCP protection To view and modify the settings of the SOTF protection To view and modify the settings of the thermal overload protection To view and modify the settings of the voltage protection To view and modify the settings of the NOV protection To view and modify the settings of the ROV protection To view and modify the settings of the frequency protection To view and modify the settings of the auto-recloser To view and modify the settings of the cold load pickup logic To view and modify the settings of the mechanical protection To view and modify the settings of the supervision function To view and modify the settings of the binary outputs

The submenu Mon/Ctrl Settings has following submenus.


No. 1 2 3 4 Item Syn Settings Control Settings Interlock Settings AC Calbr Settings Description To view and modify the settings of the closing synchronism function To view and modify the settings of the CB control function To view and modify the settings of the interlock function This submenu is only reserved for the manufacturer

The submenu Logic Links has following submenus.

8-16
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface No. 1 2 3 4 Item Function Links GOOSE Links SV Links Spare Links Description To view and modify the function link settings To view and modify the GOOSE link settings To view and modify the SV link settings To view and modify the spare link settings

The submenu Device Setup has following submenus.


No. 1 2 Item Device Settings Comm Settings Description To view and modify the device related settings To view and modify the communication settings

8.2.6.1 View Settings Here take viewing the overcurrent protection settings as an example to introduce the operating steps of viewing the setting. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Settings and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Prot Settings and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu OC Settings and press key ENT to enter the selecting interface of the setting group number. Press key + or - to select the expected setting group number and then press key ENT to show the settings of the selected group. Press key or to view the expected protection settings.

3.

4.

5.

6.

The selecting interface of the setting group number is shown as below.

Figure 8.2-11 LCD display of the selection of setting group number

The setting interface of the selected setting group is shown as below.

PCS-9611 Feeder Relay Date: 2011-08-29

8-17

8 Human Machine Interface

Figure 8.2-12 LCD display of the selected protection settings

8.2.6.2 Modify the Settings The settings can be modified through the local HMI to meet the demand of practical engineering. Operating steps: 1. Refer the Section 8.2.6.1 to locate the cursor on the expected setting, and then press key ENT to enter the setting modification state. 2. Press key + or - to modify a selected setting, and press key ESC to return to the setting interface (see Figure 8.2-12) after the selected setting modification is finished. Repeat Step 1 and 2 to modify other settings which need to be modified. After finishing the setting modification, press key ESC to prompt the user whether to save the settings. Select Yes to confirm to save the modified settings. Then the password input interface is shown on the LCD. Input the correct password and press key ENT to confirm the modification. If the modification is given up, press key ESC to exit the modification operation. After confirming the setting modification, it will show Saving Settings on the LCD. Then the device will restart, and the new settings will be in service. NOTE! It is necessary to certify whether the modified settings are correct absolutely before confirming the setting modification. 8.2.6.3 Copy the Settings The last submenu Copy Settings is used to copy the active settings to another group. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Settings and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Copy Settings and press key ENT to enter the interface for copying settings. Press key + or - to select the expected setting group number and then press key ENT to show the password input interface.

3. 4.

5.

3.

4.

8-18
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

5.

Input the correct password and then press key ENT to copy the settings of the active group to the selected group.

8.2.6.4 Switch the Active Setting Group There are two methods which are used to switch one setting group to another group. One method is to modify the setting [Active_Grp] in submenu System Settings. Another method is detailed as following operating steps. Operating steps: 1. 2. Press key GRP to enter the setting group switch interface in the default displaying situation. Press key + or - to select the expected setting group number and then press key ENT to show the password input interface. Input the correct password and then press key ENT to copy the settings of the active group to the selected group.

3.

Figure 8.2-13 LCD display of the change of active group

8.2.7 Submenu of Print


Purpose: The menu is used to print the relevant information of this device. A printer is needed, and the EPSON LQ-300K is recommended. Access approach: Move cursor to the item Print and press key ENT to enter its submenu after entering the main menu of this device. The submenu Print has following submenus.
No. 1 2 3 4 5 6 7 Device Info Settings Disturb Records Superv Events IO Events Device Status Waveforms Item Description To print the device description information To print the settings of this device To print the fault reports To print the supervision alarm records To print the records of binary state change records To print the status of this device To print the fault and disturbance records 8-19
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface 8 9 IEC103 Info Cancel Print To print the IEC60870-5-103 information of this device To cancel the printing operation

The submenu Settings maybe has following submenus.


No. 1 2 3 4 5 6 7 Item System Settings Prot Settings Mon/Ctrl Settings Logic Links Device Setup All Settings Latest Modified To print the system settings To print the protection settings To print the monitor and control settings To print the virtual enabling binary input settings To print the device and communication settings To print all the settings of this device To print the latest modified settings Description

8.2.7.1 Print a Selected Item Here take printing the overcurrent protection settings as an example to introduce the operating steps of print a selected item. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Print and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Settings and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Prot Settings and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu OC Settings and press key ENT to enter the selecting interface of the setting group number. Press key + or - to select the expected setting group number and then press key ENT to print the settings of the selected group.

3.

4.

5.

6.

8.2.7.2 Cancel Printing Operation The submenu Cancel Print is used to cancel the present printing content. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Print and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Cancel Print and press key ENT to cancel the present printing content. The information Canceling Print is shown on the LCD.

3.

8-20
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

8.2.8 Submenu of Local Cmd


Purpose: This menu is used to operate this device locally, such as signal resetting, triggering an oscillograph, controlling circuit breaker, clearing history statistic counter etc. Access approach: Move cursor to the item Local Cmd and press key ENT to enter its submenu after entering the main menu of this device. Submenu structure tree: The submenu Local Cmd maybe has following submenus.
No. 1 2 3 4 5 6 7 Item Reset Target Trig Oscillograph Download Clear Counter Clear Interlock File Clear Energy Counter Control Description To restore all the signals on the LCD and binary outputs To record present measurements as oscillogram To enable the download function of this relay To clear the statistic information of the optical channel To delete the interlock configuration file of this relay To clear the energy accumulation counter of this relay To control the circuit breaker

8.2.8.1 Reset Signals and Outputs The submenu Reset Target is used to reset the signals and outputs. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Local Cmd and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Reset Target and press key ENT to restore all the signals and relevant outputs of this relay.

3.

8.2.8.2 Trigger an Oscillogram The submenu Trig Oscillogram is used to trigger this relay to store a waveform. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Local Cmd and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Trig Oscillogram and press key ENT to trigger an oscillogram.

3.

PCS-9611 Feeder Relay Date: 2011-08-29

8-21

8 Human Machine Interface

8.2.8.3 Clear Statistic Counter The submenu Clear Counter is used to the statistic information (auto-recloser operation number, communication statistic information etc.). Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Local Cmd and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Clear Counter and press key ENT to clear the statistic information. The information Clear Statistic Data is shown on the LCD.

3.

The operation steps of the submenu Clear Interlock File and Clear Energy Counter is similar with the operation steps of the submenu Clear Counter. 8.2.8.4 Control CB through Local HMI The submenu Control is used to control the circuit breaker through the local HMI of this relay. There are 5 groups of control elements in this relay. Anyone of them can be used to control (tripping or closing) a circuit breaker or a disconnector. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Local Cmd and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Control and press key ENT to show the password input interface. Input correct password and then press key ENT to show the control item selection interface. Press key or to select an expected control element and then press key ENT to show the password input interface. Press key +, -, and to enter the correct password and then enter the control object selection interface, and then press key or to select a control object. Press key ENT to enter control command selection interface, and then press key or to select a control command. Press key ENT to enter control check condition selection interface, and then press key or to select a control check condition. Press key ENT to enter control interlock selection interface, and then press key or to select a control interlock condition.

3.

4. 5.

6.

7.

8.

9.

10. Press key ENT to enter control type selection interface, and then press key or to

8-22
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

select a control type. 11. Press key ENT to confirm the current control operation. The information about the result of the current control operation will be shown on the LCD. The interfaces related to the control are shown as below.

Figure 8.2-14 Control object and command selection interfaces

Figure 8.2-15 Control execution check and interlock selection interfaces

Figure 8.2-16 Control type selection interface and execution result interface

All the items about the control function are listed as below.
Select the control group number Ctrl1 Ctrl2 Ctrl3 Ctrl4 Ctrl5 Select the control operation open(Lower) close(Raise) (stop) Open a circuit breaker or disconnector Close a circuit breaker or disconnector Stop current operation, not supported in this relay. The No.1 remote control output The No.2 remote control output The No.3 remote control output The No.4 remote control output The No.5 remote control output

Select the control check mode

PCS-9611 Feeder Relay Date: 2011-08-29

8-23

8 Human Machine Interface NoCheck SynchroCheck DeadCheck LoopCheck EF Line Selection InterlockChk InterlockNotChk Select the control type Select Execute Cancel control selection control execution control cancellation Select the non-check mode Select the synchronism check mode Select the dead check mode Select the loop check mode, not supported in this relay. Select the grounding trip check mode, not supported in this relay. Select the interlock check mode Select the non-interlock check mode

Select the control interlock mode

8.2.9 Submenu of Information


Purpose: This menu is used to view program version information and module information of this relay. Access approach: Move cursor to the item Information and press key ENT to enter its submenu after entering the main menu of this device. Submenu structure tree: The submenu Local Cmd maybe has following submenus.
No. 1 2 Board Info Item Version Info Description To view the program version information of this relay To view the module information of this relay

8.2.9.1 View Software Version The program version information of this relay can be known through this menu. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Information and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Version Info and press key ENT to show the program version information. Press key or to show all the version information of the main program and the HMI program.

3.

4.

The software version information interface is shown as below.

8-24
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

Figure 8.2-17 LCD display of the software version

The first line shows the title of this interface, other lines show the information of the board information, including the manufacturer abbreviation name, the device name, the device code, the program version, the program CRC code and the program creation time. NOTE! It is only an example for explaining the software version menu. The practical software version of this relay should be taken as final and binding. 8.2.9.2 View Board Information All the module information can be known through this menu. 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Information and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Board Info and press key ENT to show the board information.

3.

The board information interface is shown as below.

Figure 8.2-18 LCD display of the board information

The first line shows the title of this interface, other lines show the information of the board information, including the slot sequence number, the module type, the module operation state and the module configuration state. In normal operation situation, the module configuration state should be same with the module operation state.

8.2.10 Submenu of Test


Purpose:
PCS-9611 Feeder Relay Date: 2011-08-29

8-25

8 Human Machine Interface

This menu is used to test particular functions of the device, such as testing binary signals, testing binary outputs and testing telemetering etc. It can provide convenience for the communication test and the operation electrical circuit. Access approach: Move cursor to the item Test and press key ENT to enter its submenu after entering the main menu of this device. Submenu structure tree: The submenu Test maybe has following submenus.
No. 1 2 3 4 5 6 Item AR Counter Device Test Internal Signal AC Auto Calbr Disturb Record Items CptRuntime Description To counter and show the auto-recloser operation situation To test the binary signals, binary outputs and telemetering etc. This submenu is only reserved for the manufacturer This submenu is only reserved for the manufacturer This submenu is only reserved for the manufacturer This submenu is only reserved for the manufacturer

The submenu Device Test has following submenus.


No. 1 2 3 4 5 Item Prot Elements Superv Events IO Events Measurements Contact Outputs Description To test the protective element operation signals To test the supervision alarm signals To test the binary state change signals To test the metering measurements To test the binary outputs, please disconnect the external circuit

The submenu Prot Elements, Superv Events and IO Events have following submenus.
No. 1 2 All Test Select Test Item To test all the binary signals To test the selected binary signal Description

8.2.10.1 Communication Test of the Binary Signal The binary signals include the protective element operation signals, supervision alarm signals and binary state change signals. Here take test the protective element operation signal as an example to introduce the operating steps of communication test of the binary signals. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Test and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Device Test and press key ENT
PCS-9611 Feeder Relay Date: 2011-08-29

3.
8-26

8 Human Machine Interface

to enter this submenu. 4. Press key or to locate the cursor on the submenu Prot Elements and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Select Test and press key ENT to show all the protective elements. Press key or to locate the cursor on a selected protective element and then press key ENT to create a binary signal. NOTE! The submenu All Test is used to test all the binary signals automatically. 8.2.10.2 Communication Test of the Telemetering Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Test and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Device Test and press key ENT to enter this submenu. Press key or to locate the cursor on the submenu Measurements and press key ENT to all the metering measurements. Press key or to locate the cursor on a selected metering measurements and press key + or - to modify the selected metering value. 6. After finishing the modification, press key ENT to transmit the metering values.

5.

6.

3.

4.

5.

8.2.11 Submenu of Clock


Purpose: This menu is used to modify the current time of this relay. Access approach: Move cursor to the item Clock and press key ENT to enter the clock modification interface after entering the main menu of this device. 8.2.11.1 Clock Modification Set the current time of this relay as following steps. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Clock and press key ENT to enter the clock modification interface.
8-27
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

3.

Press key or to locate the cursor on a selected item and press key + or - to modify the selected item. After finishing the clock modification, press key ENT to confirm the modification.

4.

The clock modification interface is shown as below.

Figure 8.2-19 Clock modification interface

8.2.12 Submenu of Language


Purpose: This menu is used to modify the display language of this relay. 8.2.12.1 Language Modification Modify the display language as following steps. Operating steps: 1. 2. Press key to enter the main menu in the default displaying situation. Press key or to locate the cursor on the submenu Language and press key ENT to enter the language modification interface. Press key or to select the expected display language. After finishing the language modification, press key ENT to confirm the modification.

3. 4.

The language modification interface is shown as below.

Figure 8.2-20 Language modification interface

8-28
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

8.3 Understand the LCD Display


8.3.1 Display When Tripping
If there is any protection element operating, a brief tripping report will appear on the LCD, and the backlight of the LCD and the LED TRIP will be on simultaneously. The format of the fault report is shown as below.

Figure 8.3-1 LCD display of trip report

The first line shows the report title and the sequence number of the history trip report, and the second line shows the operation time of the history trip report. Other lines show the protection elements and fault information one by one according to the relative time sequence. The fault information includes fault phase, maximum fault value and minimum fault value. NOTE! In case more than one protection element has operated, the relevant report will be displayed alternatively one by one according to time sequence on the LCD. And the fault information is listed after all the protection elements. The trip report will keep being displayed on LCD until an acknowledgement is received by pressing the key ENT+ESC, by energizing the binary input [BI_RstTarg] or by executing the submenu Reset Target. The default display then appears on LCD and LED TRIP is turned off. Protection elements listed below may be displayed.
No. 1 2 3 4 5 6 7 8 9 10 11 Protection Element FD.Pkp Op_Prot 50/51P1.Op 50/51P2.Op 50/51P3.Op 50/51P4.Op 50/51G1.Op 50/51G2.Op 50/51G3.Op 50/51G4.Op A.50/51G1.Op The fault detector operates. Anyone of the protective elements in this relay operates. The stage 1 overcurrent protection operates. The stage 2 overcurrent protection operates. The stage 3 overcurrent protection operates. The stage 4 overcurrent protection operates. The No.1 stage 1 zero sequence overcurrent protection operates. The No.1 stage 2 zero sequence overcurrent protection operates. The No.1 stage 3 zero sequence overcurrent protection operates. The No.1 stage 4 zero sequence overcurrent protection operates. The No.2 stage 1 zero sequence overcurrent protection operates. Description

PCS-9611 Feeder Relay Date: 2011-08-29

8-29

8 Human Machine Interface 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 8-30


Date: 2011-08-29

A.50/51G2.Op A.50/51G3.Op A.50/51G4.Op 50/51Q1.Op 50/51Q2.Op 50/51SEF1.Op 50/51SEF2.Op 50/51SEF3.Op 50/51SEF4.Op 50PSOTF.Op 50GSOTF.Op 50BC.Op 49.Op 50BF.Op 50BF.ReTrp 27P1.Op 27P2.Op 59P1.Op 59P2.Op 59Q.Op 59G1.Op 59G2.Op 81U1.Op 81U2.Op 81U3.Op 81U4.Op 81O1.Op 81O2.Op 81O3.Op 81O4.Op 81R1.Op 81R2.Op 81R3.Op 81R4.Op 79.Close_3PS1 79.Close_3PS2 79.Close_3PS3 79.Close_3PS4 MR1.Op MR2.Op MR3.Op MR4.Op 50/51P1.St

The No.2 stage 2 zero sequence overcurrent protection operates. The No.2 stage 3 zero sequence overcurrent protection operates. The No.2 stage 4 zero sequence overcurrent protection operates. The stage 1 negative sequence overcurrent protection operates. The stage 2 negative sequence overcurrent protection operates. The stage 1 sensitive earth fault protection operates. The stage 2 sensitive earth fault protection operates. The stage 3 sensitive earth fault protection operates. The stage 4 sensitive earth fault protection operates. The SOTF overcurrent protection operates. The zero sequence SOTF overcurrent protection operates. The broken conductor protection operates. The thermal overload protection operates. The breaker failure protection operates. The breaker failure protection re-trip operates. The stage 1 undervoltage protection operates. The stage 2 undervoltage protection operates. The stage 1 overvoltage protection operates. The stage 2 overvoltage protection operates. The negative sequence overvoltage protection operates. The stage 1 zero sequence overvoltage protection operates. The stage 2 zero sequence overvoltage protection operates. The stage 1 under-frequency protection operates. The stage 2 under-frequency protection operates. The stage 3 under-frequency protection operates. The stage 4 under-frequency protection operates. The stage 1 over-frequency protection operates. The stage 2 over-frequency protection operates. The stage 3 over-frequency protection operates. The stage 4 over-frequency protection operates. The stage 1 frequency rate-of-change protection operates. The stage 2 frequency rate-of-change protection operates. The stage 3 frequency rate-of-change protection operates. The stage 4 frequency rate-of-change protection operates. The 1st shot auto-recloser operates. The 2nd shot auto-recloser operates. The 3rd shot auto-recloser operates. The 4th shot auto-recloser operates. The No.1 mechanical protection operates. The No.2 mechanical protection operates. The No.3 mechanical protection operates. The No.4 mechanical protection operates. The stage 1 overcurrent protection picks up.

PCS-9611 Feeder Relay

8 Human Machine Interface 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 50/51P2.St 50/51P3.St 50/51P4.St 50/51G1.St 50/51G2.St 50/51G3.St 50/51G4.St A.50/51G1.St A.50/51G2.St A.50/51G3.St A.50/51G4.St 50/51Q1.St 50/51Q2.St 50/51SEF1.St 50/51SEF2.St 50/51SEF3.St 50/51SEF4.St 50PSOTF.St 50GSOTF.St 50BC.St 49.St 50BF.St 27P1.St 27P2.St 59P1.St 59P2.St 59Q.St 59G1.St 59G2.St 81U1.St 81U2.St 81U3.St 81U4.St 81O1.St 81O2.St 81O3.St 81O4.St 81R1.St 81R2.St 81R3.St 81R4.St 79.InProg MR1.St The stage 2 overcurrent protection picks up. The stage 3 overcurrent protection picks up. The stage 4 overcurrent protection picks up. The No.1 stage 1 zero sequence overcurrent protection picks up. The No.1 stage 2 zero sequence overcurrent protection picks up. The No.1 stage 3 zero sequence overcurrent protection picks up. The No.1 stage 4 zero sequence overcurrent protection picks up. The No.2 stage 1 zero sequence overcurrent protection picks up. The No.2 stage 2 zero sequence overcurrent protection picks up. The No.2 stage 3 zero sequence overcurrent protection picks up. The No.2 stage 4 zero sequence overcurrent protection picks up. The stage 1 negative sequence overcurrent protection picks up. The stage 2 negative sequence overcurrent protection picks up. The stage 1 sensitive earth fault protection picks up. The stage 2 sensitive earth fault protection picks up. The stage 3 sensitive earth fault protection picks up. The stage 4 sensitive earth fault protection picks up. The SOTF overcurrent protection picks up. The zero sequence SOTF overcurrent protection picks up. The broken conductor protection picks up. The thermal overload protection picks up. The breaker failure protection picks up. The stage 1 undervoltage protection picks up. The stage 2 undervoltage protection picks up. The stage 1 overvoltage protection picks up. The stage 2 overvoltage protection picks up. The negative sequence overvoltage protection picks up. The stage 1 zero sequence overvoltage protection picks up. The stage 2 zero sequence overvoltage protection picks up. The stage 1 under-frequency protection picks up. The stage 2 under-frequency protection picks up. The stage 3 under-frequency protection picks up. The stage 4 under-frequency protection picks up. The stage 1 over-frequency protection picks up. The stage 2 over-frequency protection picks up. The stage 3 over-frequency protection picks up. The stage 4 over-frequency protection picks up. The stage 1 frequency rate-of-change protection picks up. The stage 2 frequency rate-of-change protection picks up. The stage 3 frequency rate-of-change protection picks up. The stage 4 frequency rate-of-change protection picks up. The auto-recloser picks up. The No.1 mechanical protection picks up. 8-31
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface 98 99 100 MR2.St MR3.St MR4.St The No.2 mechanical protection picks up. The No.3 mechanical protection picks up. The No.4 mechanical protection picks up.

Fault information listed below may be displayed.


No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Fault Information Ip_Max 3I0Cal_Max 3I0Ext1_Max 3I0Ext2_Max 3I0SEF_Max I2/I1_Max Upp_Min Upp_Max Up_Min Up_Max U2_Max Ux_Max Ux_Min f_Max f_Min The maximum phase current The maximum self-calculated zero sequence current The No.1 maximum external zero sequence current The No.2 maximum external zero sequence current The maximum sensitive earth fault current The maximum ratio of I2/I1 The minimum phase-to-phase voltage The maximum phase-to-phase voltage The minimum phase voltage The maximum phase voltage The maximum negative sequence voltage The maximum synchro-check voltage The minimum synchro-check voltage The maximum system frequency The minimum system frequency Description

See Chapter 3 for more details about the protection operation theory.

8.3.2 Display under Abnormal Condition


8.3.2.1 Alarm Information on LCD If there is any abnormality in the operation or any firmware error is detected by the self-diagnostics of this relay, an alarm report will be displayed instantaneously on the LCD. Therefore, the default display will be replaced by the alarm report. The format of the alarm report is shown as below.

Figure 8.3-2 Information of alarm report on the LCD

The first line shows the alarm report title, and then shows the alarm elements one by one according to the time sequence. The alarm report will keep being displayed on LCD until the relevant alarm situation is restored to normal state. It means that this relay does not detect any alarm situation. The default display then
8-32
Date: 2011-08-29 PCS-9611 Feeder Relay

8 Human Machine Interface

appears on LCD and LED ALARM is off. The LED ALARM will not be on if either of the alarm signals [Fail_Device] and [Fail_Setting] is issued. Alarm elements listed below may be displayed. See Section 4.2 for more details about the alarm element operation theory.
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Alarm Element Fail_Device Fail_BoardConfig Fail_Setting Fail_Setting_OvRange Fail_SettingItem_Chgd Alm_Device Alm_Setting_MON Alm_Version Alm_BI_SettingGrp Alm_52b VTS.Alm_SynVT VTS.Alm CTS.Alm 49.Alm Alm_CommTest Alm_TimeSync Alm_Maintenance Alm_LowPres_Trp Alm_LowPres_Cls Alm_ResvX Description A serious fault is detected to block this device. The module configuration of this device is wrong. Anyone of the settings is modified. Anyone of the settings is out of range. Anyone of the setting items is changed. Anyone of the software supervision alarm occurs. The settings from the HMI module are not correct. The current program version is not correct. The group number is changed by the binary inputs The normal close contact of the CB is abnormal. The synchro-check VT circuit is failed. The protection voltage transformer circuit is failed. The current transformer is failed. The thermal overload situation is occurred. The communication test operation is executed. The time synchronization is not correct. The device is in maintenance situation. The pressure of the tripping circuit is low. The pressure of the closing circuit is low. The No.X reserved alarm signal is issued. HEALTHY Off Off Off Off Off ALARM On On On On On On On On On On On On On On On

Here, On means the LED is on, Off means the LED is off, and means having no influence. NOTE! When this relay is energized, in the startup process, the LED HEALTHY is off and the LED ALARM is on. The handling suggestions of the alarm events are listed as below.
No. 1 2 3 4 5 6 7 8 9 Alarm Element Fail_Device Fail_BoardConfig Fail_Setting Fail_Setting_OvRange Fail_SettingItem_Chgd Alm_Device Alm_Setting_MON Alm_Version Alm_BI_SettingGrp Handing Suggestion Please check whether there has a serious error in this relay. Please check whether the board configuration complies with the software. Please ensure whether anyone of the settings is modified. Please ensure whether anyone of the settings is out of range. Please enter the relevant setting menu of this relay to confirm it. Please ensure whether anyone of the software supervision alarm occurs. Please inform the manufacturer to deal with it. Please inform the manufacturer to deal with it. Please ensure whether the group number is changed by the binary inputs.

PCS-9611 Feeder Relay Date: 2011-08-29

8-33

8 Human Machine Interface 10 11 12 13 14 15 16 17 18 19 20 Alm_52b VTS.Alm_SynVT VTS.Alm CTS.Alm 49.Alm Alm_CommTest Alm_TimeSync Alm_Maintenance Alm_LowPres_Trp Alm_LowPres_Cls Alm_ResvX Please check the auxiliary open position contact of the circuit breaker. Please check the secondary circuit of the synchro-check voltage transformer. Please check the secondary circuit of the protection voltage transformer. Please check the secondary circuit of the current transformer. Please check whether the thermal overload condition is satisfied. Please check whether this device is in communication test situation. Please check whether the time synchronization signal is correct. Please check whether the binary input for denoting maintenance is energized. Please check the mechanism of the circuit breaker. Please check the mechanism of the circuit breaker. Please check whether the relevant alarm issuing conditions are satisfied.

8.3.2.2 Understand the Alarms Hardware circuit and operation condition of this device are self-supervised continuously. If any abnormal condition is detected, information or report will be displayed and a corresponding alarm will be issued. A common abnormality may block a certain number of protection functions while other functions can still work. However, if a serious hardware failure or abnormality is detected, all protection functions will be blocked and the LED HEALTHY will be off. When hardware failure is detected, all protection functions will be blocked and the corresponding alarm signal will be issued. This relay can not work normally in such a situation and a manual maintenance is required to fix the failure. NOTE! If this device is blocked or alarm signal is issued during operation, do please find out its reason by help of the history reports. If the reason can not be found on site, please inform the manufacturer NR Electric Co., Ltd.

8.4 Password Protection


For the safety purpose, this device provides password security function for modifying the settings and doing a control operation. Only the input password is correct, the relevant operation can be done. If the input password is correct, the relevant operation can be done; otherwise, it will show the input interface on the LCD to prompt the user to input the password again. The password for control operation is fixed, and it is 111. The following figure shows the password input interface for control operation.

8-34
Date: 2011-08-29

PCS-9611 Feeder Relay

8 Human Machine Interface

Figure 8.4-1 Password input interface for control operation

The password for modifying settings is fixed, and it is press key +, , and - in sequence. The following figure shows the password input interface for modifying settings.

Figure 8.4-2 Password input interface for modifying settings

PCS-9611 Feeder Relay Date: 2011-08-29

8-35

8 Human Machine Interface

8-36
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function

9 Configurable Function
Table of Contents
9.1 General Description .........................................................................................9-1 9.2 Introduction of PCS-PC Software....................................................................9-1 9.3 Protection Device Configuration.....................................................................9-2
9.3.1 System Configuration......................................................................................................... 9-2 9.3.2 Function Configuration....................................................................................................... 9-2 9.3.3 LED Configuration ............................................................................................................. 9-3 9.3.4 Binary Input Configuration ................................................................................................. 9-3 9.3.5 Binary Output Configuration............................................................................................... 9-4 9.3.6 Setting Configuration ......................................................................................................... 9-5 9.3.7 Logic Graph Configuration ................................................................................................. 9-5

9.4 Configurable Information.................................................................................9-6


9.4.1 Configurable Input Signals................................................................................................. 9-6 9.4.2 Configurable Output Signals ............................................................................................ 9-10 9.4.3 Configurable LED Indicators ............................................................................................ 9-15 9.4.4 Configurable Binary Inputs............................................................................................... 9-15 9.4.5 Configurable Binary Outputs............................................................................................ 9-16

List of Figures
Figure 9.3-1 Interface of system configuration ...................................................................... 9-2 Figure 9.3-2 Interface of function configuration .................................................................... 9-2 Figure 9.3-3 Interface of LED configuration ........................................................................... 9-3 Figure 9.3-4 Interface of binary input configuration .............................................................. 9-4 Figure 9.3-5 Interface of binary output configuration............................................................ 9-4 Figure 9.3-6 Interface of setting configuration....................................................................... 9-5 Figure 9.3-7 Interface of logic graph configuration ............................................................... 9-5

PCS-9611 Feeder Relay Date: 2011-08-29

9-a

9 Configurable Function

9-b
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function

9.1 General Description


The configurable function of this relay can be easy to realize the system configuration, the protection function configuration, the binary input configuration, the binary output configuration, the LED indicator configuration and the logic programming function in this relay through the PCS-PC configuration tool auxiliary software, which makes this relay can meet different practical requirements.

9.2 Introduction of PCS-PC Software


The PCS-PC software is developed in order to meet customers demand on functions of the UAPC platform device, such as device configuration and programmable design. It selects substation as the core of data management and the device as fundamental unit, supporting one substation to govern many devices. The software provides two kinds of operation modes: on-line mode and off-line mode. The on-line mode supports the Ethernet connection with the device through the standard IEC60870-5-103 and can be capable of uploading and downloading the configuration files through Ethernet net; the off-line mode supports the off-line setting configuration. In addition, it also supports programmable logic to meet the demands of a practical engineering. Please see the PCS-PC online help brochure or the instruction manual of PCS-PC configuration tool auxiliary software for more details about the PCS-PC software. The functions of the PCS-PC software: Programmable logic (off-line function) System configuration (off-line function) Function configuration (off-line function) LED indicators configuration (off-line function) Binary signals configuration (off-line function) Setting configuration (off-line & on-line function) Real-time display of analogue and digital quantity of device (on-line function) Display of sequence of report (SOE) (on-line function) Analysis of waveform (off-line & on-line function) File downloading/uploading (on-line function)

PCS-9611 Feeder Relay Date: 2011-08-29

9-1

9 Configurable Function

9.3 Protection Device Configuration


9.3.1 System Configuration
The system configuration is for configuring the hardware and default language etc. of this relay. WARNING! The system configuration shall only be operated by professionals who are familiar with protection object and protection device. Or else, any incorrect configuration may cause relay mal-operation or fail to operate. In general, these configuration works have been completed before equipment leaving factory. If the system configuration is really needed, user must select Execute whole script item in the right-click menu before other configuration operations. The interface of the system configuration is shown in Figure 9.3-1.

Figure 9.3-1 Interface of system configuration

9.3.2 Function Configuration


The system configuration is for configuring the protection function and supervision function of this relay. It can enable or disable a selected function. The interface of the system configuration is shown in Figure 9.3-2.

Figure 9.3-2 Interface of function configuration

9-2
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function

It can enable or disable a protective element or a supervision element by selecting Enable or Disable in the column Attribute.

9.3.3 LED Configuration


The LED configuration is for configuring the LED indicator of this relay. It can define a selected LED to indicate the appointed signal. This relay provides 20 LED indicators, and the first two LED indicators are defined as HEALTHY LED and ALARM, the other 18 LED indicators can be configured by users as required. The interface of the LED configuration is shown in Figure 9.3-3.

Figure 9.3-3 Interface of LED configuration

The column Variable List at the right side provides the elements including protective elements, alarm elements and binary input elements which can output signal through a LED. Drag an expected signal to the menu Signal of a selected LED to make the selected LED indicate the corresponding signal. When the Latched check box is selected, the selected LED could only be reset by a resetting signal. If the Latched check box is not selected, the signals will reset automatically once the trigger signal resets. The column Color is used to choose color for each LED: yellow, green or red are provided to choose from. The label of each LED can be edited by double-click on the item Led label of a selected LED, and then input the expected label.

9.3.4 Binary Input Configuration


The binary input configuration is for configuring the binary inputs of this relay. It can define a selected binary input for inputting a special purpose binary signal. The interface of the binary input configuration is shown in Figure 9.3-4.

PCS-9611 Feeder Relay Date: 2011-08-29

9-3

9 Configurable Function

Figure 9.3-4 Interface of binary input configuration

The column BI Terminal in Binary Input Config lists all the configurable binary inputs of this relay, and the column Variables at the right side lists all the special purpose binary input signals. Drag an expected special purpose binary input to the menu Int. Signal of a selected binary input to make the selected binary input for inputting the corresponding binary input signal. The menu rising edge delay time and falling edge delay time are used to set the pickup time and dropout time of each binary input respectively. The name of each binary input can be edited by double-click on the item BI Name of a selected binary input, and then input the expected name.

9.3.5 Binary Output Configuration


The binary output configuration is for configuring the binary outputs of this relay. It can define a selected binary output for outputting an appointed signal. The interface of the binary output configuration is shown in Figure 9.3-5.

Figure 9.3-5 Interface of binary output configuration

The column BO Terminal in Binary Output Config lists all the configurable binary outputs of this relay, and the column Variables at the right side lists all the binary output signals, such as trip signals, alarm signals etc. Drag an expected binary output signal to the menu Int. Signal of a selected binary output to make the selected binary output for output the corresponding binary
9-4
Date: 2011-08-29 PCS-9611 Feeder Relay

9 Configurable Function

output signal. The name of each binary output can be edited by double-click on the item BO Name of a selected binary output, and then input the expected name.

9.3.6 Setting Configuration


The setting configuration is for configuring the settings of this relay, including system settings, protective settings and so on. It can configure the default setting value in each setting group of a selected setting. It also can set a setting to be visible or hidden in this relay through the menu Visible. After function configuration is finished, the disabled protective function is hidden in this relay and in the setting configuration list of PCS-PC software. The interface of the setting configuration is shown in Figure 9.3-6.

Figure 9.3-6 Interface of setting configuration

9.3.7 Logic Graph Configuration


The logic graph configuration is for configuring some simple logic element to meet the demands of a practical engineering. The interface of the logic graph configuration is shown in Figure 9.3-7.

Figure 9.3-7 Interface of logic graph configuration

PCS-9611 Feeder Relay Date: 2011-08-29

9-5

9 Configurable Function

For more details about how to do a logic graph configuration, see the PCS-PC online help brochure or the instruction manual of PCS-PC configuration tool auxiliary software.

9.4 Configurable Information


9.4.1 Configurable Input Signals
All the configurable input signals of this relay are listed in following table.
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Input Signal BI_52b BI_52a Sig_MCB_VTS Ctrl.In_EnCtrl Ctrl.In_Unblock Ctrl1.In_ManOpn Ctrl1.In_ManCls Ctrl1.In_ManSynChk Ctrl1.In_ManDdChk BI_LowPres_Trp BI_LowPres_Cls 50BF.In_BFP1 50BF.In_BFP2 BI_RstTarg Alm_Maintenance BI_TrigDFR 27P1.OnLoad 27P2.OnLoad 50/51P1.En1 50/51P1.Blk 50/51P2.En1 50/51P2.Blk 50/51P3.En1 50/51P3.Blk 50/51P4.En1 50/51P4.Blk 50/51Q1.En1 breaker The binary input of the auxiliary normal open contact of the circuit breaker The binary signal for inputting the state of the VTs miniature circuit breaker The binary signal for enabling the remote control function The binary signal for unlocking the interlock control function The binary input for inputting the manual tripping signal The binary input for inputting the manual closing signal The binary signal for enabling synchronism check of manual closing The binary signal for enabling dead check of manual closing The binary input of the tripping low pressure signal The binary input of the closing low pressure signal The external initiation signal of the breaker failure protection The inner initiation signal of the breaker failure protection The binary input of the signal resetting signal The device maintenance supervision signal The binary input of the triggering oscillography signal The binary signal for inputting the system on load state of the stage 1 undervoltage protection The binary signal for inputting the system on load state of the stage 2 undervoltage protection The binary signal for enabling the stage 1 overcurrent protection The binary signal for blocking the stage 1 overcurrent protection The binary signal for enabling the stage 2 overcurrent protection The binary signal for blocking the stage 2 overcurrent protection The binary signal for enabling the stage 3 overcurrent protection The binary signal for blocking the stage 3 overcurrent protection The binary signal for enabling the stage 4 overcurrent protection The binary signal for blocking the stage 4 overcurrent protection The binary signal for enabling the stage 1 negative sequence overcurrent protection B07.BI_06 B07.BI_12 B07.BI_07 B07.BI_09 B07.BI_13 Description The binary input of the auxiliary normal close contact of the circuit Default B07.BI_04 B07.BI_05 B07.BI_08 B07.BI_03

9-6
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50/51Q1.Blk 50/51Q2.En1 50/51Q2.Blk 50/51G1.En1 50/51G1.Blk 50/51G2.En1 50/51G2.Blk 50/51G3.En1 50/51G3.Blk 50/51G4.En1 50/51G4.Blk A.50/51G1.En1 A.50/51G1.Blk A.50/51G2.En1 A.50/51G2.Blk A.50/51G3.En1 A.50/51G3.Blk A.50/51G4.En1 A.50/51G4.Blk 50/51SEF1.En1 50/51SEF1.Blk 50/51SEF2.En1 The binary signal for blocking the stage 1 negative sequence overcurrent protection The binary signal for enabling the stage 2 negative sequence overcurrent protection The binary signal for blocking the stage 2 negative sequence overcurrent protection The binary signal for enabling the No.1 group of stage 1 zero sequence overcurrent protection The binary signal for blocking the No.1 group of stage 1 zero sequence overcurrent protection The binary signal for enabling the No.1 group of stage 2 zero sequence overcurrent protection The binary signal for blocking the No.1 group of stage 2 zero sequence overcurrent protection The binary signal for enabling the No.1 group of stage 3 zero sequence overcurrent protection The binary signal for blocking the No.1 group of stage 3 zero sequence overcurrent protection The binary signal for enabling the No.1 group of stage 4 zero sequence overcurrent protection The binary signal for blocking the No.1 group of stage 4 zero sequence overcurrent protection The binary signal for enabling the No.2 group of stage 1 zero sequence overcurrent protection The binary signal for blocking the No.2 group of stage 1 zero sequence overcurrent protection The binary signal for enabling the No.2 group of stage 2 zero sequence overcurrent protection The binary signal for blocking the No.2 group of stage 2 zero sequence overcurrent protection The binary signal for enabling the No.2 group of stage 3 zero sequence overcurrent protection The binary signal for blocking the No.2 group of stage 3 zero sequence overcurrent protection The binary signal for enabling the No.2 group of stage 4 zero sequence overcurrent protection The binary signal for blocking the No.2 group of stage 4 zero sequence overcurrent protection The binary signal for enabling the stage 1 sensitive earth fault protection The binary signal for blocking the stage 1 sensitive earth fault protection The binary signal for enabling the stage 2 sensitive earth fault protection 9-7
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 50/51SEF2.Blk 50/51SEF3.En1 50/51SEF3.Blk 50/51SEF4.En1 50/51SEF4.Blk 50BC.En1 50BC.Blk 50PSOTF.En1 50PSOTF.Blk 50GSOTF.En1 50GSOTF.Blk 49.En1 49.Blk 49.Clr 59P1.En1 59P1.Blk 59P2.En1 59P2.Blk 27P1.En1 27P1.Blk 27P2.En1 27P2.Blk 59Q.En1 59Q.Blk 59G1.En1 59G1.Blk 59G2.En1 59G2.Blk 81U1.En1 81U1.Blk The binary signal for blocking the stage 2 sensitive earth fault protection The binary signal for enabling the stage 3 sensitive earth fault protection The binary signal for blocking the stage 3 sensitive earth fault protection The binary signal for enabling the stage 4 sensitive earth fault protection The binary signal for blocking the stage 4 sensitive earth fault protection The binary signal for enabling the broken conductor protection The binary signal for blocking the broken conductor protection The binary signal for enabling the SOTF overcurrent protection The binary signal for blocking the SOTF overcurrent protection The binary signal for enabling the zero sequence SOTF overcurrent protection The binary signal for blocking the zero sequence SOTF overcurrent protection The binary signal for enabling the thermal overload protection The binary signal for blocking the thermal overload protection The binary signal for clearing the heat of thermal overload protection The binary signal for enabling the stage 1 overvoltage protection The binary signal for blocking the stage 1 overvoltage protection The binary signal for enabling the stage 2 overvoltage protection The binary signal for blocking the stage 2 overvoltage protection The binary signal for enabling the stage 1 undervoltage protection The binary signal for blocking the stage 1 undervoltage protection The binary signal for enabling the stage 2 undervoltage protection The binary signal for blocking the stage 2 undervoltage protection The binary signal for enabling the negative sequence undervoltage protection The binary signal for blocking the negative sequence undervoltage protection The binary signal for enabling the stage 1 zero sequence undervoltage protection The binary signal for blocking the stage 1 zero sequence undervoltage protection The binary signal for enabling the stage 2 zero sequence undervoltage protection The binary signal for blocking the stage 2 zero sequence undervoltage protection The binary signal for enabling the stage 1 under-frequency protection The binary signal for blocking the stage 1 under-frequency protection B07.BI_10

9-8
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 81U2.En1 81U2.Blk 81U3.En1 81U3.Blk 81U4.En1 81U4.Blk 81O1.En1 81O1.Blk 81O2.En1 81O2.Blk 81O3.En1 81O3.Blk 81O4.En1 81O4.Blk 81R1.En1 81R1.Blk 81R2.En1 81R2.Blk 81R3.En1 81R3.Blk 81R4.En1 81R4.Blk 79.En1 79.Blk CLP.En1 CLP.Blk CLP.ShortRst CLP.Init MR1.En1 MR1.Blk MR2.En1 MR2.Blk MR3.En1 MR3.Blk MR4.En1 The binary signal for enabling the stage 2 under-frequency protection The binary signal for blocking the stage 2 under-frequency protection The binary signal for enabling the stage 3 under-frequency protection The binary signal for blocking the stage 3 under-frequency protection The binary signal for enabling the stage 4 under-frequency protection The binary signal for blocking the stage 4 under-frequency protection The binary signal for enabling the stage 1 over-frequency protection The binary signal for blocking the stage 1 over-frequency protection The binary signal for enabling the stage 2 over-frequency protection The binary signal for blocking the stage 2 over-frequency protection The binary signal for enabling the stage 3 over-frequency protection The binary signal for blocking the stage 3 over-frequency protection The binary signal for enabling the stage 4 over-frequency protection The binary signal for blocking the stage 4 over-frequency protection The binary signal for enabling the stage 1 frequency rate-of-change protection The binary signal for blocking the stage 1 frequency rate-of-change protection The binary signal for enabling the stage 2 frequency rate-of-change protection The binary signal for blocking the stage 2 frequency rate-of-change protection The binary signal for enabling the stage 3 frequency rate-of-change protection The binary signal for blocking the stage 3 frequency rate-of-change protection The binary signal for enabling the stage 4 frequency rate-of-change protection The binary signal for blocking the stage 4 frequency rate-of-change protection The binary signal for enabling the auto-recloser The binary signal for blocking the auto-recloser The binary signal for enabling the cold load pickup function The binary signal for blocking the cold load pickup function The binary signal for fast resetting the CLP The binary signal for initiating the CLP The binary signal for enabling the No.1 mechanical protection The binary signal for blocking the No.1 mechanical protection The binary signal for enabling the No.2 mechanical protection The binary signal for blocking the No.2 mechanical protection The binary signal for enabling the No.3 mechanical protection The binary signal for blocking the No.3 mechanical protection The binary signal for enabling the No.4 mechanical protection B07.BI_11

PCS-9611 Feeder Relay Date: 2011-08-29

9-9

9 Configurable Function 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 MR4.Blk Sig_Spare01 Sig_Spare02 Sig_Spare03 Sig_Spare04 Sig_Spare05 Sig_Spare06 Sig_Spare07 Sig_Spare08 Alm_Resv01 Alm_Resv02 Alm_Resv03 Alm_Resv04 Alm_Resv05 Alm_Resv06 Alm_Resv07 Alm_Resv08 Switch1.Dpos Switch2.Dpos Switch3.Dpos Switch4.Dpos Interlock1.In_Opn Interlock1.In_Cls Interlock2.In_Opn Interlock2.In_Cls Interlock3.In_Opn Interlock3.In_Cls Interlock4.In_Opn Interlock4.In_Cls Interlock5.In_Opn Interlock5.In_Cls The binary signal for blocking the No.4 mechanical protection The No.1 programmable spare signal The No.2 programmable spare signal The No.3 programmable spare signal The No.4 programmable spare signal The No.5 programmable spare signal The No.6 programmable spare signal The No.7 programmable spare signal The No.8 programmable spare signal The No.1 reserved alarm signal The No.2 reserved alarm signal The No.3 reserved alarm signal The No.4 reserved alarm signal The No.5 reserved alarm signal The No.6 reserved alarm signal The No.7 reserved alarm signal The No.8 reserved alarm signal The No.1 dual-position switch The No.2 dual-position switch The No.3 dual-position switch The No.4 dual-position switch The interlock check signal of the No.1 manual tripping element The interlock check signal of the No.1 manual closing element The interlock check signal of the No.2 manual tripping element The interlock check signal of the No.2 manual closing element The interlock check signal of the No.3 manual tripping element The interlock check signal of the No.3 manual closing element The interlock check signal of the No.4 manual tripping element The interlock check signal of the No.4 manual closing element The interlock check signal of the No.5 manual tripping element The interlock check signal of the No.5 manual closing element

9.4.2 Configurable Output Signals


All the configurable output signals of this relay are listed in following table.
No. 1 2 3 4 5 6 7 Output Signal FD.Pkp 50/51P1.St 50/51P1.Op 50/51P2.St 50/51P2.Op 50/51P3.St 50/51P3.Op The fault detector operates. The stage 1 overcurrent protection picks up. The stage 1 overcurrent protection operates. The stage 2 overcurrent protection picks up. The stage 2 overcurrent protection operates. The stage 3 overcurrent protection picks up. The stage 3 overcurrent protection operates. Description

9-10
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 50/51P4.St 50/51P4.Op 50/51Q1.St 50/51Q1.Op 50/51Q2.St 50/51Q2.Op 50/51G1.St 50/51G1.Op 50/51G2.St 50/51G2.Op 50/51G3.St 50/51G3.Op 50/51G4.St 50/51G4.Op A.50/51G1.St A.50/51G1.Op A.50/51G2.St A.50/51G2.Op A.50/51G3.St A.50/51G3.Op A.50/51G4.St A.50/51G4.Op 50/51SEF1.St 50/51SEF1.Op 50/51SEF2.St 50/51SEF2.Op 50/51SEF3.St 50/51SEF3.Op 50/51SEF4.St 50/51SEF4.Op 50BF.St 50BF.ReTrp 50BF.Op 50BC.St 50BC.Op 50PSOTF.St 50PSOTF.Op 50GSOTF.St 50GSOTF.Op 49.St 49.Op 27P1.St 27P1.Op The stage 4 overcurrent protection picks up. The stage 4 overcurrent protection operates. The stage 1 negative sequence overcurrent protection picks up. The stage 1 negative sequence overcurrent protection operates. The stage 2 negative sequence overcurrent protection picks up. The stage 2 negative sequence overcurrent protection operates. The No.1 stage 1 zero sequence overcurrent protection picks up. The No.1 stage 1 zero sequence overcurrent protection operates. The No.1 stage 2 zero sequence overcurrent protection picks up. The No.1 stage 2 zero sequence overcurrent protection operates. The No.1 stage 3 zero sequence overcurrent protection picks up. The No.1 stage 3 zero sequence overcurrent protection operates. The No.1 stage 4 zero sequence overcurrent protection picks up. The No.1 stage 4 zero sequence overcurrent protection operates. The No.2 stage 1 zero sequence overcurrent protection picks up. The No.2 stage 1 zero sequence overcurrent protection operates. The No.2 stage 2 zero sequence overcurrent protection picks up. The No.2 stage 2 zero sequence overcurrent protection operates. The No.2 stage 3 zero sequence overcurrent protection picks up. The No.2 stage 3 zero sequence overcurrent protection operates. The No.2 stage 4 zero sequence overcurrent protection picks up. The No.2 stage 4 zero sequence overcurrent protection operates. The stage 1 sensitive earth fault protection picks up. The stage 1 sensitive earth fault protection operates. The stage 2 sensitive earth fault protection picks up. The stage 2 sensitive earth fault protection operates. The stage 3 sensitive earth fault protection picks up. The stage 3 sensitive earth fault protection operates. The stage 4 sensitive earth fault protection picks up. The stage 4 sensitive earth fault protection operates. The breaker failure protection picks up. The breaker failure protection re-trip operates. The breaker failure protection operates. The broken conductor protection picks up. The broken conductor protection operates. The SOTF overcurrent protection picks up. The SOTF overcurrent protection operates. The zero sequence SOTF overcurrent protection picks up. The zero sequence SOTF overcurrent protection operates. The thermal overload protection picks up. The thermal overload protection operates. The stage 1 undervoltage protection picks up. The stage 1 undervoltage protection operates. 9-11
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 9-12


Date: 2011-08-29

27P2.St 27P2.Op 59P1.St 59P1.Op 59P2.St 59P2.Op 59Q.St 59Q.Op 59G1.St 59G1.Op 59G2.St 59G2.Op 81U1.St 81U1.Op 81U2.St 81U2.Op 81U3.St 81U3.Op 81U4.St 81U4.Op 81O1.St 81O1.Op 81O2.St 81O2.Op 81O3.St 81O3.Op 81O4.St 81O4.Op 81R1.St 81R1.Op 81R2.St 81R2.Op 81R3.St 81R3.Op 81R4.St 81R4.Op 79.InProg 79.Close 79.Close_3PS1 79.Close_3PS2 79.Close_3PS3 79.Close_3PS4 79.Ready

The stage 2 undervoltage protection picks up. The stage 2 undervoltage protection operates. The stage 1 overvoltage protection picks up. The stage 1 overvoltage protection operates. The stage 2 overvoltage protection picks up. The stage 2 overvoltage protection operates. The negative sequence overvoltage protection picks up. The negative sequence overvoltage protection operates. The stage 1 zero sequence overvoltage protection picks up. The stage 1 zero sequence overvoltage protection operates. The stage 2 zero sequence overvoltage protection picks up. The stage 2 zero sequence overvoltage protection operates. The stage 1 under-frequency protection picks up. The stage 1 under-frequency protection operates. The stage 2 under-frequency protection picks up. The stage 2 under-frequency protection operates. The stage 3 under-frequency protection picks up. The stage 3 under-frequency protection operates. The stage 4 under-frequency protection picks up. The stage 4 under-frequency protection operates. The stage 1 over-frequency protection picks up. The stage 1 over-frequency protection operates. The stage 2 over-frequency protection picks up. The stage 2 over-frequency protection operates. The stage 3 over-frequency protection picks up. The stage 3 over-frequency protection operates. The stage 4 over-frequency protection picks up. The stage 4 over-frequency protection operates. The stage 1 frequency rate-of-change protection picks up. The stage 1 frequency rate-of-change protection operates. The stage 2 frequency rate-of-change protection picks up. The stage 2 frequency rate-of-change protection operates. The stage 3 frequency rate-of-change protection picks up. The stage 3 frequency rate-of-change protection operates. The stage 4 frequency rate-of-change protection picks up. The stage 4 frequency rate-of-change protection operates. The auto-recloser picks up. The auto-recloser operates. The 1st shot auto-recloser operates. The 2nd shot auto-recloser operates. The 3rd shot auto-recloser operates. The 4th shot auto-recloser operates. The auto-recloser is ready for operation.

PCS-9611 Feeder Relay

9 Configurable Function 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 79.Fail 79.Reset MR1.St MR1.Op MR2.St MR2.Op MR3.St MR3.Op MR4.St MR4.Op Ctrl1.Opn Ctrl1.Cls Ctrl2.Opn Ctrl2.Cls Ctrl3.Opn Ctrl3.Cls Ctrl4.Opn Ctrl4.Cls Ctrl5.Opn Ctrl5.Cls Alm_Device Alm_52b VTS.Alm_SynVT VTS.Alm CTS.Alm 49.Alm Alm_CommTest Alm_TimeSync Alm_Maintenance Alm_LowPres_Trp Alm_LowPres_Cls Alm_Resv1 Alm_Resv2 Alm_Resv3 Alm_Resv4 Alm_Resv5 Alm_Resv6 Alm_Resv7 Alm_Resv8 B07.BI_01 B07.BI_02 B07.BI_03 B07.BI_04 The operation of auto-recloser is failed. The auto-recloser is restored. The No.1 mechanical protection picks up. The No.1 mechanical protection operates. The No.2 mechanical protection picks up. The No.2 mechanical protection operates. The No.3 mechanical protection picks up. The No.3 mechanical protection operates. The No.4 mechanical protection picks up. The No.4 mechanical protection operates. The No.1 group of remote tripping output operates. The No.1 group of remote closing output operates. The No.2 group of remote tripping output operates. The No.2 group of remote closing output operates. The No.3 group of remote tripping output operates. The No.3 group of remote closing output operates. The No.4 group of remote tripping output operates. The No.4 group of remote closing output operates. The No.5 group of remote tripping output operates. The No.5 group of remote closing output operates. Anyone of the software supervision alarm occurs. The normal close contact of the CB is abnormal. The synchro-check voltage transformer circuit is failed. The protection voltage transformer circuit is failed. The current transformer is failed. The thermal overload situation is occurred. The communication test operation is executed. The time synchronization is not correct. The binary input for denoting maintenance situation is energized. The pressure of the tripping circuit is low. The pressure of the closing circuit is low. The No.1 reserved alarm signal is issued. The No.2 reserved alarm signal is issued. The No.3 reserved alarm signal is issued. The No.4 reserved alarm signal is issued. The No.5 reserved alarm signal is issued. The No.6 reserved alarm signal is issued. The No.7 reserved alarm signal is issued. The No.8 reserved alarm signal is issued. The No.1 binary input is energized. The No.2 binary input is energized. The No.3 binary input is energized. The No.4 binary input is energized. 9-13
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 B07.BI_05 B07.BI_06 B07.BI_07 B07.BI_08 B07.BI_09 B07.BI_10 B07.BI_11 B07.BI_12 B07.BI_13 B07.BI_14 B07.BI_15 B07.BI_16 B07.BI_17 B07.BI_18 B07.BI_19 CLP.St 25M.Ok_SynChk 25M.Ok_DdChk 25A.Ok_SynChk 25A.Ok_DdChk VTS.InstAlm CTS.InstAlm Prot.OnLoad Breaker.Dpos_HMI Breaker.Dpos_RMT Switch1.Dpos_HMI Switch1.Dpos_RMT Switch2.Dpos_HMI Switch2.Dpos_RMT Switch3.Dpos_HMI Switch3.Dpos_RMT Switch4.Dpos_HMI Switch4.Dpos_RMT The No.5 binary input is energized. The No.6 binary input is energized. The No.7 binary input is energized. The No.8 binary input is energized. The No.9 binary input is energized. The No.10 binary input is energized. The No.11 binary input is energized. The No.12 binary input is energized. The No.13 binary input is energized. The No.14 binary input is energized. The No.15 binary input is energized. The No.16 binary input is energized. The No.17 binary input is energized. The No.18 binary input is energized. The No.19 binary input is energized. The cold load pickup element picks up. The synchronism check of the manual closing function is satisfied. The dead check of the manual closing function is satisfied. The synchronism check of the auto-recloser is satisfied. The dead check of the auto-recloser is satisfied. The fast voltage transformer supervision is issued. The fast current transformer supervision is issued. The system on load condition is satisfied. The state of the circuit breaker for displaying on the local HMI. The state of the circuit breaker for sending to the remote HMI. The state of the No.1 switch for displaying on the local HMI. The state of the No.1 switch for sending to the remote HMI. The state of the No.2 switch for displaying on the local HMI. The state of the No.2 switch for sending to the remote HMI. The state of the No.2 switch for displaying on the local HMI. The state of the No.2 switch for sending to the remote HMI. The state of the No.2 switch for displaying on the local HMI. The state of the No.2 switch for sending to the remote HMI.

NOTE! The configurable output signals xxxxx.Dpos_HMI and xxxxx.Dpos_RMT are used to indicate the state of the corresponding circuit breaker or switch. Each signal is a four-state output state, and the state codes are listed as below.
Target State Code 0x00 Local HMI 0x01 0x02 0x03 Open state: 0 Open state: 1 Open state: 0 Open state: 1 Description Close state: 0 Close state: 0 Close state: 1 Close state: 1

9-14
Date: 2011-08-29

PCS-9611 Feeder Relay

9 Configurable Function 0x80 Remote HMI 0x81 0x82 0x83 Open state: 0 Open state: 1 Open state: 0 Open state: 1 Close state: 0 Close state: 0 Close state: 1 Close state: 1

9.4.3 Configurable LED Indicators


All the configurable LED indicators of this relay are listed in following table.
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 LED LED_01 LED_02 LED_03 LED_04 LED_05 LED_06 LED_07 LED_08 LED_09 LED_10 LED_11 LED_12 LED_13 LED_14 LED_15 LED_16 LED_17 LED_18 LED_19 LED_20 Description The No.1 LED, it is not configurable. The No.2 LED, it is not configurable. The No.3 LED, it is configurable. The No.4 LED, it is configurable. The No.5 LED, it is configurable. The No.6 LED, it is configurable. The No.7 LED, it is configurable. The No.8 LED, it is configurable. The No.9 LED, it is configurable. The No.10 LED, it is configurable. The No.11 LED, it is configurable. The No.12 LED, it is configurable. The No.13 LED, it is configurable. The No.14 LED, it is configurable. The No.15 LED, it is configurable. The No.16 LED, it is configurable. The No.17 LED, it is configurable. The No.18 LED, it is configurable. The No.19 LED, it is configurable. The No.20 LED, it is configurable. Default HEALTHY ALARM TRIP RECLOSE CB OPEN CB CLOSE Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance

9.4.4 Configurable Binary Inputs


All the configurable binary inputs of this relay are listed in following table.
No. 1 2 3 4 5 6 7 8 9 10 Binary Input B07.BI_01 B07.BI_02 B07.BI_03 B07.BI_04 B07.BI_05 B07.BI_06 B07.BI_07 B07.BI_08 B07.BI_09 B07.BI_10 Description The No.1 binary input, it is configurable. The No.2 binary input, it is configurable. The No.3 binary input, it is configurable. The No.4 binary input, it is configurable. The No.5 binary input, it is configurable. The No.6 binary input, it is configurable. The No.7 binary input, it is configurable. The No.8 binary input, it is configurable. The No.9 binary input, it is configurable. The No.10 binary input, it is configurable. Ctrl.In_EnCtrl BI_52b BI_52a BI_RstTarg BI_LowPres_Cls Sig_MCB_VTS 50BF.In_BFP1 49.Clr 9-15
Date: 2011-08-29

Default

PCS-9611 Feeder Relay

9 Configurable Function 11 12 13 14 15 16 17 18 19 B07.BI_11 B07.BI_12 B07.BI_13 B07.BI_14 B07.BI_15 B07.BI_16 B07.BI_17 B07.BI_18 B07.BI_19 The No.11 binary input, it is configurable. The No.12 binary input, it is configurable. The No.13 binary input, it is configurable. The No.14 binary input, it is configurable. The No.15 binary input, it is configurable. The No.16 binary input, it is configurable. The No.17 binary input, it is configurable. The No.18 binary input, it is configurable. The No.19 binary input, it is configurable. 79.Blk Alm_Maintenance Ctrl1.ManCls

9.4.5 Configurable Binary Outputs


All the configurable binary outputs of this relay are listed in following table.
No. 1 2 3 4 5 Binary Output B06.BO_07 B06.BO_08 B06.BO_09 B06.BO_10 B06.BO_11 Description The No.7 programmable binary output of the module NR4521 The No.8 programmable binary output of the module NR4521 The No.9 programmable binary output of the module NR4521 The No.10 programmable binary output of the module NR4521 The No.11 programmable binary output of the module NR4521 Default Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance Alm_Maintenance

NOTE! Other configurable binary outputs which are not listed in above table only can be configured through the setting [XXXX.OutMap] (XXXX is the abbreviation of a protective element, such as 50/51P1, 50/51G1, 59P1 etc.) of each function element. For more details about these settings, please see Chapter 7.

9-16
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication

10 Communication
Table of Contents
10.1 General ..........................................................................................................10-1 10.2 Rear Communication Port Information.......................................................10-1
10.2.1 RS-485 Interface............................................................................................................ 10-1 10.2.2 Ethernet Interface .......................................................................................................... 10-3 10.2.3 IEC60870-5-103 Communication................................................................................... 10-4 10.2.4 IEC61850 Communication ............................................................................................. 10-4 10.2.5 DNP3.0 Communication ................................................................................................ 10-4

10.3 IEC60870-5-103 Interface .............................................................................10-4


10.3.1 Physical Connection and Link Layer .............................................................................. 10-5 10.3.2 Initialization .................................................................................................................... 10-5 10.3.3 Time Synchronization .................................................................................................... 10-5 10.3.4 Spontaneous Events ...................................................................................................... 10-5 10.3.5 General Interrogation ..................................................................................................... 10-6 10.3.6 Cyclic Measurements..................................................................................................... 10-6 10.3.7 General Commands....................................................................................................... 10-6 10.3.8 Generic Functions.......................................................................................................... 10-6 10.3.9 Disturbance Records ..................................................................................................... 10-7

10.4 IEC61850 Interface .......................................................................................10-7


10.4.1 Overview........................................................................................................................ 10-7 10.4.2 Communication Profiles ................................................................................................. 10-8 10.4.3 Server Data Organization .............................................................................................. 10-9 10.4.4 Server Features and Configuration .............................................................................. 10-12 10.4.5 ACSI Conformance ...................................................................................................... 10-13 10.4.6 Logical Nodes .............................................................................................................. 10-18

10.5 DNP3.0 Interface.........................................................................................10-20


10.5.1 Overview...................................................................................................................... 10-20
PCS-9611 Feeder Relay Date: 2011-08-29

10-a

10 Communication

10.5.2 Link Layer Functions ....................................................................................................10-20 10.5.3 Transport Functions......................................................................................................10-20 10.5.4 Application Layer Functions..........................................................................................10-21

List of Figures
Figure 10.2-1 EIA RS-485 bus connection arrangements ....................................................10-2 Figure 10.2-2 Format of IP and submask address ................................................................10-3 Figure 10.2-3 Ethernet communication cable .......................................................................10-3 Figure 10.2-4 Ethernet communication structure .................................................................10-4

10-b
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication

10.1 General
This section outlines the remote data communication interfaces of this relay. The relay can support several protocols: IEC60870-5-103, IEC61850 and DNP3.0. Setting the relevant communication parameter can select the expected protocol (see Section 7.6). The EIA RS-485 standardized interfaces are isolated, as well as the Ethernet interfaces, and are suitable for permanent connection whichever protocol is selected. The advantage of this type of connection is that up to 32 relays can be daisy chained together using a simple twisted pair electrical connection. It should be noted that the descriptions contained within this section do not aim to fully detail the protocol itself. The relevant documentation for the protocol should be referred to for this information. This section serves to describe the specific implementation of the protocol in the relay.

10.2 Rear Communication Port Information


10.2.1 RS-485 Interface
This relay provides some rear RS-485 communication ports, and each port has two terminals in the screw connector located on the back of the relay. This port has a common ground terminal for the earth shield of the communication cable. See Section 6.5 for details of the connection terminals. The rear ports provide RS-485 serial data communication and they are intended for use with a permanently wired connection to a remote control center. The protocol provided by the relay is indicated in the relays Comm Settings submenu (see Section 7.6). By using the keypad and LCD, configure the relevant communication protocol parameters, the corresponding protocol and will be selected. 10.2.1.1 EIA RS-485 Standardized Bus The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the product. The connection is polarized and whilst the products connection diagrams indicate the polarization of the connection terminals it should be noted that there is no agreed definition of which terminal is which. If the master is unable to communicate with the product, and the communication parameters match, then it is possible that the two-wire connection is reversed. 10.2.1.2 Bus Termination The EIA RS-485 bus must have 120 (Ohm) Watt terminating resistors fitted at either end across the signal wires (see Figure 10.2-1). Some devices may be able to provide the bus terminating resistors by different connection or configuration arrangements, in which case separate external components will not be required. However, this product does not provide such a facility, so if it is located at the bus terminus then an external termination resistor will be required.

PCS-9611 Feeder Relay Date: 2011-08-29

10-1

10 Communication

EIA RS-485

Figure 10.2-1 EIA RS-485 bus connection arrangements

10.2.1.3 Bus Connections & Topologies The EIA RS-485 standard requires that each device is directly connected to the physical cable that is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop bus topologies are not part of the EIA RS-485 standard and are forbidden by it also. Two-core screened cable is recommended. The specification of the cable will be dependent on the application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must not exceed 500m. The screen must be continuous and connected to ground at one end, normally at the master connection point; it is important to avoid circulating currents, especially when the cable runs between buildings, for both safety and noise reasons. This product does not provide a signal ground connection. If a signal ground connection is present in the bus cable then it must be ignored, although it must have continuity for the benefit of other devices connected to the bus. At no stage must the signal ground be connected to the cables screen or to the products chassis. This is for both safety and noise reasons. 10.2.1.4 Biasing It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal level has an indeterminate state because the bus is not being actively driven. This can occur when all the slaves are in receive mode and the master is slow to turn from receive mode to transmit mode. This may be because the master purposefully waits in receive mode, or even in a high impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss the first bits of the first character in the packet, which results in the slave rejecting the message and consequentially not responding. Symptoms of these are poor response times (due to retries), increasing message error counters, erratic communications, and even a complete failure to communicate. Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There should only be one bias point on the bus, which is best situated at the master connection point. The DC source used for the bias must be clean; otherwise noise will be injected. Note that some devices may (optionally) be able to provide the bus bias, in which case external components will not be required. NOTE!

10-2
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication

It is extremely important that the 120 termination resistors are fitted. Failure to do so will result in an excessive bias voltage that may damage the devices connected to the bus. As the field voltage is much higher than that required, NR can not assume responsibility for any damage that may occur to a device connected to the network as a result of incorrect application of this voltage. Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs) as this may cause noise to be passed to the communication network.

10.2.2 Ethernet Interface


This relay provides some rear Ethernet interfaces and they are unattached to each other. The parameters of each Ethernet port can be configured in the submenu Comm Settings (see Section 7.6) except for the protocol which is a uniform parameter for these Ethernet ports. 10.2.2.1 IP Address and Network Communication Address A brief explanation of IP and network submask is made as below. There are four sections for an IP address.

Figure 10.2-2 Format of IP and submask address

Where: Section 1 and Section 2 can be set separately Section 3 256 + Section 4 = network communication address for IEC60087-5-103 The network communication address for IEC60087-5-103 has above relationship described as an equation with section 3 and section 4 of the IP address. 10.2.2.2 Ethernet Standardized Communication Cable It is recommended to use 4-pair screened twisted category 5E cable as the communication cable. A picture is shown below.

Figure 10.2-3 Ethernet communication cable


PCS-9611 Feeder Relay Date: 2011-08-29

10-3

10 Communication

10.2.2.3 Connections and Topologies Each device is connected to an exchanger via communication cable and thereby to form a star structure network. Dual-network is recommended in order to increase reliability. The SCADA is also connected to the exchanger and will play a role of master station, so the every equipment which has been connected to the exchanger will play a role of slave unit.

Figure 10.2-4 Ethernet communication structure

10.2.3 IEC60870-5-103 Communication


The IEC specification IEC60870-5-103: Telecontrol Equipment and Systems, Part 5: Transmission Protocols Section 103 defines the use of standards IEC60870-5-1 to IEC60870-5-5 to perform communication with protection equipment. The IEC60870-5-103 protocol is to use a twisted pair EIA RS-485 connection over distances up to 500m. This relay operates as a slave in the system, responding to commands from a master station.

10.2.4 IEC61850 Communication


The IEC specification IEC61850: Communication Networks and Systems in Substations, a new protocol defines the communication standards in substations. The standard configuration for the IEC61850 protocol is based on the Ethernet.

10.2.5 DNP3.0 Communication


The DNP3.0 (Distributed Network Protocol) protocol can support the OSI/EPA model of the ISO (International Organization for Standards), and it includes four parts: application layer protocol, transport functions, data link layer protocol and data object library. The DNP3.0 protocol is to use a twisted pair EIA RS-485 connection over distances up to 500m. This relay operates as a slave in the system, responding to commands from a master station.

10.3 IEC60870-5-103 Interface


The IEC60870-5-103 interface is a master/slave interface with this relay as the slave device.

10-4
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication

The relay conforms to compatibility level 2; compatibility level 3 is not supported. The following IEC60870-5-103 facilities are supported by this interface: initialization (reset), time synchronization, event record extraction, general interrogation, cyclic measurements, general commands and disturbance records.

10.3.1 Physical Connection and Link Layer


The EIA RS-485 standardized ports are available for IEC60870-5-103 in this relay. The baudrate is optional: 4800bps, 9600bps, 19200bps, 38400bps, 57600bps or 115200bps. The unattached Ethernet ports are available for IEC60870-5-103 in this relay. The transmission speed is 100Mbit/s. The link layer strictly abides by the rules defined in the IEC60870-5-103.

10.3.2 Initialization
Whenever the relay has been powered up, or if the communication parameters have been changed, a reset command is required to initialize the communications. The relay will respond to either of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU will clear any unsent messages in the relays transmit buffer. The relay will respond to the reset command with an identification message ASDU 5, the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB depending on the nature of the reset command. In addition to the above identification message, if the relay has been powered up it will also produce a power up event.

10.3.3 Time Synchronization


The time and date of this relay can be set by using the time synchronization feature of the IEC60870-5-103 protocol. The relay will correct for the transmission delay as specified in IEC60870-5-103. If the time synchronization message is sent as a send/confirm message, then the relay will respond with a confirmation. Whether the time synchronization message is sent as a send confirmation or a broadcast (send without any reply) message, a time synchronization Class 1 event will be generated. If the clock is synchronized using the IRIG-B input then it will not be possible to set clock by using the IEC60870-5-103 interface. An attempt to set the time via the interface will cause this relay to create an event with the current date and time taken from the IRIG-B synchronized internal clock.

10.3.4 Spontaneous Events


The spontaneous events are categorized using the following information: type identification (TYP), function type (FUN) and information number (INF). This relay can support ASDU 1, ASDU 2, ASDU 40 and ASDU 41, the cause of transmission (COT) is 1. ASDU 1, time-tagged message: alarm messages, special purpose binary input state change messages.
10-5
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication

ASDU 2, time-tagged message with relative time: tripping messages and fault detector pickup messages. ASDU 40, single point information: general binary input state change messages. ASDU 41, single point information with time-tagged: sequence of event (SOE) messages.

10.3.5 General Interrogation


The GI can be used to read the status of the relay, the function numbers, and information numbers that will be returned during the GI cycle. The GI cycle strictly abides by the rules defined in the IEC60870-5-103. The relay will respond to this GI command with an ASDU 44 message, the cause of transmission (COT) of this response is 9. Referring the IEC60870-5-103 standard can get the enough details about general interrogation.

10.3.6 Cyclic Measurements


The relay will produce measured values using ASDU 50 on a cyclical basis, this can be read from the relay using a Class 2 poll (note ADSU 3 and ASDU 9 are not used). The cause of transmission is 2. The rate at which the relay produces new measured values is fixed (about one second). It should be noted that the measurands transmitted by the relay are sent as a proportion of corresponding times the rated value of the analog value.

10.3.7 General Commands


A list of the supported commands (in control direction) is contained in the following table. The relay will not respond to other commands, and short-term communication interruption will occur.
TYP ASDU 64 ASDU 64 ASDU 64 ASDU 64 ASDU 64 ASDU 64 FUN 1 1 1 1 1 1 INF 48 48 48 48 48 48 DCC 0x81 0x82 0x01 0x02 0xC1 0xC2 Function Remote trip with selection Remote close with selection Remote trip with execution Remote close with execution Remote trip with abortion Remote close with abortion

If the relay receives one of the command messages correctly, it will respond with an ACK message, and then send a message which has the same ASDU data with the control direction message in the next communication turn.

10.3.8 Generic Functions


The generic functions can be used to read the setting and protection measurement of this relay, and modify the setting. Two supported type identifications are ASDU 21 and ASDU 10. For more details about generic functions, see the IEC60870-5-103 standard.

10-6
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication

Generic functions in control direction


INF 240 241 243 244 245 248 249 250 251 Semantics Read headings of all defined groups Read values or attributes of all entries in one group Read directory of a single entry Read value or attribute of a single entry General interrogation of generic data Write entry Write entry with confirmation Write entry with execution Write entry abort

Generic functions in monitor direction


INF 240 241 243 244 245 249 250 251 Semantics Read headings of all defined groups Read values or attributes of all entries of one group Read directory of a single entry Read value or attribute of a single entry End of general interrogation of generic data Write entry with confirmation Write entry with execution Write entry aborted

10.3.9 Disturbance Records


This relay can store up to eight disturbance records in its memory. A pickup of the fault detector or an operation of the relay can make the relay store the disturbance records. The disturbance records are stored in uncompressed format and can be extracted using the standard mechanisms described in the standard of IEC60870-5-103.

10.4 IEC61850 Interface


10.4.1 Overview
The IEC61850 software module of PCS-9000 series is adopted in the device. The IEC61850 standard is the result of years of work by electric utilities and vendors of electronic equipment to produce standardized communication systems. The IEC61850 is a series of standards describing client/server and peer-to-peer communications, substation design and configuration, testing, environmental and project standards. The complete set includes: IEC61850-1: IEC61850-2: IEC61850-3: Introduction and overview Glossary General requirements

PCS-9611 Feeder Relay Date: 2011-08-29

10-7

10 Communication

IEC61850-4: IEC61850-5: IEC61850-6: IEC61850-7-1: IEC61850-7-2: IEC61850-7-3: IEC61850-7-4: IEC61850-8-1: IEC61850-9-1: IEC61850-9-2: IEC61850-10:

System and project management Communications and requirements for functions and device models Configuration description language for communication in electrical substations related to IEDs Basic communication structure for substation and feeder equipment Principles and models Basic communication structure for substation and feeder equipment - Abstract communication service interface (ACSI) Basic communication structure for substation and feeder equipment Common data classes Basic communication structure for substation and feeder equipment Compatible logical node classes and data classes Specific Communication Service Mapping (SCSM) Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC8802-3 Specific Communication Service Mapping (SCSM) Sampled values over serial unidirectional multi-drop point to point link Specific Communication Service Mapping (SCSM) Sampled values over ISO/IEC8802-3 Conformance testing

These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended that all those involved with any IEC61850 implementation obtain this document set.

10.4.2 Communication Profiles


The PCS-9600 series relay supports IEC61850 server services over TCP/IP communication protocol stacks. The TCP/IP profile requires the PCS-9600 series relay to have an IP address to establish communications. These addresses are located in the submenu Comm Settings, see Section 7.6 for further details. MMS Protocol IEC61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer of real-time data. This protocol has been in existence for a number of years and provides a set of services suitable for the transfer of data within a substation LAN environment. Actual MMS protocol services are mapped to IEC61850 abstract services in IEC61850-8-1. Client/server This is a connection-oriented type of communication. The connection is initiated by the client, and communication activity is controlled by the client. IEC61850 clients are often substation computers running HMI programs or SOE logging software. Servers are usually substation equipment such as protection relays, meters, RTUs, transformer, tap changers, or bay controllers. Peer-to-peer
10-8
Date: 2011-08-29 PCS-9611 Feeder Relay

10 Communication

This is a non-connection-oriented, high speed type of communication usually between substation equipment, such as protection relays. GOOSE is the method of peer-to-peer communication. Substation configuration language (SCL) A substation configuration language is the number of files used to describe the configuration of substation equipment. Each configured device has an IED Capability Description (ICD) file and a Configured IED Description (CID) file. The substation single line information is stored in a System Specification Description (SSD) file. The entire substation configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individual ICD files and the SSD file.

10.4.3 Server Data Organization


IEC61850 defines an object-oriented approach to data and services. An IEC61850 physical device can contain one or more logical device(s) (for proxy). Each logical device can contain many logical nodes. Each logical node can contain many data objects. Each data object is composed of data attributes and data attribute components. Services are available at each level for performing various functions, such as reading, writing, control commands, and reporting. Each IED represents one IEC61850 physical device. The physical device contains one logical device, and the logical device contains many logical nodes. The logical node LPHD contains information about the IED physical device. The logical node LLN0 contains information about the IED logical device. 10.4.3.1 Digital Status Values The GGIO logical node is available in the PCS-9600 series relays to provide access to digital status points (including general I/O inputs and warnings) and associated timestamps and quality flags. The data content must be configured before the data can be used. GGIO provides digital status points for access by clients. It is intended that clients use GGIO in order to access digital status values from the PCS-9600 series relays. Clients can utilize the IEC61850 buffered reporting features available from GGIO in order to build sequence of events (SOE) logs and HMI display screens. Buffered reporting should generally be used for SOE logs since the buffering capability reduces the chances of missing data state changes. All needed status data objects are transmitted to HMI clients via buffered reporting, and the corresponding buffered reporting control block (BRCB) is defined in LLN0. 10.4.3.2 Analog Values Most of the analog measured values are available through the MMXU logical nodes, and metering values in MMTR, the others in MMXN, MSQI and so on. Each MMXU logical node provides data from an IED current/voltage source. There is one MMXU available for each configurable source. MMXU1 provides data from CT/VT source 1 (usually for protection purpose), and MMXU2 provides data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the following data for each source:

PCS-9611 Feeder Relay Date: 2011-08-29

10-9

10 Communication

MMXU.MX.TotW: MMXU.MX.TotVAr: MMXU.MX.TotPF: MMXU.MX.Hz: MMXU.MX.PPV.phsAB: MMXU.MX.PPV.phsBC: MMXU.MX.PPV.phsCA: MMXU.MX.PhV.phsA: MMXU.MX.PhV.phsB: MMXU.MX.PhV.phsC: MMXU.MX.A.phsA: MMXU.MX.A.phsB: MMXU.MX.A.phsC: MMXU.MX.A.neut:

three-phase active power three-phase reactive power three-phase power factor frequency phase AB voltage magnitude and angle phase BC voltage magnitude and angle Phase CA voltage magnitude and angle phase AG voltage magnitude and angle phase BG voltage magnitude and angle phase CG voltage magnitude and angle phase A current magnitude and angle phase B current magnitude and angle phase C current magnitude and angle ground current magnitude and angle

10.4.3.3 Protection Logical Nodes The following list describes the protection elements for all PCS-9600 series relays. The specified relay will contain a subset of protection elements from this list. PDIF: PDIS: PIOC: PTOC: transformer instantaneous differential, transformer percent differential phase distance, ground distance phase instantaneous overcurrent, neutral instantaneous overcurrent, ground instantaneous overcurrent, negative-sequence instantaneous overcurrent. phase time overcurrent, neutral time overcurrent, ground time overcurrent, negative-sequence time overcurrent, neutral directional overcurrent, negative-sequence directional overcurrent phase undervoltage, auxiliary undervoltage, third harmonic neutral undervoltage underfrequency phase overvoltage, neutral overvoltage, auxiliary overvoltage, negative sequence overvoltage breaker failure autoreclosure

PTUV: PTUF: PTOV: RBRF: RREC:

The protection elements listed above contain start (pickup) and operate flags, instead of any element has its own start (pickup) flag separately, all the elements share a common start (pickup) flags PTRC.ST.Str.general in a PCS-9600 series relay. The operate flag for PTOC1 is PTOC1.ST.Op.general. For the PCS-9600 series relay protection elements, these flags take their values from related module for the corresponding element. Similar to digital status values, the protection trip information is reported via BRCB, and it also locates in LLN0. 10.4.3.4 LLN0 and Other Logical Nodes Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address common issues for Logical Devices. In PCS-9600 series relays, most of the public services, the
10-10
Date: 2011-08-29 PCS-9611 Feeder Relay

10 Communication

common settings, control values and some device oriented data objects are available here. The public services may be BRCB, URCB and GSE control blocks and similar global defines for the whole device; the common settings (the logic nodes LPHDPTRC also contain some related common settings) include all the setting items of communication settings. System settings and some of the protection setting items, which can be configured to two or more protection elements (logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local operation for complete logical device, when it is true, all the remote control commands to the IED will be blocked and those commands make effective until the item Loc is changed to false. Besides the logical nodes we describe above, there are some other logical nodes below in the IEDs: MMUX: This LN shall be used to acquire values from CTs and VTs and calculate measurands such as RMS values for current and voltage or power flows out of the acquired voltage and current samples. These values are normally used for operational purposes such as power flow supervision and management, screen displays, state estimation, etc. The requested accuracy for these functions has to be provided. Physical device information, the logical node to model common issues for physical device. Protection trip conditioning, it shall be used to connect the operate outputs of one or more protection functions to a common trip to be transmitted to XCBR. In addition or alternatively, any combination of operate outputs of protection functions may be combined to a new operate of PTRC. Disturbance recorder function. It triggers the fault wave recorder and its output refers to the IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System (IEC60255-24). All enabled channels are included in the recording, independently of the trigger mode. Generic automatic process control, it is used to model in a generic way the processing/automation of functions, for example the sequence control functions for PCS-9600 series relays. Switch controller. This class is used to control all switching conditions of XCBR and XSWI. A remote switching command (for example select-before-operate) arrives here firstly. Breaker control. The XCBR logical node is directly associated with the breaker control feature. XCBR1.ST.Pos: This is the position of the breaker. If the breaker control logic indicates that the breaker, or any single pole of the breaker, is closed, then the breaker position state is on. If the breaker control logic indicates that the breaker is open, then the breaker position state is off. XCBR1.ST.BlkOpn: This is the state of the block open command logic. When true, breaker open commands from IEC61850 clients will be rejected. XCBR1.ST.BlkCls: This is the state of the block close command logic. When true, breaker close commands from IEC61850 clients will be rejected. XCBR1.CO.Pos: This is where IEC61850 clients can issue open or close commands to the breaker. SBO control with normal enhanced security is the only supported IEC61850 control model.
10-11
Date: 2011-08-29

LPHD: PTRC:

RDRE:

GAPC:

CSWI:

XCBR:

PCS-9611 Feeder Relay

10 Communication

10.4.4 Server Features and Configuration


10.4.4.1 Buffered/Unbuffered Reporting IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured to transmit information of protection trip information (in the Protection logical nodes), binary status values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The reporting control blocks can be configured in CID files, and then be sent to the IED via an IEC61850 client. The following items can be configured. TrgOps: Trigger options. The following bits are supported by the PCS-9600 series relays: Bit 1: Data-change Bit 4: Integrity Bit 5: General interrogation OptFlds: Option Fields. The following bits are supported by the PCS-9600 series relays: Bit 1: Sequence-number Bit 2: Report-time-stamp Bit 3: Reason-for-inclusion Bit 4: Data-set-name Bit 5: Data-reference Bit 6: Buffer-overflow (for buffered reports only) Bit 7: EntryID (for buffered reports only) Bit 8: Conf-revision Bit 9: Segmentation IntgPd: Integrity period. BufTm: Buffer time. 10.4.4.2 File Transfer MMS file services are supported to allow transfer of oscillography, event record or other files from a PCS-9600 series relay. 10.4.4.3 Timestamps The universal time coordinated (UTC) timestamp values associated with all IEC61850 data items represent the time of the last change of either the value or quality flags of the data item. 10.4.4.4 Logical Node Name Prefixes IEC61850 specifies that each logical node can have a name with a total length of 11 characters. The name is composed of: a five or six-character name prefix; a four-character standard name (for
10-12
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication

example, MMXU, GGIO, PIOC, etc.); a one or two-character instantiation index. Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable. Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is recommended that a consistent naming convention be used for an entire substation project. 10.4.4.5 GOOSE Services IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support, Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be given a higher priority than standard Ethernet traffic, and they can be separated onto specific VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE publisher contains a GOOSE control block to configure and control the transmission. The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE function link settings in device. The PCS-9600 series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE) communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this dataset that is transferred using GOOSE message services. The GOOSE related dataset is configured in the CID file and it is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between the PCS-9600 series relays. IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact match in terms of data structure, and that the GOOSE addresses and name strings match exactly. The general steps required for transmission configuration are: 1. 2. 3. Configure the data. Configure the transmission dataset. Configure the GOOSE service settings.

The general steps required for reception configuration are: 1. 2. 3. Configure the data. Configure the reception dataset. Configure the GOOSE service settings.

10.4.5 ACSI Conformance


10.4.5.1 ACSI Basic Conformance Statement

PCS-9611 Feeder Relay Date: 2011-08-29

10-13

10 Communication Services Client-Server Roles B11 B12 Server Client side side (of (of Two-party Two-party Application-Association) Application-Association) SCSM: IEC61850-8-1 used SCSM: IEC61850-9-1 used SCSM: IEC61850-9-2 used SCSM: other C1 C1 Y N Client Server PCS-9600 Series

SCSMS Supported B21 B22 B23 B24 B31 B32 B41 B42 N N N N N N N N O Y N N N Y Y N N

Generic Substation Event Model (GSE)

Publisher side Subscriber side Publisher side Subscriber side

Transmission Of Sampled Value Model (SVC) O O

NOTE! C1: Shall be M if support for LOGICAL-DEVICE model has been declared O: Optional M: Mandatory Y: Supported by PCS-9600 series relays N: Currently not supported by PCS-9600 series relays 10.4.5.2 ACSI Models Conformance Statement
Services M1 M2 M3 M4 M5 M6 Reporting M7 M7-1 M7-2 M7-3 M7-4 M7-5 M7-6 M7-7 Buffered report control sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference buffer-overflow entryID O Y Y Y Y Y Y Y O Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Logical device Logical node Data Data set Substitution Setting group control Client C2 C3 C4 C5 O O Server C2 C3 C4 C5 O O PCS-9600 Series Y Y Y Y Y Y

10-14
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication M7-8 M7-9 M7-10 M8 M8-1 M8-2 M8-3 M8-4 M8-5 M8-6 M8-7 Logging M9 M9-1 M10 GSE M12 M13 M14 M15 M16 M17 GOOSE GSSE Multicast SVC Unicast SVC Time File transfer O O O O M O O O O O M O Y N N N Y Y Log Log control IntgPd O N O O N O N N N BufTm IntgPd GI Unbuffered report control sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference BufTm IntgPd N Y Y M Y Y Y Y Y N N N Y Y M Y Y Y Y Y N Y N Y Y Y Y Y Y Y Y N Y

NOTE! C2: Shall be M if support for LOGICAL-NODE model has been declared C3: Shall be M if support for DATA model has been declared C4: Shall be M if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared C5: Shall be M if support for Report, GSE, or SMV models has been declared M: Mandatory Y: Supported by PCS-9600 series relays N: Currently not supported by PCS-9600 series relays 10.4.5.3 ACSI Services Conformance Statement
Services Server S1 S2 S3 S4 ServerDirectory Associate Abort Release M M M M Y Y Y Y Application association Server/Publisher PCS-9600 Series

Logical device

PCS-9611 Feeder Relay Date: 2011-08-29

10-15

10 Communication S5 S6 S7 Data S8 S9 S10 S11 Data set S12 S13 S14 S15 S16 S17 S18 S19 S20 S21 S22 S23 Reporting Buffered report control block S24 S24-1 S24-2 S24-3 S25 S26 S27 S27-1 S27-2 S27-3 S28 S29 Logging Log control block S30 S31 10-16
Date: 2011-08-29

LogicalDeviceDirectory LogicalNodeDirectory GetAllDataValues GetDataValues SetDataValues GetDataDirectory GetDataDefinition GetDataSetValues SetDataSetValues CreateDataSet DeleteDataSet GetDataSetDirectory SetDataValues SelectActiveSG SelectEditSG SetSGValuess ConfirmEditSGValues GetSGValues GetSGCBValues

M M M M M M M M O O O M M M/O M/O M/O M/O M/O M/O

Y Y Y Y Y Y Y Y

Logical node

Y Y Y Y Y Y Y Y

Substitution Setting group control

Report data-change qchg-change data-update GetBRCBValues SetBRCBValues Report data-change qchg-change data-update GetURCBValues SetURCBValues

C6

Y Y Y Y

C6 C6 C6

Y Y Y Y Y Y

Unbuffered report control block

C6 C6

Y Y

GetLCBValues SetLCBValues

O O

PCS-9611 Feeder Relay

10 Communication Log S32 S33 S34 QueryLogByTime QueryLogAfter GetLogStatusValues O O O

Generic substation event model (GSE) GOOSE control block S35 S36 S37 S38 S39 SendGOOSEMessage GetGoReference GetGOOSEElementNumber GetGoCBValues SetGoCBValuess C8 C9 C9 O O Y Y Y

Transmission Of Sample Value Model (SVC) Multicast SVC S45 S46 S47 S48 S49 S50 Control S51 S52 S53 S54 S55 S56 S57 S58 S59 S60 Time SNTP M Y Select SelectWithValue Cancel Operate Command-Termination TimeActivated-Operate GetFile SetFile DeleteFile GetFileAttributeValues O M M M O O M/O O O M/O Y Y Y Y Y Y Y SendMSVMessage GetMSVCBValues SetMSVCBValues SendUSVMessage GetUSVCBValues SetUSVCBValues C10 O O C10 O O

Unicast SVC

File transfer

NOTE! C6: Shall declare support for at least one (BRCB or URCB) C7: Shall declare support for at least one (QueryLogByTime or QueryLogAfter) C8: Shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) C9: Shall declare support if TP association is available C10: Shall declare support for at least one (SendMSVMessage or SendUSVMessage)

PCS-9611 Feeder Relay Date: 2011-08-29

10-17

10 Communication

10.4.6 Logical Nodes


10.4.6.1 Logical Nodes Table The PCS-9600 series relays support IEC61850 logical nodes as indicated in the following table. NOTE! The actual instantiation of each logical node is respectively determined by an actual product of the PCS-9600 series relays.
Nodes L: System Logical Nodes LPHD: Physical device information LLN0: Logical node zero P: Logical Nodes For Protection Functions PDIF: Differential PDIR: Direction comparison PDIS: Distance PDOP: Directional overpower PDUP: Directional underpower PFRC: Rate of change of frequency PHAR: Harmonic restraint PHIZ: Ground detector PIOC: Instantaneous overcurrent PMRI: Motor restart inhibition PMSS: Motor starting time supervision POPF: Over power factor PPAM: Phase angle measuring PSCH: Protection scheme PSDE: Sensitive directional earth fault PTEF: Transient earth fault PTOC: Time overcurrent PTOF: Overfrequency PTOV: Overvoltage PTRC: Protection trip conditioning PTTR: Thermal overload PTUC: Undercurrent PTUV: Undervoltage PUPF: Underpower factor PTUF: Underfrequency PVOC: Voltage controlled time overcurrent PVPH: Volts per Hz PZSU: Zero speed or underspeed R: Logical Nodes For Protection Related Functions RDRE: Disturbance recorder function YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES PCS-9600 Series

10-18
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing RSYN: Synchronism-check or synchronizing C: Logical Nodes For Control CALH: Alarm handling CCGR: Cooling group control CILO: Interlocking CPOW: Point-on-wave switching CSWI: Switch controller G: Logical Nodes For Generic References GAPC: Generic automatic process control GGIO: Generic process I/O GSAL: Generic security application I: Logical Nodes For Interfacing And Archiving IARC: Archiving IHMI: Human machine interface ITCI: Telecontrol interface ITMI: Telemonitoring interface A: Logical Nodes For Automatic Control ANCR: Neutral current regulator ARCO: Reactive power control ATCC: Automatic tap changer controller AVCO: Voltage control M: Logical Nodes For Metering And Measurement MDIF: Differential measurements MHAI: Harmonics or interharmonics MHAN: Non phase related harmonics or interharmonic MMTR: Metering MMXN: Non phase related measurement MMXU: Measurement MSQI: Sequence and imbalance MSTA: Metering statistics S: Logical Nodes For Sensors And Monitoring SARC: Monitoring and diagnostics for arcs SIMG: Insulation medium supervision (gas) SIML: Insulation medium supervision (liquid) SPDC: Monitoring and diagnostics for partial discharges YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES

PCS-9611 Feeder Relay Date: 2011-08-29

10-19

10 Communication T: Logical Nodes For Switchgear TCTR: Current transformer TVTR: Voltage transformer Y: Logical Nodes For Power Transformers YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer Z: Logical Nodes For Further Power System Equipment ZAXN: Auxiliary network ZBAT: Battery ZBSH: Bushing ZCAB: Power cable ZCAP: Capacitor bank ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component YES YES YES

10.5 DNP3.0 Interface


10.5.1 Overview
The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0 implementation. This manual only specifies which objects, variations and qualifiers are supported in this relay, and also specifies what data is available from this relay via DNP3.0. The relay operates as a DNP3.0 slave and supports subset level 2 of the protocol, plus some of the features from level 3. The DNP3.0 communication uses the Ethernet ports at the rear side of this relay. The Ethernet ports are optional: electrical or optical.

10.5.2 Link Layer Functions


Please see the DNP3.0 protocol standard for the details about the linker layer functions.

10.5.3 Transport Functions


Please see the DNP3.0 protocol standard for the details about the transport functions.

10-20
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication

10.5.4 Application Layer Functions


10.5.4.1 Time Synchronization 1. Time delay measurement
Master/Slave Master Slave Function Code 0x17 0x81 Object 0x34 Variation 0x02 Qualifier 0x07

2.

Read time of device


Master/Slave Master Slave Function Code 0x01 0x81 Object 0x34 0x32 Variation 0x00, 0x01 0x01 Qualifier 0x07 0x07

3.

Write time of device


Master/Slave Master Slave Function Code 0x02 0x81 Object 0x32 Variation 0x01 Qualifier 0x00,0x01,0x07,0x08

10.5.4.2 Supported Writing Functions 1. Write time of device See Section 10.5.4.1 for the details. 2. Reset the CU (Reset IIN bit7)
Master/Slave Master Slave Function Code 0x02 0x81 Object 0x50 Variation 0x01 Qualifier 0x00, 0x01

10.5.4.3 Supported Reading Functions 1. Supported qualifiers


Master Qualifier Slave Qualifier 0x00 0x00 0x01 0x01 0x06 0x01 0x07 0x07 0x08 0x08

2.

Supported objects and variations Object 1, Binary inputs


Master Variation Slave Variation 0x00 0x02 0x01 0x01 0x02 0x02

The protection operation signals, alarm signals and binary input state change signals are transported respectively according to the variation sequence in above table. Object 2, SOE

PCS-9611 Feeder Relay Date: 2011-08-29

10-21

10 Communication Master Variation Slave Variation 0x00 0x02 0x01 0x01 0x02 0x02 0x03 0x03

If the master qualifier is 0x07, the slave responsive qualifier is 0x27; and if the master qualifier is 0x01, 0x06 or 0x08, the slave responsive qualifier is 0x28. Object 30, Analog inputs
Master Variation Slave Variation 0x00 0x01 0x01 0x01 0x02 0x02 0x03 0x03 0x04 0x04

The measurement values are transported firstly, and then the protection measurement values are transported. Object 40, Analog outputs
Master Variation Slave Variation 0x00 0x01 0x01 0x01 0x02 0x02

The protection settings are transported in this object. Object 50, Time Synchronization See Section 10.5.4.1 for the details. 3. Class 0 data request The master adopts the Object 60 for the Class 0 data request and the variation is 0x01. The slave responds with the above mentioned Object 1, Object 30 and Object 40 (see Supported objects and variations in Section 10.5.4.3). 4. Class 1 data request The master adopts the Object 60 for the Class 1 data request and the variation is 0x02. The slave responds with the above mentioned Object 2 (see Supported objects and variations in Section 10.5.4.3). 5. Multiple object request The master adopts the Object 60 for the multiple object request and the variation is 0x01, 0x02, 0x03 and 0x04. The slave responds with the above mentioned Object 1, Object 2, Object 30 and Object 40 (see Supported objects and variations in Section 10.5.4.3). 10.5.4.4 Remote Control Functions The function code 0x03 and 0x04 are supported in this relay. The function code 0x03 is for the remote control with selection; and the function code 0x04 is for the remote control with execution. The selection operation must be executed before the execution operation, and the single point control object can be supported to this relay.

10-22
Date: 2011-08-29

PCS-9611 Feeder Relay

10 Communication Master Qualifier Slave Qualifier 0x17 0x17 0x27 0x27 0x18 0x18 0x28 0x28

The Object 12 is for the remote control functions.


Master Variation Slave Variation 0x01 0x01 Control Code 0x01: closing 0x10: tripping

PCS-9611 Feeder Relay Date: 2011-08-29

10-23

10 Communication

10-24
Date: 2011-08-29

PCS-9611 Feeder Relay

11 Installation

11 Installation
Table of Contents
11.1 General ..........................................................................................................11-1 11.2 Safety Instructions .......................................................................................11-1 11.3 Checking the Shipment................................................................................11-2 11.4 Material and Tools Required ........................................................................11-2 11.5 Device Location and Ambient Conditions ..................................................11-2 11.6 Mechanical Installation ................................................................................11-3 11.7 Electrical Installation and Wiring ................................................................11-4
11.7.1 Grounding Guidelines .....................................................................................................11-4 11.7.2 Cubicle Grounding ..........................................................................................................11-4 11.7.3 Ground Connection on the Device ..................................................................................11-5 11.7.4 Grounding Strips and their Installation ............................................................................11-6 11.7.5 Guidelines for Wiring.......................................................................................................11-6 11.7.6 Wiring for Electrical Cables .............................................................................................11-7

11.8 Typical Wiring of the Relay ..........................................................................11-7

List of Figures
Figure 11.6-1 Dimensions of this relay and the cut-out in the cubicle (unit: mm) .............11-3 Figure 11.6-2 Demonstration of plugging a board into its corresponding slot ..................11-4 Figure 11.7-1 Cubicle grounding system ...............................................................................11-5 Figure 11.7-2 Ground terminal of this relay ...........................................................................11-6 Figure 11.7-3 Ground strip and termination ..........................................................................11-6 Figure 11.7-4 Glancing demo about the wiring for electrical cables ...................................11-7 Figure 11.8-1 Control panel (button, switch and link) of the cubicle...................................11-7 Figure 11.8-2 Typical wiring diagram of this relay ................................................................11-8

PCS-9611 Feeder Relay Date: 2011-08-29

11-a

11 Installation

11-b
Date: 2011-08-29

PCS-9611 Feeder Relay

11 Installation

11.1 General
The equipment must be shipped, stored and installed with the greatest care. Choose the place of installation such that the communication interface and the controls on the front of the device are easily accessible. Air must circulate freely around the equipment. Observe all the requirements regarding place of installation and ambient conditions given in this instruction manual. Take care that the external wiring is properly brought into the equipment and terminated correctly and pay special attention to grounding. Strictly observe the corresponding guidelines contained in this section.

11.2 Safety Instructions


Modules and units may only be replaced by correspondingly trained personnel. Always observe the basic precautions to avoid damage due to electrostatic discharge when handling the equipment. In certain cases, the settings have to be configured according to the demands of the engineering configuration after replacement. It is therefore assumed that the personnel who replace modules and units are familiar with the use of the operator program on the service PC. DANGER! Only insert or withdraw the power supply module while the power supply is switched off. To this end, disconnect the power supply cable that connects with the power supply module. WARNING! Only insert or withdraw other modules while the power supply is switched off.

WARNING! The modules may only be inserted in the slots designated in Section 6.2. Components can be damaged or destroyed by inserting boards in the wrong slots. DANGER! Improper handling of the equipment can cause damage or an incorrect response of the equipment itself or the primary plant. WARNING! Industry packs and ribbon cables may only be replaced or the positions of jumpers be changed on a workbench appropriately designed for working on electronic equipment. The modules, bus backplanes are sensitive to electrostatic discharge when not in the unit's housing. The basic precautions to guard against electrostatic discharge are as follows:

PCS-9611 Feeder Relay Date: 2011-08-29

11-1

11 Installation

Should boards have to be removed from this relay installed in a grounded cubicle in an HV switchgear installation, please discharge yourself by touching station ground (the cubicle) beforehand. Only hold electronic boards at the edges, taking care not to touch the components. Only works on boards that have been removed from the cubicle on a workbench designed for electronic equipment and wear a grounded wristband. Do not wear a grounded wristband, however, while inserting or withdrawing units. Always store and ship the electronic boards in their original packing. Place electronic parts in electrostatic screened packing materials.

11.3 Checking the Shipment


Check that the consignment is complete immediately upon receipt. Notify the nearest NR Company or agent, should departures from the delivery note, the shipping papers or the order be found. Visually inspect all the material when unpacking it. When there is evidence of transport damage, lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or agent. If the equipment is not going to be installed immediately, store all the parts in their original packing in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the permissible storage temperature range in dry air are listed in Section 2.1.3.

11.4 Material and Tools Required


The necessary mounting kits will be provided, including screws, pincers and assembly instructions. A suitable drill and spanners are required to secure the cubicles to the floor using the plugs provided (if this relay is mounted in cubicles).

11.5 Device Location and Ambient Conditions


The place of installation should permit easy access especially to front of the device, i.e. to the human machine interface of the equipment. There should also be free access at the rear of the equipment for additions and replacement of electronic boards. Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient conditions, such as: 1.
11-2
Date: 2011-08-29

The location should not be exposed to excessive air pollution (dust, aggressive substances).

PCS-9611 Feeder Relay

11 Installation

2.

Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of high amplitude and short rise time and strong induced magnetic fields should be avoided as far as possible. Air must not be allowed to circulate freely around the equipment.

3.

The equipment can in principle be mounted in any attitude, but it is normally mounted vertically (visibility of markings). WARNING! Excessively high temperature can appreciably reduce the operating life of this relay.

11.6 Mechanical Installation


This relay is made of a single layer 4U height 9.5" chassis with 8 connectors on its rear panel (See Figure 6.1-3). The following figure shows the dimensions of this relay for reference in mounting.
264.24 246.74 224.80 197.50

1 HEALTHY 2 ALARM 3 4 5 6 7 8 9 10

11 12 13 14 15 16 17 18 19 20

FEEDER RELAY

ENT

246.740.10 226.00 4-7.5

Cut-out in the cubicle

Figure 11.6-1 Dimensions of this relay and the cut-out in the cubicle (unit: mm)

NOTE! It is necessary to leave enough space top and bottom of the cut-out in the cubicle for heat emission of this relay. As mentioned in Chapter 6, up to eight modules are installed in the enclosure of this relay, and
PCS-9611 Feeder Relay Date: 2011-08-29

11-3

11 Installation

these modules must be plugged into the proper slots of this relay respectively. The safety instructions must be abided by when installing the boards, please see Section 11.2 for the details. Figure 11.6-2 shows the installation way of a module being plugged into a corresponding slot.

Figure 11.6-2 Demonstration of plugging a board into its corresponding slot

In the case of equipment supplied in cubicles, place the cubicles on the foundations that have been prepared. Take care while doing so not to jam or otherwise damage any of the cables that have already been installed. Secure the cubicles to the foundations.

11.7 Electrical Installation and Wiring


11.7.1 Grounding Guidelines
Switching operations in HV installations generate transient over voltages on control signal cables. There is also a background of electromagnetic RF fields in electrical installations that can induce spurious currents in the devices themselves or the leads connected to them. All these influences can influence the operation of electronic apparatus. On the other hand, electronic apparatus can transmit interference that can disrupt the operation of other apparatus. In order to minimize these influences as far as possible, certain standards have to be observed with respect to grounding, wiring and screening. NOTE! All these precautions can only be effective if the station ground is of good quality.

11.7.2 Cubicle Grounding


The cubicle must be designed and fitted out such that the impedance for RF interference of the ground path from the electronic device to the cubicle ground terminal is as low as possible. Metal accessories such as side plates, blanking plates etc., must be effectively connected
11-4
Date: 2011-08-29 PCS-9611 Feeder Relay

11 Installation

surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF interference. The contact surfaces must not only conduct well, they must also be non-corroding. NOTE! If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it forming a resonant circuit at certain frequencies that would amplify the transmission of interference by the devices installed and also reduce their immunity to induced interference. Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be effectively grounded to the frame by three braided copper strips (see Figure 11.7-1). The metal parts of the cubicle housing and the ground rail are interconnected electrically conducting and corrosion proof. The contact surfaces shall be as large as possible. NOTE! For metallic connections please observe the voltage difference of both materials according to the electrochemical code. The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip (braided copper).

Figure 11.7-1 Cubicle grounding system

11.7.3 Ground Connection on the Device


There is a ground terminal on the rear panel (see Figure 11.7-2), and the ground braided copper strip can be connected with it. Take care that the grounding strip is always as short as possible. The main thing is that the device is only grounded at one point. Grounding loops from unit to unit are not allowed. There are some ground terminals on some connectors of this relay, and the sign is GND. All the ground terminals are connected in the cabinet of this relay. So, the ground terminal on the rear panel (see Figure 11.7-2) is the only ground terminal of this device.
PCS-9611 Feeder Relay Date: 2011-08-29

11-5

11 Installation

Figure 11.7-2 Ground terminal of this relay

11.7.4 Grounding Strips and their Installation


High frequency currents are produced by interference in the ground connections and because of skin effect at these frequencies, only the surface region of the grounding strips is of consequence. The grounding strips must therefore be of (preferably tinned) braided copper and not round copper conductors, as the cross-section of round copper would have to be too large. Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting them firmly to the items to be connected. The surfaces to which the grounding strips are bolted must be electrically conducting and non-corroding. The following figure shows the ground strip and termination.

Figure 11.7-3 Ground strip and termination

11.7.5 Guidelines for Wiring


There are several types of cables that are used in the connection of this relay: braided copper cable, serial communication cable etc. Recommendation of each cable: Grounding: braided copper cable, 2.5mm2 ~ 6.0mm2 Power supply, binary inputs & outputs: brained copper cable, 1.5mm2 ~ 2.5mm2 AC voltage inputs: brained copper cable, 1.5mm2 ~ 2.5mm2 AC current inputs: brained copper cable, 2.5mm2 ~ 6.0mm2 Serial communication: 4-core shielded braided cable
11-6
Date: 2011-08-29 PCS-9611 Feeder Relay

11 Installation

Ethernet communication: 4-pair screened twisted category 5E cable

11.7.6 Wiring for Electrical Cables


A female connector is used for connecting the wires with it, and then a female connector plugs into a corresponding male connector that is in the front of one board. See Chapter 6 for further details about the pin defines of these connectors. The following figure shows the glancing demo about the wiring for the electrical cables.

01

02

Tighten
03 04

01

05

06

07

08

Figure 11.7-4 Glancing demo about the wiring for electrical cables

DANGER! Never allow the current transformer (CT) secondary circuit connected to this equipment to be opened while the primary system is live. Opening the CT circuit will produce a dangerously high voltage.

11.8 Typical Wiring of the Relay


Relevant information and sections about the modules and the connectors of the relay are described in Chapter 6. Referring the relevant sections can help to wire correctly and effectively. The following figure shows the metallic links, control switch and local operation buttons (manual closing button and manual tripping button) on the control panel.

Figure 11.8-1 Control panel (button, switch and link) of the cubicle

The typical wiring of this relay is shown as below, all the configurable binary inputs and binary
PCS-9611 Feeder Relay Date: 2011-08-29

11-7

11 Installation

output adopt the default definition in the factory.


A B C

05 Ux

06 Uxn

01 Ua

02 Ub

03 Uc

04 Un

07 U0

08 U0n

09 10 11 I02 I02n Ia

12 Ian

13 Ib

14 Ibn

15 Ic

16 Icn

17 18 19 20 21 22 23 24 25 26 I01 I01n I0s I0sn Iam Iamn Ibm Ibmn Icm Icmn

Voltage Inputs

For Protection Current Inputs

For Metering

NR4412
Ethernet 1 Ground at Remote device 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 NET1 BI_01+ BI_01BI_02+ BI_02BI_03 BI_04 BI_05 BI_06 BI_07 BI_08 BI_09 BI_10 BI_11 BI_12 BI_13 BI_14 BI_15 BI_16 BI_17 BI_18 BI_19 BI_Opto01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22

Ethernet 2

NET2

485-1A 485-1B SGND FGND 485-2A 485-2B SGND FGND SYN+ SYNSGND FGND RTS TXD SGND SIG_COM BO_Alm_Fail BO_Alm_Abnor BO_01 BO_02

NET3

NET4

NET5

NET6

RX

GPS

TX1

BO_01 BO_02

RX1 BO_03 TX2 BO_04 BO_05 BO_06

BO_03 BO_04 BO_05 BO_06 RX3 BO_07 BO_09 BO_08 PSW+ PSWGND TX4 BO_10 BO_08 RX2

TX3

BO_07

Power Supply

RX4

BO_11

Figure 11.8-2 Typical wiring diagram of this relay

11-8
Date: 2011-08-29

PCS-9611 Feeder Relay

12 Commissioning

12 Commissioning
Table of Contents
12.1 General ..........................................................................................................12-1 12.2 Safety Instructions .......................................................................................12-1 12.3 Commission Tools........................................................................................12-2 12.4 Setting Familiarization .................................................................................12-2 12.5 Product Checks ............................................................................................12-3
12.5.1 With the Relay De-energized ......................................................................................... 12-4 12.5.2 With the Relay Energized .............................................................................................. 12-5 12.5.3 Protective Function Test................................................................................................. 12-8 12.5.4 On-load Checks ........................................................................................................... 12-17

PCS-9611 Feeder Relay Date: 2011-08-29

12-a

12 Commissioning

12-b
Date: 2011-08-29

PCS-9611 Feeder Relay

12 Commissioning

12.1 General
This relay is fully numerical in their design, implementing all protection and non-protection functions in software. The relay employs a high degree of self-checking and in the unlikely event of a failure, will give an alarm. As a result of this, the commissioning test does not need to be as extensive as with non-numeric electronic or electro-mechanical relays. To commission numerical relays, it is only necessary to verify that the hardware is functioning correctly and the application-specific software settings have been applied to the relay. Blank commissioning test and setting records are provided at the end of this manual for completion as required. Before carrying out any work on the equipment, the user should be familiar with the contents of the safety and technical data sections and the ratings on the equipments rating label.

12.2 Safety Instructions


WARNING! Hazardous voltages are present in this electrical equipment during operation. Non-observance of the safety rules can result in severe personal injury or property damage. WARNING! Only the qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations. Particular attention must be drawn to the following: The earthing screw of the device must be connected solidly to the protective earth conductor before any other electrical connection is made. Hazardous voltages can be present on all circuits and components connected to the supply voltage or to the measuring and test quantities. Hazardous voltages can be present in the device even after disconnection of the supply voltage (storage capacitors!) The limit values stated in the technical data (Chapter 2) must not be exceeded at all, not even during testing and commissioning. When testing the device with secondary test equipment, make sure that no other measurement quantities are connected. Take also into consideration that the trip circuits and maybe also close commands to the circuit breakers and other primary switches are disconnected from the device unless expressly stated.

PCS-9611 Feeder Relay Date: 2011-08-29

12-1

12 Commissioning

DANGER! Current transformer secondary circuits must have been short-circuited before the current leads to the device are disconnected. WARNING! Primary test may only be carried out by qualified personnel, who are familiar with the commissioning of protection system, the operation of the plant and safety rules and regulations (switching, earthing, etc.).

12.3 Commission Tools


Minimum equipment required: Multifunctional dynamic current and voltage injection test set with interval timer. Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and 0~250V respectively. Continuity tester (if not included in the multimeter). Phase angle meter. Phase rotation meter. NOTE! Modern test set may contain many of the above features in one unit. Optional equipment: An electronic or brushless insulation tester with a DC output not exceeding 500V (for insulation resistance test when required). A portable PC, with appropriate software (this enables the rear communications port to be tested, if this is to be used, and will also save considerable time during commissioning). EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested). PCS-9600 serials relay dedicated protection tester HELP-2000A.

12.4 Setting Familiarization


When commissioning this device for the first time, sufficient time should be allowed to become familiar with the method by which the settings are applied. A detailed description of the menu structure of this relay is contained in Chapter 8. With the front cover in place all keys are accessible. All menu cells can be read. The LED indicators and alarms can be reset. Protection or configuration settings can be changed, or fault and event records cleared. However, menu cells will require the appropriate password to be entered before changes can be made.

12-2
Date: 2011-08-29

PCS-9611 Feeder Relay

12 Commissioning

Alternatively, if a portable PC is available together with suitable setting software (such as PCS-PC or PCS-9700 SAS software), the menu can be viewed one page at a time to display a full column of data and text. This PC software also allows settings to be entered more easily, saved to a file on disk for future reference or printed to produce a setting record. Refer to the PC software user manual for details. If the software is being used for the first time, allow sufficient time to become familiar with its operation.

12.5 Product Checks


These product checks cover all aspects of the relay which should be checked to ensure that it has not been physically damaged prior to commissioning, is functioning correctly and all input quantity measurements are within the stated tolerances. If the application-specific settings have been applied to the relay prior to commissioning, it is advisable to make a copy of the settings so as to allow them restoration later. This could be done by extracting the settings from the relay itself via printer or manually creating a setting record. This relay is fully numerical and the hardware is continuously monitored. Commissioning tests can be kept to a minimum and need only include hardware tests and conjunctive tests. The function tests are carried out according to users correlative regulations. The following tests are necessary to ensure the normal operation of the equipment before it is first put into service. Hardware tests These tests are performed for the following hardware to ensure that there is no hardware defect. Defects of hardware circuits other than the following can be detected by self-monitoring when the power supply is energized. User interfaces test Binary input circuits and output circuits test AC input circuits test Function tests These tests are performed for the following functions that are fully software-based. Tests of the protection schemes and fault locator require a dynamic test set. Measuring elements test Timers test Metering and recording test Conjunctive tests The tests are performed after the relay is connected with the primary equipment and other external equipment.

PCS-9611 Feeder Relay Date: 2011-08-29

12-3

12 Commissioning

On load test. Phase sequence check and polarity check.

12.5.1 With the Relay De-energized


12.5.1.1 Visual Inspection After unpacking the product, check for any damage to the relay case. If there is any damage, the internal module might also have been affected, contact the vendor. The following listed items are necessary. Protection panel Carefully examine the protection panel, protection equipment inside and other parts inside to see that no physical damage has occurred since installation. The rated information of other auxiliary protections should be checked to ensure it is correct for the particular installation. Panel wiring Check the conducting wire which is used in the panel to assure that their cross section meeting the requirement. Carefully examine the wiring to see that they are no connection failure exists. Label Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to make sure that their labels meet the requirements of this project. Equipment plug-in modules Check each plug-in module of the equipment on the panel to make sure that they are well installed into the equipment without any screw loosened. Earthing cable Check whether the earthing cable from the panel terminal block is safely screwed to the panel steel sheet. Switch, keypad, isolator binary inputs and push button Check whether all the switches, equipment keypad, isolator binary inputs and push buttons work normally and smoothly. 12.5.1.2 Insulation Test (if required) Insulation resistance tests are only necessary during commissioning if it is required for them to be done and they have not been performed during installation. Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:

12-4
Date: 2011-08-29

PCS-9611 Feeder Relay

12 Commissioning

Voltage transformer circuits Current transformer circuits DC power supply Optic-isolated binary inputs Binary output contacts Electrical communication ports The insulation resistance should be greater than 100M at 500V. Test method: To unplug all the terminals sockets of this relay, and do the Insulation resistance test for each circuit above with an electronic or brushless insulation tester. On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the protection. 12.5.1.3 External Wiring Check that the external wiring is correct to the relevant relay diagram and scheme diagram. Ensure as far as practical that phasing/phase rotation appears to be as expected. Check the wiring against the schematic diagram for the installation to ensure compliance with the customers normal practice. 12.5.1.4 Auxiliary Power Supply The relay only can be operated under the auxiliary power supply depending on the relays nominal power supply rating. The incoming voltage must be within the operating range specified in Section 2.1.1.1, before energizing the relay, measure the auxiliary supply to ensure it within the operating range. Other requirements to the auxiliary power supply are specified in Section 2.1.1.1. See this section for further details about the parameters of the power supply. WARNING! Energize this relay only when the power supply is within the specified operating ranges in Section 2.1.1.1.

12.5.2 With the Relay Energized


The following groups of checks verify that the relay hardware and software is functioning correctly and should be carried out with the auxiliary supply applied to the relay. The current and voltage transformer connections must remain isolated from the relay for these checks. The trip circuit should also remain isolated to prevent accidental operation of the associated circuit breaker.

PCS-9611 Feeder Relay Date: 2011-08-29

12-5

12 Commissioning

12.5.2.1 Front Panel LCD Display The liquid crystal display (LCD) is designed to operate in a wide range of substation ambient temperatures. For this purpose, this relay has an automatic LCD contrast adjusting feature, which is capable to adjust LCD contrast automatically according to the ambient temperature. Connect the relay to DC power supply correctly and turn the relay on. Check program version and forming time displayed in command menu to ensure that are corresponding to what ordered. 12.5.2.2 Date and Time If the time and date is not being maintained by substation automation system, the date and time should be set manually. Set the date and time to the correct local time and date using menu item Clock. In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will be maintained. Therefore when the auxiliary supply is restored the time and date will be correct and not need to set again. To test this, remove the auxiliary supply from the relay for approximately 30s. After being re-energized, the time and date should be correct. 12.5.2.3 Light Emitting Diodes (LEDs) On power up, the green LED HEALTHY should have illuminated and stayed on indicating that the relay is healthy. The relay has latched signal relays which remember the state of the trip, auto-reclose when the relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing required for that that LED because it is known to be operational. It is likely that alarms related to voltage transformer supervision will not reset at this stage. 12.5.2.4 Test the HEALTHY and ALARM LEDs Apply the rated power supply and check that the HEALTHY LED is lighting in green. We need to emphasize that the HEALTHY LED is always lighting in operation course except that this device finds serious errors in it. Produce one of the abnormal conditions listed in Chapter 4, the ALARM LED will light in yellow. When abnormal condition reset, the ALARM LED extinguishes. 12.5.2.5 Test the Other LEDs Test the other LEDs according to the configuration of the LEDs (through the PCS-PC configuration tool auxiliary software). If the conditions which can turn on the selected LED are satisfied, the selected LED will be on.

12-6
Date: 2011-08-29

PCS-9611 Feeder Relay

12 Commissioning

12.5.2.6 Test the AC Current Inputs This test verifies that the accuracy of current measurement is within the acceptable tolerances. Apply current equal to the current transformer secondary winding rating to each current transformer input of the corresponding rating in turn, see the following table or external connection diagram for appropriate terminal numbers, checking its magnitude using a multimeter/test set readout. The corresponding reading can then be checked in the relays menu. The current measurement accuracy of the relay is 2.5%. However an additional allowance must be made for the accuracy of the test equipment being used. Current channel linearity and precision checkout
Item Ia Ib Ic I01 I02 I0s Practical Input Measurement (on LCD) Error

12.5.2.7 Test the AC Voltage Inputs This test verifies that the accuracy of voltage measurement is within the acceptable tolerances. Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a multimeter/test set readout. The corresponding reading can then be checked in the relays menu. The voltage measurement accuracy of the relay is 0.5%. However an additional allowance must be made for the accuracy of the test equipment being used. Voltage channel linearity and precision checkout
Item Ua Ub Uc U0 Ux Practical Input Measurement (on LCD) Error

12.5.2.8 Test the Binary Inputs This test checks that all the binary inputs on the relay are functioning correctly. The binary inputs should be energized one at a time, see external connection diagrams for terminal numbers. Ensure that the voltage applied on the binary input must be within the operating range. The status of each binary input can be viewed using the submenu Contact Inputs and Prot Inputs.
PCS-9611 Feeder Relay Date: 2011-08-29

12-7

12 Commissioning

Binary inputs testing checkout


BI Name State without energized State with energized Correct?

12.5.3 Protective Function Test


The setting checks ensure that the entire application-specific relay, for the particular installation, has been correctly applied to the relay. NOTE! The trip circuit should remain isolated during these checks to prevent accidental operation of the associated circuit breaker. 12.5.3.1 Demonstrate correct protection operation The above tests have already demonstrated that the protection is within calibration, thus the purpose of these tests is as follows: To conclude that the primary function of the protection can trip according to the correct application settings. To verify correct setting of all related protective elements. 12.5.3.2 Overcurrent Protection Check This check, performed the stage 1 overcurrent protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings.

12-8
Date: 2011-08-29

PCS-9611 Feeder Relay

12 Commissioning

1.

Enable the stage 1 overcurrent protection with VCE and directional element control. Set the logic setting [50/51P1.En] as 1 in the submenu OC Settings. Set the logic setting [50/51P1.En_VCE] as 1 in the submenu OC Settings. Set the setting [50/51P1.Opt_Dir] as 1 in the submenu OC Settings. Set the setting [50/51P1.OutMap] as 0x0001 in the submenu OC Settings. Set other logic settings as 0 in the submenu OC Settings.

2. 3. 4.

De-energize all the binary inputs of this relay. Simulate a normal condition with normal protection voltages and currents. Simulate a single-phase fault or multi-phase fault, the current of the fault phase is 1.05 [50/51P1.I_Set], and the protection voltages satisfy the VCE condition (see Section 3.3.3) and forward directional control condition (see Section 3.3.4). After the period of [50/51P1.t_Op], the stage 1 overcurrent protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD.

5.

6.

After the fault is disappeared, this relay will restore the stage 1 overcurrent protection automatically. Restore the TRIP indicator and the LCD manually.

12.5.3.3 IDMT Overcurrent Protection Check This check, performed the IDMT overcurrent protection function with very inverse curve in No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the IDMT overcurrent protection. Set the logic setting [50/51P4.En] as 1 in the submenu OC Settings. Set the setting [50/51P4.Opt_Curve] as 2 in the submenu OC Settings. Set the setting [50/51P4.OutMap] as 0x0001 in the submenu OC Settings. Set other logic settings as 0 in the submenu OC Settings. 2. 3. 4. De-energize all the binary inputs of this relay. Simulate a normal condition with normal protection voltages and currents. Simulate a single-phase fault or multi-phase fault, and the current of the fault phase is 2 [50/51P4.I_Set]. After the period of 13.5 [50/51P4.TMS] [50/51P4.t_Op], the IDMT overcurrent protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the fault is disappeared, this relay will restore the IDMT protection automatically. Restore the TRIP indicator and the LCD manually.

5.

PCS-9611 Feeder Relay Date: 2011-08-29

12-9

12 Commissioning

NOTE! The IDMT overcurrent protection with other characteristic inverse curves can be checked through the same method. Note to set the relevant characteristic and logic settings correctly. 12.5.3.4 Zero Sequence Overcurrent Protection Check This check, performed the No.1 stage 1 zero sequence overcurrent protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the No.1 stage 1 zero sequence overcurrent protection. Set the logic setting [50/51G1.En] as 1 in the submenu EF1 Settings. Set the setting [50/51G1.En.OutMap] as 0x0001 in the submenu EF1 Settings. Set other logic settings as 0 in the submenu EF1 Settings. Set the setting [Opt_3I0] as 0 in the submenu System Settings. 2. 3. De-energize all the binary inputs of this relay. Simulate a normal condition, the external input current of the zero sequence CT is less than 0.95 [50/51G1.3I0_Set]. Simulate a single-phase earth fault, the external input current of the zero sequence CT is greater than 1.05 [50/51G1.3I0_Set]. After the period of [50/51G1.t_Op], the No.1 stage 1 zero sequence overcurrent protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the fault is disappeared, this relay will restore the No.1 stage 1 zero sequence overcurrent protection automatically. Restore the TRIP indicator and the LCD manually. NOTE! Another way for testing the zero sequence overcurrent protection is using the self-calculated zero sequence current. 12.5.3.5 Sensitive Earth Fault Protection Check This check, performed the stage 1 sensitive earth fault protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the stage 1 sensitive earth fault protection. Set the logic setting [50/51SEF1.En] as 1 in the submenu SEF Settings. Set the setting [50/51SEF1.En.OutMap] as 0x0001 in the submenu SEF Settings. Set other logic settings as 0 in the submenu SEF Settings. 2. 3. De-energize all the binary inputs of this relay. Simulate a normal condition, the external input current of the sensitive zero sequence CT is
PCS-9611 Feeder Relay Date: 2011-08-29

4.

5.

12-10

12 Commissioning

less than 0.95 [50/51SEF1.3I0_Set]. 4. Simulate a single-phase earth fault, the external input current of the zero sequence CT is greater than 1.05 [50/51SEF1.3I0_Set]. After the period of [50/51SEF1.t_Op], the stage 1 sensitive earth fault protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the fault is disappeared, this relay will restore the stage 1 sensitive earth fault protection automatically. Restore the TRIP indicator and the LCD manually. 12.5.3.6 Negative Sequence Overcurrent Protection Check This check, performed the stage 1 negative sequence overcurrent protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the stage 1 negative sequence overcurrent protection. Set the logic setting [50/51Q1.En] as 1 in the submenu NegOC Settings. Set the setting [50/51Q1.OutMap] as 0x0001 in the submenu NegOC Settings. Set other logic settings as 0 in the submenu NegOC Settings. 2. 3. De-energize all the binary inputs of this relay. Simulate a normal condition; the negative sequence current is less than 0.95 [50/51Q1.I2_Set]. Simulate an unbalance fault; the negative sequence current is greater than 1.05 [50/51Q1.I2_Set]. After the period of [50/51Q1.t_Op], the stage 1 negative sequence overcurrent protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the fault is disappeared, this relay will restore the stage 1 negative sequence overcurrent protection automatically. Restore the TRIP indicator and the LCD manually. 12.5.3.7 Thermal Overload Protection Check This check, performed the thermal overload protection function in No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the definite time overload protection. Set the logic setting [49.En_Trp] as 1 in the submenu ThOvLd settings. Set the setting [49.OutMap] as 0x0001 in the submenu ThOvLd settings. Set other logic settings as 0 in the submenu ThOvLd settings. 2. De-energize all the binary inputs of this relay.

5.

4.

5.

PCS-9611 Feeder Relay Date: 2011-08-29

12-11

12 Commissioning

3.

Simulate a normal condition with normal protection voltages and currents, and the load current is 0.5 [49.K_Trp] [49.Ib_Set]. Simulate a thermal overload condition; the load current is 2 [49.K_Trp] [49.Ib_Set]. After the period of about 0.223 [49.Tau], the definite time overload protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD.

4. 5.

6.

After the fault is disappeared, this relay will restore the thermal overload protection automatically. Restore the TRIP indicator and the LCD manually.

12.5.3.8 Under-frequency Protection Check This check, performed the stage 1 under-frequency protection function in No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the stage 1 under-frequency protection. Set the logic setting [81U1.En] as 1 in the submenu FreqProt Settings. Set the setting [81U1.OutMap] as 0x0001 in the submenu FreqProt Settings. Set other logic settings as 0 in the submenu FreqProt Settings. 2. 3. 4. De-energize all the binary inputs of this relay. Simulate a normal condition with normal protection voltages. Simulate a system frequency decline condition. The input protection voltage is greater than the setting [81.Upp_VCE]. After the period of [81U1.t_Op], the stage 1 under-frequency protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the fault is disappeared, this relay will restore the stage 1 under-frequency protection automatically. Restore the TRIP indicator and the LCD manually. 12.5.3.9 Undervoltage Protection Check This check, performed the stage 1 undervoltage protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the stage 1 undervoltage protection. Set the logic setting [27P1.En] as 1 in the submenu Voltage Settings. Set the setting [27P.Opt_1P/3P] as 1 in the submenu Voltage Settings. Set the setting [27P.Opt_Up/Upp] as 1 in the submenu Voltage Settings. Set the setting [27P.OutMap] as 0x0001 in the submenu Voltage Settings. Set other logic settings as 0 in the submenu Voltage Settings.

5.

12-12
Date: 2011-08-29

PCS-9611 Feeder Relay

12 Commissioning

2. 3. 4.

De-energize all the binary inputs of this relay. Simulate a normal condition with normal protection voltages and the circuit breaker is closed. Simulate an undervoltage condition; anyone of the three phase-to-phase voltages is less than 0.95 [27P1.U_Set]. After the period of [27P1.t_Op], the stage 1 undervoltage protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD.

5.

6.

After the fault is disappeared, this relay will restore the stage 1 undervoltage protection automatically. Restore the TRIP indicator and the LCD manually.

12.5.3.10 Overvoltage Protection Check This check, performed the stage 1 overvoltage protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the stage 1 overvoltage protection. Set the logic setting [59P1.En] as 1 in the submenu Voltage Settings. Set the setting [59P.Opt_1P/3P] as 1 in the submenu Voltage Settings. Set the setting [59P.Opt_Up/Upp] as 1 in the submenu Voltage Settings. Set the setting [59P.OutMap] as 0x0001 in the submenu Voltage Settings. Set other logic settings as 0 in the submenu Voltage Settings. 2. 3. 4. De-energize all the binary inputs of this relay. Simulate a normal condition with normal protection voltages. Simulate an overvoltage condition; anyone of the three phase-to-phase voltages is greater than 1.05 [59P1.U_Set]. After the period of [59P1.t_Op], the stage 1 overvoltage protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the fault is disappeared, this relay will restore the stage 1 overvoltage protection automatically. Restore the TRIP indicator and the LCD manually. 12.5.3.11 Negative Sequence Overvoltage Protection Check This check, performed the negative sequence overvoltage protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the negative sequence overvoltage protection. Set the logic setting [59Q.En] as 1 in the submenu NegOV Settings. Set the setting [59Q.OutMap] as 0x0001 in the submenu NegOV Settings.

5.

PCS-9611 Feeder Relay Date: 2011-08-29

12-13

12 Commissioning

Set other logic settings as 0 in the submenu NegOV Settings. 2. 3. 4. De-energize all the binary inputs of this relay. Simulate a normal condition; the negative sequence voltage is less than 0.95 [59Q.U2_Set]. Simulate an unbalance fault; the negative sequence voltage is greater than 1.05 [59Q.U2_Set]. After the period of [59Q.t_Op], the negative sequence overvoltage protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the fault is disappeared, this relay will restore the negative sequence overvoltage protection automatically. Restore the TRIP indicator and the LCD manually. 12.5.3.12 Broken Conductor Protection Check This check, performed the broken conductor protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the broken conductor protection. Set the logic setting [50BC.En] as 1 in the submenu BrknCond Settings. Set the setting [50BC.OutMap] as 0x0001 in the submenu BrknCond Settings. Set other logic settings as 0 in the submenu BrknCond Settings. 2. 3. 4. 5. De-energize all the binary inputs of this relay. Simulate a normal condition with normal currents. Simulate a broken conductor condition; the ratio I2/I1 is greater than 1.05 [50BC.I2/I1_Set]. After the period of [50BC.t_Op], the broken conductor protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the fault is disappeared, this relay will restore the broken conductor protection automatically. Restore the TRIP indicator and the LCD manually. 12.5.3.13 Auto-recloser Check This check, performed the auto-reclosing with synchronism check function in No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. There are many protective elements can make the auto-recloser operate. Here, all the check is based on the assumption that the stage 1 overcurrent protection is operated. 1. Enable the stage 1 overcurrent protection and auto-recloser of this relay. Set the logic setting [50/51P1.En] as 1 in the submenu OC Settings. Set the logic setting [50/51P1.En_VCE] as 1 in the submenu OC Settings. Set the setting [50/51P1.Opt_Dir] as 1 in the submenu OC Settings.
12-14
Date: 2011-08-29 PCS-9611 Feeder Relay

5.

12 Commissioning

Set the setting [50/51P1.OutMap] as 0x0001 in the submenu OC Settings. Set other logic settings as 0 in the submenu OC Settings. Set the logic setting [79.En] as 1 in the submenu AR Settings. Set the logic setting [79.En_SynChk] as 1 in the submenu AR Settings. Set the setting [79.N_Rcls] as 1 in the submenu AR Settings. Set other logic settings as 0 in the submenu AR Settings. Set the setting [79.OutMap] as 0x0002 in the submenu AR Settings. 2. 3. De-energize all the binary inputs of this relay. Simulate a normal condition with normal protection voltages, currents and synchro-check voltage, and the circuit breaker is closed. After a period of time delay, the auto-recloser is ready and in service. A full charged battery sign is shown on the right bottom of the LCD. Make the stage 1 overcurrent protection operate according the method which is described in Section 12.5.3.2. Just at the same time when the stage 1 overcurrent protection is operated, simulate a normal condition with normal voltage inputs (protection and synchro-check) and without current inputs, and the circuit breaker is opened. After the period of [79.t_3PS1], the auto-recloser will operate, the RECLOSE LED indicator will be on; a relevant report will be shown on the LCD. The auto-recloser with other check modes can be checked through the same method. Note to set the relevant logic settings as 1. For the details about the auto-recloser theory, see Section 3.17. 12.5.3.14 SOTF Overcurrent Protection Check This check, performed the SOTF overcurrent protection in No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the SOTF overcurrent protection. Do the following configuration on the base of the setting configuration as described in Section 12.5.3.13. Set the logic setting [50PSOTF.En] as 1 in the submenu SOTF Settings. Set the setting [SOTF.Opt_Mode] as 0 in the submenu SOTF Settings. Set the setting [50PSOTF.OutMap] as 0x0001 in the submenu SOTF Settings. Set other logic settings as 0 in the submenu SOTF Settings. 2. 3. De-energize all the binary inputs of this relay. Repeat the step 3 to step 5 as described in Section 12.5.3.13, and make the stage 1 overcurrent protection and the auto-recloser operate successfully. Simulate a single-phase fault or multi-phase fault, and the current of the fault phase is greater than 1.05 [50PSOTF.I_Set], and the circuit breaker is closed at the same time.

4.

5.

4.

PCS-9611 Feeder Relay Date: 2011-08-29

12-15

12 Commissioning

5.

After the period of [50PSOTF.t_Op], the SOTF overcurrent protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD.

12.5.3.15 Breaker Failure Protection Check This check, performed the breaker failure protection function in the No.1 setting group, demonstrates that the relay is operating correctly at the application-specific settings. There are many protective elements can initiate the breaker failure protection. Here, all the check is based on the assumption that the stage 1 overcurrent protection is operated. 1. Enable the stage 1 breaker failure protection and the stage 1 overcurrent protection. Set the logic setting [50/51P1.En] as 1 in the submenu OC Settings. Set the logic setting [50/51P1.En_VCE] as 1 in the submenu OC Settings. Set the setting [50/51P1.Opt_Dir] as 1 in the submenu OC Settings. Set the setting [50/51P1.OutMap] as 0x0001 in the submenu OC Settings. Set other logic settings as 0 in the submenu OC Settings. Set the logic setting [50BF.En] as 1 in the submenu BFP Settings. Set the logic setting [50BF.En_ReTrp] as 1 in the submenu BFP Settings. Set the setting [50BF.Opt_LogicMode] as 0 in the submenu BFP Settings. Set the setting [50BF.OutMap] as 0x0004 in the submenu BFP Settings. Set other logic settings as 0 in the submenu BFP Settings. 2. 3. 4. De-energize all the binary inputs of this relay. Simulate a normal condition with normal currents and the circuit breaker is closed. Make the stage 1 overcurrent protection operate according the method which is described in Section 12.5.3.2. Make the fault phase current is greater than 1.05 [50BF.I_Set] and the circuit breaker is closed. After the period of [50BF.t_ReTrp], the breaker failure protection will operate and issue the re-trip command; and after the period of [50BF.t_Op], the breaker failure protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 7. After the fault is disappeared, this relay will restore the breaker failure protection automatically. Restore the TRIP indicator and the LCD manually. 12.5.3.16 Mechanical Protection Check This check, performed the No.1 mechanical protection function in the No.1 setting group,

5.

6.

12-16
Date: 2011-08-29

PCS-9611 Feeder Relay

12 Commissioning

demonstrates that the relay is operating correctly at the application-specific settings. 1. Enable the No.1 mechanical protection. Set the logic setting [MR1.En] as 1 in the submenu MR Prot Settings. Set the setting [MR1.OutMap] as 0x0001 in the submenu MR Prot Settings. Set other logic settings as 0 in the submenu MR Prot Settings. 2. 3. 4. 5. De-energize all the binary inputs of this relay. Simulate a normal condition without any signal of mechanical protection. Energized the binary input which is defined as the input of the No.1 mechanical protection. After the period of [MR1.t_Op], the No.1 mechanical protection will operate and issue the trip command. The TRIP LED indicator will be on; a relevant report will be shown on the LCD. 6. After the signal of the No.1 mechanical protection is disappeared, this relay will restore the No.1 mechanical protection automatically. Restore the TRIP indicator and the LCD manually.

12.5.4 On-load Checks


The objectives of the on-load checks are: Confirm the external wiring to the current and voltage inputs is correct. Measure the magnitude of on-load current and voltage (if applicable). Check the polarity of each current transformer. However, these checks can only be carried out if there are no restrictions preventing the tenderization of the plant being protected. Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has been removed to allow testing. If it has been necessary to disconnect any of the external wiring from the protection in order to perform any of the foregoing tests, it should be ensured that all connections are replaced in accordance with the relevant external connection or scheme diagram. Confirm current and voltage transformer wiring. 12.5.4.1 Final Checks After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been necessary to disconnect any of the external wiring from the protection in order to perform the wiring verification tests, it should be ensured that all connections are replaced in accordance with the relevant external connection or scheme diagram. Ensure that the protection has been restored to service. If the protection is in a new installation or the circuit breaker has just been maintained, the circuit breaker maintenance and current counters should be zero. If a test block is installed, remove the
PCS-9611 Feeder Relay Date: 2011-08-29

12-17

12 Commissioning

test plug and replace the cover so that the protection is put into service. Ensure that all event records, fault records, disturbance records and alarms have been cleared and LEDs has been reset before leaving the protection.

12-18
Date: 2011-08-29

PCS-9611 Feeder Relay

13 Maintenance

13 Maintenance
Table of Contents
13.1 Maintenance Schedule.................................................................................13-1 13.2 Regular Testing.............................................................................................13-1 13.3 Failure Tracing and Repair ..........................................................................13-1 13.4 Replace Failed Modules...............................................................................13-1

PCS-9611 Feeder Relay Date: 2011-08-29

13-a

13 Maintenance

13-b
Date: 2011-08-29

PCS-9611 Feeder Relay

13 Maintenance

13.1 Maintenance Schedule


It is recommended that products supplied by NR receive periodic monitoring after installation. In view of the critical nature of protective relays and their infrequent operation, it is desirable to confirm that they are operating correctly at regular intervals. This relay is self-supervised and so requires less maintenance than earlier designs of relay. Most problems will result in an alarm so that remedial action can be taken. However, some periodic tests should be done to ensure that the relay is functioning correctly and the external wiring is intact.

13.2 Regular Testing


The relay is almost completely self-supervised. The circuits which can not be supervised are binary input, output circuits and human machine interfaces. Therefore regular testing can be minimized to checking the unsupervised circuits.

13.3 Failure Tracing and Repair


Failures will be detected by automatic supervision or regular testing. When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on the front panel with LED indicators and LCD display. It is also recorded in the alarm record. Failures detected by supervision are traced by checking the ALM REPORT screen on the LCD. See Section 8.3.2 for the details of the alarm events. When a failure is detected during regular testing, confirm the following: Test circuit connections are correct Modules are securely inserted in position Correct DC power voltage is applied Correct AC inputs are applied Test procedures comply with those stated in the manual

13.4 Replace Failed Modules


If the failure is identified to be in the relay module and the user has spare modules, the user can recover the protection by replacing the failed modules. Repair at the site should be limited to module replacement. Maintenance at the component level is not recommended. Check that the replacement module has an identical module name and hardware type-form as the
PCS-9611 Feeder Relay Date: 2011-08-29

13-1

13 Maintenance

removed module. Furthermore, the replaced module should have the same software version. And the replaced analog input module and power supply module should have the same ratings. WARNING! Units and modules may only be replaced while the supply is switched off and only by appropriately trained and qualified personnel. Strictly observe the basic precautions to guard against electrostatic discharge. WARNING! When handling a module, take anti-static measures such as wearing an earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many of the electronic components could suffer damage. After replacing the CPU module, check the settings. DANGER! After replacing modules, be sure to check that the same configuration is set as before the replacement. If this is not the case, there is a danger of the unintended operation of switchgear taking place or of protections not functioning correctly. Persons may also be put in danger.

13-2
Date: 2011-08-29

PCS-9611 Feeder Relay

14 Decommissioning and Disposal

14 Decommissioning and Disposal


Table of Contents
14.1 Decommissioning ........................................................................................14-1
14.1.1 Switching off .................................................................................................................. 14-1 14.1.2 Disconnecting cables ..................................................................................................... 14-1 14.1.3 Dismantling .................................................................................................................... 14-1

14.2 Disposal ........................................................................................................14-1

PCS-9611 Feeder Relay Date: 2011-08-29

14-a

14 Decommissioning and Disposal

14-b
Date: 2011-08-29

PCS-9611 Feeder Relay

14 Decommissioning and Disposal

14.1 Decommissioning
14.1.1 Switching off
To switch off this relay, switch off the external miniature circuit breaker of the power supply.

14.1.2 Disconnecting cables


Disconnect the cables in accordance with the rules and recommendations made by relational department. DANGER! Before disconnecting the power supply cables that connected with the power supply module of this relay, make sure that the external miniature circuit breaker of the power supply is switched off. DANGER! Before disconnecting the cables that are used to connect analog input module with the primary CT and VT, make sure that the circuit breaker for the primary CT and VT is switched off.

14.1.3 Dismantling
The rack of this relay may now be removed from the system cubicle, after which the cubicles may also be removed. DANGER! When the station is in operation, make sure that there is an adequate safety distance to live parts, especially as dismantling is often performed by unskilled personnel.

14.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste. NOTE! Strictly observe all local and national regulations when disposing of the device.

PCS-9611 Feeder Relay Date: 2011-08-29

14-1

14 Decommissioning and Disposal

14-2
Date: 2011-08-29

PCS-9611 Feeder Relay

15 Manual Version History

15 Manual Version History


In the current version of the instruction manual, several descriptions on existing features have been modified. Manual version and modification history records
Manual Version Source Beta New 1.00 Software Version 2.00 Date 2011-06-24 Description of change Form the original manual. 1. 2. 3. 4. 5. 6. 7. Update the technical data of the fault and disturbance recording function in Section 2.3.4; Update the description of the auto-recloser and the check modes in Section 3.17; Update the description of the manual closing function and the check modes in Section 3.18; 1.00 1.01 2.01 2011-08-29 Update the range and explain of the setting [Opt_PwrDir] in Section 7.2; Update the explain of the setting [Protocol_RS485A] and [Protocol_RS485B] in Section 7.6.2; Update the HMI operation and relevant information in Chapter 8; Update the programmable input signal and output signal tables in Section 9.4.

PCS-9611 Feeder Relay Date: 2011-08-29

15-1

15 Manual Version History

15-2
Date: 2011-08-29

PCS-9611 Feeder Relay

S-ar putea să vă placă și