PROJECT NAME: WALL SCHEDULE DATA INPUT

Concrete Strength (f'c) Steel Yield Strength (fy)

CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL
3.87 Mpa 276.18 MPa 561 psi 40000 psi

All dimensions are in Newtons or millimeters unless otherwise indicated Wall NUMBER SW-1 SW-2 SW-3 SW-5 SW-6 Wall Mark 2W-1 2W-2 3W-1 3W-3 4W-3 Length (m) 25.50 18.78 25.50 37.67 37.67 Thickness Total Height (m) 7.95 7.95 5.15 5.15 7.97 Horizontal Reinforcement (Both Faces) Diameter Spacing 12 250 12 200 12 10 10 250 250 250 Vertical Reinforcement (Both Faces) Diameter Spacing 12 250 12 200 12 10 10 250 250 250 Demands Shear Moment (kN) (kN-m) 57.78 397.48 6770.43 2538.04 57.78 5952.06 5952.06 397.48 389.94 389.94

300 500 300 150 150

PROJECT NAME:

CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL

SUMMARY OF RESULTS
All dimensions are in Newtons or millimeters, unless otherwise indicated Wall NUMBER SW-1 SW-2 SW-3 SW-5 SW-6 Wall Mark 2W-1 2W-2 3W-1 3W-3 4W-3 Shear Capacity (kN) 6,039.35 6,083.37 6,039.35 5,705.46 5,705.91 Shear Demand (kN) 57.78 6,770.43 57.78 5,952.06 5,952.06 Shear C/D Ratio 104.52 0.90 104.52 0.96 0.96 Horizontal Reinforcement Vertical Reinforcement Minimum Maximum Minimum Maximum Area Spacing Area Spacing Compliant Compliant Non-Compliant Compliant Non-Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Compliant Moment Capacity (kN-m) 59,477.26 41,923.35 59,477.26 85,735.00 85,748.65 Moment Moment Demand C/D Ratio (kN-m) 397.48 149.64 2,538.04 16.52 397.48 149.64 389.94 219.87 389.94 219.90

SHEAR WALL CAPACITY WORKSHEET PROJECT NAME: CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL WALL NUMBER: SW-1 WALL MARK: 2W-1 All dimensions are in Newtons or Millimeters unless otherwise indicated Length of Wall, lw (m) Thickness, h Horizontal Reinforcement (both faces) Diameter Spacing, s2 Vertical Reinforcement (both faces) Diameter Spacing, s1 Total Height of Wall, Hw (m) Concrete Compresive Strength, f'c (MPa) Steel Yield Strength, fy (MPa) 411.11.3 Calculate Maximum Shear Strength Vmax (kN) = (5/6)*sqrt(f'c)*h*d = Calculate Shear Strength Provided by Concrete Vc (kN) = (1/6)*sqty(f'c)*h*d = Calculate Shear Strength Provided by Horizontal Shear Reinforcement Vs (kN) = (Avh*fy*d)/s2 = Calculate Nominal Shear Capacity Vu (kN) = Vc + Vs = Calculate Design Shear Capacity Vd (kN) = f*Vu = Calculate Minimum Horizontal Shear Reinforcement minimum Avh = 0.0025*h*s2 actual Avh = Calculate Maximum Spacing of Horizontal Shear Reinforcement maximum s2: lw/5 = 3*h 450 mm smallest of above = actual s2 = Calculate Minimum Vertical Shear Reinforcement minimum Avv: [0.0025 + 0.5*(2.5 - hw/lw)*(rh - 0.0025)]*h*s1 = (0.0025)*h*s1 = Avh biggest of above = actual Avv = Calculate the maximum spacing of vertical shear reinforcement maximum s1: lw/3 = 3*h = 450 mm smallest of above = actual s1 = Calculate Nominal Moment Capacity Mn (kN-m) = 0.5*Ast*fy*lw*(1 - z/lw) = z/lw = 1/[(2 + 0.85*b1*lw*h*f'c/(Ast*fy)] = Ast = Avv*(lw/s1) = Calculate Design Moment Capacity Md = f*Mn = 25.50 300 12 250 12 250 7.95 3.87 276.18

10,037.36

411.11.5

2,007.47

411.11.9.1

5,097.64

411.2.1

7,105.12

409.4.4

6,039.35

411.11.9.2

187.50 226.20 Compliant 5100 750 450 450 250 Compliant 229.84 187.50 226.20 229.84 226.20 Non-Compliant 8,500 900 450 450 250 Compliant 66,085.8 0.19 23,071.91 59,477.3

411.11.9.3

411.11.9.4

411.11.9.5

SHEAR WALL CAPACITY WORKSHEET PROJECT NAME: CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL WALL NUMBER: SW-2 WALL MARK: 2W-2 All dimensions are in Newtons or Millimeters unless otherwise indicated Length of Wall, lw (m) Thickness, h Horizontal Reinforcement (both faces) Diameter Spacing, s2 Vertical Reinforcement (both faces) Diameter Spacing, s1 Total Height of Wall, Hw (m) Concrete Compresive Strength, f'c (MPa) Steel Yield Strength, fy (MPa) 411.11.3 Calculate Maximum Shear Strength Vmax (kN) = (5/6)*sqrt(f'c)*h*d = Calculate Shear Strength Provided by Concrete Vc (kN) = (1/6)*sqty(f'c)*h*d = Calculate Shear Strength Provided by Horizontal Shear Reinforcement Vs (kN) = (Avh*fy*d)/s2 = Calculate Nominal Shear Capacity Vu (kN) = Vc + Vs = Calculate Design Shear Capacity Vd (kN) = f*Vu = Calculate Minimum Horizontal Shear Reinforcement minimum Avh = 0.0025*h*s2 actual Avh = Calculate Maximum Spacing of Horizontal Shear Reinforcement maximum s2: lw/5 = 3*h 450 mm smallest of above = actual s2 = Calculate Minimum Vertical Shear Reinforcement minimum Avv: [0.0025 + 0.5*(2.5 - hw/lw)*(rh - 0.0025)]*h*s1 = (0.0025)*h*s1 = Avh biggest of above = actual Avv = Calculate the maximum spacing of vertical shear reinforcement maximum s1: lw/3 = 3*h = 450 mm smallest of above = actual s1 = Calculate Nominal Moment Capacity Mn (kN-m) = 0.5*Ast*fy*lw*(1 - z/lw) = z/lw = 1/[(2 + 0.85*b1*lw*h*f'c/(Ast*fy)] = Ast = Avv*(lw/s1) = Calculate Design Moment Capacity Md = f*Mu = 18.78 500 12 200 12 200 7.95 3.87 276.18

12,320.4

411.11.5

2,464.07

411.11.9.1

4,692.83

411.2.1

7,156.90

409.4.4

6,083.37

411.11.9.2

250.00 226.20 Non-Compliant 3756 600 450 450 200 Compliant 225.28 250.00 226.20 226.20 226.20 Compliant 6,260 1,500 450 450 200 Compliant 46,581.5 0.15 21,239.7 41,923.3

411.11.9.3

411.11.9.4

411.11.9.5

SHEAR WALL CAPACITY WORKSHEET PROJECT NAME: CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL WALL NUMBER: SW-3 WALL MARK: 3W-1 All dimensions are in Newtons or Millimeters unless otherwise indicated Length of Wall, lw (m) Thickness, h Horizontal Reinforcement (both faces) Diameter Spacing, s2 Vertical Reinforcement (both faces) Diameter Spacing, s1 Total Height of Wall, Hw (m) Concrete Compresive Strength, f'c (MPa) Steel Yield Strength, fy (MPa) 411.11.3 Calculate Maximum Shear Strength Vmax (kN) = (5/6)*sqrt(f'c)*h*d = Calculate Shear Strength Provided by Concrete Vc (kN) = (1/6)*sqty(f'c)*h*d = Calculate Shear Strength Provided by Horizontal Shear Reinforcement Vs (kN) = (Avh*fy*d)/s2 = Calculate Nominal Shear Capacity Vu (kN) = Vc + Vs = Calculate Design Shear Capacity Vd (kN) = f*Vu = Calculate Minimum Horizontal Shear Reinforcement minimum Avh = 0.0025*h*s2 actual Avh = Calculate Maximum Spacing of Horizontal Shear Reinforcement maximum s2: lw/5 = 3*h 450 mm smallest of above = actual s2 = Calculate Minimum Vertical Shear Reinforcement minimum Avv: [0.0025 + 0.5*(2.5 - hw/lw)*(rh - 0.0025)]*h*s1 = (0.0025)*h*s1 = Avh biggest of above = actual Avv = Calculate the maximum spacing of vertical shear reinforcement maximum s1: lw/3 = 3*h = 450 mm smallest of above = actual s1 = Calculate Nominal Moment Capacity Mn (kN-m) = 0.5*Ast*fy*lw*(1 - z/lw) = z/lw = 1/[(2 + 0.85*b1*lw*h*f'c/(Ast*fy)] = Ast = Avv*(lw/s1) = Calculate Design Moment Capacity Md = f*Mu = 25.50 300 12 250 12 250 5.15 3.87 276.18

10,037.36

411.11.5

2,007.47

411.11.9.1

5,097.64

411.2.1

7,105.12

409.4.4

6,039.35

411.11.9.2

187.50 226.20 Compliant 5100 750 450 450 250 Compliant 231.96 187.50 226.20 226.20 226.20 Compliant 8,500 900 450 450 250 Compliant 66,085.84 0.19 23,071.91 59,477.26

411.11.9.3

411.11.9.4

411.11.9.5

SHEAR WALL CAPACITY WORKSHEET PROJECT NAME: CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL WALL NUMBER: SW-4 WALL MARK: 3W-3 All dimensions are in Newtons or Millimeters unless otherwise indicated Length of Wall, lw (m) Thickness, h Horizontal Reinforcement (both faces) Diameter Spacing, s2 Vertical Reinforcement (both faces) Diameter Spacing, s1 Total Height of Wall, Hw (m) Concrete Compresive Strength, f'c (MPa) Steel Yield Strength, fy (MPa) 411.11.3 Calculate Maximum Shear Strength Vmax (kN) = (5/6)*sqrt(f'c)*h*d = Calculate Shear Strength Provided by Concrete Vc (kN) = (1/6)*sqty(f'c)*h*d = Calculate Shear Strength Provided by Horizontal Shear Reinforcement Vs (kN) = (Avh*fy*d)/s2 = Calculate Nominal Shear Capacity Vu (kN) = Vc + Vs = Calculate Design Shear Capacity Vd (kN) = f*Vu = Calculate Minimum Horizontal Shear Reinforcement minimum Avh = 0.0025*h*s2 actual Avh = Calculate Maximum Spacing of Horizontal Shear Reinforcement maximum s2: lw/5 = 3*h 450 mm smallest of above = actual s2 = Calculate Minimum Vertical Shear Reinforcement minimum Avv: [0.0025 + 0.5*(2.5 - hw/lw)*(rh - 0.0025)]*h*s1 = (0.0025)*h*s1 = Avh biggest of above = actual Avv = Calculate the maximum spacing of vertical shear reinforcement maximum s1: lw/3 = 3*h = 450 mm smallest of above = actual s1 = Calculate Nominal Moment Capacity Mn (kN-m) = 0.5*Ast*fy*lw*(1 - z/lw) = z/lw = 1/[(2 + 0.85*b1*lw*h*f'c/(Ast*fy)] = Ast = Avv*(lw/s1) = Calculate Design Moment Capacity Md = f*Mu = 18.78 200 10 200 10 200 5.15 3.87 276.18

4,928.15

411.11.5

985.63

411.11.9.1

3,258.91

411.2.1

4,244.54

409.4.4

3,607.86

411.11.9.2

100.00 157.08 Compliant 3756 600 450 450 200 Compliant 163.52 100.00 157.08 157.08 157.08 Compliant 6,260 600 450 450 200 Compliant 29,900.27 0.22 14,749.81 26,910.24

411.11.9.3

411.11.9.4

411.11.9.5

SHEAR WALL CAPACITY WORKSHEET PROJECT NAME: CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL WALL NUMBER: SW-5 WALL MARK: 3W-3 All dimensions are in Newtons or Millimeters unless otherwise indicated Length of Wall, lw (m) Thickness, h Horizontal Reinforcement (both faces) Diameter Spacing, s2 Vertical Reinforcement (both faces) Diameter Spacing, s1 Total Height of Wall, Hw (m) Concrete Compresive Strength, f'c (MPa) Steel Yield Strength, fy (MPa) 411.11.3 Calculate Maximum Shear Strength Vmax (kN) = (5/6)*sqrt(f'c)*h*d = Calculate Shear Strength Provided by Concrete Vc (kN) = (1/6)*sqty(f'c)*h*d = Calculate Shear Strength Provided by Horizontal Shear Reinforcement Vs (kN) = (Avh*fy*d)/s2 = Calculate Nominal Shear Capacity Vu (kN) = Vc + Vs = Calculate Design Shear Capacity Vd (kN) = f*Vu = Calculate Minimum Horizontal Shear Reinforcement minimum Avh = 0.0025*h*s2 actual Avh = Calculate Maximum Spacing of Horizontal Shear Reinforcement maximum s2: lw/5 = 3*h 450 mm smallest of above = actual s2 = Calculate Minimum Vertical Shear Reinforcement minimum Avv: [0.0025 + 0.5*(2.5 - hw/lw)*(rh - 0.0025)]*h*s1 = (0.0025)*h*s1 = Avh biggest of above = actual Avv = Calculate the maximum spacing of vertical shear reinforcement maximum s1: lw/3 = 3*h = 450 mm smallest of above = actual s1 = Calculate Nominal Moment Capacity Mn (kN-m) = 0.5*Ast*fy*lw*(1 - z/lw) = z/lw = 1/[(2 + 0.85*b1*lw*h*f'c/(Ast*fy)] = Ast = Avv*(lw/s1) = Calculate Design Moment Capacity Md = f*Mu = 37.67 150 10 250 10 250 5.15 3.87 276.18

7,413.87

411.11.5

1,482.77

411.11.9.1

5,229.53

411.2.1

6,712.30

409.4.4

5,705.46

411.11.9.2

93.75 157.08 Compliant 7534 750 450 450 250 Compliant 168.58 93.75 157.08 157.08 157.08 Compliant 12,557 450 450 450 250 Compliant 95,261.1 0.23 23,668.81 85,735.0

411.11.9.3

411.11.9.4

411.11.9.5

SHEAR WALL CAPACITY WORKSHEET PROJECT NAME: CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL WALL NUMBER: SW-6 WALL MARK: 4W-3 All dimensions are in Newtons or Millimeters unless otherwise indicated Length of Wall, lw (m) Thickness, h Horizontal Reinforcement (both faces) Diameter Spacing, s2 Vertical Reinforcement (both faces) Diameter Spacing, s1 Total Height of Wall, Hw (m) Concrete Compresive Strength, f'c (MPa) Steel Yield Strength, fy (MPa) 411.11.3 Calculate Maximum Shear Strength Vmax (kN) = (5/6)*sqrt(f'c)*h*d = Calculate Shear Strength Provided by Concrete Vc (kN) = (1/6)*sqty(f'c)*h*d = Calculate Shear Strength Provided by Horizontal Shear Reinforcement Vs (kN) = (Avh*fy*d)/s2 = Calculate Nominal Shear Capacity Vu (kN) = Vc + Vs = Calculate Design Shear Capacity Vd (kN) = f*Vu = Calculate Minimum Horizontal Shear Reinforcement minimum Avh = 0.0025*h*s2 actual Avh = Calculate Maximum Spacing of Horizontal Shear Reinforcement maximum s2: lw/5 = 3*h 450 mm smallest of above = actual s2 = Calculate Minimum Vertical Shear Reinforcement minimum Avv: [0.0025 + 0.5*(2.5 - hw/lw)*(rh - 0.0025)]*h*s1 = (0.0025)*h*s1 = Avh biggest of above = actual Avv = Calculate the maximum spacing of vertical shear reinforcement maximum s1: lw/3 = 3*h = 450 mm smallest of above = actual s1 = Calculate Nominal Moment Capacity Mn (kN-m) = 0.5*Ast*fy*lw*(1 - z/lw) = z/lw = 1/[(2 + 0.85*b1*lw*h*f'c/(Ast*fy)] = Ast = Avv*(lw/s1) = Calculate Design Moment Capacity Md = f*Mu = 37.67 150 10 250 10 250 7.97 3.87 276.18

7,414.46

411.11.5

1,482.89

411.11.9.1

5,229.94

411.2.1

6,712.84

409.4.4

5,705.91

411.11.9.2

93.75 157.08 Compliant 7534.6 750 450 450 250 Compliant 166.21 93.75 157.08 157.08 157.08 Compliant 12,558 450 450 450 250 Compliant 95,276.28 0.23 23,670.70 85,748.65

411.11.9.3

411.11.9.4

411.11.9.5

SHEAR WALL CAPACITY WORKSHEET PROJECT NAME: CONSULTING SERVICES FOR THE DETAILED ENGINEERING (STRUCTURAL) INVESTIGATION OF THE MANILA CATHEDRAL WALL NUMBER: SW-7 WALL MARK: 4W-3 All dimensions are in Newtons or Millimeters unless otherwise indicated Length of Wall, lw (m) Thickness, h Horizontal Reinforcement (both faces) Diameter Spacing, s2 Vertical Reinforcement (both faces) Diameter Spacing, s1 Total Height of Wall, Hw (m) Concrete Compresive Strength, f'c (MPa) Steel Yield Strength, fy (MPa) 411.11.3 Calculate Maximum Shear Strength Vmax (kN) = (5/6)*sqrt(f'c)*h*d = Calculate Shear Strength Provided by Concrete Vc (kN) = (1/6)*sqty(f'c)*h*d = Calculate Shear Strength Provided by Horizontal Shear Reinforcement Vs (kN) = (Avh*fy*d)/s2 = Calculate Nominal Shear Capacity Vu (kN) = Vc + Vs = Calculate Design Shear Capacity Vd (kN) = f*Vu = Calculate Minimum Horizontal Shear Reinforcement minimum Avh = 0.0025*h*s2 actual Avh = Calculate Maximum Spacing of Horizontal Shear Reinforcement maximum s2: lw/5 = 3*h 450 mm smallest of above = actual s2 = Calculate Minimum Vertical Shear Reinforcement minimum Avv: [0.0025 + 0.5*(2.5 - hw/lw)*(rh - 0.0025)]*h*s1 = (0.0025)*h*s1 = Avh biggest of above = actual Avv = Calculate the maximum spacing of vertical shear reinforcement maximum s1: lw/3 = 3*h = 450 mm smallest of above = actual s1 = Calculate Nominal Moment Capacity Mn (kN-m) = 0.5*Ast*fy*lw*(1 - z/lw) = z/lw = 1/[(2 + 0.85*b1*lw*h*f'c/(Ast*fy)] = Ast = Avv*(lw/s1) = Calculate Design Moment Capacity Md = f*Mu = 18.78 200 10 200 10 200 7.97 3.87 276.18

4,928.15

411.11.5

985.63

411.11.9.1

3,258.91

411.2.1

4,244.54

409.4.4

3,607.86

411.11.9.2

100.00 157.08 Compliant 3756 600 450 450 200 Compliant 159.24 100.00 157.08 157.08 157.08 Compliant 6,260 600 450 450 200 Compliant 29,900.27 0.22 14,749.81 26,910.24

411.11.9.3

411.11.9.4

411.11.9.5