Sunteți pe pagina 1din 89

SINGLE-PHASE TO THREE-PHASE DRIVE SYSTEM USING TWO PAPALLEL SINGLE PHASE RECTIFIERS

A Main Project Report submitted in partial fulfilment of the Requirements for the award of the degree of BACHELORE OF TECHNOLOGY IN ELECTRICAL & ELECTRONICS ENGINEERING By

M.THRIVENI B.RAJU P.KARUNAKAR B.NAGESWARA RAO K.NAVEEN Under the guidance of Mr.P.PURNA CHANDA RAO M.Tech Assistant Professor

(09HT1A0225) (09HT1A0205) (09HT1A0235) (09HT1A0206) (09HT1A0221)

Department of Electrical & Electronics Engineering

Chalapathi Institute Of Technology


(Approved by AICTE, Affiliated to JNTU Kakinada) (2009-2013)

Department of Electrical & Electronics Engineering

Chalapathi Institute Of Technology


(Approved by AICTE, Affiliated to JNTU Kakinada) ( 2009-2013)

CERTIFICATE
This is to certify that the project entitled SINGLE -PHASE TO THREE-PHASEDRIVE SYSTEM USING TWO PAPALLEL SINGLE PHASE RECTIFIERS is a bonafide Work done by M.THRIVENI (09HT1A0225), B.RAJU (09HT1A0205), P.KARUNAKAR (09HT1A0235), B.NAGESWARA RAO (09HT1A0206), K.NAVEEN (09HT1A0221) in partial Fulfillment of the Academic requirements for the award of the degree of Bachelor of Technology in Electrical& Electronics Engineering, Submitted to the Department of Electrical and Electronics Engineering, Chalapathi Institute of Technology, Mothadaka, Guntur during the Period. This results embodied in the project report Have not been Submitted to any other University or institute for the award of any degree.

Mr.P.Purna Chandra Rao Project Guide, DepartmentofEEE,

M.Tech.

Mr.N.Rajesh Babu

M.Tech, MBA.

HeadoftheDepartment, DepartmentofEEE, Chalapathi institute of Technology. .

Chalapathi institute of Technology.

Acknowledgment

We would like to express our heartfelt gratitude to my guide Mr. P.PURNA CHANDRA RAO, Assistant Professor, Department of Electrical and Electronics Engineering, Chalapathi Institute of Technology. He has given us tremendous support in both technical and moral front. Without his support and encouragement, we would never have been able to complete the project successfully. We are grateful to Mr. N.RAJESH BABU, Head of the Department of Electrical And Electronics Engineering, Chalapathi institute of Technology, for presenting us this opportunity and for extending constant support and valuable guidance throughout the project. Our profound thanks to Dr.C.Ravi Kanth, principal, chalapathi institute of Technology, for his support. We would also like to thank all our teaching staff members of EEE for giving us Their valuable suggestions. Finally, we are thankful to one and all who contributed for the Successful completion of our project work by M.THRIVENI B.RAJU P.KARUNAKAR B.NAGESWARA RAO K.NAVEEN (09HT1A0225) (09HT1A0205) (09HT1A0235) (09HT1A0206) (09HTIA0221)

DECLARATION

We hereby declare that the project entitled SINGLE PHASE TO THREE PHASE DRIVE SYSTEM USING TWO PARALLEL SINGLE PHASE RECTIFIERS, submitted in the partial Fulfillment of the requirements for the award of Bachelor of Technology in Electrical & Electronics Engineering, to Chalapathi Institute of Technology, Mothadaka, Guntur, affiliated to JNTU, Kakinada is a authentic work and has not been submitted to any other university or institution for Award of the degree by M.THRIVENI B.RAJU P.KARUNAKAR B.NAGESWARA RAO K.NAVEEN (09HT1A0225) (09HT1A0205) (09HTA10235) (09HT1A0206) (09HT1A0221) .

ABSTRACT

Single-phase to three-phase acdcac conversion usually employs a full-bridge topology. In these three phase induction motor is operated from single-phase supply by using two parallel single-phase rectifiers The topology permits to reduce the rectifier switch currents, the harmonic distortion at the input converter side, and presents improvements on the fault tolerance characteristics and it is shown by reduction of circulating current. . The system is composed of two parallel single-phase rectifiers, a three-phase inverter, and an induction motor. The power continuity is a major issue solved in this project and is achieved by using parallel converters. The fault in the rectifier does not affect the power flow and if a fault in any rectifier is occurred the entire power is fed through the other rectifier. The topology was simulated in Matlab/simulink software and performance of induction motor by this topology was studied.

CONTENTS
ABSTRACT List of Figures List of Tables i iv vi

ABSTRACT LIST OF FIGURES LIST OF TABLES Chapter 1: INTRODUCTION


1.1 Introduction: 1.2 Motivation of Work: 1.3 Problem Definition: 1.4 Scope of the project: 1.5 Solution Technique: 1.6 Literature Overview:

1 5 8 1
1 2 2 2 2 3

Chapter 2:SINGLE PHASE A.C TO THREE PHASE A.C CONVERSION METHODS


2.1 Methods to Convert Single Phase to Three Phase Drive Systems 2.1.1 Rotary phase converter: 2.1.2 Static Phase Converter 2.1.3 Phase Perfect Digital Phase Converter: 2.2 Single-Phase to Three-Phase (1-3) Cycloconverters: 2.2.1 Integral Pulse Modulated (1-3) Cycloconverters: 2.2.2 Phase-Controlled (1-3) Cycloconverter: 2.3 Single-Phase-to-Three-Phase AC/DC/AC PWM Converter:

8
8 8 9 9 10 11 11 11

Chapter 3: CHARACTERISTICS OF INDUCTION MOTOR


3.1 Starting characteristics: 3.2 Running Characteristics: 3.3 Load characteristics: 3.3.1 Constant Torque, Variable Speed Loads: 3.3.2 Variable Torque, Variable Speed Loads: 3.3.3 Constant Power Loads: 3.3.4 Constant Power, Constant Torque Loads: 3.3.5 High Starting/Breakaway Torque followed by Constant Torque 3.4. Induction motor characteristics in the proposed system:

13
13 14 15 15 16 16 16 17 17

Chapter 4: CONTROL STRATEGIES OF CONVERTERS


4.1 Introduction: 4.2 Sinusoidal Pulse Width Modulation:

19
19 21

4.2.1 SPWM Spectra: 4.3 Space Vector PWM: 4.3.1 Principle of Space Vector PWM: 4.4. Vector Control technique: 4.5 control circuits adopted in the system: 4.5.1. Rectifier control circuit: 4.5.2. Inverter control circuit: 4.5.3. pi controller:

24 25 25 33 34 35 35 36

Chapter 5: DESIGN METHODOLOGY OF PROPOSED CONVERTER


5.1 Introduction: 5.2 Mathematical Modelling of the proposed system: 5.2.1.Different modes/loops in the proposed system: 5.3 PWM Strategy: 5.4 Control Strategy: 5.5 Harmonic Distortion: 5.6 Ratings of Switches: 5.7 DC-Link Capacitor Design: 5.8 Input Inductors: 5.9 Fault Compensation: 5.10 Losses and Efficiency: 5.11 Costs and Applications of Configuration: 5.12 pulse train of control circuits of rectifier and inverter switches:

37
37 39 39 43 45 46 49 50 51 52 54 56 56

Chapter 6: SIMULATION AND RESULT DISCUSSION


6.1 Simulation Results for 110V AC: 6.1.1 Simulation of Conventional Model: 6.1.2 Simulation of Proposed Model: 6.2 Simulation Results for 230V AC: 6.2.1 Simulation of Conventional Model: 6.2.2 Simulation of proposed Model:

58
58 58 61 68 68 70

Chapter 7: CONCLUSION AND FUTURE SCOPE


Conclusion: Future Scope:

75
75 75

Chapter 8: BIBLIOGRAPHY

76

LIST OF FIGURES

Figure no.
Fig. 2.1: Fig 2.2: Fig. 2.3(a): Fig.2.3(b): Fig. 3.1: Fig. 3.2: Fig .3.3: Fig. 3.4: Fig. 3.5: Fig. 3.6: Fig. 3.7: Fig. 3.8 Fig. 4.1 Fig. 4.2: Fig. 4.3: Fig. 4.4: Fig. 4.5: Fig. 4.6: Fig. 4.7: Fig. 4.8: Fig. 4.9:

Description
Block diagram for rotary phase converter Block diagram of Phase Perfect Digital Phase Converter Single-phase-to-three-phase ac/dc/ac PWM converter wave form of grid voltage & current Typical torque-speed curve of the three-phase induction motor Torque-speed curves of the motor with two different loads Constant Torque, Variable Speed Loads Variable Torque, Variable Speed Loads Constant Power Loads Constant Power, Constant Torque Loads Relation between the Voltage and Torque versus Frequency wave forms of three phase voltage, current, speed and torque Unipolar and bipolar modulation Simple Voltage Sourced Inverter Principal of Pulse Width Modulation SPWM Harmonic Spectra Three-phase voltage source PWM Inverter The eight inverter voltage vectors (V0 to V7) Locus comparison of maximum linear control voltage in Sine PWM and SVPWM The relationship of abc reference frame and stationary dq reference frame Basic switching vectors and sectors

Page no.
9 10 12 12 14 15 15 16 16 17 17 18 22 23 24 25 25 27 27 28 29

Fig.4.10: Fig. 4.11: Fig. 4.12: Fig. 4.13: Fig. 4.14: Fig 4.15: Fig. 5.1 Fig. 5.2(a) Fig. 5.2(b) Fig: 5.2.1a: Fig: 5.2.1(b): Fig: 5.2.1(c): Fig: 5.2.1(d): Fig. 5.3 Fig. 5.4

Reference vector as a combination of adjacent vectors at sector 1 Space vector PWM switching patterns at each sector Block diagram for vector control technique using direct torque and speed control Control circuit for rectifier Control circuit for inverter Block diagram of pi controller Conventional single-phase to three phase drive system Proposed single-phase to three phase drive system Block diagram of proposed single-phase to three phase drive system model Loop1 of the system model Loop2 of the system model Loop3 of the system model Loop4 of the system model Control Block Diagram for rectifier WTHD of rectifier voltage (vab for proposed configuration and vg for Standard configuration) as a function of Variables of rectifiers A and B. Currents ia , ia , and io for double-carrier Flow of active power in Conventional acdcac singlephase to three phase converter Flow of active power in Proposed system with two rectifiers Inductor specification in terms of THD of ig and Proposed configuration highlighting devices of faulttolerant system. Block diagram of the fault diagnosis system Possibilities of configurations in terms of fault occurrence pulse trainee of rectifier control circuit pulse trainee of inverter control circuit Simulink model of conventional system

31 32 34 35 36 36 37 38 38 39 40 40 41 45 47 48 49 50 50 52 53 53 54 56 57 58

Fig. 5.5 Fig. 5.6 Fig. 5.7(a) Fig. 5.7(b) Fig. 5.8: Fig. 5.9(a): Fig.5.9 (b): Fig.5.10: Fig5.11(a): Fig.5.11(b): Fig. 6.1:

Fig. 6.2: Fig. 6.3: Fig. 6.4: Fig. 6.5: Fig. 6.6: Fig. 6.7: Fig. 6.8: Fig. 6.9: Fig. 6.10: Fig. 6.11 : Fig. 6.12: Fig. 6.13: Fig. 6.14: Fig. 6.15: Fig. 6.16: Fig. 6.17: Fig. 6.18 : Fig. 6.19: Fig. 6.20 : Fig.6.21: Fig. 6.22: Fig. 6.23: Fig. 6.24: Fig. 6.25: Fig. 6.26: Fig. 6.27: Fig. 6.28 : Fig. 6.29: Fig. 6.30 : Fig. 6.31 :

Wave forms of grid input voltage & current Wave form of DC-Link capacitor voltage Wave form of current ia in rectifier A Wave form of output line voltage THD content at input current is 19.36% Simulink model of proposed system Simulink model of control circuit for rectifier Simulink model of control circuit for inverter Wave forms of grid input voltage & current Wave form of DC-Link capacitor voltage Wave form of circulating current Wave forms of currents in rectifier A & B Wave forms of grid voltage & current in fault condition Wave forms currents in rectifier A & B in fault condition Wave forms currents in rectifier A in fault condition THD content at input current using SPWM Technique THD content at input current using SVPWM Technique THD content at output voltage using SPWM Technique THD content at output voltage using SVPWM Technique Wave forms of grid input voltage & current Wave form of current in rectifier A Wave form of DC-Link capacitor voltage Wave forms of currents in rectifier A & B Wave form of output line voltage Wave form of circulating current Wave form of DC-Link capacitor voltage THD content at input current using SVPWM Technique THD content at input current using SPWM technique THD content at output voltage with SPWM technique THD content at output voltage with SVPWM technique

58 59 59 60 60 61 61 62 62 63 63 64 64 65 65 66 66 67 67 68 69 69 70 70 71 71 72 72 73 73

LIST OF TABLES

Description
Table 1: ratings of induction motor Table 2: Switching vectors, phase voltages and output line to line voltages Table 3: Efficiency of the Proposed System Normalized In Terms Conventional Table 4: Comparison of conventional and proposed systems for 110V supply Table 5: Comparison of conventional and proposed systems for 230V Table 6: Distribution of currents for different values of modulation index

Pg. No.
19 26 55 68 74 74

Introduction Chapter 1

INTRODUCTION

1.1 Introduction:

Many solutions have been proposed when the objective is to supply threephase motors from single-phase ac mains. It is quite common to have only a single phase power grid in residential, commercial, manufacturing and mainly in rural areas, while the induction motor may require a three-phase power grid. The motor and power factor control and reduction of total harmonic distortion have been presented by using a single phase to three-phase converter topology, this is a two step conversion which involves single phase a.c to d.c by using a rectifier and then d.c to a.c by using three phase inverter reduced number of switching devices. The most desirable characteristics of ac to ac power converters are: Sinusoidal input and output currents Operation with nearly unity power factor for any load Simple and compact power circuit Generation of load voltage with arbitrary amplitude and frequency

A front end-rectifier followed by a pulse width modulated voltage source inverter (VSI-PWM) has been well-established power converter configuration for many industrial drives. The increasing costs on the utility usage, due to power quality regulations and the need to improve the fault tolerance characteristics and VA capacity of systems, have increased the interest in the development of power electronic equipment with power factor quality capability. Electrical motors consume a large amount of the available electrical energy and this energy tends to increase due to the massive emerging applications of electrical motor drives, in appliances and in industrial processes. Therefore, the improvement of the power factor of these low power drive systems, usually in the range from fractional horsepower to one horsepower is of particular interest. For these power ratings, the system configuration usually comprises a single-phase to three-phase type of converter with additional circuitry for power factor control and reduction of T.H.D. Single-phase to three-phase acdcac conversion usually employs a full-bridge topology. This system composed of two parallel singlephase rectifiers and a three-phase inverter and induction motor. The proposed system is
1

Introduction conceived to operate where the single-phase utility grid is the unique option available. Three such converter topologies, which use reduced number of switching devices, were presented along with their power factor control scheme. .
1.2 Motivation of Work:

In the present work a way to operate the motor and power factor control, reduction of total harmonic distortion has been presented by using a single phase to three-phase converter topology, which involves reduced number of switching devices. The proposed schemes were shown to achieve unity power factor operation at the supply side and high performance control of the motor drive system, etc. We will analyze the performance of a single-phase a.c to three phase a.c circuit with emphasis on the output harmonic content and utilization of input voltage. Parallel converters have been used to improve the power capability, reliability, efficiency, and redundancy. Also continuity of the power is obtained even though any one of the rectifier is failed.
1.3 Problem Definition:

Single phase to three phase ac-dc-ac conversion usually has the rectifier switching currents, the harmonic distortion at the input converter side. Discontinuity of the power is observed when a fault occurs across the rectifier.So these problems are minimised in the given system by using parallel converter techniques.
1.4 Scope of the project:

As switching currents are more at the input side, parallel converters technique has been used to reduce the switching currents. SVPWM technique has been used to reduce the T.H.D content. If one of the rectifiers is failed, Continuity of the power is observed by using parallel rectifiers.
1.5 Solution Technique:

parallel converter techniques has been employed for continuity of power for sharing of current between two parallel rectifiers, so that switching currents are reduced. PWM technique has been used to generate the gating pulses across the rectifier switches. SVPWM technique is used to reduce the T.H.D content in the overall system.

Introduction
1.6 Literature Overview:

High-Performance Speed-Sensorless Control of an Induction Motor Drive Using a Minimalist Single-Phase PWM Converter by Olorunfemi Ojo, Senior Member, IEEE, Zhiqiao Wu, Student Member, IEEE, Gan Dong, Student Member, IEEE, and Sheetal K. Asuri. Summary: Home appliances and comfort conditioners are yet to benefit from the recent developments in power electronics because of cost constraints. In this paper, a speedsensor less induction motor drive system using converters with reduced device counts (minimalist, sparse converters) and actuated from a single-phase system is proposed for such low-cost applications. The analysis, control, dynamic, and steady-state characteristics of the proposed drive are experimentally illustrated.

This paper has presented the methodology for the analysis and control of a highperformance induction motor drive actuated by two controlled rectifierinverter systems with reduced count of switching devices. The general approach for determining the modulation signals required for the carrier-based PWM pulse generation for this class of minimalist converters has been set forth. The input supply voltage is a single phase and the input current is controlled using a natural reference frame controller to operate close to unity displacement power factor. The nature of the modulation signals, the achievable motor dynamics, and waveforms are clearly layout in simulation results. Reduced Switch Count Multiple Three-Phase AC Machine Drive Systems by Cursino Brando Jacobina, Senior Member, IEEE, Euzeli Cipriano dos Santos, Jr., Student Member, IEEE, Edison Roberto Cabral da Silva, Fellow, IEEE, Mauricio Beltro de Rossiter Correa, Member, IEEE, Antonio Marcus Nigeria Lima, Senior Member, IEEE, and Talvanes Meneses Oliveira, Member, IEEE Summary: In this paper, two three-phase ac drive systems with reduced number of components, named configurations and, are investigated. Configuration uses multiple two-leg voltage source inverters in which all inverters share an extra-leg. Configuration also employs multiple two-leg inverters but in this case the inverters share the midpoint of a capacitor bank in the dc-link, instead. These configurations are compared to configuration that employs multiple three-leg inverters. The main characteristics of the

Introduction machine drive systems are presented together with selected experimental results that demonstrate the feasibility of the proposed configurations. Two components minimized multiple three-phase ac drive systems have been examined in this paper. Configuration uses multiple two-leg converter topologies in which all the inverters share an extra-leg. Configuration also uses multiple two-leg converter topologies but, instead, they share the midpoint of the capacitor bank of the dc-link. Configuration uses 1 legs and configuration uses 2 legs, while configuration demands 3 legs, where is the number of drives. The overall performance of configuration is superior to that of configuration because: 1) the lower THD; 2) the voltage capability that can be split among the inverters; 3) the fact that the machine voltages do not depend on the individual capacitor voltages; and 4) there is no ac fundamental current flowing through the dc-link capacitors. Configurations and require less power devices and consequently a less complex gating control circuitry. A Three-Phase Parallel Active Power Filter Operating With PCC Voltage Compensation with Consideration for an Unbalanced Load by Woo-Cheol Lee, TaeckKie Lee, and Dong-Seok Hyun, Senior Member, IEEE Summary: The performance and dynamic characteristics of a three-phase parallel active power filter (APF) with point of the common coupling (PCC) voltage compensation with consideration for an unbalanced load is presented and analyzed in this paper. The proposed scheme employs a pulse-width modulation (PWM) voltage-source inverter and has two operation modes. First, it operates as a conventional active filter with reactive power compensation when PCC voltage is within the 15% voltage drop range. Second, it operates as a voltage compensator when PCC voltage is not within the 15% voltage drop range. Both the APF and the voltage compensator compensate asymmetries caused by nonlinear loads. Finally, the validity of this scheme is investigated through the analysis of simulation and experimental results for a prototype APF system rated at 10kVA. So it can be conclude that three-phase parallel APF operating with PCC voltage compensation with consideration for an unbalanced load, and compared functions of an APF and a voltage compensator. The proposed scheme has two operation modes. First, it operates as an APF with reactive power compensation when PCC voltage is within the 15% voltage drop range. Second, when the PCC voltage is not within the 15% voltage drop range, it operates as a voltage compensator. In order to improve APF
4

Introduction performance, a dc voltage control loop was implemented with both the APF and the voltage compensator. Both the APF and the voltage compensator compensate asymmetries caused by nonlinear loads. This scheme will be used for critical industrial equipment like PLCs, HID and adjustable speed drives, and it may fail in situations where there are dramatic drops and harmonics in the PCC. To test the validity of the proposed scheme, simulation and experimental results were analyzed. Control of Circulating Current in Two Parallel Three-Phase Boost Rectifiers by Zhihong Ye, Member, IEEE, Dushan Boroyevich, Member, IEEE, Jae-Young Choi, Member, IEEE, and Fred C. Lee, Fellow, IEEE Summary: One unique feature in parallel three-phase converters is a potential zerosequence circulating current. To avoid the circulating current, most present technology uses isolation approach, such as transformers or separate power supplies. This paper proposes a parallel system where individual converters connect both ac and dc sides directly without additional passive components to reduce size and cost of the overall parallel system. In this case, the control of the circulating current becomes an important objective in the converter design. This paper 1) develops an averaged model of the parallel converters based on a phase-leg averaging technique; 2) a zero-sequence model is then developed to predict the dynamics of the zero-sequence current; 3) based on the zero-sequence model, this paper introduces a new control variable, which is associated with space-vector modulation; 4) a strong zero-sequence current control loop is designed to suppress the circulating current; 5) simulation and experimental results validate the developed model and the proposed control scheme. This work has developed an averaged model to predict zero sequence dynamics in two parallel three-phase boost rectifiers. To control the zero-sequence current, a new control variable associated with space-vector modulation was introduced. Since the zero-sequence dynamic is a first-order system, a high bandwidth control loop was designed to effectively suppress the circulating current. Both simulation and experimental results validated the proposed control scheme. The implementation requires only one additional current sensor. The control algorithm can be easily programmed in a digital signal processor (DSP).This modelling approach and control concept can be generalized for paralleling any two multi-phase converters, such as full bridge rectifiers and inverters, three-phase three-leg rectifiers and inverters, and three-

Introduction phase four-leg rectifiers and inverters. These converters cover most medium and high power applications, such as motor drives, ac power supplies and dc power supplies. Study on Ideal Operation Status of Parallel Inverters by Hui Cai, Rongxiang Zhao, and Huan Yang, Student Member, IEEE Summary: In order to keep a parallel inverter system operating stably, it is important to restrain the circulating current effectively. Based on the theoretical analysis, the limitation of a conventional conclusion about ideal operation status of parallel inverters is studied in detail. And then, the ideal operation status of the parallel inverter system is well investigated in this paper. A new criterion about ideal operation status of parallel inverters is concluded, i.e., there will be no circulating current among parallel inverters only when their output voltages have the same frequency, phase, amplitude and are also uniformly modulated. The concept of uniform modulation and the corresponding conclusion are verified by simulation and experimental results. The concept of uniform modulation for a parallel inverter system was introduced. A new conclusion about the ideal operation status of a parallel inverter system was concluded. Simulation and experimental results verified the theoretical analysis result and the proposed conclusion. The new conclusion is more complete to analyze the circulating current of a parallel inverter system. It also offers a new point of view to restrain the circulating current of the parallel inverter system. Shunt Active-Power-Filter Topology Based on Parallel Interleaved Inverters. by Lucian Asiminoaei, Member, IEEE, Eddy Aeloiza, Student Member, IEEE, Prasad N. Enjeti, Fellow, IEEE, and Frede Blaabjerg, Fellow, IEEE. Summary: In this paper, an interleaved active-power-filter concept with reduced size of passive components is discussed. The topology is composed of two pulse width modulation interleaved voltage-source inverters connected together on the ac line and sharing the same dc-link capacitor. The advantages of the proposed approach are as follows: 1) significant reduction in the linkage inductors size by decreasing the linecurrent ripple due to the interleaving; 2) reduction of the switching stress in the dc-link capacitor, due to the shared connection; and 3) more accurate compensation for highpower applications, because the power sharing allows one to use a higher switching frequency in each inverter. This paper analyzes the design of the passive components and gives a practical and low-cost solution for the minimization of the circulation
6

Introduction currents between the inverters, by using common-mode coils. Several simulation results are discussed, and experimental results with a three-phase 10-kVA 400-V unit are obtained to validate the theoretical analysis. This paper discussed the advantages of two inverters connected in parallel and sharing the same dc capacitor for reactive power and current-harmonic compensation. Design specification analysis shows that the values of the passive components are significantly reduced. The intrinsic modularity characteristic of the topology increases the reliability and makes it suitable for high-power applications. Simulation results and experiments validate the presented analysis. This paper concludes that the usage of smaller line inductors and the replacement of the isolation transformer with common mode coils gives lower costs and allows a faster response in tracking the harmoniccurrent reference, which makes the topology very attractive for high-power industrial APFs.

1-3 AC Conversion Methods Chapter 2

SINGLE PHASE A.C TO THREE PHASE A.C CONVERSION METHODS

2.1 Methods to Convert Single Phase to Three Phase Drive Systems: A wide variety of commercial and industrial electrical equipment requires three-phase power. Electric utilities do not install three-phase power as a matter of course because it costs significantly more than single-phase installation. As an alternative to utility installed three-phase, rotary phase converters, static phase converters and phase converting variable frequency drives (VFD) have been used for decades to generate three-phase power from a single-phase source. However these technologies have serious limitations, which motivated Phase Technologies, LLC to develop a new digital phase converter, Phase Perfect. This new patented technology overcomes the limitations of earlier phase converters, and is an affordable alternative to utility three-phase.
2.1.1 Rotary phase converter:

A rotary phase converter, abbreviated RPC, is an electrical machine that produces three-phase electric power from single-phase electric power. This allows three phase loads to run using generator or utility-supplied single-phase electric power. A rotary phase converter may be built as a motor-generator set. These have the advantage that in isolating the generated three-phase power from the single phase supply and balancing the three-phase output. However, due to weight, cost, and efficiency concerns, most RPCs are not built this way. Rotary Phase Converters Provide Reliable, Balanced, and Efficient Three Phase Power. All converters can be mainly categorized into two groups: one is cascade type and another is unified type. In cascade type, the PWM converter for power factor correction and the PWM inverter for speed control are connected in series with large DC-Link capacitor and two static power converters are operated and controlled in separate. In this type, specific number of switches, to compose the converter and inverter, are required. Therefore, the required number of switches cannot be reduced significantly. On the other hand, in the unified type, conventional concepts of PWM converter and inverter are merged together and same converter handles the functions of

1-3 AC Conversion Methods PWM converter (power factor correction) and PWM inverter(motor control) at the same time. As an added advantage, the input inductor, which is commonly used in the PWM converter for power factor correction, can be eliminated and replaced by the existing motor inductor. Therefore, this new concept can significantly reduce the number of components, compared to any conventional cascade type topologies.

Fig. 2.1. block diagram for rotary phase converter 2.1.2 Static Phase Converter:

Static Phase Convertor allows three phase motors to operate on single phase power Static Phase Converters operate by charging and discharging capacitors to temporarily produce a 3rd phase of power for only a matter of seconds during start up of electric motors, then it will drop out forcing the motor to continue to run on just 1 phase and only part of its windings. Due to their technology, Static Phase Converters do not properly power any class of 3 phase machinery or equipment. They will not in any way power 3 phase welders, 3 phase battery chargers, 3 phase lasers, or any type of machinery with 3 phase circuitry. Static Phase Converters also will not start delta wound 3 phase motors.
2.1.3 Phase Perfect Digital Phase Converter:

The Phase Perfect digital phase system is similar to static and rotary phase converters in that two of the phase leads to the load come directly from the power line. At that point the similarity ends. Power to generate the voltage for the third lead flows

1-3 AC Conversion Methods into the digital phase converter through an inductor and a set of semiconductor switches which feed a DC (constant voltage) link capacitor. The switches on the input can control the waveform of the input current and insure that it is sinusoidal, so as not to create harmonic distortion on the power grid. The DC link capacitor is connected to a second set of semiconductor switches which feed a second inductor and a filter capacitor to smooth out the high-frequency pulses created by the switches. The system is controlled by a small microcontroller, specifically a digital signal processor (DSP) which can measure voltages and feed controlled pulses into the switches, in addition to performing high-speed calculations. The DSP is constantly monitoring the system voltages and current to insure that the input current is sinusoidal, and the output voltage is also sinusoidal. The output voltage can be made equal in magnitude to the input voltage to an accuracy that is primarily determined by the measurement accuracy of the DSP. Typically, the line-line output voltages of Phase Perfect are balanced to within 1-2%. As the load on the system changes, the DSP senses any drop in the voltage and adjusts the pulses to the semiconductor switches to maintain this accuracy from no load up to full load. Any motor load or any combination of motors up to the maximum rating of the digital phase converter can be connected without creating unbalanced voltages. This is the first product to apply modern technology to the problem of phase conversion.

Fig 2.2. Block diagram of Phase Perfect Digital Phase Converter

2.2 Single-Phase to Three-Phase (1-3) Cycloconverters:

Recently, with the decrease in the size and the price of power electronics switches, single-phase to three-phase cycloconverters started drawing more research interest. Usually, an H bridge inverter produces a high frequency single-phase voltage waveform, which is fed to the cycloconverter either through a high frequency transformer or not. If a transformer is used, it isolates the inverter from the cycloconverter. In addition to this, additional taps from the transformer can be used to
10

1-3 AC Conversion Methods power other converters producing a high frequency ac link. The single-phase high frequency ac (HFAC) voltage can be either sinusoidal or trapezoidal. There might be zero voltage intervals for control purposes or zero voltage commutation.
2.2.1 Integral Pulse Modulated (1-3) Cycloconverters:

The input to these cycloconverters is single-phase high frequency sinusoidal or square waveforms with or without zero voltage gaps. Every half-cycle of the input signal, the control for each phase decides if it needs a positive pulse or a negative pulse using integral pulse modulation. For integral pulse modulation, the command signal and the output phase voltage are integrated and the latter result is subtracted from the former. For a positive difference, a negative pulse is required, and vice versa for the negative difference. For the positive (negative) input half-cycle, if a positive pulse is required, the upper (lower) switch is turned on; otherwise, the lower (upper) switch is turned on. Therefore, the three-phase output voltage consists of positive and negative halfcycle pulses of the input voltage. Note that this converter can only work at output frequencies which are multiples of the input frequency.

2.2.2 Phase-Controlled (1-3) Cycloconverter:

This cycloconverter converts the single-phase high frequency sinusoidal or square wave voltage into three-phase voltages using the previously explained phase control principles. The voltage command is compared to a saw tooth waveform to find the firing instant of the switches. Depending on the polarity of the current and the input voltage, the next switch to be turned on is determined. Compared to the previous one, this converter has more complex control but it can work at any frequency.

2.3 Single-Phase-to-Three-Phase AC/DC/AC PWM Converter:

Single phase to three-phase pulse width-modulation (PWM) converters for lowpower three-phase induction motor drives, where a single- phase half-bridge PWM rectifier and a two-leg inverter are used. The simplest circuit of an ac/dc/ac converter topology converting from a single-phase supply to a three-phase variable-voltage system is a single-phase full-bridge rectifier and a three-leg PWM inverter system. This converter gives excellent performance such as sinusoidal control of source current, unity power-factor control of the source side, constant dc voltage control, and
11

1-3 AC Conversion Methods bidirectional power flow. However, it requires ten active switching devices, so that it is more expensive than other circuits.

Fig. 2.3(a). Single-phase-to-three-phase ac/dc/ac PWM converter

Fig.2.3 (b) wave form of grid voltage & current

12

Control Strategies of Converters Chapter 3

CHARACTERISTICS OF INDUCTION MOTOR

Three-phase AC induction motors are widely used in industrial and commercial applications. They are classified either as squirrel cage or wound-rotor motors. These motors are self-starting and use no capacitor, start winding, centrifugal switch or other starting device. Almost 90% of the three-phase AC Induction motors are of Squirrelcage type.
3.1 Starting characteristics:

Induction motors, at rest, appear just like a short circuited transformer and if connected to the full supply voltage, draw a very high current known as the Locked Rotor Current. They also produce torque which is known as the Locked Rotor Torque. The Locked Rotor Torque (LRT) and the Locked Rotor Current (LRC) are a function of the terminal voltage of the motor and the motor design. As the motor accelerates, both the torque and the current will tend to alter with rotor speed if the voltage is maintained constant. The starting current of a motor with a fixed voltage will drop very slowly as the motor accelerates and will only begin to fall significantly when the motor has reached at least 80% of the full speed. The actual curves for the induction motors can vary considerably between designs but the general trend is for a high current until the motor has almost reached full speed. The LRC of a motor can range from 500% of Full-Load Current (FLC) to as high as 1400% of FLC. Typically, good motors fall in the range of 550% to 750% of FLC. The starting torque of an induction motor starting with a fixed voltage will drop a little to the minimum torque, known as the pull-up torque, as the motor accelerates and then rises to a maximum torque, known as the breakdown or pull-out torque, at almost full speed and then drop to zero at the synchronous speed. The curve of the start torque against the rotor speed is dependent on the terminal voltage and the rotor design. The LRT of an induction motor can vary from as low as 60% of FLT to as high as 350% of FLT. The pull-up torque can be as low as 40% of FLT and the breakdown torque can be as high as 350% of FLT. Typically, LRTs for medium to large motors are in the order of 120% of FLT to 280% of FLT. The PF of the motor at start is typically

13

Control Strategies of Converters 0.1-0.25, rising to a maximum as the motor accelerates and then falling again as the motor approaches full speed.

Fig. 3.1 Typical torque-speed curve of the three-phase induction motor

3.2 Running Characteristics:

Once the motor is up to speed, it operates at a low slip, at a speed determined by the number of the stator poles. Typically, the full-load slip for the squirrel cage induction motor is less than 5%. The actual full-load slip of a particular motor is dependent on the motor design. The typical base speed of the four pole induction motor varies between 1420 and 1480 RPM at 50 Hz, while the synchronous speed is 1500 RPM at 50 Hz. The current drawn by the induction motor has two components: reactive component (magnetizing current) and active component (working current). The magnetizing current is independent of the load but is dependent on the design of the stator and the stator voltage. The actual magnetizing current of the induction motor can vary, from as low as 20% of FLC for the large two pole machine, to as high as 60% for the small eight pole machine. The working current of the motor is directly proportional to the load. The tendency for the large machines and high-speed machines is to exhibit a low magnetizing current, while for the low-speed machines and small machines the tendency is to exhibit a high magnetizing current. A typical medium sized four pole machine has a magnetizing current of about 33% of FLC. A low magnetizing current

14

Control Strategies of Converters indicates a low iron loss, while a high magnetizing current indicates an increase in iron loss and a resultant reduction in the operating efficiency.
3.3 Load characteristics:

In real applications, various kinds of loads exist with different torque-speed curves. For example, Constant Torque, Variable Speed Load (screw compressors, conveyors, feeders), Variable Torque, Variable Speed Load (fan, pump), Constant Power Load (traction drives), Constant Power, Constant Torque Load (coiler drive) and High Starting/Breakaway Torque followed by Constant Torque Load (extruders, screw pumps). The motor load system is said to be stable when the developed motor torque is equal to the load torque requirement. The motor will operate in a steady state at a fixed speed. The response of the motor to any disturbance gives us an idea about the stability of the motor load system. This concept helps us in quickly evaluating the selection of a motor for driving a particular load.

Fig. 3.2 Torque-speed curves of the motor with two different loads

3.3.1 Constant Torque, Variable Speed Loads:

The torque required by this type of load is constant regardless of the speed. In contrast, the power is linearly proportional to the speed. Equipment, such as screw compressors, conveyors and feeders, has this type of characteristic.

15

Control Strategies of Converters


Fig 3.3. Constant Torque, Variable Speed Loads

3.3.2 Variable Torque, Variable Speed Loads:

This is most commonly found in the industry and sometimes is known as a quadratic torque load. The torque is the square of the speed, while the power is the cube of the speed. This is the typical torque-speed characteristic of a fan or a pump.

Fig 3.4. Variable Torque, Variable Speed Loads

3.3.3 Constant Power Loads:

This type of load is rare but is sometimes found in the industry. The power remains constant while the torque varies. The torque is inversely proportional to the speed, which theoretically means infinite torque at zero speed and zero torque at infinite speed. In practice, there is always a finite value to the breakaway torque required. This type of load is characteristic of the traction drives, which require high torque at low speeds for the initial acceleration and then a much reduced torque when at running speed.

Fig 3.5. Constant Power Loads

3.3.4 Constant Power, Constant Torque Loads:


16

Control Strategies of Converters This is common in the paper industry. In this type of load, as speed increases, the torque is constant with the power linearly increasing. When the torque starts to decrease, the power then remains constant.

Fig 3.6 Constant Power, Constant Torque Loads 3.3.5 High Starting/Breakaway Torque followed by Constant Torque:

This type of load is characterized by very high torque at relatively low frequencies. Typical applications include extruders and screw pumps.

Fig. 3.7. Relation between the Voltage and Torque versus Frequency

3.4. Induction motor characteristics in the proposed system:

17

Control Strategies of Converters


Fig 3.8(a) line-line voltage(V)

The above figure shows line-line voltage of three phase induction motor of a given input of 230V a.c to three phase inverter. It can be noticed that due to presence of harmonic content there exists a distortion in the wave form.

Fig 3.8(b) Three phase currents (A)

The above figure shows three phase currents obtained from given input current of 23A. Here in the induction motor the induced e.m.f in the rotor is very large, as a result a very high starting current is seen.

Fig 3.8(c) Rotor speed of induction motor in rad/sec

The above figure shows rotor speed obtained as 120 rad/sec for applied voltage of 230 a.c, the reference speed set for this induction motor is 120 rad/sec, it can be clearly observed that speed is maintained constant even though the input voltage is varied.

Fig 3.8(d) electromagnetic torque in N/m

18

Control Strategies of Converters The above figure shows electromagnetic in newton/metre, it can be observed that the starting torque is very much high in the interval t=0 to t=0.1 and it has come to steady state after t=0.1. The high starting torque is because it has to run high inertia load at starting time.

Power Frequency Speed Rotor Type Voltage(Line To Line) Stator Resistance(Rs) Stator Inductance(Lls) Rotor Resistance(Rr) Rotor Inductance(Llr) Mutual Inductance(Lm) Inertia(J) Reference Frame

2 hp, 230v 50hz 1425rpm Squirrel cage 230v 0.64ohms 0.21e-3h 0.26ohms 0.48e-3h 4e-3h 0.0226kg.m^2 Rotor

Table 1: Ratings of Induction Motor

The above table shows ratings of three phase induction motor for different parameters.

Chapter 4

CONTROL STRATEGIES OF CONVERTERS

4.1 Introduction:

At present, voltage source converters are mostly used in electrical drives. These converters utilize capacitors in the DC-link to store temporarily electrical energy.
19

Control Strategies of Converters Switching the power electronic devices allows the DC voltage to be modulated which can result in a variable voltage and frequency waveform. The purpose of the modulator is to generate the required switching signals for these switching devices on the basis of user defined inputs. For this purpose, the voltagetime integral was introduced, which in turn is tied to the average voltage per sample U(tk) that may be written as

(4.1) where Ts is a given sample interval and u(t) represents the instantaneous voltage across a single-phase of a load. The introduction of the variable Ts assumes the use of a fixed sampling frequency which is normally judicially chosen higher than the fundamental frequency range required to control electrical machines. The upper sampling frequency limit is constrained by the need to limit the switching losses of the converter semiconductor devices. The ability to control the converter devices in such a manner that the load is provided with a user defined mean reference voltage per sample U(tk) is instrumental to control current accurately. This statement can be made plausible by considering the incremental flux linkage for one sample interval of a load in the form of a coil with inductance L and resistance R which may be written as

(4.2) The corresponding incremental change of load current (over a sample interval Ts) may be written as in

(4.3) the event that magnetic saturation effects may be ignored. This expression can, with the aid of (4.3), be expressed as

(4.4) which may be reduced to

(4.5)
20

Control Strategies of Converters when the time constant = L/R of the load is deemed to be relatively large compared to Ts, as is normally the case for electrical machines. Central to the issue of controlling the incremental current is therefore, according to (4.5), the ability of the modulator to realize (within the constraint of this unit) the condition

(4.6) for each sampling instance. Note that (4.6) simply states that the switching states of the converter must be controlled by the modulator to ensure that the average voltage (per sample) equals the user defined average reference value to ensure that the actual and reference incremental current change (per sample interval) are equal. How this may be achieved will be outlined in subsequent sections for various converter topologies using an approach taken by Svensson. In effect, this approach considers how the average voltage per sample U(tk) varies as function of the converter switch on/off time within a sample interval. Once this relation is known for the converter under consideration, the function in question is compared with the user defined reference value to determine the converter switch state within each sample. Initially, a single-phase half-bridge converter, will be considered followed by an analysis of a single-phase full-bridge converter and three-phase converter.
4.2 Sinusoidal Pulse Width Modulation:

This is a method in which fixed dc input voltage is given to an inverter and the output is a controlled ac voltage. This is done by adjusting the on and off periods of the inverter components. The advantages of PWM control are: 1. No additional components are required with this method. 2. Lower order harmonics are eliminated or minimised along with its output voltage control. Hence, the filtering requirements are minimised since higher order harmonics can be filtered easily. If the half-cycle sine wave modulation, the triangular carrier only in a positive or negative polarity range of changes, the resulting SPWM wave only in a polar Range, called unipolar control mode. Figure 4.1(a) shows the unipolar and bipolar modulation of PWM pulses. If the half-cycle sine wave modulation, triangular carrier in continuous

21

Control Strategies of Converters change between positive and negative polarity, the SPWM wave is between positive and negative changes, known as bipolar control.

Fig. 4.1: Unipolar and bipolar modulation

The switches in the voltage source inverter (See Fig. 4.1(b)) can be turned on and off as required. In the simplest approach, the top switch is turned on If turned on and off only once in each cycle, a square wave waveform results. However, if turned on several times in a cycle an improved harmonic profile may be achieved. In the most straightforward implementation, generation of the desired output voltage is achieved by comparing the desired reference waveform (modulating signal) with a high-frequency triangular carrier wave as depicted schematically in Fig.4.2. Depending on whether the signal voltage is larger or smaller than the carrier waveform, either the positive or negative dc bus voltage is applied at the output. Note that over the period of one triangle wave, the average voltage applied to the load is proportional to the amplitude of the signal (assumed constant) during this period. The resulting chopped square waveform contains a replica of the desired waveform in its low frequency components, with the higher frequency components being at frequencies of an close to the carrier frequency.

Fig. 4.2: Simple Voltage Sourced Inverter

22

Control Strategies of Converters Notice that the root mean square value of the ac voltage waveform is still equal to the dc bus voltage, and hence the total harmonic distortion is not affected by the PWM process. The harmonic components are merely shifted into the higher frequency range and are automatically filtered due to inductances in the ac system. When the modulating signal is a sinusoid of amplitude Am, and the amplitude of the triangular carrier is Ac, the ratio m=Am/Ac is known as the modulation index. Note that controlling the modulation index therefor controls the amplitude of the applied output voltage. With a sufficiently high carrier frequency (see Fig. 4.3 drawn for fc/fm = 21 and t = L/R = T/3; T = period of fundamental), the high frequency components do not propagate significantly in the ac network (or load) due the presence of the inductive elements. However, a higher carrier frequency does result in a larger number of switchings per cycle and hence in an increased power loss. Typically switching frequencies in the 2-15 kHz range are considered adequate for power systems applications. Also in three-phase systems it is advisable to use so that all three waveforms are symmetric.

(4.7) Note that the process works well for m<1. For m>1, there are periods of the triangle wave in which there is no intersection of the carrier and the signal as in Fig.4.4. However, a certain amount of this over modulation is often allowed in the interest of obtaining a larger ac voltage magnitude even though the spectral content of the voltage is rendered somewhat poorer.

23

Control Strategies of Converters

Fig. 4.3: Principal of Pulse Width Modulation

Note that with an odd ratio for fc/fm, the waveform is anti-symmetric over a 360 degree cycle. With an even number, there are harmonics of even order, but in particular also a small dc component. Hence an even number is not recommended for single phase inverters, particularly for small ratios of fc/fm.

4.2.1 SPWM Spectra:

Although the SPWM waveform has harmonics of several orders in the phase voltage waveform, the dominant ones other than the fundamental are of order n and n2 where n = fc/fm. This is evident for the spectrum for n=15 and m = 0.8 shown in Fig.4.5. Note that if the other two phases are identically generated but 120o apart in phase, the line-line voltage will not have any triple n harmonics. Hence it is advisable to choose, as then the dominant harmonic will be eliminated. It is evident from Fig 4.5b, that the dominant 15th harmonic in Fig. 4.5 is effectively eliminated in the line voltage. Choosing a multiple of 3 is also convenient as then the same triangular waveform can be used as the carrier in all three phases, leading to some simplification in hardware. It is readily seen that as the where E is the dc bus voltage, that the rms value of the output voltage signal is unaffected by the PWM process.. However, the problematic harmonics

24

Control Strategies of Converters are shifted to higher orders, thereby making filtering much easier. Often, the filtering is carried out via the natural high-impedance characteristic of the load.

Fig. 4.4: SPWM Harmonic Spectra: n = 15, m =0.8

4.3 Space Vector PWM: 4.3.1 Principle of Space Vector PWM:

The circuit model of a typical three-phase voltage source PWM inverter is shown in Fig. 4.9. S1 to S6 are the six power switches that shape the output, which are controlled by the switching variables a, a, b, b, c and c. When an upper transistor is switched on, i.e., when a, b or c is 1, the corresponding lower transistor is switched off, i.e., the corresponding a, b or c is 0. Therefore, the on and off states of the upper transistors S1, S3 and S5 can be used to determine the output voltage.

25

Control Strategies of Converters


Fig. 4.5: Three-phase voltage source PWM Inverter

The relationship between the switching variable vector [a, b, c]t and the line-toline voltage vector [Vab Vbc Vca]t is given by (2.1) in the following:

(4.8) Also, the relationship between the switching variable vector [a, b, c]t and the phase voltage vector [Va Vb Vc]t can be expressed below.

(4.9) there are eight possible combinations of on and off patterns for the three upper power switches. The on and off states of the lower power devices are opposite to the upper one and so are easily determined once the states of the upper power transistors are determined. According to equations (4.8) and (4.9), the eight switching vectors, output line to neutral voltage (phase voltage), and output line-to-line voltages in terms of DC-link Vdc, are given in Table below which shows the eight inverter voltage vectors (V0 to V7).

26

Control Strategies of Converters


Table 2: Switching vectors, phase voltages and output line to line voltages

Fig. 4.6: The eight inverter voltage vectors (V0 to V7)

Space Vector PWM (SVPWM) refers to a special switching sequence of the upper three power transistors of a three-phase power inverter. It has been shown to generate less harmonic distortion in the output voltages and or currents applied to the phases of an AC motor and to provide more efficient use of supply voltage compared with sinusoidal modulation technique as shown in Fig. 4.11.

27

Control Strategies of Converters


Fig. 4.7: Locus comparison of maximum linear control voltage in Sine PWM and SVPWM.

To implement the space vector PWM, the voltage equations in the abc reference frame can be transformed into the stationary dq reference frame that consists of the horizontal (d) and vertical (q) axes as depicted in below Figure.

Fig. 4.8: The relationship of abc reference frame and stationary dq reference frame.

From this figure, the relation between these two reference frames is below

fdq0
where,

=K

sfabc

(4.10) f denotes either a voltage or a current variable. As described in above figure, the transformation is equivalent to an orthogonal projection of [a, b, c] t onto the two-dimensional perpendicular to the vector [1, 1, 1] t (the equivalent d-q plane) in a three-dimensional coordinate system. As a result, six non-zero vectors and two zero vectors are possible. Six nonzero vectors (V 1 - V6) shape the axes of a hexagonal as depicted and feed electric power to the load.

28

Control Strategies of Converters The angle between any adjacent two non-zero vectors is 60 degrees. Meanwhile, two zero vectors (V0 and V7) are at the origin and apply zero voltage to the load. The eight vectors are called the basic space vectors and are denoted by V0, V1, V2, V3, V4, V5, V6, and V7. The same transformation can be applied to the desired output voltage to get the desired reference voltage vector Vref in the d-q plane. The objective of space vector PWM technique is to approximate the reference voltage vector Vref using the eight switching patterns. One simple method of approximation is to generate the average output of the inverter in a small period, T to be the same as that of Vref in the same period.

Fig. 4.9: Basic switching vectors and sectors.

Therefore, space vector PWM can be implemented by the following steps: Step 1. Determine Vd, Vq, Vref, and angle () Step 2. Determine time duration T1, T2, T0 Step 3. Determine the switching time of each transistor (S1 to S6)

Step 1: Determine Vd, Vq, Vref, and angle ():


From Fig. 4.14, the Vd, Vq, Vref, and angle () can be determined as follows:

29

Control Strategies of Converters

(4.11)

(4.12)

(4.13)

where f = fundamental frequency

Step 2: Determine time duration T1, T2, T0:


From Fig. 4.15, the switching time duration can be calculated as follows: Switching time duration at Sector 1

(4.14)

30

Control Strategies of Converters

(4.15)

(4.16)

(4.17) Switching time duration at any Sector

(4.18)

Fig. 4.10: Reference vector as a combination of adjacent vectors at sector 1.

31

Control Strategies of Converters

Step 3: Determine the switching time of each transistor (S1 to S6):

(a) Sector 1.

(b) Sector 2.

(c) Sector 3.

(d) Sector 4.

(e) Sector 5.

(f) Sector 6.

Fig. 4.11: Space vector PWM switching patterns at each sector.

32

Control Strategies of Converters

Table 3: Switching Time Calculation at Each Sector

4.4. Vector Control technique:

This control is also known as the field oriented control, flux oriented control or indirect torque control. Using field orientation (Clarke-Park

transformation), three-phase current vectors are converted to a two-dimensional rotating reference frame (d-q) from a three-dimensional stationary reference frame. The d component represents the flux producing component of the stator current and the q component represents the torque producing component. These two decoupled components can be independently controlled by passing though separate PI controllers. The outputs of the PI controllers are transformed back to the three-dimensional stationary reference plane using the inverse of the Clarke-Park transformation. The corresponding switching pattern is pulse width modulated and implemented using the SVM. This control simulates a separately exited DC motor model, which provides an excellent torque-speed curve. The transformation from the stationary reference frame to the rotating reference frame is done and controlled with reference to a specific flux linkage space vector (stator flux linkage, rotor flux linkage or magnetizing flux

33

Control Strategies of Converters linkage). In general, there exists three possibilities for such selection and hence, three different vector controls. They are: Stator flux oriented control Rotor flux oriented control Magnetizing flux oriented control The most challenging and ultimately, the limiting feature of the field orientation, is the method whereby the flux angle is measured or estimated. Depending on the method of measurement, the vector control is divided into two subcategories: direct and indirect vector control. In direct vector control, the flux measurement is done by using the flux sensing coils or the Hall devices. This adds to additional hardware cost and in addition, measurement is not highly accurate. Therefore, this method is not a very good control technique. The more common method is indirect vector control. In this method, the flux angle is not measured directly, but is estimated from the equivalent circuit model and from measurements of the rotor speed, the stator current and the voltage.

Fig. 4.12: block diagram for vector control technique using direct torque and speed control

4.5 control circuits adopted in the system:

Two control circuits has been used, one for rectifier circuit using pwm technique and other for inverter using vector control technique, the details are as follows.

34

Control Strategies of Converters


4.5.1. Rectifier control circuit:

The dc-link voltage vc is adjusted to its reference value v*c using the controller Rc , which is a standard PI type controller. This controller provides the amplitude of the reference grid current Ig . To control power factor and harmonics in the grid side, the instantaneous reference current ig must be synchronized with voltage eg, as given in the voltage oriented control (VOC) for three-phase system. This is obtained via blocks GeIg, based on a PLL scheme. The reference currents i*a and i*b are obtained by making ia = ib = ig /2, which means that each rectifier receives half of the grid current. The control of the rectifier currents is implemented using the controllers indicated by blocks Ra and Rb . These controllers can be implemented using linear or nonlinear techniques. In this paper, the current control law is the same as that used in the two sequences synchronous controller described.

Fig. 4.13: control circuit for rectifier

4.5.2. Inverter control circuit:

In these control circuit speed reference has been taken from induction motor to generate the gating pulses across the inverter switches. To implement vector control the induction motor parameters must be known and values put into complex set of mathematical equations developed from generalized machine theory. Here speed controller generates a signal representing the demanded speed, and to drive a motor at that speed also voltage signal is generated by using three phase sequence analyzer
35

Control Strategies of Converters where the magnitude of the voltage is generated, in order to generate pulses this two phase transformation is changed to three phase transformation by using d-q axis of trigonometric functions i.e., 2 sint (where t= 0, 145, 270 degrees), thus three gating pulses are generated.

Fig.4.14: control circuit for inverter

4.5.3. pi controller:

Pi controller consists of two components 1) kp which is proportional to the error, it increases the loop gain of the sysytem 2) ki which is proportional to the integral of the error, it increases the order of the system and reduces the steady state error.

Fig 4.15: block diagram of pi controller

In the simulink circuit KP & Ki values chosen based on trial and error method.

36

Design Methodology of Proposed Converter

Chapter 5 DESIGN METHODOLOGY OF PROPOSED CONVERTER

5.1 Introduction:

In this chapter the conventional and proposed system is design and analysed. The circuit of conventional system ac-dc-ac is shown below in Fig. 5.1, which consists of rectifier, a three phase inverter and induction motor. The conventional system consists of total ten switches, a input inductor (Lg) and two capacitor banks.

Fig. 5.1: Conventional single-phase to three phase drive system

In the proposed system two parallel rectifiers, an inverter and induction motor has been used. The system consists of total fourteen switches i.e., qa1, qa1 , qa2 , and qa2 , and qb1, qb1, qb2 and qb2 of rectifier A & B, . The inverter is constituted of switches qs1, qs1, qs2, qs2, qs3 and qs3. The system is composed of grid, input inductors (La , La ,Lb , and Lb ), capacitor bank at the dc link. The conduction state of the switches is represented by variable sqa1 to sqs3, where sq = 1 indicates a closed switch while sq = 0 an open one. Four gating pulses has been given across to each two anti parallel switches in rectifier circuit by using pwm technique and three pulses have generated by using vector control across inverter where only one switch is on at upper leg lower leg at a instant.

37

Design Methodology of Proposed Converter

Fig. 5.2(a): Proposed single-phase to three phase drive system

The below figure shows the block diagram of proposed system where single phase a.c supply is converted to d.c by using a rectifier and by using a three phase inverter d.c is converted to three phase a.c to operate a three phase induction motor and also control circuits are designed in order to generate gating pulses across rectifier and inverter switches.

Control circuit

Rectifier A

+
Vdc

1ph ac supply
Rectifier B

3PH VSI

IM

Speed Ref

Parallel converters

Fig. 5.2(b): Block diagram of proposed single-phase to three phase drive system model

38

Design Methodology of Proposed Converter


5.2 Mathematical Modelling of the proposed system:

From Fig. 2, the following equations can be derived for the front-end rectifier, the below equations (5.1), (5.2), (5.3), (5.4), has been derived by applying kvl across four loops in proposed circuit. Here resistance is also taken in to consideration in the system.
5.2.1.Different modes/loops in the proposed system:

Here four different loops are considered for the designing of mathematical modelling of the proposed system.

Fig: 5.2.1(a): loop1 of the system model

By applying the kirchoff voltage law in the above loop, we get

(5.1) Where Va10 , va20 are pole voltages across switches qa1 and qa2 respectively, eg is the grid voltage ra, ra, la, la are the resistances and inductances across input side, Also ia, ia are currents across rectifier A.

39

Design Methodology of Proposed Converter

Fig: 5.2.1(b): loop2 of the system model

Similarly from the loop 2 we can get, (5.2) Where Vb10 , vb20 are pole voltages across switches qb1 and qb2 respectively, eg is the grid voltage rb, rb, lb, lb are the resistances and inductances across input side, ib and ib are currents in rectifier B.

Fig: 5.2.1(c): loop3 of the system model

(5.3) Where Va10 , Vb10 are pole voltages across switches qa1 and qb1 respectively, ra, rb, la, lb are the resistances and inductances across input side, ia and ib are currents in rectifier A and B respectively.
40

Design Methodology of Proposed Converter

Fig: 5.2.1(d): loop4 of the system model

(5.4)

Where Va20 , Vb20 are pole voltages across switches qa2 and qb2 respectively ra, rb, la, lb are the resistances and inductances across input side, , ia and ib are currents in rectifier A and B respectively. Where p = d/dt and symbols like r and l represent the resistances and inductances of the input inductors La, La, Lb, and Lb.

The grid current can be derived as, (5.5) The circulating current io can be defined from ia and ia or ib and ib , i.e., (5.6) Introducing io and adding (5.3) and (5.4), relations (5.1)(5.4) become (5.7) (5.8)

(5.9)

41

Design Methodology of Proposed Converter

Where (5.10) (5.11) (5.12) Relations (5.7)(5.9) and (5.5) constitute the front-end rectifier dynamic model. Therefore, va (rectifier A), vb (rectifier B), and vo (rectifiers A and B) are used to regulate currents ia, ib, and io, respectively. Reference currents ia and ib are chosen equal to ig /2 and the reference circulating current io is chosen equal to 0. In order to both facilitate the control and share equally current,voltage, and power between the rectifiers, the four inductors should be equal, i.e., rg = ra = ra = rb = rb and lg = la =la = lb = lb . In this case, the model (5.7)(5.9) can be simplified to the model given by

(5.13)

(5.14) (5.15) Additionally, the equations for ig , ia , and ib can be written as

(5.16)

(5.17)

(5.18) In this ideal case (four identical inductors), the circulating current can be reduced to zero imposing (5.19) When io = 0 (ia = ia , ib = ib ) the system model (5.7)(5.9) is reduced to

42

Design Methodology of Proposed Converter

(5.20) (5.21) Then, the model of the proposed system becomes similar to that of a system composed of two conventional independent rectifiers

5.3 PWM Strategy:

The inverter can be commanded by using an adequate pulse width modulation (PWM) strategy for three-phase voltage source inverter (VSI), so that it will not be discussed here. In this section, the PWM strategy for the rectifier will be presented. The rectifier pole voltages va10, va20, vb10, and vb20 depend on the conduction states of the power switches, i.e.,

(5.22) Where vc is the total dc-link voltage. Considering that va , vb , and vo denote the reference voltages determined by the current controllers ,we found (5.23) (5.24) (5.25) The gating signals are directly calculated from the reference pole voltages va10, va20, vb10, and vb20. However, (5.23)(5.25) are not sufficient to determine the four pole voltages uniquely from va, vb and vo. Introducing an auxiliary variable vx = va20, that equation plus the three equations (5.23)(5.25) constitute a four independent equations system with four variables (va10, va20, vb10, and vb20). Solving this system of equations, we obtain (5.26) (5.27)

(5.28)
43

Design Methodology of Proposed Converter

(5.29) From these equations, it can be seen that, besides va, vb and vo, the pole voltages depend on also of vx . The limit values of the variable vx can be calculated by taking into account the maximum vc /2 and minimum vc /2 value of the pole voltages

(5.30)

(5.31) Where vc is the reference dc-link voltages, vmax = max and vmin = min with = {va , 0, va/2 + vb /2 vo/2, va/2 vb /2 vo/2} Introducing a parameter (0 1), the variable vx can be written as (5.32) When = 0, = 0.5, and = 1 the auxiliary variable vx has the following values vx = vxmin, vx = vx have = (vxmin +vxmax)/2, and vx = vxmax, respectively. When vx = vxmin or vx = vxmax a converter leg operates with zero switching frequency. Once vx is chosen, pole voltages va10, va20, vb10, and vb20are defined from (5.26) to (5.29). The gating signals are obtained by comparing pole voltages with one (vt1), two (vt1 and vt2) or more high frequency triangular carrier signals. In the case of double-carrier approach, the phase shift of the two triangular carrier signals (vt1 and vt2) is 180 . The parameter changes the place of the voltage pulses related to va and vb . When vx = vxmin ( = 0) or vx = vxmax( = 1) are selected, the pulses are placed in the begin or in the end of the half period (Ts ) of the triangular carrier signal. On the other hand, when vx =vx have the pulses are centred in the half period of the carrier signal. The change of the position of the voltage pulses leads also to the change in the distribution of the zero instantaneous voltages (i.e., va = 0 and vb = 0).With = 0 or = 1 the zero instantaneous voltages are placed at the beginning or at the end of the switching period, respectively, while with = 0.5, they are distributed equally at the beginning and at the end of the half period. This is similar to the distribution of the
44

Design Methodology of Proposed Converter zero-voltage vector in the three-phase inverter. Consequently, influences the harmonic distortion of the voltages generated by the rectifier.

5.4 Control Strategy:

Fig. 5.3 presents the control block diagram of the system in Fig. 5.2, highlighting the control of the rectifier. The rectifier circuit of the proposed system has the same objectives of that in Fig. 5.1, i.e., to control the dc-link voltage and to guarantee the grid power factor close to one. Additionally, the circulating current io in the rectifier of the proposed system needs to be controlled. In this way, the dc-link voltage vc is adjusted to its reference value vc using the controller Rc , which is a standard PI type controller. This controller provides the amplitude of the reference grid current Ig . To control power factor and harmonics in the grid side, the instantaneous reference current ig must be synchronized with voltage eg , as given in the voltage oriented control (VOC) for three-phase system. This is obtained via blocks Ge-Ig, based on a PLL scheme. The reference currents i*a and i*b are obtained by making ia = ib = ig /2, which means that each rectifier receives half of the grid current. The control of the rectifier currents is implemented using the controllers indicated by blocks Ra and Rb . These controllers can be implemented using linear or nonlinear techniques. In this paper, the current control law is the same as that used in the two sequences synchronous controller described.

Fig. 5.3: Control Block Diagram for rectifier

These current controllers define the input reference voltages va and vb .The homopolar current is measured (io ) and compared to its reference (io = 0). The error is the input of PI controller Ro , that determines the voltage vo . The calculation of
45

Design Methodology of Proposed Converter voltage vx is given from (5.30) to (5.32) as a function of , selected as shown in the Section V. The motor there-phase voltages are supplied from the inverter (VSI). Block VSI-Ctr indicates the inverter and its control. The control system is composed of the PWM command and a torque/flux control strategy (e.g., field-oriented control or volts/hertz control).

5.5 Harmonic Distortion:

The harmonic distortion of the converter voltages has been evaluated by using the weighted THD (WTHD). It is computed by using

(5.33) where a1 is the amplitude of the fundamental voltage, ai is the amplitude of ith harmonic and p is the number of harmonics taken into consideration Fig. 4 shows the WTHD of voltages generated by rectifiers [vab = (va + vb )/2 for the proposed configuration and vg =vg10 vg20 for the conventional one] at rated grid voltage as a function of . Note that the parameter determines vx from (5.30) to (5.32). The resultant voltage vab generated by rectifier is responsible to control ig, which means that this voltage is used to regulate the harmonic distortion of the utility grid. When the single-carrier PWM is used, the behaviour of WTHD of the proposed system is similar to that of conventional one for all , as observed in Fig. 5.4. When the double-carrier PWM is used with = 0.5, the WTHD is also the same for both configurations. However, for the other values of the WTHD of the proposed system is lower than that of the conventional one. The WTHD of the proposed topology (doublecarrier with = 0 or = 1) is close to 63% of that of the conventional topology (with = 0.5). The study has also shown that it is possible to reduce the switching frequency of the proposed system in 60% and still have the same WTHD of the standard configuration.

46

Design Methodology of Proposed Converter

Fig. 5.4: WTHD of rectifier voltage (vab for proposed configuration and vg for standard configuration) as a function of .

The WTHD behaviour in Fig. 5.4 can be explained from Fig. 5.5. That figure depicts the pole voltages (va10, va20, vb10, vb20) and their references (va10, va20, vb10, vb20), the triangular carrier signals (vt1 , vt2 ), the resultant rectifier voltage (vab ) and the circulating voltage (vo ). Fig. 5.5(a) and (c) shows these variables with single-carrier (with = 1) and double-carrier (with =1), respectively. For the doublecarrier the voltage vab has smaller amplitude and better distribution along the half switching period than that of single-carrier, which means a lower WTHD (as observed in Fig. 5.4 for = 1). On the other hand, for = 0.5 the distribution of voltage vab along the switching period is the same for both cases, i.e., single-carrier and doublecarrier have the same WTHD (as observed in Fig. 4 for = 0.5). Besides the total harmonic distortion (THD) of the grid current ig , associated to the WTHD of the voltage vab , the harmonic distortion analysis must also consider the currents in the rectifiers. This is an important issue due to losses of the converter. The harmonic distortion of the rectifier currents (ia , ia , ib , and ib ) with double-carrier is higher than that of the grid current ig . When the parallel rectifier with double-carrier is used, the THD of all these currents are reduced for = 0 or = 1 and increased for = 0.5. On the other hand, the THD of the circulating current is also smaller with = 0 or = 1. Fig. 5.6 shows currents ia , ia , and io for double-carrier with = 1 and = 0.5.

47

Design Methodology of Proposed Converter It can be seen that the mean values of the ripples of all currents are smaller when = 1 is selected. In conclusion the optimal rectifier operation is obtained with double-carrier making = 0 or = 1. A four-carrier approach may also be used. Compared with the two-carrier strategy, the four-carrier strategy permits to reduce the harmonic distortion of the grid current, but increases the rectifier losses.

Fig. 5.5: Variables of rectifiers A and B. (a) Single-carrier with = 1. (b) Single-carrier with = 0.5. (c) Double-carrier with = 1. (d) Double carrier with = 0.5. 48

Design Methodology of Proposed Converter

Fig. 5.6: Currents ia , i_a , and io for double-carrier with = 1 and = 0.5.

5.6 Ratings of Switches:

Assuming same rms voltages at both grid and machine sides, a machine power factor of 0.85 and neglecting the converter losses, currents of the rectifier switches normalized in terms of currents of the inverter switches are 2.55 and 1.27 for the conventional and the proposed single-phase to three-phase converter, respectively. Fig. 5.7(a) and (b) shows the flow of active power in the conventional and in the proposed single-phase to three-phase converter, respectively. For balanced system (Lg =La = La = Lb = Lb ), voltage vo is close to zero, so that the dc-link voltage is equal to that required by the conventional system. Since the parallel connection scheme permits to reduce the switch currents and preserve the dc-link voltage, the rating of each power switch in the rectifier side is reduced.

49

Design Methodology of Proposed Converter

Fig. 5.7(a): Flow of active power in Conventional acdcac single-phase to three phase converter

Fig. 5.7(b): Flow of active power in proposed system with two rectifiers

5.7 DC-Link Capacitor Design:

The dc-link capacitor design and calculation carried out in this section.

The

voltage ripple over the dc capacitor is limited to an imposed maximum value of vmax. some simplified assumptions are considered such that the integration time interval (t1, t2) is half of the switching period Tsw and the dc current (Idc) is half of the peak value of the nominal line current. Then the minimum required dc capacitor is given by

50

Design Methodology of Proposed Converter Where idc and dc are current and voltage of the dc capacitor, respectively, Tsw is the switching period, and dc is the voltage ripple.

C=4.7mF

5.8 Input Inductors:

The design of input inductors is carried out in this section.

Where Vdc is the voltage on the dc capacitor and i is the amplitude of the cross-current developed during the interval t0, the Vdc obtained is 230V

LF= L= 5mH The THD of the grid current as a function of for different values of ln [the inductances of rectifiers A and B (lg ) referred to that of the conventional configuration (lg ), i.e., ln = lg /lg ]. For ln > 0.4 (lg > 0.4lg) the THD of the grid current of the proposed topology is smaller than that of the conventional topology.

51

Design Methodology of Proposed Converter

Fig. 5.8: Inductor specification in terms of THD of ig and .

5.9 Fault Compensation:

The proposed system presents redundancy of the rectifier converter, which can be useful in fault-tolerant systems. The proposed system can provide compensation for open-circuit and short-circuit failures occurring in the rectifier or inverter converter devices. The fault compensation is achieved by reconfiguring the power converter topology with the help of isolating devices (fast active fusesFj , j = 1, . . . , 7) and connecting devices (back-to-back connected SCRst1 , t2 , t3 ), as observed in Fig. 5.10(a). These devices are used to redefine the post-fault converter topology, which allows continuous operation of the drive after isolation of the faulty power switches in the converter. Fig. 5.10(b) presents the block diagram of the fault diagnosis system. In this figure, the block fault identification system (FIS) detects and locates the faulty switches, defining the leg to be isolated. This control system is based on the analysis of the pole voltage error. The fault detection and identification is carried out in four steps: 1) Measurement of pole voltages (vj0). 2) Computation of the voltage error j0 by comparison of reference voltages and measurements affected in Step 1). 3) Determination as to whether these errors correspond or not to a faulty condition; this can be implemented by the hysteresis detector shown in Fig. 5.10(b).

52

Design Methodology of Proposed Converter 4) Identification of the faulty switches by using j0.

Fig. 5.9(a): Proposed configuration highlighting devices of fault-tolerant system.

Fig.5.9 (b): Block diagram of the fault diagnosis system.

This way, four possibilities of configurations have been considered in terms of faults 1) Pre-fault (healthy) operation. 2) Post-fault operation with fault at the rectifier B 3) Post-fault operation with fault at the rectifier A. 4) Post-fault operation with fault at the inverter.

When the fault occurrence is detected and identified by the control system, the proposed system is reconfigured and becomes similar to that in Fig. 1. For instance, if a fault in any switch of rectifier A has been detected by the control system, the whole rectifier needs to be isolated.

53

Design Methodology of Proposed Converter

Fig. 5.10: Possibilities of configurations in terms of fault occurrence. (a) Pre-fault system. (b) Post-fault system with fault at the rectifier B. (c) Post-fault system with fault at the rectifier A. (d) Post-fault system with fault at the inverter.

This isolation procedure depends on the kind of fault detected. If an open-circuit failure is detected, the control system will open all switches of the rectifier A. On the other hand, if a short circuit is detected, the control system will turn on all switches related to rectifier A, and in this case, the fuses will open, and consequently, the rectifier will be isolated. Considering now a fault in one leg of inverter, in this case the SCR related with this leg in turned on and the leg b1 is isolated, so that the leg b2 of rectifier B will operate as the leg of inverter

5.10 Losses and Efficiency:

The evaluation of the rectifier losses is obtained through regression model presented. The switch loss model includes: 1) IGBT and diode conduction losses 2) IGBT turn-on losses 3) IGBT turn-off losses and 4) Diode turn-off energy.

54

Design Methodology of Proposed Converter The loss evaluation takes into account just the rectifier circuit, since the inverter side of converter is the same for the proposed and standard configurations. When the rectifiers operate with a switching frequency equal to 5 kHz, the conduction and switching losses of the proposed topology were 70% and 105%, respectively, of the corresponding losses of the conventional topology. Consequently, in this case, the total loss of the proposed topology was smaller than that of the conventional topology. The increase of the switching frequency does not change the conduction losses of both topologies, but increases their switching losses, especially for the proposed topology that has a high number of switches. The efficiency of the topologies operating with a switching frequency equal to 10 kHz and 5 kHz was evaluated by experimental measurement with a 2 kW load. Table Figure below shows the experimental results of the rectifier efficiency. Such results are obtained for the proposed system (p) normalized in terms conventional one (c), for three cases: 1) Both rectifiers operating at 10 kHz and Lg = Lg 2) Both rectifiers operating at 10 kHz and Lg = Lg /2 and 3) Both rectifiers operating at 5 kHz and Lg = Lg. Three strategies are considered in terms of PWM control: 1) Single-carrier with = 0.5 (S-Ca = 0.5) 2) Double-carrier with = 0.5 (D-Ca = 0.5) and 3) Double carrier with = 0 (D-Ca = 0). For case 1) the proposed configuration with double-carrier and = 0 have its efficiency slightly smaller than that of the conventional one, but with the other PWM strategies its efficiency is clearly inferior. In the other cases, the proposed configuration with double-carrier and = 0 presents higher efficiency than the conventional one.

Table 3: Efficiency of the Proposed System Normalized In Terms Conventional One

55

Design Methodology of Proposed Converter


5.11 Costs and Applications of Configuration:

The initial investment of the proposed system is higher than that of the standard one, since the number of switches and devices such as fuses and triacs is highest. But, considering the scenario when faults may occur, the drive operation needs to be stopped for a non-programmed maintenance schedule. The cost of this schedule can be high and this justifies the high initial investment inherent of fault-tolerant motor drive systems. On the other hand, the initial investment can be justified if the THD or losses of the conventional system is a critical factor. Furthermore, the cost of power switches has decreased substantially. This permits to employ extra switches without increasing the final price of converter dramatically The proposed system can be used in the same applications as the conventional configuration (rural or remote application), especially when the THD of the grid current, fault tolerance and efficiency of converter are critical issues. In Brazil, it is quite common to have a single-phase distribution system and a demand to supply a three-phase motor. A single-phase to three phase converter with bidirectional flux in the rectifier circuit has been required in the distributed generation system.
5.12 pulse train of control circuits of rectifier and inverter switches:

Fig 5.11(a) pulse trainee of rectifier control circuit

The above figure shows four generated pulse signals of qa1, qa2, qb1, qb2 for rectifier switches.

56

Design Methodology of Proposed Converter

Fig 5.11(b) pulse train for inverter switches

The above figure shows pulse train signals for inverter switches

57

Simulation and result discussion


Chapter 6 SIMULATION AND RESULT DISCUSSION

6.1 Simulation Results for 110V AC: 6.1.1 Simulation of Conventional Model:

Fig. 6.1: Simulink model of conventional system

The above figure shows the matlab/simulink model of the conventional system with single rectifier and three phase inverter.

Fig. 6.2: Wave forms of grid input voltage & current

The above figure shows the input side grid voltage of 110 Volts and grid current of 10 Amps which are in phase, so that the power factor is close to unity.
58

Simulation and result discussion

Fig. 6.3: Wave form of DC-Link capacitor voltage

The above figure shows constant capacitor voltage of 230 V d.c across dc link capacitors for a given input voltage of 110V a.c at the grid side, it can be seen that small amount of dc link ripple component exists in the above waveform.

Fig. 6.4: Wave form of current in rectifier A

The above figure shows the input currents i'a of 4 Amps and along with their dutycycles which is pure sinusoidal.

59

Simulation and result discussion

Fig. 6.5: Wave form of output line voltage

The above figure shows the synthesized three-phase balanced line to line voltage of 125V obtained from input of 230V d.c to the three phase inverter. However, there still exist some distortion and unbalance due to low speed at starting.

Fig. 6.6: THD content at input current is 19.36%

The above figure shows harmonic content of 19.35% at the input current side for the conventional system.

60

Simulation and result discussion


6.1.2 Simulation of Proposed Model:

Fig. 6.7: Simulink model of proposed system

The above figure shows the matlab/simulink model of the two single phase rectifiers connected in parallel which is controlled by a control strategy which helps in controlling the DC link voltage, controls the circulating current io in the rectifier and guarantees the grid power factor to be close to unity. The system is connected to a three phase drive system with the help of an inverter.

Fig. 6.8: Simulink model of control circuit for rectifier

61

Simulation and result discussion

The above figure shows Matlab /simulink model of rectifier control circuit where voltage Vc ic adjusted to its reference value V*c using pi controller.

Fig. 6.9: Simulink model of control circuit for inverter

The above figure shows Matlab /simulink model of inverter control circuit where speed and torque is taken as reference from induction motor

Fig. 6.10: Wave forms of grid input voltage & current

The above figure shows the input side grid voltage of 110 Volts and grid current of 10 Amps which are in phase, so that the power factor is nearly to unity.

62

Simulation and result discussion

Fig. 6.11: Wave form of DC-Link capacitor voltage

The above figure shows constant capacitor voltage of 230 Volts across dc link capacitors obtained from 110V a.c supply, it can be seen that small amount of dc link ripple component exists in the above waveform.

Fig. 6.12: Wave form of circulating current

The above figure shows circulating current which is close to zero, this current circulates in the system itself and doesnt goes to load, so these current made to zero.

63

Simulation and result discussion

Fig. 6.13: Wave forms of currents in rectifier A & B

The above figure shows the input currents of rectifier ia & ib of 4 Amps each and along with their duty-cycles. It can be noticed that the currents are sinusoidal of equal magnitude, this is due to modulation index(1/2) given in the control circuit for sharing of equal currents from the total input current of 8A between two rectifiers.

6.1.1.1 Simulation results of Proposed Model when a fault is identified at rectifier B:

Fig. 6.14: Wave forms of grid voltage & current in fault condition

The above figure shows grid voltage and grid current which are in phase and also there is a variation in waveforms due to failure of rectifier B
64

Simulation and result discussion

Fig. 6.15: Wave forms currents in rectifier A & B in fault condition

The above figure shows rectifier currents of rectifier ia & ib, it can be observed the current ib is zero at interval 0.2, because of failure of rectifier B.

Fig. 6.16: Wave forms currents in rectifier A & B in fault condition

The above figure shows rectifier currents of rectifier ia & ib, it can be observed the current ib is zero at interval 0.2,because of failure of rectifier B and then the fault is isolated at interval 0.6. By using a clock signal the time period of fault is adjusted intentionally by using circuit breaker.
65

Simulation and result discussion

Fig. 6.17: THD content at input current using SPWM Technique is 9.24%

The above figure shows harmonic content of 9.24% at the input current side for the proposed system by using SPWM Technique.

Fig. 6.18: THD content at input current using SVPWM Technique is 4.55%

The above figure shows harmonic content of 4.55% at the input current side for the proposed system by using SVPWM Technique.
66

Simulation and result discussion

Fig. 6.19: THD content at output voltage using SPWM Technique is 14.84%

The above figure shows harmonic content of 14.84% at the output voltage side for the conventional system by using SPWM Technique.

Fig. 6.20: THD content at output voltage using SVPWM Technique is 12.90%

The above figure shows harmonic content of 12.90% at the output voltage side for the proposed system by using SPWM Technique.

67

Simulation and result discussion

Parameters

Conventional System 7.831 Amps 110 Volts 0.937 608.4 Watts 19.35% 7.8Amps 6.1 Watts 121.24 Volts 4.023 Amps 487.76 Watts 80.17%

Proposed System SPWM SVPWM 5.35 Amps 110 Volts 0.996 415.69 Watts 4.55% 6.3 Amps 3.9 Watts 121.24 Volts 3.3 Amps 400.54Watts 96.25%

Input Current Input Voltage Power Factor Input Power Total Harmonic Distortion Current through Switch Power Loss across switch Output Voltage Output Current Output Power Efficiency

5.518 Amps 110 Volts 0.989 428.7 Watts 9.24% 6.8 Amps 4.6 Watts 121.24 Volts 3.28 Amps 398.22 Watts 92.89%

Table 4: Comparison of conventional and proposed systems

The above table shows comparison between conventional and proposed (with spwm and svpwm) system, it can be clearly noticed that the total harmonic distortion is reduced from 19.35% to 4.55% and improvement in power factor (0.937 t0 0.996) and efficiency (80.17% to 96.25%).

6.2 Simulation Results for 230V AC: 6.2.1 Simulation of Conventional Model:

Fig.6.21: Wave forms of grid input voltage & current

68

Simulation and result discussion

The above figure shows the input side grid voltage of 230 Volts and grid current of 24 Amps which are in phase, so that the power factor is nearly unity.

Fig. 6.22: Wave form of current in rectifier A

The above figure shows the input current of rectifier ia of 22 Amps which is sinusoidal and along with their duty-cycles.

Fig. 6.23: Wave form of DC-Link capacitor voltage

The above figure shows constant capacitor voltage of 440 Volts across dc link capacitors obtained from 230V a.c supply, it can be seen that small amount of dc link ripple component exists in the above waveform.
69

Simulation and result discussion

6.2.2 Simulation of proposed Model:

Fig. 6.24: Wave forms of currents in rectifier A & B

The above figure shows the input currents of rectifier ia & ib of 13 Amps each and along with their duty-cycles. It can be noticed that the currents are sinusoidal of equal magnitude, this is due to modulation index(1/2) given in the control circuit for sharing of equal currents from the total input current of 23A between two rectifiers

Fig. 6.25: Wave form of output line voltage

The above figure shows the synthesized three-phase balanced line to line voltage of 230V obtained from input of 440V d.c to the three phase inverter. However, there still exist some distortion and unbalance due to low speed at starting.
70

Simulation and result discussion

Fig. 6.26: Wave form of circulating current

The above figure shows above shows circulating current which is close to zero, this current circulates in the system itself and doesnt goes to load, so these current is made to zero.

Fig. 6.27: Wave form of DC-Link capacitor voltage

The above figure shows constant capacitor voltage of 440 Volts across dc link capacitors obtained from 230V a.c supply, it can be seen that small amount of dc link ripple component exists in the above waveform.

71

Simulation and result discussion

Fig. 6.28: THD content at input current using SVPWM Technique of 4.02%

The above figure shows harmonic content of 4.02% at the input side for the proposed system by using SVPWM Technique

Fig. 6.29: THD content at input current using SPWM technique of 8.12%

The above figure shows harmonic content of 8.12% at the input side for the proposed system by using SPWM Technique.

72

Simulation and result discussion

Fig. 6.30: THD content at output voltage with SPWM technique of 15.34%

The above figure shows harmonic content of 15.34% at the output voltage side for the proposed system by using SPWM Technique.

Fig. 6.31: THD content at output voltage with SVPWM technique of 10.26%

The above figure shows harmonic content of 10.26% at the output voltage side for the proposed system by using SVPWM Technique.

73

Simulation and result discussion

Table 5: Comparison of conventional and proposed systems

Parameters Input Current Input Voltage Power Factor Input Power Total Harmonic Distortion Current through Switches Power Loss across switches Output Voltage Output Current Output Power Efficiency

Conventional System 25.96 Amps 230 Volts 0.937 3226.6 Watts 19.32% 12.98Amps 16.84 Watts 440 Volts 11.66 Amps 2794.37 Watts 86.67%

Proposed System SPWM 20.15 Amps 230 Volts 0.989 2646.29 Watts 15.82% 10.7 Amps 11.45 Watts 440 Volts 9.5 Amps 2413.32 Watts 91.96% SVPWM 18.05 Amps 230 Volts 0.996 2390.23 Watts 4.55% 9 Amps 8.1 Watts 440 Volts 8.945 Amps 2260.90Watts 94.6%

The above table shows comparison between conventional and proposed (with spwm and svpwm) system, it can be clearly noticed that the total harmonic distortion is reduced from 19.32% to 4.55% and improvement in power factor (0.937 to 0.996) and efficiency (86.67% to 96.25%).

Table 6: Distribution of currents for different values of modulation index

Modulation index() 0.2 0.4 0.5 0.7 0.9

Current of rectifier A (ia) 18.4 Amps 13.8 Amps 11.5 Amps 6.9 Amps 2.3 Amps

Current of rectifier B (ib) 4.6 Amps 9.2 Amps 11.5 Amps 16.1 Amps 20.7Amps

Table above shows sharing of input current (23Amps) between rectifier A and rectifier B which are connected in parallel.
74

Conclusion and Future Scope


Chapter 7 CONCLUSION AND FUTURE SCOPE

Conclusion:

The system model and a suitable control strategy, including the pulse width modulation technique (PWM), is developed. Parallel converters have been used to improve the power capability, reliability, efficiency, and redundancy and other advantage is parallel connection scheme permits to reduce the switching currents and therefore rating of power in each switch of the rectifier side is reduced, hence continuity of the power is observed. The system combines two parallel rectifiers without the use of transformers. The complete comparison between the proposed and standard configurations has been carried out in this project. The proposed topology permits to reduce the total harmonic distortion and current and consequently to reduce the power ratings of the power switches of the rectifier. Compared to the conventional topology, the proposed system permits to reduce the rectifier switch currents, the THD of the grid current and THD across output side and to increase the fault tolerance characteristics. In addition, the losses of the proposed system is lower than that of the conventional system.

Future Scope:

Parallel converter techniques can be employed to improve the performance of active power filters uninterruptible power supplies (UPS), fault tolerance of doubly fed induction generators, and three-phase drives. To achieve even less %THD and to improve the dc bus utilisation advanced inverter topologies (multilevel inverters, multi-cell inverters) with advanced modulation and control techniques can be used. The speed control of three phase induction motor can be done more precisely, % THD and dc bus utilisation can be improved if the control strategy if the inverter is changed to DPWM (discontinuous pulse width modulation) techniques.

75

Bibliography

Chapter 8 BIBLIOGRAPHY

[1] P. Enjeti and A. Rahman, A new single phase to three phase converter with active input current shaping for low cost AC motor drives, IEEE Trans. Ind. Appl., vol. 29, no. 2, pp. 806813, Jul./Aug. 1993. [2] J. Itoh and K. Fujita, Novel unity power factor circuits using zero-vector control for single-phase input systems, IEEE Trans. Power Electron., vol. 15, no. 1, pp. 3643, Jan. 2000. [3] B.K. Lee, B. Fahimi, and M. Ehsani, Overviewof reduced parts converter topologies for AC motor drives, in Proc. IEEE PESC, 2001, pp. 2019 2024. [4] C. B. Jacobina, M. B. de R. Correa,A.M. N. Lima, and E. R. C. da Silva, AC motor drive systems with a reduced switch count converter, IEEE Trans. Ind. Appl., vol. 39, no. 5, pp. 13331342, Sep./Oct. 2003. [5] R. Q. Machado, S. Buso, and J. A. Pomilio, A line-interactive singlephase to three-phase converter system, IEEE Trans. Power Electron., vol. 21, no. 6, pp. 16281636, May 2006. [6] O. Ojo, W. Zhiqiao, G. Dong, and S. Asuri, High-performance speedsensorless control of an induction motor drive using a minimalist singlephase PWM converter, IEEE Trans. Ind. Appl., vol. 41, no. 4, pp. 996 1004, Jul./Aug. 2005. [7] J. R. Rodrguez, J. W. Dixon, J. R. Espinoza, J. Pontt, and P. Lezana, PWMregenerative rectifiers: State of the art, IEEE Trans. Ind. Electron., vol. 52, no. 1, pp. 522, Feb. 2005. [8] M. N. Uddin, T. S. Radwan, and M. A. Rahman, Fuzzy-logic controller-based cost-effective four-switch three-phase inverter-fed IPM pp. 2130, Jan./Feb. 2006. [9] D.-C. Lee and Y.-S. Kim, Control of single-phase-to-three-phase AC/DC/AC PWM converters for induction motor drives, IEEE Trans. Ind. Electron., vol. 54, no. 2, pp. 797804, Apr. 2007.`

76

S-ar putea să vă placă și