PLC Connection Guide

Rockwell PLC5
Website: http://www.ab.com

HMI Setting:
Parameters PLC type PLC I/F Baud rate Data bits Parity Stop bits HMI sta. no. PLC sta. no. Recommended Allen-Bradley PLC5 RS232 19200 8 Even 1 0 1 1-31 9600, 19200 8 Even, Odd, None 1 Options Notes

PLC Setting:
Communication mode DF1 Full Duplex protocol 19200, None, 8, 1 (default)

Allen-Bradley PLC-5 Family PLCs use DF1 Full Duplex protocol. For PLC-5/10, PLC-5/15 and PLC-5/25, MT8000 should be connected to the DF1 port on the 1785-KE module. For PLC-5/11, PLC-5/20, PLC-5/30 and PLC-5/40, MT8000 should be connected to the Channel 0 Port on the PLC.

Device Address:
Bit/Word Device type Format B B B B B B B W I1 O0 B3 B10 ~ 13 S_Bit Bfn NfnBit T4SV DDDdd DDDdd DDDdd DDDdd FFFDDDdd FFFDDDdd DDD Range 0 ~ 25515 0 ~ 25515 0 ~ 99915 0 ~ 99915 0 ~ 25599915 0 ~ 25599915 0 ~ 999
Timer Preset Value (T4)

Memo
Input (I) Output (O) Bit data file (B3) Bit data file (B10 ~ 13)

DDDDDDdd 0 ~ 25599915

PLC Connection Guide

Bit/Word Device type Format W W W W W W W W W W W W W T4PV C5SV C5PV TfnSV TfnPV CfnSV CfnPV N7 N10 ~ 15 Nfn S F8 Ffn DDD DDD DDD FFFDDD FFFDDD FFFDDD FFFDDD DDD DDD FFFDDD DDD DDD FFFDDD

Range 0 ~ 999 0 ~ 999 0 ~ 999 0 ~ 255999 0 ~ 255999 0 ~ 255999 0 ~ 255999 0 ~ 999 0 ~ 999 0 ~ 255999 0 ~ 255 0 ~ 999 0 ~ 255999

Memo
Timer Accumulator Value (T4) Counter Preset Value (C5) Counter Accumulator Value (C5)

Integer data file (N7) Integer data file (N10 ~ 15) Integer data file (V2.5.0 or newer)

Floating point data file (F8) Floating point data file (V2.5.0 or newer)

Wiring Diagram:
The following is the view from the soldering point of a cable. 9P D-Sub to 25P D-Sub: PLC5 CPU CH0 eMT3000 series COM1 RS232 9P D-Sub Female 2 RX 3 TX 5 GND COM3 RS232 9P D-Sub Female 8 RX 7 TX 5 GND AB CPU CH0 RS232 25P D-Sub Male 3 TD 2 RD 7 GND

cMT series COM1 RS232 9P D-Sub Female 2 RX 3 TX 5 GND AB CPU CH0 RS232 25P D-Sub Male 3 TD 2 RD 7 GND

PLC Connection Guide

MT8000iE series COM1 RS232 9P D-Sub Female 2 RX 3 TX 5 GND AB CPU CH0 RS232 25P D-Sub Male 3 TD 2 RD 7 GND

MT6000/8000 series except MT6050i/MT8050i COM1 RS232 9P D-Sub Female 2 RX 3 TX 5 GND COM2 RS232 9P D-Sub Female 6 RX 4 TX 5 GND COM3 RS232 9P D-Sub Male 8 RX 7 TX 5 GND AB CPU CH0 RS232 25P D-Sub Male 3 TD 2 RD 7 GND

MT6050i/MT8050i COM1 RS232 9P D-Sub Female 9 RX 6 TX 5 GND AB CPU CH0 RS232 25P D-Sub Male 3 TD 2 RD 7 GND

PLC Connection Guide

Note:
The default error checking of Rockwell PLC5 is BCC, whereas our driver is CRC.

Access [Channel Configuration] from RSLogix5, under Channel 0 tab, please select CRC for [Error Detect].

PLC Connection Guide