Setting Brush MICROTRIP Recloser Controllers in the Computer-Aided Protection Engineering System (CAPE)

Prepared for CAPE Users' Group

June 20-21, 2000

Electrocon International, Inc. Ann Arbor, Michigan

Georgia Power Company Atlanta, Georgia

This document is the sole property of Electrocon International, Inc. and is provided to the CAPE Users Group for its own use only. It may not be supplied to any third party, or copied or reproduced in any form, without the express written permission of Electrocon International, Inc. All copies and reproductions shall be the property of Electrocon International, Inc. and must bear this ownership statement in its entirety.

Application Notes on Setting Brush MICROTRIP Recloser Controllers I. Recloser Models

This is a summary of the data a CAPE user must provide for the Brush MICROTRIP recloser controller. Typical STYLE used in CAPE is as follows: Style MICROTRIP Properties General purpose controller style for model MICROTRIP, suitable for use with all applicable recloser switchgear.

For details of the recloser, refer to the description in the Brush Instruction Manual No55/4118. II. Recloser Elements

The recloser contains phase and ground overcurrent elements, with separate settings possible for quick and delayed trip. Element Ground CLP Ground TCC1 Ground TCC2 Ground TCC3 Ground TCC4 Phase CLP Phase TCC1 Phase TCC2 Phase TCC3 Phase TCC4 SEF TCC1 SEF TCC2 SEF TCC3 SEF TCC4 III. Description Ground operation Cold Load Pickup Ground operation 1st trip Ground operation 2nd trip Ground operation 3rd trip Ground operation 4th trip Phase operation Cold Load Pickup Phase operation 1st trip Phase operation 2nd trip Phase operation 3rd trip Phase operation 4th trip Sensitive Earth Fault 1st trip Sensitive Earth Fault 2nd trip Sensitive Earth Fault 3rd trip Sensitive Earth Fault 4th trip

Overcurrent Timing Curves

There are a number of timing curves available, all of which are included in the text tap range named MICROTRIP Curves. The following table lists the curves included:

Curve ID SI VI EI Df Ds 1 2 3 4 5 6 7 8* 8 9 11 13 14 15 16 18 IV.

Description Standard Inverse Very Inverse Extremely Inverse 1 Second Definite Time Trip 10 Second Definite Time Trip McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve McGraw Ground Curve

Curve ID A B C D E KP L M N P R T V W Y Z

Description McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve McGraw Phase Curve

Recloser Taps

When placing a recloser, set the following taps. Only the settings with Internal Name shown in bold are actually used in the Program Model for this recloser. Tap Name
Auto-Reclose Earth/Ground Fault Phase Trips to Lockout Residual Trips to Lockout SEF Trips to Lockout Dead Time - 1st Dead Time - 2nd

Internal Name
AUTO_RCLS GND_PROT PHS_LO_NUM GND_LO_NUM SEF_LO_NUM RECLOSE_1 RECLOSE_2

Tap Descriptions
IN/OUT 1 4 1 4 1 4 1 4, OUT 0.25 180.0 sec 0.25 180.0 sec

Dead Time - 3rd Reclaim Time Sequence Coordination Cold Load Pickup CT Ratio Phase Minimum Trip Residual Minimum Trip SEF Minimum Trip Phase Time Multiplier 1 Phase Curve 1 Phase Time Multiplier 2 Phase Curve 2 Phase Time Multiplier 3 Phase Curve 3 Phase Time Multiplier 4 Phase Curve 4 Phase Additional Delay 1 Phase Additional Delay 2 Phase Additional Delay 3 Phase Additional Delay 4 Phase Min. Response Time 1 Phase Min. Response Time 2 Phase Min. Response Time 3 Phase Min. Response Time 4 Phase Inst Override 1 Phase Inst Override 2 Phase Inst Override 3 Phase Inst Override 4 Phase Inst Delay 1 Phase Inst Delay 2 Phase Inst Delay 3 Phase Inst Delay 4 Residual Time Multiplier 1 Residual Curve 1 Residual Time Multiplier 2 Residual Curve 2 Residual Time Multiplier 3 Residual Curve 3

RECLOSE_3 RESET_TIME SEQ_COORD CLP_PROT CT_RATIO PHS_MIN_TRIP GND_MIN_TRIP SEF_MIN_TRIP PHS_TCC1_TMULT PHS_TCC1_ID PHS_TCC2_TMULT PHS_TCC2_ID PHS_TCC3_TMULT PHS_TCC3_ID PHS_TCC4_TMULT PHS_TCC4_ID PHS_TCC1_ADDER PHS_TCC2_ADDER PHS_TCC3_ADDER PHS_TCC4_ADDER PHS_TCC1_TMIN PHS_TCC2_TMIN PHS_TCC3_TMIN PHS_TCC4_TMIN PHS_TCC1_INST_MULT PHS_TCC2_INST_MULT PHS_TCC3_INST_MULT PHS_TCC4_INST_MULT PHS_TCC1_INST_DELAY PHS_TCC2_INST_DELAY PHS_TCC3_INST_DELAY PHS_TCC4_INST_DELAY GND_TCC1_TMULT GND_TCC1_ID GND_TCC2_TMULT GND_TCC2_ID GND_TCC3_TMULT GND_TCC3_ID

0.25 180.0 sec 5 180 sec IN/OUT IN/OUT 560:1 50:1 20 240 % 10 120 % 1 8 % 0.10 2.00 MICROTRIP Curves 0.10 2.00 MICROTRIP Curves 0.10 2.00 MICROTRIP Curves 0.10 2.00 MICROTRIP Curves 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 1.0 0 20.0 X, OUT 1.0 0 20.0 X, OUT 1.0 0 20.0 X, OUT 1.0 0 20.0 X, OUT 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.10 2.00 MICROTRIP Curves 0.10 2.00 MICROTRIP Curves 0.10 2.00 MICROTRIP Curves

Residual Time Multiplier 4 Residual Curve 4 Residual Additional Delay 1 Residual Additional Delay 2 Residual Additional Delay 3 Residual Additional Delay 4 Residual Min. Response Time 1 Residual Min. Response Time 2 Residual Min. Response Time 3 Residual Min. Response Time 4 Residual Inst Override 1 Residual Inst Override 2 Residual Inst Override 3 Residual Inst Override 4 Residual Inst Delay 1 Residual Inst Delay 2 Residual Inst Delay 3 Residual Inst Delay 4 SEF Definite Delay 1 SEF Definite Delay 2 SEF Definite Delay 3 SEF Definite Delay 4 Phase Non-Auto Time Multiplier Phase Non-Auto Curve Residual Non-Auto Time Multiple Residual Non-Auto Curve Phase Non-Auto Inst Override Residual Non-Auto Inst Override Phase Non-Auto Inst Delay Residual Non-Auto Inst Delay Phase CLP Time Multiplier Phase CLP Curve Residual CLP Time Multiplier Residual CLP Curve Phase CLP Inst Override Ground CLP Inst Override Phase CLP Inst Delay Residual CLP Inst Delay

GND_TCC4_TMULT GND_TCC4_ID GND_TCC1_ADDER GND_TCC2_ADDER GND_TCC3_ADDER GND_TCC4_ADDER GND_TCC1_TMIN GND_TCC2_TMIN GND_TCC3_TMIN GND_TCC4_TMIN GND_TCC1_INST_MULT GND_TCC2_INST_MULT GND_TCC3_INST_MULT GND_TCC4_INST_MULT GND_TCC1_INST_DELAY GND_TCC2_INST_DELAY GND_TCC3_INST_DELAY GND_TCC4_INST_DELAY SEF1_TRIP_TIME SEF2_TRIP_TIME SEF3_TRIP_TIME SEF4_TRIP_TIME PHS_NONAUTO_TMULT PHS_NONAUTO_ID GND_NONAUTO_TMULT GND_NONAUTO_ID PHS_NONAUTO_INST_MULT GND_NONAUTO_INST_MULT PHS_NONAUTO_INST_DELAY GND_NONAUTO_INST_DELAY PHS_CLP_TMULT PHS_CLP_ID GND_CLP_TMULT GND_CLP_ID PHS_CLP_INST_MULT GND_CLP_INST_MULT PHS_CLP_INST_DELAY GND_CLP_INST_DELAY

0.10 2.00 MICROTRIP Curves 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 1.0 0 20.0 X, OUT 1.0 0 20.0 X, OUT 1.0 0 20.0 X, OUT 1.0 0 20.0 X, OUT 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.00 2.00 sec 0.5 180.0 sec, INST 0.5 180.0 sec, INST 0.5 180.0 sec, INST 0.5 180.0 sec, INST 0.10 2.00 MICROTRIP Curves 0.10 2.00 MICROTRIP Curves 1.0 - 0 20.0 X, OUT 1.0 - 0 20.0 X, OUT 0.00 2.00 sec 0.00 2.00 sec 0.10 2.00 MICROTRIP Curves 0.10 2.00 MICROTRIP Curves 1.0 - 0 20.0 X, OUT 1.0 - 0 20.0 X, OUT 0.00 2.00 sec 0.00 2.00 sec

Phase High "I" L/O Trip No Residual High "I" L/O Trip No Phase High "I" L/O Mult. Residual High "I" L/O Mult. Phase High "I" L/O Delay Residual High "I" L/O Delay

PHS_HI_CURR_LO_NUM GND_HI_CURR_LO_NUM PHS_HI_CURR_LO_MULT GND_HI_CURR_LO_MULT PHS_HI_CURR_LO_ADDER GND_HI_CURR_LO_ADDER

1 4, OUT 1 4, OUT 5.0 20.0 X 5.0 20.0 X 0.00 2.00 sec 0.00 2.00 sec

V.

Element Settings

On the element forms, set only the necessary contact logic codes; other settings are taken from the common taps. You can also change the settings from CAPE CG using the forms or using DRAG_CURVE. The new common taps are computed automatically from the element settings. VI. Contact Logic Element
Ground CLP Ground TCC1 Ground TCC2 Ground TCC3 Ground TCC4 Phase CLP Phase TCC1 Phase TCC2 Phase TCC3 Phase TCC4 SEF TCC1 SEF TCC2 SEF TCC3 SEF TCC4

Suggested contact logic codes: Contact Logic Code


GND_CLP GND_TCC1 GND_TCC2 GND_TCC3 GND_TCC4 PHS_CLP PHS_TCC1 PHS_TCC2 PHS_TCC3 PHS_TCC4 SEF_TCC1 SEF_TCC2 SEF_TCC3 SEF_TCC4

If there are duplicates from other reclosers in the same LZOP, you may add the prefix "MICROTRIP_" , e.g. "MICROTRIP_GND_TCC1". The LZOP LOGIC (e.g. MICROTRIP_TRIP) for all elements is PHS_TCC1 OR PHS_TCC2 OR PHS_TCC3 OR PHS_TCC4 OR GND_TCC1 OR GND_TCC2 OR GND_TCC3 OR GND_TCC4 OR SEF_TCC1 OR SEF_TCC2 OR SEF_TCC3 OR SEF_TCC4 OR PHS_CLP OR GND_CLP

To prevent an element from tripping the logical breakers in its local zone of protection (LZOP), omit its contact-logic code from this expression. For ground elements alone, the expression would be: GND_TCC1 OR GND_TCC2 OR GND_TCC3 OR GND_TCC4 OR SEF_TCC1 OR SEF_TCC2 OR SEF_TCC3 OR SEF_TCC4 OR GND_CLP