VEVTILATION CALCULATION FOR THE TRANSFORMER ROOM

PROJECT : 1ASSUMPTION

- Ambient Temperature - Max. Allowed Temp. Rise


- Sub- Station Ref. No.

= = = = = = = =

- Number Of Transformers - Transformer Rateing - Number Of Transformers - Transformer Rateing - Power Factor - Transformer Eff. 2CALCULATION Heat Loss / Transformer

115 10.8 1 1 1000 2 2000 0.98 0.98

= =

98 98000

KW Watt

Total Heat Dissipation = = 98000 = 334474 = 1.08 x CFM = 1.08 x CFM Air Quantity Required for ventilation Then :The Air Quantity
VENTILATION SYSTEM DISCRIPTION

x x x

3.413 Btu/hr Temp. Rise 10.8

28,676

CFM

Number of fans Fan Capacity / Each Fan rating KW/Each Fan st. Pressure

= = = =

1 28,676 =
4.23

CFM
KW

IN.WG

F F Nos. KVA Nos. KVA