* Ensure that trees or plants grown under or in the vicinity of the high voltage electricity supply lines are less than 2.4 metres in height
Minimum clearance of any building or structures from high voltage supply lines, apart from a substation building, must not be less than 4.57 metres.
* Ensure that trees or plants grown under or in the vicinity of the high voltage electricity supply lines are less than 2.4 metres in height
Minimum clearance of any building or structures from high voltage supply lines, apart from a substation building, must not be less than 4.57 metres.
20m
20m
20m
20m
Red Zone measured 12m either side of transmission line + distance around structure and conductor swing Orange Zone measured 20m either of the red zone Green Zone beyond the orange zone
Road
No
Voltage System
Corridor for Underground Cable from Road Shoulder / Perimeter Drain (A) 5m 3m
1 2
2m
Gas/Water/Telco. pipe
SESB Cable
3m
Use of gas-insulated switchgear allowed the 132-kV transformer substation in the center of Kota Kinabalu to be constructed underground and a park built over it which harmonizes with the surroundings. The sound of the waterfall, which acts as a heat-exchanger, hides the noise made by the fans.
Type of conductor Aerial Bundled Cable (ABC) 33 kV Aerial Bundled Cable (ABC) 11 kV Overhead Line (Bare) 33 kV Overhead Line (Bare) 11 kV Overhead Line (Lattice Tower) 33 kV
Road
No
Voltage System
Corridor for Underground Cable from Road Shoulder / Perimeter Drain (A) 2m 1.5 m
1 2
1.2m
Gas/Water/Telco. pipe
SESB Cable
2m
Building / Structure Building / Structure PPU PE Sewerage Pump House 50m 30m
Distance
Sewerage Pond
PPU/PE SESB Garbage Collection Center 50m 50m Waste Disposal Center 500m 100m
250m 100m
River
Ocean
50m 50m
250m 100m
Pencawang Penurun Utama (PPU) 33/11kV Main Switching Substation (SSU) 33kV & 11kV
The issue of incompatible land uses between high voltage transmission and distribution lines, substations and sensitive land uses could be addressed by creating buffer zones that apply to future development areas to be implemented in the next update of the Kota Kinabalu Local Plan 2020 and Structural Plan 2030 and Land Use Bylaw review.