Project Name Project Name Calculation Location R&S - Column restrain tie Drawing Reference Originator HP

Date
17-May-13

Job Number 10000 Sheet Number Rev. 1 of 1 Checker Date

Ref. Brief

Calculations Design end moments for column restrain ties for Refining and Storage building needs to be estimated Sections
Column : UB 914 305 201 Tie : CHS 114.3 3 [depth, h = 903 mm]

Output

Robot

Actions
Max. Factored axial load, P Max. Factored bending moment, M Max. Axial force in flange, F = = 392 kN 1445 kNm

= P/2 + M/h = 392 / 2 + 1445 / 0.903 1796.2 kN = say 1800 kN

Design end moment for tie

2.5% of Flange force h/2 = = 2.5 / 100 1800 0.903 / 2


= 20.32kNm 21 kN say

The end connections of ties shall have a capacity of 21kNm