Documente Academic
Documente Profesional
Documente Cultură
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
BREVIARDECALCULELECTRIC
1
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
CUPRINS
BREVIARDECALCULELECTRIC............................................................................................................1
CUPRINS..............................................................................................................................................2
1.Formule...........................................................................................................................................5
1.1.FormulConductivitateElectric.............................................................................................5
1.2.FormuleSuprasarcini................................................................................................................6
1.3.Formulecompensareenergiereactiv....................................................................................6
1.4.Formulentrerupere.................................................................................................................6
1.5.Formuledebarecolectoare.....................................................................................................8
1.5.1.Calculelectrodinamic........................................................................................................8
1.5.2.Verificarepersolicitaretermicncurentdescurtcircuit................................................8
1.6.FormuleRezistenPmnt.....................................................................................................8
1.6.1.Placngropat..................................................................................................................8
1.6.2.Tijvertical......................................................................................................................8
1.6.3.Conductorngropatpeorizontal.....................................................................................8
1.6.4.Asociereanparaleladiferiilorelectrozi.........................................................................9
2.CALCULEELECTRICSTAP...............................................................................................................10
2.1.TABLOUGENERALDECOMANDIPROTECIE....................................................................10
2.1.1.CEREREDEPUTERI...........................................................................................................10
2.1.2.CALCULMPMNTARE..................................................................................................15
3.CALCULELINIEPOMPRI...............................................................................................................16
3.1.cALCULELINIEJOASATENSIUNETrf(PTA5721).....................................................................16
3.1.1.CEREREDEPUTERI...........................................................................................................16
3.1.2.CalcululDERIVAIEIINDIVIDUALE...................................................................................16
3.1.3.CalculLinie:Put22..........................................................................................................17
3.1.4.CalculLinie:Put23..........................................................................................................17
3.1.5.CalculLinie:Put24..........................................................................................................18
2
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
CONTRACTORUL:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
3.1.6.CALCULBARECOLECTOARETABLOULGENERALDECONTROLIPROTECIE................18
3.1.7.Rezultateleobinute........................................................................................................19
3.2.CALCULELINIEJOASATENSIUNETrf(PTA5719).....................................................................20
3.2.1.CEREREDEPUTERI...........................................................................................................20
3.2.2.CalcululDERIVAIEIINDIVIDUALE...................................................................................20
3.2.3.CalculLinie:Put13..........................................................................................................20
3.2.4.CalculLinie:Put14..........................................................................................................21
3.2.5.CalculLinie:Put15..........................................................................................................21
3.2.6.CalculLinie:Put21..........................................................................................................22
3.2.7.CALCULBARECOLECTOARETABLOUGENERALDECOMANDIPROTECIE................22
3.2.8.Rezultateleobinute........................................................................................................23
3.3.CALCULELINIEJOASATENSIUNETrf(PTA5718).....................................................................24
3.3.1.CEREREDEPUTERI...........................................................................................................24
3.3.2.CalculDERIVAIEINDIVIDUAL.......................................................................................24
3.3.3.CalculLinie:Put6............................................................................................................24
3.3.4.CalculLinie:Put7............................................................................................................25
3.3.5.CALCULBARECOLECTOARETABLOUGENERALDECONTROLIPROTECIE..................25
3.3.6.Rezultateleobinute........................................................................................................26
3.4.CALCULELINIEJOASATENSIUNETrf(PTA5717).....................................................................27
3.4.1.CEREREDEPUTERI...........................................................................................................27
3.4.2.CalculDERIVAIEINDIVIDUAL.......................................................................................27
3.4.3.CalculLinie:Put2............................................................................................................27
3.4.4.CalculLinie:put5............................................................................................................28
3.4.5.CALCULBARECOLECTOARETABLOUGENERALDECONTROLIPROTECIE..................28
3.4.6.Rezultateleobinute........................................................................................................29
3.5.CALCULELINIEJOASATENSIUNETrf(PTA5716).....................................................................30
3.5.1.CEREREDEPUTERI...........................................................................................................30
3.5.2.CalculDERIVAIEINDIVIDUAL.......................................................................................30
3.5.3.CalculLinie:Put20..........................................................................................................30
3.5.4.CalculLinie:Put19..........................................................................................................31
3
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
CONTRACTORUL:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
3.5.5.CalculLinie:Put18..........................................................................................................31
3.5.6.CalculLinie:Put17..........................................................................................................32
3.5.7.CalculLinie:Put16..........................................................................................................32
3.5.8.CALCULBARECOLECTOARETABLOUGENERALDECONTROLIPROTECIE..................33
3.5.9.Rezultateleobinute........................................................................................................33
4
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
1. FORMULE
Se vor folosi urmtoarele formule:
Sistem Trifazic
I = Pc / 1,732 x U x Cos x R = amp (A)
e = (L x Pc / k x U x n x S x R) + (L x Pc x Xu x Sen / 1000 x U x n x R x Cos) = voli (V)
Sistem Monofazic:
I = Pc / U x Cos x R = amp (A)
e = (2 x L x Pc / k x U x n x S x R) + (2 x L x Pc x Xu x Sen / 1000 x U x n x R x Cos) = voli (V)
Unde:
Pc = Putere Calcul n Watt.
L = Lungime Calcul n metri.
e = Cdere de tensiune n Voli.
K = Conductivitate.
I = Intensitate n Amperi.
U = Tensiunea de funcionare n Voli (Trifazic sau Monofazic).
S = Seciunea conductorului n mm.
Cos = Cosinus de fi. Factor de putere.
R = Randament. (Pentru liniile motor).
n = Numr de conductoare per faz.
Xu = Reactan per unitate de lungime n m/m.
1.1. FORMULCONDUCTIVITATEELECTRIC
K = 1/
= 20[1+ (T-20)]
T = T0 + [(Tmax-T0) (I/Imax)]
Unde,
K = Conductivitatea conductorului la temperatura T.
= Rezistivitate conductor la temperatura T.
20 = Rezistivitate conductor la 20C.
Cu = 0.018
Al = 0.029
= Coeficient de temperatur:
Cu = 0.00392
Al = 0.00403
T = Temperatura conductorului (C).
T0 = Temperatura mediului (C):
Cabluri ngropate = 25C
Cabluri n aer = 40C
Tmax = Temperatura maxim admis a conductorului (C):
XLPE, EPR = 90C
PVC = 70C
I = Intensitate prevzut per conductor (A).
Imax = Intensitate maxim admis a conductorului (A).
5
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
1.2. FORMULESUPRASARCINI
Ib In Iz
I2 1,45 Iz
Unde:
Ib: intensitatea folosit n circuit.
Iz: intensitatea admis a canalizrii.
In: intensitatea nominal a dispozitivului de protecie. Pentru dispozitivele de protecie reglabile, In este
intensitatea de reglare aleas.
I2: intensitatea care asigur efectiv funcionarea dispozitivului de protecie. n practic I2 se consider egal:
- la intensitatea de funcionare n timpul convenional, n timpul convenional, pentru ntreruptoare
automate (1,45 In maxim).
- la intensitatea de fuziune n timpul convenional, pentru sigurane (1,6 In).
1.3. FORMULECOMPENSAREENERGIEREACTIV
cos = P/(P+ Q).
tg = Q/P.
Qc = Px(tg1-tg2).
C = Qcx1000/Ux; (Monofazic - Trifazic conexiune stea).
C = Qcx1000/3xUx; (Trifazic conexiune triunghi).
Unde:
P = Putere activ instalaie (kW).
Q = Putere reactiv instalaie (kVAr).
Qc = Putere reactiv de compensat (kVAr).
1 = Unghi de decalaj al instalaiei fr compensare.
2 = Unghi de decalaj care se dorete a fi obinut.
U = Tensiune compus (V).
= 2xPixf ; f = 50 Hz.
C = Capacitate condensatoare (F); cx1000000(F).
1.4. FORMULENTRERUPERE
* IpccI = Ct U / 3 Zt
Unde,
IpccI: intensitate permanent a c.c. la nceputul liniei n kA.
Ct: Coeficient de tensiune.
U: Tensiune trifazic n V.
Zt: Impedan total n mohm, amonte fa de punctul de scurtcircuit (fr s se includ linia sau circuitul n
studiu).
* IpccF = Ct UF / 2 Zt
Unde:
IpccF: Intensitate permanent a c.c. la finalul liniei n kA.
Ct: Coeficient de tensiune.
UF: Tensiune monofazic n V.
6
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
Zt: Impedan total n mohm, inclusiv cea specific liniei sau circuitului (astfel este egal cu Impedan de la
baz plus cea specific conductorului sau lnea).
* Impedana total pn la punctul de scurtcircuit va fi:
Zt = (Rt + Xt)
Unde:
Rt: R1 + R2 + ................+ Rn (suma rezistenelor liniilor n amonte pn la punctul de c.c.)
Xt: X1 + X2 + .............. + Xn (suma reactanelor liniilor n amonte pn la punctul de c.c.)
R = L 1000 CR / K S n
(mohm)
X = Xu L / n
(mohm)
R: Rezistena liniei n mohm.
X: Reactana liniei n mohm.
L: Lungimea liniei n m.
CR: Coeficient de rezistivitate.
K: Conductivitate a metalului.
S: Seciunea liniei n mm.
Xu: Reactana liniei, n mohm per metru.
n: numr de conductoare per faz.
* tmcicc = Cc S / IpccF
Unde:
tmcicc: Timp maxim n secunde n care un conductor suport Ipcc.
Cc= Constant ce depinde de natura conductorului i de izolaia sa.
S: Seciunea liniei n mm.
IpccF: Intensitate permanent a c.c. la captul liniei n A.
* tficc = cte. siguran / IpccF
Unde:
tficc: timp de fuziune a unei sigurane pentru o anumit intensitate a curentului de scurtcircuit.
IpccF: Intensitate permanent a c.c. la captul liniei n A.
* Lmax = 0,8 UF / 2 IF5 (1,5 / K S n) + (Xu / n 1000)
Unde:
Lmax: Longimea maxim a conductorului protejat la c.c. (m) (pentru protecie prin sigurane)
UF: Tensiune de faz (V)
K: Conductivitate
S: Seciunea conductorului (mm)
Xu: Reactan per unitate de lungime (mohm/m). n conductoare izolate este de obicei 0,1.
n: num de conductoare per faz
Ct= 0,8: Este coeficientul de tensiune.
CR = 1,5: Este coeficientul de rezisten.
IF5 = Intensitatea de fuziune n amperi a siguranelor n 5 sg.
* Curbe valabile.(Pentru protecia ntreruptoarelor automate dotate cu Releu electromagnetic).
CURBA B
CURBA C
CURBA D Y MA
IMAG = 5 In
IMAG = 10 In
IMAG = 20 In
7
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
1.5. FORMULEDEBARECOLECTOARE
1.5.1. CALCULELECTRODINAMIC
max = Ipcc L / ( 60 d Wy n)
Unde:
max: Tensiune maxim n plcue (kg/cm)
Ipcc: Intensitate permanent a c.c. (kA)
L: Desprire ntre supori (cm)
d: Desprire ntre plcue (cm)
n: numr de plcue per faz
Wy: Modul rezistent per plcu axul y-y (cm)
adm: Tensiune admis material (kg/cm)
1.5.2. VERIFICAREPERSOLICITARETERMICNCURENTDESCURTCIRCUIT
Icccs = Kc S / ( 1000 tcc)
Unde:
Ipcc: Intensitate permanent a c.c. (kA)
Icccs: Intensitate c.c. suportat de conductor n timpul duratei c.c. (kA)
S: Seciune total a plcuelor (mm)
tcc: Timpul de durat a scurtcircuitului (s)
Kc: Constanta conductorului: Cu = 164, Al = 107
1.6. FORMULEREZISTENPMNT
1.6.1. PLACNGROPAT
Rt = 0,8 / P
Unde:
Rt: Rezistena de pmnt (Ohm)
: Rezistivitatea terenului (Ohmm)
P: Perimetru de la placa (m)
1.6.2. TIJVERTICAL
Rt = / L
Unde:
Rt: Rezistena de pmnt (Ohm)
: Rezistivitatea terenului (Ohmm)
L: Lungimea lncii (m)
1.6.3. CONDUCTORNGROPATPEORIZONTAL
8
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
Rt = 2 / L
Unde:
Rt: Rezistena de pmnt (Ohm)
: Rezistivitatea terenului (Ohmm)
L: Lungimea conductorului (m)
1.6.4. ASOCIEREANPARALELADIFERIILORELECTROZI
Rt = 1 / (Lc/2 + Lp/ + P/0,8)
Unde:
Rt: Rezistena de pmnt (Ohm)
: Rezistivitatea terenului (Ohmm)
Lc: Lungimea total conductor (m)
Lp: Lungimea total a lncilor (m)
P: Perimetrul plcilor (m)
9
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
2. CALCULEELECTRICSTAP
2.1. TABLOUGENERALDECOMANDIPROTECIE
2.1.1. CEREREDEPUTERI
2.1.1.1. PUTERETOTALINSTALAT:
DEBFI/1
DEBFI/2
DEBFI/3
DEBLFI/1
DEBLFI/2
DEBLFII/1
DEBLFII/2
DEBP/1
DEBP/2
DEBP/3
DEBRL/1
DEBRL/2
DEBF/1
DEBF/2
DEBF/3
DEBF/4
DESLFI/1
DESLFI/2
DESLFII/1
DESLFII/2
DESTII/1
DESTII/2
tablou local DEPG
tablou local DEVC
DEBC/1
DEBC/2
DEBA
t.local FILTRE I
t.local FILTRE II
DEBCI1
DEBCI2
DVRE1
DVME8
DVME9/1
15000 W
15000 W
15000 W
11000 W
11000 W
55000 W
55000 W
45000 W
45000 W
45000 W
2200 W
2200 W
1100 W
1100 W
1100 W
1100 W
7500 W
7500 W
30000 W
30000 W
15000 W
15000 W
1850 W
2200 W
750 W
750 W
2200 W
3470 W
3080 W
90 W
1500 W
200 W
90 W
200 W
10
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
DVME9/2
DVME9/3
DVCME2/1
DVCME2/2
DVCME3/1
DVCME3/2
Tablou ILUMINAT
Tablou ILUMINAT
Tablou DIFERITE
DIF1
DIF3
DIPH1
DIPH2
DIT1
DIT2
DITU1
DITU2
DITU3
DICLA1
DICL1
DIO21/1
DIO21/2
DIO23
DIO1/1
DIO1/2
DIL1/1
DIL1/2
DIL2/1
DIL2/2
DIL3/1
DIL3/2
TOTAL
CONTRACTORUL:
200 W
200 W
90 W
90 W
90 W
90 W
35774 W
3710 W
4000 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
100 W
488624 W
11
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
2.1.1.2. REZULTATELETABLOUGENERALDECONTROLIPROTECIE
Denumire
COLONA DE TRAFO
DEBFI/1
DEBFI/2
DEBFI/3
DEBLFI/1
DEBLFI/2
DEBLFII/1
DEBLFII/2
DEBP/1
DEBP/2
DEBP/3
DEBRL/1
DEBRL/2
DEBF/1
DEBF/2
DEBF/3
DEBF/4
DESLFI/1
DESLFI/2
DESLFII/1
DESLFII/2
DESTII/1
DESTII/2
tablou local DEPG
tablou local DEVC
DEBC/1
DEBC/2
DEBA
t.local FILTRE I
t.local FILTRE II
DEBCI1
DEBCI2
DVRE1
DVME8
DVME9/1
DVME9/2
DVME9/3
DVCME2/1
DVCME2/2
DVCME3/1
DVCME3/2
Tablou ILUMINAT
Tablou ILUMINAT
Tablou DIFERITE
DIF1
Putere
de
calcul
(W)
310684.
72
32000
18750
32000
18750
32000
18750
16500
16500
68750
68750
68500
56250
68500
56250
68500
56250
2750
2750
1375
1375
1375
1375
9375
9375
37500
37500
32000
18750
32000
18750
2312.5
2750
937.5
937.5
2750
3845
3130
112.5
1875
250
112.5
250
250
250
112.5
112.5
112.5
112.5
20536.6
1871.2
2000
2200
100
Intensit Intensi
C.T.P
ate de
tate
C.T.Tot
arial(
Calcul Admis
al (%)
%)
(A)
(A)
Dist.de
calcul
(m)
Seciune
(mm)
100
2(4x185)Cu
527.59
582
1.17
1.17
5
75
5
75
5
75
20
20
22
22
5
30
5
30
5
30
45
45
38
38
55
55
75
75
72
72
5
70
5
70
70
61
16
16
25
18
18
5
5
17
45
12
13
14
40
40
47
47
8
30
10
0.3
12
3x16+TTx16Cu
3x6+TTx6Cu
3x25+TTx16Cu
3x25+TTx16Cu
3x16+TTx16Cu
3x6+TTx6Cu
3x10+TTx10Cu
3x10+TTx10Cu
3x50+TTx25Cu
3x50+TTx25Cu
3x35+TTx16Cu
3x35+TTx16Cu
3x35+TTx16Cu
3x35+TTx16Cu
3x35+TTx16Cu
3x35+TTx16Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x25+TTx16Cu
3x25+TTx16Cu
3x16+TTx16Cu
3x6+TTx6Cu
3x16+TTx16Cu
3x6+TTx6Cu
4x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
4x4+TTx4Cu
4x4+TTx4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
4x16+TTx16Cu
2x4+TTx4Cu
2x4+TTx4Cu
2x4Cu
2x2.5+TTx2.5Cu
46.19
33.83
46.19
33.83
46.19
33.83
29.77
29.77
116.75
116.75
98.87
101.49
98.87
101.49
98.87
101.49
4.67
4.67
2.33
2.33
2.33
2.33
15.92
15.92
63.68
63.68
46.19
33.83
46.19
33.83
4.17
4.96
1.59
1.59
4.67
6.94
5.65
0.61
10.19
0.45
0.2
0.45
0.45
0.45
0.2
0.2
0.2
0.2
37.05
10.17
10.87
11.96
0.54
73
37
95
96
73
44
52
52
145
145
119
110
119
110
119
110
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
96
96
73
44
73
44
23
23
22
22
22
35
35
23
23
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
59
42
42
31
32.5
0.11
3.28
0.07
0.7
0.11
3.15
0.42
0.42
0.41
0.41
0.11
0.68
0.11
0.68
0.13
0.68
0.6
0.6
0.25
0.25
0.37
0.37
3.62
3.62
1.42
1.42
0.11
2.94
0.11
2.94
0.79
0.82
0.07
0.07
0.34
0.21
0.17
0.02
0.29
0.02
0.02
0.01
0.02
0.02
0.02
0.02
0.03
0.03
0.13
1.04
0.37
0.01
0.04
1.28
4.56
1.24
1.94
1.28
4.43
1.6
1.6
1.58
1.58
1.28
1.96
1.28
1.96
1.3
1.98
1.77
1.77
1.42
1.42
1.54
1.54
4.79
4.79
2.59
2.59
1.28
4.22
1.28
4.22
1.96
1.99
1.24
1.24
1.51
1.38
1.34
1.19
1.46
1.19
1.2
1.19
1.19
1.19
1.19
1.19
1.2
1.2
1.3
2.21
1.54
1.18
1.22
12
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
DIF3
DIPH1
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
DIPH2
DIT1
DIT2
DITU1
DITU2
DITU3
DICLA1
DICL1
DIO21/1
DIO21/2
DIO23
DIO1/1
DIO1/2
DIL1/1
DIL1/2
DIL2/1
DIL2/2
DIL3/1
DIL3/2
12
16
16
11
16
16
16
16
62
16
80
80
16
80
80
80
80
20
20
50
50
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
0.54
CONTRACTORUL:
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
32.5
0.04
0.05
0.05
0.03
0.05
0.05
0.05
0.05
0.18
0.05
0.23
0.23
0.05
0.23
0.23
0.23
0.23
0.06
0.06
0.15
0.15
1.22
1.23
1.23
1.22
1.23
1.23
1.23
1.23
1.37
1.23
1.42
1.42
1.23
1.42
1.42
1.42
1.42
1.24
1.24
1.33
1.33
2.1.1.3. REZULTATELESUBTABLOUTABLOULOCALDEPG
Denumire
DEPG
Putere
de calcul
(W)
Dist.de
calcul (m)
2312.5
Seciune
(mm)
3x2.5+TTx2.5Cu
3.93
27.5
0.03
1.99
2.1.1.4. REZULTATELESUBTABLOUTABLOULOCALDEVC
Denumire
DEVC
Putere
de calcul
(W)
Dist.de
calcul (m)
2750
Seciune
(mm)
3x2.5+TTx2.5Cu
4.67
27.5
0.03
2.02
2.1.1.5. REZULTATELESUBTABLOUT.LOCALFILTRUI
Denumire
Putere
de
calcul
(W)
DEC/1
DEC/2
DESF/1
DIF2
DIO22/1
DIO22/2
1875
1875
212.5
300
100
100
100
Dist.de
calcul
(m)
80
80
80
0.3
80
15
16
Seciune
(mm)
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
22
27.5
32.5
31
32.5
32.5
32.5
0.73
0.73
0.5
0
0.23
0.04
0.05
2.11
2.11
1.88
1.38
1.62
1.43
1.43
2.1.1.6. REZULTATELESUBTABLOUT.LOCALFILTRUII
13
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
Denumire
Putere
de
calcul
(W)
DVCME5/1
DVME5/2
DVME5/3
DVME5/4
DVME6/1
DVME6/2
DVME6/3
DVME6/4
DVME7/1
DVME7/2
DVME7/3
DVME7/4
DVCME1/1
DVCME1/2
DVCME1/3
DVCME1/4
DVCME1/5
DVCME1/6
DVCME1/7
DVCME1/8
DIL4/1
DIL4/2
DIL4/3
DIL4/4
112.5
112.5
112.5
112.5
250
250
250
250
250
250
250
250
112.5
112.5
112.5
112.5
112.5
112.5
112.5
112.5
400
100
100
100
100
Dist.de
calcul
(m)
43
37
43
49
31
31
31
31
31
31
31
31
43
43
43
43
43
43
43
43
0.3
10
10
10
10
Seciune
(mm)
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
3x2.5+TTx2.5Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
CONTRACTORUL:
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
31
32.5
32.5
32.5
32.5
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0
0.03
0.03
0.03
0.03
1.37
1.36
1.37
1.37
1.38
1.38
1.38
1.38
1.38
1.38
1.38
1.38
1.37
1.37
1.37
1.37
1.37
1.37
1.37
1.37
1.34
1.37
1.37
1.37
1.37
2.1.1.7. REZULTATELESUBTABLOUTABLOUILUMINAT
Denumire
proces
Sala tablouri
Sali clor
Sala pompe
birouri
etaj 0
locale 29-30
locale 31-29
loclae 34-35/33
toalete
etaj 0
etaj 0
vestiare
etaj 0
etaj 1
parter
sala tablouri-transf
E
local 1
local 2
local 3
Putere
de
calcul
(W)
11000
4500
2500
2500
2500
4000
2500
2500
2500
2500
3250
2500
2500
3250
2500
2500
3976.56
1056.24
90
835.2
417.6
417.6
Dist.de
calcul
(m)
0.3
0.3
60
25
80
0.3
20
20
20
30
0.3
5
15
0.3
20
30
0.3
0.3
70
66
62
62
Seciune
(mm)
4x6Cu
2x6Cu
2x4+TTx4Cu
2x2.5+TTx2.5Cu
2x6+TTx6Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x4Cu
2x4Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
36
40
27
21
36
31
21
21
21
21
31
21
21
31
21
21
27
31
15
15
15
15
0.01
0.02
2.83
1.92
2.48
0.02
1.53
1.53
1.53
2.3
0.02
0.38
1.15
0.02
1.53
2.3
0
0.01
0.31
2.59
1.25
1.25
1.31
1.32
4.15
3.24
3.81
1.33
2.87
2.87
2.87
3.63
1.33
1.71
2.48
1.33
2.86
3.63
1.3
1.31
1.62
3.9
2.56
2.56
14
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
proces
local 4-5
local 11
local 12
local 15
E
vestiare
E
local 13
Local 9
toalete
E
local 19-20-21
Local 16-17-18
Coridoare de evacuare P0
E
local 6-7
Local 10-8-Scara
Coridoare de evacuare P1
local 22-32
Local 26-24-27
birouri
local 34
local 30
local 28
local 31
local 33/35
local 29
local 29
Iluminat exterior
1557.36
1461.6
417.6
208.8
417.6
90
311.22
90
129.6
259.2
549.9
90
432
324
3000
3000
2386.8
90
1252.8
1044
3052.8
1382.4
1670.4
1477.44
201.6
201.6
518.4
518.4
388.8
216
417.6
2430
0.3
55
12
15
17
80
0.3
40
10
17
0.3
40
19
14
4
0.3
0.3
80
70
27
0.3
39
59
0.3
17
17
21
21
24
12
62
225
2x4Cu
2x2.5+TTx2.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x4Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x4Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x4+TTx4Cu
2x4Cu
2x4Cu
2x1.5+TTx1.5Cu
2x2.5+TTx2.5Cu
2x1.5+TTx1.5Cu
2x2.5Cu
2x1.5+TTx1.5Cu
2x2.5+TTx2.5Cu
2x4Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x10+TTx10Cu
7.97
6.35
1.82
0.91
1.82
0.39
1.59
0.39
0.56
1.13
2.81
0.39
1.88
1.41
16.3
16.3
12.21
0.39
5.45
4.54
15.62
6.01
7.26
7.56
0.88
0.88
2.25
2.25
1.69
0.94
1.82
10.57
CONTRACTORUL:
31
21
15
15
15
15
31
15
15
15
31
15
15
15
36
31
31
15
21
15
23
15
21
31
15
15
15
15
15
15
15
70
0.01
2.01
0.23
0.15
0.35
0.35
0
0.18
0.06
0.2
0
0.18
0.34
0.19
0.23
0.02
0.01
0.35
2.04
0.99
0.03
2.17
2.18
0.01
0.16
0.16
0.46
0.46
0.42
0.12
1.25
2.24
1.31
3.33
1.54
1.47
1.66
1.67
1.31
1.48
1.37
1.51
1.31
1.48
1.65
1.5
1.53
1.55
1.56
1.91
3.6
2.55
1.57
3.75
3.75
1.31
1.47
1.47
1.77
1.77
1.73
1.43
2.56
3.54
2.1.1.8. REZULTATELESUBTABLOUTABLOUILUMINAT
Denumire
E
Iluminat cladirea noua
Putere cladirea noua
Putere
de
calcul
(W)
Dist.de
calcul
(m)
2178
90
2088
2500
2500
0.3
40
24
0.3
35
Seciune
(mm)
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x4Cu
2x2.5+TTx2.5Cu
16.5
15
15
31
21
0.03
0.18
1.59
0.01
2.69
2.25
2.42
3.84
2.23
4.91
2.1.1.9. REZULTATELESUBCUADROTABLOUDIFERITE
Denumire
Putere
de
calcul
(W)
Dist.de
calcul
(m)
4000
25
Seciune
(mm)
2x2.5+TTx2.5Cu
26.5
3.29
4.84
2.1.2. CALCULMPMNTARE
15
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
35 mm 16 m.
95 mm
14 mm
14 mm 4 lncii de 2m.
25 mm
3. CALCULELINIEPOMPRI
3.1. CALCULELINIEJOASATENSIUNETRF(PTA5721)
3.1.1. CEREREDEPUTERI
- Putere total instalat:
Put 22
Put 23
Put 24
TOTAL....
15000 W
15000 W
18500 W
48500 W
3.1.2. CALCULULDERIVAIEIINDIVIDUALE
- Tensiune de funcionare: 400 V.
- Canalizare: B1-Unip.Tuburi Superficiale sau ncastrate n lucrare
- Lungime: 4 m; Cos : 0.8; Xu(m/m): 0;
- Putere la instalare: 48500 W.
- Putere de calcul:
18500x1.25+30000=53125 W.(Coeficient de Simultaneitate: 1 )
I=53125/1,732x400x0.8=95.85 A.
16
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.1.3. CALCULLINIE:PUT22
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Longime: 155 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere calcul:
15000x1.25=18750 W.
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoarele Tripolare 4x10mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 58 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 57.01
e(parial)=155x18750/48.52x400x10x1=14.98 V.=3.74 %
e(total)=3.83% ADMIS (6.5% MAX.)
Protecie termic:
Intensitate Magnetic ntreruptor Tetrapolar: 40 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial.: 40 A. Sens. Int.: 300 mA. Clasa AC.
3.1.4. CALCULLINIE:PUT23
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 135 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoarele Tripolare 4x10mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 58 A.
Diametru exterior tub: 90 mm.
17
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
Protecie termic:
Temperatura cablu (C): 57.01
e(parial)=135x18750/48.52x400x10x1=13.04 V.=3.26 %
e(total)=3.34% ADMIS (6.5% MAX.)
Protecie termic:
Intensitate Magnetic ntreruptor Tetrapolar: 40 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial: 300 mA. Clasa AC.
3.1.5. CALCULLINIE:PUT24
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat.
- Lungime: 500 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 18500 W.
- Putere de calcul:
18500x1.25=23125 W.
I=23125/1,732x400x0.8x1=41.72 A.
Se aleg conductoare Tripolare 4x35mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 117 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 46.36
e(parial)=500x23125/50.35x400x35x1=16.4 V.=4.1 %
e(total)=4.18% ADMIS (6.5% MAX.)
Protecie termic:
Intensitate Magnetic ntreruptor Tetrapolar. 50 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial:: 300 mA. Clasa AC.
3.1.6. CALCULBARECOLECTOARETABLOULGENERALDECONTROLIPROTECIE
3.1.6.1. DATE
- Metal: Cu
- Stare plcue: dezvelite
- numr plcue per faz: 1
- Desprire ntre plcue, d(cm): 10
- Desprire ntre supori, L(cm): 25
- Timp de durat c.c. (s): 0.5
3.1.6.2. PLCUADOPTAT
- Seciune (mm): 40
18
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
- Lime (mm): 20
- Grosime (mm): 2
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.133, 0.133, 0.0133, 0.0013
- Intensitate admis a barelor colectoare (A): 185
a) Calcul electrodinamic
max = Ipcc L / ( 60 d Wy n) =3.51 25 /(60 10 0.0133 1) = 965.02 <= 1200 kg/cm Cu
b) Calcul termic, per intensitate admis
Ical = 95.85 A
Iadm = 185 A
c) Verificare per solicitare termic n scurtcircuit
Ipcc = 3.51 kA
Icccs = Kc S / ( 1000 tcc) = 164 40 1 / (1000 0.5) = 9.28 kA
3.1.7. REZULTATELEOBINUTE
Denumire
Put 22
Put 23
Put 24
P.Calcul
(W)
18750
18750
23125
Dist.Calcul
(m)
155
135
500
Seciune
(mm)
4x10Cu
4x10Cu
4x35Cu
I.Calcul I.Admis
(A)
(A)
33.83
58
33.83
58
41.72
117
C.T.Parc. C.T.Total
(%)
(%)
3.74
3.83
3.26
3.34
4.1
4.18
Scurtcircuit
Denumire
Put 22
Put 23
Put 24
Lungime
(m)
155
135
500
Seciune
(mm)
4x10Cu
4x10Cu
4x35Cu
IpccI P de C
(kA)
(kA)
3.52
4.5
3.52
4.5
3.52
4.5
IpccF
(A)
236.67
268.59
255.08
tmcicc
(sg)
36.51
28.35
384.98
tficc
(sg)
Lmx
(m)
Curbe
valabile
40;B
40;B
50;B
19
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.2. CALCULELINIEJOASATENSIUNETRF(PTA5719)
3.2.1. CEREREDEPUTERI
- Putere total instalat:
Put 13
Put 14
Put 15
Put 21
TOTAL....
15000 W
15000 W
18500 W
18500 W
67000 W
3.2.2. CALCULULDERIVAIEIINDIVIDUALE
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 4 m; Cos : 0.8; Xu(m/m): 0;
- Putere la instalare: 67000 W.
- Putere de calcul:
18500x1.25+48500=71625 W.(Coef. de Simult.: 1 )
I=71625/1,732x400x0.8=129.23 A.
Se aleg conductoare Unipolare 4x70mmCu
Nivel Izolare, Izolare: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 170 A.
Diametru exterior tub: 125 mm.
Cdere de tensiune:
Temperatur cablu (C): 68.89
e(parial)=4x71625/46.62x400x70=0.22 V.=0.05 %
e(total)=0.05% ADMIS (4.5% MAX.)
Protecie Termic:
Intrerupator Automat: 160 A. Termic Reglarea intensitii.: 150 A.
3.2.3. CALCULLINIE:PUT13
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 10 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
20
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x6mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 44 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 69.56
e(parial)=10x18750/46.52x400x6x1=1.68 V.=0.42 %
e(total)=0.47% ADMIS (6.5% MAX.)
Protecie termic:
Intensitate Magnetic ntreruptor Tetrapolar 40 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial.: 40 A. Sens. Int.: 300 mA. Clasa AC.
3.2.4. CALCULLINIE:PUT14
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 295 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x16mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 75 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 50.17
e(parial)=295x18750/49.68x400x16x1=17.4 V.=4.35 %
e(total)=4.4% ADMIS (6.5% MAX.)
Protecie termic:
Intensitate Magnetic ntreruptor Tetrapolar 40 A.
Protecie diferenial:
ntensitate ntreruptor Tetrapolar Diferenial.: 40 A. Sens. Int.: 300 mA. Clasa AC.
3.2.5. CALCULLINIE:PUT15
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 615 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 18500 W.
- Putere de calcul:
18500x1.25=23125 W.
I=23125/1,732x400x0.8x1=41.72 A.
Se aleg conductoare Tripolare 4x50mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
21
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.2.6. CALCULLINIE:PUT21
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 910 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 18500 W.
- Putere de calcul:
18500x1.25=23125 W.
I=23125/1,732x400x0.8x1=41.72 A.
Se aleg conductoare Tripolare 4x70mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 170 A.
Diametru exterior tub: 160 mm.
Cdere de tensiune:
Temperatur cablu (C): 43.01
e(parial)=910x23125/50.96x400x70x1=14.75 V.=3.69 %
e(total)=3.74% ADMIS (6.5% MAX.)
Protecie Termic:
Intensitate Magnetic ntreruptor Tetrapolar: 50 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial.: 63 A. Sens. Int.: 300 mA. Clasa AC.
3.2.7. CALCULBARECOLECTOARETABLOUGENERALDECOMANDIPROTECIE
3.2.7.1. DATE
- Metal: Cu
- Stare plcue: dezvelite
- numr plcue per faz: 1
- Desprire ntre plcue, d(cm): 10
- Desprire ntre supori, L(cm): 25
- Timp durat c.c. (s): 0.5
3.2.7.2. PLCUADOPTAT
22
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
- Seciune (mm): 60
- Lime (mm): 20
- Grosime (mm): 3
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.2, 0.2, 0.03, 0.0045
- I. admis a barelor colectoare (A): 220
a) Calcul electrodinamic
max = Ipcc L / ( 60 d Wy n) =5.66 25 /(60 10 0.03 1) = 1112.093 <= 1200 kg/cm Cu
b) Calcul termic, per intensitate admisibil
Ical = 129.23 A
Iadm = 220 A
c) Verificare per solicitare termic n scurtcircuit
Ipcc = 5.66 kA
Icccs = Kc S / ( 1000 tcc) = 164 60 1 / (1000 0.5) = 13.92 kA
3.2.8. REZULTATELEOBINUTE
Denumire
Put 13
Put 14
Put 15
Put 21
P.Calcul
(W)
18750
18750
23125
23125
Dist.Calcul
(m)
10
295
615
910
Seciune
(mm)
4x6Cu
4x16Cu
4x50Cu
4x70Cu
I.Calcul
(A)
33.83
33.83
41.72
41.72
I.Admis C.T.Parc.
(A)
(%)
44
0.42
75
4.35
138
3.51
170
3.69
C.T.Total
(%)
0.47
4.4
3.56
3.74
ntrerupere
Denumire
Put 13
Put 14
Put 15
Put 21
Lungime
(m)
10
295
615
910
Seciune
(mm)
4x6Cu
4x16Cu
4x50Cu
4x70Cu
IpccI P de C
(kA)
(kA)
5.68
6
5.68
6
5.68
6
5.68
6
IpccF
(A)
1537.76
207.48
305.67
290.03
tmcicc
(sg)
0.31
121.61
547.16
1191.16
tficc
(sg)
L max.
(m)
Curbe
valabile
40;B,C,D
40;B
50;B
50;B
23
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.3. CALCULELINIEJOASATENSIUNETRF(PTA5718)
3.3.1. CEREREDEPUTERI
- Putere total instalat:
Put 6
Put 7
TOTAL....
15000 W
15000 W
30000 W
3.3.2. CALCULDERIVAIEINDIVIDUAL
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 4 m; Cos : 0.8; Xu(m/m): 0;
- Putere la instalare: 30000 W.
- Putere de calcul:
15000x1.25+15000=33750 W.(Coeficient de Simultaneitate: 1)
I=33750/1,732x400x0.8=60.89 A.
Se aleg conductoare Unipolare 4x50mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 138 A.
Diametru exterior tub: 110 mm.
Cdere de tensiune:
Temperatur cablu (C): 49.74
e(parial)=4x33750/49.76x400x50=0.14 V.=0.03 %
e(total)=0.03% ADMIS (4.5% MAX.)
Protecie Termic:
Intensitate Magnetic ntreruptor Tetrapolar 63 A.
3.3.3. CALCULLINIE:PUT6
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Mult.Conductor ngropat
- Lungime: 871 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
24
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x50mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 138 A.
Diametru exterior tub: 160 mm.
Cdere de tensiune:
Temperatur cablu (C): 43
e(parial)=871x18750/50.96x400x50x1=16.02 V.=4.01 %
e(total)=4.04% ADMIS (6.5% MAX.)
Protecie Termic:
Intensitate Magnetic ntreruptor Tetrapolar 40 A.
Protecie diferenial:
Intensitate Magnetic ntreruptor Tetrapolar: 40 A. Sens. Int.: 300 mA. Clas AC.
3.3.4. CALCULLINIE:PUT7
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 320 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x25mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 96 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 46.21
e(parial)=320x18750/50.38x400x25x1=11.91 V.=2.98 %
e(total)=3.01% ADMIS (6.5% MAX.)
Protecie termic:
Intensitate Magnetic ntreruptor Tetrapolar 40 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial.: 40 A. Sens. Int.: 300 mA. Clasa AC.
3.3.5. CALCULBARECOLECTOARETABLOUGENERALDECONTROLIPROTECIE
3.3.5.1. DATE
- Metal: Cu
- Stare plcue: dezvelite
- numr plcue per faz: 1
- Desprire ntre plcue, d(cm): 10
- Desprire ntre supori, L(cm): 25
- Timp durat curent de scurtcircuit (s): 0.5
25
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.3.5.2. PLCUAADOPTAT
- Seciune (mm): 40
- Lime (mm): 20
- Grosime (mm): 2
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.133, 0.133, 0.0133, 0.0013
- I. admis a barei colectoare (A): 185
a) Calcul electrodinamic
max = Ipcc L / ( 60 d Wy n) =3.54 25 /(60 10 0.0133 1) = 979.051 <= 1200 kg/cm Cu
b) Calcul termic, per intensitate admis
Ical = 60.89 A
Iadm = 185 A
c) Verificare per solicitare termic n scurtcircuit
Ipcc = 3.54 kA
Icccs = Kc S / ( 1000 tcc) = 164 40 1 / (1000 0.5) = 9.28 kA
3.3.6. REZULTATELEOBINUTE
Denumire
Put 6
Put 7
P.Calcul
(W)
18750
18750
Dist.Calcul
(m)
871
320
Seciune
(mm)
4x50Cu
4x25Cu
I.Calcul
(A)
33.83
33.83
I.Admis
(A)
138
96
C.T.Parc.
(%)
4.01
2.98
C.T.
Total (%)
4.04
3.01
ntrerupere
Denumire
Put 6
Put 7
Lungime
(m)
871
320
Seciune
IpccI (kA)
(mm)
4x50Cu
3.55
4x25Cu
3.55
P de C (kA)
4.5
4.5
IpccF
(A)
212.79
282.56
tmcicc
(sg)
1129.08
160.07
tficc
(sg)
L max.
(m)
Curbe
valabile
40;B
40;B
26
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.4. CALCULELINIEJOASATENSIUNETRF(PTA5717)
3.4.1. CEREREDEPUTERI
- Putere total instalat:
Put 2
put 5
TOTAL....
15000 W
15000 W
30000 W
3.4.2. CALCULDERIVAIEINDIVIDUAL
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 4 m; Cos : 0.8; Xu(m/m): 0;
- Putere la instalare: 30000 W.
- Putere de calcul:
15000x1.25+15000=33750 W.(Coeficient de Simultaneitate: 1 )
I=33750/1,732x400x0.8=60.89 A.
Se aleg conductoare Unipolare 4x35mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 117 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 53.54
e(parial)=4x33750/49.1x400x35=0.2 V.=0.05 %
e(total)=0.05% ADMIS (4.5% MAX.)
Protecie termic:
I. Mag. Tetrapolar Int. 63 A.
3.4.3. CALCULLINIE:PUT2
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Mult.Conductorngropat
- Lungime: 505 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
27
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x35mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 117 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 44.18
e(parial)=505x18750/50.75x400x35x1=13.33 V.=3.33 %
e(total)=3.38% ADMIS (6.5% MAX.)
Protecie Termic:
Intensitate Magnetic ntreruptor Tetrapolar 40 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial.: 40 A. Sens. Int.: 300 mA. Clasa AC.
3.4.4. CALCULLINIE:PUT5
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Mult.Conductori ngropai
- Lungime: 592 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x35mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 117 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 44.18
e(parial)=592x18750/50.75x400x35x1=15.62 V.=3.91 %
e(total)=3.96% ADMIS (6.5% MAX.)
Protecie termic:
Intensitate Magnetic ntreruptor Tetrapolar 40 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial.: 40 A. Sens. Int.: 300 mA. Clasa AC.
3.4.5. CALCULBARECOLECTOARETABLOUGENERALDECONTROLIPROTECIE
3.4.5.1. DATE
- Metal: Cu
- Stare plcue: dezvelite
- numr plcue per faz: 1
- Desprire ntre plcue, d(cm): 10
- Desprire ntre supori, L(cm): 25
- Timp durat c.c. (s): 0.5
28
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.4.5.2. PLCUADOPTAT
- Seciune (mm): 40
- Lime (mm): 20
- Grosime (mm): 2
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.133, 0.133, 0.0133, 0.0013
- I. admis a barelor colectoare (A): 185
a) Calcul electrodinamic
max = Ipcc L / ( 60 d Wy n) =3.51 25 /(60 10 0.0133 1) = 965.02 <= 1200 kg/cm Cu
b) Calcul termic, per intensitate admis
Ical = 60.89 A
Iadm = 185 A
c) Verificare per solicitare termic scurtcircuit
Ipcc = 3.51 kA
Icccs = Kc S / ( 1000 tcc) = 164 40 1 / (1000 0.5) = 9.28 kA
3.4.6. REZULTATELEOBINUTE
Denumire
Put 2
put 5
P.Calcul
(W)
18750
18750
Put 2
put 5
Lungime
(m)
505
592
Dist.Calcul
(m)
505
592
Seciune
(mm)
4x35Cu
4x35Cu
I.Calcul I.Admis
(A)
(A)
33.83
117
33.83
117
C.T.Parc.
(%)
3.33
3.91
C.T.Total
(%)
3.38
3.96
ntrerupere
Denumire
Seciune
(mm)
4x35Cu
4x35Cu
IpccI (kA)
P de C
(kA)
3.52
4.5
3.52
4.5
IpccF
(A)
252.77
218.3
tmcicc
(sg)
392.06
525.67
tficc
(sg)
Lmx
(m)
Curbe
valabile
40;B
40;B
29
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.5. CALCULELINIEJOASATENSIUNETRF(PTA5716)
3.5.1. CEREREDEPUTERI
- Putere total instalat:
Put 20
Put 19
Put 18
Put 17
Put 16
TOTAL....
18500 W
15000 W
18500 W
15000 W
15000 W
82000 W
3.5.2. CALCULDERIVAIEINDIVIDUAL
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Mult.Conductoare ngropate
- Lungime: 4 m; Cos : 0.8; Xu(m/m): 0;
- Putere la instalare: 82000 W.
- Putere de calcul:
18500x1.25+63500=86625 W.(Coeficient de Simultaneitate: 1 )
I=86625/1,732x400x0.8=156.3 A.
Se aleg conductoare Unipolare 4x70mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 170 A.
Diametru exterior tub: 125 mm.
Cdere de tensiune:
Temperatur cablu (C): 82.26
e(parial)=4x86625/44.66x400x70=0.28 V.=0.07 %
e(total)=0.07% ADMIS (4.5% MAX.)
Protecie Termic:
Intensitate Automat: 160 A. Termic Reglarea intensitii: 160 A.
3.5.3. CALCULLINIE:PUT20
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 327 m; Cos : 0.8; Xu(m/m): 0; R: 1
30
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.5.4. CALCULLINIE:PUT19
- Tensiune de serviciu: 400 V.
- Canalizare: D-Unipolar su Multi Conductor ngropat
- Lungime: 65 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x6mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 44 A.
Diametru exterior tub: 90mm.
Cdere de tensiune:
Temperatur cablu (C): 69.56
e(parial)=65x18750/46.52x400x6x1=10.92 V.=2.73 %
e(total)=2.8% ADMIS (6.5% MAX.)
Protecie Termic:
Intensitate Magnetic ntreruptor Tetrapolar . 40 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial. 40 A. Sens. Int.: 300 mA. Clasa AC.
3.5.5. CALCULLINIE:PUT18
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductori ngropat
- Lungime: 255 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 18500 W.
- Putere de calcul:
18500x1.25=23125 W.
31
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
I=23125/1,732x400x0.8x1=41.72 A.
Se aleg conductoare Tripolare 4x25mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 96 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 49.44
e(parial)=255x23125/49.81x400x25x1=11.84 V.=2.96 %
e(total)=3.03% ADMIS (6.5% MAX.)
Protecie Termic:
Intensitate Magnetic ntreruptor Tetrapolar 50 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial.: 63 A. Sens. Int.: 300 mA. Clasa AC.
3.5.6. CALCULLINIE:PUT17
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductor ngropat
- Lungime: 559 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x35mmCu
Nivel Izolaie, Izolaie: 0.6/1 kV, XLPE.
Intensitate admis la 25C (Fc=1) 117 A.
Diametru exterior tub: 90 mm.
Cdere de tensiune:
Temperatur cablu (C): 44.18
e(parial)=559x18750/50.75x400x35x1=14.75 V.=3.69 %
e(total)=3.76% ADMIS (6.5% MAX.)
Protecie termic:
Intensitate Magnetic ntreruptor Tetrapolar. 40 A.
Protecie diferenial:
Intensitate ntreruptor Tetrapolar Diferenial.: 40 A. Sens. Int.: 300 mA. Clasa AC.
3.5.7. CALCULLINIE:PUT16
- Tensiune de funcionare: 400 V.
- Canalizare: D-Unipolar sau Multi Conductori ngropat
- Lungime: 859 m; Cos : 0.8; Xu(m/m): 0; R: 1
- Putere la instalare: 15000 W.
- Putere de calcul:
15000x1.25=18750 W.
I=18750/1,732x400x0.8x1=33.83 A.
Se aleg conductoare Tripolare 4x50mmCu
32
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
CONTRACTORUL:
3.5.8. CALCULBARECOLECTOARETABLOUGENERALDECONTROLIPROTECIE
3.5.8.1. DATE
- Metal: Cu
- Starea plcuelor: dezvelite
- numr plcue per faz: 1
- Desprirea ntre plcue, d(cm): 10
- Desprirea ntre supori, L(cm): 25
- Timp durat c.c. (s): 0.5
3.5.8.2. PLCUADOPTAT
- Seciune (mm): 60
- Lime (mm): 20
- Grosime (mm): 3
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.2, 0.2, 0.03, 0.0045
- I. admis a barelor colectoare (A): 220
a) Calcul electrodinamic
max = Ipcc L / ( 60 d Wy n) =5.66 25 /(60 10 0.03 1) = 1112.093 <= 1200 kg/cm Cu
b) Calcul termic, per intensitate admis
Ical = 156.3 A
Iadm = 220 A
c) Verificare per solicitare termic n ntrerupere
Ipcc = 5.66 kA
Icccs = Kc S / ( 1000 tcc) = 164 60 1 / (1000 0.5) = 13.92 kA
3.5.9. REZULTATELEOBINUTE
33
BREVIARDECALCULELECTRIC
OBIECTULCONTRACTULUI: AUTORITATEACONTRACTANTA:
Reabilitareastatieidetratare
aapeipotabilesifrontuluide
captaredinlocalitateaDoba
Denumire
Put 20
Put 19
Put 18
Put 17
Put 16
P. Calcul
(W)
23125
18750
23125
18750
18750
Dist.Calcul
(m)
327
65
255
559
859
Seciune
(mm)
4x25Cu
4x6Cu
4x25Cu
4x35Cu
4x50Cu
I.Calcul
I.Admis
(A)
(A)
41.72
96
33.83
44
41.72
96
33.83
117
33.83
138
CONTRACTORUL:
C.T.Parc. C.T.Total
(%)
(%)
3.8
3.86
2.73
2.8
2.96
3.03
3.69
3.76
3.95
4.02
ntrerupere
Denumire
Put 20
Put 19
Put 18
Put 17
Put 16
Lungime
(m)
327
65
255
559
859
Seciune
IpccI (kA)
(mm)
4x25Cu
5.68
4x6Cu
5.68
4x25Cu
5.68
4x35Cu
5.68
4x50Cu
5.68
P de C
(kA)
6
6
6
6
6
IpccF
(A)
288.35
344.55
364.55
238.25
222.11
tmcicc
(sg)
153.72
6.2
96.17
441.3
1036.28
tficc
(sg)
L max.
(m)
Curbe
valabile
50;B
40;B
50;B
40;B
40;B
34