Wenner Four Pin Method for Soil Resistivity Test


(http://hurricane193.files.wordpress.com/2013/09/05-wenner-4-pointtest.jpg)Before design grounding system for the plant, soil resistivity shall determine first. This value of soil resistant will be an input in designing grounding system later (i.e. substation grounding, engine hall grounding and pump house grounding). To determine the soil resistivity value, there are several steps to be done. First of all we will discuss a method used to determine the soil resistivity value. This method known as Wenner four-pin method, developed by Dr. Frank Wenner, US Bureau of Standards in 1915. On these methods used four electrodes, two for current injection and two for voltage measurement. The four electrodes embedded to the ground in straight line, the two outer electrodes are current electrode and two inner electrodes to measure voltage drop due to resistance of soil path when current passed between the outer electrodes.

(http://hurricane193.files.wordpress.com/2013/09/wenner-4-pin-method.jpg)Figure 1. Wenner Four Pin Arrangement


hurricane193.wordpress.com/2013/09/08/wenner-four-pin-method-for-soil-resistivity-test/ 1/4

11/16/13

Wenner Four Pin Method for Soil Resistivity Test | My little world

The resistance can be measure and resistivity calculated according the following formula.

(http://hurricane193.files.wordpress.com/2013/09/sr-formula.jpg) Where: = Resistivity in Ohm-cm a = spacing between pin in cm R = Resistance measurement in Ohm The depth of electrode shall not exceed the value of a/20 It should be noted that measurement made in this manner indicate average resistivity over a depth of soil corresponding to the spacing between adjacent pin/electrode. Before perform the test, please take attention to the below condition: 1. Prepare the coordinate to be tested. This coordinate normally located at the equipment (i.e. substation, turbine hall, compressor area and pump house) location. 2. This test is better to perform in flat location, for 10 meter depth assessment needed 30 meter flat area. 3. Cable path shall not crossing any metallic material.

(http://hurricane193.files.wordpress.com/2013/09/wenner-method-principle.jpg)Figure 2. Wenner Method Work Priciple The following step used to test the soil resistivity in this method: 1. Placed the soil resistivity measure equipment on the center of the assessment location. 2. Put two potential electrode on the left and right side point of view based on the distance test required. This electrode embedded from 5 to 10 cm to ground, based on the soil condition. 3. Put two current electrode on the left and right side point of view based on the distance test required. This electrode embedded from 5 to 10 cm to ground based on the soil condition. 4. Connect all electrodes cable with the soil resistivity measuring equipments. 5. Energize the electrode with the power supply form soil resistance measuring equipments. 6. Please make sure no one touch the electrode when the electrode energize.
hurricane193.wordpress.com/2013/09/08/wenner-four-pin-method-for-soil-resistivity-test/ 2/4

11/16/13

Wenner Four Pin Method for Soil Resistivity Test | My little world

7. The value of soil resistivity will calculate and appear on the soil resistivity measuring equipment LCDs or monitor. Repeat step 2 until step 6 based on the depth required.

(http://hurricane193.files.wordpress.com/2013/09/soil-resistivity-test1.jpg)Figure 3. Soil Resistivity Test Any comment and discussion, please fill the comment field below Reference: NEEC Soil Resistivity

You May Like


1.

About these ads (http://en.wordpress.com/aboutthese-ads/)

This entry was posted in My Story and tagged compressor grounding, Earthing, engine hall grounding, Frank Wenner, Grounding, Procedure for Soil Soil Resistivity Test, pump house grounding, Soil Resistance, Soil Resistivity, Soil Resistivity Test, substation grounding, turbine hall, turbine hall grounding, Wenner Method, Wenner Soil Resistivity Test Method. Bookmark the permalink. Blog at WordPress.com. | The Misty Lake Theme. Follow
hurricane193.wordpress.com/2013/09/08/wenner-four-pin-method-for-soil-resistivity-test/ 3/4

11/16/13

Wenner Four Pin Method for Soil Resistivity Test | My little world

Follow My little world


Powered by WordPress.com

hurricane193.wordpress.com/2013/09/08/wenner-four-pin-method-for-soil-resistivity-test/

4/4

S-ar putea să vă placă și