Sunteți pe pagina 1din 13

PAGE 5 OF 5

EXTERNAL STATIC PRESSURE CALCULATION


PROJECT

DUBAI MARINA 2N TOWER

CLIENT

EMAAR

CONSULTANT

KHATIB & ALAMI

MAIN CONTRACTOR

UNEC

A/C CONTRACTOR

Emirates Trading Agency L.L.C., dubai

SL NO

REF

14.02.2005

AHU REF

AHU -2 ( Banch take off )

DRAWING REF.

MAIN DUCT BRANCH DUCT

CFM ( A )

DATE

RATIO

BRANCH
DUCT SIZE
(INCH )

BRANCH DUCT
TOTAL S.P. LOSS

REMARKS

VELOCITY

CFM ( B )

(R=B/A)

FPM

( IWG )

6700

3910

0.58

26

12

1805

0.1600

3910

2610

0.67

26

16

903

0.0400

2610

1590

0.61

20

14

818

0.0350

1020

255

0.25

453

0.0110

765

255

0.33

453

0.0110

510

255

0.50

453

0.0110

2610

0.39

26

16

903

0.0420

SUB TOTAL

0.3100

1
2

Supply air Banch take off :


Mezzanine

3
4
5

8
9

Ground

Return air Banch take off :


Mezzanine

6700

10
11
12
13
14
15
16
17
18
19
20

EXTERNAL STATIC PRESSURE CALCULATION

PAGE 4 OF 5

DUBAI MARINA 2N TOWER

DATE

14.02.2005

EMAAR

AHU REF

AHU -2 ( Fresh Air )

CONSULTANT

KHATIB & ALAMI

DRAWING REF.

MAIN CONTRACTOR

UNEC

A/C CONTRACTOR

Emirates Trading Agency L.L.C., dubai

PROJECT
CLIENT

INITIAL
SL NO

REF

SIZE
SIZE (INCH)

FINAL

DUCT
WORK
REFERENCE

At Level 2 Straight Piece

(INCH )

INITIAL
FINAL
VOLUME
VELOCITY VELOCITY
OF AIR
PRESSURE PRESSURE

S.P. TO
CHANGE IN
VELOCITY
PRESSURE

STRAIGHT /

S.P. LOSS
TOTAL S.P.
PER 100 FT
EQUIVALENT
QTY
LENGTH OF
LENGTH
DUCT
LOSS

( CFM )

( hv1 )

( hv2 )

( IWG )

( FT )

( IWG )

12

10

12

10

600

0.0323

0.0323

0.0000

0.080

0.0040

6
_

0.080
_

0.0048

0.0000

Elbow

12

10

12

10

600

0.0323

0.0323

0.0000

Expansion

12

10

600

0.0323

0.1136

0.0000

( IWG )

Sub Total
`

0.009

4 OF 5

sh Air )

REMARKS

S.P.regain ignored

EXTERNAL STATIC PRESSURE CALCULATION

PAGE 3 OF 5

DUBAI MARINA 2N TOWER

DATE

14.02.2005

EMAAR

AHU REF

AHU -1 ( RETURN )

CONSULTANT

KHATIB & ALAMI

DRAWING REF.

MAIN CONTRACTOR

UNEC

A/C CONTRACTOR

Emirates Trading Agency L.L.C., dubai

PROJECT
CLIENT

INITIAL
SL NO

REF

SIZE
SIZE (INCH)

Ground

FINAL

DUCT
WORK
REFERENCE

Straight Piece

(INCH )

INITIAL
FINAL
VOLUME
VELOCITY VELOCITY
OF AIR
PRESSURE PRESSURE

S.P. TO
CHANGE IN
VELOCITY
PRESSURE

STRAIGHT /

S.P. LOSS
TOTAL S.P.
PER 100 FT
EQUIVALENT
QTY
LENGTH OF
LENGTH
DUCT
LOSS

( CFM )

( hv1 )

( hv2 )

( IWG )

( FT )

( IWG )

26

16

26

16

2790

0.0581

0.0581

0.0000

0.070

0.0028

26

16

2790

0.0581

0.0581

0.0000

11

0.070

0.0077

0.1280

( IWG )

Elbow

26

16

Return Air grill

26

16

Mezzanine Straight Piece

26

16

26

16

2790

0.0581

0.0581

0.0000

24

0.070

0.0168

Elbow
Fire Damper

26

16

26

16

2790

0.0581

0.0581

0.0000

11

0.070

0.0077

26

16

0.0400

Straight Piece

24

38

24

38

6700

0.0698

0.0698

0.0000

16.5

0.050

0.0083

Elbow
Fire Damper

24

38

24

38

6700

0.0698

0.0698

0.0000

20

0.070

0.0140

24

38

6700

0.0400

34

24

34

24

6700

0.0872

0.0872

0.0000

50

0.050

0.0250

Elbow
Fire Damper

34

24

34

24

6700

0.0872

0.0872

0.0000

24

0.050

0.0120

34

24

6700

0.0400

Contraction

38

24

18

18

3760

0.0220

0.1741

0.1552

0.1552

5
6

At Level 1 Straight Piece

2790

2790

Sub Total
`

0.497

3 OF 5

URN )

REMARKS

S.P.LOSS=1.02(hv2-hv1)

EXTERNAL STATIC PRESSURE CALCULATION

PAGE 2 OF 5

DUBAI MARINA 2N TOWER

DATE

14.02.2005

EMAAR

AHU REF

AHU -1 ( SUPPLY )

CONSULTANT

KHATIB & ALAMI

DRAWING REF.

MAIN CONTRACTOR

UNEC

A/C CONTRACTOR

Emirates Trading Agency L.L.C., dubai

PROJECT
CLIENT

INITIAL
SL NO

REF

FINAL

DUCT
WORK
REFERENCE

SIZE
SIZE (INCH)

(INCH )

INITIAL
FINAL
VOLUME
VELOCITY VELOCITY
OF AIR
PRESSURE PRESSURE

S.P. TO
CHANGE IN
VELOCITY
PRESSURE

STRAIGHT /

S.P. LOSS
TOTAL S.P.
PER 100 FT
EQUIVALENT
QTY
LENGTH OF
LENGTH
DUCT
LOSS

( CFM )

( hv1 )

( hv2 )

( IWG )

( FT )

( IWG )

( IWG )

Straight Piece

12

10

12

10

510

0.0234

0.0234

0.0000

10

0.060

0.0060

Elbow

12

10

12

10

510

0.0234

0.0234

0.0000

0.060

0.0036

Straight Piece

12

12

255

0.0162

0.0162

0.0000

10

0.055

0.0055

Elbow
Supply air

12

12

255

0.0162

0.0162

0.0000

0.055

0.0022

diffuser

12

12

255

0.1880

Sub Total

0.2053

Sub Total of page 1/5

0.5770

Sub Total of AHU-2 Return ( Ref: Page 3/5)

0.4970

Sub Total of AHU- 2 Fresh air ( Ref: Page 4/5)

0.0090

Sub Total of branch take off ( Ref: Page 5/5)

0.3100

TOTAL

1.5983

SFETY FACTOR 12.5 %

0.1998

GRAND TOTAL

1.7981

SELECTED ESP

1.80

2 OF 5

PPLY )

REMARKS

EXTERNAL STATIC PRESSURE CALCULATION

PAGE 1 OF 5

DUBAI MARINA 2N TOWER

DATE

14.02.2005

EMAAR

AHU REF

AHU -2 ( SUPPLY )

CONSULTANT

KHATIB & ALAMI

DRAWING REF.

MAIN CONTRACTOR

UNEC

A/C CONTRACTOR

Emirates Trading Agency L.L.C., dubai

PROJECT
CLIENT

INITIAL
SL NO

REF

FINAL

DUCT
WORK
REFERENCE

SIZE
SIZE (INCH)

(INCH )

INITIAL
FINAL
VOLUME
VELOCITY VELOCITY
OF AIR
PRESSURE PRESSURE

S.P. TO
CHANGE IN
VELOCITY
PRESSURE

STRAIGHT /

S.P. LOSS
TOTAL S.P.
PER 100 FT
EQUIVALENT
QTY
LENGTH OF
LENGTH
DUCT
LOSS

( CFM )

( hv1 )

( hv2 )

( IWG )

( FT )

( IWG )

Straight Piece

38

24

38

24

6700

0.0698

0.0698

0.0000

34

0.050

0.0170

Expansion

18

18

38

24

6700

0.5528

0.0698

0.0000

0.0000

Elbow

38

24

38

24

6700

0.0698

0.0698

0.0000

21

0.050

0.0525

Sound
attenuator

38

24

6700

0.3000

Fire Damper

38

24

6700

0.0800

Straight Piece

38

24

38

24

6700

0.0698

0.0698

0.0000

11

0.050

0.0055

Mezzanine Straight Piece

38

24

38

24

6700

0.0698

0.0698

0.0000

13

0.050

0.0065

Elbow

38

24

38

24

6700

0.0698

0.0698

0.0000

21

0.050

0.0105

11

Fire Damper

38

24

6700

0.0400

12

Straight Piece

26

22

26

22

3910

0.0604

0.0604

0.0000

20

0.060

0.0120

13

Straight Piece

26

16

26

16

2610

0.0509

0.0509

0.0000

10

0.060

0.0060

14

Elbow

26

16

26

16

2610

0.0509

0.0509

0.0000

11

0.060

0.0066

26

16

26

16

2610

0.0509

0.0509

0.0000

12

0.060

0.0072

15

Level 1

Ground Straight Piece

( IWG )

16

Contraction

26

16

22

10

1020

0.0078

0.0278

0.0204

0.0204

17

Straight Piece

22

10

22

10

1020

0.0278

0.0278

0.0000

15

0.055

0.0083

18

Elbow

22

10

22

10

1020

0.0278

0.0278

0.0000

0.055

0.0044

19

Contraction

22

10

16

10

765

0.0156

0.0296

0.0142

0.0142

20

Straight Piece

16

10

16

10

765

0.0296

0.0296

0.0000

10

0.065

0.0065

21

Elbow

16

10

16

10

765

0.0296

0.0296

0.0000

0.065

0.0039

Sub Total

0.577

1 OF 5

PPLY )

REMARKS

S.P.regain ignored

S.P.LOSS=1.02(hv2-hv1)

S.P.LOSS=1.02(hv2-hv1)

S-ar putea să vă placă și