Sunteți pe pagina 1din 16

PROIECT

MANAGEMENTUL ENERGIEI
Marian kos
1741

1.) Se consider reeaua de distribuie a unui consumator industrial racordat la sistemul energetic
naional printr-o staie de transformare 110/6kV cu puterea de 16 MVA. S se determine:
a.) Dimensionarea trasformatorului T1
b.) Varianta optim de compensare a puterii reactive (punctul de delimitare fiind bara de 110 kV).

Se d:
M1:

PM1=2500 kW

lM1=0.89

M2:

PM2=1000 kW

lM2=0.87

M3:

PM3=2500 kW

lM3=0.89

L1:

(2x3x120) Al - 740 m

L2:

(3x3x150) Al - 1184 m

L3:

(3x240) Al - 888 m

L4:

(2x3x240) Al - 740 m

L5:

(3x3x150) Al - 1480 m

L6:

(3x3x120) Al - 1184 m

Cons1=(400+j300)(1.2)=480+j360 kVA
Cons4=(1400+j1000)(1.2)=1680+j1200 kVA
Cons5=(800+j500)(1.2)=960+j600 kVA
Cons7=(1000+j700)(1.2)=1200+j840 kVA
Obs. Put. aparent complex=Put. act + j*Put. react.

a.) Cons1=480+j360 kVA


P=480 kW;
Q=360 kVAr;

Tabel 1. Parametrii transformatoare/cabluri

Transformatoare
ST

DPFe

U1/U2

Cabluri
DPCu

usc

i0

r0

x0

Y0

(kVA)

(kV)

(kW)

(kW)

(%)

(%)

(mm )

(/km)

(/km)

(S/km)

630
1000
1600
16000

6/0,4
6/0,4
6/0,4
110/6

1,3
1,7
2,6
24

8,4
13
20
97

4
6
6
11

1,8
1,5
1,4
1,2

120
150
240

0,257
0,204
0,133

0,08
0,08
0,08

0,000144
0,00017
0,00033

Tabel 2.1 Parametrii transformatoarelor:

ST [kVA]

630

2000

1600

16000

ur [%]

1,3333

1,3000

1,2500

0,606

ux [%]

3,7712

5,8575

5,8683

10,983

DQFe [kVAr]

11,3400

15,0000

22,4000

192

Tabel 2.2 Parametrii liniilor:

Tronson
L1 (1-7)
L2 (2-8)
L3 (3-9)
L4 (4-10)
L5 (5-11)
L6 (6-12)

Nr. Lin. Paral. Nr. Faze

r0

x0

Y0

(mm )

(km)

(/km)

(/km)

(S/km)

()

()

(S)

120
150
240
240
150
120

0,74
1,184
0,888
0,74
1,48
1,184

0,257
0,204
0,133
0,133
0,204
0,257

0,08
0,08
0,08
0,08
0,08
0,08

0,000144
0,000170
0,000330
0,000330
0,000170
0,000144

0,0951
0,0805
0,1181
0,0492
0,1006
0,1014

0,0296
0,0316
0,0710
0,0296
0,0395
0,0316

0,000213
0,000604
0,000293
0,000488
0,000755
0,000511

2
3
1
2
3
3

3
3
3
3
3
3

Tabel 3. Puterile consumatorilor (P,S,Q)

Consumator
Cons. 1
Cons. 2 (M1)
Cons. 3 (M2)
Cons. 4
Cons. 5
Cons. 6 (M3)
Cons. 7

Pc

Qc

Sc

(kW)

(kVAr)

(kVA)

(V)

480
2500
1000
1680
960
2500
1200

360,00
1280,79
566,73
1200,00
600,00
1280,79
840,00

600,00
2808,99
1149,43
2064,56
1132,08
2808,99
1464,79

0,80
0,89
0,87
0,81
0,85
0,89
0,82

0,40
6,00
6,00
6,00
0,40
6,00
0,40

Tabel 4.Rezistena/Reactaa echivalent transformatoarelor i pierderile de putere reactiv n Fe a


transformatoarelor

ST

DPFe

DPCu

usc

(kVA)

(kW)

(kW)

630
2000
1600
16000

1,3
1,7
2,6
24

8,4
13
20
97

i0

(%)

(%)

(kV)

4
6
6
11

1,8
1,5
1,4
1,2

6,0
6,0
6,0
110,0

ur

ux

(%)

(%)

1,3333 3,7712
1,3000 5,8575
1,2500 5,8683
0,6060 10,9830

Rtrafo

Xtrafo

DQFe

()

()

(kVAr)

0,7619 2,1550
0,2340 1,0543
0,2813 1,3204
4,5829 83,0589

11,34
15
22,4
192

Tabel 5. Pierderile de putere activ/reactiv a transformatoarelor

Trafo
T1 (cons1)
T2 (cons5)
T3 (cons7)

DPFe

DQFe

Un

XT

RT

DPtrafo

DQtrafo

(kW)

(kW)

(kVAr)

(kV)

()

()

(kW)

(kVAr)

480
960
1200

1,3
2,6
3,4

11,34
22,4
30

6,0
6,0
6,0

0,80
0,85
0,82

2,1550
1,3204
1,0543

0,7619
0,2813
0,2340

8,92
12,61
17,35

32,89
69,41
92,84

Tabel 6. Puterile totale i factorul de putere n punctele 7,8,9,10,11,12

Punct 7
Punct 8
Punct 9
Punct 10'
Punct 10
Punct 11

Pc
(kW)
480
2500
1000
1680
960
2500

Qc
(kVAr)
360,000
1280,788
566,726
1200,000
600,000
1280,788

DPtrafo DQtrafo
l
Sc
PT
QT
ST
(kVA)
(kW)
(kVAr)
(kVA)
(kW)
(kVAr)
600,000 8,919 32,890 488,919 392,890 627,220 0,78
2808,989 0,000 0,000 2500,000 1280,788 2808,989 0,89
1149,425 0,000 0,000 1000,000 566,726 1149,425 0,87
2064,558 0,000 0,000 1680,000 1200,000 2064,558 0,81
1132,078 12,613 69,405 972,613 669,405 1180,711 0,82
2808,989 0,000 0,000 2500,000 1280,788 2808,989 0,89

Punct 12

1200

840,000

1464,787 17,346 92,839 1217,346

Punct

932,839

1533,663 0,79

Tabel 7. Pierderi de putere activ/reactiv a liniilor i aportul capacitiv al cablurilor

Linie
L1
L2
L3
L4
L5
L6

DPlinie

DQlinie

QC

(kW)

(kV)

()

()

(S)

(kW)

(kVAr)

(kVAr)

488,919
2500,000
1000,000
2652,613
2500,000
1217,346

6
6
6
6
6
6

0,78
0,89
0,87
0,82
0,89
0,79

0,0951
0,0805
0,1181
0,0492
0,1006
0,1014

0,0296
0,0316
0,0710
0,0296
0,0395
0,0316

0,0002
0,0006
0,0003
0,0005
0,0008
0,0005

1,039
17,646
4,334
14,395
22,058
6,627

0,323
6,920
2,607
8,659
8,650
2,063

7,672
21,738
10,549
17,582
27,173
18,414

obs. L4-P=Pcons4+Pcons5+PierdTrans, Fact. de put=P/Scons4+Scons5.

Tabel 8. Puterile totale i factorul de putere n punctele 1,2,3,4,5,6

Punct
Punct 1
Punct 2
Punct 3
Punct 4
Punct 5
Punct 6

DPlinie DQlinie
PT
QT
ST
(kW)
(kVAr)
(kVA)
(kW)
(kVAr)
488,919 392,890 627,220 1,039 0,323
2500,000 1280,788 2808,989 17,646 6,920
1000,000 566,726 1149,425 4,334 2,607
2652,613 1869,405 3245,155 14,395 8,659
2500,000 1280,788 2808,989 22,058 8,650
1217,346 932,839 1533,663 6,627 2,063

QC
(kVAr)

7,672
21,738
10,549
17,582
27,173
18,414

l
Ptotal
Qtotal
Stotal
(kW)
(kVAr)
(kVA)
489,958 385,541 623,459 0,79
2517,646 1265,970 2818,018 0,89
1004,334 558,784 1149,316 0,87
2667,008 1860,482 3251,819 0,82
2522,058 1262,265 2820,300 0,89
1223,973 916,488 1529,072 0,80

Tabel 9.

Total:

Ptotal

Qtotal

Stotal

(kW)

(kVAr)

(kVA)

10424,98

6249,53

12154,70

0,858

Tabel 10. Pierderile de putere activ/reactiv a transformatorului de ST =1,6 MVA

DPFe

DQFe

Rtrafo

Xtrafo

DPtrafo

DQtrafo

(kW)

(kV)

(kW)

(kVAr)

()

()

(kW)

(kVAr)

10424,98

110,00

0,86

24,00

192,00

4,5829

83,0589

79,96

1206,12

Tabel 11. Puterile i factorul de putere n punctul de delimitare


Rezultate in
punctul de
delimitare:

Ptotal

Qtotal

(kW)

(kVAr)

10504,93

7455,65

Stotal
(kVA)

12881,78437

l
-

0,8155

b.)

lnatural=0.83 (factorul de putere existent, nainte de compensare)


lneutral=0.92

(factorul de putere dorit, dup compensare)

Soluia I.

))

lnatural

lneutral

QBC

Qales

(kW)

(kVAr)

(kVAr)

0,82

0,92

10504,93

2980,57

3000

Consumator
Cons. 1
Cons. 2 (M1)
Cons. 3 (M2)
Cons. 4
Cons. 5
Cons. 6 (M3)
Cons. 7

Trafo

Pc

Qc

Qcond

Qnou

Sc(nou)

(kW)

(kVAr)

(kVAr)

(kVAr)

(kVA)

480
2500
1000
1680
960
2500
1200

360,00
1280,79
566,73
1200,00
600,00
1280,79
840,00

100,00
750,00
400,00
400,00
200,00
750,00
400,00

260,00
530,79
166,73
800,00
400,00
530,79
440,00

545,89
2555,73
1013,80
1860,75
1040,00
2555,73
1278,12

0,879
0,978
0,986
0,903
0,923
0,978
0,939

Total:

3000,00

DPFe

DQFe

Un

XT

RT

DPtrafo

DQtrafo

(kW)

(kW)

(kVAr)

(kV)

()

()

(kW)

(kVAr)

T1 (cons1)
T2 (cons5)
T3 (cons7)

480
960
1200

1,30
2,60
3,40

11,34
22,40
30,00

6,00
6,00
6,00

0,88
0,92
0,94

2,1550
1,3204
1,0543

0,7619
0,2813
0,2340

7,61
11,05
14,02

29,18
62,07
77,84

Punct

Pc

Qc(nou)

Sc(nou)

DPtrafo

DQtrafo

PT

QT

ST

(kW)

(kVAr)

(kVA)

(kW)

(kVAr)

(kW)

(kVAr)

(kVA)

480
2500
1000
1680
960
2500
1200

260,000
530,788
166,726
800,000
400,000
530,788
440,000

487,607
2500,000
1000,000
1680,000
971,050
2500,000
1214,018

289,179
530,788
166,726
800,000
462,070
530,788
517,844

566,908
2555,726
1013,804
1860,753
1075,382
2555,726
1319,850

0,86
0,98
0,99
0,90
0,90
0,98
0,92

Punct 7
Punct 8
Punct 9
Punct 10'
Punct 10
Punct 11
Punct 12

545,894 7,607 29,179


2555,726 0,000 0,000
1013,804 0,000 0,000
1860,753 0,000 0,000
1040,000 11,050 62,070
2555,726 0,000 0,000
1278,124 14,018 77,844

Linie

(kW)

(kV)

()

()

L1
L2
L3
L4
L5
L6

487,607
2500,000
1000,000
2651,050
2500,000
1214,018

6
6
6
6
6
6

0,86
0,98
0,99
0,90
0,98
0,92

0,0951
0,0805
0,1181
0,0492
0,1006
0,1014

0,0296
0,0316
0,0710
0,0296
0,0395
0,0316

Punct
Punct 1
Punct 2
Punct 3
Punct 4
Punct 5
Punct 6

DPlinie DQlinie
PT
QT
ST
(kW)
(kVAr)
(kVA)
(kW)
(kVAr)
487,607 289,179 566,908 0,849 0,264
2500,000 530,788 2555,726 14,608 5,729
1000,000 166,726 1013,804 3,372 2,028
2651,050 1262,070 2936,135 11,784 7,088
2500,000 530,788 2555,726 18,260 7,161
1214,018 517,844 1319,850 4,908 1,528

Total:

DPlinie

DQlinie

QC

(S)

(kW)

(kVAr)

(kVAr)

0,0002
0,0006
0,0003
0,0005
0,0008
0,0005

0,849
14,608
3,372
11,784
18,260
4,908

0,264
5,729
2,028
7,088
7,161
1,528

7,672
21,738
10,549
17,582
27,173
18,414

QC
(kVAr)

7,672
21,738
10,549
17,582
27,173
18,414

l
Ptotal
Qtotal
Stotal
(kW)
(kVAr)
(kVA)
488,456 281,770 563,900 0,87
2514,608 514,778 2566,759 0,98
1003,372 158,205 1015,768 0,99
2662,834 1251,576 2942,300 0,91
2518,260 510,776 2569,538 0,98
1218,926 500,958 1317,855 0,92

Ptotal

Qtotal

Stotal

(kW)

(kVAr)

(kVA)

10406,46

3218,06

10892,670

0,9554

DPFe

DQFe

Rtrafo

Xtrafo

DPtrafo

DQtrafo

(kW)

(kV)

(kW)

(kVAr)

()

()

(kW)

(kVAr)

10406,46

110,00

0,96

24,00

192,00

4,5829

83,0589

68,94

1006,46

Rezultate in
punctul de
delimitare:

Ptotal

Qtotal

Stotal

(kW)

(kVAr)

(kVA)

10475,39

4224,52

11295,154

0,9274

Soluia II.

lnatural

lneutral

QBC

Qales

(kW)

(kVAr)

(kVAr)

0,82

0,92

10504,93

2980,57

3000

Consumator
Cons. 1
Cons. 2 (M1)
Cons. 3 (M2)
Cons. 4
Cons. 5
Cons. 6 (M3)
Cons. 7

Pc

Qc

Qcond

Qnou

Sc(nou)

(kW)

(kVAr)

(kVAr)

(kVAr)

(kVA)

480
2500
1000
1680
960
2500
1200

360,00
1280,79
566,73
1200,00
600,00
1280,79
840,00
Total:

0,00
300,00
300,00
500,00
0,00
250,00
0,00
3000,00

360,00
980,79
266,73
700,00
600,00
1030,79
840,00

600,00
2685,51
1034,96
1820,00
1132,08
2704,17
1464,79

0,800
0,931
0,966
0,923
0,848
0,924
0,819

DPFe

DQFe

Un

XT

RT

DPtrafo

DQtrafo

(kW)

(kW)

(kVAr)

(kV)

()

()

(kW)

(kVAr)

T1 (cons1)
T2 (cons5)
T3 (cons7)

480
960
1200

1,30
2,60
3,40

11,34
22,40
30,00

6,00
6,00
6,00

0,80
0,85
0,82

2,1550
1,3204
1,0543

0,7619
0,2813
0,2340

8,92
12,61
17,35

32,89
69,41
92,84

Punct

Pc

Qc(nou)

Sc(nou)

DPtrafo

DQtrafo

PT

QT

ST

(kW)

(kVAr)

(kVA)

(kW)

(kVAr)

(kW)

(kVAr)

(kVA)

480
2500
1000
1680
960
2500
1200

360,000
980,788
266,726
700,000
600,000
1030,788
840,000

Trafo

Punct 7
Punct 8
Punct 9
Punct 10'
Punct 10
Punct 11
Punct 12

600,000 8,919 32,890


2685,506 0,000 0,000
1034,960 0,000 0,000
1820,000 0,000 0,000
1132,078 12,613 69,405
2704,168 0,000 0,000
1464,787 17,346 92,839

Linie

(kW)

(kV)

()

()

L1
L2
L3
L4
L5
L6

488,919
2500,000
1000,000
2652,613
2500,000
1217,346

6
6
6
6
6
6

0,78
0,93
0,97
0,89
0,92
0,79

0,0951
0,0805
0,1181
0,0492
0,1006
0,1014

0,0296
0,0316
0,0710
0,0296
0,0395
0,0316

Punct
Punct 1
Punct 2
Punct 3
Punct 4
Punct 5
Punct 6

488,919 392,890 627,220


2500,000 980,788 2685,506
1000,000 266,726 1034,960
1680,000 700,000 1820,000
972,613 669,405 1180,711
2500,000 1030,788 2704,168
1217,346 932,839 1533,663

DPlinie

DQlinie

QC

(S)

(kW)

(kVAr)

(kVAr)

0,0002
0,0006
0,0003
0,0005
0,0008
0,0005

1,039
16,129
3,514
12,182
20,443
6,627

0,323
6,325
2,114
7,327
8,017
2,063

7,672
21,738
10,549
17,582
27,173
18,414

DPlinie DQlinie
PT
QT
ST
(kW)
(kVAr)
(kVA)
(kW)
(kVAr)
488,919 392,890 627,220 1,039 0,323
2500,000 980,788 2685,506 16,129 6,325
1000,000 266,726 1034,960 3,514 2,114
2652,613 1369,405 2985,234 12,182 7,327
2500,000 1030,788 2704,168 20,443 8,017
1217,346 932,839 1533,663 6,627 2,063

10

0,78
0,93
0,97
0,92
0,82
0,92
0,79

QC
(kVAr)

7,672
21,738
10,549
17,582
27,173
18,414

l
Ptotal
Qtotal
Stotal
(kW)
(kVAr)
(kVA)
489,958 385,541 623,459 0,79
2516,129 965,375 2694,968 0,93
1003,514 258,290 1036,221 0,97
2664,794 1359,150 2991,391 0,89
2520,443 1011,632 2715,885 0,93
1223,973 916,488 1529,072 0,80

Ptotal

Qtotal

Qcond

Qnou

Stotal

(kW)

(kVAr)

(kVAr)

(kVAr)

(kVA)

10418,81

4896,48

1650,000

3246,477

10912,894

0,9547

Total:

DPFe

DQFe

Rtrafo

Xtrafo

DPtrafo

DQtrafo

(kW)

(kV)

(kW)

(kVAr)

()

()

(kW)

(kVAr)

10418,81

110,00

0,95

24,00

192,00

4,5829

83,0589

69,11

1009,49

Rezultate in
punctul de
delimitare:

Ptotal

Qtotal

Stotal

(kW)

(kVAr)

(kVA)

10487,92

4255,96

11318,553

0,9266

Determinarea Energiilor Consumate


P

DP

Ea

DEa

Eatot

(kW)

(h)

(kW)

(h)

(kW h/an)

(kW h/an)

(kW h/an)

1. nainte de compensare 10.320,00 6.600 184,93 0,8155 5.150 68.112.000,00 952.408,63 69.064.408,63
2. Soluia 1
10.320,00 6.600 155,39 0,9274 4.900 68.112.000,00 761.434,80 68.873.434,80
3. Soluia 2
10.320,00 6.600 167,92 0,9266 4.900 68.112.000,00 822.795,20 68.934.795,20

DQ

Qcablu

Er

DEr

Ecablu

Ertot

(kVAr)

(h)

(kVAr)

(h)

(kVAr)

(kVAr h/an)

(kVAr h/an)

(kVAr h/an)

(kVAr h/an)

1. n. de co.

6.025,17

6.600

1.430,48

0,8155

5.150

103,13

39.766.143,97

7.366.961,48

680.649,87

46.452.455,58

2. Soluia 1

3.025,17

6.600

1.199,35

0,9274

4.900

103,13

19.966.143,97

5.876.815,59

680.649,87

25.162.309,70

3. Soluia 2

3.025,17

6.600

1.230,79

0,9266

4.900

103,13

19.966.143,97

6.030.873,93

680.649,87

25.316.368,04

1. nainte de compensare
2. Soluia 1
3. Soluia 2

Energia Reactiv
Total

Energia Reactiv
consumat fr
plat

Energia Reactiv
consumat taxat

(kVAr h/an)

(kVAr h/an)

(kVAr h/an)

46.452.455,58
25.162.309,70
25.316.368,04

29.535.547,95
29.452.496,85
29.487.705,05

19.671.750,53
0,00
0,00

11

Determinarea Costurilor
Varianta NECOMPENSAT

Eatot
(kW h/an)

69.064.408,63

cEa
(lei/kW h)
0,5

CostEa
(lei/an)
34.532.204,32

Ertot taxat
(kVAr h/an)

19.671.750,53

cEr
(lei/kVAr h)
0,05

CostEr
(lei/an)
983.587,53

cEr
(lei/kVAr h)
0,05

CostEr comp
(lei/an)
0,00

cEr
(lei/kVAr h)
0,05

CostEr comp
(lei/an)
0,00

Varianta COMPENSAT
Soluia 1.
Ea comp
(kW h/an)

68.873.434,80

cEa
(lei/kW h)
0,5

CostEa comp
(lei/an)
34.436.717,40

Er taxat comp
(kVAr h/an)

0,00
Soluia 2.

Ea comp
(kW h/an)

68.934.795,20

cEa
(lei/kW h)
0,5

CostEa comp
(lei/an)
34.467.397,60

Er taxat comp
(kVAr h/an)

0,00

Chelt. Totale NECOMPENSAT


CostEa
(lei/an)
34.532.204,32

CostEr
(lei/an)
983.587,53

CostTOTAL
(lei/an)
35.515.791,84

Chelt. Totale COMPENSAT


Soluia 1.
CostEa comp
(lei/an)
34.436.717,40

CostEr comp
(lei/an)
0,00

CostTOTAL
(lei/an)
34.436.717,40

Ctig Soluia 1.
CostTOTAL necomp
(lei/an)
35.515.791,84

CostTOTAL comp
(lei/an)
34.436.717,40

12

DC
(lei/an)
1.079.074,44

Soluia 2.
CostEa comp
(lei/an)
34.467.397,60

CostEr comp
(lei/an)
0,00

CostTOTAL
(lei/an)
34.467.397,60

Ctig Soluia 2.
CostTOTAL necomp
(lei/an)
35.515.791,84

CostTOTAL comp
(lei/an)
34.467.397,60

DC
(lei/an)
1.048.394,24

Investiie
Soluia 1.

Soluia 2.

cbat

Qcond

(lei/kVAr)

(kVAr)

65

3000,00

I
(lei)
195.000,00

cbat

Qcond

(lei/kVAr)

(kVAr)

65

3000,00

Termenul de recuperare al investiiei

Soluia 1.
(an)

Solutia 2.
(an)
0,200820713

0,195039884

13

I
(lei)
195.000,00

Formule

Parametrii liniei se determin cu relaiile:


-rezistena liniei
-reactana liniei
-admitana liniei
-pierderi de putere activ

-pierderi de putere reactiv


-aportul capacitiv al cablurilor

Parametrii transformatoarelor se determin cu relaiile:


-Rezistena echivalent a transformatorului

-Reactana echivalent a transformatorului

-Componenta activ a tensiunii de scurtcircuit


- Componenta reactiv a tensiunii de scurtcircuit
-Pierderi de putere activ

-Pierderi de putere reactiv

-Pierderi de putere reactiv n fier

14

Determinarea energiilor:
-Energia (activ - reactiv) util consumat

-Pierderi de energie (activ - reactiv) consumat

-Aportul capacitiv

-Energii totale (active - reactive)

unde T=6600 h, t=5150 h (pt. l=0,815) i t=5150 h (pt. l=0,92)

15

Determinarea costurilor:
- Cost energie

- Investiie
I=
- Economie

-Recuperarea investiiei
(
(

)
)

16

, unde d=13,5%

S-ar putea să vă placă și