DNP3.0 PROTOCOL
http://www.entecene.co.kr
NOTE
The below points will be set by the condition described as follows; 1) The points are able to be implemented to be doble-points. 2) No. 14, Battery Discharge Test Fail Status = 0 : Battery Voltage is normal or high. Status = 1 : Battery Discharge Test Fail is Failed(15V < Battery Voltage < 21V).
3) No. 15, Battery Volt Low Alarm : Status = 0 : Battery Voltage is normal or high. Status = 1 : Battery Voltage is low(Battery Voltage 15V).
ENHANCED TECHNOLOGY
DNP3.0 PROTOCOL
http://www.entecene.co.kr
Table 1. DNP 3.0 INDEX - BINARY INPUT (2/2) BINARY INPUT POINTS Static (Steady-State) Object Number : 1 Change Event Object Number : 2 Request Function Codes supported : 1 (read) Static Variation reported when variation 0 requested : 1 (Single-Bit Binary Input) Change Event variation reported when variation 0 requested : 2 (Binary Input change with time)
Point Index 18 19 Status Description 0 Spare 1 Spare 2 1 Static, Event Static, Event Point Property Assigned Class Class 1 Class 1 Notes
NOTE
All BI Points can change assigned Class on EMIS Interface Software. Please refer to EMIS Interface Software Users Manual for more detail information.
ENHANCED TECHNOLOGY
DNP3.0 PROTOCOL
http://www.entecene.co.kr
Table 2. DNP 3.0 INDEX - BINARY OUTPUT (1/1) BINARY OUTPUT STATUS POINTS Object Number : 10 Request Function Codes supported : 1 (read) Default Variation reported when variation 0 requested : 2 (Binary Output with Status) CONTROL RELAY OUTPUT BLOCKS Object Number : 12 Request Function Codes supported : 3(select), 4(operate), 5(direct operate), 6(direct operate, noack)
Point Index 0 1 2 3 4 5 Description Remote Command Open Remote Command Close Fault Event Clear Battery Test Control Lock Control Unlock Code Field Pulse ON Pulse ON Pulse ON Pulse ON Pulse ON Pulse ON TR/CL Field CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE Block Condition CTR Lock || Mec Lock CTR Lock || Seq Running || Mec Lock Synchro || Hot Line Tag CTR Lock || Seq Running CTR Lock || AC power FAIL CTR Lock CTR Lock ||
NOTE
1) Block Condition Description CTR Lock(Control Lock) : CONTROL Function is locked status in panel Mec Lock(Mechanism Lock) : Circuit Breaker(Tank) is locked status Seq Running : Currently Sequence is conducting Synchro : Synchronism check
ENHANCED TECHNOLOGY
DNP3.0 PROTOCOL
http://www.entecene.co.kr
Table 3. DNP 3.0 INDEX - ANALOG INPUT (1/1) ANALOG INPUT POINTS Static (Steady-State) Object Number : 30 Change Event Object Number : 32 Request Function Codes supported : 1 (read) Static Variation reported when variation 0 requested : 4 (16-Bit Analog Input with out Flag) Change Event Variation reported when variation 0 requested : 4 (16-Bit Analog Change Event with Time)
Point Description Index 0 1 2 3 4 5 6 7 8 9 RMS Current Magnitude- A(A) RMS Current Magnitude- B(A) RMS Current Magnitude- C(A) RMS Current Magnitude- G(A) RMS Voltage Magnitude - AN (kV) (Source) RMS Voltage Magnitude - BN (kV) (Source) RMS Voltage Magnitude - CN (kV) (Source) RMS Voltage Magnitude - AN (kV) (Load) RMS Voltage Magnitude - BN (kV) (Load) RMS Voltage Magnitude - CN (kV) (Load) Static, Event Static, Event Static, Event Static, Event Static, Event Static, Event Static, Event Static, Event Static, Event Static, Event Point Property Class Class 3 Class 3 Class 3 Class 3 Class 3 Class 3 Class 3 Class 3 Class 3 Class 3 1A/1Count 1A/1Count 1A/1Count 1A/1Count 1V/1Count 1V/1Count 1V/1Count 1V/1Count 1V/1Count 1V/1Count Assigned Notes