Sunteți pe pagina 1din 1

Project No.

DUMMY LEG CALCULATION.

DOC NO-

NODE No. LINE No.

: :

15060

These Local Wall Stress Calculations are in accordance with the Kellogg method as applied to Cylindrical Pipe Attachments. The program calculates the stress ratio based on "1.5 x Hot Allowable Stress".

OD RUN PIPE RUN PIPE WALL THICKNESS CORROSION ALLOWANCE RE - PAD THICKNESS CORRODED PIPE WALL THICKNESS OD TRUNNION TRUNNION WALL THICKNESS ID TRUNNION LENGTH OF TRUNNION RADIAL LOAD LONGITUDINAL LOAD CIRCUMFERENTIAL LOAD INTERNAL PRESSURE HOT ALLOWABLE STRESS

Sustained

280 N Thermal

168.30 mm 7.11 mm 1.50 mm mm 4.72 mm 114.30 mm 6.0198 mm 106.77 mm 300 mm 14030 N 4210 N 3340 N 0.1 BarG 140.00 N/mm2

If only longitudinal, axial or circumferential forces are calculated, they should be multiplied by the friction coefficient to obtain load values in unrestrained directions. RADIAL STRESS LONGITUDINAL BENDING STRESS CIRCUMFERENTIAL BENDING STRESS PRESSURE STRESS = = = = 61.31 128.76 115.00 0.23 N/mm2 N/mm2 N/mm2 N/mm2

DUMMY LEG COMBINED STRESS RATIO PIPE WALL STRESS RATIO

0.454

1.454

FAILED

Calc by:-

SPS

Chk'd:-

App'd:-

PVS

S-ar putea să vă placă și