ID FAN 8A CHANNEL-1 LOAD BREAKER TESTING

NAME PLATE: VOLTAGE FREQUENCY NOMINAL CURRENT SYSTEM BREAKING CAPACITY SHORT TIME CURRENT DURATION MAKING CAPACITY p.f. WITHSTAND IMPULSE WITHSTAND SHUNT TRIP COIL SPRING RECHARGE COIL INTERRUPTER TYPE SPECIFICATION SERIAL NUMBER DIVISION YEAR : : : : : : : : : : : : : : : : : 7.2 KV 50 Hz 1250 A 40 KA 40 KA 3 SEC 100 KAP 20 KV 60 KVP 220 V 220 V BEL-VS 10007 VM12 IS 13118/IEC 62271-100 BP 9091690 BHOPAL 2011

Document1

ID FAN 8A CHANNEL-1 LOAD BREAKER TESTING

1. IR MEASUREMENT: USING 2.5 KV DIGITAL MEGGER. TEST IS PERFORM FOR 1 MIN. ALL VALUES IN GEGA OHM BREAKER OPEN R-R >100 R-Y >100 R-EARTH 56.2 Y-Y 80.9 Y-B 84.7 Y-EARTH 38.36 B-B >100 R-B >100 B-EARTH 61.3

BREAKER CLOSE

2. BREAKER CONTACT RESISTANCE MEASUREMENT: At I= 100 A ALL VALUES ARE IN MICRO-OHM POLE R 29.8 Y 31.5 B 30.6

3. *BREAKAR TIMIMG: R CLOSE OPEN CLOSE-OPEN 4. COIL RESISTANCE MEASUREMENT: CLOSING COIL: TRIPPING COIL: SPRING CHARGING MOTOR: 226.1 ohm 225.3 ohm 18.3 ohm Y B

*NOTE: BREAKER MECHANICAL PROBLEM HENCE TIMING TEST PENDING.