053-029 ISSUE 10
Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset Press the Stop/Reset and Info buttons simultaneously. If a module security PIN has been set, the PIN number request is then shown :
button.
(up) or
Press (right) when the first digit is correctly entered. The digit you have just entered will now show # for security.
Repeat this process for the other digits of the PIN number. You can press move back to adjust one of the previous digits.
When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, you must re-enter the PIN. If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed :
EDITING A PARAMETER
Enter the editor as described above. Press the left or right buttons to cycle to the section you wish to view/change. Press the up or down buttons to select the parameter you wish to view/change within the currently selected section. To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. Press the up or down buttons to change the parameter to the required value. Press to save the value. The parameter ceases flashing to indicate that it has been saved. button.
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure security. NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. NOTE: More comprehensive module configuration is possible using the 7xxx series PC configuration software. Please contact us for further details
ADJUSTABLE PARAMETERS (Configuration editor) Section Parameter as shown on display Factory Settings
Contrast Language LCD Page Timer Auto Scroll Delay Current Date and time EDITOR Alt Config ENGINE Oil Pressure Low Shutdown Oil Pressure Low Pre Alarm Coolant Temperature Low Warning Coolant Temperature High Pre Alarm Coolant Temperature High Shutdown Start Delay Off Load Start Delay On Load Start Delay Mains Fail Start Delay Telemetry Start Delay Timer Crank Duration Timer Crank Rest Timer Safety On Delay Smoke Limiting Smoke Limiting Off Warm Up Timer Cool Down Timer Engine Under Speed Shutdown Engine Under Speed Shutdown Engine Under Speed Warning Engine Under Speed Warning Engine Over Speed Warning Engine Over Speed Warning Engine Over Speed Shutdown Engine Speed Overshoot Delay Engine Speed Overshoot Fail To Stop Delay Battery Under Voltage Warning Battery Under voltage Warning Delay Battery Under Voltage Battery Over Voltage Warning Battery Over Voltage Warning Delay Battery Over Voltage Warning Charge Alternator Failure Warning Charge Alternator Failure Warning Charge Alternator Warning Delay Charge Alternator Failure Shutdown Charge Alternator Failure Shutdown Charge Alternator Shutdown Delay Droop control Droop control DPTC Auto Regeneration Inhibit Fuel Usage Alarm (Running Rate) Fuel Usage Alarm (Stopped Rate) GENERATOR Generator Under Voltage Shutdown Generator Under Voltage Pre Alarm Generator Nominal Voltage Generator Over Voltage Pre Alarm Generator Over Voltage Shutdown Generator Under Frequency Shutdown Generator Under Frequency Pre Alarm Generator Nominal Frequency Generator Over Frequency Pre Alarm Generator Over Frequency Shutdown Full Load Rating KW Overload Trip Delayed Over Current Delayed Over Current AC System CT Primary CT Secondary Earth CT Primary Earth Fault Trip Earth Fault Trip Generator transient delay DISPLAY 0% English 0h 0m 0s 0h 0m 0s hh:mm Default Config 0.00bar 0.00bar 0C 0C 0C 0h 0m 0s 0h 0m 0s 0h 0m 0s 0h 0m 0s 0h 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0h 0m 0s Active / Inactive 0 rpm Active / Inactive 0 rpm Active / Inactive 0 rpm 0 rpm 0m 0s 0% 0m 0s Active / Inactive 0h 0m 0s 0V Active / Inactive 0h 0m 0s 0V Active / Inactive 0V 0h 0m 0s Active / Inactive 0.0 V 0h 0m 0s Active / Inactive 0% (Compatible engine ECUs only) Active / Inactive 0% - 100% ( If Fuel Sender Configured) 0% - 100% ( If Fuel Sender Configured) 0V 0V 0V 0V 0V 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0A 0% Active / Inactive 0% 3 Phase, 4 Wire 0A 0A 0A Active / Inactive 0% 0s
TIMERS
SCHEDULE
ACCESSING THE RUNNING CONFIGURATION EDITOR The running editor can be entered while the engine is running. All protections remain active if the engine is running while the running editor is entered. Press and hold the button to enter the running editor.
EDITING A PARAMETER Enter the editor as described above. Press the left or right buttons to cycle to the section you wish to view/change. Press the up or down buttons to select the parameter you wish to view/change within the currently selected section. To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. Press the up or down buttons to change the parameter to the required value. Press to save the value. The parameter ceases flashing to indicate that it has been saved. button.
Factory Settings
53% English 0.0Hz
DIMENSIONS AND MOUNTING For flat surface mounting in a Type 1 enclosure to meet UL requirements DIMENSIONS 240.0mm x 181.1mm x 41.7mm (9.4 x 7.1 x 1.6) PANEL CUTOUT: 220mm x 160mm (8.7 x 6.3)