Volume 2 - Mechanical, Fire Protection & Electrical
Vol. 2
Signature# Date# Signature# Date# Signature# Date# Signature# Date#
OF
ABBREVIATIONS A
AAV AC ACU AD AE AFF AFT AHU APD APPROX. ARCH ASR AIR ADMITTANCE VALVE AIR COMPRESSOR AIR CONDITIONING UNIT ACCESS DOOR AIR EXTRACTOR ABOVE FINISHED FLOOR AIR FLOW TRANSMITTED AIR HANDLING UNIT AIR PRESSURE DROP APPROXIMATELY ARCHITECTURAL AUTOMATIC SPRINKLER RISER
NOTATION METHODS
D
DB DBP DDC DEG DN D/N DPR D&T DTC DRY BULB DOMESTIC BOOSTER PUMP DIRECT DIGITAL CONTROL DEGREES DOWN DAY/NIGHT DAMPER DRIP & TRAP DRAIN TILE CONNECTION
CONT FIRE DEPARTMENT CONNECTION FIRE DAMPER FIRE HYDRANT FIRE HOSE CABINET FIRE HOSE VALVE FIRE LINE FULL LOAD AMPS FLOW MEASUREMENT STATION FEET PER MINUTE FOOT/FEET FLOAT & THERMOSTATIC STEAM TRAP FINNED TUBE RADIATION FIRE VALVE CABINET
L
LAV LBS/HR LEF LL LP LP STM LRA LWT LAVATORY POUNDS PER HOUR LAB EXHAUST FAN LOW LIMIT LIGHTING PANEL LOW PRESSURE STEAM LOCKED ROTOR AMPS LEAVING WATER TEMPERATURE
P
P PA PAC PCR PD PG PLBG PRV PSI PVC PUMP PIPE ANCHOR PACKAGED AIR CONDITIONING UNIT PUMPED CONDENSATE RETURN PRESSURE DROP PIPE GUIDE PLUMBING PRESSURE REDUCING VALVE POUNDS PER SQUARE INCH - GAUGE POLYVINYL CHLORIDE PLASTIC
CONT SYSTEM STATIC TOTALIZER STORM STEAM SOLENOID VALVE SAFE WASTE SINK
SD-A 10" DIA 350 CFM SD-A 10" DIA 350 CFM
SUPPLY DIFFUSER, TYPE 'A', 10" NECK, 350 CFM SUPPLY DIFFUSER (3-WAY) RETURN OR EXHAUST REGISTER, TYPE 'A', 350 CFM EXHAUST REGISTER, TYPE 'A', 350 CFM SIDEWALL SUPPLY REGISTER, TYPE 'A', 350 CFM
E
EA EAT EDB EF EG EHC EIH EJ EV ELEC EMCS ENT ER ERC ES ESP ET EWB EWC EWT EXH (E) EXP EXHAUST AIR ENTERING AIR TEMPERATURE ENTERING DRY BULB EXHAUST FAN EXHAUST GRILLE ELECTRIC HEATING COIL ELECTRIC INFRARED HEATER EXPANSION JOINT ELEVATION ELECTRICAL ENERGY MONITORING AND CONTOL SYSTEM ENTERING EXHAUST REGISTER ENERGY RECOVERY UNIT EMERGENCY SHOWER EXTERNAL STATIC PRESSURE EXPANSION TANK ENTERING WET BULB ELECTRIC WATER COOLER ENTERING WATER TEMPERATURE EXHAUST EXISTING EXPANSION
B
BAS BBD BF BFP BHP BP BWV BUILDING AUTOMATION SYSTEM BOILER BLOWDOWN BARRIER FREE BOILER FEEDWATER PUMP BRAKE HORSEPOWER BACKFLOW PREVENTER BACKWATER VALVE
FDC FDAMP FH FHC FHV FL FLA FMS FPM FT F&T FTR FVC
T
TC TD TMV TV TW TYP TEMPERATURE CONTROL TRENCH DRAIN THERMOSTATIC MIXING VALVE TURNING VANES TEMPERED WATER TYPICAL
M
MA MAV MAX MBH MCC MECH MFR MGV MH MIN MS MZ MIXED AIR MANUAL AIR VENT MAXIMUM THOUSAND BRITISH THERMAL UNITS PER HOUR MOTOR CONTROL CENTER MECHANICAL MANUFACTURER MASTER GAS VALVE MAN HOLE MINIMUM MOTOR STARTER MULTI-ZONE UNIT
R
RA RAD RCP RG RH RF RM RPBP RP RPM RR RS RTD RETURN AIR RADIATOR RADIANT CEILING PANEL RETURN GRILLE RELATIVE HUMIDITY RETURN FAN ROOM REDUCED PRESSURE BACKFLOW PREVENTER RADIANT PANEL REVOLUTIONS PER MINUTE RETURN REGISTER ROOF SUMP RESISTANCE TEMPERATURE DETECTOR
G
GA GALV GHX GPM GPH GR GV GWD GAGE/GAUGE GALVANIZED GROUND HEAT EXCHANGE GALLONS PER MINUTE GALLONS PER HOUR GRILLE GATE VALVE GLASSWASH WASHER/DRYER
SUPPLY AIR DIFFUSER, TYPE 'A' WITH FLEXIBLE DUCT CONNECTION (TWO WAY THROW) BELL MOUTH AIR INLET AREA SHALL BE EQUAL TO '2' TIMES DUCT AREA
U
UH UL UR UV UNIT HEATER UNDERWRITERS LABORATORY URINAL UNIT VENTILATOR
AHU 1
C
CAP CC CD CFH CFM CI CLG CO COND CONN CON'T CONTR CONV CPU CR CT CUH CV CW CAPACITY COILING COIL COLD DECK CUBIC FEET PER HOUR CUBIC FEET PER MINUTE CAST IRON CEILING CLEANOUT CONDENSATE CONNECTION CONTINUATION CONTRACTOR CONVECTOR CENTRAL PROCESSING UNIT CONDENSATE RETURN COOLING TOWER CABINET UNIT HEATER CONTROL VALVE COLD WATER
H
HUMD HB HD HO HOA HP HP STM HV HVAC HYD HUMIDIFIER HOSE BIBB HOT DECK HUB OUTLET HAND-OFF-AUTO HORSEPOWER HIGH PRESSURE STEAM HEATING AND VENTILATION UNIT HEATING, VENTILATION & AIR CONDITIONING HYDRANT
N
NC NCR NIC NO No. NTS NORMALLY CLOSED NOISE CRITERION NOT IN CONTRACT NORMALLY OPEN NUMBER NOT TO SCALE
V
V VAV VD VI VS VTR VENT VARIABLE AIR VOLUME VOLUME DAMPER VIBRATION ISOLATOR VENT STACK VENT THROUGH ROOF
EF 1
S
SA SAN SAT SC SCW SD SEF SF SH SHT SP SP HD SPEC SPKR SS SUPPLY AIR SANITARY SATURATED STEAM COIL SOFTENED COLD WATER SUPPLY DIFFUSER SMOKE EXHAUST FAN SUPPLY FAN SPRING HANGER SHEET SUMP PUMP SPRINKLER HEAD SPECIFICATIONS SPRINKLER SERVICE SINK
O
OA OD OED OS&Y OV OUTSIDE AIR OUTSIDE DIAMETER OPEN ENDED DUCT OUTSIDE SCREW AND YOKE OUTLET VELOCITY
W
W W&V WB WC WCO WG WH WS WASTE WASTE AND VENT WET BULB WATER CLOSET WALL CLEANOUT WATER GAUGE WALL HYDRANT (FREEZE PROTECTED) WASTE STACK
ST 1 FTR-A 5'-0" 5.7 MBH
F
F FA F & BD FC FCO FD FARENHEIT FACE AREA FACE AND BYPASS DAMPER FLEXIBLE CONNECTION FLOOR CLEANOUT FLOOR DRAIN
I
ID IE IW INSIDE DIAMETER INVERT ELEVATION INDIRECT WASTE
FINNED TUBE RADIATION, TYPE 'A', 5'-0" ELEMENT, 5.7 TOTAL MBH (REFER TO EQUIPMENT SCHEDULES)
CUH A
SYMBOLS
COMBINATION FIRE/SMOKE DAMPER VOLUME DAMPER WITH REMOTE OPERATOR
CONV A
RPBP
NIT-OX OXY
RO/DI TW HRR HRS COND HPC LPC CWR CWS PCR STM LPS( #) HPS( #)
2
LAB HIGH PURITY WATER TEMPERED WATER HEAT RECOVERY LOOP RETURN PIPING HEAT RECOVERY LOOP SUPPLY PIPING CONDENSATE DRAIN PIPING (AIR CONDITIONER) HIGH PRESSURE CONDENSATE RETURN PIPING LOW PRESSURE CONDENSATE RETURN PIPING CONDENSER WATER RETURN PIPING CONDENSER WATER SUPPLY PIPING PUMPED CONDENSATE RETURN PIPING LOW PRESSURE STEAM LOW PRESSURE STEAM (PRESSURE IND.) HIGH PRESSURE STEAM (PRESSURE IND.) PNEUMATIC 2-POSITION SELECTOR SWITCH
F
SD
AREA SMOKE DETECTOR DUCT SMOKE DETECTOR FIRE STAT - DUCT MOUNTED FREEZE STAT - DUCT MOUNTED FLOW METER AQUASTAT (STRAP ON) AIR FLOW SENSOR LOOP POWER INDICATOR DAY/NIGHT MAIN AIR SWITCH MANOMETER
PP M M
PILOT POSITIONER MOUNTED ON DEVICE WITH POSITIVE FEEDBACK MAIN AIR SUPPLY (TEMPERATURE CONTROL) PNEUMATIC LINE SWITCHED AIR LINE
CONVECTOR, TYPE 'A' TERMINAL VARIABLE VOLUME BOX, TYPE 'A', SIZE '1' (HEATING COIL, REFER TO EQUIPMENT SCHEDULES) TERMINAL VARIABLE VOLUME BOX, TYPE 'B', SIZE '1' (NO HEATING COIL, REFER TO EQUIPMENT SCHEDULES) DUAL DUCT CONSTANT VOLUME MIXING BOX (REFER TO EQUIPMENT SCHEDULES) HEATING COIL, TYPE 'A' (REFER TO EQUIPMENT SCHEDULES)
F F FZ FM AQ AFS LPI
DD
SH CO CO MH
SPRING HANGER FLOOR CLEANOUT WALL CLEANOUT MANHOLE FLOOR DRAIN VAC AW SAN DT PST RC ST
VACUUM PIPING ACID WASTE SANITARY SEWER DRAIN TILE PUMPED STORM WATER RAIN CONDUCTOR STORM SEWER DOMESTIC COLD WATER PIPING
CO H T
CARBON MONOXIDE SENSOR HUMIDISTAT THERMOSTAT CUH OR CONVECTOR (SURFACE) FINNED TUBE RADIATION TERMINAL VOLUME BOX (W/O HEATING COIL) TERMINAL VOLUME BOX (W/ HEATING COIL) FLEXIBLE PIPE CONNECTION ANGLE RELIEF VALVE ANGLED STOP CHECK VALVE BALANCE VALVE BUTTERFLY VALVE (SEE SPECIFICATION FOR TYPE) BALL, GAS, GATE, GLOBE, PLUG VALVE (SEE SPECIFICATION FOR TYPE) CHECK VALVE W/ ARROW INDICATING FLOW CONTROL VALVE LINEAR STOP CHECK VALVE MIXING VALVE PRESSURE REDUCING VALVE PRESSURE RELIEF VALVE STRAINER UNION PIPE ANCHOR PIPE GUIDE
A3
HC-A
VALVE - TWO WAY PNEUMATIC CONTROLLED VALVE - THREE WAY PNEUMATIC CONTROLLED TWO WAY MOTORIZED VALVE THREE WAY MOTORIZED VALVE TWO WAY GATE VALVE AI AO DI DO DPT
MHL 1234567
CB
D/N
PRESSURE INDICATOR TEMPERATURE INDICATOR THERMOMETER MANUAL AIR VENT FLOW MEASURING DEVICE CW HPCW PCHR
CR CS DM
DOMESTIC COLD WATER PIPING HIGH PRESSURE COLD WATER PROCESS CHILLED WATER RETURN PROCESS CHILLED WATER SUPPLY
ANALOG INPUT ANALOG OUTPUT DIGITAL INPUT DIGITAL OUTPUT DIFFERENTIAL PRESSURE TRANSMITTER LOAD ANALYZER PRESSURE TRANSMITTER RECIEVER CONTROLLER
EXISTING MECHANICAL
PNEUMATIC GRADUAL POSITION SWITCH DAMPER (OPPOSED BLADE) DPS PS T DIFFERENTIAL PRESSURE SWITCH EP ELECTRIC - PNEUMATIC RELAY START STOP (MOTOR CONTROL) RELAY (ELECTRICAL) TWIST TIMER VELOCITY CONTROLLER MOTOR DISCONNECT SWITCH MOTOR STARTER, W/O HOA SWITCH MOTOR STARTER, W/ HOA SWITCH EXISTING MOTOR STARTER PROVIDE HOA SWITCH MOTOR STARTER PROVIDE HOA SWITCH, TRANSFORMER AND CONTROL ROOM ES FM PE REV PS END SWITCH FLOW SWITCH - INLINE PNEUMATIC - ELECTRIC RELAY PNEUMATIC REVERSING RELAY PNEUMATIC SWITCHING RELAY ST L PRESSURE SWITCH S/S TEMPERATURE INDICATOR GAUGE TYPE R PT
PCHS CHILLED WATER RETURN PIPING CHWR CHILLED WATER SUPPLY PIPING CHWS DOMESTIC HOT WATER RETURN PIPING
FE
FLOW ELEMENT (ORIFICE PLATE) POINT OF NEW CONNECTION TO BE DEMOLISHED AND REMOVED
DOMESTIC HOT WATER PIPING OWNER EQUIPMENT IDENTIFICATION NUMBER F FL SP AV A CA( #) CO2 FOR FOS G G(EPS) FIRE LINE FIRE PROTECTION WATER SUPPLY PIPING SPRINKLER PIPING ACID VENT PIPING LAB COMPRESSED AIR COMPRESSED AIR PIPING PRESSURE INDICATED CARBON DIOXIDE GAS FUEL OIL RETURN FUEL OIL SUPPLY NATURAL GAS PIPING NATURAL GAS PIPING (EMERGENCY POWER SUPPLY) DP HR HS HW HWR HWHR HWHS HTHWR HEATING RETURN DIFFERNTIAL PRESSURE GAUGE HUMIDISTAT (ROOM) HUMIDITY HIGH LIMIT SENSOR (DDC) HUMIDITY SENSOR (DDC) HUMIDITY TRANSMITTER THERMOSTAT WITH GUARD TEMPERATURE SENSOR (RTU) - SPACE MOUNTED TEMPERATURE SENSOR (RTD) DUCT MOUNTED AVERAGING ELEMENT TEMPERATURE SENSOR (RTU) W/ SUNSHIELD TEMPERATURE SENSOR (RTD) DUCT MOUNTED RIGID ELEMENT T SP GHXR GROUND HEAT EXCHANGE RETURN PIPING TEMPERATURE SENSOR (RTD) IMMERSION TYPE ELEMENT STATIC PRESSURE SENSOR TT VC
H
HEATING SUPPLY DOMESTIC HOT WATER PIPING DOMESTIC HOT WATER RETURN PIPING HOT WATER HEATING RETURN PIPING HOT WATER HEATING SUPPLY PIPING HIGH TEMPERATURE HOT WATER RETURN PIPING HIGH TEMPERATURE HOT WATER SUPPLY PIPING NON-POTABLE WATER PIPING SOFTENED COLD WATER DEIONIZED WATER SUPPLY GROUND HEAT EXCHANGE SUPPLY PIPING T T T HL H HT
STATUS OCCUPANCY SENSOR - WALL MOUNTED ELECTRICAL LINE - 24v DC (DDC WIRING) ELECTRICAL LINE - 120 v AC ELECTRICAL LINE DESIGNATION ON WIRING DIAGRAMS (VOLTAGE AS NOTED)
T
T
MGS PRV
GHXS
SYMBOL LEGEND
DETAIL SYMBOL DETAIL IDENTIFICATION 2 M2.1 ELEVATION SYMBOL
MOUNTING HEIGHTS
COMPRESSED AIR QUICK DISCONNECT FIRE PUMP TEST CONNECTION FIRE DEPARTMENT CONNECTION (HOSE, INSIDE) FIRE DEPARTMENT CONNECTION (SIAMESE) WALL MOUNTED CABINET UNIT HEATER WALL CLEAN OUT SUPPLY AIR DIFFUSER (AREAS WITHOUT CEILINGS) THERMOSTAT HUMIDISTAT HOSE BIB
GENERAL NOTES
1. 2. 3. 4. 5. 6. BOTTOM CORD OF JOIST/TRUSS 7. 8. 9. VERIFY ALL CONDITIONS IN FIELD BEFORE START OF CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNERS REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSTALLATION OF ALL PIPE, SHEET METAL AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5-0. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
THIS PROJECT MAY NOT UTILIZE ALL THE SYMBOLS, MATERIALS, ABBREVIATIONS AND STANDARD INFORMATION SHOWN ON THIS SHEET.
DETAIL
DETAIL SCALE
3
ELEVATION NUMBER
4
M5.1
CP-11243
ARCH. MECH.
DRAWING WHERE DETAIL IS REFERENCED OR CUT PLAN OR DETAIL ENLARGEMENT PLAN OR DETAIL IDENTIFICATION
J. Kasdorf
ELEC.
R. Frazee
L.A.
2 M5.1
H 48" AFF
D. Wilber
Project Administrator: Project Designer:
10. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). 8" AFF 11. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
J. Johnson
Project Arch/Eng:
WCO
NEW ROOM NAME AND NUMBER ROOM NAME A101 ROOM FLOOR BUILDING OR UNIT (IF ANY)
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
No Scale
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
8.
9.
10. ALL CONTROL DEVICES INCLUDING CONTROL VALVES, CONTROL DAMPERS, AND CONTROL ACTUATORS ON TEMPERATURE CONTROL DRAWINGS SHALL BE PROVIDED BY TEMPERATURE CONTROLS CONTRACTOR, UNLESS NOTED OTHERWISE. DAMPER SIZE AND LOCATIONS ARE INDICATED ON MECHANICAL DRAWING FLOOR PLANS. 11. DUCT SMOKE DETECTORS SHALL BE FURNISHED, INSTALLED, AND WIRED TO FIRE ALARM SYSTEM BY THE ELECTRICAL CONTRACTOR. TEMPERATURE CONTROL CONTRACTOR SHALL PROVIDE SMOKE DETECTOR WIRING INTERLOCK TO MOTOR STARTERS. 12. CONTROL VALVES FURNISHED BY TEMPERATURE CONTROLS CONTRACTOR SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. ALL PIPE PENETRATIONS REQUIRED FOR SENSOR INSTALLATIONS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. 13. ELECTRICAL POWER REQUIRED FOR CONTROLS SHALL BE PROVIDED BY TC CONTRACTORS UNLESS NOTED OTHERWISE FROM DESIGNATED CIRCUITS WITHIN NEAREST ELECTRIC DISTRIBUTION PANEL.
12204-1000
Mechanical Reference Information
1/5/2014 9:49:05 PM
NORTH
M0.1
OF
NEW MECHANICAL
S. Gardner
APPR.
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
SHEET METAL
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5'-0". REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
KEY NOTES
SHEET METAL
1 2 3 4 5 MOUNT DOOR CURTAIN AGAINST ROLL-UP DOOR ASSEMBLY. AIR NOZZLE TO BE LEVEL WITH TOP OF DOOR OPENING. EXHAUST AIR THROUGH OPENING IN CEILING BY ARCHITECTURAL TRADES. RETURN AIR TRANSFERED TO WRITE-UP SPACE. REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATION OF DIFFUSER/GRILLE. TOTAL AIRFLOW FROM LABORATORY AIR VALVE SHALL BE EQUALLY BALANCED BETWEEN ALL ZONE SUPPLY DIFFUSERS OR EXHAUST GRILLES. REFER TO SCHEDULE ON SHEET M8.2.
2. 3. 4.
5. 6. 7. 8. 9.
10. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
A
LD-I 10'-0" LENGTH 4'-0" ACTIVE 6'-0" BLANK -OFF 170 CFM 8" NECK (TYP-9)
LE-A 6'-0" LENGTH 2'-0" ACTIVE 4'-0" BLANK-OFF LD-I 500 CFM 12" NECK 12" GLEA
STAIR SW3-1
(TYPE B) FCU (AT FLOOR) SW3-1.2 10"x10" SA (TYPE B) SD-A 250 CFM (TYP-3) V-E.1610 5 8" SA (TYP-3)
OFFICE 1311
OFFICE 1312
OFFICE 1313
WORKROOM 1301
OFFICE 1314
OFFICE 1315
OFFICE 1316
WORKROOM 1302
OFFICE 1317
OFFICE 1318
OFFICE 1319
6" GLEA
A.6
12" GLEA 16" SA V-E.1600 6" GLEA V-E.1611 V-S.1611 EG-A 120 CFM 6" SA V-S.1610
16"x14" SA
16"x14" SA
12"x12" SA
8" SA
B
14"x10" SA A-4 690/460 LD-A 345 CFM FCU 1011A (TYPE C) 12"x10" RA BELL MOUTH 355 CFM RG-B 50 CFM
LAB 1400
CORRIDOR 1450
LE-A 6'-0" LENGTH 2'-0" ACTIVE 4'-0" BLANK-OFF 5
MECHANICAL 1611
12" SA 1 M6.0
ELEVATOR #1 EP1
IT CLOSET 1011A
22"x16" SA
10" SA (TYP-2) LD-I 225 CFM (TYP-2) 10"x10" SA 10"x4" SA (TYP-3) A-3 450/300
VD 26"x16" RA
C C.1
ELECTRICAL CLOSET 1011B
24"x5" SA UP TO 2ND FLR. (TYP-3) BALANCE 465 CFM EQUALLY BETWEEN DUCTS
C.9 D
BELL MOUTH 225 CFM VD (TYP)
20"x16" RA
JANITOR CLOSET 1815 LAB SUPPORT 1230 FLUORESCENT IMAGING LAB 1702
14"x14" GLEA
16"x14" SA 6"x10" SA
12"x10" SA
E
A-3 550/365 10"x8" EA
10" SA 6"x6" SA
14" SA 14" SA MAIL ROOM A-6 1500/1000 1042 CORRIDOR 22" x12" RA BOOT 1HW1C 8" SA 16"x14" SA A-2 160/105 SD-C 8"x6" RA 300 CFM BELL MOUTH 140 CFM (TYP-4) LD-G WORKROOM 150 CFM 1040A 20" SA LD-E 300 CFM SD-A 75 CFM SD-A 85 CFM
LAB 1200
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
6"x8" EA UP 6"x8" EA EG-B 1100 CFM DC 2 SG-B 1000 CFM UH 1.1 (TYPE A)
R. Frazee
L.A.
(TYPE D)
D. Wilber
Project Administrator: Project Designer:
UNASSIGNED 1840
14" SA
20"x12" RA
12" SA
20"x12" RA
10"x10" SA
10"x10" RA
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
6"x8" EA
E.4
8" SA
4 14"x14" SA
D. DiCiuccio
Drawing Scale:
As indicated
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
VESTIBULE 1VB2
OFFICE 1111
OFFICE 1112
OFFICE 1113
WORKROOM 1101
OFFICE 1114
RG-B 4 1715 CFM (TYP-2)
OFFICE 1115
OFFICE 1116
LD-H 8" NECK 5'-0" LENGTH 200 CFM
WORKROOM 1102
OFFICE 1117
LD-I 10'-0" LENGTH 4'-0" ACTIVE 6'-0" BLANK -OFF 255 CFM 10" NECK (TYP-9)
OFFICE 1118
OFFICE 1119
SD-A 85 CFM (TYP-9) 22" x6" 3 RA BOOT (TYP-9) RG-A 70 CFM (TYP-9)
STAIR SW2-1
O.E. RA DUCT
12204-1000
First Floor Plan - Sheet Metal
1/5/2014 9:49:23 PM
NORTH
M2.1
OF
6" SA
S. Gardner
APPR.
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
SHEET METAL
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5'-0". REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
KEY NOTES
SHEET METAL
1 2 3 COORDINATE AND PROVIDE TRANSITION TO FUME HOOD COLLAR CONNECTION. COORDINATE, PROVIDE TRANSITION AND CONNECT TO MANUFACTURED COLD ROOM SA AND EA CONNECTIONS. TOTAL AIRFLOW FROM LABORATORY AIR VALVE SHALL BE EQUALLY BALANCED BETWEEN ALL ZONE SUPPLY DIFFUSERS OR EXHAUST GRILLES. REFER TO SCHEDULE ON SHEET M8.2.
2. 3. 4.
5. 6. 7. 8. 9.
10. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
4.5
5.5
6.5
7
3
7.5
8.5
10
28"x20" GLEA (TYP)
SD-A 10"
10" SA
16" SA
6" SA 20" RA 20" RA 20" RA SD-A 10" 3 SD-A 10" 8" SA 10" SA 12" GLEA 3 8" GLEA V-E.1410 VD (TYP) FD FD 20" SA 8" GLEA 10" SA 12" SA 14" GLEA 10" GLEA 8" GLEA 16" SA 14" SA 16" SA 14" GLEA 10" GLEA 10" SA 10" SA 10" SA SD-A 10" 3 3 10" SA SD-A 10" 10" SA 16" RA 12" GLEA EG-A 255 CFM 28" GLEA
12" GLEA
14" GLEA
VD (TYP)
CORRIDOR 1450
48"x24" GLEA V-E.1400.C LE-A 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF 3
30"x14" FHEA
16" SA
6" SA
LAB 1400
V-S.1400.C
44"x42" RA UP
28" GLEA
V-E.1400.B
V-S.1400.A
10" SA
40"x24" RA
3 EG-A 10"
3 EG-A 10"
V-S.1400.B
3 EG-A 10"
3 EG-A 10"
12" GLEA
14" GLEA
14" GLEA
B.6
VD (TYP.) 26"x16" RA
8" SA
14" SA
34"x14" SA
8" SA
8" GLEA
10" GLEA
B.5
8" GLEA
8" GLEA
22"x16" SA
14" SA
B.7
8" SA EG-A 350 CFM EG-A 350 CFM
12" SA 8" SA
28" SA
V-S.1531
V-S.1521
V-S.1522
V-S.1532
16" GLEA
14" FHEA
V-C.1523.A
V-C.1523.B
V-E.1500
V-C.1526.A
V-C.1526.B
V-S.1510
6" GLEA
C C
EG-A LE-A 350 CFM 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF (TYP-4) 3 10" GLEA 10" GLEA 24"x4" PLENUM (TYP-4) 8" GLEA (TYP-4)
14" FHEA
C.1 C.1
LE-A 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF (TYP-4) 3 8" GLEA (TYP-4)
8" GLEA
8" SA
8" SA
14" FHEA
14" FHEA
14" FHEA
14" FHEA
8" SA
V-E.1521
V-E.1522
8" SA
V-E.1524
10" GLEA
10" GLEA
10" GLEA
V-E.1525
14" GLEA
8" SA
10" GLEA
6" GLEA
8" SA
20" GLEA
V-S.1704
V-E.1531
V-E.1532
6" SA
14" GLEA
12"x10" SA
V-S.1703
14" GLEA
14" EA DN TO FUME HOOD 1 (TYP-2) 6" GLEA SD-A 300 CFM V-E.1501 24" SA
V-S.1524
V-S.1525
40"x20" RA
10" GLEA
10" GLEA
14"x14" GLEA
8" FHEA
16" SA
12" SA
6" FHEA
LE-A 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF 155 CFM TOTAL
40"x16" SA
SD-A 8"
28" SA
30" SA
46"x18" SA
24"x14" GLEA
16" GLEA
SD-A 10" 3
8" GLEA
C.2
26"x14" SA
V-E.1511
26"x14" SA
14" SA
V-S.1600
14" SA
40"x16" SA
8" SA
8" GLEA
14" FHEA
14" FHEA
V-E.1534
V-S.1533
8" GLEA
V-E.1535
V-C.1533.A
V-C.1533.B
V-C.1536.A
24" SA
C.9 C.9
10" GLEA
8" FHEA
22" EA UP 40"x20" RA
V-C.1536.B
18" FHEA
C.8
V-C.1703.A
16" SA
8" SA 1
10" GLEA
10" GLEA
44"x18" SA 4" FHEA DN TO HOLDING CAGES (TYP-5) SD-B 16" NECK 790 CFM
60"x18" SA
V-S.1536
V-S.1500
14" FHEA
26" FHEA 14" SA SD-B 16" NECK 1390 CFM 22" SA 26" FHEA
14" SA
42"x36" SA UP 24"x20" SA HORIZONTAL COMBINATION FIRE/SMOKE DAMPER AT PENETRATION INTO SHAFT ABOVE (TYP-4)
14" FHEA
V-S.1511
D D
FD
14" FHEA
6" SA
3
" 14
8" GLEA
SD-A 8"
CP-11243
ARCH. MECH.
8" GLEA
V-S.1701 LD-G 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF 105 CFM TOTAL SD-A 8" (TYP-2) LD-G 10" NECK 6'-0" LENGTH (TYP-9) 3
J. Kasdorf
ELEC.
R. Frazee
L.A.
12" SA
24" FHEA
18" FHEA
26"x16" SA
D. Wilber
Project Administrator: Project Designer:
V-E.1701
FD
10" SA
22" SA EG-A 240 CFM 14" SA 12" GLEA 8" GLEA 12" GLEA EG-A 240 CFM 12" SA 8" GLEA 8" SA EG-A 240 CFM
30" SA EG-A 240 CFM 12" SA 12" SA 12" GLEA 8" GLEA V-S.1200.C
D.3
40"x20" RA
8" GLEA
6" SA
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
V-S.1240
D. DiCiuccio
Drawing Scale:
1/4" = 1'-0"
8" GLEA
V-S.1200.A
V-S.1200.B
V-S.1100
8" SA
V-E.1200.C
12" GLEA
8" SA
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
LE-A 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF 3
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
14"x14" GLEA
10" SA
12" GLEA
12" GLEA
V-S.1220 16" SA
10" SA
8" SA
16" SA
6" SA V-E.1230
24"x14" GLEA
6" SA
12" GLEA
14" SA
8" GLEA
V-S.1210 24"x20" RA 8" GLEA 6" SA EG-A 160 CFM 8" SA SD-A 10" 3 8" GLEA 14" GLEA V-E.1210 14" SA 8" GLEA 22" RA SD-A 10" 3 SD-A 10"
10" SA 14" SA
10" SA
3 SD-A 10"
10" SA
16" GLEA
12" GLEA
SD-A 3 10"
3 SD-A 10"
10" SA
8" SA
V-E.1702
LAB 1200
8"x10" SA
8" GLEA
20" GLEA
18" RA
10"x10" RA 8" GLEA 3 SD-A 10" 20"x12" RA EG-A 235 CFM SD-A 340 CFM
c
A-7 2800/1865
A-2 255/170
20"x12" RA
CORRIDOR 1250
14"x14" GLEA
12204-1000
9 9.5 10
Enlarged First Floor Lab Plan - Sheet Metal
4.5
5.5
6.5
7.5
8.5
1
1/5/2014 9:49:35 PM
M2.1
NORTH
M2.1a
OF
22" FHEA
18" FHEA
14"x24" GLEA
18" SA
S. Gardner
APPR.
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
A "S 16 "x 26
EA FH
GENERAL NOTES
SHEET METAL
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5'-0". REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
KEY NOTES
SHEET METAL
1 2 3 EXHAUST AIR THROUGH OPENING IN CEILING BY ARCHITECTURAL TRADES. RETURN AIR THROUGH CEILING OPENING TO ATRIUM BY ARCHITECTURAL TRADES. FLOOR MOUNTED BAR GRILLE TO RUN CONTINUOUS WALL-TOWALL. CONTRACTOR TO VERIFY EXACT FIELD CONDITIONS PRIOR TO ORDERING. TOTAL SUPPLY AIR INDICATED TO BE DIVIDED EQUALLY TO THREE SUPPLY PLENUM CONNECTIONS. RETURN AIR TRANSFERED TO WRITE-UP SPACE. LINEAR DIFFUSER MOUNTED VERTICALLY IN METAL PANEL WALL SYSTEM. TOTAL AIRFLOW FROM LABORATORY AIR VALVE SHALL BE EQUALLY BALANCED BETWEEN ALL ZONE SUPPLY DIFFUSERS OR EXHAUST GRILLES. REFER TO SCHEDULE ON SHEET M8.2.
2. 3. 4.
4 5 6
5. 6. 7. 8. 9.
10. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
0.1
4.5
5.5
6.5
7.5
8.5
10
11
LD-1 9'-0" LENGTH 3'-0" ACTIVE 6'-0" BLANK -OFF 200 CFM 10"x6" SA BELL MOUTH 180 CFM 10"x10" RA
LE-A 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF 305 CFM TOTAL RG-A 4 70 CFM (TYP-2)
14"x24" GLEA 28"x20" GLEA LD-I 12" NECK 5'-0" LENGTH 500 CFM LE-A 6'-0" LENGTH 2'-0" ACTIVE 4'-0" BLANK-OFF 305 CFM TOTAL LD-G 10" NECK 6'-0" LENGTH 395 CFM TOTAL
A
LOUNGE 2HW1A
LD-D 500 CFM 10"x10" SA RG-A 90 CFM 22" x12" RA BOOT BELL MOUTH 90 CFM
ADMIN 2060
A-7 1710/1140
LD-I 10'-0" LENGTH 4'-0" ACTIVE 6'-0" BLANK -OFF 170 CFM 8" NECK (TYP-9)
14"x24" GLEA
STAIR SW3-2
OFFICE 2311
A-2 200/135
OFFICE 2312
OFFICE 2313
WORKROOM 2301
OFFICE 2314
OFFICE 2315
OFFICE 2316
WORKROOM 2302
OFFICE 2317
OFFICE 2318
OFFICE 2319
6" GLEA
A.6
LD-A 18'-0" LENGTH 10'-0" ACTIVE 8'-0" BLANK -OFF 730 CFM DISTRIBUTED EQUALLY BETWEEN TWO BRANCHES
16" SA
12" GLEA 16" SA V-E.2600 6" GLEA V-E.2611 10" SA V-S.2611 6" SA SD-A 120 CFM 6" SA
10" SA 16"x14" SA
B
14"x10" SA A-4 730/485 12"x6" SA (TYP-6) BELL MOUTH 1580 CFM
LR-A 18'-0" LENGTH 8'-0" ACTIVE 10'-0" BLANK -OFF A-6 1500/1000 BELL MOUTH 570 CFM 16"x12" RA BELL MOUTH 850 CFM (TYP-2) 20"x16" SA SD-A 100 CFM
10" SA
20"x14"x14" WYE
MECHANICAL 2611
1 M6.1
CORRIDOR 2HW3
24"x12" SA
36"x12" RA
SUBSTATION 2810
C C.1
CORRIDOR 2HW1D TISSUE CULTURE 2522 TISSUE CULTURE 2521 FUME HOOD 2523 EQUIP ROOM 2500
CORRIDOR 2HW1
STAIR SW1-2
1 M2.2a
C.9 D
BELL MOUTH 225 CFM VD (TYP)
6"x6" EA
BELL MOUTH 1965 CFM LR-A 18'-0" LENGTH 8'-0" ACTIVE 10'-0" BLANK -OFF 18"x16" SA
ELEVATOR #2 EP2
LD-A 6'-0" LENGTH 2'-0" ACTIVE 4'-0" BLANK -OFF 75 CFM 14" SA PERSONAL HEALTH ROOM 2042 A-2 160/105 OFFICE/ WORKROOM 2040 8" SA SD-A 85 CFM 12"x10" RA A-3 500/335 10"x10" SA 24" SA
CP-11243
LAB 2200 CORRIDOR SD-A 2HW2 250 CFM
ARCH.
6"x10" SA
A-6 1500/1000 16"x14" SA CORRIDOR 2HW1C SD-C 300 CFM (TYP-4) LD-G 150 CFM
J. Kasdorf
ELEC.
R. Frazee
L.A.
8"x8" EA
D. Wilber
Project Administrator: Project Designer:
J. Johnson
6"x8" EA
12"x10" SA
A-2 255/170
Project Arch/Eng:
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
CUSTODIAL 2840
OFFICE 2111
10" SA
8" SA
10" SA
8" SA
E.4
As indicated
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
BELL MOUTH 145 CFM BELL MOUTH 245 CFM 6"x10" SA 10" SA
OFFICE 2112
OFFICE 2113
WORKROOM 2101
OFFICE 2114
OFFICE 2115
OFFICE 2116
LD-H 8" NECK 5'-0" LENGTH 200 CFM
WORKROOM 2102
OFFICE 2117
LD-I 10'-0" LENGTH 4'-0" ACTIVE 6'-0" BLANK -OFF 255 CFM 10" NECK (TYP-9)
OFFICE 2118
OFFICE 2119
LOUNGE 2HW1B
LR-A 48"x5" 270 CFM 48"x5" RA BOOT
STAIR SW2-2
LD-1 9'-0" LENGTH 3'-0" ACTIVE 6'-0" BLANK -OFF 270 CFM
12204-1000
Second Floor Plan - Sheet Metal
1/5/2014 9:49:52 PM
NORTH
M2.2
OF
S. Hopper
CIVIL
S. Gardner
APPR.
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
SHEET METAL
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5'-0". REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
KEY NOTES
SHEET METAL
1 2 3 COORDINATE AND PROVIDE TRANSITION TO FUME HOOD COLLAR CONNECTION. COORDINATE, PROVIDE TRANSITION AND CONNECT TO MANUFACTURED COLD ROOM SA AND EA CONNECTIONS. TOTAL AIRFLOW FROM LABORATORY AIR VALVE SHALL BE EQUALLY BALANCED BETWEEN ALL ZONE SUPPLY DIFFUSERS OR EXHAUST GRILLES. REFER TO SCHEDULE ON SHEET M8.2.
2. 3. 4.
5. 6. 7. 8. 9.
10. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
4.5
5.5
6.5
7.5
8.5
10
12"x12" RA
20"x10" RA
B B
SD-A 95 CFM 10" SA 22" RA 12" GLEA 32"x30" EA UP & DN 44"x42" RA UP & DN SD-A 10" 3 SD-A 10" 3 SD-A 10" 3 12" GLEA 14" SA 10" SA 14" SA 14" GLEA SD-A 10" 3 12" GLEA SD-A 10" 10" SA 3 14" SA 10" SA 10" SA 16" GLEA SD-A 10" 3 SD-A 10" 3 12" GLEA 14" SA SD-A 10" 3 SD-A 10" 3 12" GLEA 14" SA 10" SA SD-A 10" 3 20" RA 20" RA 16" RA
18" GLEA
20" GLEA
10" SA 16" SA
10" SA
FD
6" SA
VD (TYP)
10" SA
10" SA
10" SA
10" SA V-E.2400.C V-S.2400.C V-E.2400.D V-S.2400.D V-E.2400.A V-S.2400.A V-E.2400.B V-S.2400.B FD 40"x24" RA 30"x14" FHEA V-S.2410
LAB 2400
12" GLEA
12" GLEA
V-S.2300
12" GLEA
12" GLEA
6" SA
B.5
VD (TYP)
20" SA
V-E.2400.E
V-S.2400.E
40"x20" GLEA
12" SA
12" SA
12" SA
12" SA
6" GLEA
12" SA
FD
10" GLEA
10" GLEA
10" GLEA
B.7
22" SA 14" SA 24" SA 28" SA 32" SA 44"x16" SA 14" SA
V-E.2410
18" FHEA 14" FHEA 14" FHEA LE-A 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF (TYP-4) 3 V-S.2501 LE-A 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF (TYP-4) 6" SA 3 6" GLEA (TYP-4) V-S.2510 6" GLEA 3 SD-A 8" V-C.2527.A 12" SA SD-B 16" NECK 1395 CFM
8" SA
V-C.2523.A
V-C.2523.B
V-C.2527.B
V-S.2529
8" SA
8" SA
C C
14" SA
6" SA
14" FHEA
14" FHEA
14" SA
44"x16" SA
8" SA
10" GLEA
10" GLEA
14" FHEA
14" FHEA
14" FHEA
14" FHEA
6" GLEA
V-S.2527
6" GLEA
V-S.2521 V-E.2521
V-S.2522
C.2
8" SA SD-A 300 CFM
3 SD-A 8"
V-E.2522
V-E.2524
V-E.2525
V-E.2526
20" SA
8" SA
8" SA
26"x14" SA
8" SA
8" SA
V-E.2529
10" GLEA
8" SA
V-E.2528
V-S.2528
16" SA
10" GLEA
V-S.2523
V-S.2524
8" SA
V-S.2525
V-S.2526
8" SA
C.1 C.1
10" GLEA
8" GLEA
8" SA
16" SA 16" GLEA 12" SA 20" GLEA 6" SA 14" EA DN TO FUME HOOD (TYP-2) 1 8" SA 8" GLEA 22" GLEA
6" SA
8" SA
6" SA V-S.2532 10" GLEA V-E.2501 SD-A 300 CFM V-E.2531 V-S.2531 SD-A 180 CFM 6" GLEA
10" GLEA
12" SA
12" GLEA
6" GLEA
8" SA
V-E.2534
V-S.2500
V-E.2536
V-E.2532
8" SA
V-E.2535
6" GLEA
8" SA
8" SA
38"x16" GLEA
12" GLEA
40"x20" GLEA
14"x14" GLEA
10" GLEA
10" GLEA
10" GLEA
44"x16" SA
8" GLEA
12" GLEA
12" GLEA
V-E.2500
10" GLEA
14" FHEA
14" FHEA
10" GLEA
10" GLEA
16" SA
V-S.2534
V-S.2535
V-S.2536
V-S.2538
V-S.2533
V-E.2539
12" GLEA
V-C.2537.A
V-C.2533.A
V-C.2533.B
40"x20" RA
8" SA
8" SA
8" SA
8" SA
8" SA
20" SA
C.9 C.9
FD
SD-A 8"
V-C.2537.B
C.8
V-S.2537
10" GLEA
V-S.2539
16" SA
20" SA
V-E.2510
8" SA
8" SA
8" GLEA
10" GLEA
CP-11243
ARCH. MECH.
LE-A 6'-0" LENGTH 2'-0" ACTIVE 4'-0" BLANK-OFF (TYP-11)
D D
COMBINATION FIRE/SMOKE DAMPER (TYP.)
14" FHEA
14" FHEA
10" GLEA 8" GLEA EG-A 230 CFM 26"x26" EA UP 22" EA DN FD 22" FHEA
14" SA
10" GLEA
A "S 16 "x 26
J. Kasdorf
ELEC.
R. Frazee
L.A.
8" GLEA
FH EA
D. Wilber
Project Administrator:
30" SA 32" SA 44"x16" SA LD-G 10" NECK 6'-0" LENGTH (TYP-9) 3
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
22" FHEA 42"x36" SA FD 8" SA EG-A 365 CFM FD EG-A 290 CFM 10" GLEA
18" FHEA 12" SA 10" GLEA 12" GLEA 10" GLEA 12" GLEA 12" SA 12" SA EG-A 290 CFM EG-A 290 CFM 10" GLEA 12" GLEA EG-A 290 CFM EG-A 290 CFM 10" GLEA 8" GLEA EG-A 290 CFM 14"x14" GLEA 22"x18" GLEA
26"x16" SA
22" SA
D. DiCiuccio
Drawing Scale:
10" SA
12" SA
12" GLEA
10" GLEA
1/4" = 1'-0"
12" SA
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
D.3
V-E.2210
10" GLEA 12" GLEA V-S.2200.A 10" GLEA V-S.2200.B 10" GLEA
V-E.2200.C
V-E.2200.D
V-E.2200.A
V-E.2200.B
V-S.2210
14"x14" GLEA
LAB 2200
V-E.2200.E
V-S.2100
28"x16" RA
12" GLEA
12" GLEA
12" GLEA
10" SA 14" SA
12" GLEA
10" SA
12" GLEA
10" SA
10" SA
8" GLEA
LE-A 4'-0" LENGTH 2'-0" ACTIVE 2'-0" BLANK-OFF (TYP-3) 3 8" GLEA
14" SA
14" SA
10" GLEA
16" SA
SD-A 10"
SD-A 10"
SD-A 10"
SD-A 10"
SD-A 10"
SD-A 10"
14" SA
8" SA
3 SD-A 10"
8" SA 10" GLEA 12" SA SD-A 10" 3 14" GLEA 16" GLEA 18" GLEA 20" GLEA 22" GLEA 22"x18" GLEA
22" RA
18" RA
10"x10" RA
12204-1000
Enlarged Second Floor Lab Plan Sheet Metal
E E
A-2 255/170 20"x12" RA 20"x12" RA
3
1/5/2014 9:50:04 PM
4.5
5.5
6
1 M2.2
1/4" = 1'-0"
NORTH
6.5
7.5
8.5
9.5
10
M2.2a
OF
10" SA
B.6
10" GLEA
8" SA
14"x24" GLEA
12" GLEA
S. Gardner
APPR. Project Designer:
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
A "R 20 "x 40
GENERAL NOTES
SHEET METAL
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5'-0". REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
KEY NOTES
SHEET METAL
1 LINEAR DIFFUSER MOUNTED VERTICALLY IN METAL PANEL WALL SYSTEM.
2. 3. 4.
5. 6. 7. 8. 9.
10. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
LD-1 9'-0" LENGTH 3'-0" ACTIVE 6'-0" BLANK -OFF 200 CFM 10"x6" SA BELL MOUTH 180 CFM 10"x10" RA
STAIR SW3-3
FCU SW3-3 (TYPE B)
LOUNGE 3HW1A
10"x6" SA 6"x6" RA CAPPED FOR FUTURE
SHELL 3300
A-2 200/135
A.6
A-3 500/335
8" SA 16"x14" SA
16"x14" SA
A-6 1500/1000 28"x12" RA BELL MOUTH 2225 CFM (TYP-2) 10" SA 14" SA 28"x16" SA 14"x20" SA 20"x16" RA 44"x42" RA UP & DN
22" RA
12" SA FD
20" SA
48"x48" EA UP & DN
ELEVATOR #1 EP1
FD FD VD (TYP.)
46"x46" SA UP & DN
28"x16" SA
32"x30" EA UP & DN
VD
VD
42"x18" RA
C C.1
14"x20" SA 14"x14" RA UP TO 4TH FLR.
(TYP-4)
14"x14" RA 10"x4" SA
48"x20" RA
STAIR SW1-3
10"x6" SA
20" SA
30"x12" SA
48"x30" RA
SD-C 300 CFM (TYP-5) A-3 465/310 14"x16" SA UP TO 4TH FLR. 14"x16" SA 42"x36" SA UP & DN 42"x36" SA UP 32"x30" EA UP & DN (OFFSET BELOW 26"x26" SA) 22" EA CAPPED FOR FUTURE
C.9 D
UNIT HEATER (UH) TYP. SEE PIPING PLANS
VD (TYP)
10" SA
10"x4" SA (TYP-3)
FD
56"x44" EA UP
CORRIDOR 3HW1
ELEVATOR #2 EP2
CP-11243
FD COMBINATION FIRE/SMOKE DAMPER (TYP FOR SHAFT PENETRATIONS)
28"x20" RA
ARCH.
J. Kasdorf
ELEC.
R. Frazee
8" SA 12"x10" RA 10" SA 40"x16" RA 14" SA VD ( TYP.) 12"x12" EA UP 12"x8" EA DN
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
CORRIDOR 3HW1C
E
10" SA LD-E 300 CFM A-3 500/335
J. Schwartz
Q.M. Review:
D. DiCiuccio
MECHANICAL ROOM 3650
Drawing Scale:
SHELL 3840
As indicated
SHELL 3020
10"x10" SA
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
FCU SW2-3 (TYPE B)
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
E.4
10" SA LD-1 9'-0" LENGTH 3'-0" ACTIVE 6'-0" BLANK -OFF 270 CFM
SHELL 3100
LOUNGE 3HW1B
LD-D 1 500 CFM
STAIR SW2-3
12204-1000
Third Floor Plan - Sheet Metal
1/5/2014 9:50:10 PM
NORTH
M2.3
OF
SHELL 3000
10" SA
10" SA 12"x12" RA
S. Hopper
CIVIL
S. Gardner
APPR.
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
SHEET METAL
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5'-0". REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
KEY NOTES
SHEET METAL
1 2 RETURN AIR THROUGH CEILING OPENING TO ATRIUM BY ARCHITECTURAL TRADES. FLOOR MOUNTED BAR GRILLE TO RUN CONTINUOUS WALL-TOWALL. CONTRACTOR TO VERIFY EXACT FIELD CONDITIONS PRIOR TO ORDERING. TOTAL SUPPLY AIR INDICATED TO BE DIVIDED EQUALLY TO THREE SUPPLY PLENUM CONNECTIONS. LINEAR DIFFUSER MOUNTED VERTICALLY IN METAL PANEL WALL SYSTEM. 50"x50" EA DUCT OFFSET FROM SEF. PROVIDE TRANSITION AND FINAL CONNECTION TO CEILING GRILLE BY ARCHITECTURAL TRADES. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS.
2. 3. 4.
3 4
5. 6. 7. 8. 9.
10. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
LD-1 9'-0" LENGTH 3'-0" ACTIVE 6'-0" BLANK -OFF 200 CFM
STAIR SW3-4
10"x10" SA 10"x6" SA 10"x10" RA A-3 500/0 A-2 200/135 10" SA 8" SA
10"x10" SA
SHELL 4300
A.6
STAIR SW5-4
B
SHELL 4000
A-6 1500/1000
20" SA
48"x48" EA UP & DN
ELEVATOR #1 EP1
10" SA 14" SA 20"x14" SA 50"x50" EA UP TO SEF (TYP-4) FD FD
46"x46" SA UP & DN
32"x30" EA UP & DN
VD ( TYP.)
C C.1
STAIR SW1-4
4
40"x20" RA
56"x44" SA UP
C.9 D
14"x16" UP FROM 3RD FLR. 22"x16" EA UP TO TEF-1 10"x10" EA CAPPED FOR FUTURE 22"x16" EA DN (TOILET ROOM EXHAUST) 14" SA
56"x44" EA UP
22" SA
Unoccupied Unoccupied
FD 40"x20" RA
ELEVATOR #2 EP2
STAIR SW4-4
CUH 4.2
CP-11243
ARCH.
HORIZONTAL FIRE DAMPER AT FLOOR 16"x12" EA 12"x12" EA DN
FD
12"x12" EA UP TO EF-1
14" SA 20" EA CAPPED FOR FUTURE 12"x12" RA 8" SA 12"x10" RA 10" SA 14" SA
SHELL 4600
J. Kasdorf
ELEC.
16"x12" EA
R. Frazee
L.A.
SHELL 4020
(TYP-5)
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
E
10" SA
D. DiCiuccio
MECHANICAL ROOM 4650
Drawing Scale:
SHELL 4840
As indicated
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
E.4
LR-A 48"x5" 270 CFM 48"x5" RA BOOT
LD-1 9'-0" LENGTH 3'-0" ACTIVE 6'-0" BLANK -OFF 200 CFM
LOUNGE 4HW1B
12204-1000
Fourth Floor Plan - Sheet Metal
1/5/2014 9:50:17 PM
NORTH
M2.4
OF
22" RA
30"x12" SA
S. Hopper
CIVIL
S. Gardner
APPR.
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
SHEET METAL
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5'-0". REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
2. 3. 4.
5. 6. 7. 8. 9.
10. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
4
RELIEF PLENUM 26" W x 72" H x 24" D INSULATED PLENUM CONNECT TO LOUVER BY ARCH. TRADES
4.5
1 M6.2 LAB EXHAUST BYPASS 110" W x 84" H x 24" D INSULATED PLENUM CONNECT TO LOUVER BY ARCH. TRADES
5.5
6
2 M6.2
6.5
7
CONTROL PANEL (TYP)
7.5
8
3 M6.2
8.5
OUTSIDE AIR INTAKE TO HVAC-3 190" W x 120" H x 36" D INSULATED PLENUM CONNECT TO LOUVER BY ARCH. TRADES
OUTSIDE AIR INTAKE TO HVAC-1 148" W x 120" H x 36" D INSULATED PLENUM CONNECT TO LOUVER BY ARCH. TRADES
10
B B
VESTIBULE SW5-5A
CUH PH.1 UH PH.1 MOTORIZED CONTROL DAMPER SA-1 SA-1 (TYPE B) 14"x14" MOTORIZED CONTROL DAMPER (TYP-2) HVAC 3A UH PH.3 (TYPE B) SERVICE CLEARANCE (TYP.) UH PH.5 MOTOR CONTROL DAMPERS
M6.2
FD FD
96"x24" OA
54"x36" RA
32 "x 30 "F
54"x36" RA
46"x46" GLEA
52"x44" GLEA FD
56"x36" OA
B.5 B.6
44"x42" RA
SH 3
96"x26" OA
46"x46" SA
B.7 B.7
42" GLEA TO LEF-1 ON ROOF
46"x46" SA
C C
90"x48" GLEA TWO-STACKED CONTROLLED ENVIRONMENTAL ROOM CONDENSERS (TYP-8) FUTURE TWO-STACKED CONTROLLED ENVIRONMENTAL ROOM CONDENSERS (TYP-8) HVAC 2 56"x36" OA 96"X36" OA DN TO HVAC-1 HVAC 1 56"x36" OA
UH PH.7 (TYPE B)
C.1 C.1
C.2
56"x36" OA
46"x46" SA
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
STAIR SW4-5
96"x28" OA HVAC 4 56"x44" SA
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
42" GLEA TO LEF-3 ON ROOF 42"x36" SA DN TO HVAC-2 56"x36" OA 56"x44" SA SH 4
Q.M. Review:
D. DiCiuccio
Drawing Scale:
C.8
C.9 C.9
42"x36" SA DN TO 3RD & 4TH FLR
UH PH.2 (TYPE B)
42"x36" SA DN TO HVAC-1
1/4" = 1'-0"
96"X28" OA DN TO HVAC-4
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
42"x36" SA
42"x36" SA
96"x28" OA
SH 2
60"x44" GLEA
56"x44" GLEA
56"x44" GLEA
D D
D:\Revit Local\122041000-MSU BioEngineering-M14_Central_draphael.rvt
UH PH.6
56 "x4 4" G
(TYPE B)
LE A
FD
ELEVATOR #2 EP2
FD
FD 42"x36" SA 42"x36" SA
32"x30" FHEA
STAIR SW4-4
32"x30" FHEA
UH PH.4 (TYPE B)
FD
c
D.3
FD SH 1 OUTSIDE AIR INTAKE TO HVAC-4 190" W x 120" H x 36" D INSULATED PLENUM CONNECT TO LOUVER BY ARCH. TRADES OUTSIDE AIR INTAKE TO HVAC-2 148" W x 120" H x 36" D INSULATED PLENUM CONNECT TO LOUVER BY ARCH. TRADES
12204-1000
Enlarged Penthouse Plan - Sheet Metal
2.9 3
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
1/5/2014 9:50:22 PM
1/4" = 1'-0"
NORTH
M2.5
OF
H EA
32"x30" FHEA
32"x30" GLEA
(TYPE B)
FD
S. Gardner
APPR.
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
SHEET METAL
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSTALLATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE IN AREA WITHOUT A CEILING UNLESS INDICATED OTHERWISE. DUCT CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT CONNECTION SIZE UNLESS NOTED OTHERWISE. MAXIMUM LENGTH ON FLEXIBLE DUCT SHALL BE 5'-0". REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT DIFFUSER LOCATIONS IN AREAS WITH A CEILING.
KEY NOTES
SHEET METAL
1 2 3 4 5 ROOF MOUNTED PIPE SUPPORT. ROOF MOUNTED DUCT SUPPORT 3" PCHS & PCHR UP ALONG WALL. ROUTE THROUGH WALL INTO PENTHOUSE AT 8'-8" ABOVE ROOF DECK. 42" DIAM. EXHAUST DUCT THROUGH WALL INTO PENTHOUSE. AIR-COOLED CHILLER, ACCH-1, MOUNTED WITH SPRING VIBRATION ISOLATORS TO STRUCTURAL ROOF CURB BY OTHERS. LAB EXHAUST FAN ON FACTORY-BUILT BASE MOUNTED WITH SPRING VIBRATION ISOLATORS TO STRUCTURAL ROOF CURB BY OTHERS. EXHAUST FAN MOUNTED ON ROOF CURB PROVIDED BY FAN MANUFACTURER. ROOF CURB BASE SHALL BE PITCHED TO MATCH ROOF SLOPE. CURB SHALL EXTEND 18" ABOVE TOP OF FINISHED ROOF. 46" DIAM. EXHAUST STACK TO EXTEND 10'-0" ABOVE TOP OF PENTHOUSE PARAPET. STACK TO BE SUPPORTED BY STRUCTURAL STEEL BASE FRAME PROVIDED BY OTHERS. 4" PCHS & PCHR DN THROUGH ROOF INTO PENTHOUSE. COORDINATE ROOF PENETRATIONS WITH ARCHITECTURAL TRADES.
2. 3. 4.
5. 6. 7. 8. 9.
10. DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
A.6
B
5 ACCH 1 3 4" PCHS FROM PENTHOUSE 4" PCHS TO PENTHOUSE 1 (TYP.) 10" STEAM RELIEF VENT. TERMINATE MINIMUM 7'-0" ABOVE ROOF SURFACE. 6" STEAM RELIEF VENT. TERMINATE MINIMUM 7'-0" ABOVE ROOF SURFACE.
9 SEF 1 7
C C.1
SEF 2 7 FC 1
6 LEF 1
42" GLEA 2 4
SEF 3 7 6 LEF 3
42" GLEA
C.9 D
SEF 4 7
CP-11243
ARCH. MECH.
J. Kasdorf
TEF 1 7 EF 1 7
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
As indicated
Issue Date:
E.4
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
12204-1000
Roof Plan - Sheet Metal
1/6/2014 8:37:24 AM
NORTH
M2.6
OF
S. Gardner
APPR.
B. Moore
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
HVAC PIPING
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
2. 3. 4.
5. 6. 7.
0.1
4.5
5.5
6.5
7.5
8.5
10
A.6
C C.1
8" HPS(88#) 6" LPC 2" HPC 4" LPC 4" PCR CR 1
C.9 D
CP-11243
ARCH. MECH.
J. Kasdorf
INCOMING STEAM UTILITY PIPING. REFER TO SITE UTILITY MECHANICAL DRAWINGS HPS(88#) PCR
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
As indicated
4" 8"
Issue Date:
01-08-2014
Issued for:
Bid Release #2 - Bids
E.4
12204-1000
Steam Tunnel Floor Plan - Piping
1/5/2014 9:50:35 PM
NORTH
M3.0
OF
S. Gardner
APPR.
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
HVAC PIPING
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
KEY NOTES
HVAC PIPING
1 FINNED TUBE RADIATOR CONTROLLED BASED ON OUTDOOR AIR TEMPERATURE. REFER TO TEMPERATURE CONTROLS DRAWINGS. SPILL COND DRAIN INDIRECTLY TO FLOOR DRAIN. ROUTE COND DRAIN PIPING THROUGH LAB CASEWORK AND SPILL INDIRECTLY TO OPEN HUB DRAIN BELOW SINK. ROUTE HWH PIPING THROUGH PRE-DRILLED HOLE IN COLUMN. 1 1/2" COND DRAIN TO SPILL 1'-6" ABOVE FINISHED GRADE. TERMINATE WITH 90-DEGREE ELBOW TURNED DOWN WITH INSECT SCREEN. SEAL ANNULAR SPACE AROUND PIPE AT WALL PENETRATION WEATHER TIGHT WITH SILICONCE-BASED SEALANT. FACILITY MONITORING SYSTEM SENSOR SUITES, VACUUM PUMPS, AND CONTROLS. 3/4" HWHS & HWHR ROUTED IN WALL CAVITY BEHIND PERIMETER FINNED-TUBE RADIATION. COMPENSATOR TYPE EXPANSION JOINT, METRAFLEX MODE HPFF2 OR EQUAL.
2. 3. 4.
2 3
4 5
5. 6. 7.
6 7 8
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
PIPE ANCHOR HWHS IN WALL 1" HWHS DN TO WALL CAVITY BEHIND FTR
HWHR 8 5 FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHS FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHS FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHR FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHR FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3)
PIPE ANCHOR HWHR IN WALL 1" HWHR UP FROM WALL CAVITY BEHIND FTR 2
VESTIBULE 1VB1
T 3/4" 3/4"
COND
1
PCHR PCHS HWHS HWHR
4
HWHR
M6.1
FCU 1VB1
STAIR SW3-1
PIPE ANCHOR (TYP.)
(TYPE A)
OFFICE 1311
OFFICE 1319
A-2 5.5 MBH 0.6 GPM A-2 5.5 MBH 0.6 GPM T T T 1"
(TYPE B)
A.6
FTR-A 4' - 0" AL 3.3 MBH 1.0 GPM
3/4" 1 1/4"
OFFICE 1313
3/4" 3/4"
3/4" 3/4"
RHC 1610
3/4" 3/4"
OFFICE 1314
OFFICE 1315
OFFICE 1316
3/4" 3/4"
OFFICE 1317
OFFICE 1318
3/4" 3/4"
3" 3"
1" 1" 6
B
3/4" 3/4" A-6 32.4 MBH 3.2 GPM 1" 1" 1" 1 1/4" T T
ELEVATOR #1 EP1
WORKROOM 1302
3 M6.0
LAB 1400
SD
IT CLOSET 1011A
1" 1"
3/4" 3/4"
PCHS PCHR HWHR HWHS
SD
T 1" 1" T
HWHS
1" 1 1/4"
1 1/4" 1 1/4"
C C.1
KITCHENETTE 1011
3/4" FTR-B 5' - 0" AL 4.1 MBH 1.0 GPM FTR-B 5' - 0" AL 4.1 MBH 1.0 GPM FTR-B 5' - 0" AL 4.1 MBH 1.0 GPM
CORRIDOR 1HW1
1 M3.1a
C.9
HWHR
D
CONV A
3/4" 3/4"
T T
STAIR SW1-1
ELEVATOR #2 EP2
CP-11243
3/4" 3/4" PCHS PCHR HWHR HWHS FCU 1830 (TYPE D) 1" 1" 3/4" 3/4" 3/4" 3/4" 1" 1" T 1 1/2" 1 1/2" 1 1/4" 1 1/4" T FCU 1830A.2 3/4" 3/4" (TYPE D) 3/4" 3/4" 1" 1" 1 1/2" FCU 1840 (TYPE C) 1 1/2" 1 1/2" 1 1/2" T T 3/4" 3/4"
1" 1"
CORRIDOR 1HW2
ARCH.
J. Kasdorf
ELEC.
3/4" 3/4"
WORKROOM 1040A
R. Frazee
L.A.
UNASSIGNED 1840
2" 2"
D. Wilber
DC 2 3/4" 3/4" 1 1/4" 1 1/4"
Project Administrator:
UH 1.1 (TYPE A)
3/4" 3/4"
E
CONV B
3/4" 3/4"
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
1" 3/4" T
OFFICE 1113
OFFICE 1115
T
OFFICE 1116
OFFICE 1118
T
OFFICE 1119
As indicated
Issue Date:
DC 1
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
E.4
WOMEN'S TOILET 1022
PCHS HWHS
HWHS
OFFICE 1111
1" HWHR UP FROM WALL CAVITY BEHIND FTR PIPE ANCHOR HWHR IN WALL 4 4 4 4 4 4
FCU (AT LANDING) SW2-1.2 (TYPE B) FCU (AT FLOOR) SW2-1.1 (TYPE B)
STAIR SW2-1
3 M6.1
VESTIBULE 1VB2
1 1/2"
COND
3/4" 3/4"
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHR
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHR
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHS
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHS 8 HWHS
1" HWHS DN TO WALL CAVITY BEHIND FTR PIPE ANCHOR HWHS IN WALL
c
8 HWHS
12204-1000
First Floor Plan - Piping
1/5/2014 9:50:46 PM
NORTH
M3.1
OF
3/4" 3/4"
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144" Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
GENERAL NOTES
HVAC PIPING
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
KEY NOTES
HVAC PIPING
1 REHEAT COIL TO CONTROL TO SET DISCHARGE AIR TEMPERATURE. REFER TO TEMPERATURE CONTROLS DRAWINGS. 1 1/2" PCHS & PCHR VALVED AND CAPPED FOR FUTURE. 1" PCHS & PCHR VALVED AND CAPPED FOR FUTURE.
2. 3. 4.
2 3
5. 6. 7.
4.5
5.5
6.5
7.5
8.5
10
1" 1"
1 1/4" 1"
1" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3" 3" 1" 1"
B B
HWHR
HWHR
HWHS
HWHR
HWHS
HWHS
3/4"
3/4" 3/4"
HWHR
PCHR
V-S.1400.C
RHC 1300
B.5
1"
V-S.1410
V-S.1300
PCHS
3/4" 3/4"
RHC 1400.A
RHC 1400.B
B.6
2 1/2" 2 1/2"
V-S.1531
V-S.1521
V-S.1522
V-S.1532
C C
V-S.1523
PCHS
C.1 C.1
PCHR
C.2
TISSUE CULTURE 1521
1" 1"
3/4" 3/4" 3/4" 3/4" RHC 1523 2 RHC 1501 1 3/4" 3/4"
V-S.1526
RHC 1531
RHC 1521
RHC 1522
RHC 1532
RHC 1600
PCHS
RHC 1510 RHC 1526 3/4" 3/4" V-S.1704 2 RHC 1704 PCHS
3 3"
V-S.1524
2 1/2" 2 1/2"
PCHS
V-S.1703
1 1/4" 1 1/4"
V-S.1525
RHC 1524
RHC 1703
2 1/2" 2 1/2"
PCHR
2 PCHR
V-S.1534
V-S.1535
PCHS
PCHS
V-S.1501
PCHR
3/4" 3/4"
3/4" 3"
LPC
LPS(15#)
RHC 1535
3
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
RHC 1533 3/4" 3/4" 3/4" 3/4" RHC 1500 3/4" 3/4" T V-S.1500 T T
RHC 1536
C.8
C.9 C.9
V-S.1533
V-S.1536
SH 5
CP-11243
ARCH. MECH.
V-S.1511
T HWHR V-S.1701
PCHR
D D
J. Kasdorf
ELEC.
PCHS
R. Frazee
L.A.
HWHS
HWHR
HWHR
HWHR
HWHS
RHC 1701
D. Wilber
Project Administrator: Project Designer:
J. Johnson
HWHR
HWHS
HWHS
HWHS
3 3
Project Arch/Eng:
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
D.3
1 1/4" 1 1/4"
HWHS
3/4" 3/4"
3/4"
V-S.1200.C
2 1/2"
V-S.1100
RHC 1230
HWHR
LAB 1200
3/4"
HWHS
V-S.1230
1/4" = 1'-0"
1 1/2" 1 1/2" 2" 2"
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
RHC 1220
2 1/2"
3/4" 3/4"
3/4" 3/4"
RHC 1200.C
3/4" 3/4"
V-S.1220
3/4" 3/4"
RHC 1210
1" 1"
3/4" 3/4"
3/4" 3/4"
1" 1"
V-S.1200.D
V-S.1210
RHC 1200.A
RHC 1200.B
3/4" 3/4"
RHC 1100
1 RHC 1200.D
3/4" 3/4"
12204-1000
Enlarged First Floor Lab Plan - Piping
4.5
5.5
6.5
7.5
8.5
9.5
10
1/5/2014 9:50:52 PM
M3.1
1/4" = 1'-0"
NORTH
M3.1a
OF
B.7
3/4" 3/4"
HWHS
2 1/2"
HWHR
LAB 1400
RHC 1400.C 3/4"
1" 1"
1" 1"
HWHR
S. Gardner
APPR.
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
GENERAL NOTES
HVAC PIPING
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
KEY NOTES
HVAC PIPING
1 FINNED TUBE RADIATOR CONTROLLED BASED ON OUTDOOR AIR TEMPERATURE. REFER TO TEMPERATURE CONTROLS DRAWINGS. ROUTE HWH PIPING THROUGH PRE-DRILLED HOLE IN COLUMN. FACILITY MONITORING SYSTEM SENSOR SUITES, VACUUM PUMPS, AND CONTROLS. 3/4" HWHS & HWHR ROUTED IN WALL CAVITY BEHIND PERIMETER FINNED-TUBE RADIATION. COMPENSATOR TYPE EXPANSION JOINT, METRAFLEX MODE HPFF2 OR EQUAL. FINNED-TUBE RADIATOR INSTALLED IN FRONT OF STRUCTURAL ELEMENT INSIDE CUSTOM ARCHITECTURAL ENCLOSURE. REFER TO DETAIL.
2. 3. 4.
2 3 4 5 6
5. 6. 7.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
PIPE ANCHOR HWHS IN WALL 1" HWHS DN TO WALL CAVITY BEHIND FTR FTR-C 4' - 6" AL 3.7 MBH 1.0 GPM FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) HWHR 5 FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHS PIPE GUIDE HWHS FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHR FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHR FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) HWHS 5 FTR-A 1' - 4" AL 1.1 MBH 1.0 GPM (TYP-4)
PIPE ANCHOR HWHR IN WALL 1" HWHR UP FROM WALL CAVITY BEHIND FTR 2
A
T HWHR
LOUNGE 2HW1A
T
ADMIN 2060
M6.1
STAIR SW3-2
FCU SW3-2 (TYPE B)
1"
WORKROOM 2301
A-2 5.5 MBH 0.6 GPM T T
A.6
FTR-A 4' - 0" AL 3.3 MBH 1.0 GPM
OFFICE 2319
A-2 5.5 MBH 0.6 GPM 3/4" 3/4"
B
FTR-A 4' - 0" AL 3.3 MBH 1.0 GPM FTR-C 2' - 6" AL 2.0 MBH 1.0 GPM FTR-C 6' - 0" AL 4.9 MBH 1.0 GPM FTR-C 6' - 0" AL 4.9 MBH 1.0 GPM FTR-C 6' - 0" AL 4.9 MBH 1.0 GPM 3/4" 3/4" A-4 15.8 MBH 1.6 GPM 1 1/2" COND UP/DN 3/4" 3/4" T
HWHS
HWHR
WORKROOM 2302
3" HPS(50#) 10" SRV-V 2" HPC 6" HWHS 6" HWHR 10" CHWR 10" CHWS 8" LPS(15#) 4" LPC
ELEVATOR #1 EP1
CORRIDOR 2HW3
3/4" 3/4"
LAB 2400
C C.1
T T T
T T
T T T T
T T
T T
FTR-A 5' - 0" AL 4.1 MBH 1.0 GPM FTR-A 5' - 0" AL 4.1 MBH 1.0 GPM FTR-A 5' - 0" AL 4.1 MBH 1.0 GPM
FUME HOOD 2527 TISSUE CULTURE 2529 LINEAR EQUIPMENT ROOM 2600 SUBSTATION 2810
1 M3.2a
C.9 D
CONV A 3/4" 3/4"
T T
T T
T T
T T
1" 1"
HWHR
HWHS
LAB 2200
CP-11243
1" 1"
PCHR HWHS
CORRIDOR 2HW2
PCHS HWHR T FCU 2830 (TYPE D) 3/4" 3/4" T
ARCH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
CORRIDOR 2HW1C
3/4" 3/4" A-3 11.9 MBH 1.2 GPM
WORKROOM 2101
WORKROOM 2102
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
E
CONV B
D. DiCiuccio
GENDER NEUTRAL TOILET 2023
3/4" A-3 10.8 MBH 1.1 GPM A-2 4.3 MBH 0.5 GPM OFFICE 2111
E.4
OFFICE 2112
HWHS
OFFICE 2113
OFFICE 2114
T
3/4"
3/4"
OFFICE 2115
OFFICE 2116
OFFICE 2118
OFFICE 2119
1" T
MECHANICAL CUSTODIAL ROOM 2840 3/4" 2650 3/4" 205 A-2 3/4" 7.6 MBH 3/4" 0.8 GPM
1" 1"
Drawing Scale:
As indicated
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
3/4" 3/4"
LOUNGE 2HW1B
STAIR SW2-2
3 M6.1
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHR
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHR
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHS
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHS 5 HWHR
1" HWHS DN TO WALL CAVITY BEHIND FTR PIPE ANCHOR HWHS IN WALL
c
1" HWHR UP FROM WALL CAVITY BEHIND FTR PIPE ANCHOR HWHR IN WALL
5 HWHS
12204-1000
Second Floor Plan - Piping
1/5/2014 9:51:05 PM
NORTH
M3.2
OF
1" 1 1/4"
OFFICE 2313
OFFICE 2314
3/4" 3/4"
OFFICE 2315
OFFICE 2316
3/4" 3/4"
OFFICE 2317
OFFICE 2318
3/4" 3/4" 3/4" 1"
PCHR HWHR
3/4" 3/4"
3" 3"
S. Hopper
CIVIL
S. Gardner
APPR.
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
HVAC PIPING
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
KEY NOTES
HVAC PIPING
1 REHEAT COIL TO CONTROL TO SET DISCHARGE AIR TEMPERATURE. REFER TO TEMPERATURE CONTROLS DRAWINGS. 1 1/2" PCHS & PCHR VALVED AND CAPPED FOR FUTURE. 1" PCHS & PCHR VALVED AND CAPPED FOR FUTURE.
2. 3. 4.
2 3
5. 6. 7.
4.5
5.5
6.5
7.5
8.5
3/4" 3/4"
B B
LAB SUPPORT 2410
HWHS 1 1/4" 1"
2 1/2" 2" HWHR HWHS PIPE ANCHOR (TYP.) 3/4" 3/4" 1" 1" RHC 2400.A 3/4" 3/4" V-S.2400.A V-S.2400.B V-S.2410 HWHR 3/4" 3/4" RHC 2400.B 3/4" 3/4" 1 RHC 2300 3/4" V-S.2400.C V-S.2400.D V-S.2400.E 3/4" RHC 2400.C 3/4" 3/4" 3/4" 3/4" 1" 1"
HWHR
HWHS
2 1/2" 1 1/2"
3" 1"
HWHR
1" 1"
3/4" 3/4"
HWHR PCHR
RHC 2400.D
3/4" 3/4"
RHC 2400.E
3/4" 3/4"
HWHS
3/4"
V-S.2300
B.5 B.6
3/4" 3/4"
3/4" 3/4"
3/4" 3/4"
3/4" 3/4"
3/4"
HWHS
2 1/2"
HWHR
2" 2 1/2"
PCHR
PCHS
HWHS
1" 1" T T T T 3/4" 3/4" 3/4" T 3/4" 3/4" V-S.2529 3/4" 3/4" T T 3/4" 3/4" 3 V-S.2600
T T
C C
V-S.2523
V-S.2524
V-S.2525
V-S.2510
V-S.2521
V-S.2522
V-S.2511
C.2
TISSUE CULTURE 2521
V-S.2527
V-S.2526
C.1 C.1
V-S.2501
3/4"
PCHS
1 RHC 2523 RHC 2501 RHC 2524 2 2 1/2" 2 1/2" RHC 2525 RHC 2526
3/4" 3/4"
RHC 2527
RHC 2522
1 1/4" 1 1/4"
RHC 2510
RHC 2511
RHC 2528
PCHR
HWHS HWHR
PCHR
V-S.2532
2 V-S.2531 RHC 2500 V-S.2500 RHC 2534 3/4" 3/4" 3/4" 3/4" V-S.2533
PCHS
RHC 2535
PCHR
V-S.2536
RHC 2532
V-S.2534
V-S.2535
V-S.2539
RHC 2531
RHC 2533
1 1/4" 1 1/4"
3/4" 3/4"
3 3
HWHR
C.8
C.9 C.9
V-S.2537
3/4" 3/4"
CP-11243
ARCH. MECH.
PCHS
D D
T T
T T
T T
T T
T T
J. Kasdorf
ELEC.
HWHR PCHR
R. Frazee
L.A.
HWHR
D. Wilber
Project Administrator:
HWHS
HWHR
HWHR
HWHR
HWHR
HWHS
HWHR
J. Johnson
3 3
Project Arch/Eng:
J. Schwartz
Q.M. Review:
HWHS
HWHS
HWHS
HWHS
HWHR
HWHS
D. DiCiuccio
Drawing Scale:
D.3
HWHR HWHS V-S.2200.A V-S.2200.B 1" 1" 3/4" 3/4" 3/4" 3/4" V-S.2100 V-S.2200.C V-S.2200.D 3/4" V-S.2200.E 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 1" 1" 1" 1"
1/4" = 1'-0"
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
LAB 2200
V-S.2210
3/4" 3/4"
HWHS HWHR
RHC 2400.A
3/4" 3/4"
3/4" 3/4"
RHC 2400.C
3/4" 3/4"
RHC 2400.D
3/4" 3/4"
RHC 2400.E
1 1/4" 1 1/4"
HWHS
RHC 2210
RHC 2100
3/4"
1 1/4" 2 1/2"
1" 3"
c
12204-1000
Enlarged Second Floor Lab Plan Piping
4.5
5.5
6.5
7.5
8.5
9.5
10
1/6/2014 8:37:35 AM
M3.2
1/4" = 1'-0"
NORTH
M3.2a
OF
HWHR
HWHR
HWHR
B.7
HWHR
HWHR
1 1/4"
3/4" 3/4"
HWHS
1 1/4"
HWHS
HWHS
2 1/2"
LAB 2400
HWHS
HWHR
PCHS
S. Gardner
APPR. Project Designer:
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
HVAC PIPING
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
KEY NOTES
HVAC PIPING
1 FINNED TUBE RADIATOR CONTROLLED BASED ON OUTDOOR AIR TEMPERATURE. REFER TO TEMPERATURE CONTROLS DRAWINGS. ROUTE HWH PIPING THROUGH PRE-DRILLED HOLE IN COLUMN. FACILITY MONITORING SYSTEM SENSOR SUITES, VACUUM PUMPS, AND CONTROLS. 3/4" HWHS & HWHR ROUTED IN WALL CAVITY BEHIND PERIMETER FINNED-TUBE RADIATION. COMPENSATOR TYPE EXPANSION JOINT, METRAFLEX MODE HPFF2 OR EQUAL. 1 1/2" PCHS & PCHR VALVED AND CAPPED FOR FUTURE. 1 1/4" PCHS & PCHR VALVED AND CAPPED FOR FUTURE. 1" PCHS & PCHR VALVED AND CAPPED FOR FUTURE.
2. 3. 4.
2 3 4 5 6 7
5. 6. 7.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
PIPE ANCHOR HWHS IN WALL 1" HWHS DN TO WALL CAVITY BEHIND FTR FTR-C 4' - 6" AL 3.7 MBH 1.0 GPM FTR-C 4' - 6" AL 3.7 MBH 1.0 GPM FTR-C 4' - 6" AL 3.7 MBH 1.0 GPM FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3)
3/4" HWHS FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3)
HWHS PIPE GUIDE HWHS FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHR FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHR FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 5 FTR-A 1' - 4" AL 1.1 MBH 1.0 GPM (TYP-4) PIPE ANCHOR HWHR IN WALL 1" HWHR UP FROM WALL CAVITY BEHIND FTR
A
T
HWHR
SHELL 3300
LOUNGE 3HW1A
M6.1
1 1"
STAIR SW3-3
A.6
3/4" 3/4" 1" 1" HWHS HWHR PCHR PCHS 3" 3" LAB SHELL OUT 3610
3/4" 3/4"
UH 3.4 (TYPE B)
SHELL 3000
B
3/4" 1 1/4" UH 3.2 (TYPE B) A-6 32.4 MBH 3.2 GPM
HWHS
HWHS
HWHS
3/4" 3/4"
HWHS
ELEVATOR #1 EP1
4" PCHS
2" HPS (70#) & 1" HPL CAPPED FOR FUTURE 3" HPS(50#) 2" HPC 10" SRV-V 4" HWHS 6" SRV-V 4" HWHR 10" CHWR 10" CHWS 8" LPS(15#) 4" LPC
3/4"
3/4" HWHS
SHELL 416
3/4" 3/4"
HWHS
C C.1
1" 1"
1 1/4" 1 1/4"
2 1/2" 2 1/2"
3"
HWHR
PCHR
3/4" HWHS UP 3/4" HWHR UP FTR-B 5' - 0" AL 4.1 MBH 1.0 GPM FTR-B 5' - 0" AL 4.1 MBH 1.0 GPM FTR-B 5' - 0" AL 4.1 MBH 1.0 GPM
PCHS
PCHR
STAIR SW1-3
6
2 1/2" 2 1/2" 7 6
2 1/2" 2"
UH 3.3 (TYPE B)
HWHR
HWHS
UH 3.1 (TYPE B)
HWHR
C.9
8 8
ELEVATOR #2 EP2
HWHR
HWHS
3/4" 3/4"
HWHS HWHR PCHS PCHR
CP-11243
ARCH. MECH.
1 1/4" 1 1/4"
1" 1"
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
CORRIDOR 3HW1
HWHS T
J. Schwartz
Q.M. Review:
A-3 10.8 MBH 1.1 GPM A-2 5.8 MBH 0.6 GPM 1"
SHELL 3840
UH 3.6 (TYPE B)
D. DiCiuccio
Drawing Scale:
As indicated
SHELL 3100
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
E.4
HWHS
STAIR SW2-3
LOUNGE 3HW1B
3 M6.1
1" HWHR UP FROM WALL CAVITY BEHIND FTR PIPE ANCHOR HWHR IN WALL
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHR
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHR
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHS
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 5 3/4" HWHS HWHR
1" HWHS DN TO WALL CAVITY BEHIND FTR PIPE ANCHOR HWHS IN WALL
c
5 HWHS
12204-1000
Third Floor Plan - Piping
1/5/2014 9:51:22 PM
NORTH
M3.3
OF
3/4" 1"
S. Gardner
APPR.
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
HVAC PIPING
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
KEY NOTES
HVAC PIPING
1 FINNED TUBE RADIATOR CONTROLLED BASED ON OUTDOOR AIR TEMPERATURE. REFER TO TEMPERATURE CONTROLS DRAWINGS. ROUTE HWH PIPING THROUGH PRE-DRILLED HOLE IN COLUMN. FACILITY MONITORING SYSTEM SENSOR SUITES, VACUUM PUMPS, AND CONTROLS. 3/4" HWHS & HWHR ROUTED IN WALL CAVITY BEHIND PERIMETER FINNED-TUBE RADIATION. COMPENSATOR TYPE EXPANSION JOINT, METRAFLEX MODE HPFF2 OR EQUAL. FINNED-TUBE RADIATOR INSTALLED IN FRONT OF STRUCTURAL ELEMENT INSIDE CUSTOM ARCHITECTURAL ENCLOSURE. REFER TO DETAIL.
2. 3. 4.
2 3 4 5 6
5. 6. 7.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
PIPE ANCHOR HWHS IN WALL 1" HWHS DN TO WALL CAVITY BEHIND FTR FTR-C 4' - 6" AL 3.7 MBH 1.0 GPM FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3)
HWHR 5 FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHS FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHS FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHR FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHR FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3)
HWHS 5 FTR-A 1' - 4" AL 1.1 MBH 1.0 GPM (TYP-4) PIPE ANCHOR HWHR IN WALL 1" HWHR UP FROM WALL CAVITY BEHIND FTR
A
T
1"
A.6
HWHS CUH 4.1 A-3 0.0 MBH 0.5 GPM 1 1/4" 3/4" BOT. OF PIPE 14'-1" AFF 2 1/2" 2" HWHS BOT. OF PIPE 14'-1" AFF 1 1/2" 1 1/2" 1 1/2" 1 1/2" 3" A-2 4.3 MBH 0.5 GPM T
HWHR
SHELL 4300
LOUNGE 4HW1A
M6.1
STAIR SW3-4
HWHR
HWHS
B
SHELL 4000
A-6 32.4 MBH 3.2 GPM
3"
HWHS LPC
HWHR 2" BOT. OF PIPE 14'-1" AFF BOT. OF PIPE 11'-9" AFF
HWHR
HWHS LPC
1 1/2"
UH 4.2 (TYPE B)
4" 3" HPS(50#) BOT. OF PIPE 11'-7" AFF 10" CHWR 10" CHWS 8" LPS(15#) 4" LPC
10" SRV-V
ELEVATOR #1 EP1
6" SRV-V
HWHR
HWHR
4" PCHR
3"
3/4" 3/4" 2 1/2" PCHS & PCHR CAPPED FOR FUTURE 1 1/2" LPC UP 2"
SHELL 417
C C.1
FTR-A 5' - 0" AL 4.1 MBH 1.0 GPM FTR-A 5' - 0" AL 4.1 MBH 1.0 GPM FTR-A 5' - 0" AL 4.1 MBH 1.0 GPM
HWHR HWHS
2" 2 1/2"
UH 4.5 (TYPE B)
C.9 D
UH 4.1 (TYPE B) T
HWHR
HWHR
CORRIDOR 4HW1
CUH 4.2
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
HWHS
HWHR
SHELL 4020
R. Frazee
L.A.
3" 1"
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
UH 4.6 (TYPE B)
E
A-5 21.6 MBH 2.2 GPM
D. DiCiuccio
Drawing Scale:
SHELL 4840
As indicated
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
STAIR SW2-4
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
E.4
SHELL 4100
LOUNGE 4HW1B
HWHS
3 M6.1
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 3/4" HWHR
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) PIPE GUIDE HWHR
FTR-A 1' - 3" AL 1.0 MBH 1.0 GPM (TYP-3) 5 3/4" HWHS HWHR
1" HWHR UP FROM WALL CAVITY BEHIND FTR PIPE ANCHOR HWHR IN WALL
1" HWHS DN TO WALL CAVITY BEHIND FTR PIPE ANCHOR HWHS IN WALL
c
5 HWHS
12204-1000
Fourth Floor Plan - Piping
1/5/2014 9:51:26 PM
NORTH
M3.4
OF
2 1/2" 2"
1 1/2" 2 1/2"
1"
1" 3/4"
3" 3"
3/4" 3/4"
4" STM RELIEF VENT UP THROUGH ROOF 2 1/2" HWHS 2 1/2" HWHR 2" HPC 2" HPS (50#) & 1" HPC CAPPED FOR FUTURE
UH 4.4 (TYPE B)
HWHR
S. Gardner
APPR.
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
HVAC PIPING
1. VERIFY ALL CONDITIONS IN FIELD BEFORE CONSTRUCTION. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE. PROVIDE ALL MISC. STEEL AND ITEMS REQUIRED FOR THE PROPER INSULATION OF ALL PIPE SHEET METAL, AND EQUIPMENT. COORDINATE FLOOR, WALL & ROOF PENETRATIONS ETC. WITH ARCHITECTURAL TRADES. ALL HOT WATER FIN TUBE RADIATION COVERS SHALL RUN WALL TO WALL (OR COLUMN). DO NOT RUN ANY PIPING OR DUCTWORK INTO AN ELECTRICAL ROOM THAT DOES NOT SERVE THAT ROOM.
KEY NOTES
HVAC PIPING
1 LPC PIPING IN PIPE SLEEVE DOWN THROUGH FLOOR. PIPE SLEEVE SHALL BE CAST-IN-PLACE AND EXTEND A MINIMUM OF 4" ABOVE FINISH FLOOR. TWO-STACKED CONTROLLED ENVIRONMENT ROOM WATERCOOLED CONDENSERS PROVIDED BY OTHERS. PROCESSED CHILLED WATER PIPING, VALVES AND ACCESSORIES BY MECHANICAL (TYP-8). 1 1/2" PCHS & PCHR CAPPED FOR FUTURE.
2. 3. 4.
5. 6. 7.
4.5
1 M6.2
5.5
6
2 M6.2
6.5
7.5
8
3 M6.2
8.5
4 M6.2
10
B B
HWHR HWHS 1" 3/4" 3/4" HVAC 3A AHU-1 & AHU-2 TEMPERATURE CONTROL PANELS
10" CHWS DN 10" CHWR DN 8" LPS(15#) DN 2" LPC DN LPC UH PH.3 (TYPE B)
CUH PH.1
3/4" 3/4"
M6.2 UH PH.1 PCHS 4" PCHS & PCHR THROUGH WALL TO ROOF PCHR
6" 6"
LPC
ADS 2 UH PH.5
(TYPE B)
HRR
(TYPE B)
B.5 B.6
4" PCHS 4" PCHR ADS 4 ERU-1&1A TEMPERATURE CONTROL PANELS HWHR HWHS SH 3
LPC
4" 4"
HRS
1"
LPS(15#)
B.7 B.7
PCHP 1
4" 4"
HVAC 3
PCHR
PCHS
6"
6"
3" 10"
2 1/2"
CHWR
1 1/2" 3"
CHWS
1 1/2"
1 1/2"
1 2" LPC DN
LPC
2" 6"
C C
PCHR PCHS
6"
LPS(15#)
2"
LPS(15#) 6" CHWS CHWR CHWR CHWS 3/4" 3/4" 3/4" 3/4" 6" HWHS HWHR
LPS(15#)
LPS(15#)
4"
CHWS CHWR
LPC
CHWS CHWR
C.1 C.1
PCHR
LPC
3/4"
LPS(15#)
PFHX 1
C.2
4"
LPC
LPS(15#)
HWHR HWHS HWHS HWHR 6" 6" 3/4" 3/4" 2" 6"
HWHR HWHS
3/4" 3" 3" FUTURE TWO-STACKED CONTROLLED ENVIRONMENTAL ROOM CONDENSERS (TYP-8) 3/4" 3/4" 1 1/4" LPS(15#)
CHWS CHWR
3"
6"
2"
LPC
LPC
1 2" LPC DN
HWHR HWHS
CUH PH.2
3/4" 6" HVAC 1 1 1/4" LPS(15#) HVAC 2 6" ERU-2 & 2A TEMPERATURE CONTROL PANELS 3/4"
VESTIBULE SW4-5A
CP-11243
ARCH. MECH.
3 3
J. Kasdorf
ELEC.
HWHR HWHS HRS HRS
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
HWHR HWHS
HVAC 4
STAIR SW4-5
3/4" 3/4"
HWHR
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
ELEVATOR CONTROL EP2A
2"
6"
HWHS
2"
6"
SH 4
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
C.8
C.9 C.9
1/4" = 1'-0"
2 3
Issue Date:
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
D D
6 M6.2
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
1" LPC
6" LPC
SH 1
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
HVAC 4A SH 2
3/4"
UH PH.4 (TYPE B)
D.3
12204-1000
Enlarged Penthouse Plan - Piping
2.9 3
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
NORTH
M3.5
OF
VESTIBULE SW5-5A
HRS
HRS
CHWS
CHWR
HWHR HWHS
S. Gardner
APPR.
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO".
2. 3. 4.
$. 6.
0.1
4.5
5.5
6.5
7.5
8.5
10
A.6
3" SAN UP TO F) 3" SAN UP TO ,CO SAN I.E.=98' 6" FCO S 14 3" SAN UP I.E.=9'' 0" 3" SAN UP TO F) 2" SAN UP (PU"PE)) 6" ST UP 6" ST I.E.=9'' 0" S 1$ 3" SAN UP 3" 3" SAN UP 3" SAN UP S 2$ 3" SAN UP ST S 3" V UP 3" SAN UP 16 S 1' 3" SAN UP 3" V UP S 19 3" SAN UP 3" V UP 3" 2" V UP 4" 3" SAN UP FCO S 26 6" SAN 3" SAN UP S 12 3" V UP 3" SAN UP 3" SAN UP TO F) 3" SAN UP TO ,CO 3" SAN UP 3" S 13 3" SAN UP TO F) FCO SAN S 2' 3" SAN UP 4" S 32 3" SAN UP 3" V UP 3" 6" FCO 6" 3" SAN UP TO FU"E HOO)S
/
3" SAN UP
S 33
4"
FCO
3"
6" ST UP
S 18
FCO
3" 6" ST UP
3" SAN UP
6"
3" SAN UP TO F)
3" 6"
SAN
ST
SAN
SAN
SAN
3" SAN UP TO F) ST
4" SAN UP TO F)
4"
C C.1
SAN
3" SAN UP
S 36 6"
SAN
SAN
3" SAN UP TO FU"E HOO)S 2" SAN UP 3" 4" 3" SAN UP TO F) 2" SAN UP TO S3" SAN UP 3" V UP 3" SAN
4" SAN UP TO F) 3" 6" FCO 3" 2" SAN UP TO S3" SAN 2" SAN UP (PU"PE)) 2" SAN UP TO SS 3" SEP 2 FCO 4" CR 1 HPS(88#) PCR 3"
3" REFER TO CIVIL PLANS FOR CONTINUATION SAN 6" PIPIN( )ROP 4"
3"
I.E.=93' 0"
3"
FCO
SAN
3"
SAN
C.9 D
S 28
3" SAN UP
2" V UP
3"
SAN
3" SAN UP TO F) 3" SAN UP TO F) 3" SAN UP TO ,CO 3" 4" SAN UP S 1C 8" 3" SAN UP TO SS
S 6 4"
S '
S 8
S 9
2" SAN UP TO S-
3" SAN UP
S 11
3" V UP
ST
CP 11243
")!/. (&!/.
SAN
S 1+ 3" SAN UP
SAN
3" SAN UP TO S-
SAN
ST
ST
4" FCO
3"
J. Kasdorf
& &!.
2" V UP 3" SAN UP S 3$ 3" SAN UP 3" SAN UP TO F) 3" 3" FCO I.E.=98' 6"
). 1ra2ee
.".
SAN
S 30
SAN
2" V UP
8" ST UP
D. 3ilber
Project "dministrator#
3" SAN UP TO F)
3" SAN UP
J. Jo$nson
Project "rc$%&ng#
2" V UP
6" ST UP
J. Sc$+art2
'.(. )e*ie+#
E
4" FCO I.E.=98' 6" 3" SAN UP TO F) ST 4" SAN UP 3" V UP S 1A 3" SAN UP TO F) 8" S 2 3" SAN UP
S 3 I.E.=96' 0"
3" SAN UP
3" SAN UP
D. Di!iuccio
Dra+ing Scale#
"s indicated
FCO
8"
S 34
Issue Date#
0$ 10 11 01
HPS(88#) PCR
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
3" SAN UP
E.4
ST 10" 8" FCO
8" ST
06 23 20 08
10"! STOR" # I.E.=9$' 8" (19%430 S&. FT.) REFER TO CIVIL PLANS FOR CONTINUATION
10"! STOR" # I.E.=9$' 8" (21%182 S&. FT.) REFER TO CIVIL PLANS FOR CONTINUATION
ST
4"
8"
12204-1000
Underground Plan - Plumbing
U1<83;3@71< P97AB:1;
1?8" = 1' 0"
NORTH
M4.0
OF
S 20
ST
S. 4ardner
"PP). Project Designer#
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
2. 3. 4.
$. 6. '.
8.
0.1
4.5
5.5
6.5
7.5
8.5
10
A
1E! IBU&E 11B1 #*&&"B*R" I*) !P"#E )*R ' 10(0
! "IR !W$-1
A.6
3" FS 1 2" SAN FRO" SEP 1 TO A+OVE CEILIN( G SPILL INTO FS 1 2" V UP 3" SAN )N ,CO 3?4" C, CAPPE) FOR FUTURE
W*R0R**M 1$02
FCO
*FFI#E 1$12
*FFI#E 1$1$
W*R0R**M 1$01
*FFI#E 1$14
*FFI#E 1$1,
*FFI#E 1$1(
3?4" C, )N 3?4" H, )N 3" SAN IN ,ALL
*FFI#E 1$1/
*FFI#E 1$1.
*FFI#E 1$1-
&"B 1400
2 "6.0
6" )S 1
I #&*!E 1011"
-S 1
C C.1
0I #'E)E 1011
FUME '**+ 1,2$ I!!UE #U& URE 1,21 I!!UE #U& URE 1,22 I!!UE #U& URE 1,24
#*&&"B*R" I*) &*U)%E 1010 I!!UE #U& URE 1,$1 I!!UE #U& URE 1,$2
C.9 D
5")I *R #&*!E 1020
1 "4.10 3?4" H,R 1 1?2" H, 3" C,
.
E&E1" *R 42 EP2
4" VTR
1 1?2" H,
CP 11243
F&U*RE!#E) IM"%I)% &"B 1/02
ST 3?4" C, H,R ( H, 3?4" 3?4" 3" SAN UP TO SS SAN 3" SAN UP?)N CO 2" 6" ST FCO CO 6" ST UP 6" ST UP
")!/.
J. Kasdorf
& &!.
&"B 1200
ST V
0.$ (P"
). 1ra2ee
.".
,H 2 3" F) 1
2"
D. 3ilber
Project "dministrator# Project Designer#
W*R0R**M 1040"
U)"!!I%)E+ 1.40
J. Jo$nson
Project "rc$%&ng#
ST
J. Sc$+art2
&*"+I)% +*#0 1.(0
E
%E)+ER )EU R"& *I&E 102$ BUI&+I)% M%R *FFI#E 1040
6" ST )N 3" SAN IN ,ALL 3?4" C, )N 3?4" H, )N 3" SAN )N *FFI#E 111(
'.(. )e*ie+#
3 "4.10
D. Di!iuccio
Dra+ing Scale#
*FFI#E 1111
*FFI#E 1112
*FFI#E 111$
W*R0R**M 1101
*FFI#E 1114
*FFI#E 111,
*FFI#E 111.
*FFI#E 111-
6"
"s indicated
Issue Date#
0$ 10 11 01 06 23 20 08 2013 2013 2013 2014
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
E.4
,H 1 6" )S 1 FCO
W*R0R**M 1102
1 1?2" SC, 1 1?2" RO?)I 1 1?2" RO?)I FIRST FLOOR FINISHE) ELEVATION = 100' 0" FCO 2" 3"
10" )S 1 # I.E. 103' 0" ROUTE (AS PIPIN( UP ALON( ,ALL AN) INTO +UIL)IN( CHASE # I.E. 101' 0" E"ER(ENC* (ENERATOR SERVICE SHUT OFF +UIL)IN( SERVICE SHUT OFF NATURAL (AS "ETER AN) RE(ULATOR ASSE"+L* "OUNTE) TO CONCRETE RETAININ( ,ALL NATURAL (AS SERVICE +* LOCAL UTILIT* CO"PAN*
WRI E-UP !P"#E 1100 1E! IBU&E 11B2 #*&&"B*R" I*) !P"#E !*U ' 10$0
! "IR !W2-1
3 "6.1
12204-1000
Fir8t Floor Plan - Plumbing
NORTH
M4.1
OF
*FFI#E 1$11
FCO
6" ST UP
FCO
ME#'")I#"& 1(11
$ "4.10
S. /o..er
!I0I
S. 4ardner
"PP).
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
F408 ,:<6= 41< F408 H8:;=6 =4>8 A:1:A7A <:A815:@15 @2 12" 41< A4H:A7A <:A815:@15 @2 144" F408 ,:<6= 41< F408 H8:;=6 =4>8 A:1:A7A <:A815:@15 @2 12" 41< A4H:A7A <:A815:@15 @2 144"
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
-E* NOTES
PLU"+IN(
1 KFIRST FLOOR LA+ ONL* L E"ER(ENC* NATURAL (AS SHUT OFF VALVE +OIM ,ITH "ANUAL SHUT OFF VALVE. KSECON) FLOOR LA+ ONL* L E"ER(ENC* NATURAL (AS SHUT OFF VALVE +OIM ,ITH "ANUAL SHUT OFF VALVE. E"ER(ENC* NATURAL (AS ELECTRICALL* OPERATE) SHUT OFF VALVE. ROUTE NM COL) ,ATER )O,N INSI)E ,ALL TO ICE "ACHINE% CO"PLETE ,ITH +ALL VALVE SHUT OFF% +AC-FLO, PREVENTER% (AS "FR.O) +* JURN ,IL-INS "O)EL '40)% FILTER% (AS "FR.O) +* C PURE # '90 FILTER 10 -IT ,ITH EITRA FILTER CARTRI)(E)% AN) 3?4M )RAIN ,ITH AIR (AP TO FLOOR )RAIN ,ITH FUNNEL.
2. 3. 4.
2 3 4
$. 6. '.
8.
4.5
5.5
6.5
7.5
8.5
10
S 14
S 18
3?4" H, 3?4" C,
S 20
B
3" SAN UP ES 1 3" F) 1
. . / /
CO
ES 1 3" F) 1
. .
T"V 1
(1 A1 V1
C, H, 3?4"
C, H, 1 1?2" 1 1?2"
#*RRI+*R 14,0
FCO
/ .
V1 A1 (1 (1 A1 8 V1 3?4"
&"B 1400
C, ( CA VAC
CO
S- 2 E, 1
8 V1
RO?)I RO?)I CA H,R H, C,
V1
. / / / /
2" V UP?)N
S 1' S- 1 E, 1 1 1?2"
/
VAC ( CA H, C,
S- 1 E, 1
1 1?2"
/
S- 1 E, 1
1 1?2"
/
RO?)I
RO?)I
S 21
C
S- 2 E, 1
CO2 1
CO2 1 S- 2 E, 1 3" SAN UP?)N 3" SAN UP 3" V UP FUME '**+ 1,2$ 4 C, 22
/ / / .
3" F) 1
3" V UP
CO2 1 S- 2 E, 1
CO2 1 S- 2 E, 1
C.1
CO
RO?)I C, H, H,R
(1 A1 V1
(1 A1 V1
H, C,
C, ( CA VAC
V 22 C, 3 (3 A3 V3
V 22
/ / / .
V 22
V 22 CO 3?4" H,R H, C,
( CA VAC
/ . .
V2
(1 A1 V1 3" SAN UP
(1 A1 V1
C, ( CA VAC
C, 3 (3 A3 V3 CO
CO 3" F) 1
CO V2 3" F) 1
/RO?)I /H,R . H, . C,
/ . .
/ / . .
RO?)I H,R H, C,
CO2 1
/ . . /
CO2 1
3"
S- 4
3"
VAC CA (
C,
RO?)I C, H, H,R
C, H, RO?)I RO?)I
2" 3?4"
. . / .
H,
3?4" 3?4"
S- 4
VAC
FCO
FCO
3?4"
3?4"
FCO
FCO
. . / .
V1 A1 (1
C, 3 (3 A3 V3
. / / /
C.9
S- 2 E, 1
S- 2 E, 1
CO2
V C, H,
V 22
C, V H,
V 22
VAC CA ( C,
V1 A1 (1
. VAC / CA / ( / C,
C, 3 (3 A3 V3
C,
CO
V 22
H, C,
CO
V1
3" 1 1?2"
CO
V1 CO
CO2 ( VAC CA
CO2 ( VAC CA
HOSE STATION
HS
3" SAN UP
1 1?2"
S- 2 E, 1
CP 11243
")!/. (&!/.
CO2 1
CO2 1
1 1?4"
J. Kasdorf
& &!.
RO?)I
). 1ra2ee
.".
D. 3ilber
Project "dministrator# Project Designer#
2" V )N
2" V UP
C,
J. Jo$nson
V
Project "rc$%&ng#
V C, H,
/ / . . . .
S- 2 E, 1 (1 A1 V1 V1 A1 (1
J. Sc$+art2
'.(. )e*ie+#
S- 2 E, 1 V1
VAC CA ( H,
D. Di!iuccio
F&U*RE!#E) IM"%I)% &"B 1/02
1 1?2" 3?4" 3?4"
3" SAN )N
Dra+ing Scale#
1%8? @ 1A90?
S- 2 E, 1 FCO 1 1?2"
Issue Date#
0$ 10 11 01 06 23 20 08 2013 2013 2013 2014
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
. . /
S- 2 E, 1
RO?)I
V1 A1 (1
&"B 1200
V1 A1 (1
1 1?2" RO?)I H, F) 1 3" SAN UP 3" SAN )N ES 1 3" SAN UP T"V 1 3" SAN UP 6" ST )N F) 1 ES 1 T"V 1
. .
1 1?2"
. .
C, H,
3" SAN UP
C, H,
#*RRI+*R 12,0
1 1?2"
8" ST UP?)N
0
RO?)I
E
S 2 S 3 S 4
12204-1000
Enlarged Fir8t Floor &ab Plan Plumbing
"4.1
NORTH
M4.1a
OF
S 1$
S 16
3" V UP
/ / / .
S. 4ardner
"PP).
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
2. 3. 4.
$. 6. '.
8.
0.1
4.5
5.5
6.5
7.5
8.5
10
A
&*U)%E 2'W1" "+MI) 20(0 ! "IR !W$-2 WRI E-UP !P"#E 2$00
A.6
*FFI#E 2$11 *FFI#E 2$12 *FFI#E 2$1$ W*R0R**M 2$01 *FFI#E 2$14
6" ST UP?)N
H,R C,
2" V UP?)N
4" VACUU" EIHAUST UP?)N 6" ST UP?)N 6" ST UP?)N 3?4" C, )N 3?4" H, )N 3?4" H,R )N
E&E1" *R 41 EP1
C C.1
#*RRI+*R 2'W1+
S 2$
FUME '**+ 2,2$ I!!UE #U& URE 2,21 !M"&& #*)FERE)#E R**M 2010 I!!UE #U& URE 2,22 I!!UE #U& URE 2,24 I!!UE #U& URE 2,2, I!!UE #U& URE 2,2(
FUME '**+ 2,2/ I!!UE #U& URE 2,2. E7UIP R**M 2,10 #*&+ R**M 2,11 I!!UE #U& URE 2,2&I)E"R E7UIPME) R**M 2(00
3" SAN UP?)N 1" H,R UP?)N 3" H, UP?)N 4" C, UP?)N 1 1?4" SC, UP?)N 2" ( UP?)N 2 1?2" VAC UP?)N 1 1?4" CA UP?)N
#*RRI+*R 2'W1
C.9 D
5")I *R #&*!E 2020
1 "4.24
E&E1" *R 42 EP2
4" VTR
2 "4.10
S 24
#*RRI+*R 2'W2 ME)6! *I&E 2021 PER!*)"& 'E"& ' R**M 2042 #*RRI+*R 2'W1#
LAV 2
3?4" 3?4"
/ /
CP 11243
")!/. (&!/.
J. Kasdorf
& &!.
C,
H,
). 1ra2ee
.".
E&E# RI#"& #&*!E 2.20
D. 3ilber
UF# R**M 2.$0
Project "dministrator#
SS 2 3" SAN TO 3R) FLR 3" SAN UP?)N 2 1?2"
J. Jo$nson
Project "rc$%&ng#
J. Sc$+art2
'.(. )e*ie+#
%E)+ER )EU R"& *I&E 202$ *FFI#E2 W*R0R**M 2040 *FFI#E 2111 *FFI#E 2112 *FFI#E 211$
6" ST UP?)N
W*R0R**M 2101
*FFI#E 2114
*FFI#E 211,
S 34 -S 1
D. Di!iuccio
( 2 1?2"
Dra+ing Scale#
*FFI#E 211.
"s indicated
*FFI#E 211-
E.4
*FFI#E 211(
W*R0R**M 2102
*FFI#E 211/
Issue Date#
0$ 10 11 01 06 23 20 08 2013 2013 2013 2014
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
! "IR !W2-2
&*U)%E 2'W1B
3 "6.1
12204-1000
!econd Floor Plan - Plumbing
NORTH
M4.2
OF
*FFI#E 2$1,
H,
W*R0R**M 2$02
-S 1
*FFI#E 2$1/
6" ST UP?)N
*FFI#E 2$1.
*FFI#E 2$1-
ME#'")I#"& 2(11
$ "4.10
S. 4ardner
"PP). Project Designer#
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
-E* NOTES
PLU"+IN(
1 KFIRST FLOOR LA+ ONL* L E"ER(ENC* NATURAL (AS SHUT OFF VALVE +OIM ,ITH "ANUAL SHUT OFF VALVE. KSECON) FLOOR LA+ ONL* L E"ER(ENC* NATURAL (AS SHUT OFF VALVE +OIM ,ITH "ANUAL SHUT OFF VALVE. E"ER(ENC* NATURAL (AS ELECTRICALL* OPERATE) SHUT OFF VALVE. ROUTE NM COL) ,ATER )O,N INSI)E ,ALL TO ICE "ACHINE% CO"PLETE ,ITH +ALL VALVE SHUT OFF% +AC-FLO, PREVENTER% (AS "FR.O) +* JURN ,IL-INS "O)EL '40)% FILTER% (AS "FR.O) +* C PURE # '90 FILTER 10 -IT ,ITH EITRA FILTER CARTRI)(E)% AN) 3?4M )RAIN ,ITH AIR (AP TO FLOOR )RAIN ,ITH FUNNEL.
2. 3. 4.
2 3 4
$. 6. '.
8.
4.5
5.5
6.5
7.5
8.5
10
S 14
S 18
S 20
B
3?4" 3?4" 3?4" ( CA VAC ES 1 T"V 1 3" F) 1 C, H, 1 1?2" 1 1?2" C, H, 2 1?2" 1 1?2" 1 1?2" 1 1?2"
/ . /
H, C,
ES 1
T"V 1
3?4" 3?4"
/ /
ES 1 1 1?2" 3" F) 1
(1 A1 V1
1 1?2" 3?4"
&"B 2400
VAC CA ( H,
(1 A1 V1 3"
. / / / /
SAN V1
1 1?2" V1
. . .
1 1?2" 1 1?2"
VAC ( CA H, C,
1 1?2" 1 1?2"
S 12
S 1' S- 1 E, 1 S 16 3" SAN UP?)N RO?)I 3" SAN UP?)N 3" SAN UP?)N 3" V UP?)N S 1$ 3" V UP?)N 1 1?2" S- 1 E, 1 RO?)I 1 1?2" 3" SAN UP?)N 3" V UP?)N S- 1 E, 1 1 1?2" RO?)I
3?4" S 19 3" SAN UP?)N 1 1?2" RO?)I 3" SAN UP?)N 3" V UP?)N CO2 1 CO2 1
. / /
S- 1 E, 1
S 21
S- 1 E, 1
C
3" SAN UP S- 2 E, 1
CO2 1
CO2 1 3" F) 1 S- 2 E, 1 S- 2 E, 1
CO2 1
CO2 1 S- 2 E, 1
CO2 1
C.1
V 22
V 22 C, 3 (3 A3 V3 V2 CO 3" F) 1
.
RO?)I
V 22 1 1?4"
V 22
CO
V 22
V 22 1 1?4"
V 22 F) 1 H, C, CO
CO
V 22 1"
CO
3?4" H, C,
V1
(1 A1 V1
V1
/ RO?)I . H, . H, . C,
! "IR !W1-2
CO2 1
C, ( CA VAC
H, C,
VAC CA (
H, C,
CO2 1
CO2 VAC VAC CA ( H, C, ( CA VAC H, C,
VAC
CO2 1
S- 4
VAC
2"
CO2 1 CO2 1
VAC CO2
2"
CO2 1
2"
CO2
CO2 1
CO2 VAC
3?4" 2
2" 2"
C,
S- 2 E, 1
CO2 1
3?4" 1 1?2"
. . / .
CO2 1
3
. / .
. . / .
CO2 ( VAC CA V 22
1 1?2"
V1 A1 (1
(1 A1 V1
CO
V1
CO
V 22 V 22
CO
V2
CO
C, 3 (3 A3 V3
CA NOR"ALL* OPEN
V 22
V 22 S- 2 E, 1
V 22 V 22 C, 22 4 S 9
C.9
1 1?2"
CO2 1 RO?)I H,
/ . . . .
V 22
V 22
VAC ( CA C, H,
V1 A1 (1
(1 A1 V1 (1 A1 V1
V 22 C, 3 (3 A3 V3
V1 A1 (1
V1 A1 (1
V1
V1 A1 (1
V1
/ . . .
. / . / .
(1 A1 V1
(1 A1 V1
(1 A1 V1
(1 A1 V1 (1 A1 V1
T*P.
(1 A1 V1
C, 3 (3 A3 V3
. / / / /
V 22
V 22
V 22
V 22
. .
. .
VAC ( CA H, C,
C, 22 S- 2 E, 1
RO?)I
S- 2 E, 1
1" H,R 3?4" H,R 3" H, 2 1?2" H, 4" C, 3" C, 1 1?2" SC, 1" SC, 2" ( 2" ( 2 1?2" VAC 2" VAC 1 1?2" CA 1" CA
V1
1 1?2"
1 1?2"
3" V UP?)N
S- 2 E, 1 CO2 1 CO2 1
F) 1
RO?)I
SC,
S- 2 E, 1
S- 2 E, 1 CO2 1 3" V UP
S- 2 E, 1
CP 11243
")!/. (&!/.
CO2 1
. .
J. Kasdorf
& &!.
S 6 S- 1 E, 1
1 1?2" RO?)I
S ' S- 1 E, 1
1 1?2" RO?)I S- 1 E, 1
S 8 RO?)I
1 1?2" RO?)I
). 1ra2ee
.".
S 11 S- 1 E, 1
1 1?2" RO?)I
D. 3ilber
Project "dministrator# Project Designer#
J. Jo$nson
1 1?2"
Project "rc$%&ng#
1 1?2" 1 1?2"
VAC CA ( H,
1 1?2" 3?4"
J. Sc$+art2
'.(. )e*ie+#
D. Di!iuccio
Dra+ing Scale#
1%8? @ 1A90?
V1 3?4" C, G H, FRO" +ELO, LAV 2 2" V UP?)N 1 1?2" V V1 A1 (1 1 1?4" VAC CAPPE)
/ VAC . ( . CA . C, . H,
V1 8
Issue Date#
0$ 10 11 01 06 23 20 08 2013 2013 2013 2014
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
&"B 2200
3"
S- 2 E, 1 3?4" C, H, 3" F) 1 ES 1 3" SAN UP?)N 3" SAN UP?)N S 2 S 3 S 4 T"V 1 1 1?2" 3" F) 1 ES 1 T"V 1 1 1?2" 1 1?2" C, H, 3" F) 1 1 1?2" ES 1 T"V 1
/ . .
V1 A1 (1
1 1?2" (1 A1 V1
12204-1000
Enlarged !econd Floor &ab Plan Plumbing
"4.2
NORTH
M4.2a
OF
&"B 2400
/ . /
RO?)I RO?)I CA
(1 A1 V1
H,R H, C,
S. 4ardner
"PP).
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
2. 3. 4.
$. 6. '.
8.
0.1
4.5
5.5
6.5
7.5
8.5
10
! "IR !W$-$
!'E&& $$00
A.6
2" V UP?)N 4" SAN CAPPE) FOR FUTURE 4TH FLOOR (LASS ,ASH. LOCATE CAPPE) PIPE AT APPROI. 13' 0" A.F.F. 3" SAN UP?)N S 14 6" ST UP?)N S 18 3" SAN UP?)N 3" SAN UP?)N S 33 3" SAN UP?)N S 20
B
3" F) 1 3" F) 1 6" ST UP?)N 3" F) 1 6" ST UP?)N FCO 4" FS 1 4" FS 1 4" FS 1
!'E&& $000
2" V UP?)N
E&E1" *R 41 EP1
S 3'
3?4" H, )N 3?4" C, )N S 2$
#*RRI+*R $'W1
3" V UP?)N 3" SAN UP?)N S 12
S 1$ 3" V UP?)N 3" SAN UP?)N S 16 3" V UP?)N 3" SAN UP?)N S 1' 3" V UP?)N 3" SAN UP?)N S 19 3" V UP?)N 3" SAN UP?)N S 21
!'E&& 41(
3" SAN UP?)N 2" V UP?)N 3" SAN UP?)N S 36
C C.1
3" SAN UP?)N 3" SAN UP?)N S 26 3" SAN UP?)N 3" V UP?)N S 13 3" SAN UP?)N 3" V UP?)N 3" F) 1 3?4" H,R 2 1?2" H, 3" C, 1" SC, 1 1?2" ( 2" VAC 1" CA
3" F) 1
! "IR !W1-$
2 1?2" VAC UP?)N 1 1?2" CA UP?)N
3?4" H,R UP 2 1?2" H, UP 3" C, UP 1 1?2" SC, UP 1 1?2" ( UP 2" VAC UP 1" CA UP
3" SAN UP?)N S 2' 1 1?2 VAC G CA CAPPE) 3" SAN UP?)N 3" V UP?)N 3" F) 1 2" V UP?)N 2" V UP?)N 3" F) 1
S 10
C.9 D
2" C, UP?)N
3" SAN UP?)N 3" F) 1 3?4" C, UP?)N 3?4" H, UP?)N 3" F) 1 3" SAN )N (CAPPE)) 3" SAN UP?)N 3" V UP?)N S 6 3" SAN UP?)N 3" V UP?)N S ' 3" SAN UP?)N 3" V UP?)N S 8 3" SAN UP?)N 3" V UP?)N S 9 3" SAN UP?)N 3" V UP?)N S 11
E&E1" *R 42 EP2
CP 11243
2" V UP?)N
!'E&& $020
1 1?2" V 3?4" C, 2" SAN 3" V UP?)N 3" F) 1 3" SAN )N (CAPPE) AT FLOOR) S 1A 3" SAN UP 4" SAN UP?)N 3" V UP?)N E,C 1 S 1C
")!/.
J. Kasdorf
& &!.
). 1ra2ee
.".
3" SAN CAPPE) FOR FUTURE. LOCATE CAPPE) NEAR UN)ERSI)E OF STRUCTURE (T*P. 6) 8" ST UP?)N 3" SAN UP?)N SAN 3" SAN )N
#*RRI+*R $'W1#
D. 3ilber
Project "dministrator# Project Designer#
S 1+
J. Jo$nson
Project "rc$%&ng#
E
3?4" C, UP?)N 3?4" H, UP?)N 2" C, UP?)N 3?4" H, UP 3" F) 1 3" F) 1
3" F) 1
3" F) 1
6" ST UP?)N
3" F) 1
J. Sc$+art2
'.(. )e*ie+#
S 2
6" ST UP?)N
S 3
S 3
S 4
D. Di!iuccio
!'E&& $.40
Dra+ing Scale#
"s indicated
Issue Date#
0$ 10 11 01 06 23 20 08 2013 2013 2013 2014
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
E.4
6" ST UP
3 "6.1
12204-1000
9ird Floor Plan - Plumbing
NORTH
M4.$
OF
!'E&& $(1$
3" F) 1
S. /o..er
!I0I
S. 4ardner
"PP).
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
2. 3. 4.
$. 6. '.
8.
0.1
4.5
5.5
6.5
7.5
8.5
10
A
&*U)%E 4'W1" #*&&"B*R" I*) !P"#E 40(0 !'E&& 4$00
! "IR !W$-4
6" ST UP
A.6
! "IR !W,-4
2" V )N S 12
S 13 4" V UP
4" V UP
S 18 S 16 S 1' 4" V UP
6" ST UP 3" SAN )N 6" ST UP 4" V UP 4" V UP S 19 S 20 3" SAN )N 3" SAN UP
V
CO 4" V UP S 21 6" ST UP
ST
6" ST UP
V
4" V UP
ST
V
CO 6" ST )N ST
B
CO
6" ST UP
!'E&& 4000
3" SAN )N
2" V )N V
3" SAN UP TO F)
3"
3"
E&E1" *R 41 EP1
3"
3" SAN UP TO FS
FCO
CO
V SAN
3" SAN UP TO FCO 3" SAN UP TO FS 3" 3" SAN )N 3" V UP 3" SAN UP G )N SAN
2" 3" SAN UP TO F) 3" SAN 2" V 3?4" H,R 2 1?2" H, 3" C, 1" SC, 1 1?2" ( 2" VAC 1" CA
CO
V
4" V UP V
3" V )N
S 2$
C C.1
3" SAN CO
3"
3" SAN )N
2"
3" SAN UP
3"
3" SAN UP TO FS 3" SAN UP TO FS 3" SAN UP TO FS 2" V UP?)N 3" SAN )N 3" V )N 2" V UP?)N
3" SAN UP TO FS
C.9 D
3" SAN )N
3" SAN UP
!'E&& 4020
H,R
6" ST UP 3"
V
6" ST UP
3" SAN UP TO FS
CO
3"
3"
3"
CP 11243
")!/. (&!/.
3"
3"
3"
6" ST UP 6" ST UP
ST
!'E&& 4(00
3" SAN )N
J. Kasdorf
& &!.
3?4" H, )N 1" C, )N
ST
S '
4" V UP
S 8
S 9
4" V UP
4" V UP
4" V UP
S 10
4" V UP
S 11
ST
). 1ra2ee
2" 6"
V
ST
S 1A
.".
UF# R**M 4.$0
D. 3ilber
3" SAN CAPPE) 4" V UP 3" SAN )N
Project "dministrator#
S 1+
S 2
CO 4" V UP 6"
6" ST 6" 4" V )N S 4 3" SAN )N 4" V UP S $ 6" ST UP 6" ST UP 6" ST UP CO 3" V )N ST CO 8" ST CO 4" V UP 3" ST ST 8" ST )N 6" ST UP
J. Jo$nson
Project "rc$%&ng#
J. Sc$+art2
'.(. )e*ie+#
!'E&& 4.40
6" ST UP CO
D. Di!iuccio
Dra+ing Scale#
6" ST )N CO
S 3
6" ST )N CO
6" ST 10"
"s indicated
3?4" H, )N CO
6" ST UP 6" ST UP
Issue Date#
10" ST )N
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
E.4
6" ST )N
!'E&& 4100 ! "IR !W2-4 &*U)%E 4'W1B #*&&"B*R" I*) !P"#E 40$0
0$ 10 11 01
06 23 20 08
3 "6.1
12204-1000
Fourt9 Floor Plan - Plumbing
NORTH
M4.4
OF
S. 4ardner
"PP). Project Designer#
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
2. 3. 4.
$. 6. '.
8.
4.5
1 "6.2
5.5
6
2 "6.2
6.5
7.5
8
3 "6.2
8.5
10
B
3" SAN )N 3" SAN )N 4" VTR SERVICE CLEARANCE (T*P.)
4" VTR
FCO 1 1?2" H,R H, C, 3" F) 1 1 1?2" C, G H, )N TO ES 2 ES 2 FAN SERVICE FAN SERVICE FAN SERVICE HVAC 3
3?4" C, TO ,H 1 ON ROOF
S 23
SS 2 2" V
CO
3" SAN )N V
HVAC 2
HVAC 1 3" FS 1 FAN SERVICE FCO COIL PULL COIL PULL COIL PULL
4" VTR
C
FUTURE T,O STAC-E) CONTROLLE) ENVIRON"ENTAL ROO" CON)ENSERS (T*P 8) FCO COIL PULL CO 3?4" 1 1?2" H,R H, C, 1 1?2" 6" ST UP TO RS COIL PULL PIPE ROUTE) THROU(H STRUCTURAL STEEL AT UN)ERSI)E OF PENTHOUSE ROOF COIL PULL 4" VTR T,O STAC-E) CONTROLLE) ENVIRON"ENTAL ROO" CON)ENSERS (T*P 8)
3?4" 1 1?2"
C.1
FAN SERVICE
COIL PULL
CO 6" ST UP TO RS
COIL PULL
CO
3" FS 1 6" ST UP TO RS
3" FS 1
3" FS 1
3" FS 1
3" FS 1
6" ST UP TO RS
CP 11243
")!/. (&!/.
J. Kasdorf
& &!.
2" V HVAC 4 FAN SERVICE FAN SERVICE FAN SERVICE FAN SERVICE
! "IR !W4-,
). 1ra2ee
.".
D. 3ilber
Project "dministrator# Project Designer#
J. Jo$nson
Project "rc$%&ng#
E&E1" *R #*) R*& EP2"
ST
J. Sc$+art2
'.(. )e*ie+#
ST
D. Di!iuccio
Dra+ing Scale#
1%8? @ 1A90?
2" V )N
ST
Issue Date#
0$ 10 11 01 06 23 20 08 2013 2013 2013 2014
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
C.9
6" 6" 6" 6" 6" 6"
D
D#7)e*it ocal71220810009(S: ,io&ngineering9(18;!entral;jsc$+art2.r*t
E&E1" *R 42 EP2
! "IR !W4-4
12204-1000
Enlarged Pent9ou8e Plan - Plumbing
M4.,
OF
3" F) 1
S. 4ardner
"PP).
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
(ENERAL NOTES
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
2. 3. 4.
$. 6. '.
8.
0.1
4.5
5.5
6.5
7.5
8.5
10
A.6
S 12 4" VTR 4" VTR S 13 4" VTR 6" RS 1 1928 SF 6" OS 1 1928 SF S 1$ 4" VTR S 16 4" VTR S 1' 4" VTR 6" RS 1 1928 SF S 18 4" VTR 6" OS 1 1928 SF S 19 4" VTR S 21 4" VTR 6" RS 1 1928 SF 6" OS 1 1928 SF
4" VTR
B
10" STEA" RELIEF VENT 4" VTR 4" VTR S 20 ACCH 1 4" LA+ VACUU" S*STE" EIHAUST. TER"INATE "INI"U" '' 0" A+OVE ROOF SURFACE ,ITH (OOSENEC-. COVER OPEN EN) ,ITH +IR) SCREEN. 6" STEA" RELIEF VENT
6" RS 1 480' SF
6" OS 1 480' SF
4" VTR
S 26
,H 1 S 2$ 4" VTR SEF 1 LEF 1 4" VTR 4" VTR S 23 4" VTR 4" VTR
C C.1
4" VTR SEF 2 LEF 2 6" RS 1 3330 SF 6" OS 1 3330 SF 6" RS 1 3330 SF 6" OS 1 3330 SF 6" RS 1 3330 SF 6" OS 1 3330 SF
FC 1
SEF 3
LEF 3
C.9 D
SEF 4
4" VTR
CP 11243
6" RS 1 480' SF 6" OS 1 480' SF 4" VTR 4" VTR S 6 TEF 1 4" VTR 4" VTR S 1 S 2 4" VTR 6" RS 1 2630 SF 6" OS 1 2630 SF 4" VTR S 3 6" RS 1 2630 SF 6" OS 1 2630 SF 4" VTR S 4 6" RS 1 2630 SF 6" OS 1 2630 SF 4" VTR S $ 6" RS 1 2630 SF 6" OS 1 2630 SF REFER TO SECON) FLOOR PLAN. 4" VTR 4" VTR 4" VTR S ' 4" VTR S 8 4" VTR 4" VTR S 9 4" VTR S 10 4" VTR S 11 4" VTR S $
")!/.
J. Kasdorf
& &!.
). 1ra2ee
.".
D. 3ilber
Project "dministrator# Project Designer#
J. Jo$nson
Project "rc$%&ng#
J. Sc$+art2
'.(. )e*ie+#
D. Di!iuccio
Dra+ing Scale#
"s indicated
Issue Date#
E.4
0$ 10 11 01 06 23 20 08 2013 2013 2013 2014
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
12204-1000
Roo: Plan - Plumbing
NORTH
M4.(
OF
S. /o..er
!I0I
S. 4ardner
"PP).
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
(ENERAL NOTES
1 1
3?4" H,R UP?)N 3?4" H,R UP 1 1?2" H, UP 2 1?2" C, UP
-E* NOTES
PLU"+IN(
1 ROUTE 1?2M COL) ,ATER G HOT ,ATER )O,N TO (LASS ,ASHER% CO"PLETE ,ITH +ALL VALVE SHUT OFFS% ROUTE 1 1?2" RO?)I )O,N TO (LASS ,ASHER (PURE ,ATER CONNECTION)% CO"PLETE ,ITH +ALL VALVE SHUT OFF. ROUTE 1?2" CO"PRESSE) AIR )O,N TO (LASS ,ASHER% CO"PLETE ,ITH +ALL VALVE SHUT OFF CO"PRESSE) AIR FILTER AN) PRESSURE RE(ULATOR (CO"PRESSE) AIR )ROP )ETAIL). ROUTE 1 1?2" (LASS ,ASHER )RAIN ,ITH AIR (AP TO FLOOR SIN-. ROUTE 1" NON POTA+LE ,ATER )O,N TO STERILIJER% CO"PLETE ,ITH +ALL VALVE SHUT OFF. ROUTE 2" STERILIJER )RAIN ,ITH AIR (AP TO FLOOR SIN-. 1 1?2" COL) ,ATER ,ITH +AC-FLO, PREVENTER (AS "FR.') +* ,ATTS SERIES '19 S &T. )OU+LE CHEC- VALVE ASSE"+L* ,ITH STRAINER AN) &UARTER TURN +ALL VALVES).
PLU"+IN(
1. VERIF* ALL CON)ITIONS IN FIEL) +EFORE CONSTRUCTION. NOTIF* ARCHITECT?EN(INEER OF )ISCREPANCIES +ET,EEN )RA,IN(S AN) ACTUAL FIEL) CON)ITIONS. COOR)INATE ALL ,OR- ,ITH APPROPRIATE TRA)ES. COOR)INATE AN* RE&UIRE) SHUT)O,N OF SERVICES OR E&UIP"ENT ,ITH O,NER'S REPRESENTATIVE. PROVI)E ALL "ISC. STEEL AN) ITE"S RE&UIRE) FOR THE PROPER INSULATION OF ALL PIPE SHEET "ETAL% AN) E&UIP"ENT. COOR)INATE FLOOR% ,ALL G ROOF PENETRATIONS ETC. ,ITH ARCHITECTURAL TRA)ES. )O NOT RUN AN* PIPIN( OR )UCT,OR- INTO AN ELECTRICAL ROO" THAT )OES NOT SERVE THAT ROO". REFER TO LA+ FIITURE SCHE)ULE ON SHEET A12.1 FOR COOR)INATION OF LA+ VACUU"% NATURAL (AS% CO"PRESSE) AIR AN) CAR+ON )IOII)E (CO2) CONNECTION RE&UIRE"ENTS. REFER TO PIPIN( )IA(RA"S FOR A))ITIONAL PIPE SIJES.
2. 3. 4.
D
3" SAN FRO" F) 1 A+OVE 3" F) 1
$.
C, H, H,R
6. '.
4" SAN
,CO 3" SAN )N 2" V UP 3" C, (REFER TO 1 1?2" H, SHT "4.1 3?4" H,R FOR CONT.) 3" SAN FRO" F) 1 A+OVE 3?4" C, UP?)N 3?4" H, UP?)N UR 1
3" F) 1
UR 1 2 1?2"
1 1?2"
UR 1
V C, H, H,R
. .
8.
,H 2
UR 1
SS 1
SS 1 2" SAN FRO" SS 1 A+OVE 1 1?2" C, UP 1 1?2" H, UP 3" SAN UP?)N 2" SAN LAV 1 3?4" C, TO E,C E,C 1 ,CO +ELO, E,C LAV 1 2" V UP?)N 1 1?4" 3?4" C, (LO,) 1 1?2" V 3?4" H, (HI(H) H, C, 6" ST UP 8" ,CO G ST )N TO U( 2" V UP?)N LAV 1 3?4" C, (LO,) 1 1?2" V 3?4" H, (HI(H) 6" ST UP?)N S 1 4" SAN UP?)N 3" V UP?)N 2" SAN FRO" SS 1 A+OVE 4" SAN UP?)N 3" V UP?)N S 1
3?4" H, )N 3?4" C, )N
. .
1 1?2" 2 1?2"
2" SAN
#*RRI+*R 2'W1#
3?4" C, TO E,C E,C 1 ,CO +ELO, E,C
#*RRI+*R 1'W1#
LAV 1
2 1?2" 1 1?2"
E
2" V )N 3?4" C, UP?)N 3?4" H, UP?)N ,H 2 ,C 1 2" C, 2" V 3" F) 1 ,C 1 LAV 2 3" F) 1 3" SAN FRO" F) 1 A+OVE FCO ,C 1 (A)A) 3" SAN FRO" F) 1 A+OVE 1 1?4" H, UP ,C 1 (A)A) ,CO 2 1?2" C, UP 4" SAN
E
%E)+ER )EU R"& *I&E 102$
,H 2 3?4" C, UP?)N 3?4" H, UP?)N 3" F) 1 ,C 1 ,C 1 2" C, 2" V LAV 2 3" F) 1 3" SAN FRO" F) 1 A+OVE 3" SAN FRO" F) 1 A+OVE 1" H, UP 1 1?4" H, )N ,C 1 (A)A) ,CO 2" C, UP 2 1?2" C, )N 4" SAN
,C 1 (A)A)
6" ST UP?)N
E.4
E.4
6" ST UP ,H 1 )S 1
1 "4.1
2 "4.2
10
10.9
11
CP 11243
")!/. (&!/.
10
S 22 REFER TO RO?)I S*STE" E&UIP"ENT PIPIN( )IA(RA" ON SHT. "4.23
1 1?2" IN)IRECT ,ASTE ,? P TRAP G AIR (AP FOR FCU CON)ENSATE )RAINA(E
J. Kasdorf
,H 1
& &!.
). 1ra2ee
.".
D. 3ilber
A.6
8" )S 1 1 1?2" 1 1?2" 3?4" REFER TO "4.1 G "4.2 FOR CONT. RO?)I RO?)I H,R H, C, CA +ALANCE TO 0.$ (P" 4" 3?4" 3?4" 3?4" S- $ E, 1 SP 1 3" F) 1 3?4" C, 8" ST UP
10
REFER TO RO?)I S*STE" E&UIP"ENT PIPIN( )IA(RA" ON SHT. "4.23
Project "dministrator#
J. Jo$nson
Project "rc$%&ng#
J. Sc$+art2
'.(. )e*ie+#
E
RO?)I LOOP PU"P G UV LI(HT S-I) 3" SAN UP TO FS CAR+ON FILTERS S $ 3" FS 1 CO SAN 3" 2$0 (AL. STORA(E TAN-S
D. Di!iuccio
Dra+ing Scale#
1%8? @ 1A90?
RP+P 3 2" 3" 1" 1?2" 1 1?2" 3" SAN UP TO F) REFER TO RO?)I RISER )IA(RA" ON "4.23 FOR A))ITIONAL PIPE SIJES
SAN
E E
3" SAN UP TO FS CAR+ON FILTERS S $ 3" FS 1 CO SAN 3" REFER TO 1 1?2" SC, "4.1 FOR 1 1?2" RO?)I CONT. 1 1?2" RO?)I
/ / .
ME#'")I#"& 1(11
1 1?2"
RP+P
Issue Date#
0$ 10 11 01
4" SAN UP CO
V
Issued for#
)85:;1 )8>89@CA816 +:< P40D #2 &" R8>:8E +P#2 99F OE183 R8>:8E +:< R898458 #2 +:<5
REFER TO 1" SC, "4.2 FOR 1 1?2" RO?)I CONT. 1 1?2" RO?)I
/ / .
B
6" ST UP 4" LA+ VACUU" EIHAUST UP
1"
06 23 20 08
E.4
3" SAN UP TO FS
FCO
4" FS 1
E.4 E.4
E.$
4" SAN UP TO FS
4" SAN UP TO FS
10
3 "4.1
12204-1000
4 "4.2
$ "4.1
NORTH
M4.10
OF
S. 4ardner
"PP). Project Designer#
J. Sc$+art2
Dra+n ,-#
J. Sc$+art2
"..ro*ed#
D. Di!iuccio
Date#
10.9
11
10
10.9
11
HWHR
HWHR HWHS
10
10.9
11
B B
HPC
12" SA TMV-1 1 1/2" HW CW 12"x10" SA 1 1/2" HWHP 1 CHWP 1 CHWP 2 4" FD-1 HWHP 1 4" FD-1 LV 1 4"
CHWS
ES-2
4"
ET 1
CHWR
CHWR
LV 1
10"
) 0# (5 PS #) H 15 S( LP
10" CHWR
B.5 B.6
VD
B.5
FCO 46"x46" SA UP HWHP 2
B.5
HWHP 2 4" FD-1 4" FD-1 4" FD-1 2" V DN LAC 1
CHWS 4"
B.6
38"x38" SA
B.6
HX 1 HX 2
ADS 1 6"
8" 6"
LAC 1
B.7
B.7 B.7
VAC CA SCW
B.7
MECHANICAL ROOM 1810
(3) WATER SOFTENER TANKS
C C
C C
3" SAN UP 1" HWR UP 3" HW UP HX 2 HX 1 4" 3" CW SCW VAC CA 3" 1 1/2" 4" FD-1 CW CW 6" FS-2
C C
8"
WH 2
C.2
44"x16" SA UP 48"W x 24"H x 24"D OA INTAKE PLENUM. CONNECT TO LOUVER BY ARCH. TRADES. MOUNT 6'-6"+/- AFF.
C.2
1 1/2" SCW UP 2" G UP 2 1/2" VAC UP 1 1/2" CA UP CA 16"x16" EA VF 1 VAC WH 2 4" FD-1
DBP 1
C.2
6" WH 1 LPS(15#) SRV-V
LPS(15#)
C.1 C.1
C.1 C.1
4" CW UP
C.1 C.1
RPBP
38"x38" SA
1 1/2" 2"
LPC HPC
LPS(15#)
HPS(88#)
16"x16" EA
48"W x 18"H x 24"D EXHAUST PLENUM. CONNECT TO LOUVER BY ARCH. TRADES. MOUNT TIGHT TO UNDERSIDE OF STRUCTURE.
60"x18" SA 12" SA
3" 3/4"
6" FS-2
UH 1.3 (TYPE B)
16"x16" EA
C.8
C.9 C.9
EG-B 100 CFM
6"x6" EA 9"x9" EA
C.8
C.9 C.9
SS-1
D D
26"x24" SA UP
A-5 1000/665
D D
JANITOR CLOSET 1815
3" FD-1
D D
6" FS-2
ELEVATOR #2 EP2
16"x14" SA
HWHR
ELEVATOR #2 EP2
ELEVATOR #2 EP2
EF 2
C.8
C.9 C.9
A-5 21.6 MBH 2.2 GPM
CP-11243
10
1 M2.1
10.3
10.4
10.9
11
10
2 M4.1
10.3
10.4
10.9
11
10
3 M3.1
10.3
10.4
10.9
11
ARCH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
1/4" = 1'-0"
Issue Date:
05-06-2013 11-20-2013 01-08-2014
Issued for:
Design Development BP#2 - 99% Owner Review Bid Release #2 - Bids
12204-1000
Enlarged Mechanical Room Plan
1/6/2014 9:11:44 AM
NORTH
M6.0
OF
S. Hopper
CIVIL
S. Gardner
APPR.
J. Schwartz
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
10.9
11
46"x46" GLEA
46"x46" SA
B.5 B.6
38"x38" EA
VF 2
B.7 B.7
SOUND ATTENUATOR PACKAGED W/ FAN
C C
MOTORIZED CONTROL DAMPER (TYP) PROVIDE FILTER RACK FOR 2x4 ARRAY OF 24"x24" DISPOSABLE FILTERS 48" W x72" H x 24" D OA INTAKE PLENUM. CONNECT TO LOUVER BY ARCH. TRADES. MOUNT 6"+/- AFF.
C.1 C.1
C.2
44"x16" SA 44"x16" SA UP FROM 1ST
42" EA
112" W x60" H x 24" D EXHAUST PLENUM. CONNECT TO LOUVER BY ARCH. TRADES. MOUNT 8'-10"+/- AFF.
42" EA
SUBSTATION 2810
C.8
C.9 C.9
26"x24" SA UP FROM 1ST
48" W x72" H x 24" D OA INTAKE PLENUM. CONNECT TO LOUVER BY ARCH. TRADES. MOUNT 4" AFF.
(TYPE B)
D D
44"x16" SA
ELEVATOR #2 EP2
FCU SW3-1.1 (TYPE B) FCU SW2-1.1 (TYPE B)
2 1 M2.2
10.3
10.4
10.9
11
3 M3.1
M3.1
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
1/4" = 1'-0"
Issue Date:
05-06-2013 11-20-2013 01-08-2014
Issued for:
Design Development BP#2 - 99% Owner Review Bid Release #2 - Bids
12204-1000
Enlarged Substation Plan & Stairwell Sections
1/6/2014 9:11:47 AM
NORTH
M6.1
OF
FP
FP
S. Gardner
APPR.
J. Schwartz
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
FP
4" V 1 1/2" CW
84"x110" GLEA
48"x90" GLEA
42"x44" RA 54"x36" RA 54"x36" RA 3/4" HWHS 2" LPS(15#) UH PH.1 (TYPE B) 4" CHWR 32"x30" FHEA 4" FP 32"x30" FHEA 4" CHWS UH PH.2 (TYPE B) 3/4" HWHR 42"x36" SA 42"x36" SA
PFHX 1
30"x32" FHEA
5 M2.5
Mechanical Section
1/4" = 1'-0"
1 M2.5
Mechanical Section
1/4" = 1'-0"
32"x30" GLEA 56"x36" OA 36"x96" RA 24"x96" OA 56"x36" OA 6" CHWS 6" CHWR 1 1/4" LPS(15#) 3/4" HWHR 3/4" HWHS 36"x42" SA 60"x44" GLEA
32"x30" GLEA
36"x42" SA
54"x36" RA
96"x24" RA
3/4" LPC 3" LPS(15#) 6" CHWR 6" CHWS 6" HRS 6" HRR 6" HRS 6" HRR
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
30"x32" FHEA
HVAC 2
HVAC 3A
6 M2.5
Mechanical Section
1/4" = 1'-0"
2 M2.5
Mechanical Section
1/4" = 1'-0"
24"x96" OA
96"x26" OA
56"x36" OA
56"x36" OA
96"x28" OA
28"x96" OA
6" LPS(15#)
HVAC 3
6" LPS(15#)
HVAC 4
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
3 M2.5
Mechanical Section
1/4" = 1'-0"
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
D. DiCiuccio
8" LPS(15#) UH PH.5 (TYPE B) 1 1/2" HW 1 1/2" HW 3/4" CW 1 1/2" CW 10" CHWS 10" CHWR 6" ST 6" ST
Drawing Scale:
1/4" = 1'-0"
Issue Date:
05-06-2013 11-20-2013 01-08-2014
SH 4 6" ST UH PH.6 (TYPE B)
Issued for:
Design Development BP#2 - 99% Owner Review Bid Release #2 - Bids
3/4" HWHR
2 1/2" HWHS 2 1/2" HWHR 46"x46" SA 46"x46" SA 1 1/2" CW 1 1/2" HW 3/4" LPC
c
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
46"x46" GLEA
46"x46" SA
8" LPS(15#)
56"x44" SA
56"x44" GLEA
3/4" HW
12204-1000
Mechanical Sections
4
1/5/2014 10:37:22 PM
Mechanical Section
1/4" = 1'-0"
M2.5
M6.2
OF
1 1/2" LPC
HVAC 4A
S. Gardner
APPR.
D. Raphael
Drawn By:
D. Raphael
Approved:
D. DiCiuccio
Date:
E
E EA EA EAT EC ECC ECON ED EDB EEW EEWS EF EFF EG EHC EIH EJ EL ELEC ELEV ELL EMS ENCL ENT EP EQ EQUIP ER ERC ERR ERS ES ESP ET EWB EWC EWT EX EXH EXP EXT EAST EACH EXHAUST AIR ENTERING AIR TEMPERATURE ENTHALPY CONTROLLER ECCENTRIC ECONOMIZER EXHAUST DIFFUSER ENTERING DRY BULB EMERGENCY EYE WASH EMERGENCY EYE WASH AND SHOWER EXHAUST FAN EFFICIENCY EXHAUST GRILLE ELECTRIC HEATING COIL ELECTRIC INFRARED HEATER EXPANSION JOINT ELEVATION ELECTRICAL, ELECTRONIC ELEVATOR ELBOW ENERGY MANAGEMENT SYSTEM ENCLOSURE, ENCLOSED ENTERING ELECTRIC-PNEUMATIC EQUAL EQUIPMENT EXHAUST REGISTER ENERGY RECOVERY COIL ENERGY RECOVERY RETURN ENERGY RECOVERY SUPPLY EMERGENCY SHOWER EXTERNAL STATIC PRESSURE EXPANSION TANK ENTERING WET BULB ELECTRIC WATER COOLER ENTERING WATER TEMPERATURE EXISTING EXHAUST EXPANSION EXTERIOR, EXTERNAL FAHRENHEIT FACE AREA FACE AND BY PASS FLOAT AND THERMOSTATIC FILTER BANK FORWARD CURVED FP FLOOR CONTROL VALVE ASSEMBLY FLOOR CLEANOUT FAN COIL UNIT FIRE DAMPER FLOOR DRAIN FIRE DEPARTMENT CONNECTION FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FUME HOOD FIRE HYDRANT FIRE HOSE CABINET FIRE HOSE RACK/REEL FIRE HOSE VALVE FINISH, FINISHED FULL LOAD AMPS FLEXIBLE FLOOR FACTORY MUTUAL FLOW MEASURING STATION FIRE PROTECTION FEET PER MINUTE FIBERGLASS REINFORCED PLASTIC FLOW SWITCH FREEZESTAT FOOT, FEET FINNED TUBE RADIATION FUTURE FACE VELOCITY GAS (NATURAL) GRAM GAUGE GALLON GALVANIZED GENERAL GRAVITY HOOD GALVANIZED IRON GLYCOL GALLONS PER DAY GALLONS PER HOUR GALLONS PER MINUTE GRAINS PER POUND GRADE GRAVITY HIGH, HEIGHT HUMIDIFIER HUMIDISTAT HOSE BIBB HEATING COIL HEAT DETECTOR HOT DECK HIGH EFFICIENCY PARTICULATE AIR HUMIDITY HIGH LIMIT HAND-OFF-AUTO HORIZONTAL, HORIZONTALLY HORSEPOWER HIGH PRESSURE HIGH PRESSURE CONDENSATE HIGH PRESSURE STEAM HOUR HUMIDITY SENSOR HIGH TEMP DETECTOR HEATING HEAT TRANSFER PACKAGE HEATER HUMIDITY HEATING, VENTLATING AND AIR CONDITIONING HOT WATER HOT WATER HEATING RETURN HOT WATER HEATING SUPPLY HOT WATER RETURN HEAT EXCHANGER HYDRANT HERTZ INPUT/OUTPUT INSIDE DIAMETER INVERT ELEVATION INTAKE HOOD INCH, INCHES INCREASER INCLUDING, INCLUSIVE INSULATION, INSULATED INTERIOR, INTERNAL INVERT IONIZATION SMOKE DETECTOR INTERNAL STATIC PRESSURE INDIRECT WASTE
K
K KG KV KVA KVAR KW KWH KIP (1000 POUNDS) KILOGRAM KILOVOLT KILOVOLT AMPERES KILOVOLT AMPERE REACTIVE KILOWATTS KILOWATT HOUR LONG, LENGTH LOUVER LABORATORY LEAVING AIR TEMPERATURE LAVATORY POUNDS LEVEL LEFT HAND LINEAR LOW LIMIT CONTROLLER LIQUID PROPANE LOW PRESSURE LOW PRESSURE CONDENSATE LOW PRESSURE STEAM LOCKED ROTOR AMPS LOW TEMP DETECTOR LIGHTING 'A' WEIGHTED SOUND POWER LEVEL LEAVING WATER TEMPERATURE METER MOTOR, MOTORIZED MILLIAMPERE MIXED AIR MAKE-UP AIR CONTROLLER MACHINE MANUAL MATERIAL MANUAL AIR VENT MAXIMUM MODULAR BUILDING CONTROLLER THOUSAND BRITISH THERMAL UNITS PER HOUR MOTOR CONTROL CENTER MOTORIZED DAMPER MECHANICAL MEZZANINE MANUFACTURING MANUFACTURER MANHOLE MINIMUM MISCELLANEOUS MILLIMETER MEDIUM PRESSURE MEDIUM PRESSURE CONDENSATE MEDIUM PRESSURE STEAM MOTOR STARTER MAKE UP AIR NORTH NATIONAL NOISE CRITERIA NORMALLY CLOSED NORTHEAST NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MANUFACTURERS ASSOC. NATIONAL FIRE PROTECTION ASSOCIATION NOT IN CONTRACT NORMALLY OPEN NUMBER NOMINAL NET POSITIVE SUCTION HEAD NOT TO SCALE NORTHWEST OUTSIDE AIR OUTSIDE AIR INTAKE OUTSIDE AIR TEMPERATURE SENSOR ON CENTER OUTSIDE DIAMETER OFFICE OPPOSITE OPERATOR, OPERATED, OPERATIONAL ORIGINAL OUTSIDE SCREW AND YOKE OCCUPATIONAL SAFTY AND ENVIRON. HEALTH OCCUPATIONAL SAFETY AND HEALTH ACT OUTLET VELOCITY OUNCE PRESSURE DIFFERENTIAL PRESSURE PUMP PRE-ACTION FIRE PROTECTION PIPING PUSH BUTTON PROGRAMMABLE CONTROLLER PUMPED CONDENSATE PRESSURE DROP PNEUMATIC-ELECTRIC PENDANT PERFORATED PERMANENT PIPE GUIDE PHASE PREHEAT COIL PLUMBING PNEUMATIC POSITION POUNDS PER HOUR PARTS PER MILLION PREFABRICATED PREPARATION PRESENT PROCESS, PROCESSING PRESSURE REDUCING VALVE POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH ABSOLUTE POUNDS PER SQUARE INCH GAUGE POLYVINYL CHLORIDE POWER PROCESS WATER RETURN PROCESS WATER SUPPLY QUANTITY RADIUS RISE, RISER RETURN AIR REVERSE ACTING RADIATOR, RADIATION RAINWATER CONDUCTOR ROOM CRITERION RADIENT CEILING PANEL REINFORCED CONCRETE PIPE RETURN DIFFUSER ROOF DRAIN RECIRCULATION REDUCER
FP (CONTINUED) REFERENCE REFRIGERANT, REFRIGERATION, REFRIGERATOR REGISTER REMARKS REQUIREMENT REQUIRED RETURN REVISION RETURN FAN RETURN GRILLE RELATIVE HUMIDITY RELIEF HOOD RIGHT HAND REHEAT COIL ROOM REDUCED PRESSURE BACKFLOW PREVENTER ROOM PRESSURE CONTROLLER REVOLUTIONS PER MINUTE RETURN REGISTER RESISTANCE TEMPERATURE DETECTOR SOUTH SHELL AND TUBE SOUND ATTENUATOR SUPPLY AIR SANITARY SEWER WASTE STANDARD CUBIC FEET PER MINUTE SCHEDULE STAND ALONE COMPUTER UNIT SOFTENED COLD WATER SMOKE DETECTOR SUPPLY DIFFUSER SOUTHEAST STATIC EFFICIENCY SECOND SECTION SELECTOR SENSIBLE SEPARATOR SUPPLY FAN STEAM GENERATOR SUPPLY GRILLE SHOWER SHEET SIMILAR STANDPIPE STATIC PRESSURE SPECIFICATION SPRINKLER STATIC PRESSURE SENSOR SQUARE SUPPLY REGISTER SERVICE SINK STAINLESS STEEL CHECK VALVE STAINLESS STEEL STORM SEWER STORAGE TANK STATION STANDARD STEEL STEAM STORAGE STRAINER STRUCTURAL SUPPLY SOUTHWEST SWITCH SYMMETRICAL SYSTEM TRAP TESTING, ADJUSTING, AND BALANCING TEMPERATURE AND PRESSURE THRUST BLOCK TEMPERATURE CONTROLS TRANSFER DIFFUSER TOTAL DYNAMIC HEAD TEMPERATURE TRANSFER GRILLE TERMINAL HEATING COIL TOTAL THERMOSTAT TOTAL STATIC PRESSURE TURNING VANES TYPICAL UNDERGROUND UNIT HEATER UNDERWRITERS LABORATORIES UNINTERRUPTABLE POWER SYSTEM URINAL UNITED STATES GEOLOGICAL SURVEY UNIT VENTILATOR VENT VALVE VACUUM VARIABLE VARIABLE AIR VOLUME VACUUM BREAKER VOLUME DAMPER VELOCITY VENTILATING, VENTILATION VERTICAL VERIFY IN FIELD VOLUME VOLTAGE VARIABLE SPEED DRIVE VENT THROUGH ROOF WEST WIDE, WIDTH WITH WITHOUT WASTE AND VENT WET BULB WET BULB TEMPERATURE WATER CLOSET WALL CLEANOUT WATER GAUGE WALL HYDRANT WATER HEATER WATER PRESSURE DROP WEIGHT TRANSFORMER EXTRA HEAVY EXPLOSION PROOF YARD YARD HYDRANT DP SP SP/GL PA A FOR FOS NG G(EPS)
FIRE PROTECTION WATER SUPPLY PIPING DRY PIPE FIRE PROTECTION PIPING WET PIPE FIRE PROTECTION SPRINKLER PIPING
CB
CATCH BASIN PRESSURE GAUGE FIRE PUMP TEST HEADER TAMPER SWITCH PRESSURE/TEMPERATURE PLUG MANUAL AIR VENT AUTOMATIC AIR VENT
AI AO CS DM
ANALOG INPUT ANALOG OUTPUT CURRENT SWITCH DAMPER MOTOR DAMPER (PARALLEL BLADE) DAMPER (OPPOSED BLADE)
A A A-E AC AC AC ACCU AC&V AD ADA ADJ AF AFF AHU AI ALT ALUM AMS ANSI AO AP APD APPROX AQST ARCH ARGMNT ASME ASR ASTM ATM AUTO AUX AVG AVAIL
AMP, AMPERES AIR (COMPRESSED) ARCHITECT - ENGINEER AIR CONDITIONING AIR COMPRESSOR ALTERNATING CURRENT AIR COOLED CONDENSING UNIT AIR CONDITIONING & VENTILATING ACCESS DOOR AMERICAN DISABILITIES ACT ADJUSTABLE AIR FOIL ABOVE FINISHED FLOOR AIR HANDLING UNIT ANALOG INPUT ALTERNATE ALUMINUM AIR MEASURING STATION AMERICAN NATIONAL STANDARDS INSTITUTE ANALOG OUTPUT ACCESS PANEL AIR PRESSURE DROP APPROXIMATE AQUASTAT ARCHITECTURAL ARRANGEMENT AMERICAN SOCIETY OF MECH. ENGINEERS AUTOMATIC SPRINKLER RISER AMERICAN SOCIETY FOR TESTING MATERIALS ATMOSPHERE AUTOMATIC AUXILIARY AVERAGE AVAILABLE BOILER BACKWARD CURVED BUILDING AUTOMATION SYSTEM BARRIER FREE BOILER FEED BACK FLOW PREVENTOR BOILER HORSEPOWER BRAKE HORSEPOWER BACKWARDLY INCLINED BUILDING BOTTOM OF DUCT BOTTOM OF PIPE BOTTOM LOWER LEVEL BRITISH THERMAL UNIT BRITISH THERMAL UNIT PER HOUR BACKWATER VALVE CENTIGRADE * CELSIUS CABINET CAPACITY CONSTANT AIR VOLUME CATCH BASIN COOLING COIL COUNTER CLOCKWISE CUBIC FEET PER HOUR CUBIC FEET PER MINUTE CHILLER CHILLED WATER RETURN CHILLED WATER SUPPLY CAST IRON CIRCLE, CIRCULAR, CIRCULATION CENTER LINE CEILING CENTIMETER CLEANOUT CARBON DIOXIDE COEFFICIENT COLUMN CONCRETE CONDENSATE CONNECTION CONSTRUCTION CONTINUATION, CONTINUE, CONTINUOUS CONTRACTOR CONVECTOR COOLING COORDINATE CORRIDOR CONDENSATE PUMP CONTROL PANEL CENTRAL PROCESSING UNIT CHLORINATED POLYVINYL CHLORIDE CUP SINK CLEAN STEAM COOLING TOWER COPPER CUBIC CABINET UNIT HEATER CONTROL VALVE CAPACITY INDEX CLOCKWISE COLD WATER CONDENSER WATER RETURN CONDENSER WATER SUPPLY
L L LAB LAT LAV LBS LEV LH LIN LLC LP LP LPC LPS LRA LTD LTG LWA LWT M M mA MA MAC MACH MAN MATL MAV MAX MBC MBH MCC MD MECH MEZZ MFG MFR MH MIN MISC MM MP MPC MPS MS MUA N NATL NC NC NE NEC NEMA NFPA NIC NO NO NOM NPSH NTS NW OA OAI OATS OC OD OFF OPP OPER ORIG OS&Y OSEH OSHA OV OZ P P P PA PB PC PC PD PE PEND PERF PERM PG PH PHC PLBG PNEU POS PPH PPM PREFAB PREP PRES PROC PRV PSF PSI PSIA PSIG PVC PWR PWR PWS QTY R R RA RA RAD RC RC RCP RCP RD RD RECIRC RED
REF REFRIG REG REM REQ REQD RET REV RF RG RH RH RH RHC RM RPBP RPC RPM RR RTD
ABBREVIATIONS A
SYMBOLS
WET PIPE FIRE PROTECTION PIPING WITH 50% GLYCOL PRE-MIXED SOLUTION PRE-ACTION FIRE PROTECTION PIPING COMPRESSED AIR FUEL OIL RETURN FUEL OIL SUPPLY NATURAL GAS PIPING
ELBOW, UP ELBOW, W/ 90 CUH OR CONVECTOR (SURFACE) FINNED TUBE RADIATION GLOBE VALVE PLUG VALVE BALL VALVE
F F DD SD
DI DO
DIGITAL INPUT DIGITAL OUTPUT PRESSURE TRANSMITTER PNEUMATIC LINE RECEIVER CONTROLLER
DUCT SMOKE DETECTOR AREA SMOKE DETECTOR FIRE PULL STATION FIRE ALARM BELL ROAD BOX ROOM PRESSURIZATION INDICATOR (FLOW TUBE)
PT
PS AB
BUTTERFLY VALVE ANGLE RELIEF VALVE ANGLED STOP CHECK VALVE LINEAR STOP CHECK VALVE
MGS
DP
R S/S ST
RELAY (ELECTRICAL) START STOP (MOTOR CONTROL) STATUS SWITCHED AIR LINE VALVE - TWO WAY ELECTRIC OPERATOR 2-WAY MOTORIZED VALVE 3-WAY MOTORIZED VALVE
B BC BAS BF BF BFP BH BHP BI BLDG BOD BOP BOT BSMT BTU BTUH BWV C CAB CAP CAV CB CC CCW CFH CFM CH CHWR CHWS CI CIRC CL CLG CM CO CO2 COEF COL CONC COND CONN CONST CONT CONTR CONV COOL COORD CORR CP CP CPU CPVC CS CSTM CT CU CU CUH CV Cv CW CW CWR CWS
F FA F&BP F&T FB FC FCVA FCO FCU FD FD FDC FE FEC FH FH FHC FHR FHV FIN FLA FLEX FLR FM FMS FP FPM FRP FS FS FT FTR FUT FV G G GA GAL GALV GEN GH GI GLY GPD GPH GPM GPP GR GRAV H H H HB HC HD HD HEPA HHL HOA HORIZ HP HP HPC HPS HR HS HTD HTG HTP HTR HUM HVAC HW HWHR HWHS HWR HX HYD HZ I/O ID IE IH IN INC INCL INSUL INT INV ISD ISP IW
S S&T SA SA SAN SCFM SCHED SCU SCW SD SD SE SE SEC SECT SEL SENS SEP SF SG SG SH SHT SIM SP SP SPEC SPR SPS SQ SR SS SSCV SSTL ST ST STA STD STL STM STOR STR STRUCT SUP SW SW SYM SYS T TAB T&P TB TC TD TDH TEMP TG THC TOT TSTAT TSP TV TYP UG UH UL UPS UR USGS UV V VA VAC VAR VAV VB VD VEL VENT VERT VIF VOL VOLT VSD VTR W W W/ W/O W&V WB WBT WC WCO WG WH WH WPD WT XFMR XH XP YD YH
AQ
MASTER GAS SHUT-OFF VALVE PRESSURE REDUCING STATION FLOOR CLEANOUT WALL CLEANOUT
T
CO
MH
T
CO
EP ES FS M
ELECTRIC - PNEUMATIC RELAY END SWITCH FLOW SWITCH - IN LINE MAIN AIR SUPPLY (TEMPERATURE CONTROL) MOTOR DISCONNECT SWITCH
AIR FLOW SENSOR CONTROL RELAY DAY/NIGHT MAIN AIR SWITCH DIFFERENTIAL PRESSURE GAUGE PRESSURE SWITCH PNEUMATIC GRADUAL POSITION SWITCH
2
CHILLED WATER RETURN PIPING CHILLED WATER SUPPLY PIPING DOMESTIC HOT WATER RETURN PIPING
CR
D/N
PE PS REV P
PNEUMATIC - ELECTRIC RELAY PNEUMATIC SWITCHING RELAY PNEUMATIC REVERSING RELAY PRESSURE GAUGE VALVE - TWO WAY PNEUMATIC CONTROLLED VALVE - THREE WAY PNEUMATIC CONTROLLED ELECTRICAL LINE - 24v DC (DDC WIRING ELECTRICAL LINE - 120v AC VALVE - TWO WAY GATE MOTOR STARTER, W/O HOA SWITCH MOTOR STARTER, W/ HOA SWITCH
DPS PS
DOMESTIC HOT WATER PIPING HWHR HWHS ERR ERS COND HPCR PC PCR LPS LPC MPS MPC HOT WATER HEATING RETURN PIPING HOT WATER HEATING SUPPLY PIPING ENERGY RECOVERY LOOP RETURN PIPING ENERGY RECOVERY LOOP SUPPLY PIPING CONDENSATE DRAIN PIPING (AIR CONDITIONER) HIGH PRESSURE CONDENSATE RETURN PIPING
BFP
BACK FLOW PREVENTER CAPPED PIPE DETECTOR CHECK VALVE VALVE WITH TAMPER SWITCH OS&Y VALVE TRIPLE DUTY VALVE
T T
T
PNEUMATIC 2 - POSITION SELECTOR SWITCH STATIC PRESSURE SENSOR TEMPERATURE SENSOR (RTU) W/SUNSHIELD TEMPERATURE INDICATOR GAUGE TYPE THERMOSTAT WITH GUARD FLOW METER FIRE STAT - DUCT MOUNTED FREEZE STAT - DUCT MOUNTED HUMIDISTAT (ROOM) HUMIDITY SENSOR (DDC) HUMIDITY HIGH LIMIT SENSOR (DDC)
PP
M
SP
FM F FZ H HS HL LPI
S
PUMPED CONDENSATE RETURN PIPING PUMPED CONDENSATE RETURN PIPING LOW PRESSURE STEAM (15 PSI) PIPING LOW PRESSURE CONDENSATE (15 PSI) PIPING MEDIUM PRESSURE STEAM (15 PSI) PIPING MEDIUM PRESSURE CONDENSATE (15 PSI) PIPING FIRE DAMPER (VERTICAL), W/ ACCESS DOOR FIRE DAMPER (HORIZONTAL),W/ ACCESS DOOR (E) (SD) EXISTING FIRE DAMPER SMOKE DAMPER (VERTICAL),W/ACCESS DOOR
FCVA
SOLENOID VALVE REDUCER AUTOMATIC BALANCE VALVE CHECK VALVE W/ARROW INDICATING FLOW VALVE GAS VALVE STRAINER PIPE GUIDE
T
PILOT POSITIONER MOUNTED ON DEVICE WITH POSITIVE FEEDBACK ELECTRICAL LINE DESIGNATION ON WIRING DIAGRAMS (VOLTAGE AS NOTE) MOTOR STARTER EXISTING - PROVIDE HOA SWITCH MOTOR STARTER PROVIDE HOA SWITCH, TRANSFORMER AND CONTROL ROOM
LOOP POWER INDICATOR MANOMETER TEMPERATURE SENSOR (RTD) DUCT MOUNTED RIGID ELEMENT TEMPERATURE SENSOR (RTD) DUCT MOUNTED AVERAGING ELEMENT TEMPERATURE SENSOR (RTD) IMMERSION TYPE ELEMENT
FM
S
EXPANSION COMPENSATOR OR EXPANSION JOINT FIRE CONTROL VALVE DRY PIPE VALVE THRUST BLOCK
T
DPT
(F/SD) FIRE SMOKE DAMPER (VERTICAL),W/ACCESS DOOR (SD) SMOKE DAMPER (HORIZONTAL),W/ ACCESS DOOR
FMS
(F/SD) FIRE SMOKE DAMPER (VERTICAL),W/ACCESS DOOR FLOW DIRECTION TEE UP LINE THRU WALL
D
D D D DA DAT D&T DB dB DC DDC DEG DEMO DEPT DET DF DI DIA DIFF DIFF DIM DISC DISCH DIV DN DO DOM DP DP DPR DPG DPT DR DS DT DWG DX DEEP, DEPTH DRIVE DROP DIRECT ACTING DISCHARGE AIR TEMP DRIP AND TRAP DRY BULB DECIBEL DIRECT CURRENT DIRECT DIGITAL CONTROL DEGREE DEMOLISH, DEMOLITION DEPARTMENT DETAIL DRINKING FOUNTAIN DIGITAL INPUT DIAMETER DIFFUSER DIFFERENTIAL DIMENSION DISCONNECT DISCHARGE DIVISION DOWN DIGITAL OUTPUT DOMESTIC DRIP POCKET DRY PENDANT DAMPER DIFFERENTIAL PRESSURE GAUGE DEW POINT TEMPERATURE DRAIN DOWNSPOUT DRAIN TILE DRAWING DIRECT EXPANSION
NOTATION METHODS
SD-A 10" DIA 350 CFM SD-A 10" DIA 350 CFM RR-A 350 CFM ER-A 350 CFM SD-A 350 CFM SD-A 350 CFM SUPPLY AIR DIFFUSER, TYPE 'A' WITH FLEXIBLE DUCT CONNECTION (TWO WAY THROW) BELL MOUTH AIR INLET AREA SHALL BE EQUAL TO '2' TIMES DUCT AREA AHU 1 AIR HANDLING UNIT No. 1 SUPPLY DIFFUSER, TYPE 'A', 10" NECK, 350 CFM SUPPLY DIFFUSER (3-WAY) RETURN OR EXHAUST REGISTER, TYPE 'A', 350 CFM EXHAUST REGISTER, TYPE 'A', 350 CFM FTR-A 5'-0" 5.7 MBH ST 1 FINNED TUBE RADIATION, TYPE 'A', 5'-0" ELEMENT, 5.7 TOTAL MBH (REFER TO EQUIPMENT SCHEDULES) CUH A CONV A A-1 6.5 MBH 0.6 GPM B-1 SPRINKLER HEAD SCHEDULE SOUNT TRAP (ATTENUATOR) TYPE SYMBOL TYPE & MODEL NO. QUICK RESPONSE CONCEALED PENDENT QUICK RESPONSE UPRIGHT QUICK RESPONSE HORIZONTAL SIDEWALL QUICK RESPONSE DRY PENDENT FINISH REFER TO SPECIFICATIONS FOR MANUFACTURERS
A B
CABINET UNIT HEATER, TYPE 'A' C CONVECTOR, TYPE 'A' TERMINAL VARIABLE VOLUME BOX, TYPE 'A', SIZE '1' (HEATING COIL, REFER TO EQUIPMENT SCHEDULES) TERMINAL VARIABLE VOLUME BOX, TYPE 'B', SIZE '1' (NO HEATING COIL, REFER TO EQUIPMENT SCHEDULES) DUAL DUCT CONSTANT VOLUME MIXING BOX (REFER TO EQUIPMENT SCHEDULES) HEATING COIL, TYPE 'A' (REFER TO EQUIPMENT SCHEDULES) D D
UNLESS NOTED PUBLIC AREAS W/FINISHED OTHERWISE CEILINGS BRASS(UNFINISHED AREAS) AREAS W/O CEILINGS CHROME(FINISHED AREAS) SEE DRAWINGS, HI-TEMP WHITE STANDARD IN ELEV. PITS WHITE SEE DRAWINGS
Q R
X Y
A3
EF 1
HC-A
POINT WHERE CHANGE IN DUCT SIZE OR PIPE PITCH TAKES PLACE SUPPLY AIR BRANCH CONNECTION SPIN-IN FITTING WITH VOLUME DAMPER POINT WHERE DEMOLITION ENDS/POINT OF NEW CONSTRUCTION RETURN AIR/EXHAUST AIR BRANCH CONNECTION WITH VOLUME DAMPER
3. 4. 5.
6. 7.
THIS PROJECT MAY NOT UTILIZE ALL THE SYMBOLS, MATERIALS, ABBREVIATIONS AND STANDARD INFORMATION SHOWN ON THIS SHEET.
MOUNTING HEIGHTS
COMPRESSED AIR QUICK DISCONNECT FIRE PUMP TEST CONNECTION FIRE DEPARTMENT CONNECTION (HOSE, INSIDE) FIRE DEPARTMENT CONNECTION (SIAMESE) WALL MOUNTED CABINET UNIT HEATER WALL CLEAN OUT SUPPLY AIR DIFFUSER (AREAS WITHOUT CEILINGS) THERMOSTAT HUMIDISTAT HOSE BIB
SYMBOL LEGEND
DETAIL SYMBOL DETAIL IDENTIFICATION 2 M2.1 SECTION LOCATOR SECTION IDENTIFICATION ELEVATION NUMBER 2 M5.1 3 DRAWING WHERE DETAIL IS REFERENCED OR CUT PLAN OR DETAIL ENLARGEMENT PLAN OR DETAIL IDENTIFICATION DRAWING WHERE PLAN OR DETAILS IS DRAWN 4 M5.1 2 1 DRAWING WHERE ELEVATION IS DRAWN NEW ROOM NAME AND NUMBER MATCHLINE INDICATOR DETAIL LOCATOR DETAIL IDENTIFICATION 2 8" AFF DRAWING WHERE PLAN OR DETAILS IS DRAWN NORTH ARROW
N
GENERAL NOTES
ELEVATION SYMBOL COLUMN CENTERLINE 1. 2. ALL DESIGN, INSTALLATIONA AND MATERIALS SHALL CONFORM TO NFPA 13, NFPA 14, NFPA 20, FACTORY MUTUAL (GUIDELINES, AND ALL STATE AND LOCAL CODES DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. VERIFY ALL CONDITIONS. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURE'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, MISC STEEL AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION. APPROPIATE SIGNAGE SHALL BE AFFIXED TO ALL FIRE PROTECTION EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED TO OWNER. PROVIDE FLUSH TYPE ACCESS DOORS OR PANEL NO SMALLER THAN 12"X12" AND NO LARGER THEN 30"x30" FOR ALL VALVES OR APPARATUS LOCATED IN CHASES, WALLS AND ABOVE NON ACCESSIBLE CEILINGS. PROVIDE ACCESS LADDER TO ALL SPRINKLER FLOOR CONTROL ASSEMBLIES LOCATED MORE THEN 7'-0" ABOVE FLOOR. ALL PIPE SIZES SHOWN ON DRAWINGS ARE APPROXIMATE AND ARE SHOWN ONLY TO ASSIST THE DESIGN. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. SPRINKLER HEAD TYPES TO BE USED: REFER TO SPRINKLER HEAD SCHEDULE.
CP-11243
ARCH. MECH.
DETAIL
DETAIL SCALE
J. Kasdorf
ELEC.
EXISTING
3.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
H 48" AFF
2 M5.1
D. DiCiuccio
Drawing Scale:
No Scale
1' - 6" TO
WCO
M5.1
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
10. PENDENT TYP SPRINKLER HEADS LOCATED IN SUSPENDED CEILING TILES, SHALL BE CENTERED IN CEILING TILE. 11. PROVIDE SPRINKLER PROTECTION INSIDE ELEVATOR MACHINE ROOMS AND PITS WITH SHUT-OFF AND TAMPER SWITCH +VALVE IN BOX WITH GLASS DOOR. 12. PROVIDE SPRINKLER HEAD CAGES AT ALL ELECTRIC AND MECHANICAL EQUIPMENT ROOMS. 13. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE.
12204-1000
Fire Protection Reference Information
1/5/2014 9:48:32 PM
NORTH
FP0.1
OF
(W)
S. Gardner
APPR.
J. Schwartz
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
10.9
11
ALL DESIGN, INSTALLATIONA AND MATERIALS SHALL CONFORM TO NFPA 13, NFPA 14, NFPA 20, FACTORY MUTUAL (GUIDELINES, AND ALL STATE AND LOCAL CODES DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. VERIFY ALL CONDITIONS. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURE'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, MISC STEEL AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION. APPROPIATE SIGNAGE SHALL BE AFFIXED TO ALL FIRE PROTECTION EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED TO OWNER. PROVIDE FLUSH TYPE ACCESS DOORS OR PANEL NO SMALLER THAN 12"X12" AND NO LARGER THEN 30"x30" FOR ALL VALVES OR APPARATUS LOCATED IN CHASES, WALLS AND ABOVE NON ACCESSIBLE CEILINGS.
FIRE PROTECTION
1 2 3 4 5 6 7 6" COMBINATION STANDPIPE AND 2" DRAIN RISER UP AND DOWN. 4" STANDPIPE RISER. SPRINKLER CONTROL VALVE ASSEMBLY. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTE 11 ON THIS DRAWING. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTES ON THIS DRAWING. PRE-ACTION SYSTEM. VALVE LOCATED IN PUMP ROOM DRY PIPE SYSTEM HIGH TEMPERATURE SPRINKLERS .20/2500 SQ FT - INSTALL UPRIGHT SPRINKLERS ON SPRINGS TO ACCOMMODATE FUTURE USE. .10/1500 SQ FT. +250 GPM HOSE ALLOWANCE
1.
2.
THE ENTIRE FIRE STANDPIPE SYSTEM SHALL BE DESIGNED, LOCATED, INSTALLED AND MAINTAINED THROUGHOUT THE BUILDING IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 14 FACTORY MUTUAL DATA SHEET 4-4N AND ALL STATE AND LOCAL CODES AND AUTHORITY HAVING JURISDICTION. THE STANDPIPE SYSTEM SHALL BE DESIGNED TO PROVIDE 65 PSI. @ THE TOP OF THE STANDPIPE. HOSE VALVE STATION SHALL BE UNOBSTRUCTED AND INSTALLED BETWEEN 3 FEET AND NOT MORE THAN 5 FEET ABOVE THE FINISHED FLOOR. PROVIDE VALVE CABINET WHERE INDICATED. HOSE VALVE STATION SHALL BE EQUIPPED WITH 2-1/2" FIRE DEPARTMENT VALVE & CAP. FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED AND LOCATED IN ACCORDANCE WITH NFPA 13, FACTORY MUTUAL GUIDELINES AND ALL STATE AND LOCAL CODES. REQUIREMENTS AND AUTHORITY HAVING JURISDICTION. SPRINKLER HEADS SHALL BE SIZED IN ACCORDANCE W/FACTORY MUTUAL DATA SHEET 3-26.
6" x 1'-0" SPOOL PIECE 4" 750 GPM @ 55 PSI VERTICAL IN LINE ELECTRIC FIRE PUMP 6" GROOVED SWING CHECK VALVE 6" WATTS MODEL 757 DOUBLE CHECK BACKFLOW PREVENTER FIRE PUMP CONTROLLER
3. 4. 5.
PROVIDE ACCESS LADDER TO ALL SPRINKLER FLOOR CONTROL ASSEMBLIES LOCATED MORE THEN 7'-0" ABOVE FLOOR. 6. ALL PIPE SIZES SHOWN ON DRAWINGS ARE APPROXIMATE AND ARE SHOWN ONLY TO ASSIST THE DESIGN. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. SPRINKLER HEAD TYPES TO BE USED: REFER TO SPRINKLER HEAD SCHEDULE. 7.
8 9 10
C.9
6" PUMP BYPASS JOCKEY PUMP CONTROLLER (PUMP SHALL BE 5GPM @55PSI (3/4 HP)
10. PENDENT TYP SPRINKLER HEADS LOCATED IN SUSPENDED CEILING TILES, SHALL BE CENTERED IN CEILING TILE. 11. PROVIDE SPRINKLER PROTECTION INSIDE ELEVATOR MACHINE ROOMS AND PITS WITH SHUT-OFF AND TAMPER SWITCH +VALVE IN BOX WITH GLASS DOOR. 12. PROVIDE SPRINKLER HEAD CAGES AT ALL ELECTRIC AND MECHANICAL EQUIPMENT ROOMS. 6" GROOVED B'FLY VALVE 4" UP TO FIRE DEPT CONNETION 13. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE.
6"
4"
6"
2 FP.1
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
A
VESTIBULE 1VB1 COLLABORATION SPACE NORTH 1060
FHV (TYP)
STAIR SW3-1
4 2
A.6
FP
OFFICE 1311
OFFICE 1312
OFFICE 1313
WORKROOM 1301
OFFICE 1314
OFFICE 1315
OFFICE 1316
WORKROOM 1302
OFFICE 1317
OFFICE 1318
OFFICE 1319
MECHANICAL 1611
B
LARGE CONFERENCE ROOM 1000
FP
CORRIDOR 1450
FP
FP
ELEVATOR #1 EP1
6 4"
IT CLOSET 1011A
4"
KITCHENETTE 1011
FP
C C.1
STAIR SW1-1
EQUIP ROOM 1705 LINEAR EQUIPMENT ROOM 1600 ANIMAL HOLDING 1704 IMAGING SUITE 1700
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
CORRIDOR 1HW1
2 FP.1
C.9 D
JANITOR CLOSET 1020 MEN'S TOILET 1021
FP
JANITOR CLOSET 1815 LAB SUPPORT 1230 FLUORESCENT IMAGING LAB 1702 LAB 1200 LAB SUPPORT 1240
FP
ELEVATOR #2 EP2
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
4" 4"
CORRIDOR 1HW2
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
ELECTRICAL CLOSET 1820
Q.M. Review:
UFC ROOM 1830 UNASSIGNED 1840 LOADING DOCK 1860
7
D. DiCiuccio
Drawing Scale:
4" FP
CORRIDOR 1250
As indicated
E
GENDER NEUTRAL TOILET 1023 BUILDING MGR OFFICE 1040 MECHANICAL ROOM 1650
3" SPRINKLER LINE SP
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
OFFICE 1111
OFFICE 1112
OFFICE 1113
WORKROOM 1101
OFFICE 1114
OFFICE 1115
OFFICE 1116
WORKROOM 1102
OFFICE 1117
OFFICE 1118
OFFICE 1119
4" 6"
E.4
1
FHV (TYP)
STAIR SW2-1
COMBINATION SPRINKLER /STANDPIPE (TYP) REFER TO DETAIL ON FP.7
FDC
12204-1000
First Floor Plan - Fire Protection
1/5/2014 9:48:41 PM
NORTH
FP.1
OF
FP
S. Gardner
APPR.
R. Cuperus
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
SYSTEMS SHALL BE DESIGNED TO PROVIDE A DENSITY/AREA OF COVERAGE AS FOLLOWS: A. OFFICES - .10 GPM OVER THE MOST REMOTE 1500 SQ FT. W/250 GPM HOSE ALLOWANCE. B. LABS & MECHANICAL ROOMS - .20 GPM OVER THE MOST REMOTE 2500 SQ. FT. W/ 250 GPM FOR HOSE ALLOWANCE.
GENERAL NOTES
KEY NOTES
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
1. 2.
ALL DESIGN, INSTALLATIONA AND MATERIALS SHALL CONFORM TO NFPA 13, NFPA 14, NFPA 20, FACTORY MUTUAL (GUIDELINES, AND ALL STATE AND LOCAL CODES DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. VERIFY ALL CONDITIONS. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURE'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, MISC STEEL AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION. APPROPIATE SIGNAGE SHALL BE AFFIXED TO ALL FIRE PROTECTION EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED TO OWNER. PROVIDE FLUSH TYPE ACCESS DOORS OR PANEL NO SMALLER THAN 12"X12" AND NO LARGER THEN 30"x30" FOR ALL VALVES OR APPARATUS LOCATED IN CHASES, WALLS AND ABOVE NON ACCESSIBLE CEILINGS. PROVIDE ACCESS LADDER TO ALL SPRINKLER FLOOR CONTROL ASSEMBLIES LOCATED MORE THEN 7'-0" ABOVE FLOOR. ALL PIPE SIZES SHOWN ON DRAWINGS ARE APPROXIMATE AND ARE SHOWN ONLY TO ASSIST THE DESIGN. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. SPRINKLER HEAD TYPES TO BE USED: REFER TO SPRINKLER HEAD SCHEDULE.
KEY NOTES
FIRE PROTECTION
1 2 6" COMBINATION STANDPIPE AND 2" DRAIN RISER UP AND DOWN. 4" STANDPIPE RISER. SPRINKLER CONTROL VALVE ASSEMBLY. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTE 11 ON THIS DRAWING. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTES ON THIS DRAWING. PRE-ACTION SYSTEM. VALVE LOCATED IN PUMP ROOM DRY PIPE SYSTEM HIGH TEMPERATURE SPRINKLERS .20/2500 SQ FT - INSTALL UPRIGHT SPRINKLERS ON SPRINGS TO ACCOMMODATE FUTURE USE. .10/1500 SQ FT. +250 GPM HOSE ALLOWANCE
1.
3.
2.
THE ENTIRE FIRE STANDPIPE SYSTEM SHALL BE DESIGNED, LOCATED, INSTALLED AND MAINTAINED THROUGHOUT THE BUILDING IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 14 FACTORY MUTUAL DATA SHEET 4-4N AND ALL STATE AND LOCAL CODES AND AUTHORITY HAVING JURISDICTION. THE STANDPIPE SYSTEM SHALL BE DESIGNED TO PROVIDE 65 PSI. @ THE TOP OF THE STANDPIPE. HOSE VALVE STATION SHALL BE UNOBSTRUCTED AND INSTALLED BETWEEN 3 FEET AND NOT MORE THAN 5 FEET ABOVE THE FINISHED FLOOR. PROVIDE VALVE CABINET WHERE INDICATED. HOSE VALVE STATION SHALL BE EQUIPPED WITH 2-1/2" FIRE DEPARTMENT VALVE & CAP. FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED AND LOCATED IN ACCORDANCE WITH NFPA 13, FACTORY MUTUAL GUIDELINES AND ALL STATE AND LOCAL CODES. REQUIREMENTS AND AUTHORITY HAVING JURISDICTION. SPRINKLER HEADS SHALL BE SIZED IN ACCORDANCE W/FACTORY MUTUAL DATA SHEET 3-26.
3 4 5 6 7 8 9 10
4. 5. 6. 7. 8. 9.
3. 4. 5. 6. 7.
10. PENDENT TYP SPRINKLER HEADS LOCATED IN SUSPENDED CEILING TILES, SHALL BE CENTERED IN CEILING TILE. 11. PROVIDE SPRINKLER PROTECTION INSIDE ELEVATOR MACHINE ROOMS AND PITS WITH SHUT-OFF AND TAMPER SWITCH +VALVE IN BOX WITH GLASS DOOR. 12. PROVIDE SPRINKLER HEAD CAGES AT ALL ELECTRIC AND MECHANICAL EQUIPMENT ROOMS. 13. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
A
LOUNGE 2HW1A ADMIN 2060 STAIR SW3-2
WORKROOM 2301
WORKROOM 2302
FHV (TYP)
A.6
2
OFFICE 2311
OFFICE 2312
OFFICE 2313
OFFICE 2314
OFFICE 2315
OFFICE 2316
OFFICE 2317
OFFICE 2318
OFFICE 2319
MECHANICAL 2611
B
LARGE CONFERENCE ROOM 2000
2
LAB 2400
5
CORRIDOR 2HW3 ELECTRICAL CLOSET 2009 CORRIDOR 2HW1 TISSUE CULTURE 2521 TISSUE CULTURE 2522 TISSUE CULTURE 2524 TISSUE CULTURE 2525 TISSUE CULTURE 2526
C C.1
FUME HOOD 2523 FUME HOOD 2527 TISSUE CULTURE 2529 SUBSTATION 2810
STAIR SW1-2
ELEVATOR #2 EP2
C.9 D
JANITOR CLOSET 2020 PERSONAL HEALTH ROOM 2042 TISSUE CULTURE 2532
CP-11243
CORRIDOR 2HW2
ARCH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
UFC ROOM 2830
FHV (TYP)
Project Administrator:
J. Johnson
Project Arch/Eng:
E
2
J. Schwartz
Q.M. Review:
D. DiCiuccio
Drawing Scale:
As indicated
CUSTODIAL 2840
OFFICE 2111
OFFICE 2112
OFFICE 2113
OFFICE 2114
OFFICE 2115
OFFICE 2116
OFFICE 2117
OFFICE 2118
OFFICE 2119
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
E.4
GENDER NEUTRAL TOILET 2023
3" SPRINKLER LINE 3
SP
STAIR SW2-2
COMBINATION SPRINKLER /STANDPIPE (TYP) REFER TO DETAIL ON FP.7
4
c
12204-1000
Second Floor Plan - Fire Protection
1/5/2014 9:48:47 PM
NORTH
FP.2
OF
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
R. Cuperus
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
SYSTEMS SHALL BE DESIGNED TO PROVIDE A DENSITY/AREA OF COVERAGE AS FOLLOWS: A. OFFICES - .10 GPM OVER THE MOST REMOTE 1500 SQ FT. W/250 GPM HOSE ALLOWANCE. B. LABS & MECHANICAL ROOMS - .20 GPM OVER THE MOST REMOTE 2500 SQ. FT. W/ 250 GPM FOR HOSE ALLOWANCE.
GENERAL NOTES
KEY NOTES
FIRE PROTECTION
1 2 3 4 6" COMBINATION STANDPIPE AND 2" DRAIN RISER UP AND DOWN. 4" STANDPIPE RISER. SPRINKLER CONTROL VALVE ASSEMBLY. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTE 11 ON THIS DRAWING. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTES ON THIS DRAWING. PRE-ACTION SYSTEM. VALVE LOCATED IN PUMP ROOM DRY PIPE SYSTEM HIGH TEMPERATURE SPRINKLERS .20/2500 SQ FT - INSTALL UPRIGHT SPRINKLERS ON SPRINGS TO ACCOMMODATE FUTURE USE. .10/1500 SQ FT. +250 GPM HOSE ALLOWANCE
1. 2.
ALL DESIGN, INSTALLATIONA AND MATERIALS SHALL CONFORM TO NFPA 13, NFPA 14, NFPA 20, FACTORY MUTUAL (GUIDELINES, AND ALL STATE AND LOCAL CODES DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. VERIFY ALL CONDITIONS. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURE'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, MISC STEEL AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION. APPROPIATE SIGNAGE SHALL BE AFFIXED TO ALL FIRE PROTECTION EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED TO OWNER. PROVIDE FLUSH TYPE ACCESS DOORS OR PANEL NO SMALLER THAN 12"X12" AND NO LARGER THEN 30"x30" FOR ALL VALVES OR APPARATUS LOCATED IN CHASES, WALLS AND ABOVE NON ACCESSIBLE CEILINGS. PROVIDE ACCESS LADDER TO ALL SPRINKLER FLOOR CONTROL ASSEMBLIES LOCATED MORE THEN 7'-0" ABOVE FLOOR. ALL PIPE SIZES SHOWN ON DRAWINGS ARE APPROXIMATE AND ARE SHOWN ONLY TO ASSIST THE DESIGN. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. SPRINKLER HEAD TYPES TO BE USED: REFER TO SPRINKLER HEAD SCHEDULE.
1.
3.
2.
THE ENTIRE FIRE STANDPIPE SYSTEM SHALL BE DESIGNED, LOCATED, INSTALLED AND MAINTAINED THROUGHOUT THE BUILDING IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 14 FACTORY MUTUAL DATA SHEET 4-4N AND ALL STATE AND LOCAL CODES AND AUTHORITY HAVING JURISDICTION. THE STANDPIPE SYSTEM SHALL BE DESIGNED TO PROVIDE 65 PSI. @ THE TOP OF THE STANDPIPE. HOSE VALVE STATION SHALL BE UNOBSTRUCTED AND INSTALLED BETWEEN 3 FEET AND NOT MORE THAN 5 FEET ABOVE THE FINISHED FLOOR. PROVIDE VALVE CABINET WHERE INDICATED. HOSE VALVE STATION SHALL BE EQUIPPED WITH 2-1/2" FIRE DEPARTMENT VALVE & CAP. FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED AND LOCATED IN ACCORDANCE WITH NFPA 13, FACTORY MUTUAL GUIDELINES AND ALL STATE AND LOCAL CODES. REQUIREMENTS AND AUTHORITY HAVING JURISDICTION. SPRINKLER HEADS SHALL BE SIZED IN ACCORDANCE W/FACTORY MUTUAL DATA SHEET 3-26.
4. 5. 6. 7. 8. 9.
3. 4. 5. 6. 7.
5 6 7 8 9 10
10. PENDENT TYP SPRINKLER HEADS LOCATED IN SUSPENDED CEILING TILES, SHALL BE CENTERED IN CEILING TILE. 11. PROVIDE SPRINKLER PROTECTION INSIDE ELEVATOR MACHINE ROOMS AND PITS WITH SHUT-OFF AND TAMPER SWITCH +VALVE IN BOX WITH GLASS DOOR. 12. PROVIDE SPRINKLER HEAD CAGES AT ALL ELECTRIC AND MECHANICAL EQUIPMENT ROOMS. 13. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
A
LOUNGE 3HW1A
STAIR SW3-3
SHELL 3300
A.6
B
SHELL 3000
FP
4" FP UP 4"
CORRIDOR 3HW1
SHELL 416
C C.1
STAIR SW1-3
C.9
5
SHELL 3020
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
CORRIDOR 3HW1C ELECTRICAL CLOSET 3820 COLLABORATION SPACE 3040
D. Wilber
UFC ROOM 3830
Project Administrator:
J. Johnson
Project Arch/Eng:
FHV (TYP)
J. Schwartz
Q.M. Review:
E
2
D. DiCiuccio
MECHANICAL ROOM 3650
FP
Drawing Scale:
SHELL 3840
As indicated
Issue Date:
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
E.4
3" SPRINKLER LINE 10 1
FHV (TYP)
STAIR SW2-3
SHELL 3100
COMBINATION SPRINKLER /STANDPIPE (TYP) REFER TO DETAIL ON FP.7
4
c
12204-1000
Third Floor Plan - Fire Protection
1/5/2014 9:48:52 PM
NORTH
FP.3
OF
S. Gardner
APPR. Project Designer:
R. Cuperus
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
SYSTEMS SHALL BE DESIGNED TO PROVIDE A DENSITY/AREA OF COVERAGE AS FOLLOWS: A. OFFICES - .10 GPM OVER THE MOST REMOTE 1500 SQ FT. W/250 GPM HOSE ALLOWANCE. B. LABS & MECHANICAL ROOMS - .20 GPM OVER THE MOST REMOTE 2500 SQ. FT. W/ 250 GPM FOR HOSE ALLOWANCE.
GENERAL NOTES
1. 2.
ALL DESIGN, INSTALLATIONA AND MATERIALS SHALL CONFORM TO NFPA 13, NFPA 14, NFPA 20, FACTORY MUTUAL (GUIDELINES, AND ALL STATE AND LOCAL CODES DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. VERIFY ALL CONDITIONS. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURE'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, MISC STEEL AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION. APPROPIATE SIGNAGE SHALL BE AFFIXED TO ALL FIRE PROTECTION EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED TO OWNER. PROVIDE FLUSH TYPE ACCESS DOORS OR PANEL NO SMALLER THAN 12"X12" AND NO LARGER THEN 30"x30" FOR ALL VALVES OR APPARATUS LOCATED IN CHASES, WALLS AND ABOVE NON ACCESSIBLE CEILINGS. PROVIDE ACCESS LADDER TO ALL SPRINKLER FLOOR CONTROL ASSEMBLIES LOCATED MORE THEN 7'-0" ABOVE FLOOR. ALL PIPE SIZES SHOWN ON DRAWINGS ARE APPROXIMATE AND ARE SHOWN ONLY TO ASSIST THE DESIGN. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
FIRE PROTECTION
1 2 3 4 5 6 7 8 9 10 6" COMBINATION STANDPIPE AND 2" DRAIN RISER UP AND DOWN. 4" STANDPIPE RISER. SPRINKLER CONTROL VALVE ASSEMBLY. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTE 11 ON THIS DRAWING. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTES ON THIS DRAWING. PRE-ACTION SYSTEM. VALVE LOCATED IN PUMP ROOM DRY PIPE SYSTEM HIGH TEMPERATURE SPRINKLERS .20/2500 SQ FT - INSTALL UPRIGHT SPRINKLERS ON SPRINGS TO ACCOMMODATE FUTURE USE. .10/1500 SQ FT. +250 GPM HOSE ALLOWANCE
GENERAL NOTES
KEY NOTES
3.
4. 5. 6. 7. 8. 9.
3. 4. 5. 6. 7.
10. PENDENT TYP SPRINKLER HEADS LOCATED IN SUSPENDED CEILING TILES, SHALL BE CENTERED IN CEILING TILE. 11. PROVIDE SPRINKLER PROTECTION INSIDE ELEVATOR MACHINE ROOMS AND PITS WITH SHUT-OFF AND TAMPER SWITCH +VALVE IN BOX WITH GLASS DOOR. 12. PROVIDE SPRINKLER HEAD CAGES AT ALL ELECTRIC AND MECHANICAL EQUIPMENT ROOMS. 13. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
A
LOUNGE 4HW1A
4
STAIR SW3-4
SHELL 4300
A.6
2
B
SHELL 4000
ELEVATOR #1 EP1
4" UP TO PENTHOUSE
CORRIDOR 4HW1
SHELL 417
C C.1
5 6" UP TO PENTHOUSE
ELEVATOR #2 EP2
C.9
5
STAIR SW4-4
SHELL 4020
6"
CP-11243
ELECTRICAL CLOSET 4820
ARCH.
J. Kasdorf
ELEC.
CORRIDOR 4HW1C
R. Frazee
COLLABORATION SPACE 4040 UFC ROOM 4830
FHV (TYP)
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
Q.M. Review:
MECHANICAL ROOM 4650
SUPPLY TO 4TH FLOOR SPRINKLERS
E
2
D. DiCiuccio
Drawing Scale:
As indicated
Issue Date:
SP FHV (TYP)
SHELL 4100
SHELL 2 4840
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
E.4
3" SPRINKLER LINE W/ 2" GANG DRAIN 10 1
STAIR SW2-4
LOUNGE 4HW1B
12204-1000
Fourth Floor Plan - Fire Protection
1/5/2014 9:48:57 PM
NORTH
FP.4
OF
S. Hopper
CIVIL
S. Gardner
APPR.
R. Cuperus
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
GENERAL NOTES
1. 2. ALL DESIGN, INSTALLATIONA AND MATERIALS SHALL CONFORM TO NFPA 13, NFPA 14, NFPA 20, FACTORY MUTUAL (GUIDELINES, AND ALL STATE AND LOCAL CODES DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. VERIFY ALL CONDITIONS. NOTIFY ARCHITECT/ENGINEER OF DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS. COORDINATE ALL WORK WITH APPROPRIATE TRADES. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURE'S RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, MISC STEEL AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION. APPROPIATE SIGNAGE SHALL BE AFFIXED TO ALL FIRE PROTECTION EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED TO OWNER.
KEY NOTES
FIRE PROTECTION
1 2 3 4 5 6 7 6" COMBINATION STANDPIPE AND 2" DRAIN RISER UP AND DOWN. 4" STANDPIPE RISER. SPRINKLER CONTROL VALVE ASSEMBLY. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTE 11 ON THIS DRAWING. PROVIDE WET SPRINKLER FIRE PROTECTION COVERAGE. SEE ADDITIONAL FIRE PROTECTION NOTES ON THIS DRAWING. PRE-ACTION SYSTEM. VALVE LOCATED IN PUMP ROOM DRY PIPE SYSTEM HIGH TEMPERATURE SPRINKLERS .20/2500 SQ FT - INSTALL UPRIGHT SPRINKLERS ON SPRINGS TO ACCOMMODATE FUTURE USE. .10/1500 SQ FT. +250 GPM HOSE ALLOWANCE
1.
2.
THE ENTIRE FIRE STANDPIPE SYSTEM SHALL BE DESIGNED, LOCATED, INSTALLED AND MAINTAINED THROUGHOUT THE BUILDING IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 14 FACTORY MUTUAL DATA SHEET 4-4N AND ALL STATE AND LOCAL CODES AND AUTHORITY HAVING JURISDICTION. THE STANDPIPE SYSTEM SHALL BE DESIGNED TO PROVIDE 65 PSI. @ THE TOP OF THE STANDPIPE. HOSE VALVE STATION SHALL BE UNOBSTRUCTED AND INSTALLED BETWEEN 3 FEET AND NOT MORE THAN 5 FEET ABOVE THE FINISHED FLOOR. PROVIDE VALVE CABINET WHERE INDICATED. HOSE VALVE STATION SHALL BE EQUIPPED WITH 2-1/2" FIRE DEPARTMENT VALVE & CAP. FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED AND LOCATED IN ACCORDANCE WITH NFPA 13, FACTORY MUTUAL GUIDELINES AND ALL STATE AND LOCAL CODES. REQUIREMENTS AND AUTHORITY HAVING JURISDICTION. SPRINKLER HEADS SHALL BE SIZED IN ACCORDANCE W/FACTORY MUTUAL DATA SHEET 3-26.
3.
3. 4.
4. 5. 6. 7. 8. 9.
5. PROVIDE FLUSH TYPE ACCESS DOORS OR PANEL NO SMALLER THAN 12"X12" AND NO LARGER THEN 30"x30" FOR ALL VALVES OR APPARATUS LOCATED IN CHASES, WALLS AND ABOVE NON ACCESSIBLE CEILINGS. PROVIDE ACCESS LADDER TO ALL SPRINKLER FLOOR CONTROL ASSEMBLIES LOCATED MORE THEN 7'-0" ABOVE FLOOR. 7. ALL PIPE SIZES SHOWN ON DRAWINGS ARE APPROXIMATE AND ARE SHOWN ONLY TO ASSIST THE DESIGN. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. SPRINKLER HEAD TYPES TO BE USED: REFER TO SPRINKLER HEAD SCHEDULE. 6.
8 9 10
10. PENDENT TYP SPRINKLER HEADS LOCATED IN SUSPENDED CEILING TILES, SHALL BE CENTERED IN CEILING TILE. 11. PROVIDE SPRINKLER PROTECTION INSIDE ELEVATOR MACHINE ROOMS AND PITS WITH SHUT-OFF AND TAMPER SWITCH +VALVE IN BOX WITH GLASS DOOR. 12. PROVIDE SPRINKLER HEAD CAGES AT ALL ELECTRIC AND MECHANICAL EQUIPMENT ROOMS. 13. COORDINATE ANY REQUIRED SHUTDOWN OF SERVICES OR EQUIPMENT WITH OWNER'S REPRESENTATIVE.
0.1
4.5
5.5
6.5
7.5
8.5
10
10.9
11
A.6
B
FP 4" FROM 4TH FLOOR 2
C C.1
SPRINKLER ENTIRE AREA TO .20/2500 SQ. FT. +250 GPM HOSE
3 1
C.9
5
D
STAIR SW4-4
CP-11243
ELEVATOR #2 EP2
4
ARCH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
J. Schwartz
E
Q.M. Review:
D. DiCiuccio
Drawing Scale:
As indicated
Issue Date:
E.4
05-06-2013 10-23-2013 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP#2 - 99% Owner Review Bid Release #2 - Bids
12204-1000
Penthouse Plan - Fire Protection
1/5/2014 9:49:00 PM
NORTH
FP.5
OF
S. Hopper
CIVIL
S. Gardner
APPR.
R. Cuperus
Drawn By:
B. Moore
Approved:
D. DiCiuccio
Date:
SYSTEMS SHALL BE DESIGNED TO PROVIDE A DENSITY/AREA OF COVERAGE AS FOLLOWS: A. OFFICES - .10 GPM OVER THE MOST REMOTE 1500 SQ FT. W/250 GPM HOSE ALLOWANCE. B. LABS & MECHANICAL ROOMS - .20 GPM OVER THE MOST REMOTE 2500 SQ. FT. W/ 250 GPM FOR HOSE ALLOWANCE.
ABBREVIATIONS
A
A AC ACU AF AFF AHU AIC ALT AP ARCH AS AT ATS AV AWG AMPERES ALTERNATING CIRCUIT AIR CONDITIONING UNIT AMPERE FRAME ABOVE FINISHED FLOOR AIR HANDLING UNIT AMPERES INTERRUPTING CAPACITY ALTERNATE AMPERE PLUG ARCHITECT / ARCHITECTURAL AMPERE SENSOR AMPERE TRIP AUTOMATIC TRANSFER SWITCH AUDIO / VIDEO AMERICAN WIRE GAUGE
G
GA GFI GFCI GRD GYP BD GAGE / GAUGE GROUND FAULT INTERRUPTER GROUND FAULT CIRCUIT INTERRUPTER GROUND GYPSUM BOARD
M
MAX MCB MCC MDF MECH MH MIN MISC MLO MOD MTD MTG MAXIMUM MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MAIN DISTRIBUTION FRAME MECHANICAL MANHOLE MINIMUM MISCELLANEOUS MAIN LUGS ONLY MODULATOR MOUNTED MOUNTING
R
R R-NET RAF RCP REQD RF RGS RMS RP RPSS RELOCATE OR RELOCATED ITEM RESIDENTIAL CABLE NETWORK RETURN AIR FAN RECEPTACLE CONTROL PANEL REQUIRED RADIO FREQUENCY RIGID GALVANIZED STEEL ROOT MEAN SQUARE RECEPTACLE PANEL RECEPTACLE PANEL WITH INTEGRAL SURGE SUPPRESSION
U
UH UL UON UPS UV UNIT HEATER UNDERWRITERS LABORATORIES INC! UNLESS OTHERWISE NOTED UNINTERRUPTIBLE POWER SUPPLY UNIT VENTILATOR
H
HH HID HOA HP HTR HV HVAC HANDHOLE HIGH INTENSITY DISCHARGE HAND-OFF-AUTO HORSEPOWER HEATER HEATING AND VENTILATION UNIT HEATING' VENTILATION ( AIR CONDITIONING
V
VCR VFC VIF VP VTS VIDEO CASSETTE RECORDER VARIABLE FREQUENCY CONTROLLER VERIFY IN FIELD VAPOR PROOF VIDEO TAPE STORAGE
E
EA EC EDH EF ELEC ELEV EM EMCS EMT EP EPT EQUIP ET EUH EWC EWH EXIST EACH ELECTRICAL CONTRACTOR ELECTRIC DUCT HEATER EXHAUST FAN ELECTRICAL ELEVATOR EMERGENCY ENERGY MONITORING AND CONTROL SYSTEM ELECTRIC METALLIC TUBING ELECTRIC PNEUMATIC SWITCH ELECTRIC POWER TRANSDUCER EQUIPMENT ETHERNET ELECTRIC UNIT HEATER ELECTRIC WATER COOLER ELECTRIC WATER HEATER EXISTING
S
SAF SD SF SPECS SPKR SS STD SUB SW SWGR SUPPLY AIR FAN SMOKE DETECTOR SQUARE FEET SPECIFICATIONS SPEAKER SURGE SUPPRESSION STANDARD SUBSTATION SWITCH SWITCHGEAR
N
NC NF NIC NL NO NTS NORMALLY CLOSED NON-FUSED NOT IN CONTRACT NIGHT LIGHT NORMALLY OPEN NOT TO SCALE
B
BLDG BOT BSMT BUILDING BOTTOM LOWER LEVEL
W
WAN WAP WG WP WIDE AREA NETWORK WIRELESS ACCESS POINT WIRE GUARD WEATHERPROOF
I
IAC IN ITS INTERLOCKED ARMORED CABLE INCH / INCHES INTEGRATED TECHNOLOGY SYSTEMS
C
CAB CB CC CCP CCTV CD CHBD CKT CLG COMP CPU CP CT CUH CABINET CIRCUIT BREAKER CARD CATALOG CLASSROOM CONTROL PANEL CLOSED CIRCUIT TELEVISION CANDELA CHALKBOARD CIRCUIT CEILING COMPUTER CENTRAL PROCESSING UNIT CONTROL PANEL CABLE TRAY CABINET UNIT HEATER
J
JB JC JUNCTION BOX JANITOR CLOSET
O
OC OFE OS ON CENTER OWNER FURNISHED EQUIPMENT OCCUPANCY SENSOR
X
XP EXPLOSION PROOF
T
TC TEL TELCOM TERM TKBD TTB TTC TV TVSS TYP TIME CLOCK TELEPHONE TELCOMMUNICATION TERMINAL TACKBOARD TELEPHONE TERMINAL BACKBOARD TELEPHONE TERMINAL CABINET TELEVISION TRANSIENT VOLTAGE SURGE SUPPRESSOR TYPICAL
M+,3R 4X X C OR C C # $ % PH * NEMA 3R ENCLOSURE NEMA 4X ENCLOSURE ANGLE BY CENTERLINE CHANNEL DEGREE / DEGREES FOOT / FEET INCH / INCHES NUMBER PHASE PERCENT'PERCENTAGE
K
KVA KW KWH KILOVOLT AMPERE KILOWATT KILOWATT HOUR
P
PA PB PC PE PH PL POS PP PT PTD PVC PUBIC ADDRESS PULL BOX PHOTOCELL PNEUMATIC ELECTRIC SWITCH PHASE PILOT LIGHT POINT OF SALES POWER PANELBOARD POKE THROUGH POWER TRANSFER DEVICE POLYVINYL CHLORIDE
F
FA FAAP FACP FCU FLA FLR FT FU FVNR FIRE ALARM FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM CONTROL PANEL FAN COIL UNIT FULL LOAD AMPS FLOOR FOOT / FEET FUSE FULL VOLTAGE NON REVERSING
L
LAN LCP LP LRA LTG LOCAL AREA NETWORK LIGHTING CONTROL PANEL LIGHTING PANEL LOCKED ROTOR AMPS LIGHTING
SYMBOLS
XX
LIGHTING FIXTURE RECESSED OR SURFACE MOUNTED' LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE RECESSED OR SURFACE MOUNTED ON NIGHT LIGHT OR EMERGENCY CIRCUIT LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE SUSPENDED MOUNTED' LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE SUSPENDED MOUNTED ON NIGHT LIGHT OR EMERGENCY CIRCUIT LETTERS INDICATE TYPE 0TYP1 STRIP LIGHTING FIXTURE LETTERS INDICATE TYPE 0TYP1 STRIP LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE - RECESSED WALL WASH LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE - RECESSED OR PENDANT MTD LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE - RECESSED OR PENDANT MTD ON NIGHT LIGHT OR EMERGENCY CIRCUIT LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE - SURFACE MOUNTED LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE - SURFACE MOUNTED ON NIGHT LIGHT OR EMERGENCY CIRCUIT LETTERS INDICATE TYPE 0TYP1
L
K D L
KEY OPERATED SWITCH DIMMER SWITCH LIGHTING OCCUPANCY SENSOR WITH INTEGRAL ON/OFF SWITCH - WALL MOUNTED LIGHTING OCCUPANCY SENSOR WITH INTEGRAL DUAL LEVEL ON/OFF SWITCH - WALL MOUNTED SWITCH WITH PILOT LIGHT SWITCH WITH TIMER
/
J J
JUNCTION BOX - CEILING MOUNTED JUNCTION BOX - WALL MOUNTED PUSHBUTTON STATION
E
S S M M A V B
CEILING MOUNTED SPEAKER CLUSTER WALL MOUNTED SPEAKER MICROPHONE OUTLET - CEILING MOUNTED MICROPHONE OUTLET - WALL MOUNTED AUXILIARY OUTLET - WALL MOUNTED VOLUME OUTLET - WALL MOUNTED BELL - WALL MOUNTED
N N N N N
DS E MS PS SS
DUTY STATION - NURSE CALL EMERGENCY STATION - NURSE CALL MASTER STATION - NURSE CALL POWER SUPPLY - NURSE CALL STAFF STATION - NURSE CALL DOME LIGHT WALL MOUNTED - NURSE CALL DOME LIGHT CEILING MOUNTED - NURSE CALL DOME LIGHT WITH CODE BLUE WALL MOUNTED - NURSE CALL COMMUNICATIONS OUTLET - WALL MOUNTED LETTER INDICATES QUANTITY OF DATA AND TELEPHONE CABLES TELEVISION OUTLET - WALL MOUNTED LETTER INDICATES QUANTITY OF DATA AND COAX CABLES TELEPHONE OUTLET - WALL MOUNTED
KIRK KEY INTERLOCK CIRCUIT BREAKER DISCONNECT SWITCH FUSE TRANSFORMER TRANSFER SWITCH
OLS
E2! E2!" E2!3 E"!2 E"! E"!" E"!3 E"!4 E"!6 E3! E3!" E3!3 E3!4 E3!6 E4! E4!" E4!3 E4!4 E4!6 E6! E6!" E6!3 E6!4 E6!6 E6!5 E6!3 E6!) E6!4 E5! E5!" E5!3 E5!4 E3! E3!" E3!3
E=<-:9+-.= R<8<9<7-< I78B9C.:+B7 L+>@:+7> F+D:;9< S-@<?;=< S+:< P=.7 S:<.C T;77<= F=BB9 P=.7 - L+>@:+7> F+9,: F=BB9 P=.7 - L+>@:+7> S<-B7? F=BB9 P=.7 - L+>@:+7> T@+9? F=BB9 P=.7 - L+>@:+7> FB;9:@ F=BB9 P=.7 - L+>@:+7> P<7:@B;,< P=.7 - L+>@:+7> F+9,: F=BB9 P=.7 - PBE<9 S<-B7? F=BB9 P=.7 - PBE<9 T@+9? F=BB9 P=.7 - PBE<9 FB;9:@ F=BB9 P=.7 - PBE<9 P<7:@B;,< P=.7 - PBE<9 F+9,: F=BB9 P=.7 - A;D+=+.9F SF,:<C, S<-B7? F=BB9 P=.7 - A;D+=+.9F SF,:<C, T@+9? F=BB9 P=.7 - A;D+=+.9F SF,:<C, FB;9:@ F=BB9 P=.7 - A;D+=+.9F SF,:<C, P<7:@B;,< P=.7 - A;D+=+.9F SF,:<C, O7< L+7< D+.>9.C - S;/,:.:+B7 D+,:9+/;:+B7 O7< L+7< D+.>9.C - 4)2/"33 VB=: D+,:9+/;:+B7 O7< L+7< D+.>9.C - "2)/ "2 VB=: D+,:9+/;:+B7 O7< L+7< D+.>9.C - EC<9><7-F PBE<9 D+,:9+/;:+B7 F+9< A=.9C SF,:<C R+,<9 D+.>9C R+,<9 D+.>9.C, L+>@:+7> CB7:9B= R+,<9 D+.>9.C SCBG< CB7:9B= R+,<9 D+.>9.C, SCBG< CB7:9B= P.7<= P.7<=/B.9? S-@<?;=<, P.7<=/B.9? S-@<?;=<, P.7<=/B.9? S-@<?;=<, P.7<=/B.9? S-@<?;=<, D<:.+=, D<:.+=, S+:< D<:.+=,
XX'NL/EM
L"
PUSHBUTTON STATION - EMERGENCY POWER SHUTDOWN INTERCOM CALL BUTTON INTERCOM CALL BUTTON WITH PRIVACY
C
XX
XX'NL/EM
. XX
IP
CHIME - WALL MOUNTED HORN SPEAKER - WALL MOUNTED HORN SPEAKER - CEILING MOUNTED
S CR
3.
HORIZONTALLY MOUNTED MULTI-OUTLET RACEWAY HORIZONTALLY MOUNTED MULTI-OUTLET RACEWAY WITH VERTICAL FEED VERTICALLY MOUNTED MULTI-OUTLET RACEWAY
H H
XX'NL/EM
LIGHTING OCCUPANCY SENSOR - CEILING MOUNTED LIGHTING OCCUPANCY SENSOR - WALL MOUNTED LIGHTING CONTACTOR TIME SWITCH LIGHTING CONTROL PANEL PHOTOELECTRIC SWITCH - CEILING MOUNTED
CARD READER - SECURITY SYSTEM DOOR CONTACT - SECURITY SYSTEM KEY SWITCH - SECURITY SYSTEM MOTION DETECTOR - SECURITY SYSTEM CLOSED CIRCUIT VIDEO CAMERA - SECURITY SYSTEM FIRE ALARM PULL STATION AUDIO/VISUAL FIRE ALARM INDICATING DEVICE - WALL MOUNTED AUDIO/VISUAL FIRE ALARM INDICATING DEVICE - CEILING MOUNTED VISUAL FIRE ALARM INDICATING DEVICE - WALL MOUNTED VISUAL FIRE ALARM INDICATING DEVICE - CEILING MOUNTED AUDIO FIRE ALARM INDICATING DEVICE - WALL MOUNTED AUDIO FIRE ALARM INDICATING DEVICE - CEILING MOUNTED VISUAL EMERGENCY MASS NOTIFICATION INDICATING DEVICE - WALL MOUNTED VISUAL EMERGENCY MASS NOTIFICATION INDICATING DEVICE - CEILING MOUNTED AREA SMOKE DETECTOR - WALL MOUNTED AREA SMOKE DETECTOR - CEILING MOUNTED TEMPERATURE DETECTOR DUCT SMOKE DETECTOR BEAM SMOKE DETECTOR - TRANSMITTER BEAM SMOKE DETECTOR - RECEIVER MAGNETIC DOOR HOLDER/RELEASE WATER FLOW SWITCH TAMPER SWITCH FIRE FIGHTER TELEPHONE JACK FIRE ALARM MONITOR MODULE FIRE ALARM CONTROL PANEL
M A
S C
TV A
XXXNG GFI
INDICATES WIRE SIZE AND CONDUIT SIZE GROUND FAULT PROTECTION DRAWOUT CIRCUIT BREAKER
BUS DUCT EQUIPMENT MOUNTING BACKBOARD "2)/ "2V PANELBOARD 4)2/"33V PANELBOARD
XX
OR
XX
S K S MD
LC TS
OR
XX XX
LCP PC
CCTV
OR
XX'NL/EM XX'NL/EM
PHOTOELECTRIC SWITCH - WALL MOUNTED SINGLE PHASE MOTOR EMERGENCY POWER TRANSFER DEVICE SINGLE RECEPTACLE OUTLET DUPLEX RECEPTACLE OUTLET THREE PHASE MOTOR MAGNETIC MOTOR STARTER DUPLEX RECEPTACLE OUTLET FLUSH MOUNTED IN CEILING
A 32/32A
C/A
COMMUNICATIONS OUTLET - CEILING MOUNTED LETTER INDICATES QUANTITY OF DATA AND TELEPHONE CABLES COMMUNICATIONS OUTLET - FLOOR MOUNTED
ENGINE GENERATOR
PTD
AV
XX
F C
COMBINATION MAGNETIC MOTOR STARTER - SWITCH SIZE / FUSE SIZE DISCONNECT SWITCH-SWITCH SIZE/NONFUSIBLE
EXOTHERMIC WELD OR BRAZED CONNECTION GROUND CABLE OR BUS CONDUIT CONCEALED IN WALLS OR IN CEILING SPACE OR EXPOSED IN UNFINISHED AREAS CONDUIT IN OR BELOW FLOOR SLAB OR BELOW GRADE RACEWAY TURNED UP RACEWAY TURNED DOWN
XX
TRACK LIGHTING WITH INDICATED NUMBER OF FIXTURES - CEILING MOUNTED LETTERS INDICATE TYPE 0TYP1 TRACK LIGHTING WITH INDICATED NUMBER OF FIXTURES - WALL MOUNTED LETTERS INDICATE TYPE 0TYP1 OR
XX XX
DUPLEX RECEPTACLE OUTLET FLOOR MOUNTED LETTERS INDICATE TYPE 0TYP1 DUPLEX RECEPTACLE OUTLET MOUNTED ABOVE COUNTER
32/NF 32/32A
DISCONNECT SWITCH-FUSIBLE -SWITCH SIZE/FUSE SIZE DISCONNECT SWITCH -CIRCUIT BREAKER SIZE EMERGENCY POWER TRANSFER DEVICE MAGNETIC CONTACTOR
XX
GFI
DUPLEX RECEPTACLE OUTLET WITH INTEGRAL GROUND FAULT PROTECTION DUPLEX RECEPTACLE OUTLET CONNECTED TO UPSTREAM GROUND FAULT PROTECTION DEVICE DUPLEX RECEPTACLE OUTLET WITH INTEGRAL SURGE SUPPRESSION DUPLEX RECEPTACLE OUTLET CONNECTED TO UPSTREAM SURGE SUPPRESSION DEVICE DUPLEX RECEPTACLE OUTLET SPLIT WIRED
CB
32A
LIGHTING FIXTURE - WALL MOUNTED LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE - WALL MOUNTED ON NIGHT LIGHT OR EMERGENCY CIRCUIT LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE - UNDERCABINET MOUNTED LETTERS INDICATE TYPE 0TYP1 LIGHTING FIXTURE - UNDERCABINET MOUNTED ON NIGHT LIGHT OR EMERGENCY CIRCUIT LETTERS INDICATE TYPE 0TYP1 EXIT LIGHTING FIXTURE SINGLE OR DOUBLE FACE WITH DIRECTIONAL ARROWS - CEILING OR PENDANT MOUNTED' LETTERS INDICATE TYPE 0TYP1 EXIT LIGHTING FIXTURE WITH DIRECTIONAL ARROWS - WALL MOUNTED LETTERS INDICATE TYPE 0TYP1 SELF-CONTAINED EMERGENCY LIGHTING UNIT - CEILING MOUNTED LETTERS INDICATE TYPE 0TYP1 SELF-CONTAINED EMERGENCY LIGHTING UNIT - WALL MOUNTED LETTERS INDICATE TYPE 0TYP1
GFI
VFC
F F F F
SD SD TD DD BT BR DR WF TS
OR
XX'NL/EM XX'NL/EM
SS
MANUAL MOTOR STARTER PACKAGED EQUIPMENT WITH INTEGRALLY MOUNTED PREWIRED CONTROL PANEL FURNISHED AS INTEGRAL PART OF EQUIPMENT
VOLT METER WATT METER METER POWER FACTOR METER KILOWATT HOUR METER KILOWATT METER AMPERE SWITCH VOLT SWITCH P HP C UNDERFLOOR DUCT - POWER UNDERFLOOR HEADER DUCT - POWER UNDERFLOOR DUCT - COMMUNICATIONS UNDERFLOOR HEADER DUCT - COMMUNICATIONS
SS
XX
F F F
XX'NL/EM
IG
T-
F F F M
PF
KWH
QUAD RECEPTACLE OUTLET MOUNTED ABOVE COUNTER QUAD RECEPTACLE OUTLET WITH ONE 0 1 INTEGRAL SURGE SUPPRESSION TYPE RECEPTACLE AND ONE 0 1 SURGE SUPPRESSION PROTECTED RECEPTACLE SPECIAL OUTLET - SIZES AND TYPES DENOTED ON DRAWINGS DC POWER SYSTEM - SERVICE OUTLET DC POWER SYSTEM - POWER SUPPLY POWER/COMMUNICATIONS POLE SPECIAL POWER CONNECTION
CD A PT S
HC
LIGHTNING PROTECTION AIR TERMINAL CEILING MOUNTED FAN SINGLE FACED CLOCK - CEILING MOUNTED DOUBLE FACED CLOCK - CEILING MOUNTED SINGLE FACED CLOCK - WALL MOUNTED DOUBLE FACED CLOCK - WALL MOUNTED COMBINATION SPEAKER/CLOCK PANEL - WALL MOUNTED COMBINATION SPEAKER/CLOCK PANEL -CEILING MOUNTED CEILING MOUNTED SPEAKER
KW
AS
SS SS
VS
FIRE SUPRESSION SYSTEM CONTROL PANEL FIRE ALARM REMOTE ANNUNCIATOR PANEL
XX
XX
DC DC/PS
N N N N
DOUBLE BED STATION - NURSE CALL BATHROOM STATION - NURSE CALL BATHROOM STATION PULL CORD - NURSE CALL CODE BLUE PUSHBUTTON - NURSE CALL THIS PROJECT MAY NOT UTILIZE ALL THE SYMBOLS' MATERIALS' ABBREVIATIONS AND STANDARDS INFORMATION SHOWN ON THIS SHEET
XX
XX
POLE MOUNTED LIGHTING FIXTURE QUANTITY OF LUMINARIES AS INDICATED LETTERS INDICATE TYPE 0TYP1 SITE LIGHTING FIXTURES - ADJUSTABLE FLOODS' LETTERS INDICATE TYPE 0TYP1 SINGLE POLE SWITCH
CB
XX
XX
" 3 4
CP")!/.
"43
(&!/.
J. Kasdorf
& &!.
). 1ra2ee
SYMBOL LEGEND
DETAIL SYMBOL DETAIL IDENTIFICATION " E"! ELEVATION SYMBOL
MOUNTING HEIGHTS
LINE VOLTAGE SWITCH FIRE ALARM PULL STATION LOW VOLTAGE SWITCH VOLUME CONTROL CLOCKS EXIT LIGHTS TELEVISION OUTLET FOR TV MONITOR - WALL MOUNTED BATTERY OPERATED EGRESS LIGHTING COMMUNICATIONS OUTLET TELEPHONE OUTLET- WALL MOUNTED CARD ACCESS SYSTEM CARD READER MICROPHONE OUTLET AUDIO VISUAL FIRE ALARM INDICATING DEVICE QUAD RECEPTACLE OUTLET FOR TV MONITOR VISUAL FIRE ALARM INDICATING DEVICE INTERCOM CALL BUTTON SPEAKERS RECEPTACLE OUTLET AUDIO FIRE ALARM INDICATING DEVICE ELEVATION NUMBER
4
.".
D. 3ilber
Project "dministrator# Project Designer#
J. Jo$nson
Project "rc$%&ng#
5. /ac<ett
'.(. )e*ie+#
DETAIL
DETAIL SCALE
3
TV
TV A
). ,racci
Dra+ing Scale#
E4!
No Scale
W
3# - #)$ AFF
5# - 2$ AFF
DRAWING WHERE DETAIL IS REFERENCED OR CUT PLAN OR DETAIL ENLARGEMENT PLAN OR DETAIL IDENTIFICATION
3# - 5$ AFF
"
4# - 2$ AFF
# - 5$ AFF
4# - 2$ AFF
Issue Date#
I
Issued for#
D<,+>7 D<A<=BHC<7: B+? P.-G %" - QM R<A+<E BP %" - 44* OE7<9 R<A+<E B+? R<=<.,< %" - B+?,
CR
MOTOR STARTERS
E4!
DISCONNECT SWITCHES
"
EXISTING
MOUNTING HEIGHT NOTES& ! MOUNTING HEIGHTS ARE TYPICAL UNLESS OTHERWISE NOTED ON DRAWINGS "! FOR CEILING HEIGHTS BELOW )#-4$ REFER TO DRAWINGS FOR CLOCKS' SPEAKERS' EXIT LIGHTS AND EGRESS LIGHTS MOUNTING HEIGHTS!
NEW ROOM NAME AND NUMBER ROOM NAME A 2 ROOM FLOOR BUILDING OR UNIT 0IF ANY1
GFI
44$ AFF
44$ AFF
3)$ AFF
6# - 2$ AFF
5# - 5$ AFF
35$ AFF
32$ AFF
TO TOP
TO TOP
GENERAL NOTES& ! ALL WORK AND EQUIPMENT SHALL CONFORM TO NEC! THE MEANS AND METHODS USED BY THIS CONTRACTOR SHALL CONFORM TO NEC SECTION 2-3 0. AND /1! "! FIRE ALARM SHOP DRAWINGS SHALL BE SUBMITTED TO THE FIRE MARSHALL FOR APPROVAL PRIOR TO SUBMITTING FOR ENGINEER APPROVAL!
#$$%&-#%%%
E ec!rica Re(erence In(or)a!ion
NORTH
E%'#
OF
COMMUNICATIONS OUTLET - WALL MOUNTED ABOVE COUNTER' LETTER INDICATES QUANTITY OF DATA AND TELEPHONE CABLES
6"
S. 4ardner
"PP).
S. Sc$ia..acasse
Dra+n ,-#
S. Sc$ia..acasse
"..ro*ed#
). ,racci
Date#
TYPE FA
DESCRIPTION 36 LONG X 2.75W x 3" DEEP (NOMINAL) WALL SCONCE FLUORESCENT LIGHTING FIXTURE WITH: FROSTED ACRYLIC LENS; SILVER FINISH; ONE (1) 1-LAMP BALLAST; 277 VOLT OPERATION. 2 X 4, TWO (2) LAMP LAY-IN, FLUORESCENT FIXTURE WITH: ACRYLIC PRISMATIC PATTERN 12 LENS, WITH AN OVERALL THICKNESS OF 0.125 INCH (MINIMUM); LENS RETAINING CLIPS (2 MINIMUM, 1 PER END); FLUSH STEEL WHITE DOOR FRAME WITH MITERED CORNERS AND PAINTED BLACK MECHANICAL LIGHT SEAL; ROTARY CAM DOOR LATCHES; ROLLED EDGE; DIE-FORMED AND EMBOSSED CODE GAUGE STEEL HOUSING; T-BAR SAFETY CLIPS; INTEGRALLY FUSED; ONE (1) 2-LAMP INSTANT START BALLAST; 277 VOLT OPERATION.
MANUFACTURER BARTCO CAT. NO. IST8Q-25W-U-IS-F-SM-SL BIRCHWOOD LTG. CAT. NO. HA1225RSM-T8-3-SW-FC-277-EB PHILIPS ALKCO TABLEAU CAT. NO. TAB125-SYM-277-AL COLUMBIA CAT. NO. ST824-232G-FSA12.125-EP277-GLR-PAF-SSL DAYBRITE CAT. NO. 2SPG-232-FS-21-277-1/2-EB10I-GLR LITHONIA CAT. NO. 2SP8G-232-A12.125M-277-GEB10IS-GLR-LATC LSI CAT. NO. L-A125-2-32-SD-SSO10-F-277 METALUX CAT. NO. 2GC8-232-A125-277-GL-E81-PAF-EQ-CLIP
LAMPS G.E. CAT. NO. F25T8/SPX41/ECO OR EQUAL BY OSRAM SYLVANIA OR PHILIPS G.E. CAT. NO. (2) F32T8/SPX41/ECO OR EQUAL BY OSRAM SYLVANIA OR PHILIPS
INPUT WATTS 23
TYPE LH3
DESCRIPTION SAME AS FIXTURE TYPE LH1 EXCEPT 19 x 9, L SHAPED 4 (NOMINAL) SURFACE MOUNTED LINEAR LED FIXTURE; 277 VOLT OPERATION.
MANUFACTURER AXIS LIGHTING CAT. NO. BBSLED-B1-500-SO-40-SO-S#-AP-277-D-1-SC-F (27.2 WATTS PER 4 FOOT, 105.4 WATTS) FINELITE CAT. NO. HP-4 SM-19 x 95-SO-4000K-277V-SC-SM (18 WATTS PER 4 FOOT) (WATTS)
FB
54 LH4 8 x 30 x 8, U SHAPED 4 (NOMINAL) SURFACE MOUNTED LINEAR LED FIXTURE WITH; 361 LUMENS PER FOOT MIN.; EXTRUDED ALUMINUM BODY WITH INTERNAL JOINING SYSTEM TO ENSURE CONTINUOUS UNIFORM APPEARANCE; HIGH REFLECTANCE MATTE WHITE REFLECTOR; FROST WHITE SNAP IN LENS; ILLUMINATED 90 DEGREE CORNERS; ALUMINUM PAINTED FINISH; INTEGRALLY FUSED; U.L. LISTED; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION.
AXIS LIGHTING CAT. NO. BBSLED-B1-500-SO-40-SO-S#-AP-277-D-1-SC-F W/LIT 4000K LED FURNISHED WITH CORNERS (5.46 WATTS PER FOOT) LIGHT FIXTURE FINELITE CAT. NO. HP-4 SM-8x30x8-SO-4000K-277V-SC-SM WITH 90 DEGREE LIT CORNERS (4.5 WATTS PER FOOT) PINNACLE CAT. NO. EX6A-N-40-XX-S-277-1D-CC-(2) BX6CH (6.1 WATTS PER FOOT) 4000K LED FURNISHED WITH LIGHT FIXTURE
253
FC
10.23" x 51.18" DECORATIVE GLASS LIGHTING FIXTURE WITH: HAND-BLOWN STUDIO DESIGN ITALIA 'SOAP MAX SOF' 277 VOLT GLASS DIFFUSER IN CLEAR PYREX GLASS; ADJUSTABLE SUSPENSION LUMINAIRE; DIFFUSER FROSTED ON STEM TO COVER FLUORESCENT LAMP; MOUNTS TO STANDARD JUNCTION BOX; ONE (1) 1-LAMP BALLAST; 277 VOLT OPERATION. 32 WATT COMPACT FLUORESCENT SMALL WALL PACK FIXTURE WITH: CAST ALUMINUM BACKPLATE; GASKETING BETWEEN BACKPLATE AND FRONT COVER; BRONZE FINISH; MEDIUM THROW DISTRIBUTION; INTEGRALLY FUSED; UL LISTED FOR WET LOCATIONS; 277 VOLT OPERATION. DAYBRITE CAT. NO. WPG-32C-C-277 LITHONIA CAT. NO. TWS-32TRT-MVOLT-GMF-DDB HUBBEL CAT. NO. NRG-304B-32W-MVOLT LSI CAT. NO. DMWP-32-CFL-PC-277V-BRZ TERON LIGHTING CAT. NO. CA-CAC132X-277E-BZ-41K-F
58
LH5
FD
G. E. CAT. NO. F32TBX/841/A/ECO OR EQUAL BY OSRAM SYLVANIA OR PHILIPS G.E. CAT. NO. F28W/T5/841/ECO OR EQUAL BY OSRAM SYLVANIA OR PHILIPS
36 LI
SAME AS FIXTURE TYPE LH4 EXCEPT 19 x 30 x 19, U SHAPED 4 (NOMINAL) AXIS LIGHTING CAT. NO. BBSLED-B1-500-SO-40-SO-S#-AP-277-D-1-SC-F W/LIT SURFACE MOUNTED LINEAR LED FIXTURE; 277 VOLT OPERATION. CORNERS (5.46 WATTS PER FOOT) FINELITE CAT. NO. HP-4 SM-19x30x19-SO-4000K-277V-SC-SM WITH 90 DEGREE LIT CORNERS (4.5 WATTS PER FOOT) PINNACLE CAT. NO. EX6A-N-40-XX-S-277-1D-CC-(2) BX6CH (6.1 WATTS PER FOOT) MULTIPLE LENGTH FIXTURES FROM 3-6 TO 10-0 LONG, 5 WIDE (NOMINAL) VERTICAL WALL SLOT, LED LIGHTING FIXTURE WITH: APPROX. 400 LUMENS PER FOOT; PRECISION CUT EXTRUDED ALUMINUM BODY; HIGH REFLECTANCE STEEL MATTE WHITE REFLECTOR; FROST WHITE SNAP IN LENS; CUSTOM FINISH; INTEGRALLY FUSED; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION. AXIS LIGHTING CAT. NO. B6RVLED-B2-400-40-SO-FL-S#-W-277-D-1-XX-F (4.2 WATTS PER FOOT) FINELITE CAT. NO. HP-4 R-XX-SO-4000K-277V-SC-C2 (4.5 WATTS PER FOOT) (4 WIDE) PINNACLE CAT. NO. EV6-C-40-XX-G9G-277-1C-1D-W (6.1 WATTS PER FOOT)
371
FE
3 1/2 NOMINAL SQUARE PENDANT HUNG FLUORESCENT LINEAR FIXTURE BIRCHWOOD LIGHTING CAT. NO. ERI.325-SE-TRI-4X16-SC-FW-277-EB-CSS WITH: SHARP CORNER POLISHED EXTRUDED ALUMINUM HOUSING; 36 DESIGNPLAN MESSINA RECTANGULAR CAT. NO. 4/16-14280SUS-277V AIRCRAFT CABLE SUSPENSION; 4 X 16 RECTANGLE PATTERN WITH SWIVEL SELUX NEOS CAT. NO. NEOS-F28T5-OD-C-REC4-16-SB-277 CONNECTORS AT CORNERS AND SHORT BAR CONNECTORS IN BETWEEN; ONE LAMP IN CROSS SECTION; SPECULAR ALUMINUM REFLECTOR; OPAL LENS ON TOP, SIDES AND BOTTOM; SILVER TRIM FINISH; INTEGRALLY FUSED; U.L. LISTED; FIVE (5) 2-LAMP BALLAST; 277 VOLT OPERATION. 4-0 LONG, ONE (1) LAMP SURFACE/WALL MOUNT LENSED AND GASKETED INDUSTRIAL FLUORESCENT FIXTURE WITH: CLEAR LINEAR RIBBED UV STABILIZED POLYCARBONATE SHATTER-RESISTANT LENS, FIBERGLASS HOUSING, POURED-IN GASKETING, STAINLESS STEEL SNAP IN LATCHES; INTEGRALLY FUSED; ONE (1) 1-LAMP BALLAST; 277 VOLT OPERATION. 4-0, LONG, TWO (2) LAMP, CHAIN MOUNTED, INDUSTRIAL FLUORESCENT FIXTURE WITH: BAKED HIGH GLOSS WHITE ENAMEL REFLECTOR APERTURED FOR 20% UPLIGHT (MAX), PAINT AFTER FABRICATION, PRE-WIRED 6-0 LONG 3/C #18 SO CORD AND NEMA L7-15P TWIST LOCK CAP, WIREGUARD, END PLATES, CHAIN HANGERS, INTEGRALLY FUSED; ONE (1) 2-LAMP BALLAST; 277 VOLT OPERATION. 6 (NOMINAL) ROUND APERTURE, RECESSED 1300 LUMEN LED DOWNLIGHT WITH: COMFORT CLEAR REFLECTOR AND WHITE PAINTED TRIM FLANGE; 6 MAXIMUM HOUSING DEPTH; 0-10V DIMMABLE ELECTRONIC POWER SUPPLY WITH OVERLOAD AND SHORT CIRCUIT PROTECTION; REMOTE PHOSPHOR TECHNOLOGY, REGRESSED LENS; LEDS AND POWER SUPPLY SERVICEABLE FROM BELOW; UL LISTED SUITABLE FOR WET LOCATIONS; 277 VOLT OPERATION. 6 (NOMINAL) ROUND APERTURE, RECESSED 2000 LUMEN LED DOWNLIGHT WITH: COMFORT CLEAR REFLECTOR AND TRIM FLANGE FINISH; 6 MAXIMUM HOUSING DEPTH; 0-10V DIMMABLE ELECTRONIC POWER SUPPLY WITH OVERLOAD AND SHORT CIRCUIT PROTECTION; REMOTE PHOSPHOR TECHNOLOGY, REGRESSED LENS; LEDS AND POWER SUPPLY SERVICEABLE FROM BELOW; UL LISTED SUITABLE FOR WET LOCATIONS; 277 VOLT OPERATION. 4-1/2 (NOMINAL) ROUND APERTURE, RECESSED 1100 LUMEN LED DOWNLIGHT WITH: COMFORT CLEAR REFLECTOR AND TRIM FLANGE FINISH; 6 MAXIMUM HOUSING DEPTH; 0-10V DIMMABLE ELECTRONIC POWER SUPPLY WITH OVERLOAD AND SHORT CIRCUIT PROTECTION; REMOTE PHOSPHOR TECHNOLOGY; REGRESSED LENS; LEDS AND POWER SUPPLY SERVICEABLE FROM BELOW; UL LISTED FOR WET LOCATIONS; 277 VOLT OPERATION. 4-0 LONG, 4 (NOMINAL) RECESSED SLOT, LED LIGHTING FIXTURE WITH: 500 LUMENS PER FOOT MIN.; PRECISION CUT EXTRUDED ALUMINUM BODY; HIGH REFLECTANCE STEEL MATTE WHITE REFLECTOR; FROST WHITE SNAP IN LENS; INTEGRALLY FUSED; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION. SAME AS FIXTURE TYPE LB4 EXCEPT WITH 90 DEGREE OUTER CORNER AND 4 FOOT VERTICAL WALL SLOT MOUNTED IN GYP WALL; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION. 5-0 LONG, 6 SLOT LAY-IN, LED LIGHTING FIXTURE WITH: PRECISION CUT EXTRUDED ALUMINUM BODY; STEEL HIGH REFLECTANCE MATTE WHITE REFLECTOR; FROST WHITE SNAP IN LENS; INTEGRALLY FUSED; ; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION. SAME AS FIXTURE TYPE LB5 EXCEPT WITH 90 DEGREE OUTER CORNER AND 3 FOOT VERTICAL WALL SLOT MOUNTED IN GYP WALL; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION. CGF DESIGN INC. E804-T5-1/28-277-EBX-LR-WHT-FUS-SLA ECLIPSE LIGHTING CAT. NO. VTC-N-4C-SSL-T5-EBU-FUS LITHONIA CAT. NO. FEN4-1-28T5-BMPCL-MVOLT-GEB10PS90-GLR-LP841 THE LIGHT EDGE INC. CAT. NO. MON1-4-28-41-MV-LP-GLR-HS2 METALUX LIGHTING CAT. NO. VT1-132-PCR-277V-GL-EB8 DAYBRITE CAT. NO. 2F232PR-277-1/2 EB10I-FL-173-FL5-GLR-GSX HUBBELL CAT. NO. KL4-232-U-EPU-1PK-GLR-KLWG4-KLEC C&PTL277 KHC LITHONIA CAT. NO. AF-232-MVOLT-GEB10IS-GLR-CS11-HC36-WGAFPV-ACEP-PAF LSI INDUSTRIES CAT. NO. F23-232-SSO-F-277-1WGF232-EP23-CHS METALUX CAT. NO. DIM-N-232-277V-GL-EB8-GL-PAF-6-3/18SJT-C&P-L715P-WG/DIF-4FT-AYC-CHAIN/SE T-U (CLOSED END PLATE) FOCAL POINT CAT. NO. FL6D-13LED-L40-277-RO-T TRIM L6-RO-RL-CD-WP INDY CAT. NO. SD6-13-40-2-PF-F LIGHTOLIER CAT. NO. C6L1520-DL-40K-M-CCL-W FRAME IN KIT C6L15-N-2 SPECTRUM LIGHTING CAT. NO. SGE6LEDFD-16W-41K-E2-AR6240FD-MW-FG FOCAL POINT CAT. NO. FL6D-20LED-L40-277-RO-T TRIM L6-RO-RL-CD-WP INDY CAT. NO. SD6-20-40-2-PF-F LIGHTOLIER CAT. NO. C6L1520-DL-40K-M-CCL-W FRAME IN KIT C6L20-N-2 SPECTRUM LIGHTING CAT. NO. SGE6LEDFD-25W-41K-E2-AR6240FD-MW-FG FOCAL POINT CAT. NO. FL4D-11LED-L40-277-RO-T TRIM L4-RO-RL-CD-WP INDY CAT. NO. SD4-11-40-2-PF-F LIGHTOLIER CAT. NO. C4L10-DL-40K-CCL-P FRAME IN KIT C4L10-N-1 SPECTRUM LIGHTING CAT. NO. SGE4LEDFD-14W-41K-E2-AR424OFD-MW-FG AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-4-W-277-D-1-DS-F (20.04 W) FINELITE CAT. NO. HP-4 R-4-HO-4000K-277V-SC-SF (37 W) PINNACLE CAT. NO. EV6-C-40-4-SFS-277-1D-W (28.4 W)
31 LJ
FF
G. E. CAT. NO. F28W/T5/841/ECO OR EQUAL BY OSRAM SYLVANIA OR PHILIPS G. E. CAT. NO. (2) F32T8/SPX41/ECO OR EQUAL BY OSRAM SYLVANIA OR PHILIPS
30 LK
SAME AS FIXTURE TYPE LI EXCEPT WITH 90 DEGREE OUTER CORNER AND AXIS LIGHTING CAT. NO. B6RVLED-B2-400-40-SO-FL-S#-W-277-D-1-XX-F W/LIT 8 FIXTURE ALONG UNDERSIDE OF VERTICAL WALL; 277 VOLT OPERATION. CORNER (4.2 WATTS PER FOOT) FINELITE CAT. NO. HP-4 R-XX-SO-4000K-277V-SC-C2 WITH 90 DEGREE LIT CORNER (4.5 WATTS PER FOOT) (4 WIDE) PINNACLE CAT. NO. EV6-C-40-XX-G9G-277-1C-1D-W-BX6CH (6.1 WATTS PER FOOT) 6 (NOMINAL) ROUND APERTURE, RECESSED SURGICAL LED DOWNLIGHT WITH: ALUMINUM HOUSING; SPUN ALUMINUM REFLECTOR; ANTIMICROBIAL WHITE FINISH TRIM; 7 MAXIMUM HOUSING DEPTH; 0-10V DIMMABLE ELECTRONIC POWER SUPPLY WITH OVERLOAD AND SHORT CIRCUIT PROTECTION; ROSE CHOCOLATE INNER LENS WITH STANDARD DIFFUSING FILM; LEDS AND POWER SUPPLY SERVICEABLE FROM BELOW; UL LISTED SUITABLE FOR WET LOCATIONS; 277 VOLT OPERATION. 6 (NOMINAL) ROUND APERTURE, RECESSED LED MRI DOWNLIGHT WITH: NON-FERROUS CONSTRUCTION; ALUMINUM HOUSING; SPUN ALUMINUM REFLECTOR; WHITE MATTE TRIM FINISH; 0-10V DIMMABLE ELECTRONIC POWER SUPPLY; 120 VOLT OPERATION. 13 WATT LED, DIRECTIONAL SURFACE MOUNTED FIXTURE: SUITABLE FOR WET LOCATIONS; IP65 RATING, ONE PIECE DIE-CAST ALUMINUM HOUSING; PURE ANODIZED ALUMINUM REFLECTOR; 8 DEG. BEAM; PROVIDED WITH A 1/2 I.P.S. STAINLESS STEEL NIPPLE FOR DIRECT ATTACHMENT TO CAST BOXES OR OTHER ACCESSORIES; DIE-CAST ALUMINUM SWIVEL; 180 DEG. GLARE SHIELD; SILVER FINISH; INTEGRAL DRIVER; WIRED FOR 277 VOLT OPERATION. SURFACE MOUNTED LOW PROFILE SELF-CONTAINED EMERGENCY BATTERY UNIT WITH: TWO (2) HEADS; 22-GAUGE DIE-FORMED STEEL BODY AND BACKPLATE, HIGH IMPACT THERMOPLASTIC LIGHTING HEADS (WHITE FINISH); FULLY ADJUSTABLE SELF LOCKING HEADS; LOW VOLTAGE DISCONNECT; BROWNOUT CIRCUIT; OVERLOAD/SHORT CIRCUIT PROTECTION; PUSHBUTTON TEST SWITCH/POWER INDICATOR LIGHT; SEALED MAINTENANCE FREE 6 VOLT LEAD CALCIUM BATTERY FOR 90 MINUTES (MINIMUM) OF EMERGENCY OPERATION TO AN END VOLTAGE OF 87.5% OF NORMAL BATTERY VOLTAGE; FULLY SELF DIAGNOSTIC; AC QUICK-CONNECT PLUG; UNIVERSAL MOUNT. EXIT LIGHT SHALL BE UNIVERSAL MOUNT AS INDICATED ON DRAWING AND SHALL BE CAST ALUMINUM, BLACK HOUSING, WITH BRUSHED ALUMINUM FACE WITH 6 INCH LETTERS, GREEN LED PANEL; MULTI-VOLT; UL LISTED. KENALL CAT. NO. M2DL6VL2-30L30K-277-2FW-SL
30
FI
54
LL
EVERBRITE LIGHTING CAT. NO. MEDLUX XLS-2.0-35-120-R-WM KIRLIN CAT. NO. MRR-07381 (W/REMOTE DRIVER)
50
LA1
24
LM
13
LA2
38
EBU
SURE LITES CAT. NO. XR-3 SERIES EXITRONIX CAT. NO. RS SERIES
LA4
20 XA
LB4
28 XB UNIVERSAL (TOP, END OR BACK) MOUNTED LED EDGE-LIT EXIT LIGHTING FIXTURE WITH: EXTRUDED ALUMINUM HOUSING; BRUSHED ALUMINUM FINISH; SINGLE OR DOUBLE MIRRORED THERMO-PLASTIC FACE WITH GREEN LETTERS; DIRECTIONAL CHEVRONS WHERE INDICATED; LED LAMPS; DUAL 120/277 VOLT OPERATION.
LITHONIA CAT. NO. LES-1/2-G-120/277 TRU-GREEN SERIES SURE-LITES CX6-1/2-G LIGHTOLIER LDS-A-U-G-A LIGHTPANEL DCA-A EXITRONIX CAT. NO. 400U SERIES LITHONIA CAT. NO. LRP-1/2-GC/GMR-120/277 LIGHTOLIER CAT. NO. LG-1/2-GC-A EMERGI-LITE CAT. NO. W- LXNX-42-G-C CHLORIDE CAT. NO. CN-6-GC-A-1/2 HUBBEL DUAL-LITE CAT. NO. LE SERIES LSI CAT. NO. ELX-U-6-G-1/2C-LB-120/277 SURE-LITES ELX SERIES LITHONIA CAT. NO. TWP-LED-20C-700/40K-T3M-MVOLT-SF-TP-DBLXD
LB4C
LB5
LB5C
AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-4X4-W-277-D-1-DS-F (6.7 W/FT) 4000K LED FURNISHED WITH FINELITE CAT. NO. HP-4 R-4X4-HO-4000K-277V-SC-SF (9.25 W/FT) LIGHT FIXTURE PINNACLE CAT. NO. EV6-C-40-4X4-SFS-277-1D-W (6.1 W/FT) 4000K LED FURNISHED WITH AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-5-W-277-D-1-DS-F (25 W) LIGHT FIXTURE FINELITE CAT. NO. HP-4 R-5-HO-4000K-277V-SC-SF (46 W) PINNACLE CAT. NO. EV6-C-40-5-SFS-277-1D-W (35.5 W) 4000K LED FURNISHED WITH AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-5X3-W-277-D-1-DS-F (5.01 LIGHT FIXTURE W/FT) FINELITE CAT. NO. HP-4 R-5X3-HO-4000K-277V-SC-SF (9.25 W/FT) PINNACLE CAT. NO. EV6-C-40-5X3-SFS-277-1D-W (6.1 W/FT) AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-8-W-277-D-1-TG15-F (40 W) FINELITE CAT. NO. HP-4 R-8-HO-4000K-277V-SC-C2T (74 W) PINNACLE CAT. NO. EV6-C-40-8-G9G-277-1D-W (57 W) AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-12-W-277-D-1-TG15-F (60 W) FINELITE CAT. NO. HP-4 R-12-HO-4000K-277V-SC-C2T (111 W) PINNACLE CAT. NO. EV6-C-40-12-G9G-277-1D-W (85.2 W) AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-14-W-277-D-1-TG9-F (70 W) FINELITE CAT. NO. HP-4 R-14-HO-4000K-277V-SC-C2T (129.5 W) PINNACLE CAT. NO. EV6-C-40-14-G9G-277-1D-W (99.4 W) AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-16-W-277-D-1-TG9X-F (80 W) FINELITE CAT. NO. HP-4 R-16-HO-4000K-277V-SC-C2T (148 W) PINNACLE CAT. NO. EV6-C-40-16-G9G-277-1D-W (113.6 W) AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-18-W-277-D-1-TG9X-F (90.18 W) FINELITE CAT. NO. HP-4 R-18-HO-4000K-277V-SC-C2T (166 W) PINNACLE CAT. NO. EV6-C-40-18-G9G-277-1D-W (127.8 W) AXIS LIGHTING CAT. NO. BBRLED-B2-400-40-SO-FL-30-W-277-D-1-DS-F (3.85 W/FT) FINELITE CAT. NO. HP-4 R-30-SO-4000K-277V-SC-SF (4.5 W/FT) PINNACLE CAT. NO. EV6-C-40-30-SFS-277-1D-W (6.1 W/FT) AXIS LIGHTING CAT. NO. BBDILED-B1-450/650-40-SO-4-W-277-D-1-CA#-F (52 WATTS) FINELITE CAT. NO. HP-4 ID-4-HO-4000K-TG-277V-SC-C4 (55 WATTS) PINNACLE CAT. NO. EX4B-A-40-40-4-AC48ST-277-1D-W-TOP LENS (56.8 WATTS) 4000K LED FURNISHED WITH LIGHT FIXTURE
53 ELA 35
53 ELB
EXTERIOR, LED WALL PACK LIGHTING FIXTURE WITH; RUGGED, DIE-CAST ALUMINUM REAR HOUSING; UV-STABILIZED POLYCARBONATE FRONT HOUSING AND REFRACTOR, FULLY GASKETED; PRECISION-MOLDED POLYCARBONATE LENS; BLACK CORROSION-RESISTANT THERMOSET POWDER COAT FINISH; TYPE III MEDIUM DISTRIBUTION, INTEGRALLY FUSED; TAMPER PROOF SCREWS; UNIVERSAL 120-277V LED POWER SUPPLY WIRED FOR 277V OPERATION. EXTERIOR, ARCHITECTURAL LED WALL SCONCE LIGHTING FIXTURE WITH; RUGGED, DIE-CAST SINGLE-PIECE ALUMINUM HOUSING; DIE-CAST DOORFRAME IS FULLY GASKETED WITH ONE PIECE SOLID SILICONE GASKET; PRECISION-MOLDED ACRYLIC LENS; BLACK CORROSION-RESISTANT THERMOSET POWDER COAT FINISH; FORWARD THROW DISTRIBUTION, INTEGRALLY FUSED; UNIVERSAL 120-277V LED POWER SUPPLY WIRED FOR 277V OPERATION.
72
LB8
SAME AS FIXTURE TYPE LB4 EXCEPT 8-0 LONG LAY-N IN LIEU OF 4-0 LONG; 277 VOLT OPERATION.
57
GARDCO CAT. NO. 101L-4-55LA-NW-UNIV-NP-BPL LITHONIA CAT. NO. WST-LED-20A700/40K-SR4-MVOLT-SF-DBLXD COOPER MCGRAW-EDISON CAT. NO. IST-B02-LED-E1-BL4-BK TRACE LITE CAT. NO. TLED110EX-48-DT-TRH
47
LB12
SAME AS FIXTURE TYPE LB4 EXCEPT 12-0 LONG LAY-IN IN LIEU OF 4-0 LONG; 277 VOLT OPERATION.
85
ELC
LB14
SAME AS FIXTURE TYPE LB4 EXCEPT 14-0 LONG LAY-IN IN LIEU OF 4-0 LONG; 277 VOLT OPERATION.
99 ELD 114
AXIS LIGHTING CAT. NO. WBRVLED-B2-400-40-S-FL-6-AP-277-D-1-F (4.2 W/FT) EXTERIOR WET LOCATION 6-0 LONG, 4 WIDE VERTICAL WALL SLOT, LED LIGHTING FIXTURE WITH: APPROX. 400 LUMENS PER FOOT; PRECISION CUT VOIGT LIGHTING TIMO CAT. NO. T-307-4-SL-LED-450LM-DI-REC-6-NA-277-WL (4 W/FT) EXTRUDED ALUMINUM BODY; HIGH REFLECTANCE STEEL MATTE WHITE REFLECTOR; FROST WHITE SNAP IN LENS; CUSTOM FINISH; INTEGRALLY FUSED; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION. 23 1/4 X 16 1/4 ARCHITECTURAL AREA POLE MOUNTED LED WALKWAY SINGLE LUMINAIRE WITH: ONE-PIECE HEAVY WALL, DIE-CAST ALUMINUM CONSTRUCTION AND INTEGRAL REVEAL CHANNELS ALONG TOP SURFACE OF HOUSING; WEATHER-TIGHT WITH INTEGRAL FACTORY PREWIRED 0-10V DIMMABLE LED DRIVER; TYPE 2 DISTRIBUTION; U.L. LISTED FOR WET LOCATIONS; DARK BRONZE CORROSION-RESISTANT POWDER COAT FINISH; INDIVIDUALLY FUSED AT HAND HOLE; ONE (1) 120V-277V 50/60Hz CLASS 2 LED DRIVER. 16 SQUARE (NOMINAL), SURFACE MOUNTED LOW PROFILE HIGH OUTPUT LED CANOPY LIGHTING FIXTURE WITH: RUGGED EXTRUDED ALUMINUM HOUSING; 4,496 LUMENS; TYPE 3 DISTRIBUTION; SUITABLE FOR WET LOCATIONS; NATURAL ALUMINUM PAINT FINISH; INTEGRALLY FUSED; UNIVERSAL 120-277V LED DRIVER WIRED FOR 277V OPERATION. 12 X 3 RECESSED WALL MOUNTED LED LIGHTING FIXTURE WITH: DIRECTED LIGHT OUTPUT; DIE-CAST AND ALUMINUM HOUSING WITH INTEGRAL WIRING COMPARTMENT; ONE PIECE DIE-CAST ALUMINUM FACEPLATE; FACEPLATE SECURED BY TWO FLUSH STAINLESS STEEL CAPTIVE SCREWS; MOLDED SILICONE RUBBER GASKET FOR WEATHER TIGHT OPERATION; SUITABLE FOR WET LOCATIONS; SILVER PAINT FINISH; INTEGRALLY FUSED; INTEGRAL 120-277V ELECTRONIC LED DRIVER WIRED FOR 277V OPERATION. COOPER LIGHTING MCGRAW-EDISON CAT. NO. TLM-B02-LED-E1-T2-BZ-DIM
24
LB16
SAME AS FIXTURE TYPE LB4 EXCEPT 16-0 LONG LAY-IN IN LIEU OF 4-0 LONG; 277 VOLT OPERATION.
51
LB18
SAME AS FIXTURE TYPE LB4 EXCEPT 18-0 LONG LAY-IN IN LIEU OF 4-0 LONG; 277 VOLT OPERATION.
128 ELE
LITHONIA CAT. NO. KACM LED-1-49B350/40K-SR3-MVOLT-SF-DNAXD PHILIPS GARDCO CAT. NO. SFC-3-55LA-NW-UNIV-NP-FSPR
55
LB30
SAME AS FIXTURE TYPE LB4 EXCEPT 30-0 LONG IN LIEU OF 4-0 LONG AND 500 LUMENS PER FOOT MAX.; 277 VOLT OPERATION.
210 ELF 55
LC4
4-0 LONG, 4 NOMINAL SQUARE DIRECT/INDIRECT LINEAR LED FIXTURE WITH; EXTRUDED ALUMINUM BODY; 74 AIRCRAFT CABLE SUSPENSION; APPROXIMATELY 1697 LUMENS UP/ 2735 LUMENS DOWN; TOP GLOW UPLIGHT DIFFUSER AND FLUSH FROST WHITE DOWNLIGHT DIFFUSER; WHITE POWDER COATED STEEL REFLECTOR; WHITE FINISH; INTEGRALLY FUSED; U.L. LISTED; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION.
BEGA CAT. NO. 2384 LED LIGMAN RADO 6 CAT. NO. URA-40691-04 INTRIGUE LIGHTING CAT. NO. SGH-LED-SG-R-1LED-AC-POLG-WHL-277-SIL
15
CP-11243
ARCH. MECH.
J. Kasdorf
4000K LED FURNISHED WITH LIGHT FIXTURE 110
ELEC.
LC8
SAME AS FIXTURE TYPE LC4 EXCEPT 8 FEET IN LENGTH AND 74 AIRCRAFT AXIS LIGHTING CAT. NO. BBDILED-B1-450/650-40-SO-8-W-277-D-1-CA#-F (104 CABLE SUSPENSION; 277 VOLT OPERATION. WATTS) FINELITE CAT. NO. HP-4 ID-8-HO-4000K-TG-277V-SC-C4 (110 WATTS) PINNACLE CAT. NO. EX4B-A-40-40-8-AC48ST-277-1D-W-TOP LENS (113.6 WATTS) 2 X 4 LED LAY-IN FIXTURE WITH: PROPRIETARY LINEAR LED MODULE; ONE PIECE STEEL REFLECTOR AND HOUSING; BOTTOM ACCESS STEEL DRIVER COMPARTMENT; ACRYLIC LENS; WHITE FINISH; T-BAR SAFETY CLIPS; INTEGRALLY FUSED; 0-10V ANALOG DIMMING WITH STANDARD 120-277V DRIVER. COLUMBIA LIGHTING CAT. NO. LLT-24-40-ML-G-FS-A12F-ED-U-PAF-GLR DAYBRITE LIGHTING CAT. NO. 2LTG-47L-840-4-12-UNV-GLR1 LITHONIA CAT. NO. 2TL4-46L-FW-SWL-MVOLT-D50-LP840-N80 LSI CAT. NO. GA24-LED-SS-NW-UE-TSLR
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
LD
50
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
4000K LED FURNISHED WITH LIGHT FIXTURE 50
Drawing Scale:
LD1
LE
SAME AS FIXTURE TYPE 'LD' EXCEPT WITH DRYWALL GRID ADAPTER; 0-10V COLUMBIA LIGHTING CAT. NO. LLT-24-40-ML-FK24-FS-A12F-ED-U-PAF-GLR ANALOG DIMMING WITH STANDARD 120-277V DRIVER. DAYBRITE LIGHTING CAT. NO. 2LT-FMA24-47L-840-4-12-UNV-GLR1 LITHONIA CAT. NO. 2TL4-46L-FW-SWL-D50-LP840-N80-DGA24 LSI CAT. NO. FK24-LED-SS-NW-UE-TSLR CSI ECO-DOWNLIGHT LED CAT. NO. EDLM-NC-NW-2-1005-1 2 (NOMINAL) ROUND APERTURE, RECESSED 784 LUMEN LED DOWNLIGHT FOCAL POINT CAT. NO. FLS2-LL2-L11-277-RO-T2-BH-LS2-L35-RD-DN-FL-CD-TS WITH: HIGH SPUN ALUMINUM SELF-FLANGED REFLECTOR AND TRIM; 6 MAXIMUM HOUSING DEPTH; 0-10V DIMMABLE ELECTRONIC POWER SUPPLY; PRESCOLITE CAT. NO. D2LED-277V-2D9LED-40K-8-WFL45-MFC HIGH OUTPUT XICATO LED MODULE; LEDS AND POWER SUPPLY SERVICEABLE FROM BELOW; UL LISTED; 277 VOLT OPERATION. 4-0 LONG, SURFACE MOUNTED LED FIXTURE WITH: MARINE GRADE ALUMINUM HOUSING; LIGHT GRAY POLYESTER POWDERCOAT FINISH; DIE-CAST ALUMINUM FLAT END CAPS; HIGH IMPACT PEARLESCENT POLYCARBONATE LENS WITH INTEGRAL GASKET CHANNELS AND TAMPER-RESISTANT FASTENERS; CORNER MOUNT BRACKET; INTEGRALLY FUSED; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION. SAME AS FIXTURE TYPE LF EXCEPT WITHOUT CORNER MOUNT OPTION, SURFACE MOUNT. 4 x 7 U SHAPED, 4 (NOMINAL) RECESSED SLOT, LED LIGHTING FIXTURE WITH: 500 LUMENS PER FOOT MAX.; PRECISION CUT EXTRUDED ALUMINUM BODY; HIGH REFLECTANCE STEEL MATTE WHITE REFLECTOR; FROST WHITE SNAP IN LENS; SPACKLE FLANGE; ILLUMINATED 90 DEGREE CORNERS; INTEGRALLY FUSED; 0-10V DIMMABLE DRIVER WIRED FOR NON-DIMMING; 277 VOLT OPERATION. 15, 4 (NOMINAL) SURFACE MOUNTED LINEAR LED FIXTURE WITH; 500 LUMENS PER FOOT MIN.; EXTRUDED ALUMINUM BODY WITH INTERNAL JOINING SYSTEM TO ENSURE CONTINUOUS UNIFORM APPEARANCE; HIGH REFLECTANCE MATTE WHITE REFLECTOR; FROST WHITE SNAP IN LENS; ALUMINUM PAINTED FINISH; INTEGRALLY FUSED; U.L. LISTED; 0-10V DIMMABLE DRIVER WIRED FOR DIMMING; 277 VOLT OPERATION. SAME AS FIXTURE TYPE LH1 EXCEPT 25-0 IN LIEU OF 15-0. KENALL CAT. NO. MLHA5-48-F-LG-PP-50L40K-DCC-1-277-CMB-FS
No Scale
Issue Date:
4000K LED FURNISHED WITH LIGHT FIXTURE 20 05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
LF
50
LF1 LG
KENALL CAT. NO. MLHA5-48-F-LG-PP-50L40K-DCC-1-277-FS AXIS LIGHTING CAT. NO. BBRLED-B2-500-40-SO-FL-S#-W-277-R-1-DS-F W/LIT CORNERS FINELITE CAT. NO. HP-4 R-XX-SO-4000K-277V-SC-SF WITH 90 DEGREE LIT CORNERS PINNACLE CAT. NO. EV3-40-XX-SF-277V-1D-W-EV3CH WITH 90 DEGREE LIT CORNERS AXIS LIGHTING CAT. NO. BBSLED-B1-500-40-SO-15-AP-277-D-1-SC-F (7 WATTS PER FOOT) FINELITE CAT. NO. HP-4 SM-15-HO-4000K-277V-SC-SM (9.25 WATTS PER FOOT) PINNACLE CAT. NO. EX6A-N-40-XX-S-277-1D-CC (6.1 WATTS PER FOOT)
4000K LED FURNISHED WITH LIGHT FIXTURE 4000K LED FURNISHED WITH LIGHT FIXTURE
50 105
c
LH1
12204-1000
Lighting Fixture Schedule
LH2
AXIS LIGHTING CAT. NO. BBSLED-B1-500-40-SO-25-AP-277-D-1-SC-F (7 WATTS PER FOOT) FINELITE CAT. NO. HP-4 SM-25-HO-4000K-277V-SC-SM (9.25 WATTS PER FOOT) PINNACLE CAT. NO. EX6A-N-40-XX-S-277-1D-CC (6.1 WATTS PER FOOT)
175
1/2/2014 10:39:17 AM
NORTH
E0.2
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
S. Schiappacasse
Drawn By:
S. Schiappacasse
Approved:
R. Bracci
Date:
GENERAL NOTES
1. UNDERGROUND UTILITY LOCATIONS SHALL BE VERIFIED AT LEAST 100 FEET FROM UNDERGROUND CONSTRUCTION SO THAT CHANGES IN CABLE PLACEMENT CAN BE MADE IN EVENT OF CONFLICTS. 2. ALL CONSTRUCTION MATERIALS, METHODS AND PRACTICES, INCLUDING SURFACE RESTORATION, SHALL MEET NEC SPECIFICATIONS AND THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. 3. THE CONTRACTOR SHALL CALL MISS DIG, AT 800-482-7171, TO REQUEST UTILITY LOCATION AT LEAST 72 HOURS PRIOR TO BEGINNING CONSTRUCTION. 4. CONTRACTOR SHALL EXCAVATE TRENCHES FOR THE INSTALLATION OF UNDERGROUND CONDUIT. COORDINATE TRENCHING PRIOR TO COMMENCING WORK. 5. ALL UNDERGROUND SITE LIGHTING CONDUITS SHALL BE BURIED 30" BFG AND INSTALLED PER 265600. INSTALL MINIMUM 3" SCH 40 PVC CONDUIT SLEEVES UNDER ALL WALKS, ROADWAYS, PARKING LOTS, AND ALL HARD SURFACES PER 265600 (IN ADDITION TO SLEEVES SHOWN ON OTHER DRAWINGS AND/OR PROVIDED BY OTHER TRADES). 6. BRANCH CIRCUIT WIRING TO ALL SITE LIGHTING FIXTURES SHALL BE AS INDICATED PER 265600. 7. INSTALL LOCATOR BALL AT SLEEVE ENDS PER 265600. 8. COORDINATE ALL UNDERGROUND WORK WITH SITE DRAWINGS AND IRRIGATION SYSTEMS. REFER TODRAWING C5.1. 9. ROUTE DIRECT-BURIED CABLE 12 INCHES BEHIND BACK OF CURB OR EDGE OF PAVEMENT IN LANDSCAPED AREAS. 10. REFER TO DRAWING E7.3 FOR LIGHT POLE BASE MOUNTING DETAILS. 11. REFER TO DRAWING C7.3 FOR DUCT BANK PROFILE.
20
NEW SITE LIGHTING WALKWAY POLES TYPE 'ELD' TO BE CONTROLLED THRU THE EXISTING CONTROL PANEL IN EXISTING BUILDING. ELD ELD
ELF
FIXTURE TYPE 'ELF' MTD. LEVEL, APPROX. 2'-0" A.F. CONCRETE WALL AND ALONG BOTTOM OF MASONRY WALL TYP. REFER TO DETAIL 29 ON DWG. A2.9 FOR EXACT LOCATIONS.
ELF
ELD ELF
ELF REFER TO DETAIL 2 ON DWG. A2.9 FOR EXACT LOCATION AND MOUNTING HEIGHT.
ELB ELF
ELB EXISTING WALL PACKS TO BE REPLACED. CONNECT TO EXISTING CIRC. ELB ELF ELC ELD ELC ELF ELC 1E-1 ELD ELD
ELB
ELE
RP - 1A
RP - 1B
ELP - 1E LP - 1 ELE
STEAM VAULT
CP-11243
ARCH. MECH.
J. Kasdorf
ELD ELD ELD ELD ELD REFER TO DRAWING E7.3 FOR FIXTURE SITE LIGHTING DETAILS. TYP. NEW UNDERGROUND CONDUIT IS UNDER EXISTING EXIST. M.H. COMM. 243
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
PROVIDE PULLBOX AND CONNECT TO EXISTING CIRCUIT NEW SITE LIGHTING WALKWAY POLES TYPE 'ELD' TO BE CONTROLLED THRU THE EXISTING CONTROL PANEL IN EXISTING BUILDING. ELD
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
ELD EXIST. M.H. ELEC. 243
Drawing Scale:
As indicated
Issue Date:
10-23-13 11-20-2013 01-08-2014
Issued for:
Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
12204-1000
Site Plan
1/2/2014 10:39:23 AM
NORTH
E0.3
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
S. Schiappacasse
Drawn By:
Author
Approved:
R. Bracci
Date:
B.5
FD
FD
B.7
C C.1 C.2
FF 1E-6 L
FF
1E-6
C.8 C.9 D
FD FD
L
1-6 FD
FD
FF
D.3
CP-11243
ARCH. MECH.
J. Kasdorf
FF
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
E
FF
T. Hackett
Q.M. Review:
R. Bracci
Drawing Scale:
1/8" = 1'-0"
Issue Date:
E.4 E.5
FF
L
Issued for:
Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.7
12204-1000
Steam Tunnel Floor Plan - Lighting
1/2/2014 10:39:24 AM
NORTH
E2.0
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
S. Schiappacasse
Drawn By:
S. Schiappacasse
Approved:
R. Bracci
Date:
GENERAL NOTES
1. 2. 3. 4. 5. 6. 7. FIXTURE TYPE 'FA' MTD. @ 5'-4" AFF. TO CENTER LINE OF FIXTURE. FIXTURE TYPE 'FI' MTD. @ 9'-6" AFF. UNLESS OTHERWISE NOTED. FIXTURE TYPE 'FE' MOUNTED @ 7'-6" AFF. TO BOTTOM OF FIXTURE. FIXTURE TYPE 'ELB' MOUNTED @ 9'-0" AFF. TO CENTER LINE OF FIXTURE UNLESS OTHERWISE NOTED. FIXTURE TYPE'S 'LC4' & 'LC8' MOUNTED @ 9'-0" AFF. TO BOTTOM OF FIXTURE. FIXTURE TYPE'S 'LHL' & 'LHU' SHALL BE SURFACE MOUNTED TO BOTTOM OF BEAM. FIXTURE TYPE 'LF' MOUNTED @ 9'-0" AFF. AT ENTRY DOORS AND ABOVE STAIRS CENTERED ON BRICK WALL. MOUNTED HORIZONTALLY ON STEEL TUBE BEAMS ABOVE STAIRS OPPOSITE OF BRICK WALLS AND AT LANDINGS. FIXTURE TYPE 'FD' MOUNTED IN ELEVATOR PIT 4'-0" AFF. TO CENTER LINE OF FIXTURE. COORDINATE EXACT LOCATION ON WALL WITH ELEVATOR EQUIPMENT. INSTALL EXPOSED CONDUIT FOR LIGHTING FIXTURES IN WRITE-UP SPACES THRU OPENINGS IN BEAMS. REFER TO BP-1, SECTION 1/S5.2 FOR OPENING LOCATIONS.
8. 9.
KEYNOTES
1 HANDRAIL LED FIXTURES AND POWER SUPPLIES PROVIDED BY ARCHITECTURAL TRADES, REFER TO SPEC. SECTION 057313, AND WIRED BY ELECTRICAL TRADES. LED FIXTURES WILL BE PROVIDED FOR CONTINUOUS ILLUMINATION OF INNER HANDRAIL (HANDRAIL ALONG 'ART ON CAMPUS WALL' ONLY). COORDINATE EXACT ENTRY OF ELECTRICAL POWER FEED INTO POST WITH ARCH. TRADES AND HANDRAIL MANUFACTURER. POWER SUPPLIES SHALL BE LOCATED IN RAILING POST'S; REFER TO DWG. A7.7 FOR DETAILS AND A7.1 FOR PLAN NOTES. MAXIMUM DISTANCE BETWEEN POWER SUPPLIES SHALL BE 15'-22'. PROVIDE INPUT POWER CONNECTION, CIRCUIT TO PANEL ELP-1E, CIRCUIT 12. TOTAL LENGTH OF HANDRAIL IS APPROXIMATELY 115'-6", APPROXIMATELY 6 POWER SUPPLIES WILL BE PROVIDED. FIXTURE INPUT WATTAGE IS 4.5W/171 LUMENS PER FOOT, 4000 DEG. KELVIN.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
A
LA1 FIXTURE TYPES 'LI' AND 'LJ' MTD. IN VERTICAL WALL. REFER TO ARCH. ELEVATION DWG. A8.1 FOR FIXTURE QUANTITY, LENGTHS, AND EXACT LOCATION . CIRCUIT TO PANEL LP-1, CIRC. 7
VESTIBULE 1VB1
1E-1
LA1
LA1 LB5C
LB4C
(ZONE 1) LC4
LF XA
1/DIM
LA1
LA1
1/DIM
1-9
PC
STAIR SW3-1
LF 1E-11 1E-11
LC8
2/DIM
LC8 LB4C
LB5C
LC8
LC8
LB5C LB4C
LC8
1/DIM 1/DIM
LF1
LF
2/DIM
XA 1E-5
LC8
LC8
XB
1E-1
PC
XA
LC4 1E-7
1/DIM
ELB
A.5
1/DIM 1/DIM 1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
FE
FE
1/DIM
A.6
LARGE CONFERENCE ROOM 1000
LA1
FE
LA1
LA1
LB8
LB8
LB8
LB8
LB8
LB8
LB8
LB8
LB8
LB8
LB8
LB8
LB8
1E-4 LB12
1/DIM L
LB12
LD
LD 1-4
2/DIM
LA1
LA1
PB-1 1/DIM
B
FE FE
LI 1-5 LJ
1/DIM
2/DIM
1-4 FI FI
LA1 1E-3
1/DIM
LA1
2/DIM
LD 1-11 LD
LA1
L
LA1
LA1
L
LA1 LB16
LA1
LA1 LB16
LA1
L
RP - 1H
LA1
1/DIM
LA1
FE FE
FE
LA1
(ZONE 11,12)
1/DIM
LA1
LA1
ELEVATOR #1 EP1
PB-1
1E-5
LB16
LB16
LB16
CORRIDOR 1450
2/DIM
(ZONE 15)
LA1
LAB 1400
1-13
LD 1-11
L
LL
LL
LA4
LA4
LA4
LA4
B.5
IT CLOSET 1011A
1-3 FI L
KITCHENETTE 1011
LA2 LA2
LD
1/DIM L
LL
LL FI FI FI LD LB12 LB12
XB
LB16
L
LB16
L
LL
LL
LL N.I.C.
LL
1/DIM
LA2 FI RP - 1A 1-3 L
L
LA2
LA1
LA1
LA1
LA1
1/DIM
LA1
LA1
LA1
2/DIM 1/DIM
LL
LL
LL
LL
1-2 FI
1/DIM
ELB
LA2
1/DIM
LA2 1-1
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM L
1/DIM
1/DIM
1/DIM L
1-11 LD LD
L L
PC
LD
LD
L
LD
L
LD
L
LD ERP - 1BS
1/DIM
RP - 1B
LD
1-11
LD
LD
1/DIM
1-11
1-11
1-11
1-11
LE
1-11 LD
LD 1E-2
LE LD LD
1E-4
LD
LD
1-2
LD1
FI LD LD
1/DIM
LE
LE
LE
LE
LE
C.8
LM
L 2/DIM
1-10
L
1E-9 LD
1-10
1-10
L
1E-10 LD
LD1 1-2
4/Sc
LD
1/DIM
LD
L
LD
1/DIM 1/DIM 2/DIM 1/DIM
LD 1-10
L 1/DIM 1/DIM 1/DIM 1/DIM
LK
LB12
LB12
C.9
LA1
L 1/DIM
LA1 1 XB
L L
LA1
LA1
LA1
LA1
LD
LD
FI 1-6
ELEVATOR #2 EP2
PB-1
LA1
1/DIM
1-10
1/DIM
FI
1-6
FI
LA1
D.3
LA1 1-3
PB-1
LG LH4 /EM LJ
1/DIM
1/DIM
LB16
LB16
LB16
CP-11243
LD LD LD
L
LB12 LD
LD
FA FA
FA FA LA1
L
1-12
LD
LD
2/DIM
LA1
1/DIM
1-5
1E-5
LJ LI
LD LA1
1E-10 LA1
2/DIM
1/DIM
CORRIDOR 1HW1C
1/DIM
WORKROOMLJ 1040A
LB8
L
LAB 1200
LB16 LB16 (ZONE 3,4) LA1 LA1
2/DIM
1/DIM
LD
LD
LD
GATEWAY
1E-4
L
LD
ARCH.
1-4
L PB-1
CORRIDOR 1HW2
L
J. Kasdorf
ELEC.
R. Frazee
PB-1 PB-1
1-10
RP - 1C 1-6 FI
L.A.
ELP - 1E 1-6 FI
1-6 FI FI
L
D. Wilber
1-6 FI FI
Project Administrator:
1-10
LB16
LB16
LB16
CORRIDOR 1250
LA1
LP - 1 LB12
L
LA1
LA1
XA
J. Johnson
LOADING DOCK 1860 FI
PB-1
UNASSIGNED 1840
Project Arch/Eng:
T. Hackett
Q.M. Review:
ELB
1-3 FA
L LA1
1-4
LB8 1-1
L
LB8
LB8 1-10
LB8
LB8 1-10
LB8
LB8 1-10
LB8
LB8
LB8 1-10
LB8
1/DIM 1/DIM
LB8 1-10
L
LB8
LB8 1-10
LB8
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
FA LG LA1
1/DIM
LA1 LA1
1-7
LJ
WORKROOM 1101
L
LB8 1-10
L
LB8
LB8 1-10
L
LB8
LB8 1-10
L
LB8 1E-4
2/DIM
R. Bracci
1E-1
FI 1-6
FI
Drawing Scale:
As indicated
ELA
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
LA1
(ZONE 2)
(ZONE 2)
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
FIXTURE TYPE 'LJ' MTD. IN VERTICAL WALL. REFER TO ARCH. ELEVATION DWG. A8.1 FOR FIXTURE QUANTITY, LENGTHS, AND EXACT LOCATION . CIRCUIT TO PANEL LP-1, CIRC. 7.
OFFICE 1112
OFFICE 1113
OFFICE 1114
OFFICE 1115
OFFICE 1117
OFFICE 1118
OFFICE 1119
LB12
1/DIM
1-6 L
XA 1E-8
LB8 1E-5 1-1 LA1 LA1 LA1 LA1 LA1 1E-1 (ZONE 1)
L
E.7
1E-1 LA1
LC8
LC8
LB5C
PC
LC8
LC8
LB5C
PC
LC8
LC8
VESTIBULE 1VB2
LA1
1-8 LC4
LC4
1/DIM
2/DIM
LB5C
LC4
XA
LC8
LB4C
LC8
LC4 1-8
1E-8
XA
PC
1E-13 LF
1E-13 LF1
STAIR SW2-1
LF
XA
LA1 LA1
12204-1000
First Floor Plan - Lighting
1/2/2014 10:39:29 AM
NORTH
E2.1
OF
Bio-Engineering Facility
MECH.
LA1
LA1
OFFICE 1311
OFFICE 1312
OFFICE 1313
OFFICE 1314
OFFICE 1315
OFFICE 1316
2/DIM
FE
FE
1-11
1-11
WORKROOM 1301
1-11
1-11
WORKROOM 1302
1-11
1-11
1-11
OFFICE 1317 RP - 1J
OFFICE 1318
OFFICE 1319
MECHANICAL 1611 FB
LD ELB
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
S. Schiappacasse
Drawn By:
S. Schiappacasse
Approved:
R. Bracci
Date:
1 PB-
GENERAL NOTES
1. 2. 3. 4. 5. 6. 7. 8. FIXTURE TYPE 'FA' MTD. @ 5'-4" AFF. TO CENTER LINE OF FIXTURE. FIXTURE TYPE 'FI' MTD. @ 9'-0" AFF. UNLESS OTHERWISE NOTED. FIXTURE TYPE 'FC' (1) MTD. @ 8'-6" AFF., (1) MTD. @ 9'-0" AFF. & (1) MTD. @ 9'-6" AFF. TO BOTTOM OF FIXTURE. FIXTURE TYPE 'FE' MOUNTED @ 7'-6" AFF. TO BOTTOM OF FIXTURE. FIXTURE TYPE 'ELA' MOUNTED @ 9'-0" AFF. TO CENTER LINE OF FIXTURE. FIXTURE TYPE'S 'LC4' & 'LC8' MOUNTED @ 9'-0" AFF. TO BOTTOM OF FIXTURE. FIXTURE TYPE'S 'LHL' & 'LHU' SHALL BE SURFACE MOUNTED TO BOTTOM OF BEAM. FIXTURE TYPE 'LF' MOUNTED @ 9'-0" AFF. AT ENTRY DOORS AND ABOVE STAIRS CENTERED ON BRICK WALL. MOUNTED HORIZONTALLY ON STEEL TUBE BEAMS ABOVE STAIRS OPPOSITE OF BRICK WALLS AND AT LANDINGS. INSTALL EXPOSED CONDUIT FOR LIGHTING FIXTURES IN WRITE-UP SPACES THRU OPENINGS IN BEAMS. REFER TO BP-1, SECTION 1/S5.2 FOR OPENING LOCATIONS.
9.
KEYNOTES
1 HANDRAIL LED FIXTURES AND POWER SUPPLIES PROVIDED BY ARCHITECTURAL TRADES, REFER TO SPEC. SECTION 057313, AND WIRED BY ELECTRICAL TRADES. LED FIXTURES WILL BE PROVIDED FOR CONTINUOUS ILLUMINATION OF INNER HANDRAIL (HANDRAIL ALONG 'ART ON CAMPUS WALL' ONLY). COORDINATE EXACT ENTRY OF ELECTRICAL POWER FEED INTO POST WITH ARCH. TRADES AND HANDRAIL MANUFACTURER. POWER SUPPLIES SHALL BE LOCATED IN RAILING POST'S; REFER TO DWG. A7.7 FOR DETAILS AND A7.1 FOR PLAN NOTES. MAXIMUM DISTANCE BETWEEN POWER SUPPLIES SHALL BE 15'-22'. PROVIDE INPUT POWER CONNECTION, CIRCUIT TO PANEL ELP-1E, CIRCUIT 12. TOTAL LENGTH OF HANDRAIL IS APPROXIMATELY 115'-6", APPROXIMATELY 6 POWER SUPPLIES WILL BE PROVIDED. FIXTURE INPUT WATTAGE IS 4.5W/171 LUMENS PER FOOT, 4000 DEG. KELVIN.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
ADMIN 2060
FC
FC
(ZONE 1)
(ZONE 2)
LB4C
(ZONE 1)
(ZONE 1)
LF XA LF
1/DIM
PB-1
FC 2-5 LC8
2/DIM
2-9
PC
LB5C
LC8
LC8
LB5C LB4C
LC8 XA
LA1 2E-5 XB
LA1 XB
XA
LC8
LC4
L
2-5
LC4
2-9
STAIR SW3-2
LF DN. TO 1ST FLR. LTG.
2E-7
1/DIM
A.5 A.6
LARGE CONFERENCE ROOM 2000
LA1 FE FE LA1 FE FE FE FE FE FE LA1
L
LA1
FE
LA1
1/DIM
LB8
L
LB8
1/DIM
LB8
L
LB8
1/DIM 1/DIM
LB8
L
LB8
LB8
LB8 (ZONE 2)
L L
LB8
1/DIM 1/DIM
LB8
L
LB8
LB8
L
LB8
1/DIM
LB8
L
(ZONE 2)
LB8
L
LB8
1/DIM 1/DIM
LB8
L
LB8
1/DIM
LB8
L
LB8
XA LB12
LB12 2E-4
LD LD 2-4
LD
1/DIM
2-7
2-7
2-7
2-7
2-7
2/DIM
2-7
2-7
2-7
OFFICE 2311
2/DIM 1/DIM
2-4 FI FI
RP - 2D LA1
L
1/DIM
LB14 2-11
LD
L
LA1
LA1 2-1
LA1
L
LA1 LB16
LA1
LA1
L
LA1 LB16
LA1
L
LA1 LB16
LB16
LB16
1/DIM
2/DIM
2/DIM
LB12
LB12
FE
LI
2-13
2-15 EBU FI FI
LAB 2400
1/DIM
B.5
PC
LB30
L
PB-1
2E-1 LA1
L L
LA1 2-3
LA1 FI L
CORRIDOR 2HW1D
LB12 LA1
2/DIM
LB12
LA1
LA1
LA1
LA1
LA1
LA1
2E-5
2-11 LD
L
ERP - 2AS
L
1/DIM
1/DIM
1/DIM
2-11 LD
L
PB-1
XA XA LA1 LB16 (ZONE 1,2) LB16 LB16 (ZONE 5,6) LB16 LB16 (ZONE 9,10) LB16 LB16 (ZONE 13,14) LB16 LB16 (ZONE 17,18) LB16 FI
SUBSTATION 2810
FI FI
LA1
FI LD
L
FI
FI
EBU
CORRIDOR 2HW1
LD
L L
LD
LD LD
L
LD
L
LD
L
LD
L
LE
LE
LE
LE LH5 /EM
2-11
2-11
2-11
2-11
2-11
2-11
LE
LE
LE
LE
LE
STAIR SW1-2
LE
2-11 LD
LE 2-1
LE LE
1/DIM
LE
LE 2-5
LE
LE LD 2E-5
LD
LD
LD
LD
LE
LE
LE
LE
C.8
LM
2-10
2-10
L
2E-3
2-10
2-10
L
2E-3 2-10
L
FI
LD
LD 2-10
1/DIM
LD
L 1/DIM 2/DIM
LD
1/DIM
LD
L 1/DIM 2/DIM 1/DIM
LD 2-10
1/DIM
LD
1/DIM
LD FI
1/DIM L
C.9 D
L
1/DIM
ELEVATOR #2 EP2
LA1 LA1 LA1 2E-6 (ZONE 13,14) LB16
L
2E-4 XA
PB-1
LA1
LA1
LA1 ZONE 21
LA1
D.3
MEN'S TOILET 2021
LB16
LB16
LB16
LB16
LB16 LB12
1/DIM
PB-1
CP-11243
2E-4 LD 2-4 RP - 2C RP - 2D FI L 2-2 FI
L
LD
LA1
L
LD LB18 LD
1/DIM
PB-1
FA
FA
L
FA 2-3
FA LA1
2/DIM
LAB 2200
LB16
L
FA
2-3 FA FA FA
LA1
2/Sc
2-12
2-14
LD
2E-4
ARCH.
CORRIDOR 2HW2
LD
ELA
J. Kasdorf
ELEC.
R. Frazee
L.A.
2-10
ELP - 2E FI 2-4 LP - 2 RP - 2E
D. Wilber
FI
Project Administrator:
LA1 2E-3
LB16
L
LB16
L
LB16
L
RP - 2N
L
LA1
LA1
LA1
LA1
J. Johnson
Project Arch/Eng:
T. Hackett
L
E
2-3 LA1
L
2/DIM
2/DIM
LB8
LB8 2-6
LB8
LB8 2-6
LB8
LB8
LB8 2-6
LB8
LB8 2-6
LB8
LB8 2-6
LB8
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
1/DIM
FA LA1
1/DIM
WORKROOM 2101
L
LB8 2-6
L
LB8
LB8 2-6
L
LB8
LB8 2-6
L
LB8
Q.M. Review:
2-2 FI FI ELA
R. Bracci
Drawing Scale:
As indicated
2E-4 FI 2-2
1/DIM
LA1 XB
LB18
OFFICE 2111
OFFICE 2112
OFFICE 2113
(ZONE 2)
OFFICE 2114
OFFICE 2115
OFFICE 2116
(ZONE 2)
OFFICE 2117
OFFICE 2118
OFFICE 2119
LB12 XA 2E-2
LB12 L
CUSTODIAL 2840
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
GENDER NEUTRAL TOILET 2023
FIXTURE TYPE 'LI' MTD. IN VERTICAL WALL. REFER TO ARCH. ELEVATION DWG. A8.1 FOR FIXTURE QUANTITY, LENGTHS, AND EXACT LOCATION. CIRCUIT TO PANEL LP-1,CIRC. 7.
2-5 LC4
2E-5
2/DIM
LA1
L
LA1 XB
2/DIM
2/DIM
LB5C LB5C
PC
1/DIM
LC4
L
LF
E.7
LI LC4 LC4 LI
L PB-1
2-5 FC FC FC
LC4
1/DIM
2-8
LF
LF
LOUNGE 2HW1B
LB4C (ZONE 2)
STAIR SW2-2
XA LF
G
COLLABORATION SPACE 2030
c
12204-1000
Second Floor Plan - Lighting
1/2/2014 10:39:34 AM
NORTH
E2.2
OF
Bio-Engineering Facility
MECH.
OFFICE 2312 RP - 2F
OFFICE 2313
OFFICE 2314
OFFICE 2315
OFFICE 2316
WORKROOM 2302
OFFICE 2317
OFFICE 2318
OFFICE 2319 RP - 2K
RP - 2L
MECHANICAL 2611 FB
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
S. Schiappacasse
Drawn By:
S. Schiappacasse
Approved:
R. Bracci
Date:
GENERAL NOTES
1. 2. 3. 4. 5. FIXTURE TYPE 'FI' MTD. @ 9'-6" AFF. UNLESS OTHERWISE NOTED. FIXTURE TYPE 'FC' (1) MTD. @ 8'-6" AFF., (1) MTD. @ 9'-0" AFF. & (1) MTD. @ 9'-6" AFF. TO BOTTOM OF FIXTURE. FIXTURE TYPE'S 'LHL' & 'LHU' SHALL BE SURFACE MOUNTED TO BOTTOM OF BEAM. FIXTURE TYPE 'LC4' MOUNTED @ 9'-0" AFF. TO BOTTOM OF FIXTURE. FIXTURE TYPE 'LF' MOUNTED @ 9'-0" AFF. AT ENTRY DOORS AND ABOVE STAIRS CENTERED ON BRICK WALL. MOUNTED HORIZONTALLY ON STEEL TUBE BEAMS ABOVE STAIRS OPPOSITE OF BRICK WALLS AND AT LANDINGS. FIXTURE TYPE 'XB' MOUNTED @ APPROX. 10'-6" AFF. TO MOUNTING BRACKET.
6.
KEYNOTES
1 HANDRAIL LED FIXTURES AND POWER SUPPLIES PROVIDED BY ARCHITECTURAL TRADES, REFER TO SPEC. SECTION 057313, AND WIRED BY ELECTRICAL TRADES. LED FIXTURES WILL BE PROVIDED FOR CONTINUOUS ILLUMINATION OF INNER HANDRAIL (HANDRAIL ALONG 'ART ON CAMPUS WALL' ONLY). COORDINATE EXACT ENTRY OF ELECTRICAL POWER FEED INTO POST WITH ARCH. TRADES AND HANDRAIL MANUFACTURER. POWER SUPPLIES SHALL BE LOCATED IN RAILING POST'S; REFER TO DWG. A7.7 FOR DETAILS AND A7.1 FOR PLAN NOTES. MAXIMUM DISTANCE BETWEEN POWER SUPPLIES SHALL BE 15'-22'. PROVIDE INPUT POWER CONNECTION, CIRCUIT TO PANEL ELP-4E, CIRCUIT 10. TOTAL LENGTH OF HANDRAIL IS APPROXIMATELY 115'-6", APPROXIMATELY 6 POWER SUPPLIES WILL BE PROVIDED. FIXTURE INPUT WATTAGE IS 4.5W/171 LUMENS PER FOOT, 4000 DEG. KELVIN.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
A
L
FC
FC XA
LC4 FIXTURE TYPE 'LI' MTD. IN VERTICAL WALL. REFER TO ARCH. ELEVATION DWG. A8.1 FOR FIXTURE QUANTITY, LENGTHS, AND EXACT LOCATION. CIRCUIT TO PANEL LP-1, CIRC. 7.
LI
PB-1 L
LF
4/Sc
4/Sc
LOUNGE 3HW1A
LC4 3-1
LC4 LI
2/DIM
3-1
FC LF
STAIR SW3-3
LA1 4E-1
LA1 XB
XA
L
FI
FI
FI
FI
FI 4E-3
FI
LF
A.5 A.6
FI FI
XB 4E-1
LI
B
SHELL 3000
FI FI LI LI LI
ELEVATOR #1 EP1
3-5 FI FI FI FI ~ ~
FI
FI
B.5
IT CLOSET 3011A
3-3 L FI 3-3
PB-1
LH4 /EM
XB FI
L
B.7 C C.1
3-3
2/DIM
3-1
FI 4E-1
SHELL 416
LH3 /EM
C.2
ACCENT LIGHTING ON CROSS BRACING, REFER TO A8.2 FOR EXACT LOCATION.
LM LE LE LE LE LE
LE
LE
LE
LE
LE
LE 4E-1 FI FI FI FI FI FI
LE
LE
LE 3-1
LE
LE
LE
LE
LE
LE
LE
LE
C.8
LM
L 2/DIM
LH3/EM
C.9 D
FI 3-3 FI
L
4E-1 1
ELEVATOR #2 EP2
CORRIDOR 3HW1
XB
D.3
SHELL 3020
4E-1
CP-11243
4E-1 4E-5 FI
PB-1
PB-1
ARCH.
FI GATEWAY DP - 2 3-7
PB-1
LI 3-7
G
J. Kasdorf
ELEC.
LI LA1
R. Frazee
L FI
FI
CORRIDOR 3HW1C
LA1 LI
PB-1
RP - 3C FI FI FI 3-5 FI RP - 3D
L.A.
D. Wilber
Project Administrator:
FI
FI FI LP - 3
J. Johnson
Project Arch/Eng:
T. Hackett
3-7
L
E
FI FI
Q.M. Review:
R. Bracci
Drawing Scale:
LI
As indicated
FI 3-7 FI FI
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
FIXTURE TYPE 'LI' MTD. IN VERTICAL WALL. REFER TO ARCH. ELEVATION DWG. A8.1 FOR FIXTURE QUANTITY, LENGTHS, AND EXACT LOCATION. CIRCUIT TO PANEL LP-1, CIRC. 7.
XB 4E-1 LA1
L 4/Sc
SHELL 3840
FI
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
XB LA1 XA
FI
FI
FI
FI
FI
FI
L
E.7
LC4
PB-1
LC4
LI LI
3-1 FC FC FC
LOUNGE 3HW1B
4/Sc
3-1
LC4
2/DIM
LF 4E-5
LF
XA
STAIR SW2-3
LF
G
c
12204-1000
Third Floor Plan - Lighting
1/2/2014 10:39:36 AM
NORTH
E2.3
OF
Bio-Engineering Facility
MECH.
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
S. Schiappacasse
Drawn By:
S. Schiappacasse
Approved:
R. Bracci
Date:
GENERAL NOTES
1. 2. 3. 4. 5. FIXTURE TYPE 'FI' MTD. @ 9'-6" AFF. UNLESS OTHERWISE NOTED. FIXTURE TYPE 'LC4' MOUNTED @ 9'-10" AFF. TO BOTTOM OF FIXTURE. FIXTURE TYPE 'LF' IN STAIRS SW2 & SW3 MOUNTED @ 9'-0" AFF. AT ENTRY DOORS AND ABOVE STAIRS CENTERED ON BRICK WALL. FIXTURE TYPE 'LF' IN STAIRS SW4 & SW5 MOUNTED @ 8'-0" AFF. AT ENTRY DOOR, STAIRS AND STAIR LANDINGS. FIXTURE TYPE 'XB' MOUNTED @ APPROX. 10'-6" AFF. TO MOUNTING BRACKET.
KEYNOTES
1 HANDRAIL LED FIXTURES AND POWER SUPPLIES PROVIDED BY ARCHITECTURAL TRADES, REFER TO SPEC. SECTION 057313, AND WIRED BY ELECTRICAL TRADES. LED FIXTURES WILL BE PROVIDED FOR CONTINUOUS ILLUMINATION OF INNER HANDRAIL (HANDRAIL ALONG 'ART ON CAMPUS WALL' ONLY). COORDINATE EXACT ENTRY OF ELECTRICAL POWER FEED INTO POST WITH ARCH. TRADES AND HANDRAIL MANUFACTURER. POWER SUPPLIES SHALL BE LOCATED IN RAILING POST'S; REFER TO DWG. A7.7 FOR DETAILS AND A7.1 FOR PLAN NOTES. MAXIMUM DISTANCE BETWEEN POWER SUPPLIES SHALL BE 15'22'. PROVIDE INPUT POWER CONNECTION, CIRCUIT TO PANEL ELP-4E, CIRCUIT 10. TOTAL LENGTH OF HANDRAIL IS APPROXIMATELY 115'-6", APPROXIMATELY 6 POWER SUPPLIES WILL BE PROVIDED. FIXTURE INPUT WATTAGE IS 4.5W/171 LUMENS PER FOOT, 4000 DEG. KELVIN. ROUTE 3/4"C. UP THRU CEILING SPACE TO ROOF TO PHOTOCELL ON NORTH SIDE, REFER TO DWG. E2.5 PENTHOUSE PLAN - LIGHTING.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
A
LC4 FIXTURE TYPE 'LI' MTD. IN VERTICAL WALL. REFER TO ARCH. ELEVATION DWG. A8.1 FOR FIXTURE QUANTITY, LENGTHS, AND EXACT LOCATION. CIRCUIT TO PANEL LP-1, CIRC. 7. LI LI LC4
2/DIM
LB4
L 1/DIM
4/Sc
LC4 4-1
4/Sc
LOUNGE 4HW1A
4-1
L
LB4
LA1 4E-1
LA1 XB
XA FI FI FI FI FI 4E-4 FI
XA
L
STAIR SW3-4
LF LF DN. TO 3RD FLR. LTG.
A.5 A.6
FI FI
XB
LF 4E-7
LI
STAIR SW5-4
LF
SHELL 4300
LI
SHELL 417
FI 4-5 FI FI FI FI ~ ~
SHELL 4000
LI
B.5
FI FI
PB-1
XB
B.7 C C.1
3-1
CORRIDOR 4HW1
4-3 FI L
C.2
ACCENT LIGHTING ON CROSS BRACING, REFER TO A8.2 FOR EXACT LOCATION.
LE
LE
LE
LE FI
LE
LE
LE
LE
STAIR SW1-4
1 FI FI FI FI
LE 4-3
LE LE
1/DIM
LE
LE 4-1
LE
LE
LE
LE
C.8 C.9 D
LM
4-3 FI FI XB
L
UP TO PENTHOUSE FLR. TYPE 'XB' MTD. @ 10'-6" AFF. TO CENTER LINE OF MOUNTING BRACKET. TYP. 1
STAIR SW4-4
PB-1
LF
4E-8
D.3
4E-1
CP-11243
ARCH. MECH.
PB-1
4E-6 LA1 2 LI
PB-1
FI
FI
J. Kasdorf
ELEC.
SHELL 4020
FI
4-7
G
L ?
GATEWAY
R. Frazee
RP - 4C RP - 4D 4-7
PB-1
L.A.
LA1
CORRIDOR 4HW1C
LI
FI
FI
FI
4-5 FI
ELP - 4E
D. Wilber
Project Administrator: Project Designer:
LP - 4
LA1
ERP - 4AE
J. Johnson
Project Arch/Eng:
T. Hackett
4-7
L
E
FI FI
PB-1
Q.M. Review:
LI
R. Bracci
Drawing Scale:
FI
As indicated
MECHANICAL ROOM 4650 SHELL 4840
LI 4-7
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
FIXTURE TYPE 'LI' MTD. IN VERTICAL WALL. REFER TO ARCH. ELEVATION DWG. A8.1 FOR FIXTURE QUANTITY, LENGTHS, AND EXACT LOCATION. CIRCUIT TO PANEL LP-1, CIRC. 7.
XB 4E-1 LA1
L
XB LA1
4/Sc
FI XA
FI
FI
FI
FI
FI XA
4/Sc
LF
LF
4-1
LC4
2/DIM
STAIR SW2-4
E.7
4E-6
1/DIM
LC4
LC4
4-1 LB4
LI LI
LOUNGE 4HW1B
LB5
LB4
12204-1000
Fourth Floor Plan - Lighting
1/2/2014 10:39:38 AM
NORTH
E2.4
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
S. Schiappacasse
Drawn By:
S. Schiappacasse
Approved:
R. Bracci
Date:
GENERAL NOTES
1. 2. 3. FIXTURE TYPE 'FI' MTD. @ 9'-6" AFF. UNLESS OTHERWISE NOTED. FIXTURE TYPE 'LF' IN STAIRS SW4 & SW5 MOUNTED @ 8'0" AFF. AT ENTRY DOOR, STAIRS AND STAIR LANDINGS. FIXTURE TYPE'S 'LH1' & 'LH2' SHALL BE SURFACE MOUNTED TO BOTTOM OF BEAM.
KEYNOTES
1 PHOTOCELL MOUNTED ON ROOF FACING NORTH ON A 3/4" RGS CONDUIT RISER, COORDINATE ROOF PENETRATION AND THE INSTALLATION OF PIPE SLEEVE WITH THE ROOFING CONTRACTOR. ROUTE 3/4"C. DOWN INTO CEILING SPACE OF ELECTRICAL CLOSET 4820, LOCATED ON FOURTH FLOOR.
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
LH1 LF
VESTIBULE SW5-5A
2/Sc
1
PC
B
4E-9
FI
LF LF
XA
XA FI FI FI FI FI FI
FI
FI 4E-7
ELA
FI
FI FI
B.5
LF
PB-1
B.5
FI LH2 ELA FI FI
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
FI
B.7
B.7
FI FI FI FI
C C.1 C.2
ELA
C C.1 C.2
FI FI LH2 ELA 4E-12 2 E4.5 1 E2.5 FI FI FI LF FI ELEVATOR CONTROL EP2A FI FI FI FI
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
LH2/EM FI FI FI FI FI
FI 4-9
FI FI XA
2/Sc
LF
L
VESTIBULE SW4-5A
4E-8
FI
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
LF 4E-9 L 4-9 FI LF
L
C.8 C.9 D
C.8
LH2/EM ELA
4-9
C.9
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
D
ELA FI LH2
LF FI PP - C ATS - LS FI FI
ELEVATOR #2 EP2
PP - B
XA
D.3
D.3
CP-11243
ARCH. MECH.
RP - PH
J. Kasdorf
ELEC.
R. Frazee
1 E2.5
LH1
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
T. Hackett
E
LH1 /EM 4E-2
Q.M. Review:
R. Bracci
Drawing Scale:
As indicated
Issue Date:
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
LH1
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
4-1
E.7
G
c
12204-1000
Penthouse Plan - Lighting
1/2/2014 10:39:40 AM
NORTH
E2.5
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
S. Schiappacasse
Drawn By:
S. Schiappacasse
Approved:
R. Bracci
Date:
GENERAL NOTES
1. ALL CEILING MOUNTED SPECIAL RECEPTACLES LOCATED IN LABS ARE NEMA L14-20 AND ARE PROVIDED BY CASEWORK SUPPLIER FOR INSTALLATION BY EC, UNLESS OTHERWISE NOTED. CONNECT WITH 2 #10 AND 1 #10 GROUND. ALL RECEPTACLES IN EXTERIOR WALLS OF NORTH AND SOUTH WRITE-UP SPACE ARE INSTALLED IN GYP BOARD FIN TUBE ENCLOSURE AT 8" AFF TO CENTER. SEE DETAIL 8 ON A5.1. CONDUITS SHALL RUN HORIZONTALLY. PULL AN ADDITIONAL #10AWG FROM THE PANEL TO THE J-BOX FOR EVERY THREE RECEPTACLES IN LINEAR EQUIPMENT ROOM 1600. TERMINATE WIRE ON SPACE, LEAVE 6" COILED IN BOX AND LABEL WITH PANEL CIRCUIT NUMBER.
3.
4. WEATHER PROOF GFCI RECEPTACLES IN INSULATED COLD ROOM WALLS INSTALLED AND CONNECTED BY COLD ROOM INSTALLER 5. CONDUITS IN FINISHED AREAS SHALL BE CONCEALED ABOVE NEW CORRIDOR CEILING. ALL JUNCTION BOXES ABOVE NEW CEILING SHALL BE ACCESSIBLE FROM AN ACCESS PANEL. 6. INSTALL RECEPTACLES FOR MOTORIZED ROLLER SHADE IN TOP OF SOFFIT APPROXIMATELY 8'-0" AFF AND WITHIN 2'-0" OF MOTOR. SEE DETAIL 13 ON A5.1. COORDINATE WITH SHADE INSTALLER. 7. ALL MOTORIZED SCREENS AND SHADES INSIDE CONFERENCE ROOMS SHALL BE CONTR0LLED BY THE A/V SYSTEM UNLESS OTHERWISE NOTED. 8. ALL LAB SUPPORT RECEPTACLES, IE TISSUE CULTURE, EQUIP ROOM ETC, SHALL BE ABOVE COUNTER HEIGHT.
KEYNOTES
1 DOOR OPERATOR PUSH BUTTON MOUNTED TO ARCH. PROVIDED BOLLARD. EXTEND 3/4" CONDUIT UNDERGROUND TO RP-1A. COORDINATE WITH ARCH. GENERATOR LOAD BANK DISCONNECTS NEMA 4X STAINLESS STEEL. LOCATE SOUTH OF GAS RISER ON RETAINING WALL. COORDINATE WITH GAS SERVICE INSTALLER. J-BOX ABOVE RACK WITH 3 CIRCUITS. COORDINATE RACK LOCATION WITH MSU. WEATHER PROOF, GFCI RECEPTACLES IN COLD ROOM CONNECTED TO COLD ROOM CONTROL PANEL INSTALLED BY COLD ROOM INSTALLER. DOUBLE GANG BOX 18" AFF FOR NOTEBOOK CONNECTION WITH 1" CONDUIT TO TV OUTLET ABOVE. 4" CONCRETE PAD. EXTEND PAD BEYOND PANEL ENOUGH TO INSTALL A FUTURE FULL WIDTH PANEL SECTION AT PP-A.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
2AE-3
VESTIBULE 1VB1
2AE-3
TV 1B-16
1A-1 1A-1
1A-3 1A-3
1A-5 1A-5
1A-7
1A-7
1A-9
1A-9
1A-11 1A-11
1A-13 1A-13
1C-21
1C-21
1C-23 1C-23
1D-1 1C-25 1C-25 1D-3,5 1C-27 1D-1 1D-11 1D-7,9 1D-11 1D-16
STAIR SW3-1
1A-22
A.5
1B-6
A.6
OFFICE 1311
OFFICE 1312
OFFICE 1313
1A-8
1A-12
OFFICE 1314
OFFICE 1315
OFFICE 1316
1A-16 1A-18 1A-18
WORKROOM 1301
1A-14 1A-10 1A-14 1A-16
1C-28 1C-28
OFFICE 1317
OFFICE 1318
1C-32 1C-32
OFFICE 1319
1C-34 1C-34 1C-34
1D-41 1D-15,17 1D-13 1D-13 1D-19,21 MONITORING SYSTEM, 1B-42 MECHANICAL 1611 GLASS WASHER DISCONNECT
WORKROOM 1302
1C-30 1C-30
1C-30
1B-10
1B-12
1F-2 1F-4
1K-14
1K-14
1K-10,12
1K-24
1K-20,22
1K-2
1K-4
1K-6,8
1K-4
GW-1
GW-2
ST-1 TO PP-A
ST-2
RP - 1F RP - 1G
LAB 1400
1J-22 1F- 9,11 1F- 13,15 1F- 17,19 1F- 21,23 1G-21,23 1G-17,19 1G- 27,29 1G- 31,33 1G- 35,37 1G- 39,41 1H-1,3 1H-5,7 CCCC 1J-18,20 1J-22,24 1J-26,28 1J-30,32 CC 1J-21,23 CC 1J-17,19 CCCC 1J-13,15 1J-9,11 1J-5,7 1J-1,3 1J-24 1J-22 1J-24 1J-26 1J-28 1J-26 1J-28
RP - 1H RP - 1J CORRIDOR 1450
RP - 1K
TO PP-A
STERILIZER DISCONNECT
1F- 1
VFD 1D-12,14 1BS-7 1D-10 1BS-1,3 1BS-11 1D-23 1D- 25,27 1D- 35 1D- 29 VFD 1BS-23 TO PP-A 1BS-17,19 HWHP-2 1BS-27 1D- 35 1D- 37,39 1E-14 HWHP-1 VFD TO PP-A TO PP-A CHWP-1 CHWP-2
VFD
UH-1.2
CCCC
CC
GFI
CCCC
ELEVATOR #1 EP1
1B-10 1B-6 2 MICROWAVES 1B-24 1B-26 GFI 1B-31 USB TV 1B-33
1F-2
1F- 3
TO PP-A
LV-1
CCCC
CCCC
B.5
ELECTRICAL CLOSET 1011B
IT CLOSET 1011A
REF 1B-28
TO PP-A
GROUND ROD (TYP) EXTEND #4/0 CU IN CONDUIT TO GROUND BUS ON SECOND FLOOR SEE 5/E7.1. (TYP FOR 4)
1E-14
1F- 7
LAC-1
B.7
RP - 1A
TO PP-A
C C.1 C.2
1F-26 1F-28 GFI 1L-18 GFI 1L-20 1L-18 1L-22 1F-30 1F-32 1F-34
1H-10 1G-14 1AS-7 GFI 1H-2 GFI 1H-4 1H-14 1H-2 1H-6 1H-8 1N-2 1G-8
J
1G-6 1G-4
J
1H-12
1AS-12 ERP - 1AS ERP - 1BS 1AS-4,6 1D- 31,33 1BS-37 LINEAR EQUIPMENT ROOM 1BS-31,33 1600 1D-41 GFI WP 1Q-38 GFI WP 1Q-38 GFI WP 1Q-38 1BS-41 VF-1 1D-4 1D-6,8 1BS-8 GFI 1Q-30 1BS-4,6 1BS-12 1D- 24 1Q-26 WP GFI 1P- 28 1P- 28 1P- 28 1Q-30 1D- 26,28 TO PP-A 1D-4 1BS-24 1BS-20,22 1BS-28 1D-30 1D-32,34 1D-30 UP TO SECOND FLOOR 6 PP-A UH-1.3 1E-14 FIRE PUMP CONTROLLER (COORDINATE WITH INSTALLER)
1H-16 1H-18
1H-26 1H-30 1H-38,40 1H-34 1H-28 1H-36 1N-20 1N-22 1N-30 1N-32
1J-16 GFI
1AS-8 CONTROL PANEL 1J-38,40,42 1P-29,31 EQUIP ROOM 1510 1P-33 1P-33
TO PP-A
DBP-1
GFI
GFI
GFI GFI
J
1L-22 1L-34 1L-38,40 GFI 1L-24 1L-36 GFI 1L-38 1L-26 1L-28
1M-2 1M-6
1M-4
1M-8
1AS-23
C.8 C.9 D
GFI
1B-5 TV
1B-3 TV
1B-1 TV 1B-15
1M-6
1Q-28 WP GFI
1P-14
1P-16
1P- 30
1P- 30
HAND DRYER
1L-31
GFI
1B-7
GFI
1L-18
1N-26 1N-28
1P-18
1P-18
1N-18
1L-33,35
ICE
1E-12
ELEVATOR #2 EP2
CCCC
1P- 32
CORRIDOR 1HW1C
EWC 1B-9
CORRIDOR 1HW1
1L-41
1P- 24
1P- 32
1B-18
1P- 1,3 1P- 5,7 1P- 9,11 1P- 13,15 1N-27,29 1N-31,33 1N-35,37 1N-39,41
CCCC
D.3
CP-11243
1E-29
ARCH.
CORRIDOR 1HW2
J. Kasdorf
ELEC.
CC
CC
CCCC
CCCC
1P- 34
1P- 34
1N-5,7 1N-1,3
CC
1M-17,19
1Q-6,8
1Q-10,12
1Q- 24
1B-20 1B-27
1Q- 24
1Q-14
1Q-14
1Q-2
1Q-4
1Q-4
WORKROOM 1040A
1B-23
1M-21,23
1P- 21,23
R. Frazee
L.A.
UNASSIGNED 1840
FCU DC-2
1B-11
1L-29
1L-7
LAB 1200
D. Wilber
Project Administrator:
OH DOOR PUSH BUTTON UH 1.1
J. Johnson
Project Arch/Eng:
RP - 1L RP-1M 1C-10 1C-14 1C-14 1C-14 1C-16 1C-16 1C-16 1C-18 1C-18 1C-18
CORRIDOR 1250
RP - 1N
RP - 1P
RP - 1Q
T. Hackett
Q.M. Review:
E
HAND DRYER GFI 1B-13 GFI 1B-13 1B-22 1B-19 TV 1B-35 USB 1B-27
1B-21 1B-21
1C-4 1C-4
1C-8 1C-8
1C-22 1C-22
1C-24
1C-6
1C-22 1C-20
1C-24
R. Bracci
FIBER ROOM 1830A
Drawing Scale:
COMPACTOR AREA 1860A
DC-1
As indicated
1C-24
1B-21
1C-4 1C-12
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
GENDER NEUTRAL TOILET 1023 OFFICE 1111
1B-25
1C-12
1E-40
FCU
1AE-19
OFFICE 1112
OFFICE 1113
WORKROOM 1101
OFFICE 1117
OFFICE 1118
OFFICE 1119
FCU
E.7
VESTIBULE 1VB2
2AE-21 TV 1B-25 1C-1 1C-1 1C-3 1C-3 1C-5 1C-5 1C-7 1C-7 1C-9 1C-9 1C-11 1C-11 1C-13 1C-13 1C-15 1C-15 1C-17 1C-17 1C-19 1C-19 1E-31,33 1E-35
STAIR SW2-1
2
F
2AE-21 SHADE CONTROL OVERRIDE BUTTON 4 PRIMARY CONDUITS & 4 COMM.CONDUITS SEE E0.3 FOR CONTINUATION.
12204-1000
First Floor Plan - Power
1/2/2014 10:39:50 AM
NORTH
E3.1
OF
Bio-Engineering Facility
MECH.
1A-30
1A-6
1A-8
1A-14
1A-16
1A-18
1C-32
1E-20 1E-22
1E-18
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
2.
GENERAL NOTES
1. ALL CEILING MOUNTED SPECIAL RECEPTACLES LOCATED IN LABS ARE NEMA L14-20 AND ARE PROVIDED BY CASEWORK SUPPLIER FOR INSTALLATION BY EC, UNLESS OTHERWISE NOTED. CONNECT WITH 2#10 AND 1#10 GRD. ALL RECEPTACLES IN EXTERIOR WALLS OF NORTH AND SOUTH WRITE-UP SPACE ARE INSTALLED IN GYP BOARD FIN TUBE ENCLOSURE AT 8" AFF TO CENTER. SEE DETAIL 8 ON A5.1. CONDUITS SHALL RUN HORIZONTALLY. PULL AN ADDITIONAL #10AWG FROM THE PANEL TO THE J-BOX FOR EVERY THREE RECEPTACLES IN LINEAR EQUIPMENT ROOM. TERMINATE WIRE ON SPACE, LEAVE 6" COILED IN BOX AND LABEL WITH PANEL CIRCUIT NUMBER. WEATHER PROOF GFCI RECEPTACLES IN INSULATED COLD ROOM WALLS INSTALLED AND CONNECTED BY COLD ROOM INSTALLER
2.
3.
4.
5. CONDUITS IN FINISHED AREAS SHALL BE CONCEALED ABOVE NEW CORRIDOR CEILING. ALL JUNCTION BOXES ABOVE NEW CEILING SHALL BE ACCESSIBLE FROM AN ACCESS PANEL. 6. INSTALL RECEPTACLES FOR MOTORIZED ROLLER SHADE IN TOP OF SOFFIT APPROXIMATELY 8'-0" AFF AND WITHIN 2'-0" OF MOTOR. SEE DETAIL 9 ON A4.1.2. COORDINATE WITH SHADE INSTALLER. 7. ALL MOTORIZED SCREENS AND SHADES INSIDE CONFERENCE ROOMS SHALL BE CONTROLLED BY THE A/V SYSTEM UNLESS OTHERWISE NOTED. 8. ALL LAB SUPPORT RECEPTACLES, IE TISSUE CULTURE, EQUIP ROOM ETC, SHALL BE ABOVE COUNTER HEIGHT.
KEY NOTES
1 PROVIDE RACK TO INSTALL TRANSFORMERS ABOVE FINISH FLOOR AND HIGHER THAN TOP OF PANELS. EXTEND CONDUITS UNDER 2ND FLOOR FOR CONF 2010 AND ROOMS TO SOUTH. INSTALL EXPOSED WHERE NO CEILING EXISTS AND UP INSIDE WALLS. ROUTE GROUND BUS ABOVE DOORWAY. ROUTE GROUND BUS ABOVE PRIMARY SWITCHGEAR. 4" CONCRETE PAD. EXTEND PAD BEYOND SWITCH GEAR ENOUGH TO INSTALL A FUTURE FULL WIDTH SECTION.
3 4 5
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
A
2C- 23 2A- 20 2B- 27 2A- 20 2A- 1 2A- 1 2A- 3 2A- 3 2A- 5 2A- 5 2A- 7 2A- 7 2A- 9 2A- 9 2A- 11 2A- 11 2A- 13 2A- 13 2C- 21 2C- 21 2C- 23 2C- 25 2C- 25 2D-1 2D-3,5 2C- 27 2D-1 2D-1 2D-7,9 2D-11 2E-26
LOUNGE 2HW1A
ADMIN 2060
2A- 22
STAIR SW3-2
FCU 2E-8 GFI GFI GFI 2E- 24 2E- 24 2E- 24
A.5 A.6
TV 2B- 8
2B- 27
OFFICE 2311
2A- 2 2B- 6 TV 2A- 4 2A- 4
OFFICE 2312
OFFICE 2313
2A- 8
2A- 12
OFFICE 2314
2A- 14 2A- 14 2A- 14
OFFICE 2315
2A- 16 2A- 16 2A- 16
OFFICE 2316
2A- 18 2A- 18
2C- 28
OFFICE 2317
2C- 30 2C-30
OFFICE 2318
2C- 32
OFFICE 2319
2C- 34 2C- 34 2C- 34
2A- 6
2A- 8
2A- 18
2C- 32 2C- 30 RP - 2H RP - 2J
B
2B-12 2B- 10 2B-14 2A- 2 2A- 2 2A- 2 2F-37 2F-39 2F-37 2F-39 2F-37 2F-39
GW-3
GW-4
ST-3
RP - 2F
RP - 2G
LAB 2400
2F- 1 2F- 3 2F- 1 2F- 9,11 2F- 13,15 2F- 17,19 2G- 21,23 2G- 17,19 2F- 21,23 2G- 13,15 2G- 9,11 2G- 5,7 2G- 1,3 CCCC CC C CC C CCC C 2G- 27,29 2G- 31,33 2G- 35,37 2G- 39,41 2L- 22 CC CC CCCC 2J-27,29 2J-31,33 2J-35,37 2J-39,41 2K-27,29 2K-31,33 2K-35,37 2K-39,41 2L-27,29 2L-31,33 2L-35,37 2L-39,41 2L- 24 2L- 22 2L- 24 2L- 26 2L- 28 2L- 26 2L- 28
2D-25,27 2D-29 2BS-37 2BS-11 2BS-31,33 2BS-41 2D-23 3 2D-23 2BS-1,3 2BS-7
4 1/4"X2" COPPER GROUND BUS 12" AFF AROUND PERIMETER. INSTALL ABOVE DOORS AND AREAWAYS. 2E- 8
B.5
CORRIDOR 2HW3
2B-16 2B-2
C C CC
2F- 5
C CCC
CCCC
8' - 0"
2B-12
CCCC
2B- 10
ELEVATOR #1 EP1
2F- 3
2K-21,23 2K-17,19
PRIMARY SWITCHGEAR
WORKING CLEARANCE (TYP) 2E-6 2D-2 2D-4,6 MAIN SUB #2 FRONT FRONT
B.7 C
SUB #1
C.1 C.2
2G-32
2K-12
2K-12
TV 2B- 1
2B- 3
GFI
GFI GFI 2J-2 2H-32 2H-26 GFI GFI 2J-4 2H-34 2J-2 2H-28 2H-32 2H-25,27 2J-6 2H-30 2H-36 2J-8 2H-38 2J-2 2Q-2 2P-30 2P-20 2Q-4 2P-32 2P-11,13 2Q-6 2P-22 2P-34 GFI GFI 2Q-8 2P-36 2P-24 GFI GFI 2P-34 2Q-6 2P-26 2P-28
GFI GFI
TIE
2K-8
J
2G- 20
2G-4 2H-6
GFI
2K-10
J
2K-22 2K-20
2F-8
2J-18
2J-28,30 CONTROL PANEL 2Q-38,40,42 2J-32 2Q-22 2Q-24,26 2AS-24 2Q-22 2AS-20,22 2Q-32 2AS-28 ICE
J
2D-8 2BS-27 LINEAR EQUIPMENT ROOM 2D-10 2600 2D- 41 2D-12,14 2D-10 2BS-12 2BS-4,6 2BS-8 2D-22 2D-24,26 2D-22
8' - 0 1/4"
MAIN
2E- 6
2R-20 2R-22
SUBSTATION 2810
12" WIDE LADDER CABLE TRAY FOR PRIMARY CABLES. MOUNT TRAY 12" BELOW THE UNDERSIDE OF BEAM.
C.8 C.9 D
MEN'S TOILET 2021
2B- 7 GFI 2B- 5
2M-20 2M-34 GFI J 2N-2 2M-22 2M-36 2M-38,40 GFI 2M-24 2M-34 2M-26 2M-28 2N-6
GFI
2N-4
2R-4
2R-24 2S-6 GFI GFI 2R-26 2S-8 GFI GFI 2S-6 2R-24
T - LS-1 1
2E- 6 EPP-EQ2 EPP - EQ1 ATS - EQ1 (4) CONDUIT UP TO PENTHOUSE 5 ATS - EQ2
2N-6
2N-10 2AS-27
2R-8
2R-8
2B- 17
CCCC
CCCC
CCCC
2N-30 2N-28 2N-30 2N-32 CCCC 2N-34 2N-32 2N-34 2M-1,3 2M-5,7 2M-9,11 2M-13,15
2N- 19,21 2N- 23,25 2N- 27,29 2N- 31,33 2N- 1,3 2N- 5,7 2N- 9,11 2N- 13,15
2Q-19,21 2Q-23,25 2Q-27,29 2Q-31,33 2Q- 1,3 2Q- 5,7 2Q- 9,11 2Q-13,15 2Q-35,37 2Q-39,41
2S- 19,21 2S- 23,25 2S- 27,29 2S- 31,33 2R- 1,3 2R- 5,7 2R- 9,11 2R- 13,15
CCCC
D.3
ELEVATOR #2 EP2
CP-11243
ARCH. MECH.
CCCC
CCCC
GFI
EWC 2B- 9
2P-35,37 2P-39,41
CCCC
CC C C
GFI
GFI 2M-17 2M-29 GFI 2M-31 GFI 2M-19 2M-33 GFI 2M-21 2M-35GFI 2M-33 2M-23
CORRIDOR 2HW2
2E-28 GENERATOR SHUTDOWN PUSH BUTTONS 2E-4
J. Kasdorf
ELEC.
R. Frazee
L.A.
CC
CC
CC
CC
2S- 28 2S- 30 2S- 28 2S- 30 2BS-38 2BS-34,36 2BS-42 5 2E- 13,15 2E- 9,11 2C- 26 2E-17 2E-17 2E-7 SKID 2E-37,39,41 DP - 1 2E- 2 ROLLER SHADE CONTROL PANEL 2C-38 2E-10 GFI WP 2E-14 G-1 1AE- 2 2E-10 2E-2 2E-12
D. Wilber
Project Administrator: Project Designer:
CORRIDOR 2HW1C
2B- 5
2B- 19
2B- 21
J. Johnson
Project Arch/Eng:
2M-25 RP - 2M 2M-27 RP - 2N
2B- 20
? ?
RP - 2P
RP - 2Q
RP - 2R
RP - 2S
T. Hackett
Q.M. Review:
E
2B- 22 2B- 13 GFI GFI 2B- 13 HAND DRYER 2B- 21 2C- 4 2C- 4 2C- 4 2C- 6 2C- 6 2C- 6 2C- 8 2C- 10 2C- 8 2C- 8 2C- 14 2C- 16 2C- 18 2C- 16 2C- 22 2C- 24 2C- 24 2C- 26 2C- 26
R. Bracci
Drawing Scale:
G-2
WORKROOM 2101
2C- 12
WORKROOM 2102
2C- 16 2C- 18 2C- 18 2C- 20 2C- 12 2C- 22 2C- 22
1/8" = 1'-0"
2E-12
2C- 24
2C- 14
2C- 14
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
GENDER NEUTRAL TOILET 2023
OFFICE 2111
OFFICE 2112
OFFICE 2113
OFFICE 2115
OFFICE 2116
OFFICE 2117
OFFICE 2118
OFFICE 2119
2E- 4
CUSTODIAL 2840
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
CORRIDOR 2HW1
2B- 23
2E-14
E.7
2B- 15 2C- 1 2B- 23 2C- 5 2C- 5 2C- 7 2C- 7 2C- 13 2C- 13 2C- 15 2C- 15 2C- 19 2C- 19
2D- 34 2E-31,33
2E-23
LOUNGE 2HW1B
2C- 1
2C- 3 2C- 3
2C- 9
2C- 9
2C- 11 2C- 11
2C- 17 2C- 17
2E-28
STAIR SW2-2
G
COLLABORATION SPACE 2030
SHADE CONTROL OVER RIDE PUSH BUTTON (TYP) ROLLER SHADE MOTOR (TYP)
c
12204-1000
Second Floor Plan - Power
1/2/2014 10:39:58 AM
NORTH
E3.2
OF
Bio-Engineering Facility
S. Hopper
CIVIL
2A- 6
2A- 6
2A- 8
WORKROOM 2301
2A- 10
WORKROOM 2302
2C- 32
2A- 4
CC
CC
CC
S. Gardner
APPR.
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
GENERAL NOTES________________________
1. STUB CONDUITS FROM RP-3A & RP-3B INTO LAB SHELL SPACE FOR FUTURE OFFICE AND WRITE-UP SPACE. RECEPTACLES IN IDENTICAL LAYOUT AS ON 2ND FLOOR. ALL RECEPTACLES IN EXTERIOR WALLS OF NORTH AND SOUTH WRITE-UP SPACE ARE INSTALLED IN GYP BOARD FIN TUBE ENCLOSURE AT 8" AFF TO CENTER. SEE DETAIL 8 ON A5.1. CONDUITS SHALL RUN HORIZONTALLY. PULL AN ADDITIONAL #10AWG FROM THE PANEL TO THE J-BOX FOR EVERY THREE RECEPTACLES IN LINEAR EQUIPMENT ROOM. TERMINATE WIRE ON SPACE, LEAVE 6" COILED IN BOX AND LABEL WITH PANEL CIRCUIT NUMBER.
2.
3.
4. CONDUITS IN FINISHED AREAS SHALL BE CONCEALED ABOVE NEW CORRIDOR CEILING. ALL JUNCTION BOXES ABOVE NEW CEILING SHALL BE ACCESSIBLE FROM AN ACCESS PANEL. 5. INSTALL RECEPTACLES FOR MOTORIZED ROLLER SHADE IN TOP OF SOFFIT APPROXIMATELY 8'-0" AFF AND WITHIN 2'-0" OF MOTOR. SEE DETAIL 9 ON A4.1.2. COORDINATE WITH SHADE INSTALLER. 6. ALL MOTORIZED SCREENS AND SHADES INSIDE CONFERENCE ROOMS SHALL BE CONTROLLED BY THE A/V SYSTEM UNLESS OTHERWISE NOTED.
KEYNOTES
1 4" CONCRETE PAD
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
A
3A-27
3A-20
LOUNGE 3HW1A
STAIR SW3-3
A.5 A.6
3A-27
3E-24
FCU-B
UH-B
3E-24
B
SHELL 3000
3B-14
3B-30 UH-B M
ELEVATOR #1 EP1
B.5
IT CLOSET 3011A
3B-2 TV 3B-6
3C-24 UH-B
SHELL 416
UH-B 3C-1
C.8 C.9
3B-5
3C-3 3C-5
D
UH-B M 3B-30
ELEVATOR #2 EP2
CORRIDOR 3HW1
3B-2
D.3
SHELL 3020 LAB SHELL OUT 3500
3B-19 3B-9 EWC 3B-19 3B-19 RP - 3C RP - 3D RP - 3E 4AE-3 1 4AE-5 3E-4 LP - 3 3C-1 3C-3 3C-5 EPP-EQ2 3E-4
CP-11243
UFC ROOM 3830
3E-28 3E-4 DP - 2 3E-2
ARCH.
4AE-1
CORRIDOR 3HW1C
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
3B-5
T. Hackett
Q.M. Review:
SHELL 3840
3E-2
R. Bracci
Drawing Scale:
As indicated
3E-4 3E-18 M UH-B
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
COLLABORATION SPACE 3030
3B-23 3B-15
3E-14
FCU-B 3E-18 M
E.7
LOUNGE 3HW1B
STAIR SW2-3
3B-23
G
SHADE CONTROL OVERRIDE PUSH BUTTON
12204-1000
Third Floor Plan - Power
1/2/2014 10:40:01 AM
NORTH
E3.3
OF
Bio-Engineering Facility
MECH.
S. Hopper
CIVIL
S. Gardner
APPR.
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
GENERAL NOTES________________________
1. STUB CONDUITS FROM RP-4A & RP-4B INTO LAB SHELL SPACE FOR FUTURE OFFICE AND WRITE-UP SPACE. RECEPTACLES IN IDENTICAL LAYOUT AS ON 2ND FLOOR. ALL RECEPTACLES IN EXTERIOR WALLS OF NORTH AND SOUTH WRITE-UP SPACE ARE INSTALLED IN GYP BOARD FIN TUBE ENCLOSURE AT 8" AFF TO CENTER. SEE DETAIL 8 ON A5.1. CONDUITS SHALL RUN HORIZONTALLY. PULL AN ADDITIONAL #10AWG FROM THE PANEL TO THE J-BOX FOR EVERY THREE RECEPTACLES IN LINEAR EQUIPMENT ROOM. TERMINATE WIRE ON SPACE, LEAVE 6" COILED IN BOX AND LABEL WITH PANEL CIRCUIT NUMBER.
2.
3.
4. CONDUITS IN FINISHED AREAS SHALL BE CONCEALED ABOVE NEW CORRIDOR CEILING. ALL JUNCTION BOXES ABOVE NEW CEILING SHALL BE ACCESSIBLE FROM AN ACCESS PANEL. 5. INSTALL RECEPTACLES FOR MOTORIZED ROLLER SHADE IN TOP OF SOFFIT APPROXIMATELY 8'-0" AFF AND WITHIN 2'-0" OF MOTOR. SEE DETAIL 9 ON A4.1.2. COORDINATE WITH SHADE INSTALLER. 6. ALL MOTORIZED SCREENS AND SHADES INSIDE CONFERENCE ROOMS SHALL BE CONTROLLED BY THE A/V SYSTEM UNLESS OTHERWISE NOTED.
KEY NOTES________________________
1 EXTEND CONDUIT UNDER 4TH FLOOR FOR CONF ROOM 4010 AND ROOMS TO SOUTH. INSTALL EXPOSED WHERE NO CEILING EXISTS AND UP INSIDE WALLS.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
A
4A-20 4B-27 SF-B 4A-22 4E-26
LOUNGE 4HW1A
A.5
4B-27 CUH
A.6
TV 4B-6 M
SHELL 4300
UH-B 4E-18 M
B
4B-14 4C-1
4C-3
4C-5
4B-12 UH-B
SHELL 417
B.5
4B-2
CORRIDOR 4HW1
B.7
4B-16 4B-14
TO EPP-LS
C C.1 C.2
RP - 4A RP - 4B
4C-3
STAIR SW1-4
UH-B
4C-1
C.8 C.9
4B-5
UH-B M
4B-30
4C-3
4C-5
4B-17 TV 4B-2
D.3
SHELL 4600 SHELL 4020 CORRIDOR 4HW1C
4B-9 EWC 4B-19 4B-19 4B-19
CP-11243
ARCH. MECH.
4AE-2 4E-28
J. Kasdorf
ELEC.
R. Frazee
4E-4 4E-10
RP - 4C ELP - 4E RP - 4D 4AE-4 RP - 4E
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
E
4B-21 4C-1
4C-3
4C-5
4E-12
SHELL 4840
4E-10
R. Bracci
Drawing Scale:
1/8" = 1'-0"
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
4B-15
4E-4
SHELL 4100
4B-23 SF-B 4B-15 4E-14
E.7
STAIR SW2-4
LOUNGE 4HW1B
4B-23
G
COLLABORATION SPACE 4030
SHADE CONTROL OVERRIDE PUSH BUTTON
12204-1000
Fourth Floor Plan - Power
1/2/2014 10:40:04 AM
NORTH
E3.4
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
GENERAL NOTES
1. FOR THE AHU AND ERU, EACH VFD SERVES TWO MOTORS. 2. CONSTRUCT UNISTRUT RACKS TO SUPPORT VFD AND STARTERS SEPARATE FROM EQUIPMENT.
KEYNOTES
1 4" CONCRETE PAD. EXTEND PAD BEYOND PANEL ENOUGH TO INSTALL A FUTURE FULL WIDTH PANEL SECTION AT PP-B &P-C.
4.5
4.5
5.5
6.5
7.5
8.5
10
WP GFI
PH-34 ACCH-1 4X
A.6
TO PP-B
GFI WP
B
VESTIBULE SW5-5A
PH-29 M 2 E3.5 TO PP-B PH-40 UH PH.1 HVAC-4A PH-31 VFD VFD VFD VFD VFD PH-33 M UH PH.3 HRP-1
SEF-1 WP GFI 4X
TO PP-C
PH-34 GFI
VFD VFD
C
4X GFI PH-36
PH-42
PCHP-2
C.1
TO VFD IN PENTHOUSE
WP
C C.1
VFD VFD VFD VFD VFD VFD VFD
TO PP-B
SEF-2 4X FC-1
PH-40
ATS-EQ 1
PH-33 PH-35
HVAC-1 TO EPP-LS
HVAC-2 M
CUH PH.2
TO PP-B WP GFI
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
PH-42
PH-34
C.9 D
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
TO EPP-LS TO PP-B VFD VFD VFD VFD VFD UH PH.2 PH-29 M PH-3B VFD TO PP-C
HVAC-4A
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
PH-31 1 1 PP - B UH PH.4
ELEVATOR #2 EP2
M PH-33
SEF-3 4X 4X
CP-11243
ARCH. MECH.
C.9
WP GFI
TO VFD IN PENTHOUSE
GFI WP TEF-1
3R
J. Kasdorf
ELEC.
R. Frazee
TO PP-B
L.A.
D. Wilber
Project Administrator: Project Designer:
PH-34
J. Johnson
E
SEF-4 4X
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
Drawing Scale:
As indicated
E.4
TO STARTERS IN PENTHOUSE
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
12204-1000
2 E3.5
1/2/2014 10:40:08 AM
NORTH
E3.5
OF
Bio-Engineering Facility
S. Hopper
CIVIL
PH-40
S. Gardner
APPR.
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
KEY NOTES
1 2 INSTALL TEMPERATURE OR SMOKE DETECTORS NEAR CENTER OF BEAM POCKETS. (3) 4" CONDUIT SLEEVES ABOVE CEILING WITH BUSHINGS THRU WALL. DUCT SMOKE DETECTOR IN DUCTWORK ABOVE CEILING TO CLOSE DAMPER AND SHUT DOWN AHU UPON ACTIVATION. INSTALL REMOTE INDICATOR IN CEILING. 2-3" CONDUIT ACROSS BRIDGE FOR FIBER CABLE. CARD READER MOUNTED TO ARCH. PROVIDED BOLLARD. EXTEND 1" SECURITY CONDUIT UNDERGROUND AND TURN UP INSIDE INTERIOR WALL TO ABOVE CEILING AND OVER TO CABLE TRAY. PROVIDE FOUR (4) FIRE ALARM MONITOR MODULES, ONE (1) FIRE ALARM ADDRESSABLE RELAY MODULE AND ONE (1) CONTROL RELAY MODULE MOUNTED IN AUTOMATIC DOOR/WINDOW OPERATOR.
GENERAL NOTES
1. ALL WIREMOLD INDICATED ON AUXILIARY SYSTEMS PLANS IS SHOWN FOR REFERENCE ONLY AND IS A DUPLICATE OF WIREMOLD SHOWN ON POWER PLANS. 2. AT
C 4D
INSTALL 1 1/4" CONDUIT FROM CABLE TRAY TO J-BOX IN CEILING SERVICE PANEL (CSP) PROVIDED BY LAB CASEWORK SUPPLIER. INSTALL 1" CONDUIT FROM CABLE TRAY TO J-BOX IN CEILING SERVICE PANEL (CSP) PROVIDED BY LAB CASEWORK SUPPLIER. INSTALL DATA OUTLETS FOR MOTORIZED ROLLER SHADE CONTROL WIRING IN TOP OF SOFFIT AT APPROXIMATELY 8'-0" AFF AND WITHIN 2'0" OF MOTOR. EXTEND 1/2" EMPTY CONDUIT TO SHADE CONTROL PANEL IN ELECTRICAL ROOM. COORDINATE WITH SHADE INSTALLER.
3. AT
2D
4 5 6
4. AT
5.
ALL DATA IN EXTERIOR WALLS OF NORTH AND SOUTH WRITE-UP SPACE ARE INSTALLED IN GYP BOARD FIN TUBE ENCLOSURE AT 14" AFF TO CENTER. SEE DETAIL 8 ON A5.1. CONDUITS SHALL RUN HORIZONTALLY TO PULL BOX IN END WALLS. EXTEND 2" CONCEALED CONDUIT FROM J-BOX TO CABLE TRAY.
6. CONDUIT SERVING TELECOMMUNICATION OUTLETS SHALL BE 1" MINIMUM. CONDUITS WITH MORE THAN (1) 90 DEGREE BEND SHALL BE 1-1/4" MINIMUM. CONDUITS SHALL NOT HAVE MORE THAN THE EQUIVALENT OF (2.5) 90 DEGREE BENDS BETWEEN THE OUTLET AND THE CABLE TRAY. 7. WIRELESS ACCESS POINTS SHALL HAVE 1" CONDUIT TO NEAREST CABLE TRAY OR UFC ROOM. 8. ALL UFC AND FIBER ROOMS SHALL HAVE 8' HIGH 3/4" FIRE RATED PLYWOOD MOUNTED TO THREE (3) WALLS. 9. INSTALL LAB SMOKE DETECTORS CENTERED IN 6" WIDE CEILING PANELS. 10. INSTALL BEAM SMOKE DETECTOR AND RECEIVER AT APPROXIMATELY 10'-6" AFF TO AVOID 11"0" CEILING UNDER BRIDGES.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
6 5
CR S
WP
12"X12"X4" PULLBOX
VESTIBULE 1VB1
M F
7
TV
M
4D
F AV
4D
4D 30cd
4D
4D
4D
4D 30cd
4D
4D
4D
S ID,IT 30cd WP
S CR SD
F
30cd
W
AV
S CR
AV
S CR
30cd
F
BR F
60cd
AV S CR
STAIR SW3-1
A.5
F
WAP/C
A.6
AV WAP/C
S
WORKROOM 1301
OFFICE 1314
OFFICE 1315
OFFICE 1316
WORKROOM 1302
OFFICE 1317
WAP/C
OFFICE 1318
OFFICE 1319
CR S
F
SD
F
SD
S CR
F F
30cd
30cd
30cd
F
SD
30cd
SD
CORRIDOR 1450
F
SD
WAP/C
CR S
CORRIDOR 1HW1
F
S CR
MECHANICAL 1611
ID
ID
ID
ID
3
F DD
18" WIDE
F TS F WF F TS F WF
AV
ELEVATOR #1 EP1
F
SD
4D
2D
F
SD
4D
F
SD
2D
4D
F
SD
2D
SD
60cd
B.5
IT CLOSET 1011A
SD
4
F
S
F TS
F WF
TD
TD
TD
TD
4D
LAB 1400
4D
4D
F
SD
F
SD
F
SD
18" WIDE
F AV
DD
B.7 C
KITCHENETTE F 1011
SD SD
30cd
3 1
S CR
F F F F F F F F
C.1
F
WAP/C SD
F
SD
F
SD
F F
SD
C.2
TV
WAP/C
CR S
F
SD
F
SD
F
SD
F
SD
F
SD TD
1
TD TD TD
F
SD
ABOVE LANDING
WAP/C
60cd
F
SD
F MM
3
F DD
C.8 C.9 D
TV TV
30cd
F
F
F F
SD SD SD
F
SD
F
SD
F
SD
F MM F MM
60cd
TV
F
TD
CR S
F
F
SD
3
F WAP/C
F
SD
F
SD
F
30cd
AV
F
DD
D.3
MEN'S TOILET 1021 CORRIDOR 1HW1C
F F F
S CR
F
SD
F
SD
F
SD
F TS
F WF
CR S
CR S
FACP
FACP
CR S
CP-11243
ARCH. MECH.
SD
CR S
F
SD
LAB 1200
4D
F
4D
F
F
SD
ID
CORRIDOR 1HW2
S CR
F
SD V
J. Kasdorf
ELEC.
SD
SD
S CR
S CR
F TS
F WF
R. Frazee
S CR
F
S CR
L.A.
F
SD SD SD CR S
S CR
4D
2D
4D 18" WIDE
2D
WAP/C
4D
2D
D. Wilber
Project Administrator:
TD
E
F
SD
CR S
ID,IT
F AV
ID,IT
ID,IT
ID,IT
F AV
TD
S CR
2
F
SD
F F
WORKROOM 1040A
F
SD
F
CORRIDOR 1250
SD
F F
SD
J. Johnson
F
30cd
30cd
30cd
30cd
CR S
S CR
UNASSIGNED 1840
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
Drawing Scale:
OFFICE 1111
OFFICE 1113
ID,IT
WORKROOM 1101
OFFICE 1114
OFFICE 1115
OFFICE 1116
WORKROOM 1102
OFFICE 1117
WAP/C
OFFICE 1118
OFFICE 1119
1/8" = 1'-0"
WP
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
BT
60cd
AV W
F TS
F WF
E.7
F M M
7 VESTIBULE 1VB2
AV
ID,IT 4D S 4D 4D 4D S 4D 4D 4D S 4D 4D 4D S
F
M M
CR S
30cd
AV
AV
30cd
30cd
STAIR SW2-1
30cd
S C
G
CR S
12"X12"X4" PULLBOX WITH 2"C UP TO CEILING SPACE AND OVER TO CABLE TRAY
c
6 5
12204-1000
First Floor Plan - Auxiliary Systems
1/2/2014 10:40:10 AM
NORTH
E4.1
OF
Bio-Engineering Facility
S. Hopper
CIVIL
ID,IT
S CR
ID,IT
ID,IT
F AV
ID,IT
ID,IT
ID,IT
AV F
ID,IT
ID,IT
ID,IT
TD
S. Gardner
APPR. Project Designer:
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
TV TV TV TV TV TV
INSTALL 1 1/4" CONDUIT FROM CABLE TRAY TO J-BOX IN CEILING SERVICE PANEL (CSP) PROVIDED BY LAB CASEWORK SUPPLIER. INSTALL 1" CONDUIT FROM CABLE TRAY TO J-BOX IN CEILING SERVICE PANEL (CSP) PROVIDED BY LAB CASEWORK SUPPLIER. INSTALL DATA OUTLETS FOR MOTORIZED ROLLER SHADE CONTROL WIRING IN TOP OF SOFFIT AT APPROXIMATELY 8'-0" AFF AND WITHIN 2'0" OF MOTOR. EXTEND 1/2" EMPTY CONDUIT TO SHADE CONTROL PANEL IN ELECTRICAL ROOM. COORDINATE WITH SHADE INSTALLER.
3. AT
2D
4 5
4. AT
ALL DATA IN EXTERIOR WALLS OF NORTH AND SOUTH WRITE-UP SPACE ARE INSTALLED IN GYP BOARD FIN TUBE ENCLOSURE AT 14" AFF TO CENTER. SEE DETAIL 8 ON A5.1. CONDUITS SHALL RUN HORIZONTALLY TO PULL BOX IN END WALLS. EXTEND 2" CONCEALED CONDUIT FROM J-BOX TO CABLE TRAY.
6. CONDUIT SERVING ALL OTHER DATA OUTLETS SHALL BE 1" MINIMUM. CONDUITS WITH MORE THAN (1) 90 DEGREE BEND SHALL BE 1-1/4" MINIMUM. CONDUITS SHALL NOT HAVE MORE THAN THE EQUIVALENT OF (2.5) 90 DEGREE BENDS BETWEEN THE OUTLET AND THE CABLE TRAY. 7. WIRELESS ACCESS POINTS SHALL HAVE 1" CONDUIT TO NEAREST CABLE TRAY OR UFC ROOM. 8. ALL UFC AND FIBER ROOMS SHALL HAVE 8' HIGH 3/4" FIRE RATED PLYWOOD MOUNTED TO THREE (3) WALLS. 9. INSTALL LAB SMOKE DETECTORS CENTERED IN 6" WIDE CEILING PANELS. 10. INSTALL BEAM SMOKE DETECTOR AND RECEIVER AT APPROXIMATELY 10'-6" AFF TO AVOID 11"0" CEILING UNDER BRIDGES.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
12"X12"X4" PULLBOX S
F
BR
4D
4D
4D
4D
4D
4D
4D
4D
4D
4D
S ID,IT
CR S F
F
LOUNGE 2HW1A
WAP/C F
30cd
AV
60cd
AV
SD
30cd
30cd
CR S
ADMIN 2060
AV
60cd
TV
AV
4
F
STAIR SW3-2
A.5 A.6
F AV
CR S
CR S
30cd
F
OFFICE 2311
OFFICE 2312
WORKROOM 2301
OFFICE 2314
OFFICE 2315
OFFICE 2317
OFFICE 2318
WAP/C
F
SD
SD
ID,IT
ID,IT
ID,IT
ID,IT
S CR F AV
ID,IT
ID,IT
ID,IT
F S CR AV
ID,IT
F
F DD SD 3
30cd
30cd
30cd
30cd
CR S
WAP/C
TD
ID
ID
ID
ID
18" WIDE
F
F
F AV
4D
2D
4D
2D
4D
2D
4D
2D
4D
SD
F
CR S SD C AV F
LAB 2400
SD C WAP/C
F
SD C
F
SD
B.5
F
SD
30cd 4D
C
S CR
CORRIDOR 2HW3
F AV
4D
4D
4D
TD
F
SD
TD
S CR
F
SD
S CR
60cd
AV
30cd
DD
F DR
CORRIDOR 2HW1D
3
S CR
F
SD
F F
SD SD
F
SD
F
SD
F F
SD SD
F
SD
SUBSTATION 2810
F
SD
F
SD
COORDINATE LOCATION OF ETHERNET CONNECTION, FOR SUBSTATION METERING, WITH MSU FACILITY OPERATIONS.(TYP)
WAP/C
SD
ABOVE LANDING
30cd
F
TD
WAP/C
TD
18" WIDE F
SD
F
SD
3
F DD
C.8
F
SD
SD
SD
SD
SD
SD
SD
C.9
F F F F F F F F F F
SD
ELEVATOR #2 EP2
30cd
TD
F
SD
CR S F
F
DD
60cd
WAP/C F AV F DD
F DR
D.3
F
CP-11243
ARCH. MECH.
C S
CORRIDOR 2HW1C
F
4D
WAP/C
C SD
4D
C SD
4D
C SD
CORRIDOR 2HW2
F
SD
4D
SD
F F
SD
F FACP
J. Kasdorf
ELEC.
S CR
R. Frazee
L.A.
F LAB SD SUPPORT
4D
2D
4D 18" WIDE
LAB 2D 2200
C 4D
2D
4D
2D
WAP/C
4D
F
SD
7 ID
SD
2
SD
REMOTE FACP
F
D. Wilber
ID
Project Administrator:
J. Johnson
SD
Project Arch/Eng:
F
E
F
30cd
30cd
CR S
30cd
CR S
30cd
S CR
T. Hackett
Q.M. Review:
AV
R. Bracci
Drawing Scale:
OFFICE 2111
AV
1/8" = 1'-0"
F
WORKROOM 2101
OFFICE 2115
Issue Date:
CUSTODIAL 2840
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
WORKROOM 2102
OFFICE 2117
OFFICE 2118
OFFICE 2119
E.4
60cd
CR S
WAP/C
F
E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
S CR
AV
F TS F WF
CR S
AV
AV
E.7
30cd
30cd
F
SD
30cd ID,IT
BT
4D
F
4D
4D
4D
4D
4D
4D
4D
4D
4D
STAIR SW2-2
S 12"X12"X4" PULLBOX
G
COLLABORATION SPACE 2030
c
12204-1000
Second Floor Plan - Auxiliary Systems
1/2/2014 10:40:13 AM
NORTH
E4.2
OF
Bio-Engineering Facility
S. Hopper
CIVIL
OFFICE 2319
MECHANICAL 2611
F
S. Gardner
APPR. Project Designer:
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
TV
TV
GENERAL NOTES
S
1. AT
2. CONDUIT SERVING DATA OUTLETS SHALL BE 1" MINIMUM. CONDUITS WITH MORE THAN (1) 90 DEGREE BEND SHALL BE 1-1/4" MINIMUM. CONDUITS SHALL NOT HAVE MORE THAN THE EQUIVALENT OF (2.5) 90 DEGREE BENDS BETWEEN THE OUTLET AND THE CABLE TRAY. 3. IN AREAS OF EXPOSED CONSTRUCTION, SUPPORT BEAM DETECTORS FROM STRUCTURE AT APPROXIMATELY 14' AFF SO THEY ARE BELOW THE 21" DEEP BEAMS AT COLUMN LINES B,C,D,& E. PROVIDE ADDITIONAL DETECTORS WHERE BEAM DETECTORS DO NOT PROVIDE COVERAGE.
4. ALL UFC AND FIBER ROOMS SHALL HAVE 8' HIGH 3/4" FIRE RATED PLYWOOD MOUNTED TO THREE (3) WALLS.
KEY NOTES
1 2 3 INSTALL TEMPERATURE OR SMOKE DETECTORS NEAR CENTER OF BEAM POCKETS. (3) 4" CONDUIT SLEEVES WITH BUSHINGS THRU WALL. DUCT SMOKE DETECTOR IN DUCTWORK ABOVE CEILING TO CLOSE DAMPER AND SHUT DOWN AHU UPON ACTIVATION. INSTALL REMOTE INDICATOR ON SHAFT WALL AT 8'-0". 2-3" CONDUIT ACROSS BRIDGE FOR FUTURE FIBER CABLE. INSTALL CARD READER NEAREST TO DOOR JAMB AND PULL STATION ADJACENT IN THE 8" WIDE GYP BOARD.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
A
BR
S S
F
110cd
F
BR
110cd
F
BR
110cd
F
BR
LOUNGE 3HW1A
60cd
F WAP/C AV
5
F
F
SD
SHELL 3300
A.5 A.6
F AV
S CR
S CR
CR S
STAIR SW3-3
F
BR
SHELL 3000
SD
SD
B
3
F
1
DD
F
SD
F
BR
110cd
F
ELEVATOR #1 EP1
F AV
B.5
IT CLOSET 3011A
F
SD
4
AV F DD
3 60cd
F AV
1
F
SD
F
SD
F
SD
F
SD
SHELL 416
ABOVE LANDING
STAIR SW1-3
F
SD
F F
3
F BT DD
C.8 C.9
F
D
SHELL 3020
DD
F
SD F
ELEVATOR #2 EP2
110cd
110cd
60cd
110cd
CORRIDOR 3HW1
60cd
F AV
DD
D.3
S CR
CP-11243
F
SD
F
SD BT
ARCH.
J. Kasdorf
F
S CR
FACP
REMOTE FACP
ELEC.
R. Frazee
L.A.
2
F
SD
D. Wilber
ID 60cd
F
Project Administrator:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
1
TV
R. Bracci
Drawing Scale:
F
SD
1/8" = 1'-0"
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
WAP/C F
60cd
AV
CR S
CR S
F
SD
F TS F WF
E.7
LOUNGE 3HW1B
BT
110cd
BT
110cd
BT
110cd
BT
G
c
CR S
STAIR SW2-3
12204-1000
Third Floor Plan - Auxiliary Systems
1/2/2014 10:40:14 AM
NORTH
E4.3
OF
Bio-Engineering Facility
MECH.
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
INSTALL DATA OUTLETS FOR MOTORIZED ROLLER SHADE CONTROL WIRING IN TOP OF SOFFIT AT APPROXIMATELY 8'-0" AFF AND WITHIN 2'0" OF MOTOR. EXTEND 1/2" EMPTY CONDUIT TO SHADE CONTROL PANEL IN ELECTRICAL ROOM. COORDINATE WITH SHADE INSTALLER.
TV
1. AT
INSTALL DATA OUTLETS FOR MOTORIZED ROLLER SHADE CONTROL WIRING IN TOP OF SOFFIT AT APPROXIMATELY 8'-0" AFF AND WITHIN 2'0" OF MOTOR. EXTEND 1/2" EMPTY CONDUIT TO SHADE CONTROL PANEL IN ELECTRICAL ROOM. COORDINATE WITH SHADE INSTALLER.
2. CONDUIT SERVING TELECOMMUNICATION OUTLETS SHALL BE 1" MINIMUM. CONDUITS WITH MORE THAN (1) 90 DEGREE BEND SHALL BE 1-1/4" MINIMUM. CONDUITS SHALL NOT HAVE MORE THAN THE EQUIVALENT OF (2.5) 90 DEGREE BENDS BETWEEN THE OUTLET AND THE CABLE TRAY. 3. IN AREAS OF EXPOSED CONSTRUCTION, SUPPORT BEAM DETECTORS FROM STRUCTURE AT APPROXIMATELY 14' AFF SO THEY ARE 3" BELOW THE 21" DEEP BEAMS AT COLUMN LINES B,C,D,& E. 4. ALL UFC AND FIBER ROOMS SHALL HAVE 8' HIGH 3/4" FIRE RATED PLYWOOD MOUNTED TO THREE (3) WALLS.
KEY NOTES
1 2 3 INSTALL TEMPERATURE OR SMOKE DETECTORS NEAR CENTER OF BEAM POCKETS. (3) 4" CONDUIT SLEEVES WITH BUSHINGS THRU WALL. DUCT SMOKE DETECTOR IN DUCTWORK ABOVE CEILING TO CLOSE DAMPER AND SHUT DOWN AHU UPON ACTIVATION. INSTALL REMOTE INDICATOR ON SHAFT WALL AT 8'-0". INSTALL CARD READER NEAREST TO DOOR JAMB AND PULL STATION ADJACENT IN THE 8" WIDE GYP BOARD. EXTEND CONDUIT UNDER 4TH FLOOR FOR CONF. 4010. EXPOSED WHERE NO CEILING EXISTS UP INTO WALL.
0.1
1.9
2.6
2.9
4.5
5.5
6.5
7.5
8.5
9.5
10
10.3
10.4
10.9
11
S
BR
BT
110cd
BT
110cd
BT
110cd
4
F
A.5 A.6
F AV
60cd
S CR
S CR
CR S
BR
1
TV
SD
1
F
SD
B
F
SD F DD
3
BR
110cd
F
TD AV
S CR
B.5
TD
B.7
SD
DD
3
F
F
C C.1 C.2
60cd
SHELL 417
1 ABOVE LANDING 5
SD
F F
3
F BT DD
C.8 C.9
F
110cd
F
SD
60cd
F DD
ELEVATOR #2 EP2
DD
BT
60cd
60cd
60cd
D.3
SD SD SD
CP-11243
F
F
F
? ?
S CR
SD
SD
ARCH.
J. Kasdorf
ELEC.
REMOTE FACP
FACP
R. Frazee
L.A.
2
F
SD
D. Wilber
ID
SD
Project Administrator:
F
J. Johnson
Project Arch/Eng:
T. Hackett
E
F F
Q.M. Review:
1
F
R. Bracci
Drawing Scale:
TD SD
SHELL 4840
1/8" = 1'-0"
1
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
60cd
F
CR S
CR S
F
CR S
F TS F WF
E.7
STAIR SW2-4
F
F
SD
BT
S S
110cd
F
BT
110cd
BT
110cd
F
BT
G
c
12204-1000
Fourth Floor Plan - Auxiliary Systems
1/2/2014 10:40:16 AM
NORTH
E4.4
OF
Bio-Engineering Facility
MECH.
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
GENERAL NOTES
TV
B
VESTIBULE SW5-5A
60cd
60cd
60cd
60cd
TD
TD
B.5
B.5
F TD DD F DD TD F DD F DD TD
TD F DD
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
TD
HVAC-3
B.7
B.7
F DD
F
TD
C C.1 C.2
C C.1 C.2
HVAC-1 HVAC-2
TD
60cd
TD
DD
F
TD
DD
DD
DD
DD
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
HVAC-4
TD TD F
TD DD
CR S
FAAP
30cd
TD
F F
TD
C.8 C.9 D
C.8 C.9
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
ELEVATOR #2 EP2
F
TD
D
TD
Face Width and Face Height have minimum dimensions of 12" and maximum dimensions of 144"
F
TD TD
D.3
2 E2.5
60cd
60cd
60cd
F F
60cd
F
60cd
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
Drawing Scale:
1/8" = 1'-0"
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
E.4 E.5
D:\Revit Local\122041000-MSU BioEngineering-E14_Central_sschiappacasse.rvt
E.7
G
c
12204-1000
Penthouse Plan - Auxiliary Systems
1/2/2014 10:40:19 AM
NORTH
E4.5
OF
Bio-Engineering Facility
S. Hopper
CIVIL
F F
F F
S. Gardner
APPR.
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
C. PROVIDE A COMMUNICATIONS OUTLET ADJACENT TO THE PULL BOX FOR ETHERNET CONNECTION. D. INSTALL A 3/4 INCH CONDUIT FROM THE COMMUNICATION OUTLET TO THE PULL BOX AND A ONE CONDUIT FROM THE PULL BOX TO THE BROADBAND UTILITY ROOM. E. INSTALL A 1/2 INCH CONDUIT FROM EACH WATER, NATURAL GAS, STEAM, AND CONDENSATE TO THE PULL BOX FOR NETWORKING THE BUILDING UTILITY METERS. INCH
THW THHW
METER
1600NG 5@[4#500 KCM, 1#4/0 GRD - 3-1/2"C] 1600G 5@[3#500 KCM, 1#4/0 GRD - 3"C] 2000G 6@[3#500 KCM, 1#250 KCM GRD - 3-1/2"C] 2000NG 6@[4#500 KCM, 1#250 KCM GRD - 3-1/2"C] 600NBG 2@[4#350 KCM, 1#2/0 GRD - 3"C] 800NBG 2@[4#500 KCM, 1#2/0 GRD - 3-1/2"C]
NOTES: 1. 2. 3. GROUND WIRES SHOWN IN CONDUIT AND WIRE SCHEDULE ARE EQUIPMENT GROUNDING CONDUCTORS SIZED PER NEC TABLE 250-122. GROUNDING ELECTRODE CONDUCTORS SHOWN FOR MAIN DISTRIBUTION PANEL AND TRANSFORMER NEUTRALS ARE SIZED PER NEC TABLE 250-66. BONDING CONDUCTORS FOR MAIN SERVICE AND ALL DERIVED SERVICES SHOWN ARE SIZED PER NEC TABLE 250-66.
125E
125E
80E
80E ATO
T-1
T-2
T-3
T-4
TRANSITION FIRE PUMP TAP 2000/2300 KVA OA/FA 13.2KV - 480/277V 3P, 4W, 65 DEG C RISE LIQUID FILLED (LESS FLAMMABLE)
GROUND NEUTRAL BONDING JUMPER K TIE 3200AF 2800AT LSG 800AF 800AF N.O.
TRANSITION FIRE PUMP TAP 2000/2300 KVA OA/FA 13.2KV - 480/277V 3P, 4W, 65 DEG C RISE LIQUID FILLED (LESS FLAMMABLE)
800AF MAIN 3200AF 2800AT LSG K N.C. T-1 1000NG TAP CONDUCTORS SHALL BE LESS THAN 25'-0" LONG DISCONNECT SWITCH SHALL BE SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT PAINT SWITCH RED AND LABEL WITH 1" HIGH (MINIMUM) LETTERS "FIRE PUMP DISCONNECTING MEANS"
800AF
800AF
SPARE
SPARE
SPARE
EQUIPPED SPACE
EQUIPPED SPACE
SPARE
EQUIPPED SPACE
EQUIPPED SPACE
SPARE
EQUIPPED SPACE
N.C. T-2
400NG
800G
800G
800NG
1000NG
TAP CONDUCTORS SHALL BE LESS THAN 25'-0" LONG GROUND 800/ 800AF NEUTRAL GROUND GROUND GROUND 800/ 800AF
DISCONNECT SWITCH SHALL BE SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT PAINT SWITCH RED AND LABEL WITH 1" HIGH (MINIMUM) LETTERS "FIRE PUMP DISCONNECTING MEANS"
150G
150G
CONTINUED ON E5.2
CONTINUED ON E5.2
CONTINUED ON E5.2
CONTINUED ON E5.2
ATS-FIRE PUMP
225A, 480V, 3P PROVIDED BY FIRE PUMP MANUFACTURER
PROVIDE PLACARD NEXT TO CONTROLLER INDICATING LOCATION OF DISCONNECT SWITCHES. COORDINATE REQUIREMENTS WITH MSU PROJECT MANAGER
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
TRANSITION
GROUND NEUTRAL BONDING JUMPER K TIE 3200AF 3200AT LSG 800AF N.O.
TRANSITION
R. Bracci
Drawing Scale:
No Scale
1000/1150 KVA OA/FA 13.2KV - 208/120V 3P, 4W, 65 DEG C RISE LIQUID FILLED (LESS FLAMMABLE)
1000/1150 KVA OA/FA 13.2KV - 208/120V 3P, 4W, 65 DEG C RISE LIQUID FILLED (LESS FLAMMABLE)
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
800AF
800AF
EQUIPPED SPACE
SPARE
SPARE
EQUIPPED SPACE
EQUIPPED SPACE
EQUIPPED SPACE
EQUIPPED SPACE
SPARE
SPARE
800NG
800NG
800NG
800NG
BD-1
GROUND NEUTRAL GROUND NEUTRAL
BD-2
12204-1000
BD-4
BD-3
1/2/2014 10:40:20 AM
CONTINUED ON E5.3
CONTINUED ON E5.3
NORTH
E5.1
OF
CONTINUED ON E5.3
CONTINUED ON E5.3
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
T. Hackett
Drawn By:
A. Jantz
Approved:
R. Bracci
Date:
B. INSTALL A 1-1/2 INCH CONDUIT FROM THE MAIN METERING COMPARTMENT TO A PULL BOX LOCATED ON THE TRANSFORMER VAULT SOUTH WALL.
GENERAL NOTES
1. SEE E5.1 FOR CONDUIT AND WIRE SCHEDULE.
GROUND
NEUTRAL
GROUND NEUTRAL
LDP-A
480/277V, 3PH, 4W 400A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM).
PP-C
480/277V, 3PH, 4W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM). 1 2 3 4 5 6 7 8 -11 12 -15 7 16 17 18
100A 3P
100A 3P
100A 3P
100A 3P
100A 3P
100A 3P
100A
100A
100A
100A
100A 3P
100A 3P
30A 3P
200A 3P
200A 3P
30A 3P
200A 3P
60A 3P
30A 3P
200A 3P
30A 3P
30A 3P
30A 3P
100A
20A
125A
125A
20A
150A
150A
15A
15A
20A
SPARE 115NG 115NG 115NG 115NG 115G VFD LP- 1 LP- 2 LP- 3 LP- 4 115G 115G VFD 115G 20G VFD 20G 115G VFD 115G 115G VFD 115G 20G VFD 20G 150NG
SPARE
150NG
20G
20G
20G
VFD HVAC-3 HVAC-3 HVAC-3 HVAC-4 HVAC-4 HVAC-4 FUTURE 128A 20G
VFD 20G
VFD 20G
PCHP- 1 10 HP 14 FLA
TO GROUNDING SYSTEM
GROUND
PP-A
100A 3P
100A 3P
30A 3P
30A 3P
60A 3P
60A 3P
30A 3P
30A 3P
30A 3P
30A 3P
30A 3P
30A 3P
30A 3P
30A 3P
30A 3P
30A 3P
100A 3P
30A 3P
30A 3P
30A 3P
60A 3P
60A 3P
30A 3P
30A 3P
80A
80A
15A
15A
60A
50A
20A
20A
20A
20A
20A
20A
20A
20A
20A
30A
100A
30A
30A
20A
15A
15A
SPARE
SPARE
85G
85G
20G
20G
55G
55G
20G
40G
40G
40G
40G
20G
20G
20G
20G
20G
40G
20G
20G
20G
40G VFD 85G +2#14 VFD 85G +2#14 VFD 20G +2#14 VFD 20G +2#14 4 @10 HP 56A CHWP- 1 40 HP 52 FLA CHWP- 2 40 HP 52 FLA HWHP- 1 5 HP 7.6 FLA HWHP- 2 5 HP 7.6 FLA 2 @15 HP 42A 10 HP 14A ST-1 16A ST-2 16A LV-1 LAC-1 DWBP-1 ST-1 ST-2
40G
40G
40G
20G
20G
20G
20G
20G
30G
ST-3
ST-4
GW- 1
GW- 2
GW- 3
GW- 4
HGC-
MDU-
20G +2#14
DC- 1
DC- 2
ST-3 16A
ST-4 16A
GW-1 16A
GW-2 16A
GW-3 16A
GW-4 16A
3@1/2HP 2.2A
2@1/2HP 3.3A
CP-11243
TO GROUNDING SYSTEM FIRE PUMP TAP METERING 800A 800A 800A SPARE 800A METERING FIRE PUMP TAP
ARCH.
J. Kasdorf
ELEC.
GROUND
MAIN
800A SPACE
800A SPARE
800A SPACE
800A SPARE
MAIN
R. Frazee
L.A.
800A SPARE
800A SPACE
TIE
800A SPACE
D. Wilber
Project Administrator: Project Designer:
PP-B
480V, 3PH, 3W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM). 800A SPACE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 800A SPACE 800A SPACE 800A
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
480/277V
400A 3P 100A 3P 100A 3P 100A 3P 30A 3P 60A 3P 60A 3P 30A 3P 30A 3P 60A 3P 60A 3P 30A 3P 30A 3P 60A 3P 80A 3P 60A 3P 60A 3P (1) 60A 3P SPACE (1) 60A 3P SPACE
Drawing Scale:
No Scale
250A
100A
100A
100A
15A
50A
50A
25A
25A
50A
50A
25A
25A
50A
5A
SUBSTATION #1 ELEVATION
NTS
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
SPARE
SPARE
255G
30G VFD
55G
20G
TRANSITION 30G 4X HVAC-1 HVAC-1 HVAC-1 HVAC-2 HVAC-2 HVAC-2 HVAC-2 FC-1 60A TO RELAY BY TEMP CONTROL CONTRACTOR 4X ACCH-1 400A
METERING
800A
800A
800A
800A
METERING
TRANSITION
MAIN
800A
800A SPARE
800A SPACE
800A SPARE
MAIN
800A SPARE
800A SPACE
TIE
800A SPARE
c
ACCH-1 140A
LEF-160 HP 77 FLA
LEF-260 HP 77 FLA
LEF-360 HP 77 FLA
SF-1 & 2 2 @ 15 HP 42 A
SF-3 & 4 2 @ 15 HP 42 A
36.9A
800A SPACE
800A SPACE
800A SPACE
800A
12204-1000
208/120V
SUBSTATION #2 ELEVATION
NTS
1/2/2014 10:40:21 AM
E5.2
OF
Bio-Engineering Facility
MECH.
480V, 3PH, 3W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM).
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
S. Hopper
CIVIL
S. Gardner
APPR.
T. Hackett
Drawn By:
A. Jantz
Approved:
R. Bracci
Date:
GENERAL NOTES
1. SEE E5.1 FOR CONDUIT AND WIRE SCHEDULE.
TO SUBSTATION No. 3
TO SUBSTATION No. 4
BD-1
208/120V, 3PH, 4W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM). 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF
BD-2
208/120V, 3PH, 4W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM). 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
RP- 1F
RP- 1G
RP- 1H
RP- 1J
RP- 1K
RP- 1L
RP- 1M
RP- 1N
RP- 1P
RP- 1Q
RP- 2F
RP- 2G
RP- 2H
RP- 2J
RP- 2K
RP- 2L
RP- 2M
RP- 2N
RP- 2P
RP- 2Q
RP- 2R
TO SUBSTATION No. 3
TO SUBSTATION No. 4
Load Summary BD-3 Total Connected Total Demand Load Load BD-3
208/120V, 3PH, 4W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM). 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF
Load Summary BD-4 Total Connected Total Demand Load Load BD-4
208/120V, 3PH, 4W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM). 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF 100/ 100AF
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
115NG
RP- 3F
RP- 3G
RP- 3H
RP- 3J
RP- 3K
RP- 3L
RP- 3M
RP- 3N
RP- 3P
RP- 3Q
RP- 4F
RP- 4G
RP- 4H
RP- 4J
RP- 4K
RP- 4L
RP- 4M
RP- 4N
RP- 4P
RP- 4Q
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
TO SUBSTATION No. 3 TO GROUNDING SYSTEM TO SUBSTATION No. 4 TO GROUNDING SYSTEM
R. Bracci
Drawing Scale:
No Scale
Load Summary DP-1
Total Connected Load 213.0 KVA Total Connected Load 177.0 KVA GROUND NEUTRAL
GROUND NEUTRAL
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
DP-1
208/120V, 3PH, 4W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM). 1 2 3 4 5 6 7 8 9 10 11
DP-2
208/120V, 3PH, 4W 800A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 22,000 AMPERES RMS SYMMETRICAL (MINIMUM). 1 2 3 4 5 6 7 8 9 10 11 12
200A 3P
200A 3P
200A 3P
200A 3P
200A 3P
200A 3P
400A 3P
200A 3P
200A 3P
200A
200A
200A
200A
200A
200A
400A
200A 3P
200A 3P
200A 3P
200A 3P
200A 3P
200A 3P
200A 3P
400A 3P
200A 3P
200A 3P
200A
200A
200A
200A
200A
200A
200A
400A
SPARE
SPARE
SPARE
SPARE
200NG
200NG
200NG
200NG
200NG
200NG
400NG
200NG
200NG
200NG
200NG
200NG
200NG
200NG
400NG
12204-1000
RP- 1A 1 200NG RP- 1B RP- 1D RP- 1C 1 200NG 15.4 kVA 12.7 kVA RP- 2B RP- 1E RP- 2A 1 200NG RP- 2D RP- 2C 1 200NG 15.0 kVA 12.5 kVA RP- 3B RP- 2E TO ATS-EQ1 74.0 kVA 57.0 kVA SEE E5.4 RP- 3A 1 200NG RP- 3D RP- 3C 1 200NG 11.7 kVA 10.8 kVA RP- 4B RP- 3E RP- 4A 1 200NG RP- 4D RP- 4C 1 200NG RP- 4E RP- PH TO ATS-EQ2 74.0 kVA 57.0 kVA SEE E5.4
1/2/2014 10:40:23 AM
NORTH
E5.3
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
GENERAL NOTES
1. SEE E5.1 FOR CONDUIT AND WIRE SCHEDULE.
UPON RESTORATION OF NORMAL POWER, AFTER THE PRESCRIBED DELAY, THE TRANSFER SWITCHES SHALL AUTOMATICALLY TRANSFER LOAD TO NORMAL POWER IN THE FOLLOWING ORDER. 1. 2. ATS-EQ (EQUIPMENT) ATS-LS (LIFE SAFETY)
G-1 (EMERGENCY)
TO GROUNDING SYSTEM 150KW/187.5KVA, .8PF, 480/277V 3PH, 4W NATURAL GAS GENERATOR TO GROUNDING SYSTEM
G-2 (STANDBY)
150KW/187.5KVA, 0.8PF, 208/120V 3PH, 4W NATURAL GAS GENERATOR
GROUND NEUTRAL 1"C - 2#8 & 1#8 GRD FOR 120V BATTERY CHARGER TO RP-E2 BATTERY CHARGER 3 2 1 BLOCK HEATER BATTERY HEATER 225A 3P 150A 3P SHUNT TRIP 150A 3P CONTROL PANEL 1/2"C - 2#14 FOR REMOTE EMERGENCY STOP BUTTON SEE E7.1 FOR MORE INFORMATION. 1"C - 4#14 TO BUILDING AUTOMATION DDC PANEL. CONNECT A "GENERATOR RUNNING" AND "GENERATOR TROUBLE" OUTPUT CONTACT TO THE DDC PANEL. 1"C - FOR REMOTE ANNUNCIATOR WITH CABLE SPECIFIED BY GENERATOR MANUFACTURER 4X 600A 3P 1"C - 2#8 & 1#8 GRD FOR 208V BLOCK HEATER TO RP-E2
GROUND NEUTRAL 1"C - 2#8 & 1#8 GRD FOR 120V BATTERY CHARGER TO RP-E2 BATTERY CHARGER 3 2 1 BLOCK HEATER BATTERY HEATER 600A 3P 400A 3P 400A 3P CONTROL PANEL 1/2"C - 2#14 FOR REMOTE EMERGENCY STOP BUTTON SEE E7.1 FOR MORE INFORMATION. 1"C - 4#14 TO BUILDING AUTOMATION DDC PANEL. CONNECT A "GENERATOR RUNNING" AND "GENERATOR TROUBLE" OUTPUT CONTACT TO THE DDC PANEL. 1"C - FOR REMOTE ANNUNCIATOR WITH CABLE SPECIFIED BY GENERATOR MANUFACTURER 1"C - 2#8 & 1#8 GRD FOR 208V BLOCK HEATER TO RP-E2
NEC 220.44 1"C - 2#8 & 1#8 GRD FOR 208V BATTERY HEATER TO RP-E2
400NG
400NG
REMOTE ANNUNCIATOR
1"C - 6#14 (4 ACTIVE, 2 SPARE) GENERATOR START CIRCUIT. TO PP-C SEE E5.2 FOR CONTINUATION
1"C - 6#14 (4 ACTIVE, 2 SPARE) GENERATOR START CIRCUIT. TO DP-2 SEE E5.3 FOR CONTINUATION
ATS-EQ
150A, 480V, 3P
ATS-LS
150A, 480V, 3P
ATS-EQ1
400A, 208V, 3P
ATS-EQ2
400A, 208V, 3P
EPP-EQ
480/277V, 3PH, 4W 225A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM).
1"C - 4#14 TO BUILDING AUTOMATION DDC PANEL. CONNECT A "ON GENERATOR POWER" OUTPUT CONTACT TO THE SAME DDC PANEL RECEIVING THE "GENERATOR RUNNING" AND "GENERATOR TROUBLE" INPUTS. 150NG 150NG
EPP-LS
480/277V, 3PH, 4W 225A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM).
1"C - 4#14 TO BUILDING AUTOMATION DDC PANEL. CONNECT A "ON GENERATOR POWER" OUTPUT CONTACT TO THE SAME DDC PANEL RECEIVING THE "GENERATOR RUNNING" AND "GENERATOR TROUBLE" INPUTS.
1"C - 4#14 TO BUILDING AUTOMATION DDC PANEL. CONNECT A "ON GENERATOR POWER" OUTPUT CONTACT TO THE SAME DDC PANEL RECEIVING THE "GENERATOR RUNNING" AND "GENERATOR TROUBLE" INPUTS.
EPP-EQ2
208/120V, 3PH, 4W 400A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM).
400NG
400NG
TO GROUNDING SYSTEM
GROUND NEUTRAL SHUNT TRIP TO BE ACTIVATED WHEN HEAT DETECTOR IN ELEVATOR EQUIPMENT ROOM IS ACTIVATED. 1 2 3 DIGITAL MULTI-FUNCTION METER DIGITAL MULTI-FUNCTION METER
GROUND NEUTRAL
10
11
12
25A 3P
60A 3P
60A 3P
30A 3P
25A 3P
25A 3P
25A 3P
25A 3P
25A 3P
25A 3P
100A 3P
100A 3P
100A 3P
100A 3P
100A 3P
100A
100A
100A
100A
100A
SPARE 30G 30G 30G 30G 30G 30G 115NG 115NG 115NG 115NG
T- EQ-1 15 KVA 480- 208/120V #8 AWG 100/ 80AF 60/ 50AF ERP1AE 115G 70G 60NG (10' MAX) ELP- 4E 70NG ERP4AE
T- LS-2 15 KVA 480- 208/120V #8 AWG 60NG (10' MAX) 30G 30G 4X 30A 4X 30G 30A 4X 30G 30A
ERP3AS
ERP3BS
ERP4AS
ERP4BS
CP-11243
FUTURE LAB PANELS
ARCH. MECH.
70NG
4X
30A
J. Kasdorf
ELEC.
3/4" CONDUIT TO ATS-LS TO INITIATE SEQUENTIAL ELEVATOR OPERATION 3/4" CONDUIT TO INITIATE SEQUENTIAL ELEVATOR OPERATION
ELEV- 1 40 HP 46 FLA
SEF- 2 10 HP 14 FLA
SEF- 3 10 HP 14 FLA
SEF- 4 10 HP 14 FLA
R. Frazee
L.A.
D. Wilber
EPP-EQ1
208/120V, 3PH, 4W 400A MAIN COPPER BUS WITH FULL CAPACITY COPPER NEUTRAL BUS AND FULL LENGTH COPPER GROUND BUS. BUSSES AND FUSED SWITCHES SHALL HAVE A WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM), THE ENTIRE SWITCHBOARD SHALL HAVE A INTEGRAL WITHSTAND RATING OF 42,000 AMPERES RMS SYMMETRICAL (MINIMUM).
Project Administrator:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
13 kVA 13 kVA
R. Bracci
Drawing Scale:
TO GROUNDING SYSTEM
No Scale
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
5 6 7
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
100A 3P
100A 3P
100A 3P
100A 3P
100A 3P
100A
100A
100A
100A
100A
115NG
115NG
115NG
115NG
12204-1000
ERP1AS ERP1BS ERP2AS ERP2BS
1/2/2014 10:40:23 AM
NORTH
E5.4
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
2" CONDUIT WITH GOOSENECK ON SOUTH SIDE OF PENTHOUSE FOR ANTENNA ROOF PENTHOUSE UFC ROOM ROOF PENTHOUSE UFC ROOM
1 G FOURTH FLOOR G UFC ROOM IT CLOSET 1 G THIRD FLOOR SUBSTATION 3/4" CONDUIT 1#4 UNIT SUBSTATION No.2 UNIT SUBSTATION No.1 G UFC ROOM THIRD FLOOR FOURTH FLOOR
CP-11243
ARCH. MECH.
(2) 3" CONDUIT ACROSS BRIDGE ABOVE CEILING (4) 4" CONDUIT SLEEVES (TYP) LAB SHELL UFC ROOM CT
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
Drawing Scale:
No Scale
G T-EQ-1 T-EQ-2 T-LS-1 BONDING JUMPER N G N G BONDING JUMPER N G N G ATS-EQ N #4/0 CU #4/0 CU PH C G G 2 #4/0 CU 1 N G SECOND FLOOR FIBER ROOM NETWORK ROOM G UFC ROOM IT CLOSET TO GROUND MAT TO BUILDING STEEL TO WATER SERVICE PIPE (WITH JUMPER ACROSS METERS) GROUND CONDUCTOR IN PRIMARY DUCT BANK 1 G G 1 G G 1 G G LOADING DOCK FIRST FLOOR LAB (2) 3" CONDUIT ACROSS BRIDGE ABOVE CEILING 1" C. GENERATORS SECOND FLOOR CT 1" C. C 1" C. WAP/C LINEAR EQUIPMENT ROOM FIBER ROOM UFC ROOM
c
G ATS-LS G-1 (LIFE SAFETY) N PH A PH B PH A PH B PH C G N CONDUIT TO 2ND FLOOR CEILING SPACE CONDUIT SLEEVES (TYP) LAB G-2 (STAND-BY) LINEAR EQUIPMENT ROOM
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
FIRST FLOOR
12204-1000
Riser Diagrams
NOTE:
1. THE ENTIRE TELECOMM RACEWAY SYSTEM SHALL BE GROUNDED, INCLUDING BUT NOT LIMITED TO RACKS, CONDUITS, CONDUIT SLEEVES, CABLE TRAY, ETC. SEE SPECS FOR GROUNDING CONDUCTOR REQUIREMENTS.
KEYNOTES:
1 2 1/4"x2"x24" COPPER GROUND BAR WITH PREDRILLED HOLES. 1/4"x2" CONTINUOUS GROUND BAR AROUND THE PERIMETER OF THE ROOM.
NOTE:
1. 2. INSTALL PULL BOX WHERE TOTAL NUMBER OF SWEEPS EXCEED 180 DEGREES. INSTALL 4 x 8 SHEETS OF 3/4" FIRE RATED PLYWOOD CONTINOUS ON THREE (3) WALLS OF FCR AND FUCR ROOMS.
2.
1/2/2014 10:40:25 AM
E5.6
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR.
T. Hackett
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Spare Spare Spare Spare Spare Spare Spare Spare Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60 CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 20 20 20 20 20
RP-1M
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Spare Spare Spare Spare Spare Spare Spare Spare Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 20 20 20 20 20
RP-1H
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600
PANELBOARD SCHEDULE
CB 20 20 2P 20 2P 20 20 20 2P 20 2P 20 20 2P 20 20 2P 20 20 2P 20 200 AMP MLO VA PHA PHB PHC 360 A 450 B 450 C 450 A 450 B 360 C 180 A 450 B 450 C 450 A 450 B 180 C 450 A 450 B 360 C 450 A 450 B 360 C 450 A 450 B 360 C VA 360 450 450 180 450 450 180 CB 20 20 20 2P 20 20 2P 20 20 20 20 20 20 2P 20 20 2P 20 20 2P 20
RP-1D
LOAD Spare 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 Recept Stair SW3-1 Spare Spare Spare 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO VA PHA PHB PHC VA CB LOAD 180 A 360 20 Power to Fume Hood 1533 540 B 360 20 Power to Fume Hood 1533 360 C 360 20 2 Recepts Fume Hood 1533 540 A 180 20 1 Recept Equip Room 1500 180 B 850 20 1 Recept Equip Room 1500 540 C 850 2P 360 A 20 Spare 540 B 2P 180 C 20 Spare 360 A 20 Spare 180 B 180 20 Lab Ceiling Recept 180 C 540 2P TSA78M (78" Table) A 180 20 Lab Ceiling Recept B 540 2P TSA78M (78" Table) C 180 20 Lab Ceiling Recept A 540 2P TSA78M (78" Table) B 180 20 Lab Ceiling Recept C 540 2P TSA78M (78" Table) A 20 Spare B 20 Spare C 20 Spare
100 AMP MLO VA PHA PHB PHC VA CB LOAD 180 A 360 20 2 Recepts TCR 1524 360 B 180 20 1 Recept TCR 1524 180 C 180 20 1 Recept TCR 1524 180 A 750 20 Refrigerator TCR 1524 180 B 900 20 Incubator TCR 1524 540 C 600 20 Bio Safety Cabinet TCR 1524 360 A 180 20 1 Recept TCR 1524 540 B 600 20 Bio Safety Cabinet TCR 1524 180 C 900 20 Incubator TCR 1524 540 A 900 20 Incubator TCR 1525 360 B 600 20 Bio Safety Cabinet TCR 1525 540 C 180 20 1 Recept TCR 1525 A 600 20 Bio Safety Cabinet TCR 1525 B 900 20 Incubator TCR 1525 C 360 20 2 Recepts TCR 1524 A 180 20 1 Recept TCR 1524 B 180 20 1 Recept TCR 1524 C 750 20 Refrigerator TCR 2524 A 600 20 1 Recept TCR 1525 B 600 2P C 20 Spare
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 2,700 VA 3,550 VA 3,730 VA 9,980 VA 9,980 VA 27.7 A Total Continuous Load: Total Non-Continuous Load: 0 VA 9,980 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,830 VA 5,400 VA 4,410 VA 14,640 VA 12,320 VA 34.2 A Total Continuous Load: 0 VA Total Non-Continuous Load: 14,640 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 25,000 A 3 4 60
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,590 VA 4,770 VA 4,140 VA 13,500 VA 11,750 VA 32.6 A 0 VA Total Continuous Load: Total Non-Continuous Load: 13,500 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD IMAGING Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-1Q
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Lab Bench Recepts 2 Lab Bench Recepts 2 Lab Bench Recepts 2 Lab Bench Recepts Spare Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Spare 2 Recepts Lab Support 1210 2 Lab Equipment Receptacles Lab Equipment Receptacle 2 Recepts Lab Support 1220 2 Recepts Lab Support 1220 3 Recepts Lab Support 1220
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 2P 20 2P 20 2P 20 2P 20 20 20 20 2P 20 20 20
RP-1L
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Spare Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table)
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P 100 AMP MLO VA PHA PHB PHC VA 180 A 360 540 B 360 360 C 360 540 A 360 180 B 850 540 C 850 360 A 1500 540 B 180 C 360 A 180 180 B 850 180 C 850 0 A 360 B 540 C 180 A 540 B 360 C 540 A 600 180 B 600 540 C 600 CB 20 20 20 20 20 2P 20 20 20 20 20 2P 20 2P 20 20 20 20 40 3P
RP-1G
LOAD Power to Fume Hood 1523 Power to Fume Hood 1523 2 Recepts Fume Hood 1523 2 Recepts Equip Room 1500 1 Recept Equip Room 1500 Ice Machine Equip Room 1500 Spare Spare 1 Recept Equip Room 1500 1 Recept Equip Room 1500 Spare Spare Spare Spare Spare Cold Room 1501 Control Panel CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1100 2 Recepts Write-up Space 1300 2 Recepts Write-up Space 1300 2 Recepts Write-up Space 1300 Copy Machine Write-Up 1300 Spare Spare Spare Spare Spare Spare Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-1C
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO VA PHA PHB PHC VA CB LOAD CKT. A 180 20 1 Recept Corridor 1250 2 B 360 20 2 Recepts Corridor 1250 4 C 850 20 1 Recept Corridor 1250 6 A 850 2P 8 B 850 20 1 Recept Corridor 1250 10 C 850 2P 12 A 360 20 2 Recepts Corridor 1250 14 B 20 Spare 16 C 20 Spare 18 A 850 20 1 Recept Corridor 1250 20 B 850 2P 22 C 180 20 1 Recept Corridor 1250 24 A 690 20 BS Cabinet Animal Holding 1703 26 B 690 20 BS Cabinet Animal Holding 1704 28 C 360 20 2 Recepts Prep Room 1701 30 A 360 20 2 Recepts Fluorescent Imaging 1702 32 B 360 20 2 Recepts Fluorescent Imaging 1702 34 C 540 20 Cages Animal Holding 1703 36 A 540 20 Cages Animal Holding 1704 38 B 20 Spare 40 C 20 Spare 42 Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 3,830 VA 3,110 VA 2,780 VA 9,720 VA 9,720 VA 27.0 A Total Continuous Load: Total Non-Continuous Load: 0 VA 9,720 VA
100 AMP MLO VA PHA PHB PHC VA CB LOAD 360 A 750 20 Refrigerator TCR 1531 360 B 180 20 1 Recept TCR 1531 360 C 360 20 2 Recepts TCR 1531 360 A 180 20 1 Recept TCR 1531 B 900 20 Incubator TCR 1531 180 C 600 20 Bio Safety Cabinet TCR 1531 540 A 180 20 1 Recept TCR 1531 360 B 600 20 Bio Safety Cabinet TCR 1531 540 C 900 20 Incubator TCR 1531 180 A 900 20 Incubator TCR 1532 540 B 600 20 Bio Safety Cabinet TCR 1532 360 C 180 20 1 Recept TCR 1532 540 A 600 20 Bio Safety Cabinet TCR 1532 B 900 20 Incubator TCR 1532 360 C 750 20 Refrigerator TCR 1532 360 A 180 20 1 Recept TCR 1532 450 B 360 20 2 Recepts TCR 1532 450 C 180 20 1 Recept TCR 1532 360 A 600 20 1 Recept TCR 1532 360 B 600 2P 540 C 20 Spare
200 AMP MLO VA PHA PHB PHC VA CB LOAD 360 A 20 Spare 360 B 720 20 4 Recepts Office 1111 360 C 720 20 4 Recepts Office 1112 360 A 720 20 4 Recepts Office 1113 360 B 500 20 Copy Machine Workroom 1101 360 C 360 20 2 Recepts Workroom 1101 & 1102 360 A 720 20 4 Recepts Office 1114 360 B 720 20 4 Recepts Office 1115 360 C 720 20 4 Recepts Office 1116 360 A 360 20 2 Recept Workroom 1102 360 B 720 20 4 Recepts Office 1117 360 C 720 20 4 Recepts Office 1118 360 A 720 20 4 Recepts Office 1119 500 B 360 20 2 Recepts Workroom 1302 C 720 20 4 Recepts Office 1317 A 720 20 4 Recepts Office 1318 B 720 20 4 Recepts Office 1319 C 20 Spare A 125 20 Roller Shade Control Panel 1820 B 100 20 Gas Control Valve C 20 Spare
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 6,090 VA 6,210 VA 5,760 VA 18,060 VA 14,030 VA 38.9 A 0 VA Total Continuous Load: Total Non-Continuous Load: 18,060 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,160 VA 5,180 VA 5,360 VA 15,700 VA 12,850 VA 35.7 A 0 VA Total Continuous Load: Total Non-Continuous Load: 15,700 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,165 VA 5,780 VA 4,680 VA 15,625 VA 12,813 VA 35.6 A 0 VA Total Continuous Load: Total Non-Continuous Load: 15,625 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Spare 1 Recept Equip Room 1510 2 Recepts Equip Room 1510 Spare Spare Spare Spare CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 20 20 20 100 AMP MLO VA PHA PHB PHC VA 180 A 180 540 B 850 360 C 850 540 A 180 B 540 C 360 A 360 540 B 360 180 C 360 360 A 1500 180 B 540 180 C 540 A B 540 850 C 360 850 A 360 360 B 540 C A B C CB 20 20 2P 20 2P 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-1P
LOAD 1 Recept Equip Room 1510 1 Recept Equip Room 1510 Spare Spare Power to Fume Hood 1536 Power to Fume Hood 1536 2 Recept Fume Hood 1536 Ice Machine Equip Room 1510 3 Lab Bench Recept 3 Lab Bench Recept Spare 3 Recepts Lab Support 1230 2 Recepts Lab Support 1230 2 Recepts Lab Support 1240 3 Recepts Lab Support 1240 Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD IMAGING Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-1K
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Lab Bench Recepts 2 Lab Bench Recepts 2 Lab Bench Recepts 2 Lab Bench Recepts Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Incubator TCR 1521 Bio Safety Cabinet TCR 1522 1 Recept TCR 1522 Bio Safety Cabinet TCR 1522 Incubator TCR 1522 2 Recept TCR 1522 1 Recept TCR 1522 1 Recept TCR 1522 Refrigerator TCR 1522
PANELBOARD SCHEDULE
CB 20 20 20 20 20 2P 20 2P 20 2P 20 2P 20 20 20 20 20 20 20 20 20
RP-1F
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD TV Recepts Lounge 1010 TV Recepts Lounge 1010 TV Recepts Lounge 1010 2 Recepts JC 1020 MT 1021 EWC 1HW1C 2 Recepts MT 1021 WT 1022 2 Recepts WT 1022 GNT 1023 2 Recept Corridor 1HW1 TV Recepts Corridor 1HW1 TV Recepts Corridor 1HW1 4 Recepts Office 1040
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 4 Recepts Work Room 1040A, Mail 1042 20 3 Recepts Collab 1030, Write-up 1100 20 2 Recept Corridor 1HW1 20 Spare 20 2 Recept Corridor 1HW1 20 TV Recepts Corridor 1HW1 20 1 Recept Corridor 1HW1 20 Spare 20 Spare 2P Spare 20 200 AMP MLO VA PHA PHB PHC VA 300 A 360 300 B 300 480 C 360 360 A 300 500 B 360 360 C 360 360 A 180 360 B 300 300 C 1100 300 A 1100 540 B 1100 540 C 1000 540 A 1000 360 B 750 C 750 360 A 360 300 B 180 C A 0 B 0 C CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-1B
LOAD 2 Recept Corridor 1HW1 TV Recepts Corridor 1HW1 2 Recepts Conference 1000 TV Recepts Conference 1000 2 Recepts Conference 1000 2 Recept Corridor 1HW1 1 Recept Corridor 1HW1 TV Recepts Collaboration 1060 Hand Dryer MT 1021 Hand Dryer WT 1022 Hand Dryer GNT 1023 Microwave Microwave Refrigerator Refrigerator 2 Recepts Kitchenette 1011 Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO VA PHA PHB PHC VA CB LOAD A 180 20 1 Recept Corridor 1450 B 360 20 2 Recepts Corridor 1450 C 850 20 1 Recept Corridor 1450 A 850 2P B 850 20 1 Recept Corridor 1450 C 850 2P A 360 20 2 Recepts Corridor 1450 B 20 Spare C 20 Spare A 850 20 1 Recept Corridor 1450 B 850 2P C 360 20 2 Recepts Corridor 1450 A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare
100 AMP MLO VA PHA PHB PHC VA CB LOAD 360 A 360 20 2 Recepts Lab Support 1410 360 B 180 20 1 Recepts Lab Support 1410 360 C 360 20 2 Recepts Lab Support 1420 360 A 360 20 2 Recepts Lab Support 1420 180 B 360 20 2 Recepts Lab Support 1420 540 C 360 20 2 Lab Equipment Receptacles 360 A 450 20 Lab Equipment Receptacle 540 B 450 2P 180 C 360 20 2 Recept TCR 1521 540 A 180 20 1 Recept TCR 1521 360 B 180 20 1 Recept TCR 1521 540 C 750 20 Refrigerator TCR 1521 900 A 900 20 Incubator TCR 1521 600 B 600 20 Bio Safety Cabinet TCR 1521 180 C 180 20 1 Recept TCR 1521 600 A 600 20 Bio Safety Cabinet TCR 1521 900 B 900 20 Incubator TCR 1521 360 C 600 20 1 Recept TCR 1522 180 A 600 2P 180 B 20 Spare 750 C 20 Spare
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,690 VA 4,630 VA 4,220 VA 13,540 VA 11,770 VA 32.7 A Total Continuous Load: 0 VA Total Non-Continuous Load: 13,540 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 2,240 VA 2,060 VA 2,060 VA 6,360 VA 6,360 VA 17.7 A Total Continuous Load: Total Non-Continuous Load: 0 VA 6,360 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 6,750 VA 5,790 VA 5,520 VA 18,060 VA 14,030 VA 38.9 A Total Continuous Load: 0 VA Total Non-Continuous Load: 18,060 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,520 VA 5,170 VA 5,430 VA 16,120 VA 13,060 VA 36.3 A Total Continuous Load: 0 VA Total Non-Continuous Load: 16,120 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Spare Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60 CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P
RP-1N
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Spare Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P 100 AMP MLO VA PHA PHB PHC 180 A 540 B 360 C 540 A 180 B 540 C 360 A 540 B 180 C 360 A 180 B 180 C A 360 B 540 C 180 A 540 B 360 C 540 A 180 B 540 C VA CB 20 20 2P 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 40 3P
RP-1J
LOAD Spare Spare Spare Spare Spare Power to Fume Hood 1526 Power to Fume Hood 1526 2 Recepts Fume Hood 1526 Spare 2 Lab Bench Recept 2 Lab Bench Recept 2 Lab Bench Recept 2 Lab Bench Recept Spare Spare Spare Spare Cold Room 1501 Control Panel CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 2 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 2 Gen Recepts 1600, Corr 1HW2 1 Recept Linear Equipment 1600 1 Recept Linear Equipment 1600 RO Skid Motor in 1650
PANELBOARD SCHEDULE
CB 20 20 2P 20 20 2P 20 2P 20 20 2P 20 20 2P 20 20 2P 20 15 3P Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 25,000 A 3 4 60
RP-1E
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Write-up Space 1300 Write-up Space 1300 Write-up Space 1300 Write-up Space 1300 Write-up Space 1300 Write-up Space 1300 Write-up Space 1300
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 200 AMP MLO VA PHA PHB PHC 360 A 360 B 360 C 360 A 360 B 360 C 360 A B C A B C A B C A B C A B C VA 900 900 900 360 180 900 900 900 180 900 900 900 900 0 0 0 0 0 CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-1A
LOAD 4 Recepts Office 1311 4 Recepts Office 1312 4 Recepts Office 1313 Copy Machine Workroom 1301 1 Gen Recept Workroom 1301 4 Recepts Office 1314 4 Recepts Office 1315 4 Recepts Office 1316 Spare 1 Gen Recept Write-up 1300 Recept Vending/Recycle 1050 Recept Vending/Recycle 1050 Recept Vending/Recycle 1050 Recept Vending/Recycle 1050 Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO VA PHA PHB PHC VA CB LOAD 180 A 750 20 Refrigerator TCR 1534 360 B 180 20 1 Recept TCR 1534 180 C 360 20 2 Recepts TCR 1534 180 A 180 20 1 Recept TCR 1534 180 B 900 20 Incubator TCR 1534 540 C 600 20 Bio Safety Cabinet TCR 1534 360 A 180 20 1 Recept TCR 1534 540 B 600 20 Bio Safety Cabinet TCR 1534 180 C 900 20 Incubator TCR 1534 540 A 900 20 Incubator TCR 1535 360 B 600 20 Bio Safety Cabinet TCR 1535 540 C 180 20 1 Recept TCR 1535 0 A 600 20 Bio Safety Cabinet TCR 1535 360 B 900 20 Incubator TCR 1535 540 C 750 20 Refrigerator TCR 1535 180 A 180 20 1 Recept TCR 1535 540 B 360 20 2 Recepts TCR 1535 360 C 180 20 1 Recept TCR 1535 540 A 600 20 1 Recept TCR 1535 180 B 600 2P 540 C 20 Spare
200 AMP MLO VA PHA PHB PHC VA CB LOAD CKT. 360 A 540 20 3 Recepts Outdoor Gens, Cust 1840 2 450 B 540 20 3 Recepts Mech 1650, Elec 1820, 1830 4 450 C 540 20 3 Recepts Mechanical 1810 6 360 A 540 20 3 Recepts Mechanical 1810, Stor 1611 8 450 B 180 20 Recept Stair SW2-1 10 450 C 360 20 2 Recept 1811 and 1815 12 450 A 540 20 3 Recept Mechanical 1810 14 450 B 240 20 Sterilizer ST-1 Control Panel 16 360 C 240 20 Sterilizer ST-2 Control Panel 18 450 A 200 20 Glass Washer GW-1 Control Panel 20 450 B 200 20 Glass Washer GW-2 Control Panel 22 360 C 540 20 3 Recepts Glass Wash 1610 24 450 A 20 Spare 26 450 B 20 Spare 28 360 C 20 Spare 30 450 A 20 Spare 32 450 B 20 Spare 34 180 C 20 Spare 36 1000 A 20 Spare 38 1000 B 245 20 RO Skid Control Panel in 1650 40 1000 C 100 20 Facility Monitoring System 1611 42 Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,340 VA 5,105 VA 4,940 VA 15,385 VA 12,693 VA 35.2 A Total Continuous Load: 0 VA Total Non-Continuous Load: 15,385 VA
2 Recepts 2 Recepts 2 Recepts 2 Recepts 2 Recepts 2 Recepts 2 Recepts Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,370 VA 6,660 VA 5,850 VA 17,880 VA 13,940 VA 38.7 A Total Continuous Load: 0 VA Total Non-Continuous Load: 17,880 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 3,480 VA 4,200 VA 4,020 VA 11,700 VA 10,850 VA 30.1 A Total Continuous Load: 0 VA Total Non-Continuous Load: 11,700 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 3,780 VA 3,960 VA 4,500 VA 12,240 VA 11,120 VA 30.9 A Total Continuous Load: 0 VA Total Non-Continuous Load: 12,240 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Spare Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60 CB 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 100 AMP MLO VA PHA PHB PHC 180 A 540 B 360 C 540 A 180 B 540 C 360 A 540 B C 180 A 540 B 360 C 540 A 180 B 540 C 360 A 540 B 180 C 360 A 180 B 180 C VA 360 360 360 900 600 180 600 900 750 180 360 180 CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-2R
LOAD Spare Power to Fume Hood 2537 Power to Fume Hood 2537 2 Recept Fume Hood 2537 Incubator TCR 2538 Bio Safety Cabinet TCR 2538 1 Recept TCR 2538 Bio Safety Cabinet TCR 2538 Incubator TCR 2538 Refrigerator TCR 2538 1 Recept TCR 2538 2 Recept TCR 2538 1 Recept TCR 2538 Spare Spare Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Incubator Lab Support 2210 Bio Safety Cab Lab Support 2210 1 Recept Lab Support 2210 Bio Safety Cab Lab Support 2210 Incubator Lab Support 2210 1 Recept Lab Support 2210 Refrigerator Lab Support 2210 1 Recept Lab Support 2210 2 Recept Lab Support 2210 1 Recept Lab Support 2210 Spare Spare Spare Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-2M
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) 1 Recept TCR 2525 Spare Spare Space Space Space Space Space Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20
RP-2H
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 2 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 2 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 2 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 2 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600
PANELBOARD SCHEDULE
CB 20 20 2P 20 2P 20 20 2P 20 20 2P 20 20 2P 20 20 2P 20 20 2P 20
RP-2D
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO VA PHA PHB PHC VA CB LOAD 360 A 360 20 2 Recept TCR 2532 540 B 180 20 1 Recept TCR 2532 360 C 180 20 1 Recept TCR 2532 540 A 750 20 Refrigerator TCR 2532 360 B 180 20 1 Recept TCR 2532 540 C 180 20 1 Recept TCR 2532 360 A 600 20 Bio Safety Cab TCR 2532 540 B 180 20 1 Recept TCR 2532 900 C 900 20 Incubator TCR 2532 600 A 180 20 1 Recept Lab Support 2531 180 B 600 20 Bio Safety Cab Lab Support 2531 600 C 180 20 1 Recept Lab Support 2531 900 A 180 20 1 Recept Lab Support 2531 180 B 900 20 Incubator Lab Support 2531 750 C 750 20 Refrigerator Lab Support 2531 180 A 180 20 1 Recept Lab Support 2531 360 B 360 20 2 Recept Lab Support 2531 180 C 180 20 1 Recept Lab Support 2531 A 600 20 1 Recept Lab Support 2531 B 600 2P C 20 Spare
100 AMP MLO VA PHA PHB PHC VA CB LOAD 180 A 360 20 2 Recept TCR 2524 360 B 180 20 1 Recept TCR 2524 180 C 180 20 1 Recept TCR 2524 180 A 750 20 Refrigerator TCR 2524 180 B 900 20 Incubator TCR 2524 540 C 600 20 Bio Safety Cabinet TCR 2524 360 A 180 20 1 Recept TCR 2524 540 B 600 20 Bio Safety Cabinet TCR 2524 180 C 900 20 Incubator TCR 2524 540 A 20 Spare 360 B 900 20 Incubator TCR 2525 540 C 600 20 Bio Safety Cabinet TCR 2525 600 A 180 20 1 Recept TCR 2525 600 B 600 20 Bio Safety Cabinet TCR 2525 C 900 20 Incubator TCR 2525 A 360 20 2 Recept TCR 2525 B 180 20 1 Recept TCR 2525 C 180 20 1 Recept TCR 2525 A 750 20 Refrigerator TCR 2525 B 20 Spare C 20 Spare
200 AMP MLO VA PHA PHB PHC VA CB LOAD 360 A 180 20 1 Recept Linear Equipment 2600 450 B 450 20 1 Recept Linear Equipment 2600 450 C 450 2P 450 A 360 20 2 Recept Linear Equipment 2600 450 B 360 20 2 Recept Linear Equipment 2600 360 C 450 20 1 Recept Linear Equipment 2600 450 A 450 2P 450 B 360 20 2 Recept Linear Equipment 2600 360 C 450 20 1 Recept Linear Equipment 2600 450 A 450 2P 450 B 360 20 2 Recept Linear Equipment 2600 360 C 450 20 1 Recept Linear Equipment 2600 450 A 450 2P 450 B 360 20 2 Recept Linear Equipment 2600 180 C 450 20 1 Recept Linear Equipment 2600 450 A 450 2P 450 B 20 Spare 360 C 2P 450 A 20 Spare 450 B 20 Spare 360 C 0 20 Spare
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 3,990 VA 4,740 VA 4,380 VA 13,110 VA 11,555 VA 32.1 A Total Continuous Load: 0 VA Total Non-Continuous Load: 13,110 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,790 VA 5,160 VA 5,700 VA 16,650 VA 13,325 VA 37.0 A Total Continuous Load: 0 VA Total Non-Continuous Load: 16,650 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,440 VA 5,400 VA 4,800 VA 14,640 VA 12,320 VA 34.2 A Total Continuous Load: 0 VA Total Non-Continuous Load: 14,640 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 25,000 A 3 4 60
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,400 VA 5,040 VA 4,680 VA 15,120 VA 12,560 VA 34.9 A Total Continuous Load: 0 VA Total Non-Continuous Load: 15,120 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Spare Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) CB 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 100 AMP MLO VA PHA PHB PHC VA 180 A 750 540 B 180 360 C 360 540 A 180 180 B 900 540 C 600 360 A 180 540 B 600 C 900 180 A 540 B 360 360 C 850 540 A 850 180 B 540 C 360 A 1080 540 B 180 C 360 A 600 180 B 600 180 C 600 CB 20 20 20 20 20 20 20 20 20 20 20 20 2P 20 2P 20 20 20 40 3P
RP-2Q
LOAD Refrigerator TCR 2536 1 Recept TCR 2536 2 Recept TCR 2536 1 Recept TCR 2536 Incubator TCR 2536 Bio Safety Cabinet TCR 2536 1 Recept TCR 2536 Bio Safety Cabinet TCR 2536 Incubator TCR 2536 Spare 2 Recept Equip Room 2510 1 Recept Equip Room 2510 Spare Ice Flake Machine Spare Spare Cold Room 2511 Control Panel CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2P 20 2P 20 2P 20 2P
RP-2L
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Spare Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table)
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P 100 AMP MLO VA PHA PHB PHC VA 180 A 540 B 360 360 C 850 540 A 850 180 B 540 C 360 A 1080 540 B 180 C 360 A 180 180 B 850 180 C 850 0 A 360 B 540 C 180 A 180 540 B 360 360 C 360 540 A 600 180 B 600 540 C 600 CB 20 20 20 2P 20 20 20 20 20 20 20 2P 20 2P 20 20 20 20 40 3P
RP-2G
LOAD Spare 2 Recept Equip Room 2500 1 Recept Equip Room 2500 Spare Spare Ice Flake Machine Spare Spare 1 Recept Equip Room 2500 1 Recept Equip Room 2500 Spare Spare 2 Recept Fume Hood 2523 Power to Fume Hood 2523 Power to Fume Hood 2523 Cold Room 2501 Control Panel CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2100 2 Recepts Write-up Space 2300 2 Recepts Write-up Space 2300 2 Recepts Write-up Space 2300 Copy Machine Write-Up 2300 Spare Spare Spare Spare Spare Spare Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-2C
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO VA PHA PHB PHC VA CB LOAD A 360 20 2 Recept TCR 2529 B 180 20 1 Recept TCR 2529 C 180 20 1 Recept TCR 2529 A 750 20 Refrigerator TCR 2529 B 20 Spare C 900 20 Incubator TCR 2529 A 180 20 1 Recept TCR 2529 B 900 20 Incubator TCR 2529 C 600 20 Bio Safety Cabinet TCR 2529 A 900 20 Incubator TCR 2529 B 360 20 2 Lab Bench Recept C 360 20 2 Lab Bench Recept 0 A 360 20 2 Lab Bench Recept 360 B 360 20 2 Lab Bench Recept 540 C 20 Spare 180 A 20 Spare 540 B 20 Spare 360 C 20 Spare 540 A Space 180 B Space 540 C Space
200 AMP MLO VA PHA PHB PHC VA CB LOAD 360 A 20 Spare 360 B 720 20 4 Recepts Office 2111 360 C 720 20 4 Recepts Office 2112 360 A 720 20 4 Recepts Office 2113 360 B 500 20 Copy Machine Workroom 2101 360 C 360 20 2 Recepts Workroom 2101 & 2102 360 A 720 20 4 Recepts Office 2114 360 B 720 20 4 Recepts Office 2115 360 C 720 20 4 Recepts Office 2116 360 A 360 20 2 Recept Workroom 2102 360 B 720 20 4 Recepts Office 2117 360 C 720 20 4 Recepts Office 2118 360 A 720 20 4 Recepts Office 2119 500 B 20 Spare C 720 20 4 Recepts Office 2317 A 720 20 4 Recepts Office 2318 B 720 20 4 Recepts Office 2319 C 20 Spare A 125 20 Roller Shade Control Panel 2820 B 100 20 Gas Control Valve C 20 Spare
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 6,160 VA 5,340 VA 5,470 VA 16,970 VA 13,485 VA 37.4 A 0 VA Total Continuous Load: Total Non-Continuous Load: 16,970 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 3,270 VA 2,880 VA 3,480 VA 9,630 VA 9,630 VA 26.7 A Total Continuous Load: Total Non-Continuous Load: 0 VA 9,630 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,050 VA 4,690 VA 5,360 VA 15,100 VA 12,550 VA 34.8 A 0 VA Total Continuous Load: Total Non-Continuous Load: 15,100 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,165 VA 5,420 VA 4,680 VA 15,265 VA 12,633 VA 35.1 A 0 VA Total Continuous Load: Total Non-Continuous Load: 15,265 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare Spare Spare Spare 1 Recept TCR 2535 Spare Spare Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) CB 20 20 20 20 20 20 2P 20 20 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P
RP-2P
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Spare Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table)
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P
RP-2K
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Lab Bench Recepts 2 Lab Bench Recepts 2 Lab Bench Recepts 2 Lab Bench Recepts Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) 1 Recept TCR 2522 Spare Spare Spare 3 Recepts Lab Support 2410 3 Recepts Lab Support 2410 Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 20 20 20
RP-2F
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD TV Recepts Conference 2010 2 Recepts Conference 2010 2 Recept Corridor 2HW1 2 Recepts JC 2020 MT 2021 EWC 2HW1C
PANELBOARD SCHEDULE
CB 20 20 20 20 20 2 Recept Mens T 2021, Womens T 2022 20 2 Recept Womens 2022 Gender N 2023 20 2 Recept Corridor 2HW1 20 TV Recepts Corridor 2HW1 20 2 Recepts Office 2040, Health 2042 20 2 Recepts Office 2040 20 2 Recepts Collab 2030, Write-up 2100 20 Spare 20 2 Recept Corridor 2HW1 20 Spare 20 Spare 20 Spare 20 Spare 20 Spare 20 Spare 2P Spare 20 200 AMP MLO VA PHA PHB PHC VA 400 A 360 360 B 360 C 400 360 A 400 500 B 360 360 C 360 360 A 360 360 B 360 400 C 1100 360 A 1100 540 B 1100 360 C A 360 B C A B C A 0 B 0 C CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-2B
LOAD CKT. 2 Recept Corridor 2HW1 2 Spare 4 TV Recepts Corridor 2HW1 6 TV Recepts Conference 2000 8 2 Recepts Conference 2000 10 2 Recepts Conference 2000 12 2 Recept Corridor 2HW3 14 2 Recept Corridor 2HW3, EC 2009 16 Hand Dryer Men's Toilet 2021 18 Hand Dryer Women's Toilet 2022 20 Hand Dryer Gender Neutral Tlt 2023 22 Spare 24 Spare 26 Spare 28 Space 30 Space 32 Space 34 Space 36 Space 38 Space 40 Space 42
100 AMP MLO VA PHA PHB PHC VA CB LOAD A 750 20 Refrigerator TCR 2534 B 180 20 1 Recept TCR 2534 C 360 20 2 Recept TCR 2534 A 180 20 1 Recept TCR 2534 B 900 20 Incubator TCR 2534 600 C 600 20 Bio Safety Cabinet TCR 2534 600 A 180 20 1 Recept TCR 2534 B 600 20 Bio Safety Cabinet TCR 2534 C 900 20 Incubator TCR 2534 180 A 900 20 Incubator TCR 2535 540 B 600 20 Bio Safety Cabinet TCR 2535 360 C 180 20 1 Recept TCR 2535 540 A 600 20 Bio Safety Cabinet TCR 2535 180 B 900 20 Incubator TCR 2535 540 C 750 20 Refrigerator TCR 2535 360 A 180 20 1 Recept TCR 2535 540 B 360 20 2 Recept TCR 2535 180 C 180 20 1 Recept TCR 2535 360 A 20 Spare 180 B 20 Spare 180 C 20 Spare
100 AMP MLO VA PHA PHB PHC VA CB LOAD 180 A 20 Spare 540 B 20 Spare 360 C 2P 540 A 360 20 Power to Fume Hood 2527 180 B 360 20 Power to Fume Hood 2527 540 C 360 20 2 Recepts Fume Hood 2527 360 A 900 20 Incubator TCR 2528 540 B 180 20 1 Recept TCR 2528 180 C 600 20 Bio Safety Cabinet TCR 2528 360 A 900 20 Incubator TCR 2528 180 B 600 20 Bio Safety Cabinet TCR 2528 180 C 360 20 2 Recept TCR 2526 0 A 180 20 1 Recept TCR 2526 360 B 180 20 1 Recept TCR 2526 540 C 750 20 Refrigerator TCR 2526 360 A 20 Spare 540 B 20 Spare 540 C 20 Spare 180 A 20 Spare 540 B 20 Spare 180 C 20 Spare
100 AMP MLO VA PHA PHB PHC VA CB LOAD 360 A 360 20 2 Recept TCR 2521 360 B 180 20 1 Recept TCR 2521 360 C 180 20 1 Recept TCR 2521 360 A 750 20 Refrigerator TCR 2521 180 B 900 20 Incubator TCR 2521 540 C 600 20 Bio Safety Cabinet TCR 2521 360 A 180 20 1 Recept TCR 2521 540 B 600 20 Bio Safety Cabinet TCR 2521 180 C 900 20 Incubator TCR 2521 540 A 900 20 Incubator TCR 2522 360 B 600 20 Bio Safety Cab Lab Support 2522 540 C 180 20 1 Recept Lab Support 2522 600 A 600 20 Bio Safety Cab Lab Support 2522 600 B 900 20 Incubator TCR 2522 C 360 20 2 Recept TCR 2522 A 180 20 1 Recept TCR 2522 B 180 20 1 Recept TCR 2522 C 750 20 Refrigerator TCR 2522 540 A 20 Spare 540 B 20 Spare C 20 Spare
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,830 VA 4,980 VA 4,830 VA 14,640 VA 12,320 VA 34.2 A Total Continuous Load: 0 VA Total Non-Continuous Load: 14,640 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,320 VA 4,200 VA 4,590 VA 13,110 VA 11,555 VA 32.1 A Total Continuous Load: 0 VA Total Non-Continuous Load: 13,110 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,730 VA 5,940 VA 4,590 VA 16,260 VA 13,130 VA 36.4 A Total Continuous Load: 0 VA Total Non-Continuous Load: 16,260 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 3,700 VA 3,940 VA 3,340 VA 10,980 VA 10,490 VA 29.1 A Total Continuous Load: 0 VA Total Non-Continuous Load: 10,980 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Spare Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60 CB 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P
RP-2N
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA72M (72" Table) Lab Ceiling Recept TSA48M (48" Table) Lab Ceiling Recept TSA48M (48" Table) Spare Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 2P 20 2P 20 2P 20 2P
RP-2J
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 2 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 2 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 1 Recept Linear Equipment 2600 RO Skid Control Panel in 2650 RO Skid Motor in 2650
PANELBOARD SCHEDULE
CB 20 20 2P 20 20 2P 20 2P 20 20 2P 20 20 2P 20 20 2P 20 15 3P Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 25,000 A 3 4 60
RP-2E
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Write-up Space 2300 Write-up Space 2300 Write-up Space 2300 Write-up Space 2300 Write-up Space 2300 Write-up Space 2300 Write-up Space 2300
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 200 AMP MLO VA PHA PHB PHC VA 360 A 1080 360 B 900 360 C 900 360 A 900 360 B 360 360 C 180 360 A 900 B 900 C 900 A 360 B 180 C A B C A B 0 C 0 A 0 B 0 C 0 CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-2A
LOAD 5 Recepts Director's Office 2050 4 Recepts Office 2311 4 Recepts Office 2312 4 Recepts Office 2313 Copy Machine Workroom 2301 1 Gen Recept Workroom 2301 4 Recepts Office 2314 4 Recepts Office 2315 4 Recepts Office 2316 2 Recepts Admin 2060 1 Gen Recept Write-up 2300 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO VA PHA PHB PHC VA CB LOAD 180 A 360 20 Power to Fume Hood 2533 540 B 360 20 Power to Fume Hood 2533 360 C 360 20 2 Recept Fume Hood 2533 540 A 20 Spare 180 B 360 20 2 Recept Equip Room 2500 540 C 850 20 1 Recept Equip Room 2500 360 A 850 2P 540 B 20 Spare 0 C 2P 180 A 20 Spare 540 B 360 20 2 Recept Lab 2200 360 C 850 20 1 Recept Lab 2200 540 A 850 2P 180 B 360 20 2 Lab Bench Recepts 540 C 360 20 2 Lab Bench Recepts 360 A 360 20 2 Lab Bench Recepts 540 B 360 20 2 Lab Bench Recepts 180 C 20 Spare 360 A 20 Spare 180 B 20 Spare 180 C 20 Spare
100 AMP MLO VA PHA PHB PHC VA CB LOAD 180 A 360 20 2 Recept TCR 2526 540 B 180 20 1 Recept TCR 2526 360 C 180 20 1 Recept TCR 2526 540 A 750 20 Refrigerator TCR 2526 180 B 900 20 Incubator TCR 2526 540 C 600 20 Bio Safety Cabinet TCR 2526 360 A 180 20 1 Recept TCR 2526 540 B 600 20 Bio Safety Cabinet TCR 2526 180 C 900 20 Incubator TCR 2526 360 A 20 180 B 180 20 1 Recept Equip Room 2510 180 C 850 20 1 Recept Equip Room 2510 A 850 2P 360 B 850 20 1 Recept Equip Room 2510 540 C 850 2P 180 A 360 20 2 Recept Equip Room 2510 540 B 20 360 C 20 540 A 20 Spare 360 B 20 Spare 540 C 20 Spare
200 AMP MLO VA PHA PHB PHC VA CB LOAD CKT. 360 A 540 20 2 Recepts Cust 2840, FCU SW2-2 2 450 B 540 20 3 Recepts Mech 2650, Elec 2820, 2830 4 450 C 540 20 3 Recepts Substation 2810 6 180 A 540 20 3 Recept 2810, Mech 2611, FCU SW3-2 8 450 B 360 20 2 Recept Custodial 2840 10 450 C 360 20 2 Recept Custodial 2840 12 450 A 360 20 Recept Stair SW2-2 & Generator 14 450 B 240 20 Sterilizer ST-3 Control Panel 16 360 C 240 20 Sterilizer ST-4 Control Panel 18 450 A 200 20 Glass Washer GW-3 Control Panel 20 450 B 200 20 Glass Washer GW-4 Control Panel 22 360 C 540 20 3 Recepts Glass Wash 2610 24 450 A 180 20 Recept Stair SW3-2 26 450 B 20 2 General Recept 2HW2, FCU 2830 28 180 C 20 Spare 30 450 A 20 Spare 32 450 B 20 Spare 34 245 C 20 Spare 36 1000 A 20 Spare 38 1000 B 20 Spare 40 1000 C 100 20 Facility Monitoring System 2611 42 Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,160 VA 5,040 VA 4,825 VA 15,025 VA 12,513 VA 34.7 A 0 VA Total Continuous Load: Total Non-Continuous Load: 15,025 VA
2 Recepts 2 Recepts 2 Recepts 2 Recepts 2 Recepts 2 Recepts 2 Recepts Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,940 VA 4,500 VA 4,580 VA 14,020 VA 12,010 VA 33.3 A Total Continuous Load: 0 VA Total Non-Continuous Load: 14,020 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,660 VA 5,410 VA 6,080 VA 16,150 VA 13,075 VA 36.3 A Total Continuous Load: 0 VA Total Non-Continuous Load: 16,150 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 4,320 VA 3,060 VA 2,700 VA 10,080 VA 10,040 VA 27.9 A Total Continuous Load: 0 VA Total Non-Continuous Load: 10,080 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 100 AMP MLO LOAD CB VA PHA PHB PHC VA Corr. 4HW1, Lnge 4HW1A,4HW1B - Gen. Ltg. 20 1512 A 0 Rm's 4000,4010,4011B,4020-Gen. Ltg. 20 834 B 0 Lab Shell Out 4500 - Gen. Ltg. 20 756 C 0 Rm's 4820,4830,4840,4850 - Gen. Ltg. 20 432 A 0 Penthouse 5000, Rm. 5101 - Gen. Ltg. 20 1026 B 0 Spare 20 0 C 0 Spare 20 0 A 0 Spare 20 0 B 0 Spare 20 0 C 0 Space A Space B Space C 300 CB 20 20 20 20 20 20 20 20 20
LP-4
LOAD CKT. 2 4 6 8 10 12 14 16 18 20 22 24 *
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD
PANELBOARD SCHEDULE
RP-PH
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD TV Recepts Conference 4010 2 Recepts Conference 4010 2 Recept Corridor 4HW1 Spare EWC 4HW1C
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 2 Recept Corridor 4HW1 20 TV Recepts Corridor 4HW1 20 3 Recepts Collaboration 4040 20 2 Recepts Collaboration 4040 20 2 Recepts Collab 4030, Write-up 4100 20 Spare 20 2 Recept Corridor 4HW1 20 Spare 20 Spare 20 Spare 20 Spare 20 Spare 20 Spare 2P Spare 20 Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Surface 10,000 A 3 4 60
RP-4B
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Recepts, UH-B Shell Space 4 Recepts Shell Space 3 Recepts Shell Space Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-3C
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
! ! ! ! !
Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space 20 Lighting Control Power Supplies Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
200 AMP MLO CB VA PHA PHB PHC VA CB LOAD CKT. 25 1320 A 1320 25 2 Cold Room 1501 Condensing Unit 1320 B 1320 Cold Room 1511 Condensing Unit 4 3P 1320 C 1320 3P 6 25 1320 A 1320 25 8 Cold Room 2501 Condensing Unit 1320 B 1320 Cold Room 2511 Condensing Unit 10 3P 1320 C 1320 3P 12 25 1320 A 1320 25 14 Future Cold Room 3501 Condensing Unit 1320 B 1320 Future Cold Room 3511 Condensing Unit 16 3P 1320 C 1320 3P 18 25 1320 A 1320 25 20 Future Cold Room 4501 Condensing Unit 1320 B 1320 Future Cold Room 4511 Condensing Unit 22 3P 1320 C 1320 3P 24 Spare 20 A 696 15 EF-1 (1/4 HP) 26 Spare 20 B 20 Spare 28 CUH PH-1, UH PH-2 20 280 C 20 Spare 30 UH PH-1, UH PH-4 20 280 A 20 Spare 32 UH PH-3, UH PH-6, UH PH-7 20 420 B 720 20 4 Recept Equipment Platform 34 UH PH-5, CUH PH-2 20 280 C 540 20 3 Recept Equipment Platform 36 Space A 540 20 3 Recept Penthouse 38 Space B 540 20 3 Recept Penthouse 40 Space C 540 20 3 Recept Penthouse 42 Panel Information Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 12,076 VA 12,240 VA 12,200 VA 36,516 VA 23,258 VA 64.6 A Total Continuous Load: 0 VA Total Non-Continuous Load: 36,516 VA
200 AMP MLO VA PHA PHB PHC VA CB LOAD 400 A 360 20 2 Recept Corridor 4HW1 360 B 20 360 C 400 20 TV Recepts Corridor 4HW1 A 20 Spare 500 B 20 Spare 360 C 20 Spare 360 A 360 20 2 Recept Corridor 4HW3 360 B 180 20 2 Recept EC 4009 400 C 20 Spare 540 A 20 Spare 360 B 20 Spare 360 C 20 Spare A 20 Spare 360 B 20 Spare C 280 20 2 UH-B A Space B Space C Space A Space 0 B Space 0 C Space
200 AMP MLO VA PHA PHB PHC VA CB LOAD 500 20 Spare 720 B 20 Spare 540 C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 125 20 Roller Shad Control Panel 3820 B 20 Spare C 20 Spare
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
1,944 VA 1,860 VA 1,056 VA 4,860 VA 4,860 VA 5.8 A Total Continuous Load: Total Non-Continuous Load: 4,560 VA 300 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 2,020 VA 2,120 VA 2,160 VA 6,300 VA 6,300 VA 17.5 A Total Continuous Load: Total Non-Continuous Load: 0 VA 6,300 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 125 VA 720 VA 540 VA 1,385 VA 1,885 VA 5.2 A Total Continuous Load: Total Non-Continuous Load: 0 VA 1,885 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 100 AMP MLO LOAD CB VA PHA PHB PHC VA Corr. 3HW1, Lnge 3HW1A,3HW1B - Gen. Ltg. 20 1104 A 0 Rm's 3000,3011A,3011B,3020-Gen. Ltg. 20 648 B 0 Lab Shell Out 3500 - Gen. Ltg. 20 756 C 0 Rm's 3820,3830,3840,3850 - Gen. Ltg. 20 432 A 0 Spare 20 0 B 0 Spare 20 0 C 0 Spare 20 0 A 0 Spare 20 0 B 0 Spare 20 0 C 0 Space A Space B Space C 300 Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 480/277 Surface 22,000 A 3 4 60 PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS: CB 20 20 20 20 20 20 20 20 20
LP-3
LOAD CKT. 2 4 6 8 10 12 14 16 18 20 22 24 *
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 15 3P 200 AMP MLO VA PHA PHB PHC A B C A B C A B C A B C A B C A B C A B C VA 540 CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-4E
CKT. Spare 2 3 Recepts Mech 4650, Elec 4820, 4830 4 Spare 6 Spare 8 2 Recept Shell 4840 10 2 Recept Shell 4840 12 Recept Stair SW2-4 14 16 3 UH-B 18 Spare 20 Spare 22 Spare 24 Recept Stair SW3-4 26 2 General Recept 4HW2 28 Spare 30 Spare 32 Spare 34 Spare 36 Spare 38 Spare 40 Spare 42 LOAD
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 200 AMP MLO VA PHA PHB PHC VA A B C A B C A B C A B C A B C A B C A B C CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-4A
LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2P 20
RP-3B
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
! ! ! !
Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space 20 Lighting Control Power Supplies Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD
180 360
2 Recept Corridor 3HW1 TV Recepts Corridor 3HW1 3 Recepts Collaboration 3040 2 Recepts Collaboration 3040 2 Recepts Collab 3030, Shell 3100 Spare 2 Recept Corridor 3HW1 Spare Spare Spare Spare Spare Spare Spare
200 AMP MLO VA PHA PHB PHC VA CB LOAD 400 A 360 20 2 Recept Corridor 3HW1 360 B 20 360 C 400 20 TV Recepts Corridor 3HW1 A 20 Spare 500 B 20 Spare 360 C 20 Spare 360 A 360 20 2 Recept Corridor 3HW3 360 B 180 20 2 Recept EC 3009 400 C 20 Spare 540 A 20 Spare 360 B 20 Spare 360 C 20 Spare A 20 Spare 360 B 20 Spare C 280 20 2 UH-B A Space B Space C Space A Space 0 B Space 0 C Space
1,536 VA 648 VA 1,056 VA 3,240 VA 3,240 VA 3.9 A Total Continuous Load: Total Non-Continuous Load: 2,940 VA 300 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 540 VA 1,260 VA 780 VA 2,580 VA 2,580 VA 7.2 A Total Continuous Load: Total Non-Continuous Load: 0 VA 2,580 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 0 VA 0 VA 0 VA 0 VA 0 VA 0.0 A Total Continuous Load: Total Non-Continuous Load: 0 VA 0 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 2,020 VA 2,120 VA 2,160 VA 6,300 VA 6,300 VA 17.5 A Total Continuous Load: Total Non-Continuous Load: 0 VA 6,300 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 LOAD Rm's 2000,2010,2040,2040A,2042,2050 Rm's 2009,2020,2021,2022,2023
Corr. 2HW1, Lnge 2HW1A,2HW1B,2030,2060
LP-2
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare
Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 2P 20 2P 20 20 2P 20 20 20 2P 20 20 2P 20 20 2P 20 200 AMP MLO VA PHA PHB PHC VA A B C A B C A B C A B C A B C A B C A B C CB 20 20 20 2P 20 20 20 2P 20 2P 20 20 20 2P 20 2P 20 20 20 20 20
RP-4D
LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 15 3P 200 AMP MLO VA PHA PHB PHC A B C A B C A B C A B C A B C A B C A B C VA 540 CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-3E
CKT. Spare 2 3 Recepts Mech 3650, Elec 3820, 3830 4 Spare 6 Spare 8 2 Recept Shell 3840 10 2 Recept Shell 3840 12 Recept Stair SW3-3 14 16 1 UH-B, FCU SW2-3 18 Spare 20 Spare 22 2 UH-B, FCU SW3-3 24 Recept Stair SW3-3 26 2 General Recept 3HW2 28 Spare 30 Spare 32 Spare 34 Spare 36 Spare 38 Spare 40 Spare 42 LOAD
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 200 AMP MLO VA PHA PHB PHC VA A B C A B C A B C A B C A B C A B C A B C CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-3A
LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
! ! ! ! ! ! ! !
North Office's - Gen. Ltg. North Write-Up Space 2300 - Gen Ltg. Support Spaces, Tissue Cult. - Gen. Ltg. Lab 2400 - Gen. Ltg. Lab 2400 - Gen. Ltg. Spare Space Space Space
CB 20 20 20 20 20 20 20 20 20
100 AMP MLO VA PHA PHB PHC VA CB LOAD CKT. 2 ! 1560 A 432 20 Rm's 2820,2830,2840,2850 - Gen. Ltg. 623 B 1008 20 Rm's 2600,2610,2611 - Gen. Ltg. 4 ! 838 C 1026 20 South Office's - Gen. Ltg. 6 ! 1026 A 1143 20 South Write-Up Space 2100 - Gen Ltg. 8 ! 1143 B 1050 20 Support Spaces, Tissue Cult. - Gen. Ltg. 10 ! 950 C 1136 20 Lab 2200 - Gen. Ltg. 12 ! 1136 A 1136 20 Lab 2200 - Gen. Ltg. 14 ! 1136 B 0 20 Spare 16 0 C 0 20 Spare 18 A Space 20 B Space 22 C 300 20 Lighting Control Power Supplies 24 * Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 6,433 VA 4,960 VA 4,250 VA 15,643 VA 15,643 VA 18.8 A Total Continuous Load: 15,343 VA Total Non-Continuous Load: 300 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 25,000 A 3 4 60
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 0 VA 0 VA 0 VA 0 VA 0 VA 0.0 A Total Continuous Load: Total Non-Continuous Load: 0 VA 0 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 540 VA 1,260 VA 1,060 VA 2,860 VA 2,860 VA 7.9 A Total Continuous Load: Total Non-Continuous Load: 0 VA 2,860 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 0 VA 0 VA 0 VA 0 VA 0 VA 0.0 A Total Continuous Load: Total Non-Continuous Load: 0 VA 0 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
LP-1
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD 2 Recepts, UH-B Shell Space 4 Recepts Shell Space 3 Recepts Shell Space Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
RP-4C
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare
Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 2P 20 2P 20 20 2P 20 20 20 2P 20 20 2P 20 20 2P 20 200 AMP MLO VA PHA PHB PHC VA A B C A B C A B C A B C A B C A B C A B C CB 20 20 20 2P 20 20 20 2P 20 2P 20 20 20 2P 20 2P 20 20 20 20 20
RP-3D
LOAD Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Lab Ceiling Recept TSA78M (78" Table) Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
PANELBOARD SCHEDULE
CB 20 2P 20 2P 20 2P 20 2P 20 2P 20 20 20 20 20 20 20 20 20 20 20
RP-2S
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO CKT. LOAD CB VA PHA PHB PHC VA CB LOAD CKT. 1920 20 Rm's 1701,1702,1703,1704, MRI 2 ! 1 Rm's 1000,1011,1030,1040,1040A,1042,1060 20 1505 A B 1008 20 Rm's 1600,1610,1611 - Gen. Ltg. 4 ! 3 Rm's 1011A,1011B,1020,1021,1022,1023, EP120 732 Rm's 1810,1811,1815,EP2,1820,1830,1840,1850,1860 20 992 C 1386 20 6 ! 5 Corridor 1HW1, Collab. Lounge 1010 1143 20 South Write-Up Space 1100 - Gen Ltg. 8 ! 7 Corridor/Lobby Verticle Wall Linear Lights 20 1278 A 20 1143 B 1463 20 South Office's, Support Spaces-Gen. Ltg. 10 ! 9 North Write-Up Space 1300 - Gen Ltg. C 1590 20 Lab 1200 - Gen. Ltg. 12 ! 11 North Office's, Support Spaces-Gen. Ltg. 20 1263 20 1590 A 0 20 Spare 14 ! 13 Lab 1400 - Gen. Ltg. 15 Spare 20 0 B 0 20 Spare 16 17 Spare 20 0 C 0 20 Spare 18 19 Space A Space 20 21 Space B Space 22 23 Space C 300 20 Lighting Control Power Supplies 24 Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 7,436 VA 4,346 VA 5,531 VA 17,313 VA 17,313 VA 20.8 A
! ! ! ! ! !
200 AMP MLO VA PHA PHB PHC VA CB LOAD 500 20 Spare 720 B 20 Spare 540 C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 125 20 Roller Shad Control Panel 4820 B 20 Spare C 20 Spare
100 AMP MLO VA PHA PHB PHC VA CB LOAD 180 A 750 20 Refrigerator TCR 2539 540 B 180 20 1 Recept TCR 2539 360 C 360 20 2 Recept TCR 2539 540 A 180 20 1 Recept TCR 2539 180 B 900 20 Incubator TCR 2539 540 C 600 20 Bio Safety Cabinet TCR 2539 360 A 180 20 1 Recept TCR 2539 540 B 600 20 Bio Safety Cabinet TCR 2539 0 C 900 20 Incubator TCR 2539 180 A 20 Spare 540 B 20 Spare 360 C 360 20 2 Lab Bench Recept 540 A 360 20 2 Lab Bench Recept 180 B 360 20 2 Lab Bench Recept 540 C 360 20 2 Lab Bench Recept 360 A 20 Spare 540 B 20 Spare 180 C 20 Spare 360 A 20 Spare 180 B 20 Spare 180 C 20 Spare
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 125 VA 720 VA 540 VA 1,385 VA 1,885 VA 5.2 A Total Continuous Load: Total Non-Continuous Load: 0 VA 1,885 VA
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 25,000 A 3 4 60
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 0 VA 0 VA 0 VA 0 VA 0 VA 0.0 A Total Continuous Load: Total Non-Continuous Load: 0 VA 0 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 3,990 VA 4,740 VA 4,740 VA 13,470 VA 11,735 VA 32.6 A Total Continuous Load: 0 VA Total Non-Continuous Load: 13,470 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
ERP-2BS
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Rack Fiber Room 1830A Rack Fiber Room 1830A Rack Fiber Room 1830A 2 Recepts UCF Room 1830 2 Recepts UCF Room 1830 2 Recepts UCF Room 1830 2 Recepts Fiber Room 1830A 2 Recepts Fiber Room 1830A 2 Recepts Fiber Room 1830A 2 Recepts Fiber Room 1830A Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare
PANELBOARD SCHEDULE
CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 2P 20
ERP-1AE
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
100 AMP MLO LOAD CB VA PHA PHB PHC VA CB LOAD CKT. Ultra-low Temp Freezer Room 2600 20 1150 A 20 Spare 2 2P 1150 B 1150 20 Ultra-low Temp Freezer Room 2600 4 Spare 20 C 1150 2P 6 Freezer Linear Equip Room 2600 20 800 A 800 20 Freezer Linear Equip Room 2600 8 Spare 20 B 20 Spare 10 Refrigerator Linear Equip Room 2600 20 600 C 600 20 Refrigerator Linear Equip Room 2600 12 Spare 20 A 20 Spare 14 2P B 20 Spare 16 Ultra-low Temp Freezer Room 2600 20 1150 C 20 Spare 18 2P 1150 A 1150 20 Ultra-low Temp Freezer Room 2600 20 Spare 20 B 1150 2P 22 Freezer Linear Equip Room 2600 20 800 C 600 20 Refrigerator Linear Equip Room 2600 24 Spare 20 A 20 Spare 26 Refrigerator Linear Equip Room 2600 20 600 B 800 20 Freezer Linear Equip Room 2600 28 Spare 20 C 20 Spare 30 Ultra-low Temp Freezer Room 2600 20 1150 A 20 Spare 32 2P 1150 B 1150 20 Ultra-low Temp Freezer Room 2600 34 Spare 20 C 1150 2P 36 Freezer Linear Equip Room 2600 20 800 A 600 20 Refrigerator Linear Equip Room 2600 38 Spare 20 B 20 Spare 40 Refrigerator Linear Equip Room 2600 20 600 C 800 20 Freezer Linear Equip Room 2600 42 Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 7,600 VA 7,150 VA 7,450 VA 22,200 VA 16,100 VA 44.7 A Total Continuous Load: 0 VA Total Non-Continuous Load: 22,200 VA
100 AMP MLO VA PHA PHB PHC VA CB LOAD 400 A 360 20 2 Recepts UFC Room 2830 400 B 360 20 2 Recepts UFC Room 2830 400 C 360 20 2 Recepts UFC Room 2830 360 A 20 Spare 360 B 20 Spare 360 C 450 20 Fire Alarm Control Panels 360 A 130 20 Fire Alarm IGD 360 B 20 Spare 360 C 20 360 A 180 20 Recept Elevator Pit EP2 B 864 15 Dry Pipe System Air Compressor C 20 Spare A 20 Spare B 20 Spare C 20 Spare A 20 Spare B 0 20 Spare C 0 20 Spare A 0 20 Spare 0 B 0 20 Spare 0 C 0 20 Spare
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 2,150 VA 2,344 VA 1,930 VA 6,424 VA 6,424 VA 17.8 A Total Continuous Load: Total Non-Continuous Load: 0 VA 6,424 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD CB Ultra-low Temp Freezer Room 2500 20 2P Spare 20 Freezer Equipment Room 2500 20 Spare 20 Refrigerator Equipment Room 2500 20 Spare 20 Spare 20 Ultra-low Temp Freezer Room 2500 20 2P Spare 20 Freezer Equipment Room 2500 20 Spare 20 Refrigerator Equipment Room 2500 20 Spare 20 Spare 20 2P Spare 20 Spare 20 Spare 20 Spare 20 Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60 100 AMP MLO VA PHA PHB PHC 1150 A 1150 B C 800 A B 600 C A B 1150 C 1150 A B 800 C A 600 B C A B C A B C VA 1150 1150 800 600 CB 20 20 2P 20 20 20 20 20 20 20 2P 20 20 20 20 20 20 20 20 20 20
ERP-2AS
LOAD Spare Ultra-low Temp Freezer Room 2510 Freezer Equipment Room 2510 Spare Refrigerator Equipment Room 2510 Spare Spare Spare Ultra-low Temp Freezer Room 2510 Refrigerator Equipment Room 2510 Spare Freezer Equipment Room 2510 Spare Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 LOAD Corr. 3HW1/Stair Landing - EM Ltg. N. Lab Shell Out 3500 - EM Ltg. S. Lab Shell Out 3500 - EM Ltg. Stair SW5-4, SW5-5A - EM Ltg. Penthouse - EM Ltg. Spare Spare Spare Spare Space Space Space CB 20 20 20 20 20 20 20 20 20 100 AMP MLO VA PHA PHB PHC VA 1055 A 560 324 B 324 432 C 432 350 A 250 1018 B 540 0 C 432 0 A 0 0 B 0 0 C A B C CB 20 20 20 20 20 20 20 20 20
ELP-4E
LOAD Corr. 4HW1- EM Ltg. N. Lab Shell Out 4500 - EM Ltg. S. Lab Shell Out 4500 - EM Ltg. Stair SW4-4 - EM Ltg. N. & S. Main Stairs - LED Handrail Mezzanine - EM Ltg. Spare Spare Spare Space Space Space CKT. 2 4 6 8 10 12 14 16 18 20 22 24
! ! ! ! ! !
! ! ! ! ! !
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 2,215 VA 2,206 VA 1,296 VA 5,717 VA 5,717 VA 6.9 A Total Continuous Load: Total Non-Continuous Load: 5,717 VA 0 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,050 VA 4,850 VA 4,900 VA 14,800 VA 12,400 VA 34.4 A Total Continuous Load: 0 VA Total Non-Continuous Load: 14,800 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 LOAD Spare Spare 2 Recepts UFC 3830 2 Recepts UFC 3830 Security Panel ELEC Security Panel ELEC Security Panel ELEC Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Surface 10,000 A 3 4 60 CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 100 AMP MLO VA PHA PHB PHC A B 360 C 360 A 600 B 600 C 600 A 600 B 600 C 600 A 0 B 0 C 0 A 0 B 0 C 0 A 0 B 0 C 0 A 0 B 0 C VA CB 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
ERP-4AE
LOAD Spare Spare 2 Recepts UFC 4830 2 Recepts UFC 4830 FCU-1 Elevator Machine Room FCU-2 Elevator Machine Room 2 Recepts Elev Machine Room Car 1 Recept and Fan Car 1 Lights Car 2 Recept and Fan Car 2 Lights Spare Spare Spare Spare Spare Space Space Space Space CKT. 2 4 6 8 10 12 14 16 18 ! 20 22 ! 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
PANELBOARD SCHEDULE
LOAD CB Ultra-low Temp Freezer Room 1600 20 2P Spare 20 Freezer Linear Equip Room 1600 20 Spare 20 Refrigerator Linear Equip Room 1600 20 Spare 20 Spare 20 Ultra-low Temp Freezer Room 1600 20 2P Spare 20 Freezer Linear Equip Room 1600 20 Spare 20 Refrigerator Linear Equip Room 1600 20 Spare 20 Ultra-low Temp Freezer Room 1600 20 2P Spare 20 Freezer Linear Equip Room 1600 20 Spare 20 Refrigerator Linear Equip Room 1600 20 Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60 100 AMP MLO VA PHA PHB PHC 1150 A 1150 B C 800 A B 600 C A B 1150 C 1150 A B 800 C A 600 B C 1150 A 1150 B C 800 A B 600 C VA 1150 1150 800 600 CB 20 20 2P 20 20 20 20 20 2P 20 2P 20 20 20 20 20 20 2P 20 20 20
ERP-1BS
CKT. Spare 2 Ultra-low Temp Freezer Room 1600 4 6 Freezer Linear Equip Room 1600 8 Spare 10 Refrigerator Linear Equip Room 1600 12 Spare 14 Spare 16 18 Ultra-low Temp Freezer Room 1600 20 22 Refrigerator Linear Equip Room 1600 24 Spare 26 Freezer Linear Equip Room 1600 28 Spare 30 Spare 32 Ultra-low Temp Freezer Room 1600 34 36 Refrigerator Linear Equip Room 1600 38 Spare 40 Freezer Linear Equip Room 1600 42 LOAD
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 LOAD Corr. 2HW1C,2HW1D,2HW3 - EM Ltg.
T. Rm's 2021,2022, Equip. Rm's 2500,2510
ELP-2E
CKT. 2 ! 4 ! 6 ! 8 10 12 14 16 18 20 22 24
! ! ! ! !
Corridor 2HW1 - EM Ltg. North Write-Up Space 2300 - EM Ltg. Lab 2400 - EM Ltg. Spare Spare Spare Spare Space Space Space
CB 20 20 20 20 20 20 20 20 20
100 AMP MLO VA PHA PHB PHC VA CB LOAD 679 A 605 20 South Write-Up Space 2100 - EM Ltg. 389 B 1750 20 Rm's 2600,2610,2810, 2HW2 - EM Ltg. 985 C 474 20 Lab 2200 - EM Ltg. 605 A 0 20 Spare 522 B 0 20 Spare 0 C 0 20 Spare 0 A 0 20 Spare 0 B 0 20 Spare 0 C 0 20 Spare A Space B Space C Space Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 1,889 VA 2,661 VA 1,459 VA 6,009 VA 6,009 VA 7.2 A Total Continuous Load: Total Non-Continuous Load:
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 2,640 VA 2,070 VA 2,430 VA 7,140 VA 7,140 VA 19.8 A Total Continuous Load: Total Non-Continuous Load: 220 VA 6,920 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 7,600 VA 7,150 VA 7,450 VA 22,200 VA 16,100 VA 44.7 A Total Continuous Load: 0 VA Total Non-Continuous Load: 22,200 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
6,009 VA 0 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 CB 20 North Door Operators 1VB1 (4 Leafs) 20 North Window Operators (1st Floor) 20 North Window Operators (2nd Floor) 20 North Window Operators (3rd Floor) 20 North Window Operators (4th Floor) 20 Lounge Window Operators (1st Flr) 20 Lounge Window Operators (1st Flr) 20 Lounge Window Operators (3rd Flr) 20 Lounge Window Operators (3rd Flr) 20 South Door Operators 1VB2 (4 Leafs) 20 South Window Operators (1st Floor) 20 South Window Operators (2nd Floor) 20 South Window Operators (3rd Floor) 20 South Window Operators (4th Floor) 20 Spare 20 Spare 20 Spare 20 Spare 20 Spare 2P Spare 20 Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60 LOAD
ERP-2AE
CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
PANELBOARD SCHEDULE
LOAD CB Ultra-low Temp Freezer Room 1500 20 2P Spare 20 Freezer Equipment Room 1500 20 Spare 20 Refrigerator Equipment Room 1500 20 Spare 20 Spare 20 Ultra-low Temp Freezer Room 1500 20 2P Spare 20 Freezer Equipment Room 1500 20 Spare 20 Refrigerator Equipment Room 1500 20 Spare 20 Spare 20 2P Spare 20 Spare 20 Spare 20 Spare 20 Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz: 208/120 Flush 10,000 A 3 4 60 100 AMP MLO VA PHA PHB PHC 1150 A 1150 B C 800 A B 600 C A B 1150 C 1150 A B 800 C A 600 B C A B C A B C VA 1150 1150 800 600 CB 20 20 2P 20 20 20 20 20 20 20 2P 20 20 20 20 20 20 20 20 20 20
ERP-1AS
LOAD Spare Ultra-low Temp Freezer Room 1510 Freezer Equipment Room 1510 Spare Refrigerator Equipment Room 1510 Spare Spare Spare Ultra-low Temp Freezer Room 1510 Refrigerator Equipment Room 1510 Spare Freezer Equipment Room 1510 Spare Spare Spare Spare Spare Spare Spare CKT. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
PANELBOARD SCHEDULE
CKT. 1 3 5 7 9 11 13 15 17 19 21 23 LOAD CB Canopy & Exterior Bldg. Mtd. Lights 20 T. Rm's 1021,1022, Vending - EM Ltg. 20 N. & S. Vestibule's, Corridor 1HW1 - EM Ltg. 20 North Write-Up Space 1300 - EM Ltg. 20 Lab 1400 - EM Ltg. 20 Stair SW3 - EM Ltg. 20 Stair SW2 - EM Ltg. 20 Spare 20 Spare 20 Space Space Space
ELP-1E
CKT. 2 4 6 8 10 12 14 16 18 20 22 24
100 AMP MLO VA PHA PHB PHC VA CB LOAD A 20 Spare 260 B 20 Spare 250 C 20 Spare 250 A 20 Spare 250 B 20 Spare 250 C 20 Spare 500 A 20 Spare 500 B 20 Spare 500 C 180 20 Recept Elevator Pit EP1 500 A 20 260 B 20 Spare 250 C 20 Spare 250 A 20 Spare 250 B 20 Spare 250 C 20 Spare A 20 Spare B 0 20 Spare C 0 20 Spare A 0 20 Spare 0 B 0 20 Spare 0 C 0 20 Spare
! ! ! ! ! ! !
100 AMP MLO VA PHA PHB PHC VA CB LOAD 200 20 MRI Rm - EM Ltg. 817 A 403 B 1170 20 Rm's 1600,1610,1810, 1HW2 - EM Ltg. 924 C 180 20 Steam Tunnel - EM Ltg. 605 A 605 20 South Write-Up Space 1100 - EM Ltg. 526 B 526 20 Lab 1200 - EM Ltg. 700 C 540 20 N. & S. Main Stair's - LED Handrail Ltg. 700 A 0 20 Spare 0 B 0 20 Spare 0 C 0 20 Spare A Space B Space C Space Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 2,927 VA 2,625 VA 2,344 VA 7,896 VA 7,896 VA 9.5 A Total Continuous Load: Total Non-Continuous Load:
! ! ! ! ! !
Panel Information Volts: Mounting: A.I.C. (RMS Symmetrical): Phase: Wire: Hertz:
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 1,500 VA 1,520 VA 1,680 VA 4,700 VA 4,700 VA 13.0 A Total Continuous Load: Total Non-Continuous Load: 0 VA 4,700 VA
Symbols Note: All Symbols May Not Be Used * PROVIDE LOCK ON ATTACHMENT # PROVIDE SWD RATED BREAKER @ PROVIDE HACR RATED BREAKER + PROVIDE GFCI TYPE BREAKER ! INDICATES CONTINUOUS LOAD 5,050 VA 4,850 VA 4,900 VA 14,800 VA 12,400 VA 34.4 A Total Continuous Load: 0 VA Total Non-Continuous Load: 14,800 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
7,896 VA 0 VA
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
PHASE A CONNECTED LOAD: PHASE B CONNECTED LOAD: PHASE C CONNECTED LOAD: TOTAL CONNECTED LOAD: TOTAL ESTIMATED DEMAND LOAD: TOTAL ESTIMATED DEMAND AMPS:
REINF STEEL (#4 BARS @16") 1" CHAMFER (ALL AROUND) (SEE PLAN) 4" MIN 1' - 0". CONCRETE EQUIPMENT PAD WELDED WIRE FABRIC (6x6-W2.9 x W2.9)
EPOXY BONDING ADHESIVE NOTES: 1. COORDINATE SIZE AND LOCATION OF CONCRETE EQUIPMENT PADS INCLUDING ANCHORING DEVICES W/INFORMATION PROVIDED BY THE APPROPRIATE EQUIPMETN MFR. EDGE OF PAD TO EDGE OF EQUIPMENT SHALL NOT EXCEED 4".
1/2" STEEL SUPPORT ROD SPACED 6'-0" O.C. MAX #10 GREEN GROUND WIRE BOLTED TO TRAY WITH GROUND LUG CONDUIT BUSHING 3/8" BOLT CONDUIT
6" MIN
6" MIN
WORKING CLEARANCE
18".
8" MIN
1".
6" SAND BED CONCRETE ENCASEMENT DUCT BANK (SEE PLAN FOR DUCT BANK SIZE)
WALL
1/4" x 2" COPPER GROUND BUS AROUND ENTIRE PERIMETER OF SUBSTATION ROOM. SEE DETAIL 4 THIS SHEET GROUND CABLE THERMOWELDED TO BUS. PROVIDE ONE CONNECTION ON EACH SIDE OF SUBSTATION 2". TERMINATE ON BUS BAR
EQUIPMENT FRONT SPARE 1" CONDUITS SEE NOTE 1 4" HIGH CONCRETE PAD WITH CHAMFER, VERIFY EQUIPMENT SIZE WITH APPROVED SHOP DRAWING. PAD BENATH SUBSTATION SHALL BE LEVEL AND VARY NO MORE THAN 1/8" OVERALL. SEE DETAIL 7 THIS DRAWING.
GROUND CABLE BOLTED COMPRESSION LUG TO SWITCHGEAR GROUND BUS. PROVIDE ONE CONNECTION ON EACH END OF SUBSTATION 2".
EXTEND NEW 1" (MIN) CONDUIT TO CABLE TRAY, ACCESSIBLE LOCATION ABOVE CEILING, OR DESIGNATED CONTROL PANEL ROOM, AS REQUIRED.
2nd FLOOR TOP FEED PANEL (TYP) 4" x 5.4 STEEL LEVELING CHANNEL INSTALLED FLUSH WITH FLOOR. VERIFY LOCATION AND SPACING WITH APPROVED SHOP DRAWINGS (TYP.) CEILING RECESSED MOUNTED PANEL
FINISH CEILING (IF EXIST) GROUND CABLES FROM SUBSTATION GROUND BUS TO SUBSTATION ROOM BUS BAR THRU SLEEVES IN FLOOR
NEW 1/2" RECESSED CONDUIT EXTEND FROM NEW RECESSED DOOR CONTACT BOX IN FRAME NEW 1/2" RECESSED CONDUIT EXTEND FROM CARD READER BOX.
CONDUIT THROUGH SLABS NEW VON DUPRIN EPT10 POWER TRANSFER FOR NEW ELECTRIC MORTISE LOCK OR PANIC EXIT DEVICE, WITH BUILT IN REX. UP TO GROUND BAR 1st FLOOR SLAB GROUND CABLES IN CONDUIT FROM ROOM BUS BAR TO GROUND MAT BENEATH FIRST FLOOR SLAB (TYP FOR 4) GROUND CABLE THERMOWELDED TO GROUND ROD PANEL COVER TO COMPLETELY COVER WALL OPENING
NEW RECESSED MOUNTED SINGLE-GANG BOX FOR CARD READER ON EXTERIOR SIDE OF DOOR
44.5" AFF
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
NOTE: 1. INSTALL PULL STRINGS IN ALL CONDUIT RUNS.
L.A.
D. Wilber
TYPICAL ELECTRIC MORTISE LOCK OR PANIC EXIT DEVICE STYLE SINGLE DOOR PREP FOR ACCESS CONTROL
NO SCALE
Project Administrator:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
Drawing Scale:
No Scale
WALL 2" THICK FIBER SPACER STRUCTURE COPPER GROUND BUS NOTE: 1. PROVIDE A TOTAL OF (4) SPARE 1" CONDUITS STUBBED & CAPPED INTO THE ACCESSIBLE CEILING SPACE.
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
2
7/16" - 16 MACHINE BOLT WITH WASHER 4'-0" O.C. FOR GROUND BUSSES LONGER THAN 4'-0"
BEAM CLAMP SINGLE OUTLET TWIST LOCK RECEPT.-277V 3/C "SO" CORD EMT CHAIN HANGER
8'-0" U.O.N.
. 12"
12204-1000
Details
NOTES: 1. FURNISH AND INSTALL MISC. STEEL CLAMPED TO PURLINS TO SUPPORT LIGHTING FIXTURES WHERE THE FIXTURES ARE LOCATED BETWEEN STRUCTURAL MEMBERS. 2. NO FIXTURES ARE TO BE HUNG DIRECTLY FROM DECK.
PUSHBUTTON
1/2/2014 10:40:26 AM
E7.1
OF
Bio-Engineering Facility
S. Hopper
CIVIL
S. Gardner
APPR. Project Designer:
S. Schiappacasse
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date:
3".
RESE
INSERT REINFORCING BAR A MINIMUM OF 2" INTO MANHOLE WALL AND EPOXY
#4 REINFORCING BAR. SEE DUCT SECTION FOR NUMBER AND LOCATION. (IF ELECTRICAL POWER DUCT) #4 REINFORCING BAR . 4" MIN. (TYP.)
EPOXY BONDING ADHESIVE FURNISH AND INSTALL BELL-ENDS FOR EACH CONDUIT
SECTION
NOTE: DUCTS ENTERING MANHOLES/VAULTS SHALL BE CONSTRUCTED AS INTEGRAL PARTS OF THE WALL: LEAVING AN OVERSIZED (ABOUT 4" ALL AROUND) OPENING INTO WALL TO RECEIVE DUCT. PROJECT WALL REINFORCING THROUGH THE DUCT'S CROSS SECTION WITHOUT TOUCHING THE CONDUIT'S SURFACES. SEE ALSO "POWER MANHOLE BELL END INSTALLATION" DETAIL.
GRADE
2H x 2V
GENERAL NOTES
1. 2. H NUMBER OF DUCTS IN HORIZONTAL PLANE. V NUMBER OF DUCTS IN VERTICAL PLANE DUCT BANKS SHALL BE MARKED WITH A 6 WIDE RED MARKER STRIP LABELED TO INDICATE HIGH VOLTAGE AND PLACED IN THE BACKFILL APPROXIMATELY 12 ABOVE THE ENTIRE LENGTH OF THE DUCT BANK. ALL POWER DUCTS HAVE #4/0 BARE COPPER GROUND CABLE, AND #4 REINFORCING BARS. USE DUCT SPACERS TO HOLD DUCTS IN PLACE. NOTED SPACING ARE MINIMUMS. USE PRODUCTS FROM CARLON, CANTEX OR STERLING. (TIE TOGETHER USING NON-FERROUS WIRE).
3. 4.
CP-11243
ARCH. MECH.
J. Kasdorf
ELEC.
R. Frazee
L.A.
D. Wilber
Project Administrator: Project Designer:
J. Johnson
Project Arch/Eng:
T. Hackett
Q.M. Review:
R. Bracci
PVC DUCT (TYPICAL FOR ALL) 4". #4 REINFORCING BARS IN DUCT RUN (IF ELECTRICAL POWER DUCT OR AS NOTED ON DESIGN DRAWINGS) (TYP.) DUCT SPACER DUCT SPACER
Drawing Scale:
1/8" = 1'-0"
Issue Date:
05-06-13 10-23-13 11-20-2013 01-08-2014
Issued for:
Design Development Bid Pack #2 - QM Review BP #2 - 99% Owner Review Bid Release #2 - Bids
#8 AWG WIRE. TIE WIRE AROUND BELL END, PULL THROUGH PLYWOOD AND SECURE 3/8" ANCHOR WITH FENDER WASHERS IN 4 PLACES 3/4" PLYWOOD REINFORCING BARS SHALL BE TIED TO DUCT SPACERS USING NON-METALLIC MATERIALS (TYP.)
1.
DUCT RUNS SHALL EXIT AND ENTER MANHOLES IN SAME SYMMETRICAL CONFIGURATION. DUCTS SHALL CORRESPOND AS MIRROR IMAGE FROM ONE END TO THE OTHER. LOCATIONS OF DUCT BANKS ENTERING MANHOLES SHALL BE COORDINATED WITH EXISTING CONDITIONS. SEE ALSO DUCT REINFORCING AT MANHOLES, VAULTS AND BUILDINGS DETAIL.
2.
#4/0 BARE COPPER GROUND CONDUCTOR THROUGHOUT DUCT. TYPICAL FOR ALL POWER DUCT SECTIONS.
2H x 2V
12204-1000
Details
1/2/2014 10:40:26 AM
E7.2
OF
Bio-Engineering Facility
S. Hopper
CIVIL
#4/0 BARE COPPER GROUND CONDUCTOR THROUGHOUT DUCT TYPICAL FOR ALL SECTIONS
BELOW GRADE
S. Gardner
APPR.
S. Schiappacasse
Drawn By:
M. Majchrzak
Approved:
R. Bracci
Date: