Description:
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
1 of 20
SEC-COA
Site:
Project no.:
Aux. Voltage :
125VDC
Bay Name
Serial No.
Manufacturer
: AREVA
Type
: MICOM P54331AE6M0540K
C.T Ratio
: 3000/1 Amp
VT Ratio
: 380/0.115kV
Frequency
: 50/60 Hz
Function
: 87L1
Soft Ware
Drawing No
: P543____6__540_C
: 10P54302
3.
DESCRIPTION
CHECKED
ELECTRICAL TESTS:
1
Indications Checked
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
2 of 20
SEC-COA
Site:
Project no.:
OPTO RELAY No
TERMINAL
FUNCTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
D1 D2
D3 D4
D5 D6
D7 D8
D9 D10
D11 D12
D13 D14
D15 D16
F1 F2
F3 F4
F5 F6
F7 F8
F9 F10
F11 F12
F13 F14
F15 F16
SPARE
CB CLOSED
CB OPEN
SPARE
SPARE
VT FAIL
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
STATUS CHECKED
FUNCTION
COLOUR
1
2
3
4
5
6
7
8
DIFF TRIP A
DIFF TRIP B
DIFF TRIP C
DIFF START
DIFF INTER TRIP
TEST LOOP BACK
COMM FAIL
VT FAIL
R
R
R
Y
R
Y
Y
Y
STATUS CHECKED
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
3 of 20
SEC-COA
Site:
Project no.:
TERMINALS
FUNCTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
H1 H2
H3 H4
H5 H6
H8 H9
H11 H12
H14 H15
H17 H18
G1 G2
G3 G4
G5 G6
G8 G9
G11 G12
G14 G15
G17 G18
7.
STATUS CHECKED
DIFF START FR
DIFF TRIP A SOE
DIFF TRIP B SOE
DIFF TRIP C SOE
DIFF COMM FAIL SOE
SPARE
SPARE
BATTERY FAIL
V,T FAIL
DIFF. START SOE
SPARE
RELAY BURDEN:
ITEM
DESCRIPTION
DC Voltage
(V)
Current (mA)
Watts
Limits W
Normal Condition
<11
Fault Condition
<13
Limits according to the Catalogue for Technical Data P543/en TD/ H53 Page : 32
SUPPLY OFF
TERMINALS (CLOSED) - (J11, J12)
:
TERMINALS (OPEN)
- (J13, J14)
SUPPLY ON
TERMINALS (CLOSED) - (J13, J14)
TERMINALS (OPEN)
- (J11, J12)
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
4 of 20
SEC-COA
Site:
Project no.:
Terminals
IR
C3 C2 C1
IB
C6 C5 C4
IY
C9 C8 C7
IN
IM
Shorting Checked
*
*
Page No; 11
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
5 of 20
SEC-COA
Site:
Project no.:
VT RATIO
APPLIED
(V)
APPLIED VALUE
(V)
DISPLAYED
SECONDARY
VALUE (V)
DISPLAYED
PRIMARY VALUE
(KV)
VAB
VBC
VCA
VA
VB
VC
VN**
Limit: Voltage Measurement Accuracy = 1%. As per the manual P543/en TD/ H53 Page: 24
Measured
(MVA)
A
B
C
11. PICK UP & DROP OFF TEST FOR DIFFERENTIAL CURRENT (Id):
To avoid absence of fiber optic communication then blocking of differential protection element;
At Commission Tests menu, Set '' Test Loop back '' is '' Internal ''. Through HMI only.
TESTED BY : Thyssenkrupp Xervon
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
6 of 20
SEC-COA
Site:
Project no.:
Expected
Pick Up
Value (A)
Measured
Pick Up
Value (A)
Expected
Drop Out
Value (A)
SETTING
Is1 (A)
Injected
Current
I bias A
0.2
0.1
0.115
0.08625
0.4
0.2
0.23
0.1725
0.6
0.3
0.345
0.2587
0.2
0.1
0.115
0.08625
0.4
0.2
0.23
0.1725
0.6
0.3
0.345
0.2587
0.2
0.1
0.115
0.08625
0.4
0.2
0.23
0.1725
0.6
0.3
0.345
0.2587
R-Y
0.4
0.2
0.23
0.1725
Y-B
0.4
0.2
0.23
0.1725
B-R
0.4
0.2
0.23
0.1725
R-Y-B
0.4
__
0.23
0.1725
PHASE
R-N
Y-N
B-N
Measured
Drop Out
Value (A)
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
7 of 20
SEC-COA
Site:
Project no.:
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
Zero (Inst)
250
500
Zero (Inst)
250
500
Zero (Inst)
250
500
250
250
250
250
B
R-Y
Y-B
B-R
R-Y-B
Operating Time
(ms)
Accuracy:
Instantaneous Operation: <30 ms.
Definite Time Operation: 2 % or 20 ms whichever is greater.
According to the Catalogue for Technical Data P543/en TD/ H53 Page: 10
According to the Catalogue for Twice time current injected P54X/ENCM- Page: 174 Sec 6.3.3.2
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
8 of 20
SEC-COA
Site:
Project no.:
Current is injected into the R phase which is used as the bias current and another current is injected
into the Y phase which is used as differential current.
Inject a bias current of 1A in the R phase. The relay will trip and any LED associated with the R
phase will operate.
Slowly increase the current in the Y phase until phase Y trips . Record the phase Y current
magnitude and check that it corresponds to the following equation;
K1
30 %
IS1
0.2
I bias
A
1
2
Id calculated
R
Id Measured
Y
Errors %
Y
0.25
0.4
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
9 of 20
SEC-COA
Site:
Project no.:
UPPER SLOPE
Repeat the test and check the result with the following equation;
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
10 of 20
SEC-COA
Site:
Project no.:
Is2
I bias A
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
11 of 20
SEC-COA
Site:
Project no.:
2000/1 Amp
PT Ratio ;
380/0.115 kV
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
12 of 20
SEC-COA
Site:
Project no.:
Group 1
Phase Differential:
Enabled
PHASE
SETTING
Is1 (A)
Injected
Current
Ibais A
R-N
0.4
0.2
Expected
Pick Up
Value (A)
Measured
Pick Up
Value (A)
0.23
Expected
Drop Out
Value (A)
Measured
Drop Out
Value (A)
0.1725
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
13 of 20
SEC-COA
Site:
Project no.:
0.4
0.2
0.23
0.1725
B-N
0.4
0.2
0.23
0.1725
R-Y
0.4
0.2
0.23
0.1725
Y-B
0.4
0.2
0.23
0.1725
B-R
0.4
0.2
0.23
0.1725
R-Y-B
0.4
0.2
0.23
0.1725
R
Y
B
R-Y
Y-B
R-B
R-Y-B
Accuracy: Definite Time Operation; 2 % or 20 ms whichever is greater.
BIAS CHARACTRISTIC:
LOWER SLOPE
IS1; the Basic Diff Current Setting.
K1; the Lower Percentage Bias Setting.
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
14 of 20
SEC-COA
Site:
Project no.:
IS1
I bias A
0.4
1
2
3
Id
calculated
0.35
0.5
0.65
Id Measured
B
Errors %
B
Limits; 10 % According to ''Catalogue: Commissioning and Maintenance P54x/EN CM/G53 Pages No 30 & 31''
UPPER SLOPE
Is2; The Bias Current Threshold Setting.
K2; The High Percentage Bias Setting.
K2
IS2
150 %
I bias A
Id
calculated
1.45
2.2
2.95
Id Measured
R
Errors %
Y
: ________________
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
15 of 20
SEC-COA
Site:
Project no.:
- Channel 1 Unit
- Channel 2 Unit
Rating information
- Channel 1 Unit
- Channel 2 Unit
Case Earthing
- Channel 1 Unit
- Channel 2 Unit
- Channel 1 Unit
- Channel 2 Unit
- Channel 1 Unit
- Channel 2 Unit
LED Working
- Channel 1 Unit
- Channel 2 Unit
Result
LOOPBACK TEST:
Test Method: At P593 unit REMOVE EXTERNAL WIRING FROM TBs 3,4,7 & 8 AND JUMPER TB 3 to
7 AND TB 4 to 8
Sr. No
Description
Result
o
o
o
Normalize Tx and Rx cables b/w P543 and P593 and put P543 in
Test loopback External mode.
Reset alarm indications.
Check loopback alarm is still active and not reset.
Check communication working (Channel status, propagation delay
etc.)
-
Prop. Delay
Channel 1 Unit
Channel 2 Unit
Channel Status
Checked
Local Relay
Remote
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
16 of 20
SEC-COA
Site:
Project no.:
Injection Current ( A )
Injection Current ( A )
Local Checked
B
1
PICK UP AND DROP OUT TEST FOR DIFFERENTIAL CURRENT (Id):
Pick up value = (Is1 + K1 * Ibias) Ampere.
Ibias = 0.5 (IL + IR)
Drop out value = 0.75 * (pick up value) Ampere.
Phase
Setting Is1 (A)
Expected Value
Measured Pickup
(A)
Value (A)
R
0.4
0.46
Y
0.4
0.46
0.4
0.46
Measured
Dropout Value (A)
Limits :Pick up = Setting 10% and Drop out = (0.75 x Setting) 10%. According to Catalogue for technical data
P543/en TD/J74- Page no 2-6.
OPERATING TIME TEST FOR DIFFERENTIAL CURRENT (Id):
Phase
Injected Current (A)
Setting Delay Time
Measured Operating
(ms)
Time (ms)
R
0.8
0
Y
0.8
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
17 of 20
SEC-COA
Site:
Project no.:
0.8
Injected
I Local
(Amp)
Injected
I Rem ote
(Amp)
Ibias
Ibias
Idiff
Idiff
calculated measured calculated measured
(Amp)
(Amp)
(Amp)
(Amp)
Local
Relay
Optd
Remote
Relay
Optd
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
18 of 20
SEC-COA
Site:
Project no.:
PHASE
Injected
I Local
(Amp)
Injected
I Rem ote
(Amp)
Ibias
Ibias
Idiff
Idiff
calculated measured calculated measured
(Amp)
(Amp)
(Amp)
(Amp)
Local
Relay
Optd
Remote
Relay
Optd
R
Y
B
Limits : 10% According to catalogue for CM P54x/EN CM/ I 74- page no 10-37.
MEASURED DIFFERENTIAL CURRENT:
Injected CURRENT 1Amp From one side.
Go to Measurement 3 and record the Differential Current.
DIFFERENTIAL CURRENT
Phase
CT REVERSE
CT NORMAL
R
Y
B
INTERTRIP CHECK
Put a jumper between terminals ''H1 & H2'' intertrip output contact, the remote end CB should
tripped, and repeat this from remote end.
Inter trip Function
CB Trip Checked
C. ONLOAD CHECKS
CONFIRM CURRENT TRANSFORMER WIRING
Phase
Errors
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
19 of 20
SEC-COA
Site:
Project no.:
Local Current
Remote Current
R
Y
B
According Catalogue for Commissioning and Maintenance P54x/EN CM/G53 Page No; 40
Check Id Icap
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :
Contract No ::
Record no. :
10631156/00
CONTRACTOR:
End Client:
Sheet:
20 of 20
SEC-COA
Site:
Project no.:
WITNESSED BY : SEC-COA
NAME
NAME
NAME
:WALI MUHAMMAD
SIGNATURE
: Ghulam Murtaza
SIGNATURE :
: TAHIR MAHMOUD
SIGNATURE :