SITE INSPECTION AND TEST RECORD

Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

1 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


1. RELAY IDENTIFICATION:
Bay No.

Aux. Voltage :

125VDC

Bay Name

Serial No.

Manufacturer

: AREVA

Type

: MICOM P54331AE6M0540K

C.T Ratio

: 3000/1 Amp

VT Ratio

: 380/0.115kV

Frequency

: 50/60 Hz

Function

: 87L1

Rated Current : 1/5 Amp

IP/OP Voltage : 110/125 VDC

Soft Ware

Drawing No

: P543____6__540_C

: 10P54302

Fiber Optic Converter:

2. MECHANICAL CHECKS AND VISUAL INSPECTION:


ITEM
1
2
3
4
5

3.

DESCRIPTION

CHECKED

Inspect for physical damage / defects.


Verify connection as per approved drawings.
Check tightness of all connections.
Check Ferrules.
Check apparatus lists.

ELECTRICAL TESTS:
1

Case earthing checked

Test switch checked for correct function.

Human Machine Interface (HMI) checked

Indications Checked

Reset of indications checked.

4. OPTO I/P STATUS CHECKED:


TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

2 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Apply DC Voltage (125 V) at each terminals of each OPTO I/P.
Check at HMI; System Data Menu; Opto I/P Status; each I/P should change from (0) state (1) state.

OPTO RELAY No

TERMINAL

FUNCTION

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

D1 D2
D3 D4
D5 D6
D7 D8
D9 D10
D11 D12
D13 D14
D15 D16
F1 F2
F3 F4
F5 F6
F7 F8
F9 F10
F11 F12
F13 F14
F15 F16

SPARE
CB CLOSED
CB OPEN
SPARE
SPARE
VT FAIL
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

STATUS CHECKED

5. LED STATUS CHECKED:


Note: From the Local HMI Go to Commissioning Test, Test LEDS (Apply Test).
LED No

FUNCTION

COLOUR

1
2
3
4
5
6
7
8

DIFF TRIP A
DIFF TRIP B
DIFF TRIP C
DIFF START
DIFF INTER TRIP
TEST LOOP BACK
COMM FAIL
VT FAIL

R
R
R
Y
R
Y
Y
Y

STATUS CHECKED

6. OUTPUT CONTACTS FUNCTION CHECKED:

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

3 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Note: From the Local HMI Go to Commissioning Test, Test mode (blocked), Test Pattern mode and select
each relay to be tested and Apply Contact Test, after test; apply remove test to de-energized the relay.
OUTPUT RELAY No

TERMINALS

FUNCTION

1
2
3
4
5
6
7
8
9
10
11
12
13
14

H1 H2
H3 H4
H5 H6
H8 H9
H11 H12
H14 H15
H17 H18
G1 G2
G3 G4
G5 G6
G8 G9
G11 G12
G14 G15
G17 G18

86C1 DIFF TRIP


SPARE

7.

STATUS CHECKED

DIFF TRIP CP,FR,FMK

DIFF START FR
DIFF TRIP A SOE
DIFF TRIP B SOE
DIFF TRIP C SOE
DIFF COMM FAIL SOE

SPARE
SPARE
BATTERY FAIL
V,T FAIL
DIFF. START SOE
SPARE

RELAY BURDEN:
ITEM

DESCRIPTION

DC Voltage
(V)

Current (mA)

Watts

Limits W

Normal Condition

<11

Fault Condition

<13

Limits according to the Catalogue for Technical Data P543/en TD/ H53 Page : 32
SUPPLY OFF
TERMINALS (CLOSED) - (J11, J12)
:
TERMINALS (OPEN)

- (J13, J14)

SUPPLY ON
TERMINALS (CLOSED) - (J13, J14)

TERMINALS (OPEN)

- (J11, J12)

8. CURRENT TRANSFORMER SHORTING CONTACTS:


TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

4 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Current Input

Terminals

IR

C3 C2 C1

IB

C6 C5 C4

IY

C9 C8 C7

IN
IM

C15 C14 C13


C12 C11 C10

Shorting Checked

*
*

* Not be checked because it is not used in the scheme.


This table according to the Catalogue for Commissioning and Maintenance P54x/EN CM/G53

Page No; 11

9. TIME AND DATE CHECK:


If the time and date is not being maintained by an IRIG-B signal, so in the event of the auxiliary
supply failing, with a battery fitted in the relay, the time and date will be maintained.
To test this, remove the auxiliary supply from the relay for approximately 30 seconds, on restoring
the auxiliary supply the time and date should be correct.
Result: ____________

A. SECONDARY INJECTION TEST IN CLOSE LOOP MODE INTERNAL


10. MEASUREMENTS:
TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

5 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


- To check secondary values go to measurement 1.
- To check primary values go to measurement setup, set local values to: primary values, then Go to
Measurement 1.
CURRENT INPUTS CHECK:
CT RATIO
DISPLAYED
DISPLAYED
APPLIED VALUE
INPUT CT
APPLIED
SECONDARY
PRIMARY VALUE
(A)
(A)
VALUE (A)
(A)
IA
IB
IC
IN **
Limit: Current Measurement Accuracy = 10mA or 10% .As per the manual P543/en TD/ H53 Page: 24

VOLTAGE INPUTS CHECK:


INPUT VT

VT RATIO
APPLIED
(V)

APPLIED VALUE
(V)

DISPLAYED
SECONDARY
VALUE (V)

DISPLAYED
PRIMARY VALUE
(KV)

VAB
VBC
VCA
VA
VB
VC
VN**
Limit: Voltage Measurement Accuracy = 1%. As per the manual P543/en TD/ H53 Page: 24

ACTIVE, REACTIVE AND APPARENT POWER CHECK:


- Injected 66.4V and 1.0A with 45 lagging. Measurement prints out attached.
- To check the values go to measurement 2.
- Line angle (L) = 45 degree.
- P = V * I * COS (L) and Q = V * I * SIN (L)
Calculated
Measured
Calculated
Measured
Calculated
PHASE
(MW)
(MW)
(MVAR)
(MVAR)
(MVA)

Measured
(MVA)

A
B
C

11. PICK UP & DROP OFF TEST FOR DIFFERENTIAL CURRENT (Id):
To avoid absence of fiber optic communication then blocking of differential protection element;
At Commission Tests menu, Set '' Test Loop back '' is '' Internal ''. Through HMI only.
TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

6 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Pick Up Value = 0.5 x (Is1 + K1 x I bias )

Where; K1 = 30 % = 0.3 P.U


Drop Out Value = 0.75 x (Pick Up Value) A

Expected
Pick Up
Value (A)

Measured
Pick Up
Value (A)

Expected
Drop Out
Value (A)

SETTING
Is1 (A)

Injected
Current
I bias A

0.2

0.1

0.115

0.08625

0.4

0.2

0.23

0.1725

0.6

0.3

0.345

0.2587

0.2

0.1

0.115

0.08625

0.4

0.2

0.23

0.1725

0.6

0.3

0.345

0.2587

0.2

0.1

0.115

0.08625

0.4

0.2

0.23

0.1725

0.6

0.3

0.345

0.2587

R-Y

0.4

0.2

0.23

0.1725

Y-B

0.4

0.2

0.23

0.1725

B-R

0.4

0.2

0.23

0.1725

R-Y-B

0.4

__

0.23

0.1725

PHASE

R-N

Y-N

B-N

Measured
Drop Out
Value (A)

Limits: Pick up & Drop Out 10%


According to the Catalogue for Technical Data P543/en TD/ H53 Page: 10

12. OPERATING TIME TEST FOR DIFFERENTIAL CURRENT (Id):


Set; DT Mode & Is1 = 0.4 In & K1 = 30 % & Is2 = 4 In & K2 = 150 %

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

7 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Phase

Inject current (A)

Delay Time (ms)

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

Zero (Inst)
250
500
Zero (Inst)
250
500
Zero (Inst)
250
500
250
250
250
250

B
R-Y
Y-B
B-R
R-Y-B

Operating Time
(ms)

Accuracy:
Instantaneous Operation: <30 ms.
Definite Time Operation: 2 % or 20 ms whichever is greater.
According to the Catalogue for Technical Data P543/en TD/ H53 Page: 10
According to the Catalogue for Twice time current injected P54X/ENCM- Page: 174 Sec 6.3.3.2

13. BIAS CHARACTERISTIC TESTING:


For local testing of the relay put in the Loop back mode, At Commission Tests menu, Set '' Test
Loop back '' is '' Internal ''. Through HMI only.
TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

8 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


LOWER SLOPE
Connect the test circuit as shown figure.

Current is injected into the R phase which is used as the bias current and another current is injected
into the Y phase which is used as differential current.
Inject a bias current of 1A in the R phase. The relay will trip and any LED associated with the R
phase will operate.
Slowly increase the current in the Y phase until phase Y trips . Record the phase Y current
magnitude and check that it corresponds to the following equation;

Id Calculated = 0.5 * (Is1 +I bias K1)

Where; IS1; The Basic Diff Current Setting.


K1; The Lower Percentage Bias Setting.
Set; IS2 = 4 In
To check more than one point at the same slope, Change the bias current value and the equation
above can be used, and also for other differential settings '' Different slopes, I s1 ''.
Apply the above procedure for each phase.

K1
30 %

IS1
0.2

I bias
A
1
2

Id calculated
R

Id Measured
Y

Errors %
Y

0.25
0.4

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

9 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


3
0.55
1
0.35
0.4
2
0.5
3
0.65
1
0.45
0.6
2
0.6
3
0.75
1
0.3
0.2
2
0.5
3
0.7
1
0.4
40 %
0.4
2
0.6
3
0.8
1
0.5
0.6
2
0.7
3
0.9
1
0.35
0.2
2
0.6
3
0.85
1
0.45
50 %
0.4
2
0.7
3
0.95
1
0.55
0.6
2
0.8
3
1.05
Limits; 10 % According to the Catalogue for Commissioning and Maintenance P54x/EN CM/G53
Pages No; 30 & 31

UPPER SLOPE
Repeat the test and check the result with the following equation;

Id Calculated = 0.5 X [(6 X K2) {(K2 K1) X IS2} + IS1]

Is2; The Bias Current Threshold Setting.


K2; The High Percentage Bias Setting.
TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

10 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


IS1 & K1 are Fixed; IS1 = 0.2 A , K1 = 30 %
Id Measured
Errors %
Id
calculated
R
Y
B
R
Y
B
5
1.15
2
6
1.4
7
1.65
5
1.05
50%
3
6
1.3
7
1.55
5
0.95
4
6
1.2
7
1.45
5
1.9
2
6
2.4
7
2.9
5
1.55
100 %
3
6
2.05
7
2.55
5
1.2
4
6
1.7
7
2.2
5
2.65
2
6
3.4
7
4.15
5
2.05
150%
3
6
2.8
7
3.55
5
1.45
4
6
2.2
7
2.95
Limits; 10 % According to the Catalogue for Commissioning and Maintenance P54x/EN CM/G53
Pages No ; 30 & 31
K2

Is2

I bias A

14. VTS FUNCTION TEST:


LOSS OF ONE OR TWO PHASE TEST:
FIXED SETTING Negative sequence threshold used by the elements are V2= 10V.
(As per Catalogue P54x/EN OP/B74 Page No:05)
TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

11 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Note: Inject three phase (66.4) balance voltage during test of particular phase to reduce that phase
voltage until the fuse failure operates.
Phase Under
Measure Voltage
Measure Neg Seq
Set Time (Sec)
Measured Time (Sec)
Test
(Vo) Volts
Voltage (V2)
A
B
C
LOSS OF THREE PHASE VOLTAGE TEST:
FIXED SETTING Phase voltage level detector is fixed and will drop off at 10V and pick up at 30V.
(As per Catalogue P54x/EN OP/B74 Page No: 05)
Note: Inject three phase (66.4) balance voltage during testing all phase voltage decrease until the fuse
failures operate.
Measure Voltage Volts

Drop out Voltage Volts

Set Time (Sec)

Measured Time (Sec)

15. FINAL SETTING:


CT Ratio

2000/1 Amp

PT Ratio ;

380/0.115 kV

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

12 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


General Configuration:
Setting Group ;

Group 1

Phase Differential:

Enabled

Differential Prot Comm IM64


Scheme Set:
Address:
Baud Rate:
Clock Source:
Communication Delay Tolerance:
Communication Fail Timer:
Char Mode Time:
Differential Characteristics Configuration
Phase Is1:
Phase Is2:
Phase K1:
Phase K2:
Phase Characteristic:
Phase Time Delay:
Phase TMS:
Phase Time Dial:
P I T Time:
Compensation:
Susceptance:
Inrush Restraint:
Vector compensation:
Phase CT Correction:
E.F CT Correction:
Pick Up & Drop Off Test for Differential Current (id):

PHASE

SETTING
Is1 (A)

Injected
Current
Ibais A

R-N

0.4

0.2

Expected
Pick Up
Value (A)

Measured
Pick Up
Value (A)

0.23

Expected
Drop Out
Value (A)

Measured
Drop Out
Value (A)

0.1725

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

13 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Y-N

0.4

0.2

0.23

0.1725

B-N

0.4

0.2

0.23

0.1725

R-Y

0.4

0.2

0.23

0.1725

Y-B

0.4

0.2

0.23

0.1725

B-R

0.4

0.2

0.23

0.1725

R-Y-B

0.4

0.2

0.23

0.1725

Limits: Pick up & Drop Out 10%


According to the Catalogue for Technical Data P543/en TD/ H53 Page: 10
Operating Time Test for Differential Current (id):
Injection Current = Is1 = 0.4 A
PHASE

Delay Time (ms)

Operating Time (ms)

R
Y
B
R-Y
Y-B
R-B
R-Y-B
Accuracy: Definite Time Operation; 2 % or 20 ms whichever is greater.

BIAS CHARACTRISTIC:
LOWER SLOPE
IS1; the Basic Diff Current Setting.
K1; the Lower Percentage Bias Setting.

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

14 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


K1
30 %

IS1

I bias A

0.4

1
2
3

Id
calculated
0.35
0.5
0.65

Id Measured
B

Errors %
B

Limits; 10 % According to ''Catalogue: Commissioning and Maintenance P54x/EN CM/G53 Pages No 30 & 31''

UPPER SLOPE
Is2; The Bias Current Threshold Setting.
K2; The High Percentage Bias Setting.
K2

IS2

150 %

I bias A

Id
calculated

1.45

2.2

2.95

Final Setting Issue No.

Id Measured
R

Errors %
Y

: ________________

Final Setting Issue Date : ________________

B. END TO END TEST (Final Setting)


P591 INTERFACE UNIT CHECK:

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

15 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Sr. No
1
2
3
4
5
6

P591 Interface Units Checks


Visual Inspection

- Channel 1 Unit
- Channel 2 Unit

Rating information

- Channel 1 Unit
- Channel 2 Unit

Case Earthing

- Channel 1 Unit
- Channel 2 Unit

Wiring against Diagram

- Channel 1 Unit
- Channel 2 Unit

Measured Aux. Supply

- Channel 1 Unit
- Channel 2 Unit

LED Working

- Channel 1 Unit
- Channel 2 Unit

Result

LOOPBACK TEST:
Test Method: At P593 unit REMOVE EXTERNAL WIRING FROM TBs 3,4,7 & 8 AND JUMPER TB 3 to
7 AND TB 4 to 8
Sr. No

Description

Result

Signal strength received by P593 -Channel 1 Unit (-16.8dBm to -25.4dBm)


.
- Channel 2 Unit (-16.8dBm to -25.4dBm)

Signal strength transmitted by P593 -Channel 1 Unit (-16.8dBm to -28.8dBm)


.
- Channel 2 Unit (-16.8dBm to -28.8dBm)
o

o
o
o

Normalize Tx and Rx cables b/w P543 and P593 and put P543 in
Test loopback External mode.
Reset alarm indications.
Check loopback alarm is still active and not reset.
Check communication working (Channel status, propagation delay
etc.)
-

Prop. Delay
Channel 1 Unit
Channel 2 Unit

Channel Status

COMMINUCATION FAILURE CHECK.


Function

Checked
Local Relay
Remote

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

16 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


Relay
Disconnect a fiber optic channel '' Alarm should appeared''
Reconnect a fiber optic channel '' Alarm should disappeared''
Communication equipment
SECONDARY INJECTION CHECK.
SINGLE PHASE INJECTION AT LOCAL RELAY
Phase

Injection Current ( A )

Remote End Checked

SINGLE PHASE INJECTION AT REMOTE END RELAY


Phase

Injection Current ( A )

Local Checked

B
1
PICK UP AND DROP OUT TEST FOR DIFFERENTIAL CURRENT (Id):
Pick up value = (Is1 + K1 * Ibias) Ampere.
Ibias = 0.5 (IL + IR)
Drop out value = 0.75 * (pick up value) Ampere.
Phase
Setting Is1 (A)
Expected Value
Measured Pickup
(A)
Value (A)
R
0.4
0.46
Y

0.4

0.46

0.4

0.46

Measured
Dropout Value (A)

Limits :Pick up = Setting 10% and Drop out = (0.75 x Setting) 10%. According to Catalogue for technical data
P543/en TD/J74- Page no 2-6.
OPERATING TIME TEST FOR DIFFERENTIAL CURRENT (Id):
Phase
Injected Current (A)
Setting Delay Time
Measured Operating
(ms)
Time (ms)
R
0.8
0
Y

0.8

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

17 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


B

0.8

Limits : Definite time operation : 2% or 20ms which ever is greater.


According to catalogue for technical data P543 /en TD /J74 page no 2-8.
LOWER SLOP CHECK:
SETTING, IS1 = 0.4 Amp and K1 = 30%
Where Is1 = the basic differential setting.
K1 = the lower percentage bias setting.
Id calculated = (Is1 + Ibias K1) Ampere.
Ibias
= 0.5 (IL + IR)
Note: Inject the both ends bias current same, adjust the differential current zero by current angle then
increase the local current until the relay operates. Record the differential and Bias current.
PHASE

Injected
I Local
(Amp)

Injected
I Rem ote
(Amp)

Ibias
Ibias
Idiff
Idiff
calculated measured calculated measured
(Amp)
(Amp)
(Amp)
(Amp)

Local
Relay
Optd

Remote
Relay
Optd

Limits: 10% According to catalogue for CM P54x/EN CM/I 74 - page no 10-36.

UPPER SLOP CHECK:


SETTING, IS1 = 0.4 Amp, IS2 = 4.0 Amp, K1 = 30% and K2 = 150%.
Id calculated = K2* Ibias (K2 - K1)IS2 + IS1 Ampere.
Ibias
= 0.5 (IL + IR)
Note: Inject the both ends bias current same, adjust the differential current zero by current angle then
increase the local current until the relay operates. Record the differential and Bias current.
TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

18 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV

PHASE

Injected
I Local
(Amp)

Injected
I Rem ote
(Amp)

Ibias
Ibias
Idiff
Idiff
calculated measured calculated measured
(Amp)
(Amp)
(Amp)
(Amp)

Local
Relay
Optd

Remote
Relay
Optd

R
Y
B

Limits : 10% According to catalogue for CM P54x/EN CM/ I 74- page no 10-37.
MEASURED DIFFERENTIAL CURRENT:
Injected CURRENT 1Amp From one side.
Go to Measurement 3 and record the Differential Current.
DIFFERENTIAL CURRENT
Phase
CT REVERSE

CT NORMAL

R
Y
B
INTERTRIP CHECK
Put a jumper between terminals ''H1 & H2'' intertrip output contact, the remote end CB should
tripped, and repeat this from remote end.
Inter trip Function

CB Trip Checked

From Local Relay


From Remote Relay

C. ONLOAD CHECKS
CONFIRM CURRENT TRANSFORMER WIRING
Phase

Secondary Current Values


Using a Multimeter

Secondary Current Values With The


Relay's Measured

Errors

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

19 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


R
B
Y
N
Limits; 1 % According to the Catalogue for Commissioning and Maintenance P54x/EN CM/G53
Page No ; 40
MEASURE CAPACITIVE CHARGING CURRENT
With the feeder energized from one end only, Compare local and remote measured currents in the
MEASUREMENT 3 menus at HMI to confirm that the feeder capacitive charging current is similar to
that expected on all three phases.
Check that the setting of ( Is1 ) is higher than 2.5 times the capacitive charging current.
Phase

Local Current

Remote Current

Check Is1 > 2.5 Icap

R
Y
B
According Catalogue for Commissioning and Maintenance P54x/EN CM/G53 Page No; 40

CHECK DIFFERENTIAL CURRENT


With the feeder supplying load current check that the relay measurements in the MEASUREMENTS 3
menu at HMI are as expected and that the differential current is similar to the value of capacitive
charging current previously measured for all three phases.
Phase

Check Id Icap

Current Differential Measured

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :

SITE INSPECTION AND TEST RECORD


Description:

Contract No ::

LINE DIFFERENTIAL MICOM P543

Record no. :

10631156/00

CONTRACTOR:

End Client:

SIEMENS CO. LTD

Sheet:

20 of 20

SEC-COA

Site:

Panel / Designation / Location no.:

Project no.:

S/S 9019 380 kV


R
Y
B
18. REMARKS:
ATTACHMENTS;
1- Final setting file is downloading from the relay and printed.
2- PSL '' Programmable Logic Scheme'' files which include a configuration of I/P & O/P
contacts and Leds, is downloading from the relay and printed.
3- An example of one disturbance viewed by WINWAVE program is retrieved and printed.

TESTED BY : Thyssenkrupp Xervon

COUNTER SIGNED BY : SIEMENS

WITNESSED BY : SEC-COA

NAME

NAME

NAME

:WALI MUHAMMAD

SIGNATURE

: Ghulam Murtaza

SIGNATURE :

: TAHIR MAHMOUD

SIGNATURE :