Sunteți pe pagina 1din 52

DC Inverter Split Air-Condition Unit

SERVICE MANUAL


- 1 -
Tabl e of Contents
1. The model and the air conditioning unit parameters...........................................................1
2. Units operating working conditions and temperature range ............................................8
3. Units characteristic..................................................................................................................11
4. Indoor and outdoor units size ...............................................................................................26
5. Indoor and outdoor unit explosion diagram and spare parts list .....................................30
6. The analysis of indoor malfunction code ............................................................................35
7. The analysis of the complete units malfunction code.........................................................50





























- 2 -
1The model and the air conditioning unit parameters
1.1 the model.

















- 3 -
1.2. The air conditioners parameter.












- 4 -


- 5 -



















- 6 -
















- 7 -




- 8 -





- 9 -















- 10 -
2 RATI NG CONDI TI ONS and Operati ng Li mi ts
2. 1 RATING CONDITIONS
Standard conditions in accordance with ISO 5151, and EN 14511.
Cooling:
Indoor: 27 DB 19 WB
Outdoor:35 DB 24 WB
Heating:
Indoor: 20 DB 15 WB
Outdoor: 7 DB 6 WB
2. 2 Oper at i ng Li mi ts
Outdoor
Upper limit (DB) 46 Cooling
Lower limit (DB) 5
Upper limit (DB) 24 Heating
Lower limit (DB) -15
Voltage 1PH 220-240V














- 11 -
3Uni ts characteri sti c
R410a
Low noise level
Wide operating range with outdoor air temperatures, cooling:5-46,heating:-15-24
High efficiency and energy saving
Air filters easy to remove and clean
Twin rotary compressor
Auto-restart after a power supply blackout
Single-phase power supply thanks to DC inverter technology low consumption
Dynamic refrigerant control by DC inverter compressor and circuit, electronic valve and fuzzy logic
managed by a powerful micro program
EEV for each indoor unit











- 12 -















































- 13 -
The compressors energy consumption graph .
COP (W/W)/2ND











The compressors condensing pressure graph .
































- 14 -
Indoor Units Data
Indoor Units Capacity For 2.0KW
Capacity Model
2.0KW CMV-V20G3A-M75/81/84/85/87/88/95/96
Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[
0
C] DATA 22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
-10 - 20
(protection range)
PI 25 - 50 % of nominal
TC 1.94 2.06 2.18 2.32 2.44
SC 1.72 1.75 1.79 1.82 1.85
25
PI 0.49 0.50 0.51 0.51 0.53
TC 1.84 1.96 2.10 2.22 2.34
SC 1.67 1.70 1.75 1.79 1.82
30
PI 0.55 0.55 0.56 0.57 0.58
TC 1.74 1.88 2.00 2.12 2.26
SC 1.63 1.67 1.70 1.73 1.77
35
PI 0.60 0.61 0.62 0.63 0.64
TC 1.66 1.78 1.90 2.04 2.16
SC 1.58 1.62 1.65 1.70 1.73
40
PI 0.66 0.67 0.68 0.69 0.69
TC 1.54 1.66 1.80 1.92 2.04
SC 1.53 1.56 1.60 1.63 1.68 46
PI 0.73 0.74 0.74 0.76 0.76
Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[
0
C]
DATA 15 20 25
-15/-16
TC
1.54 1.42 1.32
PI 0.40 0.44 0.48
-10/-12 TC 1.70 1.58 1.49
PI 0.48 0.52 0.57
-7/-8 TC 1.82 1.73 1.61
PI 0.55 0.59 0.63
-1/-2 TC 1.90 1.80 1.68
PI 0.58 0.62 0.66
2/1
TC
1.94 1.82 1.73

- 15 -
PI 0.60 0.64 0.68
7/6
TC
2.50 2.40 2.30
PI 0.63 0.67 0.71
10/9
TC
2.64 2.54 2.42
PI 0.67 0.71 0.75
15/12
TC
2.78 2.69 2.57
PI 0.70 0.74 0.78
1524 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25 30 35 40 45
Outdoor Temperature (deg C)
C
a
p
a
c
i
t
y

R
a
t
i
o
32/23
29/27
27/19
24/17
22/15

Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (deg C)
C
a
p
a
c
i
t
y

R
a
t
i
o
15
20
25



- 16 -
Indoor Units Capacity For 2.5KW
Capacity Model
2.5KW CMV-V25G3A-M75/81/84/85/87/88/95/96
Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[
0
C] DATA 22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
-10 - 20 SC 80 - 105 % of nominal
(protection range) PI 25 - 50 % of nominal
TC 2.42 2.57 2.73 2.89 3.05
25 SC 1.72 1.75 1.79 1.82 1.86
PI 0.58 0.59 0.60 0.61 0.62
TC 2.30 2.46 2.62 2.77 2.93
30 SC 1.67 1.71 1.74 1.78 1.81
PI 0.65 0.66 0.67 0.68 0.69
TC 2.18 2.34 2.50 2.66 2.82
35 SC 1.63 1.66 1.70 1.74 1.77
PI 0.71 0.72 0.74 0.75 0.76
TC 2.07 2.23 2.38 2.54 2.70
40 SC 1.59 1.62 1.66 1.69 1.73
PI 0.78 0.79 0.80 0.81 0.82
TC 1.93 2.09 2.24 2.40 2.56
46 SC 1.53 1.57 1.60 1.64 1.67
PI 0.86 0.87 0.88 0.89 0.91

Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[
0
C]
DATA 15 20 25
-15/-16
TC
1.92 1.77 1.65
PI 0.49 0.54 0.59
-10/-12 TC 2.13 1.98 1.86
PI 0.59 0.64 0.70
-7/-8 TC 2.28 2.16 2.01
PI 0.67 0.72 0.77
-1/-2 TC 2.37 2.25 2.10
PI 0.71 0.75 0.80
2/1
TC
2.43 2.28 2.16
PI 0.73 0.78 0.83

- 17 -
7/6
TC
3.12 3.00 2.88
PI 0.77 0.82 0.87
10/9
TC
3.30 3.18 3.03
PI 0.82 0.87 0.92
15/12
TC
3.48 3.36 3.21
PI 0.86 0.90 0.96
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
LEGEND
TC Total Cooling Capacity, kW
SC Sensible Capacity, Kw
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25 30 35 40 45
Outdoor Temperature (deg C)
C
a
p
a
c
i
t
y

R
a
t
i
o
32/23
29/27
27/19
24/17
22/15








- 18 -
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (deg C)
C
a
p
a
c
i
t
y

R
a
t
i
o
15
20
25

Indoor Units Capacity For 3.5KW
Indoor Units Capacity For 3.5KW
Capacity Model
CMV-V35G3A-M75/81/84/85/87/88/95/96
3.5KW
CMV-V35G3A-P84/94/98
Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[
0
C] DATA 22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
-10 - 20 SC 80 - 105 % of nominal
(protection range) PI 25 - 50 % of nominal
TC 3.40 3.61 3.82 4.06 4.27
25 SC 3.03 3.09 3.15 3.21 3.27
PI 0.86 0.87 0.89 0.90 0.93
TC 3.22 3.43 3.68 3.89 4.10
30 SC 2.94 3.00 3.09 3.15 3.21
PI 0.96 0.97 0.99 1.00 1.02
TC 3.05 3.29 3.50 3.71 3.96
35 SC 2.88 2.94 3.00 3.06 3.12
PI 1.06 1.08 1.09 1.11 1.12
TC 2.91 3.12 3.33 3.57 3.78
40 SC 2.79 2.85 2.91 3.00 3.06
PI 1.16 1.18 1.19 1.21 1.22
TC 2.70 2.91 3.15 3.36 3.57
46 SC 2.70 2.76 2.82 2.88 2.97
PI 1.28 1.30 1.31 1.33 1.34

- 19 -
Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[
0
C]
DATA 15 20 25
-15/-16
TC
2.56 2.36 2.20
PI 0.67 0.73 0.80
-10/-12 TC 2.84 2.64 2.48
PI 0.80 0.87 0.94
-7/-8 TC 3.04 2.88 2.68
PI 0.91 0.98 1.04
-1/-2 TC 3.16 3.00 2.80
PI 0.95 1.02 1.09
2/1
TC
3.24 3.04 2.88
PI 0.99 1.05 1.12
7/6
TC
4.16 4.00 3.84
PI 1.04 1.11 1.18
10/9
TC
4.40 4.24 4.04
PI 1.11 1.18 1.24
15/12
TC
4.64 4.48 4.28
PI 1.17 1.23 1.30
1524 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25 30 35 40 45
Outdoor Temperature (deg C)
C
a
p
a
c
i
t
y

R
a
t
i
o
32/23
29/27
27/19
24/17
22/15


- 20 -

Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (deg C)
C
a
p
a
c
i
t
y

R
a
t
i
o
15
20
25

Indoor Units Capacity For 5.0KW
Capacity Model
5.0KW CMV-V50G3A-P75/81/84/85/87/88/95/96

Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[
0
C] DATA 22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
-10 - 20 SC 80 - 105 % of nominal
(protection range) PI 25 - 50 % of nominal
TC 4.85 5.15 5.45 5.80 6.10
25 SC 4.55 4.64 4.73 4.82 4.91
PI 1.23 1.25 1.28 1.29 1.33
TC 4.60 4.90 5.25 5.55 5.85
30 SC 4.41 4.50 4.64 4.73 4.82
PI 1.37 1.39 1.42 1.44 1.47
TC 4.35 4.70 5.00 5.30 5.65
35 SC 4.32 4.41 4.50 4.59 4.68
PI 1.51 1.54 1.56 1.59 1.61
TC 4.15 4.45 4.75 5.10 5.40
40 SC 4.19 4.28 4.37 4.50 4.59
PI 1.65 1.68 1.70 1.73 1.75
TC 3.85 4.15 4.50 4.80 5.10
46 SC 4.05 4.14 4.23 4.32 4.46
PI 1.83 1.86 1.87 1.90 1.92

- 21 -

Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[
0
C]
DATA 15 20 25
-15/-16
TC
3.71 3.42 3.19
PI 0.97 1.06 1.16
-10/-12 TC 4.12 3.83 3.60
PI 1.16 1.26 1.37
-7/-8 TC 4.41 4.18 3.89
PI 1.32 1.42 1.51
-1/-2 TC 4.58 4.35 4.06
PI 1.38 1.48 1.58
2/1
TC
4.70 4.41 4.18
PI 1.43 1.53 1.63
7/6
TC
6.03 5.80 5.57
PI 1.51 1.61 1.71
10/9
TC
6.38 6.15 5.86
PI 1.61 1.71 1.80
15/12
TC
6.73 6.50 6.21
PI 1.69 1.79 1.88
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal











- 22 -
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25 30 35 40 45
Outdoor Temperature (deg C)
C
a
p
a
c
i
t
y

R
a
t
i
o
32/23
29/27
27/19
24/17
22/15

Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (deg C)
C
a
p
a
c
i
t
y

R
a
t
i
o
15
20
25







- 23 -
Capacity Correction Factor Due to Tubing Length (One Way)
Cooling

Heating









- 24 -
Pressure Curve
Model
CMV-V40H13AD CMV-50V3A-E2 CMV-V71T3AT CMV-V80T3AQ

Cooling--------------Test Model

Heating-----------Test Model




- 25 -
ELECTRI CAL DATA

Model CMV-V40H13AD
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 8 A
Inrush Current 15A
Starting Current 1A
Circuit breaker 20A
Power supply wiring - No. x cross section 31.5 mm
2
6680mm
Interconnecting cable - No. x cross section 41.0 mm
2
6300mm

Model CMV-50V3A-E2
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 11 A
Inrush Current 35A
Starting Current 1A
Circuit breaker 20A
Power supply wiring - No. x cross section 32.5 mm
2
6480mm
Interconnecting cable - No. x cross section 41.0 mm
2
6300mm

Model CMV-V52E23AT
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 11A
Inrush Current 35A
Starting Current 1A
Circuit breaker 20A
Power supply wiring - No. x cross section 32.5 mm
2
6480mm
Interconnecting cable - No. x cross section 41.0 mm
2
6300mm

Model CMV- V71T3AT
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 16A
Inrush Current 35A
Starting Current 2A
Circuit breaker 20A
Power supply wiring - No. x cross section 32.5 mm
2
6480mm
Interconnecting cable - No. x cross section 41.0 mm
2
6200mm


- 26 -
Model CMV-V80T3AQ
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 16A
Inrush Current 35A
Starting Current 2A
Circuit breaker 20A
Power supply wiring - No. x cross section 32.5 mm
2
6480mm
Interconnecting cable - No. x cross section 41.0 mm
2
16100mm

Note:
Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit
controller).
Starting current is the current when starting the compressor











- 27 -
4. OUTLI NE DI MENSI ON OF OUTDOOR AND I NDOOR
4.1 Outline dimension of outdoor Units
CMV-V40H13AD

CMV-50V3A-E2/ CMV-V52E23AT


- 28 -
CMV- V71T3AT/ CMV-V80T3AQ

4.2 the outdoor unit mounting dimensions







- 29 -
the bodys dimension mounting dimensions Dimensions
Code

outdoor
units type
A B C D E
CMV-V40H13AD 845 304 542 510 278
CMV-50V3A-E2 900 352 590 505 310
CMV-V52E23AT 900 352 590 505 310
CMV-V71T3AT/
CMV-V80T3AQ
900 388 837 600 358

4.3. The indoor unit mounting dimensions






unitmm

- 30 -
the bodys dimension mounting dimensions Dimensions
Code
indoor
units type
A B C D E F
CMV-V20G3A/MXX 800 280 195 490 / /
CMV-V25G3A/MXX 800 280 195 490 / /
CMV-V35G3A/MXX 800 280 195 490 / /
CMV-V35G3A/PXX 900 296 220 583 257.5 257.5
CMV-V50G3A/PXX 900 296 220 583 257.5 257.5


31
5The outdoor uni t str uct ur e expl oded vi ew .
5. 1outdoor unit :CMV-V40H13AD


NO. description name number
1 Front Grill 1
2 Front Plate 1
3 Axial flow fan 1
4 Motor 1
5 Motor support 1
6 Condenser 1
7 Top panel 1
8 Electric box 1
9 Rear Grill 1
10 Right panel 1
11 handle 1
12 Valve installation plate 1
13 A DN4 DN4 valve 1
14 A DN8 DN8 valve 1
15 B DN4 DN4 valve 1
16 B DN8 DN8 valve 1
17 Capillary Assy 1
18 Electronic expansion valve 2
19 Four-way valve assembly 1
20 Steam liquid segregator 1
21 Compressor 1
22 Partition board 1
23 Base 1


32
5. 2outdoor uni t : CMV-50V3A-E2/ CMV-V52E23AT

















33
NO. description name number
1 front grill 1
2 front panel 1
3 fan 1
4 motor 1
5 motor bracket assemble 1
6 left grill 1
7 left pole 1
8 top cover 1
9 rear grill 1
10 condenser 1
11 4-way valve 1
12 muffle 1
13 filter 1
14 controllor 1
15 control box cover 1
16 electrical control box 1
17 A DN8 DN8 valve for A unit 1
18 A DN4 DN4 valve for A unit 1
19 B DN8 DN8 valve for B unit 1
20 B DN4 DN4 valve for B unit 1
21 valve installation plate 1
22 handle 1
23 right panel 1
24 expand valve 2
25 compressor 1
26 compressor pad 1
27 partition board 1
28 base assemble 1

34
5.3outdoor unit : CMV-V71T3AT/ CMV-V80T3AQ



















35

NO. description name number
1 top panel 1
2 electric box 1
3 rear Grill 1
4 partition board 1
5 four-way valve 1
6 electronic expansion valve 1
7 desiccation filter 1
8 right panel 1
9 large handle 1
10 valve installation plate 1
11 oil separator 1
12 high-pressure tank 1
13 compressor 1
14 base 1
15 condenser 1
16 motor support 1
17 DC motor 1
18 axial flow fan 1
19 front Grill 1
20 front Plate 1
21 left protect net 1
22 left panel 1
23 vapor-liquid separator 1
24 back panel 2
25 DN10 DN10 cut-off valve 1
26 DN8 DN8 cut-off valve 1
27 electronic control box support plate 1
28 small hand-pumped 1
29 front maintenance board 1


36
6The analysis of indoor malfunction codeinternal wiring get loose, which
will cause malfunction.


indoor detailed malfunction
1.when indoor unit live wire is disconnectedits lamp panel cant display.




Live wire is off













2.when the transformers secondary and primary disconnect or indoor fuse is offthe indoor unit lamp
panel cant display.


Transformer secondary is off


















Transformer primary is off

The relevant transfomer primary
socket






37




Indoor unit fuse is off.


The indoor unit fuse












The condition that the lamp panel
cant display


















3.1when the indoor null line is offthe system displays F1 code
2when indoor communication wire is offthe system also displays F1 code



The inserted slice to null line


The indoor unit null line is off





38

2the indoor communication wire is
off.



Communication wire socket.

















the indoor lamp panel displays F1 code.












4. when indoor fan mainline or feedback wire is offthe indoor lamp panel displays F4 code. After directly
insert it wellTo restart the unit to recover normal .





Indoor fan mainline is off

The relevant socket with indoor fan mainline













39








indoor fan feedback wire is off



the relevant socket with indoor feedback
wire












The lamp panel displays F4 code.













5.when indoor sensor has the problem, the lamp will display F
2


F
3
code. When indoor coil outlet , inlet
and middle temperature sensor appear malfunction, the lamp panel displays F3 code; when indoor
temperature sensor appears fault, the lamp panel shows F2 fault code.



Indoor temperature sensor plug






the relevant socket of indoor temperature
sensor plug





40
















The lamp panel alternately displays F2,F3
fault code.
























6.when outdoor temperature sensor is off or loose contactthe indoor lamp panel displays F6 fault
code.



the relevant socket of outdoor temp.
sensor.




The outdoor temperature sensor is
off or loose contact.






41




The indoor lamp panel displays F6
fault code.















7.when the system appears mode conflictthe indoor lamp panel shows d1 code.



the indoor lamp panel shows d1 code.















8.when the system is in the defrosting conditionThe lamp panel displays dF code.




The lamp panel displays dF code.














42
The outdoor electrical control fault code of the America 12K model .

1.the outdoor module temperature sensor is off or loose contactthe lamp panel shows F6 code.


the outdoor module temperature sensor
is off or loose contact .

the relevant socket with the outdoor
module temperature sensor plug .
















The lamp panel shows F6 code .
















2.The outdoor unit DC busbar voltage is abnormalthe lamp panel shows F7code.





The PN power wire are off .











43




The lamp panel shows F7code.













3.the outdoor module drive wire is off the lamp panel shows FC code .


The outdoor module drive wire is off .

The matching socket with the outdoor
module drive wire


















The matching socket with the outdoor
module drive wire .




The outdoor module drive wire is
off .









44








The lamp panel shows FC code .













4the wave filtering board and mainboard power wire is off or loose contactthe lamp panel shoes F1 code .

the wave filtering board and mainboard power
wire is off or loose contact



The matching socket with the wave
filtering board and mainboard power wire














the lamp panel shoes F1 code .














45

5. the evaporator middle temperature and condenser middle temperature sensor is off the lamp panel
displays P8 code .










the evaporator middle temperature and
condenser middle temperature sensor is off





























the lamp panel displays P8 code














46

The 67
th
style indoor lamp panel

















The timing lamp The turbo lamp The running lamp

The indoor unit faulty display:
Faulty contents Trouble display
Communication fault
The running lamp lightens all the timethe turbo lamp
lightens 2 times and then extinguish 2 seconds
Indoor fan fault
The running lamp lightens all the timethe turbo lamp
lightens 5 timesand then extinguish 2 seconds
Indoor temp. sensor fault
The running lamp lightens all the timethe turbo lamp
lightens 3 times and then extinguish 2 seconds
Indoor coil outlet temp. sensor fault
The running lamp lightens all the timethe turbo lamp
lightens 4 timesand then extinguish 2 seconds
Indoor coil inlet temp. sensor fault
The running lamp lightens all the timethe turbo lamp
lightens 4 times and then extinguish 2 seconds
Indoor coil middle temp. sensor fault
The running lamp lightens all the timethe turbo lamp
lightens 4 times and then extinguish 2 seconds
Mode conflict
The running lamp lightens 1 time and then extinguish
1 second
Defrosting or anti cold air
The timing lamp lightens 1 time and then extinguish
1 second
The outdoor unit faulty display:
Faulty contents Trouble display
the outdoor unit transducer module
protection faulty
The timing lamp lightens all the timethe turbo lamp
lightens 2 times and then extinguish 2 seconds
over current of outdoor unit
The timing lamp lightens all the timethe turbo lamp
lightens 3 times and then extinguish 2 seconds
discharge temp. of compressor too high,
outside ambient temp. too high, switch
temp. of compressor crust cut off, temp.
of module too high
The timing lamp lightens all the timethe turbo lamp
lightens 4 times and then extinguish 2 seconds
The outdoor unit DC busbar voltage is
abnormal
The timing lamp lightens all the timethe turbo lamp
lightens 7 times and then extinguish 2 seconds
lack refrigerant or reverse valve fault
The timing lamp lightens all the timethe turbo lamp
lightens 8 times and then extinguish 2 seconds
outdoor sensor fault
The running lamp lightens all the timethe turbo lamp
lightens 7 times and then extinguish 2 seconds
outdoor unit drive fault, start compressor
failure
The running lamp lightens all the timethe turbo lamp
lightens 6 times and then extinguish 2 seconds



47
The 85
th
style indoor lamp panel















The timing lamp The sleeping lamp The running lamp




Faulty contents Trouble display
Communication fault
The timing lamp lightens all the timethe sleeping lamp
lightens 2 times and then extinguish 2 seconds
Indoor fan fault
The timing lamp lightens all the timethe sleeping lamp
lightens 5 times and then extinguish 2 seconds
Indoor temp. sensor fault
The timing lamp lightens all the timethe sleeping lamp
lightens 3 times and then extinguish 2 seconds
Indoor coil outlet temp. sensor fault
The timing lamp lightens all the timethe sleeping lamp
lightens 4 times and then extinguish 2 seconds
Indoor coil inlet temp. sensor fault
The timing lamp lightens all the timethe sleeping lamp
lightens 4 times and then extinguish 2 seconds
Indoor coil middle temp. sensor fault
The timing lamp lightens all the timethe sleeping lamp
lightens 4 times and then extinguish 2 seconds
Mode conflict
The timing lamp lightens 1 time and then extinguish
1 second
Defrosting or anti cold air
The running lamp lightens 1 time and then extinguish
1 second



Faulty contents Trouble display
the outdoor unit transducer module
protection faulty
The running lamp lightens all the timethe sleeping lamp
lightens 2 times and then extinguish 2 seconds
over current of outdoor unit
The running lamp lightens all the timethe sleeping lamp
lightens 3 times and then extinguish 2 seconds
discharge temp. of compressor too high,
outside ambient temp. too high, switch
temp. of compressor crust cut off, temp.
of module too high
The running lamp lightens all the timethe sleeping lamp
lightens 4 times and then extinguish 2 seconds
The outdoor unit DC busbar voltage is
abnormal
The running lamp lightens all the timethe sleeping lamp
lightens 7 times and then extinguish 2 seconds
lack refrigerant or reverse valve fault
The running lamp lightens all the timethe sleeping lamp
lightens 8 times and then extinguish 2 seconds
outdoor sensor fault
The timing lamp lightens all the timethe sleeping lamp
lightens 7 times and then extinguish 2 seconds
outdoor unit drive fault, start compressor
failure
The timing lamp lightens all the timethe sleeping lamp
lightens 6 times and then extinguish 2 seconds


48
6.3 The malfunction of indoor and outdoor unit
1The common malfunction code analysis and solutions!
The fault
code
The fault content The reason of fault and its solutions
F1 The communication fault
1The communication wire is broken off. Please check
whether the wire is disentwined ;
2Please check whether the electrical control board is
damaged. It should be replaced when it is damaged;
3Please check whether the power ground wire is reliable;
4Please check whether the unit is abnormal caused by the
external interference. If it is, then find the interfering
sources, and remove them.
F2
The indoor temperature
sensor fault
1Check whether the resistance of sensor is normal,
otherwise replace it;
2Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board, repair it if there is any above;
3When the 1 and 2 are both normal, then the component
or integrated circuit is damaged, the electric control board
should be replaced.
F3
The indoor coil
temperature sensor fault
1Check whether the resistance of sensor is normal,
otherwise replace it;
2Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board ,repair it if there is any above;
3When the 1 and 2 are both normal, then the component
or integrated circuit is damaged, the electric control board
should be replaced.
F4
Indoor PG motor fault
(tap motor hasnt so
breakdown )
1Check whether the contact of the plug of the motor wire
and socket is well. Please make sure it is well contacted;
2Check whether the indoor motor has damaged, the
motor should be replaced when it is damaged;
3 Check whether the controllable silicon and other
components on the electric control board have damaged
replace the controllable silicon or electric control board
when they are damaged;
4Check whether the indoor fan is unobstructed when
running, please fix the indoor fan again when it is
obstructed.
F5

IPM protection

1Check whether the supply voltage is out of ranging from
150 to 270V(overvoltage and undervoltage protection);
Measuring the actual current, if the current is greater than
the rated current of 2A,it is over-temperature protection;
If the above are normal, that is IPM module internal circuit
fault protection, so please replace the IPM module.
F6 The outdoor sensor fault
1Check whether the resistance of sensor is normal,
otherwise replace it;
2Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board, repair it if there is any above;
3When the 1 and 2 are both normal ,then the component
or integrated circuit is damaged, the electric control board
should be replaced.

49
F7
The outdoor coil
temperature sensor fault
Including the
mid-point of tube
inspiratory gas
1Check whether the resistance of sensor is normal,
otherwise replace it;
2Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board, repair it if there is any above;
3When the 1 and 2 are both normal, then the component
or integrated circuit is damaged, the electric control board
should be replaced.
F9 Exhaust gas sensor failure
1Check whether the resistance of sensor is normal,
otherwise replace it;
2Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control
board, repair it if there is any above;
3When the 1 and 2 are both normal, then the component
or integrated circuit is damaged, the electric control board
should be replaced.


FA

The communication fault
between the wire
controller and the indoor
PCB
1 check whether the wire controllers connecting wire is
short circuit or loose, please make it connect well;
2 Check the connecting linewire controllerPCB
whether they are loose or have a bad contact. Please
make them have a good contact.
FC
outdoor unit driving fault,
starting compressor
failure
1Turn on the power again, and then check whether the
operation of the compressor is normal;
2Check whether the connection of the compressor is
correct or reliable, otherwise repair it;
3Check whether the components on the electric control
board have been damaged, if they are damaged, the
components or the electric control board should be
replaced.;
4Check whether the connecting wires are disentwined
between the Intelligent Power Module board and the main
board, otherwise make the wires connect firmly .
FF



The outdoor DC motor
fault
1Check the resistance value of the DC motor port. If it is
short circuit, please change the DC motor;
2 Check the voltage value of the DC motor port
VCC(15Vdc)Vdm(340Vdc),please change the PCB board
if the voltage values are abnormal;
3if all the voltage values of the DC motor port are
normalthe Vsp voltage0~5vis also ok ,it shows that the
inner PCB board of the DC motor is damaged, then change
the DC motor.

FH




The indoor unit
EEPROM error
1Check whether there are false weld and bad contact etc
between the EEPROM chip block and the electronic
control board ;
2Check whether the EEPROM chip pin is broken foot
and the direction of installation is in line with the
EEPROM block;
3When the procedure of EEPROM chip and itself have
fault it will appear the code FH. That is the need to replace
the EEPROM chip.
dF Defrosting state The unit is in defrosting statethat is normal.
dI Mode conflict
When the running mode for No.1 indoor unit is different
from No.2 indoor unit, the dF is displayed.

50

The fault
code
The fault content The reason of fault and solution
P1
Indoor coil
temperature
over-temperature
protection for heating
(thermal overload),
outdoor coil
temperature
overheating protection
for cooling (cooling
overload)
1 Check whether the ambient temperature is over the range
of air-conditioning running temperature ;
2 Check whether the indoor coil temperature is higher than
or equal to 63 degrees when heating and check whether
the outdoor coil temperature is higher than or equal to 65
degrees when cooling, it will appear protection if the
value is over the above;
3 Check whether the parameters of indoor and outdoor coil
temperature sensors are normal, if abnormal, please
replace the sensors;
4 If the above are normal, check whether the main control
board output parameters are normal, if abnormal, please
replace the main control board.
P2
The outdoor unit
inverter module
protection fault

1Check whether the connection of the compressor is reliable,
otherwise connect firmly again;
2Check whether the fixation between the IPM module and
the radiator is firm.;
3Check whether the compressor is well, otherwise replace it;
4Check whether the IPM module is abnormal, otherwise
replace it.
P3
Over current of
outdoor unit
1 Check whether the ambient temperature exceeds the
operation range for the air conditioner;
2Check whether the current detection circuit is abnormal, the
electric control should be replaced when it is abnormal..
P4
discharge temperature of
compressor is too high, the
outside ambient
temperature
over-temperature, switch
off the compressor shell
temperature, module
temperature
over-temperature
1Check whether the pressure is normal when the unit is
running, if it is abnormal, you should detect the leakage and
then welding and adding refrigerant;
2Check whether the ambient temperature is too high or too
low, when the temperature is more than -20 degrees and less
55 degrees, it can disappear automatically;
3 Check whether temperature switch of compressor is
damage, it should be replaced if it is damaged.
P7
The outdoor unit DC
generatrix voltage is
abnormal
1Check whether the supply voltage is out of ranging from
150 to 270V;
2Check the voltage detection circuit of the IPM base board is
abnormal, if it is abnormal, the IPM base board or the electric
control board should be replaced.
P8
lack refrigerant or reverse
valve fault
1Check whether the high and low pressure valves have been
opened, otherwise open the valves;
2Check whether the indoor coil pipe temperature sensor is
normal, if it is abnormal, the sensor should be replaced;
3Check whether the indoor coil temperature sensor hung in
the airplease plug it in a correct position if the indoor coil
temperature sensor hung in the air;
4Check the system pressure is abnormal, if it is abnormal,
yon should detect leakage and the welding and adding the
refrigerant.;
5Please change the outdoor PCB board , if all above are
normal.





PA




protection when indoor
pipe temperature is too
low (Anti-icing)
1 Check whether the ambient temperature is over the range
of air-conditioning running temperature;
2 Check the indoor coil temperature is less than or equal to
-1 degrees, if more than this value it will be the protection
of;
3 Check whether the indoor coil temperature sensor

51
parameters are normal, if abnormal it is the replacement
of the sensor;
4 If the above are normal, check whether the main control
board output parameters are normal, if abnormal ,please
replace the main control board.


PC
Outdoor ambient
temperature
over-temperature
protection (including high
and low)
1 Check whether the outdoor ambient temperature is too
high or too low, when the ambient temperature is lower
than (T> -20, T <55), this fault automatically discharges;
2 Check whether the outdoor temperature sensors ring
temperature parameters are normal, if abnormal ,please
replace the sensor;
3 If the above are normal, check whether the main control
boards output parameters are normal, f abnormal ,please
replace the main control board.
PE
EEPROM reading error
(outdoor unit)
1Check whether there are false weld and bad contact etc
between the EEPROM chip block and the electronic control
board ;
2Check whether the EEPROM chip pin is broken foot and
the direction of installation is in line with the EEPROM block;
3When the procedure of EEPROM chip and itself have fault
it will appear the code PE. At this time there is the need to
replace the EEPROM chip.

S-ar putea să vă placă și