Sunteți pe pagina 1din 1

TABEL 1 - Calculul necesarului de caldura

Nr.
Incapere

Destinatia
incaperii

Suprafata
S [mp]

Inaltime
H [m]

Volum
[V]

Temperatura
interioara ti
[C]

P01
P02
P03
P04
P05
P06
P07
P08

LIVING ROOM
DORMITOR 1
DORMITOR 2
BAIE 1
BAIE 2
BUCATARIE
BIROU
HOL

44
15
11.3
4.7
3.7
14.1
9.7
4

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

110
37.5
28.25
11.75
9.25
35.25
24.25
10

20
20
20
22
22
18
20
18

Indice
volum
q
[W/mc]
40
35
35
45
45
35
35
30

Qi [W]

Observatii

4400
1312.5
988.75
528.75
416.25
1233.75
848.75
300

3 CORPURI
1 CORP
1 CORP
1 CORP
1 CORP
1 CORP
1 CORP
1 CORP

TABEL 2 - Calculul de alegere corpuri din otel


Nr.
Incapere

P01
P02
P03
P04
P05
P06
P07
P08

Destinatia
incaperii
LIVING
ROOM
DORMITOR 1
DORMITOR 2
BAIE 1
BAIE 2
BUCATARIE
BIROU
HOL

Qi total = 11256 W

Qi [W]

Corpuri de
incalzire

Caldura
cedata de
corp
incalzire
[W]

4400

22-500/700

1499

2.93529

4497

1312.5
988.75

11-300/800
11-600/800
AND 0806 M
- 776/595
AND 0806 M
- 776/595
11-300/800
11-600/800
11-600/800

1481
1018

0.886215
0.971267

1
1

1481
1018

1 CORP
1 CORP

579

0.913212

579

1 CORP

579

0.718912

579

1 CORP

1481
985
636

0.833052
0.861675
0.471698

1
1
1

1481
985
636

1 CORP
1 CORP
1 CORP

528.75
416.25
1233.75
848.75
300

Nr corpuri
de incalzire
necesar

Nr
corpuri
de
incalzire
stabilit

Caldura
totala
cedata

observatii

S-ar putea să vă placă și