DANFOSS DRIVE - QUICK USER GUIDE

VARIABLE SPEED(NON FEEDBACK) OPERATIONS


Model No- FC 360
Name Settings-Short Name Value to Assigned
Configuration Mode 1-00 0
Torque characteristics 1-03 1
Ref Range 3-00 0
Ref Source 3-15 2
Motor Low Limit
4-12
Motor High Limit
4-14
DI 18 Selection 5-10 8
DI 27 Selection 5-12 2
AI 54 Low 6-22 4.0ma
AI 54 High 6-23 20ma
AI 54 Mode 6-29 0
Motor Data:
Motor Power 1-20 5
Motor Voltage 1-22
Special Attention:
1. Keep the Drive In stop mode while doing settings/modifications
Value & its Corresponding State Note
open loop
variable torqe
Min-Max
Reference source is Analog IP-54
5.0 HZ- Low speed limit value
Changeble as per requirements
within Motor Limitations
50.0 HZ High speed limit value
Changeble as per requirements
within Motor Limitations
If DI 18 is high then motor will Start Digital Input (PLC Controllable)
Coast Inverse
24V DC supply to be given to this DI
terminal; Without this it may not
work
Low Level settings(AI) For Analog I/P channel 54 only
High Level settings(AI) For Analog I/P channel 54 only
Current Mode For Analog I/P channel 54 only
For 0.37kw- 0.5hp
For other power range setting will
change