Tele-Protection Signal List for 132 kV Line Protection:

132 kV Line Protection with Distance (21) Relay as Main & Directional Over
Current/Earth Fault (67/67N) as Back-up
Relay Type Signal Remarks
Main (21)
21 Tx (Distance Sent)
Generally Under-Reaching
21 Rx (Distance Received)
Back-up (67N)
67N Tx (DSEF/DEF Sent)
Generally Over-Reaching 67N Rx (DSEF/DEF
Received)
Breaker Fail
DTT-1 (Direct Transfer
Trip) Rx Separate Communication Channels should be
Used for Each Signal Sent DTT-2 (Direct Transfer
Trip) Rx
DTT-1 (Direct Transfer
Trip) Tx Separate Communication Channels should be
Used for Each Signal Received DTT-2 (Direct Transfer
Trip) Tx
132 kV Line Protection with Line Differential (87L) Relay as Main & Directional Over
Current/Earth Fault (67/67N) as Back-up
Main (87L)
Inter-Tripping Signal should be Internally Sent/r
by the Same Fibre-Optic Channel with Which
both End 87L Relays are Communicating.
Back-up (67N)
67N Tx (DSEF/DEF Sent)
Generally Over-Reaching 67N Rx (DSEF/DEF
Received)
Breaker Fail
DTT-1 (Direct Transfer
Trip) Rx Separate Communication Channels should be
Used for Each Signal Sent DTT-2 (Direct Transfer
Trip) Rx
DTT-1 (Direct Transfer
Trip) Tx Separate Communication Channels should be
Used for Each Signal Received DTT-2 (Direct Transfer
Trip) Tx