PHOTO PULL-OFF TEST REPORT – ON COATED GALVANIZED PIPES CARRIED

OUT AT EASTERN BLASTING & COATING’S PREMISE ON DECEMBER 17 – 18


2009 FOR PUB’S PROJECT “PEDESTRIAN BRIDGE ACROSS SUNGEI
SERANGOON TO LORONG HALUS WETLANDS”.

Area: Coated galvanized


pipes.

Comments: General view of


some of the galvanized pipes
coated with 2-coat Sigma
Protective Coating System at
Eastern Blasting & Coating
Pte Ltd’s premise at 32
Senoko Road, Singapore.

PHOTO 1
Area: Coated galvanized
pipes.

Comments: Closed-up view


of some of the galvanized
pipes coated with 2-coat
Sigma Protective Coating
System. 4 lengths fully
coated up to 12-metre and 2
lengths coated up to 8-metre
with 4-metre galvanized
portion left uncoated.

PHOTO 2
Area: Selected coated
galvanized pipe for testing.

Comments: Fixing of pull-off


stubs or dollies on 3 locations
on one of the selected coated
pipes. Dry film thickness
(DFT) measurements were
carried out with an Elcometer
Model 456 paint thickness
gauge. The measured DFT
readings were inclusive of the
galvanizing coating thickness.

PHOTO 3
QMS / FTS Reporting Forms Issued: 08/07/01 FFTS05.PH
Area: Selected coated
galvanized pipe for testing.

Comments: Result of pull-off


or tensile strength of the paint
system on Stub/Dolly # 1, was
as follows:-

The dolly indicating 100%


glue failure with a tensile
strength of 9.0MPa.

PHOTO 4
Area: Selected coated
galvanized pipe for testing.

Comments: Result of pull-off


or tensile strength of the paint
system on Stub/Dolly # 2, was
as follows:-

The dolly indicating 100%


glue failure with a tensile
strength of 9.5MPa.

PHOTO 5
Area: Selected coated
galvanized pipe for testing.

Comments: Result of pull-off


or tensile strength of the paint
system on Stub/Dolly # 3, was
as follows:-

The dolly indicating 100%


glue failure with a tensile
strength of 6.0MPa.

The average tensile strength


for the 3 test areas was 8.2
MPa.

PHOTO 6

QMS / FTS Reporting Forms Issued: 08/07/01 FFTS05.PH