Algo-Tec 6300 INTERACTIVE

ADDRESSABLE FIRE CONTROL


SYSTEM
(1-4 LOOPS)
LOOP COMMISSIONING MANUAL

Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT.
Telephone:
Fax:
Web:
Email:

+44 (0) 1282 717171


+44 (0) 1282 717273
www.protec.co.uk
sales@protec.co.uk

CUSTOMER DETAILS
Customer / Company Name :
Customer / Company Address :

Customer Order Number :

SITE DETAILS
Site Name :
Site Address :

EQUIPMENT DETAILS
Panel Location :

Technical Help
Please contact :

Technical Support & Training

Technical Support Department


Protec Fire Detection
Protec House
Churchill Way
Nelson
Lancs
BB9 6RT

e-mail : technical@protec.co.uk
Telephone : (01282) 717444

Protec Fire Detection plc

6300 Loop Commissioning Manual

93-507-07 Issue 2

A guide on how to attach Bar-codes to the Algo-Tec 6300 Loop Commissioning Manual
Please refer to the following diagram:-

Device
Loop Commissioning Manual

Loop 1 of 4
Add

Address Serial No
Not
Used

Leave
blank

*L1002*

Leave
blank

Remove the 'Device Bar-code' label (WHITE) and place


next to the appropiate address INPUT number on the
following sheets

INPUT DEVICE

001

Not
Used

002

*L1001*

Rear of
6000PLUS
device

INPUT DEVICE

Device Bar-code label

Protec Fire Detection plc

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 1 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L1001*
INPUT DEVICE

Add
Leave
blank

001

Address Serial No
Not
Used

*L1009*
INPUT DEVICE

Add
Leave
blank

009

Not
Used

*L1002*
INPUT DEVICE

Leave
blank

002

*L1003*
INPUT DEVICE

Not
Used

Leave
blank

003

*L1010*
INPUT DEVICE

Leave
blank

*L1004*
INPUT DEVICE

Not
Used

Leave
blank

004

*L1011*
INPUT DEVICE

Leave
blank

*L1005*

Not
Used

INPUT DEVICE

*L1012*
INPUT DEVICE

Leave
blank

*L1013*

Leave
blank

INPUT DEVICE

*L1014*
INPUT DEVICE

Leave
blank

014

*L1007*
INPUT DEVICE

*L1015*
INPUT DEVICE

Leave
blank

015

*L1008*
INPUT DEVICE

008

Not
Used

*L1020*
INPUT DEVICE

Leave
blank

Not
Used

*L1021*

Leave
blank

Not
Used

*L1022*
INPUT DEVICE

Leave
blank

Not
Used

*L1023*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L1024*
INPUT DEVICE

Leave
blank

023

Not
Used

*L1016*
INPUT DEVICE

Leave
blank

016

Protec Fire Detection plc

Leave
blank

022

Not
Used

Leave
blank

007

Not
Used

*L1019*
INPUT DEVICE

021

Not
Used

Leave
blank

006

Not
Used

Not
Used

INPUT DEVICE

013

*L1006*

Leave
blank

INPUT DEVICE

005

Not
Used

*L1018*
INPUT DEVICE

020

Not
Used

Leave
blank

Not
Used

019

012

Not
Used

Leave
blank

018

011

Not
Used

*L1017*
INPUT DEVICE

017

010

Not
Used

Address Serial No
Not
Used

024

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 1 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L1025*
INPUT DEVICE

Add
Leave
blank

025

Address Serial No
Not
Used

*L1033*
INPUT DEVICE

Add
Leave
blank

033

Not
Used

*L1026*
INPUT DEVICE

Leave
blank

026

*L1027*
INPUT DEVICE

Not
Used

Leave
blank

027

*L1034*
INPUT DEVICE

Leave
blank

*L1028*
INPUT DEVICE

Not
Used

Leave
blank

028

*L1035*
INPUT DEVICE

Leave
blank

*L1029*

Not
Used

INPUT DEVICE

*L1036*
INPUT DEVICE

Leave
blank

*L1037*

Leave
blank

INPUT DEVICE

*L1038*
INPUT DEVICE

Leave
blank

038

*L1031*
INPUT DEVICE

*L1039*
INPUT DEVICE

Leave
blank

039

*L1032*
INPUT DEVICE

032

Not
Used

*L1044*
INPUT DEVICE

Leave
blank

Not
Used

*L1045*

Leave
blank

Not
Used

*L1046*
INPUT DEVICE

Leave
blank

Not
Used

*L1047*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L1048*
INPUT DEVICE

Leave
blank

047

Not
Used

*L1040*
INPUT DEVICE

Leave
blank

040

Protec Fire Detection plc

Leave
blank

046

Not
Used

Leave
blank

031

Not
Used

*L1043*
INPUT DEVICE

045

Not
Used

Leave
blank

030

Not
Used

Not
Used

INPUT DEVICE

037

*L1030*

Leave
blank

INPUT DEVICE

029

Not
Used

*L1042*
INPUT DEVICE

044

Not
Used

Leave
blank

Not
Used

043

036

Not
Used

Leave
blank

042

035

Not
Used

*L1041*
INPUT DEVICE

041

034

Not
Used

Address Serial No
Not
Used

048

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 1 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L1049*
INPUT DEVICE

Add
Leave
blank

049

Address Serial No
Not
Used

*L1057*
INPUT DEVICE

Add
Leave
blank

057

Not
Used

*L1050*
INPUT DEVICE

Leave
blank

050

*L1051*
INPUT DEVICE

Not
Used

Leave
blank

051

*L1058*
INPUT DEVICE

Leave
blank

*L1052*
INPUT DEVICE

Not
Used

Leave
blank

052

*L1059*
INPUT DEVICE

Leave
blank

*L1053*

Not
Used

INPUT DEVICE

*L1060*
INPUT DEVICE

Leave
blank

*L1061*

Leave
blank

INPUT DEVICE

*L1062*
INPUT DEVICE

Leave
blank

062

*L1055*
INPUT DEVICE

*L1063*
INPUT DEVICE

Leave
blank

063

*L1056*
INPUT DEVICE

056

Not
Used

*L1068*
INPUT DEVICE

Leave
blank

Not
Used

*L1069*

Leave
blank

Not
Used

*L1070*
INPUT DEVICE

Leave
blank

Not
Used

*L1071*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L1072*
INPUT DEVICE

Leave
blank

071

Not
Used

*L1064*
INPUT DEVICE

Leave
blank

064

Protec Fire Detection plc

Leave
blank

070

Not
Used

Leave
blank

055

Not
Used

*L1067*
INPUT DEVICE

069

Not
Used

Leave
blank

054

Not
Used

Not
Used

INPUT DEVICE

061

*L1054*

Leave
blank

INPUT DEVICE

053

Not
Used

*L1066*
INPUT DEVICE

068

Not
Used

Leave
blank

Not
Used

067

060

Not
Used

Leave
blank

066

059

Not
Used

*L1065*
INPUT DEVICE

065

058

Not
Used

Address Serial No
Not
Used

072

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 1 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L1073*
INPUT DEVICE

Add
Leave
blank

073

Address Serial No
Not
Used

*L1081*
INPUT DEVICE

Add
Leave
blank

081

Not
Used

*L1074*
INPUT DEVICE

Leave
blank

074

*L1075*
INPUT DEVICE

Not
Used

Leave
blank

075

*L1082*
INPUT DEVICE

Leave
blank

*L1076*
INPUT DEVICE

Not
Used

Leave
blank

076

*L1083*
INPUT DEVICE

Leave
blank

*L1077*

Not
Used

INPUT DEVICE

*L1084*
INPUT DEVICE

Leave
blank

*L1085*

Leave
blank

INPUT DEVICE

*L1086*
INPUT DEVICE

Leave
blank

086

*L1079*
INPUT DEVICE

*L1087*
INPUT DEVICE

Leave
blank

087

*L1080*
INPUT DEVICE

080

Not
Used

*L1092*
INPUT DEVICE

Leave
blank

Not
Used

*L1093*

Leave
blank

Not
Used

*L1094*
INPUT DEVICE

Leave
blank

Not
Used

*L1095*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L1096*
INPUT DEVICE

Leave
blank

095

Not
Used

*L1088*
INPUT DEVICE

Leave
blank

088

Protec Fire Detection plc

Leave
blank

094

Not
Used

Leave
blank

079

Not
Used

*L1091*
INPUT DEVICE

093

Not
Used

Leave
blank

078

Not
Used

Not
Used

INPUT DEVICE

085

*L1078*

Leave
blank

INPUT DEVICE

077

Not
Used

*L1090*
INPUT DEVICE

092

Not
Used

Leave
blank

Not
Used

091

084

Not
Used

Leave
blank

090

083

Not
Used

*L1089*
INPUT DEVICE

089

082

Not
Used

Address Serial No
Not
Used

096

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 1 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L1097*
INPUT DEVICE

Add
Leave
blank

097

Address Serial No
Not
Used

*L1105*
INPUT DEVICE

Add
Leave
blank

105

Not
Used

*L1098*
INPUT DEVICE

Leave
blank

098

*L1099*
INPUT DEVICE

Not
Used

Leave
blank

099

*L1106*
INPUT DEVICE

Leave
blank

*L1100*
INPUT DEVICE

Not
Used

Leave
blank

100

*L1107*
INPUT DEVICE

Leave
blank

*L1101*

Not
Used

INPUT DEVICE

*L1108*
INPUT DEVICE

Leave
blank

*L1109*

Leave
blank

INPUT DEVICE

*L1110*
INPUT DEVICE

Leave
blank

110

*L1103*
INPUT DEVICE

*L1111*
INPUT DEVICE

Leave
blank

111

*L1104*
INPUT DEVICE

104

Not
Used

*L1116*
INPUT DEVICE

Leave
blank

Not
Used

*L1117*

Leave
blank

Not
Used

*L1118*
INPUT DEVICE

Leave
blank

Not
Used

*L1119*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L1120*
INPUT DEVICE

Leave
blank

119

Not
Used

*L1112*
INPUT DEVICE

Leave
blank

112

Protec Fire Detection plc

Leave
blank

118

Not
Used

Leave
blank

103

Not
Used

*L1115*
INPUT DEVICE

117

Not
Used

Leave
blank

102

Not
Used

Not
Used

INPUT DEVICE

109

*L1102*

Leave
blank

INPUT DEVICE

101

Not
Used

*L1114*
INPUT DEVICE

116

Not
Used

Leave
blank

Not
Used

115

108

Not
Used

Leave
blank

114

107

Not
Used

*L1113*
INPUT DEVICE

113

106

Not
Used

Address Serial No
Not
Used

120

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 1 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L1121*
INPUT DEVICE

Add
Leave
blank

121

Address Serial No
Not
Used

*L1129*
INPUT DEVICE

Add
Leave
blank

129

Not
Used

*L1122*
INPUT DEVICE

Leave
blank

122

*L1123*
INPUT DEVICE

Not
Used

Leave
blank

123

*L1130*
INPUT DEVICE

Leave
blank

*L1124*
INPUT DEVICE

Not
Used

Leave
blank

124

*L1131*
INPUT DEVICE

Leave
blank

*L1125*

Not
Used

INPUT DEVICE

*L1132*
INPUT DEVICE

Leave
blank

*L1133*

Leave
blank

INPUT DEVICE

*L1134*
INPUT DEVICE

Leave
blank

134

*L1127*
INPUT DEVICE

*L1135*
INPUT DEVICE

Leave
blank

135

*L1128*
INPUT DEVICE

128

Not
Used

*L1140*
INPUT DEVICE

Leave
blank

Not
Used

*L1141*

Leave
blank

Not
Used

*L1142*
INPUT DEVICE

Leave
blank

Not
Used

*L1143*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L1144*
INPUT DEVICE

Leave
blank

143

Not
Used

*L1136*
INPUT DEVICE

Leave
blank

136

Protec Fire Detection plc

Leave
blank

142

Not
Used

Leave
blank

127

Not
Used

*L1139*
INPUT DEVICE

141

Not
Used

Leave
blank

126

Not
Used

Not
Used

INPUT DEVICE

133

*L1126*

Leave
blank

INPUT DEVICE

125

Not
Used

*L1138*
INPUT DEVICE

140

Not
Used

Leave
blank

Not
Used

139

132

Not
Used

Leave
blank

138

131

Not
Used

*L1137*
INPUT DEVICE

137

130

Not
Used

Address Serial No
Not
Used

144

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 1 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L1145*
INPUT DEVICE

Add
Leave
blank

145

Address Serial No
Not
Used

*L1153*
INPUT DEVICE

Add
Leave
blank

153

Not
Used

*L1146*
INPUT DEVICE

Leave
blank

146

*L1147*
INPUT DEVICE

Not
Used

Leave
blank

147

*L1154*
INPUT DEVICE

Leave
blank

*L1148*
INPUT DEVICE

Not
Used

Leave
blank

148

*L1155*
INPUT DEVICE

Leave
blank

*L1149*

Not
Used

Leave
blank

*L1156*
INPUT DEVICE

Leave
blank

Not
Used

*L1157*

Leave
blank

Leave
blank

Not
Used

Leave
blank

151

*L1158*
INPUT DEVICE

Leave
blank

*L1152*
INPUT DEVICE

152

Not
Used

*L1159*
INPUT DEVICE

Leave
blank

Not
Used

*L1164*
INPUT DEVICE

Leave
blank

Not
Used

*L1165*

Leave
blank

Not
Used

*L1166*
INPUT DEVICE

Leave
blank

Not
Used

*L1167*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L1168*
INPUT DEVICE

Leave
blank

167

Not
Used

*L1160*
INPUT DEVICE

Leave
blank

160

Protec Fire Detection plc

Leave
blank

166

159

Not
Used

*L1163*
INPUT DEVICE

INPUT DEVICE

158

*L1151*
INPUT DEVICE

Not
Used

165

INPUT DEVICE

150

Not
Used

Leave
blank

INPUT DEVICE

157

*L1150*

*L1162*
INPUT DEVICE

164

INPUT DEVICE

149

Not
Used

Not
Used

163

156

Not
Used

Leave
blank

162

155

Not
Used

*L1161*
INPUT DEVICE

161

154

Not
Used

Address Serial No
Not
Used

168

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 1 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L1169*
INPUT DEVICE

Add
Leave
blank

169

Address Serial No
Not
Used

*L1177*
INPUT DEVICE

Add
Leave
blank

177

Not
Used

*L1170*
INPUT DEVICE

Leave
blank

170

*L1171*
INPUT DEVICE

Not
Used

Leave
blank

171

*L1178*
INPUT DEVICE

Leave
blank

*L1172*
INPUT DEVICE

Not
Used

Leave
blank

172

*L1179*
INPUT DEVICE

Leave
blank

*L1173*

Not
Used

Leave
blank

*L1180*
INPUT DEVICE

Leave
blank

Not
Used

*L1181*

Leave
blank

Leave
blank

Not
Used

Leave
blank

175

*L1182*
INPUT DEVICE

Leave
blank

*L1176*
INPUT DEVICE

176

Leave
blank

Not
Used

*L1188*
INPUT DEVICE

Leave
blank

Not
Used

*L1189*

Leave
blank

Not
Used

*L1190*
INPUT DEVICE

Leave
blank

Not
Used

*L1191*
INPUT DEVICE

Leave
blank

190

Not
Used

*L1183*
INPUT DEVICE

Leave
blank

183

Not
Used

*L1187*
INPUT DEVICE

INPUT DEVICE

182

*L1175*
INPUT DEVICE

Not
Used

189

INPUT DEVICE

174

Not
Used

Leave
blank

INPUT DEVICE

181

*L1174*

*L1186*
INPUT DEVICE

188

INPUT DEVICE

173

Not
Used

Not
Used

187

180

Not
Used

Leave
blank

186

179

Not
Used

*L1185*
INPUT DEVICE

185

178

Not
Used

Address Serial No
Not
Used

Leave
blank

191

Not
Used

*L1184*
INPUT DEVICE

Leave
blank

184

Protec Fire Detection plc

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 2 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L2001*
INPUT DEVICE

Add
Leave
blank

001

Address Serial No
Not
Used

*L2009*
INPUT DEVICE

Add
Leave
blank

009

Not
Used

*L2002*
INPUT DEVICE

Leave
blank

002

*L2003*
INPUT DEVICE

Not
Used

Leave
blank

003

*L2010*
INPUT DEVICE

Leave
blank

*L2004*
INPUT DEVICE

Not
Used

Leave
blank

004

*L2011*
INPUT DEVICE

Leave
blank

*L2005*

Not
Used

INPUT DEVICE

*L2012*
INPUT DEVICE

Leave
blank

*L2013*

Leave
blank

INPUT DEVICE

*L2014*
INPUT DEVICE

Leave
blank

014

*L2007*
INPUT DEVICE

*L2015*
INPUT DEVICE

Leave
blank

015

*L2008*
INPUT DEVICE

008

Not
Used

*L2020*
INPUT DEVICE

Leave
blank

Not
Used

*L2021*

Leave
blank

Not
Used

*L2022*
INPUT DEVICE

Leave
blank

Not
Used

*L2023*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L2024*
INPUT DEVICE

Leave
blank

023

Not
Used

*L2016*
INPUT DEVICE

Leave
blank

016

Protec Fire Detection plc

Leave
blank

022

Not
Used

Leave
blank

007

Not
Used

*L2019*
INPUT DEVICE

021

Not
Used

Leave
blank

006

Not
Used

Not
Used

INPUT DEVICE

013

*L2006*

Leave
blank

INPUT DEVICE

005

Not
Used

*L2018*
INPUT DEVICE

020

Not
Used

Leave
blank

Not
Used

019

012

Not
Used

Leave
blank

018

011

Not
Used

*L2017*
INPUT DEVICE

017

010

Not
Used

Address Serial No
Not
Used

024

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 2 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L2025*
INPUT DEVICE

Add
Leave
blank

025

Address Serial No
Not
Used

*L2033*
INPUT DEVICE

Add
Leave
blank

033

Not
Used

*L2026*
INPUT DEVICE

Leave
blank

026

*L2027*
INPUT DEVICE

Not
Used

Leave
blank

027

*L2034*
INPUT DEVICE

Leave
blank

*L2028*
INPUT DEVICE

Not
Used

Leave
blank

028

*L2035*
INPUT DEVICE

Leave
blank

*L2029*

Not
Used

INPUT DEVICE

*L2036*
INPUT DEVICE

Leave
blank

*L2037*

Leave
blank

INPUT DEVICE

*L2038*
INPUT DEVICE

Leave
blank

038

*L2031*
INPUT DEVICE

*L2039*
INPUT DEVICE

Leave
blank

039

*L2032*
INPUT DEVICE

032

Not
Used

*L2044*
INPUT DEVICE

Leave
blank

Not
Used

*L2045*

Leave
blank

Not
Used

*L2046*
INPUT DEVICE

Leave
blank

Not
Used

*L2047*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L2048*
INPUT DEVICE

Leave
blank

047

Not
Used

*L2040*
INPUT DEVICE

Leave
blank

040

Protec Fire Detection plc

Leave
blank

046

Not
Used

Leave
blank

031

Not
Used

*L2043*
INPUT DEVICE

045

Not
Used

Leave
blank

030

Not
Used

Not
Used

INPUT DEVICE

037

*L2030*

Leave
blank

INPUT DEVICE

029

Not
Used

*L2042*
INPUT DEVICE

044

Not
Used

Leave
blank

Not
Used

043

036

Not
Used

Leave
blank

042

035

Not
Used

*L2041*
INPUT DEVICE

041

034

Not
Used

Address Serial No
Not
Used

048

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 2 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L2049*
INPUT DEVICE

Add
Leave
blank

049

Address Serial No
Not
Used

*L2057*
INPUT DEVICE

Add
Leave
blank

057

Not
Used

*L2050*
INPUT DEVICE

Leave
blank

050

*L2051*
INPUT DEVICE

Not
Used

Leave
blank

051

*L2058*
INPUT DEVICE

Leave
blank

*L2052*
INPUT DEVICE

Not
Used

Leave
blank

052

*L2059*
INPUT DEVICE

Leave
blank

*L2053*

Not
Used

INPUT DEVICE

*L2060*
INPUT DEVICE

Leave
blank

*L2061*

Leave
blank

INPUT DEVICE

*L2062*
INPUT DEVICE

Leave
blank

062

*L2055*
INPUT DEVICE

*L2063*
INPUT DEVICE

Leave
blank

063

*L2056*
INPUT DEVICE

056

Not
Used

*L2068*
INPUT DEVICE

Leave
blank

Not
Used

*L2069*

Leave
blank

Not
Used

*L2070*
INPUT DEVICE

Leave
blank

Not
Used

*L2071*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L2072*
INPUT DEVICE

Leave
blank

071

Not
Used

*L2064*
INPUT DEVICE

Leave
blank

064

Protec Fire Detection plc

Leave
blank

070

Not
Used

Leave
blank

055

Not
Used

*L2067*
INPUT DEVICE

069

Not
Used

Leave
blank

054

Not
Used

Not
Used

INPUT DEVICE

061

*L2054*

Leave
blank

INPUT DEVICE

053

Not
Used

*L2066*
INPUT DEVICE

068

Not
Used

Leave
blank

Not
Used

067

060

Not
Used

Leave
blank

066

059

Not
Used

*L2065*
INPUT DEVICE

065

058

Not
Used

Address Serial No
Not
Used

072

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 2 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L2073*
INPUT DEVICE

Add
Leave
blank

073

Address Serial No
Not
Used

*L2081*
INPUT DEVICE

Add
Leave
blank

081

Not
Used

*L2074*
INPUT DEVICE

Leave
blank

074

*L2075*
INPUT DEVICE

Not
Used

Leave
blank

075

*L2082*
INPUT DEVICE

Leave
blank

*L2076*
INPUT DEVICE

Not
Used

Leave
blank

076

*L2083*
INPUT DEVICE

Leave
blank

*L2077*

Not
Used

INPUT DEVICE

*L2084*
INPUT DEVICE

Leave
blank

*L2085*

Leave
blank

INPUT DEVICE

*L2086*
INPUT DEVICE

Leave
blank

086

*L2079*
INPUT DEVICE

*L2087*
INPUT DEVICE

Leave
blank

087

*L2080*
INPUT DEVICE

080

Not
Used

*L2092*
INPUT DEVICE

Leave
blank

Not
Used

*L2093*

Leave
blank

Not
Used

*L2094*
INPUT DEVICE

Leave
blank

Not
Used

*L2095*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L2096*
INPUT DEVICE

Leave
blank

095

Not
Used

*L2088*
INPUT DEVICE

Leave
blank

088

Protec Fire Detection plc

Leave
blank

094

Not
Used

Leave
blank

079

Not
Used

*L2091*
INPUT DEVICE

093

Not
Used

Leave
blank

078

Not
Used

Not
Used

INPUT DEVICE

085

*L2078*

Leave
blank

INPUT DEVICE

077

Not
Used

*L2090*
INPUT DEVICE

092

Not
Used

Leave
blank

Not
Used

091

084

Not
Used

Leave
blank

090

083

Not
Used

*L2089*
INPUT DEVICE

089

082

Not
Used

Address Serial No
Not
Used

096

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 2 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L2097*
INPUT DEVICE

Add
Leave
blank

097

Address Serial No
Not
Used

*L2105*
INPUT DEVICE

Add
Leave
blank

105

Not
Used

*L2098*
INPUT DEVICE

Leave
blank

098

*L2099*
INPUT DEVICE

Not
Used

Leave
blank

099

*L2106*
INPUT DEVICE

Leave
blank

*L2100*
INPUT DEVICE

Not
Used

Leave
blank

100

*L2107*
INPUT DEVICE

Leave
blank

*L2101*

Not
Used

Leave
blank

*L2108*
INPUT DEVICE

Leave
blank

Not
Used

*L2109*

Leave
blank

Leave
blank

Not
Used

Leave
blank

103

*L2110*
INPUT DEVICE

Leave
blank

*L2104*
INPUT DEVICE

104

Not
Used

*L2111*
INPUT DEVICE

Leave
blank

Not
Used

*L2116*
INPUT DEVICE

Leave
blank

Not
Used

*L2117*

Leave
blank

Not
Used

*L2118*
INPUT DEVICE

Leave
blank

Not
Used

*L2119*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L2120*
INPUT DEVICE

Leave
blank

119

Not
Used

*L2112*
INPUT DEVICE

Leave
blank

112

Protec Fire Detection plc

Leave
blank

118

111

Not
Used

*L2115*
INPUT DEVICE

INPUT DEVICE

110

*L2103*
INPUT DEVICE

Not
Used

117

INPUT DEVICE

102

Not
Used

Leave
blank

INPUT DEVICE

109

*L2102*

*L2114*
INPUT DEVICE

116

INPUT DEVICE

101

Not
Used

Not
Used

115

108

Not
Used

Leave
blank

114

107

Not
Used

*L2113*
INPUT DEVICE

113

106

Not
Used

Address Serial No
Not
Used

120

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 2 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L2121*
INPUT DEVICE

Add
Leave
blank

121

Address Serial No
Not
Used

*L2129*
INPUT DEVICE

Add
Leave
blank

129

Not
Used

*L2122*
INPUT DEVICE

Leave
blank

122

*L2123*
INPUT DEVICE

Not
Used

Leave
blank

123

*L2130*
INPUT DEVICE

Leave
blank

*L2124*
INPUT DEVICE

Not
Used

Leave
blank

124

*L2131*
INPUT DEVICE

Leave
blank

*L2125*

Not
Used

Leave
blank

*L2132*
INPUT DEVICE

Leave
blank

Not
Used

*L2133*

Leave
blank

Leave
blank

Not
Used

Leave
blank

127

*L2134*
INPUT DEVICE

Leave
blank

*L2128*
INPUT DEVICE

128

Not
Used

*L2135*
INPUT DEVICE

Leave
blank

Not
Used

*L2140*
INPUT DEVICE

Leave
blank

Not
Used

*L2141*

Leave
blank

Not
Used

*L2142*
INPUT DEVICE

Leave
blank

Not
Used

*L2143*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L2144*
INPUT DEVICE

Leave
blank

143

Not
Used

*L2136*
INPUT DEVICE

Leave
blank

136

Protec Fire Detection plc

Leave
blank

142

135

Not
Used

*L2139*
INPUT DEVICE

INPUT DEVICE

134

*L2127*
INPUT DEVICE

Not
Used

141

INPUT DEVICE

126

Not
Used

Leave
blank

INPUT DEVICE

133

*L2126*

*L2138*
INPUT DEVICE

140

INPUT DEVICE

125

Not
Used

Not
Used

139

132

Not
Used

Leave
blank

138

131

Not
Used

*L2137*
INPUT DEVICE

137

130

Not
Used

Address Serial No
Not
Used

144

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 2 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L2145*
INPUT DEVICE

Add
Leave
blank

145

Address Serial No
Not
Used

*L2153*
INPUT DEVICE

Add
Leave
blank

153

Not
Used

*L2146*
INPUT DEVICE

Leave
blank

146

*L2147*
INPUT DEVICE

Not
Used

Leave
blank

147

*L2154*
INPUT DEVICE

Leave
blank

*L2148*
INPUT DEVICE

Not
Used

Leave
blank

148

*L2155*
INPUT DEVICE

Leave
blank

*L2149*

Not
Used

Leave
blank

*L2156*
INPUT DEVICE

Leave
blank

Not
Used

*L2157*

Leave
blank

Leave
blank

Not
Used

Leave
blank

151

*L2158*
INPUT DEVICE

Leave
blank

*L2152*
INPUT DEVICE

152

Not
Used

*L2159*
INPUT DEVICE

Leave
blank

Not
Used

*L2164*
INPUT DEVICE

Leave
blank

Not
Used

*L2165*

Leave
blank

Not
Used

*L2166*
INPUT DEVICE

Leave
blank

Not
Used

*L2167*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L2168*
INPUT DEVICE

Leave
blank

167

Not
Used

*L2160*
INPUT DEVICE

Leave
blank

160

Protec Fire Detection plc

Leave
blank

166

159

Not
Used

*L2163*
INPUT DEVICE

INPUT DEVICE

158

*L2151*
INPUT DEVICE

Not
Used

165

INPUT DEVICE

150

Not
Used

Leave
blank

INPUT DEVICE

157

*L2150*

*L2162*
INPUT DEVICE

164

INPUT DEVICE

149

Not
Used

Not
Used

163

156

Not
Used

Leave
blank

162

155

Not
Used

*L2161*
INPUT DEVICE

161

154

Not
Used

Address Serial No
Not
Used

168

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 2 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L2169*
INPUT DEVICE

Add
Leave
blank

169

Address Serial No
Not
Used

*L2177*
INPUT DEVICE

Add
Leave
blank

177

Not
Used

*L2170*
INPUT DEVICE

Leave
blank

170

*L2171*
INPUT DEVICE

Not
Used

Leave
blank

171

*L2178*
INPUT DEVICE

Leave
blank

*L2172*
INPUT DEVICE

Not
Used

Leave
blank

172

*L2179*
INPUT DEVICE

Leave
blank

*L2173*

Not
Used

Leave
blank

*L2180*
INPUT DEVICE

Leave
blank

Not
Used

*L2181*

Leave
blank

Leave
blank

Not
Used

Leave
blank

175

*L2182*
INPUT DEVICE

Leave
blank

*L2176*
INPUT DEVICE

176

Leave
blank

Not
Used

*L2188*
INPUT DEVICE

Leave
blank

Not
Used

*L2189*

Leave
blank

Not
Used

*L2190*
INPUT DEVICE

Leave
blank

Not
Used

*L2191*
INPUT DEVICE

Leave
blank

190

Not
Used

*L2183*
INPUT DEVICE

Leave
blank

183

Not
Used

*L2187*
INPUT DEVICE

INPUT DEVICE

182

*L2175*
INPUT DEVICE

Not
Used

189

INPUT DEVICE

174

Not
Used

Leave
blank

INPUT DEVICE

181

*L2174*

*L2186*
INPUT DEVICE

188

INPUT DEVICE

173

Not
Used

Not
Used

187

180

Not
Used

Leave
blank

186

179

Not
Used

*L2185*
INPUT DEVICE

185

178

Not
Used

Address Serial No
Not
Used

Leave
blank

191

Not
Used

*L2184*
INPUT DEVICE

Leave
blank

184

Protec Fire Detection plc

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 3 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L3001*
INPUT DEVICE

Add
Leave
blank

001

Address Serial No
Not
Used

*L3009*
INPUT DEVICE

Add
Leave
blank

009

Not
Used

*L3002*
INPUT DEVICE

Leave
blank

002

*L3003*
INPUT DEVICE

Not
Used

Leave
blank

003

*L3010*
INPUT DEVICE

Leave
blank

*L3004*
INPUT DEVICE

Not
Used

Leave
blank

004

*L3011*
INPUT DEVICE

Leave
blank

*L3005*

Not
Used

Leave
blank

*L3012*
INPUT DEVICE

Leave
blank

Not
Used

*L3013*

Leave
blank

Leave
blank

Not
Used

*L3014*
INPUT DEVICE

Leave
blank

*L3015*
INPUT DEVICE

Leave
blank

015

*L3008*
INPUT DEVICE

008

Not
Used

*L3020*
INPUT DEVICE

Leave
blank

Not
Used

*L3021*

Leave
blank

Not
Used

*L3022*
INPUT DEVICE

Leave
blank

Not
Used

*L3023*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L3024*
INPUT DEVICE

Leave
blank

023

Not
Used

*L3016*
INPUT DEVICE

Leave
blank

016

Protec Fire Detection plc

Leave
blank

022

Not
Used

Leave
blank

007

Not
Used

*L3019*
INPUT DEVICE

INPUT DEVICE

014

*L3007*
INPUT DEVICE

Not
Used

021

INPUT DEVICE

006

Not
Used

Leave
blank

INPUT DEVICE

013

*L3006*

*L3018*
INPUT DEVICE

020

INPUT DEVICE

005

Not
Used

Not
Used

019

012

Not
Used

Leave
blank

018

011

Not
Used

*L3017*
INPUT DEVICE

017

010

Not
Used

Address Serial No
Not
Used

024

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 3 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L3025*
INPUT DEVICE

Add
Leave
blank

025

Address Serial No
Not
Used

*L3033*
INPUT DEVICE

Add
Leave
blank

033

Not
Used

*L3026*
INPUT DEVICE

Leave
blank

026

*L3027*
INPUT DEVICE

Not
Used

Leave
blank

027

*L3034*
INPUT DEVICE

Leave
blank

*L3028*
INPUT DEVICE

Not
Used

Leave
blank

028

*L3035*
INPUT DEVICE

Leave
blank

*L3029*

Not
Used

Leave
blank

*L3036*
INPUT DEVICE

Leave
blank

Not
Used

*L3037*

Leave
blank

Leave
blank

Not
Used

Leave
blank

031

*L3038*
INPUT DEVICE

Leave
blank

*L3032*
INPUT DEVICE

032

Not
Used

*L3039*
INPUT DEVICE

Leave
blank

Not
Used

*L3044*
INPUT DEVICE

Leave
blank

Not
Used

*L3045*

Leave
blank

Not
Used

*L3046*
INPUT DEVICE

Leave
blank

Not
Used

*L3047*
INPUT DEVICE

Leave
blank

Leave
blank

*L3048*
INPUT DEVICE

Leave
blank

047

Not
Used

*L3040*
INPUT DEVICE

Leave
blank

040

Protec Fire Detection plc

Leave
blank

046

039

Not
Used

*L3043*
INPUT DEVICE

INPUT DEVICE

038

*L3031*
INPUT DEVICE

Not
Used

045

INPUT DEVICE

030

Not
Used

Leave
blank

INPUT DEVICE

037

*L3030*

*L3042*
INPUT DEVICE

044

INPUT DEVICE

029

Not
Used

Not
Used

043

036

Not
Used

Leave
blank

042

035

Not
Used

*L3041*
INPUT DEVICE

041

034

Not
Used

Address Serial No
Not
Used

Not
Used

048

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 3 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L3049*
INPUT DEVICE

Add
Leave
blank

049

Address Serial No
Not
Used

*L3057*
INPUT DEVICE

Add
Leave
blank

057

Not
Used

*L3050*
INPUT DEVICE

Leave
blank

050

*L3051*
INPUT DEVICE

Not
Used

Leave
blank

051

*L3058*
INPUT DEVICE

Leave
blank

*L3052*
INPUT DEVICE

Not
Used

Leave
blank

052

*L3059*
INPUT DEVICE

Leave
blank

*L3053*

Not
Used

Leave
blank

*L3060*
INPUT DEVICE

Leave
blank

Not
Used

*L3061*

Leave
blank

Leave
blank

Not
Used

Leave
blank

055

*L3062*
INPUT DEVICE

Leave
blank

*L3056*
INPUT DEVICE

056

Not
Used

*L3063*
INPUT DEVICE

Leave
blank

Not
Used

*L3068*
INPUT DEVICE

Leave
blank

Not
Used

*L3069*

Leave
blank

Not
Used

*L3070*
INPUT DEVICE

Leave
blank

Not
Used

*L3071*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L3072*
INPUT DEVICE

Leave
blank

071

Not
Used

*L3064*
INPUT DEVICE

Leave
blank

064

Protec Fire Detection plc

Leave
blank

070

063

Not
Used

*L3067*
INPUT DEVICE

INPUT DEVICE

062

*L3055*
INPUT DEVICE

Not
Used

069

INPUT DEVICE

054

Not
Used

Leave
blank

INPUT DEVICE

061

*L3054*

*L3066*
INPUT DEVICE

068

INPUT DEVICE

053

Not
Used

Not
Used

067

060

Not
Used

Leave
blank

066

059

Not
Used

*L3065*
INPUT DEVICE

065

058

Not
Used

Address Serial No
Not
Used

072

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 3 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L3073*
INPUT DEVICE

Add
Leave
blank

073

Address Serial No
Not
Used

*L3081*
INPUT DEVICE

Add
Leave
blank

081

Not
Used

*L3074*
INPUT DEVICE

Leave
blank

074

*L3075*
INPUT DEVICE

Not
Used

Leave
blank

075

*L3082*
INPUT DEVICE

Leave
blank

*L3076*
INPUT DEVICE

Not
Used

Leave
blank

076

*L3083*
INPUT DEVICE

Leave
blank

*L3077*

Not
Used

Leave
blank

*L3084*
INPUT DEVICE

Leave
blank

Not
Used

*L3085*

Leave
blank

Leave
blank

Not
Used

Leave
blank

079

*L3086*
INPUT DEVICE

Leave
blank

*L3080*
INPUT DEVICE

080

Not
Used

*L3087*
INPUT DEVICE

Leave
blank

Not
Used

*L3092*
INPUT DEVICE

Leave
blank

Not
Used

*L3093*

Leave
blank

Not
Used

*L3094*
INPUT DEVICE

Leave
blank

Not
Used

*L3095*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L3096*
INPUT DEVICE

Leave
blank

095

Not
Used

*L3088*
INPUT DEVICE

Leave
blank

088

Protec Fire Detection plc

Leave
blank

094

087

Not
Used

*L3091*
INPUT DEVICE

INPUT DEVICE

086

*L3079*
INPUT DEVICE

Not
Used

093

INPUT DEVICE

078

Not
Used

Leave
blank

INPUT DEVICE

085

*L3078*

*L3090*
INPUT DEVICE

092

INPUT DEVICE

077

Not
Used

Not
Used

091

084

Not
Used

Leave
blank

090

083

Not
Used

*L3089*
INPUT DEVICE

089

082

Not
Used

Address Serial No
Not
Used

096

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 3 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L3097*
INPUT DEVICE

Add
Leave
blank

097

Address Serial No
Not
Used

*L3105*
INPUT DEVICE

Add
Leave
blank

105

Not
Used

*L3098*
INPUT DEVICE

Leave
blank

098

*L3099*
INPUT DEVICE

Not
Used

Leave
blank

099

*L3106*
INPUT DEVICE

Leave
blank

*L3100*
INPUT DEVICE

Not
Used

Leave
blank

100

*L3107*
INPUT DEVICE

Leave
blank

*L3101*

Not
Used

INPUT DEVICE

*L3108*
INPUT DEVICE

Leave
blank

*L3109*

Leave
blank

INPUT DEVICE

*L3110*
INPUT DEVICE

Leave
blank

110

*L3103*
INPUT DEVICE

*L3111*
INPUT DEVICE

Leave
blank

111

*L3104*
INPUT DEVICE

104

Not
Used

*L3116*
INPUT DEVICE

Leave
blank

Not
Used

*L3117*

Leave
blank

Not
Used

*L3118*
INPUT DEVICE

Leave
blank

Not
Used

*L3119*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L3120*
INPUT DEVICE

Leave
blank

119

Not
Used

*L3112*
INPUT DEVICE

Leave
blank

112

Protec Fire Detection plc

Leave
blank

118

Not
Used

Leave
blank

103

Not
Used

*L3115*
INPUT DEVICE

117

Not
Used

Leave
blank

102

Not
Used

Not
Used

INPUT DEVICE

109

*L3102*

Leave
blank

INPUT DEVICE

101

Not
Used

*L3114*
INPUT DEVICE

116

Not
Used

Leave
blank

Not
Used

115

108

Not
Used

Leave
blank

114

107

Not
Used

*L3113*
INPUT DEVICE

113

106

Not
Used

Address Serial No
Not
Used

120

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 3 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L3121*
INPUT DEVICE

Add
Leave
blank

121

Address Serial No
Not
Used

*L3129*
INPUT DEVICE

Add
Leave
blank

129

Not
Used

*L3122*
INPUT DEVICE

Leave
blank

122

*L3123*
INPUT DEVICE

Not
Used

Leave
blank

123

*L3130*
INPUT DEVICE

Leave
blank

*L3124*
INPUT DEVICE

Not
Used

Leave
blank

124

*L3131*
INPUT DEVICE

Leave
blank

*L3125*

Not
Used

INPUT DEVICE

*L3132*
INPUT DEVICE

Leave
blank

*L3133*

Leave
blank

INPUT DEVICE

*L3134*
INPUT DEVICE

Leave
blank

134

*L3127*
INPUT DEVICE

*L3135*
INPUT DEVICE

Leave
blank

135

*L3128*
INPUT DEVICE

128

Not
Used

*L3140*
INPUT DEVICE

Leave
blank

Not
Used

*L3141*

Leave
blank

Not
Used

*L3142*
INPUT DEVICE

Leave
blank

Not
Used

*L3143*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L3144*
INPUT DEVICE

Leave
blank

143

Not
Used

*L3136*
INPUT DEVICE

Leave
blank

136

Protec Fire Detection plc

Leave
blank

142

Not
Used

Leave
blank

127

Not
Used

*L3139*
INPUT DEVICE

141

Not
Used

Leave
blank

126

Not
Used

Not
Used

INPUT DEVICE

133

*L3126*

Leave
blank

INPUT DEVICE

125

Not
Used

*L3138*
INPUT DEVICE

140

Not
Used

Leave
blank

Not
Used

139

132

Not
Used

Leave
blank

138

131

Not
Used

*L3137*
INPUT DEVICE

137

130

Not
Used

Address Serial No
Not
Used

144

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 3 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L3145*
INPUT DEVICE

Add
Leave
blank

145

Address Serial No
Not
Used

*L3153*
INPUT DEVICE

Add
Leave
blank

153

Not
Used

*L3146*
INPUT DEVICE

Leave
blank

146

*L3147*
INPUT DEVICE

Not
Used

Leave
blank

147

*L3154*
INPUT DEVICE

Leave
blank

*L3148*
INPUT DEVICE

Not
Used

Leave
blank

148

*L3155*
INPUT DEVICE

Leave
blank

*L3149*

Not
Used

INPUT DEVICE

*L3156*
INPUT DEVICE

Leave
blank

*L3157*

Leave
blank

INPUT DEVICE

*L3158*
INPUT DEVICE

Leave
blank

158

*L3151*
INPUT DEVICE

*L3159*
INPUT DEVICE

Leave
blank

159

*L3152*
INPUT DEVICE

152

Not
Used

*L3164*
INPUT DEVICE

Leave
blank

Not
Used

*L3165*

Leave
blank

Not
Used

*L3166*
INPUT DEVICE

Leave
blank

Not
Used

*L3167*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L3168*
INPUT DEVICE

Leave
blank

167

Not
Used

*L3160*
INPUT DEVICE

Leave
blank

160

Protec Fire Detection plc

Leave
blank

166

Not
Used

Leave
blank

151

Not
Used

*L3163*
INPUT DEVICE

165

Not
Used

Leave
blank

150

Not
Used

Not
Used

INPUT DEVICE

157

*L3150*

Leave
blank

INPUT DEVICE

149

Not
Used

*L3162*
INPUT DEVICE

164

Not
Used

Leave
blank

Not
Used

163

156

Not
Used

Leave
blank

162

155

Not
Used

*L3161*
INPUT DEVICE

161

154

Not
Used

Address Serial No
Not
Used

168

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 3 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L3169*
INPUT DEVICE

Add
Leave
blank

169

Address Serial No
Not
Used

*L3177*
INPUT DEVICE

Add
Leave
blank

177

Not
Used

*L3170*
INPUT DEVICE

Leave
blank

170

*L3171*
INPUT DEVICE

Not
Used

Leave
blank

171

*L3178*
INPUT DEVICE

Leave
blank

*L3172*
INPUT DEVICE

Not
Used

Leave
blank

172

*L3179*
INPUT DEVICE

Leave
blank

*L3173*

Not
Used

INPUT DEVICE

*L3180*
INPUT DEVICE

Leave
blank

*L3181*

Leave
blank

INPUT DEVICE

*L3182*
INPUT DEVICE

Leave
blank

182

*L3175*
INPUT DEVICE

*L3183*
INPUT DEVICE

Leave
blank

183

*L3176*
INPUT DEVICE

176

Leave
blank

Not
Used

*L3188*
INPUT DEVICE

Leave
blank

Not
Used

*L3189*

Leave
blank

Not
Used

*L3190*
INPUT DEVICE

Leave
blank

Not
Used

*L3191*
INPUT DEVICE

Leave
blank

190

Not
Used

Leave
blank

175

Not
Used

*L3187*
INPUT DEVICE

189

Not
Used

Leave
blank

174

Not
Used

Not
Used

INPUT DEVICE

181

*L3174*

Leave
blank

INPUT DEVICE

173

Not
Used

*L3186*
INPUT DEVICE

188

Not
Used

Leave
blank

Not
Used

187

180

Not
Used

Leave
blank

186

179

Not
Used

*L3185*
INPUT DEVICE

185

178

Not
Used

Address Serial No
Not
Used

Leave
blank

191

Not
Used

*L3184*
INPUT DEVICE

Leave
blank

184

Protec Fire Detection plc

6300 Loop Commissioning Manual

93-507-07 Issue 2

LOOP 4 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L4001*
INPUT DEVICE

Add
Leave
blank

001

Address Serial No
Not
Used

*L4009*
INPUT DEVICE

Add
Leave
blank

009

Not
Used

*L4002*
INPUT DEVICE

Leave
blank

002

*L4003*
INPUT DEVICE

Not
Used

Leave
blank

003

*L4010*
INPUT DEVICE

Leave
blank

*L4004*
INPUT DEVICE

Not
Used

Leave
blank

004

*L4011*
INPUT DEVICE

Leave
blank

*L4005*

Not
Used

INPUT DEVICE

*L4012*
INPUT DEVICE

Leave
blank

*L4013*

Leave
blank

INPUT DEVICE

*L4014*
INPUT DEVICE

Leave
blank

014

*L4007*
INPUT DEVICE

*L4015*
INPUT DEVICE

Leave
blank

015

*L4008*
INPUT DEVICE

008

Not
Used

*L4020*
INPUT DEVICE

Leave
blank

Not
Used

*L4021*

Leave
blank

Not
Used

*L4022*
INPUT DEVICE

Leave
blank

Not
Used

*L4023*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L4024*
INPUT DEVICE

Leave
blank

023

Not
Used

*L4016*
INPUT DEVICE

Leave
blank

016

Protec Fire Detecion plc

Leave
blank

022

Not
Used

Leave
blank

007

Not
Used

*L4019*
INPUT DEVICE

021

Not
Used

Leave
blank

006

Not
Used

Not
Used

INPUT DEVICE

013

*L4006*

Leave
blank

INPUT DEVICE

005

Not
Used

*L4018*
INPUT DEVICE

020

Not
Used

Leave
blank

Not
Used

019

012

Not
Used

Leave
blank

018

011

Not
Used

*L4017*
INPUT DEVICE

017

010

Not
Used

Address Serial No
Not
Used

024

6300 Loop Commissioning Manaul

93-507-07 Issue 2

LOOP 4 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L4025*
INPUT DEVICE

Add
Leave
blank

025

Address Serial No
Not
Used

*L4033*
INPUT DEVICE

Add
Leave
blank

033

Not
Used

*L4026*
INPUT DEVICE

Leave
blank

026

*L4027*
INPUT DEVICE

Not
Used

Leave
blank

027

*L4034*
INPUT DEVICE

Leave
blank

*L4028*
INPUT DEVICE

Not
Used

Leave
blank

028

*L4035*
INPUT DEVICE

Leave
blank

*L4029*

Not
Used

INPUT DEVICE

*L4036*
INPUT DEVICE

Leave
blank

*L4037*

Leave
blank

INPUT DEVICE

*L4038*
INPUT DEVICE

Leave
blank

038

*L4031*
INPUT DEVICE

*L4039*
INPUT DEVICE

Leave
blank

039

*L4032*
INPUT DEVICE

032

Not
Used

*L4044*
INPUT DEVICE

Leave
blank

Not
Used

*L4045*

Leave
blank

Not
Used

*L4046*
INPUT DEVICE

Leave
blank

Not
Used

*L4047*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L4048*
INPUT DEVICE

Leave
blank

047

Not
Used

*L4040*
INPUT DEVICE

Leave
blank

040

Protec Fire Detecion plc

Leave
blank

046

Not
Used

Leave
blank

031

Not
Used

*L4043*
INPUT DEVICE

045

Not
Used

Leave
blank

030

Not
Used

Not
Used

INPUT DEVICE

037

*L4030*

Leave
blank

INPUT DEVICE

029

Not
Used

*L4042*
INPUT DEVICE

044

Not
Used

Leave
blank

Not
Used

043

036

Not
Used

Leave
blank

042

035

Not
Used

*L4041*
INPUT DEVICE

041

034

Not
Used

Address Serial No
Not
Used

048

6300 Loop Commissioning Manaul

93-507-07 Issue 2

LOOP 4 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L4049*
INPUT DEVICE

Add
Leave
blank

049

Address Serial No
Not
Used

*L4057*
INPUT DEVICE

Add
Leave
blank

057

Not
Used

*L4050*
INPUT DEVICE

Leave
blank

050

*L4051*
INPUT DEVICE

Not
Used

Leave
blank

051

*L4058*
INPUT DEVICE

Leave
blank

*L4052*
INPUT DEVICE

Not
Used

Leave
blank

052

*L4059*
INPUT DEVICE

Leave
blank

*L4053*

Not
Used

INPUT DEVICE

*L4060*
INPUT DEVICE

Leave
blank

*L4061*

Leave
blank

INPUT DEVICE

*L4062*
INPUT DEVICE

Leave
blank

062

*L4055*
INPUT DEVICE

*L4063*
INPUT DEVICE

Leave
blank

063

*L4056*
INPUT DEVICE

056

Not
Used

*L4068*
INPUT DEVICE

Leave
blank

Not
Used

*L4069*

Leave
blank

Not
Used

*L4070*
INPUT DEVICE

Leave
blank

Not
Used

*L4071*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L4072*
INPUT DEVICE

Leave
blank

071

Not
Used

*L4064*
INPUT DEVICE

Leave
blank

064

Protec Fire Detecion plc

Leave
blank

070

Not
Used

Leave
blank

055

Not
Used

*L4067*
INPUT DEVICE

069

Not
Used

Leave
blank

054

Not
Used

Not
Used

INPUT DEVICE

061

*L4054*

Leave
blank

INPUT DEVICE

053

Not
Used

*L4066*
INPUT DEVICE

068

Not
Used

Leave
blank

Not
Used

067

060

Not
Used

Leave
blank

066

059

Not
Used

*L4065*
INPUT DEVICE

065

058

Not
Used

Address Serial No
Not
Used

072

6300 Loop Commissioning Manaul

93-507-07 Issue 2

LOOP 4 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L4073*
INPUT DEVICE

Add
Leave
blank

073

Address Serial No
Not
Used

*L4081*
INPUT DEVICE

Add
Leave
blank

081

Not
Used

*L4074*
INPUT DEVICE

Leave
blank

074

*L4075*
INPUT DEVICE

Not
Used

Leave
blank

075

*L4082*
INPUT DEVICE

Leave
blank

*L4076*
INPUT DEVICE

Not
Used

Leave
blank

076

*L4083*
INPUT DEVICE

Leave
blank

*L4077*

Not
Used

INPUT DEVICE

*L4084*
INPUT DEVICE

Leave
blank

*L4085*

Leave
blank

INPUT DEVICE

*L4086*
INPUT DEVICE

Leave
blank

086

*L4079*
INPUT DEVICE

*L4087*
INPUT DEVICE

Leave
blank

087

*L4080*
INPUT DEVICE

080

Not
Used

*L4092*
INPUT DEVICE

Leave
blank

Not
Used

*L4093*

Leave
blank

Not
Used

*L4094*
INPUT DEVICE

Leave
blank

Not
Used

*L4095*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L4096*
INPUT DEVICE

Leave
blank

095

Not
Used

*L4088*
INPUT DEVICE

Leave
blank

088

Protec Fire Detecion plc

Leave
blank

094

Not
Used

Leave
blank

079

Not
Used

*L4091*
INPUT DEVICE

093

Not
Used

Leave
blank

078

Not
Used

Not
Used

INPUT DEVICE

085

*L4078*

Leave
blank

INPUT DEVICE

077

Not
Used

*L4090*
INPUT DEVICE

092

Not
Used

Leave
blank

Not
Used

091

084

Not
Used

Leave
blank

090

083

Not
Used

*L4089*
INPUT DEVICE

089

082

Not
Used

Address Serial No
Not
Used

096

6300 Loop Commissioning Manaul

93-507-07 Issue 2

LOOP 4 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L4097*
INPUT DEVICE

Add
Leave
blank

097

Address Serial No
Not
Used

*L4105*
INPUT DEVICE

Add
Leave
blank

105

Not
Used

*L4098*
INPUT DEVICE

Leave
blank

098

*L4099*
INPUT DEVICE

Not
Used

Leave
blank

099

*L4106*
INPUT DEVICE

Leave
blank

*L4100*
INPUT DEVICE

Not
Used

Leave
blank

100

*L4107*
INPUT DEVICE

Leave
blank

*L4101*

Not
Used

INPUT DEVICE

*L4108*
INPUT DEVICE

Leave
blank

*L4109*

Leave
blank

INPUT DEVICE

*L4110*
INPUT DEVICE

Leave
blank

110

*L4103*
INPUT DEVICE

*L4111*
INPUT DEVICE

Leave
blank

111

*L4104*
INPUT DEVICE

104

Not
Used

*L4116*
INPUT DEVICE

Leave
blank

Not
Used

*L4117*

Leave
blank

Not
Used

*L4118*
INPUT DEVICE

Leave
blank

Not
Used

*L4119*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L4120*
INPUT DEVICE

Leave
blank

119

Not
Used

*L4112*
INPUT DEVICE

Leave
blank

112

Protec Fire Detecion plc

Leave
blank

118

Not
Used

Leave
blank

103

Not
Used

*L4115*
INPUT DEVICE

117

Not
Used

Leave
blank

102

Not
Used

Not
Used

INPUT DEVICE

109

*L4102*

Leave
blank

INPUT DEVICE

101

Not
Used

*L4114*
INPUT DEVICE

116

Not
Used

Leave
blank

Not
Used

115

108

Not
Used

Leave
blank

114

107

Not
Used

*L4113*
INPUT DEVICE

113

106

Not
Used

Address Serial No
Not
Used

120

6300 Loop Commissioning Manaul

93-507-07 Issue 2

LOOP 4 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L4121*
INPUT DEVICE

Add
Leave
blank

121

Address Serial No
Not
Used

*L4129*
INPUT DEVICE

Add
Leave
blank

129

Not
Used

*L4122*
INPUT DEVICE

Leave
blank

122

*L4123*
INPUT DEVICE

Not
Used

Leave
blank

123

*L4130*
INPUT DEVICE

Leave
blank

*L4124*
INPUT DEVICE

Not
Used

Leave
blank

124

*L4131*
INPUT DEVICE

Leave
blank

*L4125*

Not
Used

INPUT DEVICE

*L4132*
INPUT DEVICE

Leave
blank

*L4133*

Leave
blank

INPUT DEVICE

*L4134*
INPUT DEVICE

Leave
blank

134

*L4127*
INPUT DEVICE

*L4135*
INPUT DEVICE

Leave
blank

135

*L4128*
INPUT DEVICE

128

Not
Used

*L4140*
INPUT DEVICE

Leave
blank

Not
Used

*L4141*

Leave
blank

Not
Used

*L4142*
INPUT DEVICE

Leave
blank

Not
Used

*L4143*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L4144*
INPUT DEVICE

Leave
blank

143

Not
Used

*L4136*
INPUT DEVICE

Leave
blank

136

Protec Fire Detecion plc

Leave
blank

142

Not
Used

Leave
blank

127

Not
Used

*L4139*
INPUT DEVICE

141

Not
Used

Leave
blank

126

Not
Used

Not
Used

INPUT DEVICE

133

*L4126*

Leave
blank

INPUT DEVICE

125

Not
Used

*L4138*
INPUT DEVICE

140

Not
Used

Leave
blank

Not
Used

139

132

Not
Used

Leave
blank

138

131

Not
Used

*L4137*
INPUT DEVICE

137

130

Not
Used

Address Serial No
Not
Used

144

6300 Loop Commissioning Manaul

93-507-07 Issue 2

LOOP 4 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L4145*
INPUT DEVICE

Add
Leave
blank

145

Address Serial No
Not
Used

*L4153*
INPUT DEVICE

Add
Leave
blank

153

Not
Used

*L4146*
INPUT DEVICE

Leave
blank

146

*L4147*
INPUT DEVICE

Not
Used

Leave
blank

147

*L4154*
INPUT DEVICE

Leave
blank

*L4148*
INPUT DEVICE

Not
Used

Leave
blank

148

*L4155*
INPUT DEVICE

Leave
blank

*L4149*

Not
Used

INPUT DEVICE

*L4156*
INPUT DEVICE

Leave
blank

*L4157*

Leave
blank

INPUT DEVICE

*L4158*
INPUT DEVICE

Leave
blank

158

*L4151*
INPUT DEVICE

*L4159*
INPUT DEVICE

Leave
blank

159

*L4152*
INPUT DEVICE

152

Not
Used

*L4164*
INPUT DEVICE

Leave
blank

Not
Used

*L4165*

Leave
blank

Not
Used

*L4166*
INPUT DEVICE

Leave
blank

Not
Used

*L4167*
INPUT DEVICE

Leave
blank

Leave
blank

Not
Used

*L4168*
INPUT DEVICE

Leave
blank

167

Not
Used

*L4160*
INPUT DEVICE

Leave
blank

160

Protec Fire Detecion plc

Leave
blank

166

Not
Used

Leave
blank

151

Not
Used

*L4163*
INPUT DEVICE

165

Not
Used

Leave
blank

150

Not
Used

Not
Used

INPUT DEVICE

157

*L4150*

Leave
blank

INPUT DEVICE

149

Not
Used

*L4162*
INPUT DEVICE

164

Not
Used

Leave
blank

Not
Used

163

156

Not
Used

Leave
blank

162

155

Not
Used

*L4161*
INPUT DEVICE

161

154

Not
Used

Address Serial No
Not
Used

168

6300 Loop Commissioning Manaul

93-507-07 Issue 2

LOOP 4 of 4
Add

6300 Loop Commissioning Manual

Address Serial No
Not
Used

*L4169*
INPUT DEVICE

Add
Leave
blank

169

Address Serial No
Not
Used

*L4177*
INPUT DEVICE

Add
Leave
blank

177

Not
Used

*L4170*
INPUT DEVICE

Leave
blank

170

*L4171*
INPUT DEVICE

Not
Used

Leave
blank

171

*L4178*
INPUT DEVICE

Leave
blank

*L4172*
INPUT DEVICE

Not
Used

Leave
blank

172

*L4179*
INPUT DEVICE

Leave
blank

*L4173*

Not
Used

INPUT DEVICE

*L4180*
INPUT DEVICE

Leave
blank

*L4181*

Leave
blank

INPUT DEVICE

*L4182*
INPUT DEVICE

Leave
blank

182

*L4175*
INPUT DEVICE

*L4183*
INPUT DEVICE

Leave
blank

183

*L4176*
INPUT DEVICE

176

Leave
blank

Not
Used

*L4188*
INPUT DEVICE

Leave
blank

Not
Used

*L4189*

Leave
blank

Not
Used

*L4190*
INPUT DEVICE

Leave
blank

Not
Used

*L4191*
INPUT DEVICE

Leave
blank

190

Not
Used

Leave
blank

175

Not
Used

*L4187*
INPUT DEVICE

189

Not
Used

Leave
blank

174

Not
Used

Not
Used

INPUT DEVICE

181

*L4174*

Leave
blank

INPUT DEVICE

173

Not
Used

*L4186*
INPUT DEVICE

188

Not
Used

Leave
blank

Not
Used

187

180

Not
Used

Leave
blank

186

179

Not
Used

*L4185*
INPUT DEVICE

185

178

Not
Used

Address Serial No
Not
Used

Leave
blank

191

Not
Used

*L4184*
INPUT DEVICE

Leave
blank

184

Protec Fire Detecion plc

6300 Loop Commissioning Manaul

93-507-07 Issue 2

Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT.
Telephone:
Fax:
Web:
Email:

+44 (0) 1282 717171


+44 (0) 1282 717273
www.protec.co.uk
sales@protec.co.uk

N 93-572-88 ISSUE 0 NH

Page 2 of 2

Protec Fire Detection PLC 2012