Sunteți pe pagina 1din 47

Cuprins

INTRODUCERE..............................................................................................................................3
1. PRELUCRAREA CURBELOR DE SARCIN...........................................................................5
1.1 Construirea curbelor de sarcin zilnice (de iarn i de var ) n unit i absolute (P, S). ..............5
1.2 Calculul indicatorilor curbei de sarcin anual..............................................................................7

2. ELABORAREA VARIANTELOR SCHEMEI DE PRINCIPIU A STAIEI ELECTRICE.....8


2.1 Elaborarea a 2 variante a schemei de principiu (reduse)................................................................8
2.2 Alegerea generatorului......................................................................................................................8
2.3 Determinarea puterii nominale a transformatoarelor de legtur.................................................8

3. COMPARAREA TEHNICO-ECONOMIC A VARIANTELOR.............................................11


4. CALCULUL CURENILOR DE SCURTCIRCUIT TRIFAZAT.............................................16
4.1 ntocmirea schemei echivalente i calculul reactan elor elementelor schemei. ...........................16
4.2 Calculul curentului supratranzitoriu de s.c. Ip.0 n punctele stabilite...........................................25
4.3 Calculul curentului de oc, n punctele stabilite............................................................................25
4.4 Prezentarea rezultatelor calculului curenilor de s.c. sub form de tabel....................................26

5. ALEGEREA CONDUCTOARELOR I APARATELOR DE COMUTAIE...........................27


5.1 Alegerea ntreruptoarelor i separatoarelor...................................................................................27
5.2 Alegerea barelor colectoare, seciunilor conductoarelor...............................................................35

6. ALEGEREA TRANSFORMATOARELOR DE MSUR.......................................................39


6.1 Alegerea aparatelor de msur n circuitele tip ale centralei electrice.........................................39
6.2 Alegerea transformatorului de curent............................................................................................40
6.3 Alegerea transformatorului de tensiune.........................................................................................42

7. ELABORAREA SCHEMELOR DE CONEXIUNE ALE INSTALA IILOR ELECTRICE . .43


7.1 Justificarea i alegerea schemelor de conexiune la tensiunile superioar i inferioar ...............43
7.2 Alegerea schemei de conexiune i transformatoarelor pentru alimentarea serviciilor proprii din
centrala electric....................................................................................................................................45

CONCLUZII...................................................................................................................................47
BIBLIOGRAFIE............................................................................................................................48

Mod Coala Nr. Document

Semnt.

Data

Coala

INTRODUCERE
Energia reprezint factorul motor al dezvoltrii economico-sociale a omenirii. n
special energia electric este impulsul principal n progresul tehnico-economic. Fr
energie electric, nivelul actual al civilizaiei nu poate fi imaginat.
Ansamblul de instalaii utilizate pentru producerea, conversia, transformarea,
transportul i distribuia energiei electrice legate printr-un proces comun de funcionare
poart denumirea de sistem electroenergetic. Sistemul electroenergetic este parte
component a sistemului energetic a unei ri i se consider ramur principal a
economiei naionale. n prezenta lucrare de curs se v-a proiecta o central electric cu
puterea de 48 MW. Aceast central electric este destinat pentru producerea energiei
electrice i debitarea ei n sistemul electroenergetic prin intermediul liniilor de transport i
distribuie i liniilor care alimenteaz consumatorii locali a centralei.
Fiabilitatea funcionrii reelei electrice precum i a centralelor electrice depinde de
schema de conexiune i de numrul de transformatoare. Pentru consumatori de categoria 1
se vor prevedea doua transformatoare n staiile electrice, iar pentru consumatori de
categoria 3 numai un transformator de putere. Toate transformatoarele din centrale sunt
dotate cu mijloace de reglare a tensiunii.n aceast lucrare de curs este expus conceptul
modern al calculelor tehnico-economice comparative cu adaptare la sistemele de
producere, transport i de distribuie a energiei electrice. Sunt prezentate elementele cheie
ce domin aceast problematic, indicatorii de eficien economic, metodele curente de
evaluare i analiz economic a proiectelor de investiii, criteriile de alegere a soluiilor
optime, aplicate n proiectarea centralelor electrice cu termoficare. Varianta final de
implementare a CET se va alege n urma efecturii calculului tehnico-economic. n
lucrarea dat vor fi examinate doar dou regimuri de funcionare: regimul permanent de
funcionare i regimul de postavarie (sau permanent de dup avarie).n timpul funcionrii
sistemelor electroenergetice i a sistemelor de alimentare cu energie electric a
ntreprinderilor au loc diferite perturbaii ale regimurilor, spre exemplu: varierea sarcinii,
conectarea i deconectarea diferitor surse i sarcini, scurtcircuite, ruperea conductoarelor
liniilor electrice, efectuarea testrilor i multe alte situaii de avarie. Aceste situaii,
enumerate anterior, n cele din urm aduc la modificarea strii electromagnetice a
elementelor sistemului i la modificarea vitezelor de rotaie a generatoarelor, ca rezultat a

Mod Coala Nr. Document

Semnt.

Data

Coala

unui dezechilibru ntre cuplurile mecanice i electromagnetice ale tuturor generatoarelor


conectate la sistemul electroenergetic.
Mainile i aparatele electrice, liniile de transport a energiei electrice i alte pri ale
instalaiilor electrice i reele electrice tot timpul sunt sub tensiune i sunt parcurse de
curentul ce provoac nclzire lor. De aceea n procesul de exploatare poate s apar
distrugeri care duc la apariia scurtcircuitelor.
n multitudinea de cazuri n locul de s.c. apare arcul electric cu temperatur nalt,
care duce la distrugerea izolaiilor, aparatelor electrice i a altele. La punctul de s.c. apare
cureni mari de mii de amperi care supranclzesc elementele de transport a energiei
electrice ne defectate, i poate s aduc la distrugeri complementare, deci la avarie. Tot
odat n reea legat cu locul de avarie apare scderea tensiunii, ce poate s aduc la
oprirea motoarelor i la ieire din sincronism a generatoarelor.
Proiectarea i exploatarea centralelor electrice are la baz principalele cerine de ordin
general: siguran n alimentarea consumatorilor, calitatea energiei electrice i soluia
tehnico-economic optim. Un rol important n sistemul electroenergetic (SEE) l joac
reelele elctrice de transport i staiile electrice menite transportului, transformrii i
distribuiei energiei electrice.
Deasemenea un rol foarte important l joac centralele electrice pot fi clasificate n:
- centrale termoelectrice cu condensare (CTE);
- centrale electrice cu termoficare(CET);
- centrale nucleare electrice (CNE);
- centrale hidroelectrice(CHE);
- centrale hidroelectrice cu acumulare i pompaj de ap(CHAP);
Toate centralele electrice se unesc ntrun sistem electroenergetic unic lucrnd n
paralel. Funcionarea lor n paralel prezint urmtoarele avantaje tehnico-economice:
- ridicarea fiabilitii i a siguranei n alimentare a consumatorilor de energie
electric;
- permite optimizarea producerii energiei electrice i utilizarea raional a
combustibilului;
- micorarea pierderilor de putere i energie;
- permite meninerea calitii energiei electric

Mod Coala Nr. Document

Semnt.

Data

Coala

1. PRELUCRAREA CURBELOR DE SARCIN


1.1 Construirea curbelor de sarcin zilnice (de iarn i de var ) n uniti absolute (P,
S).
Curba de sarcin este evoluia sarcinii n timp. Curbele de sarcin se folosesc pentru:
determinarea puterilor maxime, puterile de calcul n proiectarea instalaiilor
electrice pentru determinarea pierderilor de putere i de energie;
-

pentru determinarea puterilor instalate ale centralelor electrice;

pentru calculul cantitilor de energie electric produs sau consumat;

pentru determinarea cantitilor de combustibil;

pentru planificarea reparaiilor echipamentului, etc.

Se prelucreaz curba de sarcin zilnic de iarn i de var (sarcina pentru ziua de var
constituie 80% din valoarea sarcinii de iarn) datele fiind introduse n tabelul de mai jos i
se construiete curba pentru o zi de iarna si de vara:
Tabelul 1.
t, ore

0-6

6-9

9-13

13-15

15-18

18-22

22-24

P10 kV, %

50

65

90

85

100

90

70

PMWi, 10kV

40

52

72

68

80

72

56

PMWv, 10kV

32

41,6

57,6

54,4

64

57,6

44,8

Fig.1.Curbele de sarcin pentru o zi de iarna si de vara.

Mod Coala Nr. Document

Semnt.

Data

Coala

Lund n consideraie c durata perioadei de iarn const din 183 zile, iar durata
perioadei de var - 182 zile, se construiesc graficele anuale ale curbelor de sarcin.
Graficele snt prezentate n fig.2.
-

Pentru partea de tensiune inferioar:

P1=80 MW,

T1= ti t1 =1833=549 h;

P2=72 MW,

T2= ti t2 =1834=732 h;

P3=72 MW,

T3= ti t3 =1834=732 h;

P4=68 MW,

T4= ti t4 =1832=366 h;

P5=64 MW,

T5= tv t5 =1823=546 h;

P6=57,6 MW,

T6= tv t6 =1824=728 h;

P7=57,6 MW,

T7= tv t7 =1824=728 h;

P8=56 MW,

T8= ti t8 =1832=366 h;

P9=54,4 MW,

T9= tv t9 =1822=364 h;

P10=52 MW,

T10= ti t10 =1833=549 h;

P11=44,8 MW, T11= tv t11 =1822=364 h;


P12=41,6 MW, T12= tv t12 =1823=546 h;
P13=40 MW,

T13= ti t13 =1836=1098 h;

P14=32 MW,

T14= tv t14 =1826=1092 h;

Tan=T1+T2+T3+T4+T5+T6+T7+T8+T9+T10+T11+T12+T13+T14 =549+732+732+
+366+546 + 728+728+366+ 364+549+364+546+1098+1092=8760 h.

Fig.2.Graficul curbei de sarcin anual.


Mod Coala Nr. Document

Semnt.

Data

Coala

1.2 Calculul indicatorilor curbei de sarcin anual.


Energia anual consumat:
Wa Pi Ti P1
T1 P2 T2 P3 T3 P
T6 P7 T
7
P8 T8 P9 T9
4 T4 P5T5 P6
P10 T10 P11
T11 P12 T12

P13 T13 P14


T14 80 549 72 732 72 732 68 366

64 546 57, 6 728 57, 6 728

56
366
54,
4 364
52 549 44,8
364 41, 6
546 40 1098 32 1092

481513MW h;

Puterea maxim: Pmax 80 MW , din graficul anual a curbei de sarcin (Fig.3);


Timpul de utilizare a puterii maximale:
Tmax

Wa
481513

6018,9 h;
Pmax
80

Puterea medie:
Pmed

Wa 481513

54,967 MW ;
Tan
8760

Coeficientul de umplere al curbei de sarcin:


K ump

Pmed 54,967

0, 687;
Pmax
80

Timpul de utilizare a pierderilor maximale:


max

T
0,124 max4 8760
10

Mod Coala Nr. Document

Semnt.

Data

6018,9

0,124

104

8760 4615, 786 h;

Coala

2. ELABORAREA VARIANTELOR SCHEMEI DE PRINCIPIU A STAIEI


ELECTRICE.
2.1 Elaborarea a 2 variante a schemei de principiu (reduse).
Schema structural a CET depinde de urmtorii factori: puterea unitar i puterea
total a generatoarelor, raportul dintre puterea centralei i puterea consumatorilor locali.
Deoarece se schimb doar puterea unitar a transformatoarelor se alege urmtoarea
schem structural a CET, prezentat n fig.3.

Fig. 3. Varianta schemei centralei.


n continuare se vor alege generatoarele i transformatoarele schemelor centralei
electrice
2.2 Alegerea generatorului.
Cunoscnd puterea total a centralei electrice PCTE 80 MW i numrul generatoarelor 4, se determin puterea unui generator PnG 20 MW .Generatoarele se racordeaz la
instalaia de distribuie la tensiunea de producere ID-10 kV.
Deci,din [2]tab.2.1 se alege turbogeneratorul tip T-20-2 cu urmtorii parametri
nominali:
P n 20 MW , Sn 25 MVA, cos 0,8,
U n 10.5 kV , I nom 1.375 kA, f 3000 rot / min .

2.3 Determinarea puterii nominale a transformatoarelor de legtur.


Alegerea transformatoarelor presupune determinarea tipului i puterii nominale.
Puterea nominal a transformatorului se determin din condiia:
S nomT S calc ;

unde S n este puterea nominal a transformatorului ales din catalog, MVA;


Mod Coala Nr. Document

Semnt.

Data

Coala

S calc sarcina

de calcul maximal, MVA.

Pentru asigurarea fiabilitii alimentrii cu energie electric a consumatorilor locali la


CET se instaleaz dou transformatoare de legtur,pentru micorarea fluxurilor de putere
dintre seciile ID.
Puterea transmis prin transformatoarele bloc se determin cu urmtoarea expresie:


PnomG ,i Pcl Psp

i 1

Scalc

QnomG ,i Qcl Qsp ;

i 1

unde: n este numrul de geneatoare racordate la ID-10 kV;


PnomG 20 puterea activ nominal a unui generator,MW;
Psp 80 0, 06 4,8 puterea activ a serviciilor proprii,MW;
Pcl ,min 32
Pcl ,max 80

puterea activ a consumatorilor locali,MW;

QnomG PnomG tg (arccos(0,8)) 20 0, 75 15 puterea reactiv nominal a unui

generator,Mvar;
Qsp Psp tg (arccos(0,8)) 4,8 0, 75 3, 6 puterea reactiv a serviciilor

proprii,Mvar;
Qcl ,min Pcl ,min tg (arccos(0,8)) 32 0, 75 24

puterea reactiv a consumatorilor

Qcl ,max Pcl ,max tg (arccos(0,8)) 80 0, 75 60

locali,Mvar;
La determinarea puterii maximale tranzitate prin transformatorul de legtur se
examineaz trei regimuri de funcionare posibile:
1.Toate generatoarele funioneaz,consumatorii locali consum la maxim;
2. Toate generatoarele funioneaz,consumatorii locali consum la minim;
3.Regim de avarie.Un generator nu funioneaz,consumatorii locali consum la maxim;
Se alege autotransformatorul de legtur ATL:
1.Toate generatoarele funcioneaz,consumatorii locali consum la maxim:

S calc ,1

P
i 1

nomG ,i

Pcl ,max Psp

Q
i 1

nomG ,i

Qcl ,max Qsp ;

Deci:
Scalc ,1 4( SG Sp ) S max 4(25 1,5) 100 6 MVA;

2. Toate generatoarele funcioneaz,consumatorii locali consum la minim:

Mod Coala Nr. Document

Semnt.

Data

Coala

S calc , 2

i 1

nomG ,i

Pcl ,min Psp

i 1

nomG ,i

Qcl ,min Qsp ;

Scalc ,2 4( SG Sp ) Smin 4(25 1,5) 40 54 MVA;

3. Regim de avarie.Un generator nu funcioneaz,consumatorii locali consum la


maxim:

S calc ,3

i 1

n 1

PnomG ,i Pcl ,max Psp

QnomG ,i Qcl ,max Qsp ;

i 1

n 1

deci: Scalc ,3 3( SG Sp ) Smax 3(25 1,5) 100 30,5 MVA;


Scalc max Scalc ,1 , S calc ,2 , S calc ,3 ;
S

Scalc 54

38, 571 MVA


1, 4 1, 4

- Pentru prima variant a schemei CET:


Din [3]tab.2.7, se alege transformatorul bloc de tip T-40000/150 cu urmtorii
parametri tehnici:
U n,s 150 kV ; U n, j 10,5 kV ; Pmg 38kW
Psc 180 kW ; U sc 10.5%; I x 0.7 %
I 0,tr 79500 u.m.

- Pentru a doua variant a schemei CET:


Din [3]tab.2.7, se alege transformatorul bloc de tip T-63000/150 cu urmtorii
parametri tehnici:
U n,s 150 kV ; U n, j 10,5 kV ; Pmg 59kW
Psc 235 kW ; U sc 10.5%; I x 0.65%
I 0,tr 102000 u.m.

Mod Coala Nr. Document

Semnt.

Data

Coala

10

3. COMPARAREA TEHNICO-ECONOMIC A VARIANTELOR.


- Pentru prima variant a schemei CET:
CTA I act ,tot Cexp,act Dact WT ,act

n practica curent de proiectare a staiilor de transformare adesea toate variantele


preprezint spre comparare asigur unul i acelai grad de siguran normat n livrarea
energiei ctre consumatori i o calitate admisibil a energiei. n aceast ipotez D act poate fi
exclus.
Atunci, structura CTA pentru un obiectiv de reea cuprinde:
CTA I act ,tot Cexp,act WT ,act ,
T

I act I (1 i )t ;

unde: I act ,tot I act I ech ,act ;

I ech ,t Pt C p ;

t 0

T
su
I ech ,act I ech ,t (1 i )t I ech ,t
T 10,10% ;
t 0
T

Cexp.act Cexp (1 i )t ;
t 0

Wact W (1 i )t .

Investiia total actualizat, Iact, reprezint valoarea investiiilor totale anuale actualizate
la sfritul anului .
Investiiile totale anuale includ investiiile echevalente, determinate de pierderile
echevalente de putere, Iech, i investiiile n construcia staiei de transformare, I
I tot ,t I ech , act I t .

Investiiile n construcia staiilor de transformare cuprind costul transformatoarelor i


ntreruptoarelor (dac n ambele variante numrul ntreruptoarelor este acla i, costul lor
poate s nu fie luat n calcul)
I N tr I 0,tr 4 79500 318000 u.m.

Valoarea actualizat a investiiilor n construcia staiilor de transformare la sfritul


anului constituie:
T

I act I (1 i )t I (1 i )00 I 318000 u.m.


t 0

Investiiile echivalente anuale pot fi determinate cu relaia:


I ech Ptr C p ;

unde: Ptr reprezint pierderile de putere anuale n transformatoare.


C p costul unui kW de putere instalat la o central de referin.

Pierderile de putere n 2 transformatoare identice cu 2 nfurri care funcioneaz n


paralel, kW:
Ptr 2 Pmg

Mod Coala Nr. Document

S
1

Psc max
2
S nom
Semnt.

Data

2 38

1
54
180

2
40

240
kV

Coala

11

unde : Pmg sunt pierderile de putere la mers n gol, kW;


Psc pierderile de putere la scurtcircuit (n cuprul nfurrilor), kW;
S max sarcina de calcul (maximal) a transformatorului, MVA;
S nom sarcina nominal a transformatorului, MVA.

Dac considerm c costul unui kW de putere instalat la o central etalon egal cu


C p 1000 u.m, atunci investiiile echivalente anuale constituie :
I ech ,t Ptr C p 240 1000

240000 u.m.

Dac considerm c pierderile de putere n transformatoare nu variaz de la an la an,


atunci valoarea actualizat a investiiilor echivalente anuale la sfr itul anului constituie:
T
su
I ech ,act I ech,t (1 i )t I ech ,t
T 10,10% 240000 6,1446

1474857,

615 u.m.
t 0

n final, investiia total actualizat constituie:


I act ,tot I act I ech, act 318000 1474857, 615 1792857, 615 u.m.

Cheltuielile de expluatare actualizate, Cexp.act, reprezint valoarea cheltuielilor de


expluatare anuale actualizate la sfritul anului :
T

Cexp.act Cexp (1 i )t ;
t 0

Cheltuielile anuale de expluatare cuprind cheltuielile anuale cu pierderile de energie i


cheltuielile ntreinere i reparaii curente:
Cexp Ci.r .t Cw.t ;

Cheltuielile anuale de ntreinere i reparaii curente pot fi exprimate prin valoarea


investiiei iniiale:
Ci.r .t ki.r I 0, 018 318000 5724 u.m / an.

unde: ki.r este cota anual din valoarea investiiei pentru ntreinere i reparaii;
I investiia iniial.

Conform acestui tabel, pentru staii de transformare 150 kV, ki.r 1,8% din
valoarea investiie.
Cheltuielile anuale cu pierderile de energie se determin:
Cw.t Ptr
Cw 240 4615,

786 0,078 86416,515

u.m / an.
unde: Ptr reprezint pierderile de putere n transformatoare;
durata pierderilor maximale (determinat pentru curba anual) ;
Cw costul unui kWh energiei la o central de referin.

Dac durata pierderilor maximale este egal 4600 h/an costul unui kWh energiei
la central de referin Cw 0, 078 u.m / kWh , costul anual al pierderilor de energie
constituie :
Cexp Ci.r .t Cw.t 5724 86416,515 92140,515 u.m / an.

Dac considerm, c cheltuielile anuale de expluatare sunt constante pe durata de


studii, atunci valoarea actualizat a acestora la sfritul anului se determin :
Mod Coala Nr. Document

Semnt.

Data

Coala

12

Cexp.act Cexp (1 i )t 92140,515 6.1446 566166, 60 u.m.


t 0

Valoarea remanent actualizat (=0) se determin :


Wact W (1 i )T 159000 (1 0,1) 10 61301, 4 u.m.

unde: W reprezint remanent a echipamentului la sfritul perioadei de studiu, care se


determin cu relaia:

T
10

W 1 I 1
318000 159000 u.m.
Tsn
20

unde: T reprezint durata de studiu , T=10 ani;


Tsn durata normat de funcionare a transformatoarelor, Tsn 20 ani;
I investiia iniial.

Valoarea remanent actualizat (=0) se determin :


CTA I act ,tot Cexp,act WT ,act 1792857, 615 566166, 6 61301, 4 2297722,82 u.m.

- Pentru a doua variant a schemei CET:


Investiiile n construcia staiilor de transformare:
I N tr I 0,tr 4 102000

408000 u.m.

Valoarea actualizat a investiiilor n construcia staiilor de transformare la sfritul


anului constituie:
T

I act I (1 i )t I (1 i )00 I 408000 u.m.


t 0

Investiiile echivalente anuale pot fi determinate cu relaia:


I ech Ptr C p ;

unde: Ptr reprezint pierderile de putere anuale n transformatoare.


C p costul unui kW de putere instalat la o central de referin.

Pierderile de putere n 2 transformatoare identice cu 2 nfurri care funcioneaz n


paralel, kW:
Ptr 2 Pmg

S
1

Psc max
2
S nom

2 59

1
54
235

2
63

142.122

kV

unde : Pmg sunt pierderile de putere la mers n gol, kW;


Psc pierderile de putere la scurtcircuit (n cuprul nfurrilor), kW;
S max sarcina de calcul (maximal) a transformatorului, MVA;
S nom sarcina nominal a transformatorului, MVA.

Dac considerm c costul unui kW de putere instalat la o central etalon egal cu


C p 1000 u.m, atunci investiiile echivalente anuale constituie :
I ech ,t Ptr C p 142,122 1000

142122 u.m.

Dac considerm c pierderile de putere n transformatoare nu variaz de la an la an,


atunci valoarea actualizat a investiiilor echivalente anuale la sfr itul anului constituie:
Mod Coala Nr. Document

Semnt.

Data

Coala

13

T
su
I ech ,act I ech,t (1 i )t I ech ,t
T 10,10% 142122 6,1446

87328,

6 u.m.
t 0

n final, investiia total actualizat constituie:


I act ,tot I act I ech,act 408000 873285, 6 1281285, 6 u.m.

Cheltuielile de expluatare actualizate:


T

Cexp.act Cexp (1 i )t ;
t 0

Cheltuielile anuale de expluatare :


Cexp Ci.r .t Cw.t ;

Cheltuielile anuale de ntreinere i reparaii curente :


Ci.r .t ki.r I 0, 018 408000 7344 u.m / an.

unde: ki.r este cota anual din valoarea investiiei pentru ntreinere i reparaii;
I investiia iniial.

Conform acestui tabel, pentru staii de transformare 150 kV, ki.r 1,8% din
valoarea investiie.
Cheltuielile anuale cu pierderile de energie se determin:
Cw.t Ptr
Cw 142,122 4615,

786 0,078 51168,53

u.m / an.
unde: Ptr reprezint pierderile de putere n transformatoare;
durata pierderilor maximale (determinat pentru curba anual) ;
Cw costul unui kWh energiei la o central de referin.

Dac durata pierderilor maximale este egal 4600 h/an costul unui kWh energiei
la central de referin Cw 0, 078 u.m / kWh , costul anual al pierderilor de energie
constituie :
Cexp Ci.r .t Cw.t 7344 51168,53 58512,53 u.m / an.

Dac considerm, c cheltuielile anuale de expluatare sunt constante pe durata de


studii, atunci valoarea actualizat a acestora la sfritul anului se determin :
T

Cexp.act Cexp (1 i )t 58512,53 6.1446 359536 u.m.


t 0

Valoarea remanent actualizat (=0) se determin :


Wact W (1 i )T 204000 (1 0,1) 10 78642 u.m.

unde: W reprezint remanent a echipamentului la sfritul perioadei de studiu, care se


determin cu relaia:

T
10

W 1 I 1 408000 204000 u.m.


Tsn
20

unde: T reprezint durata de studiu , T=10 ani;


Tsn durata normat de funcionare a transformatoarelor, Tsn 20 ani;
I investiia iniial.

Valoarea remanent actualizat (=0) se determin :


Mod Coala Nr. Document

Semnt.

Data

Coala

14

CTA I act ,tot Cexp, act WT ,act 1281285, 6 329536 78642 1562179, 4 u.m.
CTA2 1562179, 4 u.m. i lund n
Comparnd valorile CTA1 2297722,82 u.m. cu
consideraie condiia CTA=minim se va alege varianta 2 a schemei CET.

4. CALCULUL CURENILOR DE SCURTCIRCUIT TRIFAZAT.


4.1 ntocmirea schemei echivalente i calculul reactanelor elementelor schemei.
Schema de calcul a sistemului electroenergetic examinat este reprezentat n fig.4.
Parametrii elementelor sistemului reprezentai n schema electric de calcul sunt
Mod Coala Nr. Document

Semnt.

Data

Coala

15

reprezentai n sarcin. Calculul curenilor de scurtcircuit se efectuiaz conform


urmtorului model:

1. ntocmirea schemei de calcul

2.ntocmirea schemei echivalente de calcul

3. Calculul reactanelor n uniti relative

4. Transfigurarea schemei echivalente

5 .Determinarea curentului supratranzitoriu i de oc

Fig. 4. Algoritmul de calcul a curenilor de s.c. trifazat.


ntocmirea schemei echivalente const n raportarea tensiunilor electromotoare
(T.E.M.) i a reactanelor elementelor situate la diferite trepte de transformare la una i
aceeai treapt, considerat de baz.
Pentru simplificarea calculelor, circuitele magnetice se vor nlocui printr-o schem
echivalent cu legturi galvanice ntre elementele sistemului. n schema echivalent toate
elementele schemei de calcul se introduc cu reactanele lor respective, iar generatoarele i
sarcina generalizat i cu tensiunea electromotoare (T.E.M.). Totodat n schema dat vor
fi introduse i reactoare pentru limitarea curenilor de scurtcircuit. Aceast schem este
reprezentat n figura.5.

Mod Coala Nr. Document

Semnt.

Data

Coala

16

Fig. 5. Schema electric de calcul a centralei.


-

Limitarea curenilor de s.c.

Limitarea curenilor de s.c. const n instalarea reactoarelor la barele de joas


tensiune.Pentru aceasta din http://www.elektrozavod.ru/production/8_12 se alege reactorul
-20-4000-0.35.
Parametrii tehnici ale reactorului de tip -10-2 1000-0.35.
Tipul
-20-4000-0.35

Tabelul 2

U n , kV

In , A

Pf , kW

il .d . , kA

I T , kA

tT , s

20

4000

51

91

25

Reactorul se verific la urmtoarele condiii:


1) verificarea la stabilitatea electrodinamic:
il .d i ;

se observ c condiia de stabilitate electrodinamic se respect.


il .d 91kA i 88,521 kA .

2) verificarea la stabilitatea termic:


Bs.c. IT2 tT Bs .c.calc ;
Bs.c IT2 tT 252 6 3750 kA2 s;
Bs.c.calc I p2.0 tdec Ta 32, 2652
0, 05 0, 2 246, 25 kA2 s.

unde tdec 0, 05 s - timpul de deconectare a s.c.


Ta 0, 2 s - constanta de timp, se alege din [1], tab.3.8, pag 150.
Se observ c condiia de stabilitate termic se respect:
Bs.c 3750 kA2 s Bs.c .calc 246, 25 kA2 s .

3) verificarea dup valoarea tensiunii remanente n regim de s.c.:


U rem .% 60 70,% ;

Mod Coala Nr. Document

Semnt.

Data

Coala

17

U rem xn.B

3 I p.0
U m.nom

3 32, 265
100

0,35
100
186,
28% ;
10,5

Analiznd condiiile de verificare, observm c ele se respect. Deci reactorul ales


poate fi utilizat n schem.
Alctuirea schemei echivalente de calcul a centralei.

Fig. 6. Schema echivalent de calcul a centralei

Condiiile de baz pentru calculul curenilor de s.c., n diferite puncte de s.c.


Tabelul 3

Ib

Punctul de s.c.

S b , MVA

U b , kV

I b , kA

K1

100

10,5

5,5

K2

100

150

0,385

Sb
3 U b

Calculul reactanelor n uniti relative pentru punctul K1:


Mod Coala Nr. Document

Semnt.

Data

Coala

18

1) Reactana sistemului:
xS * x1

Sb
100

0, 029;
S s.c. 3400

2) Reactana liniilor:
S
xL* x2 x3 x0 l 2b
U nom

0, 4 22

100

10,52

7,982;

3) Reactana transformatoarelor:
xTLS * x4 x11

U s.c.% Sb
10,5 100

0,16;
100 Snom 100 63

4) Reactana reactorului:
S
100
xR* x6 x8 x10 xR 2 b
0,35 2
U m.nom.
10,5

0,317;

5) Reactana generatorului:
S
100
xG* x5 x7 x9 x12 xd" b 0,125
0,5;
S nom.G
25

Transfigurarea schemei echivalente.

Fig.7. Prima treapt de transfigurare a schemei echivalente de calcul.

Mod Coala Nr. Document

Semnt.

Data

Coala

19

x13 x1

x2 x3
7,982 7,982

0, 029 4, 02;
x2 x3 7,982 7,982

x14 x4 x6

x4 x6
0,16 0,317
0,16 0,317
0,579;
x5
0,5

x15 x5 x6

x5 x6
0,5 0,317
0,5 0,317
1,81;
x4
0,16

x16 x4 x5

x4 x5
0,16 0,5
0,16 0,5
0,912;
x6
0,317

x17 x10 x11

x10 x11
0,16 0,317
0,16 0,317
0,579;
x12
0,5

x18 x11 x12

x11 x12
0,16 0,5
0,16 0,5
0,912;
x10
0,317

x19 x10 x12

x10 x12
0,5 0,317
0,5 0,317
1,81;
x11
0,16

Fig.8. A doua treapt de transfigurare a schemei echivalente de calcul.


x20

x8 x17
0,317 0,578

0,124;
x8 x14 x17 0,317 0,579 0,579

x21

x8 x14
0,317 0,579

0,124;
x8 x14 x17 0,317 0,579 0,579

x22

x14 x17
0,579 0,579

0, 227;
x8 x14 x17 0,317 0,579 0,579

x23

x7 x15
0,5 1,81

0,392;
x7 x15 0,5 1, 81

x24

x9 x19
0,5 1,81

0,392;
x9 x19 0,5 1,81

Mod Coala Nr. Document

Semnt.

Data

Coala

20

Fig.9. A treia treapt de transfigurare a schemei echivalente de calcul.


x25 x21 x23 0,124 0,392 0,516;
x26 x20 x24 0,124 0,392 0,516;

Fig.10. A patra treapt de transfigurare a schemei echivalente de calcul.


x x , x22 0, 41 0, 227 0, 637;
x,

1
1

0, 41;
1
1
1
1
1
1

x13 x16 x18 4, 02 0,912 0,912

C1

x,
0, 41
x , 0, 41
x,
0, 41

0, 449; C2

0,102; C3

0, 449;
x16 0,912
x13 4, 02
x18 0,912

x27

x 0, 637

1, 418;
C1 0, 449

x28

x 0, 637

6, 249;
C2 0,102

Mod Coala Nr. Document

Semnt.

Data

Coala

21

x29

x 0, 637

1, 418;
C3 0, 449

Fig.11. A cincea treapt de transfigurare a schemei echivalente de calcul.


x30

1
1
1
1
1

x25 x26 x27 x29

1
1
1
1
1

0,516 0,516 1, 418 1, 418

0,189;

Calculul reactanelor n uniti relative pentru punctul K2:


1) Reactana sistemului:
xS * x1

Sb
100

0, 029;
S s.c. 3400

2) Reactana liniilor:
S
xL* x2 x3 x0 l 2b
U nom

0, 4 22

100

1542

0,037;

3) Reactana transformatoarelor:
xTLS * x4 x11

U s.c.% Sb
10,5 100

0,16;
100 Snom 100 63

4) Reactana reactorului:
S
100
xR* x6 x8 x10 xR 2 b
0,35 2 0, 00147;
U m.nom.
154

5) Reactana generatorului:
S
100
xG* x5 x7 x9 x12 xd" b 0,125
0,5;
S nom.G
25

Transfigurarea schemei echivalente.

Fig.12. Prima treapt de transfigurare a schemei echivalente de calcul.


Mod Coala Nr. Document

Semnt.

Data

Coala

22

x13 x1

x2 x3
0,037 0, 037

0,029 0, 048;
x2 x3 0,037 0, 037

x14 x4 x6

x4 x6
0,16 0, 00147
0,16 0, 00147
0,162;
x5
0,5

x15 x5 x6

x5 x6
0,5 0, 00147
0,5 0, 00147
0,506;
x4
0,16

x16 x4 x5

x4 x5
0,16 0,5
0,16 0,5
54,868;
x6
0, 00147

x17 x10 x11

x10 x11
0,16 000147
0,16 0, 00147
0,162;
x12
0,5

x18 x11 x12

x11 x12
0,16 0,5
0,16 0,5
54,868;
x10
0, 00147

x19 x10 x12

x10 x12
0,5 0, 00147
0,5 0, 00147
0,506;
x11
0,16

Fig.13. A doua treapt de transfigurare a schemei echivalente de calcul.


x20

x8 x17
0, 00147 0,162

0, 0007;
x8 x14 x17 0,00147 0,162 0,162

x21

x8 x14
0, 00147 0,162

0, 0007;
x8 x14 x17 0,00147 0,162 0,162

x22

x14 x17
0,162 0,162

0, 081;
x8 x14 x17 0,00147 0,162 0,162

x23

x7 x15
0, 5 0,506

0, 252;
x7 x15 0,5 0,506

x24

x9 x19
0,5 0,506

0, 252;
x9 x19 0,5 0,506

Mod Coala Nr. Document

Semnt.

Data

Coala

23

Fig.14. A treia treapt de transfigurare a schemei echivalente de calcul.


x25 x21 x23 0, 0007 0, 252 0, 253;
x26 x20 x24 0, 0007 0, 252 0, 253;

Fig.15. A patra treapt de transfigurare a schemei echivalente de calcul.


x27 x22

x25 x26
0, 252 0, 252

0, 081 0, 207;
x25 x26 0, 252 0, 252

Fig.16. A cincea treapt de transfigurare a schemei echivalente de calcul.


Mod Coala Nr. Document

Semnt.

Data

Coala

24

x28

1
1

0, 205;
1
1
1
1
1
1

x16 x18 x27 54,868 54,868 0, 207

4.2 Calculul curentului supratranzitoriu de s.c. Ip.0 n punctele stabilite.


Calculul curentului supratranzitoriu pentru punctul K1:
I p.0

E*"
I b ;
x*

I p.0 S

ES
1
I b

5,5 0,88 kA ;
x28
6, 249

I p.0G

EG
1, 08
I b

5,5 31,385 kA ;
x30
0,189

I p.0 K 1 I p.0 S I p .0G 0,88 31,385 32, 265 kA .

Calculul curentului supratranzitoriu pentru punctul K2:


I p.0

E*"
I b ;
x*

I p.0 S

ES
1
I b
0,385 8,103 kA ;
x13
0, 048

I p.0G

EG
1, 08
I b
0,385 2, 026 kA ;
x28
0, 205

I p.0 K 1 I p.0 S I p .0G 8,103 2, 026 10,129 kA .

4.3 Calculul curentului de oc, n punctele stabilite.


Curentul de oc n punctul K1 se determin cu ajutorul relaiei:
i

2 I p .0 k ;

unde k este coeficientul de oc se alege din [1], tab.3.8, pag.150.


-pentru generatoare k 1,94 .
i. K 1 2 I p.0 K 1 k 2 31,385

1,94

86,107

kA ;

-pentru sistem k 1,82 .


i. K 1 2 I p.0 K 1 k 2 0,88
1,82

2,414 kA ;

Curentul de oc n punctul K2 se determin cu ajutorul relaiei:


i

2 I p .0 k ;

unde k -coificientul de oc se alege din [1], tab.3.8, pag,150.


-pentru sistem k 1,82 ;
i. K 2 2 I p.0 K 2 k 2 8,103

1,82

22,
232 kA ;

-pentru generatoare k 1,94 .


i. K 1 2 I p.0 K 1 k 2 2,
026 1,94

5,558

kA ;
Mod Coala Nr. Document

Semnt.

Data

Coala

25

4.4 Prezentarea rezultatelor calculului curenilor de s.c. sub form de tabel.


Tabelul 4
Locul de
s.c.

Sursa

Ip0, kA

K1

S
G

0,88
31,385

K2

S
G

8,103
2,026

Mod Coala Nr. Document

Semnt.

Data

Ip0K, kA

i, kA

i k , kA

32,265

iS =2,414
iG =86,107

88,521

10,129

iS =22,232
iG =5,558

27,79

Coala

26

5. ALEGEREA CONDUCTOARELOR I APARATELOR DE COMUTAIE.


5.1 Alegerea ntreruptoarelor i separatoarelor.
5.1.1 Alegerea aparatelor electrice de comutaie din circuitul generatorului:
Fiindc la toate generatoarele trebuie s avem acelai ntreruptor alegerea
ntreruptorului se va efectua dup cel mai mare curent de oc a circuitului.
I nom I nomG

S nom
100

1,375 kA 1375 A ;
3 U nom
3 10.5

Cel mai mare curent va circula cnd tensiunea va cobor cu 5%.


I max I nomG

S nom
100

1, 447 kA 1447 A ;
0,95 3 U
nom 0,95 3 10,5

Se alege ntreruptorul de tipul: VD4 cu parametrii nominali:


Tabelul 5
Tipul
Un,
ntreruptorului kV

Inom,
A

Irup, kA

10,5

1600

50

VD4

Curentul
electrodina
mic, kA
ild
IT

tT,
s

ttot, s

125

0,07

20

Se alege separatorul din tabelul 5.5, din [2] de tipul: P-10-2500 separator cu
amplasare n ncperi nchise cu parametrii nominali :
Tabelul 6
Tipul
separatorului

Un,
kV

Inom, A

P-10-2500 10,5

2500

Curentul
electrodinamic, kA
ild
IT
125
40

tT, s
4

Se efectueaz verificarea ntreruptorului i a separatorului din tabelele de mai sus la


stabilitatea termic i la stabilitatea dinamic:
Verificarea la stabilitatea electrodinamic :
2 I rup 1 n 2 I p i a ;
'
I nom

I p 0G
I

'
nom

4 Pnom
4 20

5, 49 kA ;
3 U mnom cos
3 10,5
0,8

31,385
5, 71 ;
5, 49

27

Din curbele tip pentru determinarea I p I p 0 din [1] desenul 3.26, pg 152 obinem:
I p G
I p 0G

0,81 I p G 0,81 I p 0G 0,81


31,385 25, 42 kA; kA;

I p 0 sist I p sist 0,88 kA


I p I p sist I p G 0,88 25, 42 26,3 kA ;

ia , S 2 I p 0 S e

Ta

ia ,G 2 I p 0G e

Ta

0,07

2 0,88
e 0,15

0,78 kA;
0,07
0,25

2 31,385

31,
278 kA;

ia ia ,S ia ,G 0, 78 31, 278 32,155 kA;


Ta - timpul aperiodic de acionare care se alege din [1] tabelul 3.8 pag, 150;

pentru k 1,9 , Ta 0, 2 s ;
Verificarea capacitatea de rupere a ntreruptorului:
2 50 1 0, 2 84,853 kA;

2 26,3

32,155

69,349

kA ;

Verificarea la stabilitatea termic :


a) ntreruptorului:
IT2 tT Bsc I p2 0 Ta ,
202 3 1200kA2 S ;
32, 2652 0, 07 0, 2 281, 08 kA2 S ;

b)separatorului:

IT2 tT Bsc I p2 0 Ta ,

452 4 8100 kA2 S ;

Tabelul 7
Parametrii calculai
Ure = 10,5 kV
Icerut = 1081,5 A
2Ip+ia=69,349kA
i=88,521
Bsc=I2po( +Ta)=281,08kA2S

Parametrii din catalog


VD4
P-10-2500
Unom=10 ,5 kV
Unom=10,5 kV
Inom=1600 A
Inom=2500 A
2Irup(1+n)=84,853 kA
ild=125 kA
ild=125 kA
I2TtT=1200 kA2s
I2TtT=8100 kA2s

28

5.1.2. Alegerea ntreruptorului i a separatorului n circuitul transformatorului la


barele de joas tensiune i ntre seciile de bare:
S nomTR

I nomTR

3 U nom

63
3, 464 kA 3464 A ;
3 10,5

I max 1, 4 I nomTR 1, 4
3464 4850 A ;

Se alege ntreruptorul de tipul: VAH cu parametrii nominali:


Tabelul 8
Tipul
Un,
ntreruptorului kV

Inom,
A

Irup, kA

10,5

5000

63

VAH

Curentul
electrodina
mic, kA
ild
IT

tT,
s

ttot, s

160

0,05

63

Se alege separatorul din tabelul 5.5, din [2] de tipul: K-10-5000 separator cu
amplasare n ncperi nchise cu parametrii nominali :
Tabelul 9
Tipul
separatorului

Un,
kV

Inom, A

K-10-5000

10,5

5000

Curentul
electrodinamic, kA
ild
IT
200
70

tT, s
10

Se efectueaz verificarea ntreruptorului i a separatorului din tabelele de mai sus la


stabilitatea termic i la stabilitatea dinamic:
Verificarea la stabilitatea electrodinamic :
2 I rup 1 n 2 I p i a ;
'
I nom

I p 0G
I

'
nom

4 Pnom
4 20

5, 49 kA ;
3 U mnom cos
3 10,5
0,8

31,385
5, 71 ;
5, 49

Din curbele tip pentru determinarea I p I p 0 din [1] desenul 3.26, pg 152 obinem:
I p G
I p 0G

0,81 I p G 0,84 I p 0G 0,81


31,385 26,365 kA; kA;

I p 0 sist I p sist 0,88 kA

29

I p I p sist I p G 0,84 26,365 27, 243 kA ;

ia , S 2 I p 0 S e

Ta

ia ,G 2 I p 0G e

Ta

0,06
0,15

2 0,88
e

0,834

kA;
0,06
0,25

2 31,385

32,881

kA;

ia ia ,S ia ,G 0,834 32,881 33, 715 kA;

Verificarea capacitatea de rupere a ntreruptorului:


2 63 1 0, 23 109,587 kA; 2 27,
243 32,881

72,
242 kA ;

Verificarea la stabilitatea termic :


b) ntreruptorului:
IT2 tT Bsc I p2 0 Ta ,
632 3 11907 kA2 S ;
32, 2652 0, 06 0, 2 260, 25 kA2 S ;

b)separatorului:

IT2 tT Bsc I p2 0 Ta ,

702 10 49000 kA2 S ;

Tabelul 10
Parametrii calculai
Ure = 10,5 kV
Icerut = 4850 A
2Ip+ia=72,242kA
i=88,521
2
Bsc=I po( +Ta)=281,08kA2S

Parametrii din catalog


VAH
K-10-5000
Unom=10 ,5 kV
Unom=10,5 kV
Inom=5000 A
Inom=5000 A
2Irup(1+n)=109,6 kA
ild=160 kA
ild=200 kA
2
2
2
I TtT=11907 kA s
I TtT=49000 kA2s

5.1.3 Alegerea ntreruptorului i a separatorului n circuitul seciei barelor la


partea de joas a tensiunii pentru alimentarea consumatorilor locali:
Alegerea ntreruptoarelor i separatoarelor se efectueaz dup puterea activ de
sarcin maxim consumat de consumatorii locali a centralei electrice.

30

10 kV

C.L.

C.L.

Fig. 17. Consumatorii locali a centralei electrice.


Limitarea curenilor de s.c. const n instalarea reactoarelor la barele de joas
tensiune. Pentru a limita curenii de s.c la barele consumatorilor locali, ei se vor conecta
la barele de 10 kV, a centralei, prin intermediul reactoarelor cu nfurarea divizat.
De pe barele 10,5 V pleac 24 linii, max= 80 W
I norm

Pmax
80

0, 229kA
cos 3 U
nom n 0,8 3 10,5
24

I max 3 I norm 687 A

Alegem reactorul de tip -10-2x1000-0,22 Unom=10 V, Inom =1000 ,


r = 0,22 , ild=60 .
Reactana rezultant a circuitului cu .s.c., pn la montarea reactorului se determin cu
ajutorul relaiei:
X rez

U mp
3 I p 0

10,5
0,188
3 32, 265

Reactana necesar se determin din condiia instalaiei ntreruptorului -10-20 :


X rez .necesar

10.5
0, 404
3 15

Reactana necesar a reactorului:


r, necesar = 0,404 0,188 = 0,216
Reactana rezultant a circuitului de sc cu reactor:
rez = 0,188 + 0,22 = 0,408 .

31

Valoarea real a curentului periodic de sc dup reactor


I p0

10.5
14,862kA .
3 0, 408

Verificarea stabilitii reactorului la sc.


Stabilitatea electrodinamic:
is 2 I p 0 k s 2 14,862

1,904

49
kA

ild = 60

>

i = 49 .

Stabilitatea termic. Uzina garanteaz timpul de stabilitate termic t=8 s i curentul


mediu ptratic de stabilitate termic I = 23,6 .
Bsc ,uz 23.62 8 4455 kA2 s f Bsc ,calc I 2 p 0 tdec Ta 492 0.07 0.1

37,55

kA2 s

Tensiunea remanent pe barele distribuiei generatoare la s.c. dup reactor este:


U rem % xr

3 I p 0 100

U nom

3 49 100

186, 71%
10

0, 22

Pierderile de tensiune la trecerea curentului maxim n regim normal lund n considerare


scaderea reactanei
U r % xr 1 kc

3 I max 100

sin

U nom

0,
22 1 0,46

3 0, 687 100

0, 75
1, 06%

10

1,06 % < 2 %,
unde = 0,46 (din catalog).
Se alege ntreruptorul de tipul: VD4 cu parametrii nominali:
Tabelul 11
Tipul
Un,
ntreruptorului kV

Inom,
A

Irup, kA

10,5

630

40

VD4

Curentul
electrodina
mic, kA
ild
IT

tT,
s

ttot, s

100

0,07

20

Se alege separatorul din tabelul 5.5, din [2] de tipul: -10-630 separator cu
amplasare n ncperi nchise cu parametrii nominali :
Tabelul 12
Tipul
separatorului

Un,
kV

Inom, A

-10-630

10,5

630

Curentul
electrodinamic, kA
ild
IT
52
20

tT, s
4

32

Se efectueaz verificarea ntreruptorului i a separatorului din tabelele de mai sus la


stabilitatea termic i la stabilitatea dinamic:
Verificarea la stabilitatea electrodinamic :
I p I p 0 14,862 kA ;

ia 2 I p 0 e

Ta

0,07

2 14,862

e 0,1

10,
437 kA;

Verificarea capacitatea de rupere a ntreruptorului:


2 40

10,
437 31,
413 kA ;
1 0, 2 67,882 kA; 2 14,862

Verificarea la stabilitatea termic :


c) ntreruptorului:
IT2 tT Bsc I p2 0 Ta ,
202 3 1200kA2 S ;
14,8622 0, 07 0,1 37,55 kA2 S ;

b)separatorului:

IT2 tT Bsc I p2 0 Ta ,

202 4 1600 kA2 S ;

Tabelul 13
Parametrii calculai
Ure = 10,5 kV
Icerut = 229 A
2Ip+ia=31,413kA
i=49
2
Bsc=I po( +Ta)=37,55kA2S

Parametrii din catalog


VD4
-10-630
Unom=10 ,5 kV
Unom=10,5 kV
Inom=630 A
Inom=630 A
2Irup(1+n)=67,882 kA
ild=100 kA
ild=52 kA
2
2
2
I TtT=1200 kA s
I TtT=1600 kA2s

5.1.4. Alegerea ntreruptorului i a separatorului n circuitul transformatorului la


barele de nalt tensiune tensiune i LEA 150 kV:
I nomTR

SnomTR
3 U nom

63
0, 242 kA 242 A ;
3 150

I max 1, 4 I nomTR 1, 4 242 339 A ;

Se alege ntreruptorul de tipul: -154-2000 cu parametrii nominali:

33

Tabelul 14
Tipul
Un,
ntreruptorului kV

Inom,
A

Irup, kA

154

2000

35,5

Curentul
electrodina
mic, kA
ild
IT

tT,
s

ttot, s

35,5

0,07

35,5

Se alege separatorul din tabelul 5.5, din [2] de tipul: -10-5000 separator cu
amplasare n exterior cu parametrii nominali :
Tabelul 15
Tipul
separatorului

Un ,
kV

Inom, A

-10-2000

154

2000

Curentul
electrodinamic, kA
ild
IT
100
40

tT, s
3

Se efectueaz verificarea ntreruptorului i a separatorului din tabelele de mai sus la


stabilitatea termic i la stabilitatea dinamic:
Verificarea la stabilitatea electrodinamic :
2 I rup 1 n 2 I p i a ;
'
I nom

I p 0G
I

'
nom

S sist
3900

14, 621 kA ;
3 U mnom
3 10,5

10,129
0, 69 ;
14, 621

Deoarece I p I p 0 p 1 :
I p 0 I p 10,129 kA

ia , S 2 I p 0 S e

Ta

ia ,G 2 I p 0G e

Ta

0,07
0,15

2 8,109

7,186

kA;

0,07

2 2,
026 e 0,2

2,019 kA;

ia ia ,S ia ,G 7,18 2, 019 9, 205 kA;

Verificarea capacitatea de rupere a ntreruptorului:


2 35,5

9,
205 23,53

kA ;
1 0, 2 60, 245 kA; 2 10,129

Verificarea la stabilitatea termic :

34

d) ntreruptorului:
IT2 tT Bsc I p2 0 Ta ,
35,52 2 2520kA2 S ;
10,1292 0, 07 0, 25 9, 747 kA2 S ;

b)separatorului:

IT2 tT Bsc I p2 0 Ta ,

402 3 4800 kA2 S ;

Tabelul 16
Parametrii calculai
Ure = 150 kV
Icerut = 330 A
2Ip+ia=23,53kA
i=27,8
2
Bsc=I po( +Ta)=9,744kA2S

Parametrii din catalog


-150-2000
-150-2000
Unom=154 kV
Unom=154 kV
Inom=2000 A
Inom=2000 A
2Irup(1+n)=60,245 kA
ild=35,5 kA
ild=100 kA
2
2
2
I TtT=2520 kA s
I TtT=4800 kA2s

5.2 Alegerea barelor colectoare, seciunilor conductoarelor.


5.2.1 Alegerea conductoarelor din circuitul generatorului.
Alegerea conductoarelor din circuitul generatorului se efectueaz dup curentul
maximal ce vine de la generator:
I cerut

Pnom
20000

1447A ;
3 0,95 U
nom cos
3 0,95
10,5
0,8

Se alege conductorul nchis de form circular --10-1600-128 1,


1.Conductorul se alege din tabelul 9.14 pagina 543 din [9.4], cu urmtorii parametrii:
Unom=10 kV; Iadm=1600 A; ild=128 kA. q=125x55x6,5 mm.
5.2.2 Alegerea

barelor

colectoare

conductoarelor din

circuitul

transformatorului la tensiunea 10 kV.


Alegerea conductoarelor din circuitul transformatorului i a barelor colectoare se
efectueaz dup curentul maximal de lucru a transformatorului:
I norm I nom.TR

S nom.TR
63000

3464 A ;
3 U nom
3 10,5

35

I max 1, 4 3464 4850 A ;

Se alege conductorul din aluminiu de form profil U.Conductorul se alege din


tabelul 3.5 pagina 625 din [1], cu urmtorii parametrii:Unom=10 kV; Iadm=5650 A;
q=2x1785 mm. Cu coeficientul de corecie a temperaturii care se alege din tabelul 3.8
pagina 627 din [1] dup temperatura a celei mai calde luni t=30C i temperatura normal
a barei t=700 C. Acest coeficient este 0,94:
Imax=5650*0,94=5311 A > Icerut=4850 A;
Verificarea barelor colectoare la stabilitate termic:
Bsc I p2 0 (tdec Ta ) 32, 2652 (0, 05 0, 2) 260, 25 kA 2 s ;

unde: Ta=0,2 s; i tdec=0,05 s;


Seciunea minim dup impulsul termic este:
qmin

Bsc
260, 25

177, 27 mm 2 ;
C
91

unde C este un coeficient care se alege din tabelul 3.14 din [1] de la pag, 192 i
care este egal cu: C=91.
qmin < qales ;

qales =3570 mm2;

Se efectueaz verificarea barelor colectoare la stabilitate mecanic:


max

i2 l 2
885212 22
2, 2
2, 2
10
8
W a
167 0,8

5,16
MPa;

a= 0,8 m distana ntre faze;


adm=75 MPa>calc=5,16 MPa;
5.2.3 Alegerea conductoarelor din circuitul consumatorilor locali 10 kV.
Alegerea conductoarelor din circuitul transformatorului i a barelor colectoare se
efectueaz dup curentul maximal a consumatorului:
I nom =I max =

Pmax
80
=
=229 A;
3 U nom cos nr

3 10,5
0,8 24

Se alege conductorul din aluminiu protejat de un furtun din policlorur de vinil


. Conductorul se alege din tabelul 3.7 pagina 626 din [1], cu urmtorii
parametrii:Unom=10 kV; Iadm=355 A; q=240 mm2. Cu coeficientul de corecie a
temperaturii care se alege din tabelul 3.8 pagina 627 din [1] dup temperatura a celei

36

t=20C i temperatura normal a barei t=70 0 C. Acest coeficient este

mai calde luni


0,95:

I adm
=I adm 0,95=355 0,95=337 A;

Determinarea seciunii conductoarelor se face conform criteriului seciunii


economice qec. Seciunea economic qec a conductoarelor, ce rezult pe baza criteriului
CTAmin, este:
qec =

I nom 229
=
=190 mm 2 ;
jec 1, 2

unde: jec=1,2 este densitatea economic a curentului se alege din tab 4.5 pg 233 [1].
Verificarea barelor colectoare la stabilitate termic:
Bsc I p2 0 (tdec Ta ) 14,8622 (0, 07 0,1) 37,55 kA 2 s ;

unde: Ta=0,1 s; i tdec=0,07 s;


Seciunea minim dup impulsul termic este:
qmin

Bsc
37,55

65,18 mm 2 ;
C
94

unde C este un coeficient care se alege din tabelul 3.14 din [1] de la pag, 192 i
care este egal cu: C=94.
5.2.4 Alegerea barelor colectoare, LEA i a conductoarelor din circuitul
transformatorului la tensiunea 150 kV.
Alegerea conductoarelor din circuitul transformatorului i a barelor colectoare se
efectueaz dup curentul maximal i a seciunii minime impuse pentru aceast tensiune:
I norm I nom.TR

S nom.TR
63000

242 A ;
3 U nom
3 150

I max 1, 4 242 0,339 A ;

Se alege conductorul flexibil neizolat din funie de aluminiu-oel AC 120/19.


Conductorul se alege din tabelul 3.3 pagina 624 din [1],

cu urmtorii

parametrii:Unom=150 kV; Iadm=390 A; d=15,2 m; q=120 mm2.


Verificarea la descrcarea corona:

37

Dup cmpul electric critic:

0, 299
0, 299
E0 30,3 1

33,368

kV / cm ;
m 30,3 1
0,82

r0
0, 76

unde: m este coeficient, care depinde de rogozitatea suprafeei conductorului;


Pentru conductoare fasciculare m=0,82 ;
r0 raza conductorului:
r0=0,76 mm ;
-

Dup cmpul electric maxim la suprafaa conductorului:

0,354 U
0,354 154

E k

25,95 kV / cm
Dmg
1, 26 360
;
0, 76 lg
r0 lg
0,
76
rech

unde: Dmg=1,26D-distana medie geometric dintre faze,cm.


D=360 distana dintre fazele vecine,cm.
-

Condiia descrcrii corona este urmtoarea :

1.07 E 0.9 E 0

1, 07 25,95 0,9
33,368
27, 77 30, 03

Verificarea la stabilitatea dinamic:


qec =

I max nom 339


=
=339 mm 2 ;
jec
1

unde: jec=1 este densitatea economic a curentului se alege din tab 4.5 pg 233 [1].
q = r 2 =3,14 7, 6=181,46 mm 2 ;

Deci adoptm 2 conductoare pe faz cu d=15,2 mm:


I max =330 A p 2 I adm =2
390=780 A;

38

6. ALEGEREA TRANSFORMATOARELOR DE MSUR


6.1 Alegerea aparatelor de msur n circuitele tip ale centralei electrice.
Controlul regimului de funcionare a echipamentului principal i secundar la o CET se face
cu ajutorul aparatelor de control i msur.

Fig. 18. Schema de msurri n circuitele CET.

39

6.2 Alegerea transformatorului de curent.

Fig. 19. Schema de conectare a aparatelor de msur.


Transformatorul de curent se alege dup curentul nominal al LEA:
I max 37 A;

Se alege transformatorului de curent:150-1


Parametrii nominali ai transformatorului:
Tabelul 17
U nom , kV I1nom , A I 2 nom , A Clasele de precizie

150

1000

0.5/10P

i l.d , kA

I T , kA

tT ,s

r2nom ,

52

20

30

Se verific TA dup sarcina secundar, utiliznd schema de conexiune i datele de


catalog. Pentru a putea efectua verificarea TA este nevoie de a cunoate tipul i parametrii
aparatelor de msur conectate n secundarul TA.

40

Tipul i parametrii aparatelor de msur conectate n secundarul TA


Tabelul 18
Aparatul

Tipul

Sarcina VA

Nr

Sarcina total VA

Watmetru
Varmetru
Ampermetru
Contor de
energie activ

-335
-335
-335
3-681

0.5
0.5
0.5
2.5

1
1
3
1

0.5
0.5
1.5
2.5

Contor de
energie activ

3-681

2.5

2.5

Total

7.5

Pentru conectarea aparatelor din secundarul TA se recomand de utilizat conductor


cu miez din aluminiu cu seciunea 4 6 , mm 2 .
Rezistena sumar a aparatelor se determin cu ajutorul relaiei:
rap

S ap
I

2
2 nom

7.5
7.5 ;
1

Rezistena admisibil a conductoarelor se determin cu relaia:


rcond z2 nom rap rc 30 7.5 0.1 22.4 ;

unde, rc 0.1 -rezistena tranzitorie a conductoarelor, pentru numrul aparatelor


n 3.

Transformatoarele de curent sunt unite n stea complet. Lungimea orientativ


L 75 m .

lcal 0.0283 100

0.126 mm 2 ;
rcond
22.4

Alegem cablul cu seciunea conductoarelor


rcond

4 mm 2 .

lcal 0.0283 100

0.7075 mm 2 ;
q
4

z2 calc rcond rap rc 0.7075 7.5 0.1 8.307 ;

Verificarea la stabilitatea termic :


IT2 tT Bsc I p2 0 Ta ,

41

20 2 3 1200kA2 S ;
10,129 2 0, 07 0, 25 9, 747 kA2 S ;
IT2 tT 1200 kA2 S Bsc I p2 0
Ta

9,
747 kA2 S;

Verificarea la stabilitatea termic :


ild 1200 kA is 27, 79 kA2 S ;

6.3 Alegerea transformatorului de tensiune.


Alegerea transformatorului de tensiune se efectueaz dup sarcina secundar.
Tabelul 18
-150
U1 220 / 3

S 200MVA

U 2 100 / 3

S max 2500 MVA

100

cl.p=0,5

Tipul aparatelor conectate n secundarul TV:


Tabelul 19
Sarcina
P, W
Q, VAr
6
9
9
2
-

Aparat

Tip

Sonf

Nr. onf

cos

sin

Nr. apar.

Voltmetru
Watmetru
Varmetru
Frecvenmetru
nregistrator
de impulsuri
Contor de
energie activ
Contor
de energie
reactiv
Total

-335
-335
-335
-362

2
1.5
1.5
1

1
2
2
1

1
1
1
1

0
0
0
0

3
3
3
2

18

3681

0.38

0.925

12

29.2

4676

0.38

0.925

18

43,8

74

73

Sarcina secundar a TV se determin cu formula:


S 2 P 2 Q 2 742 732 104 VA;

Alegem TV de tipul -150cu S 2 nom 75 VA n clasa de precizie 0.5.


S 2 104 VA S 2 nom 200 VA;

TV va lucra n clasa de precizie dat.


10000 100 100
,
,
.
3
3
3

42

7. ELABORAREA SCHEMELOR DE CONEXIUNE ALE INSTALA IILOR


ELECTRICE
7.1 Justificarea i alegerea schemelor de conexiune la tensiunile superioar i
inferioar.
Elaborarea schemei electrice de conexiune 10,5 kV.
Lund n considerare prezena consumatorilor de categoria 1 i a 2 n schema electric
dar i un numr mare de conexiuni la bara colectoare n urma calculelor tehnico
economic se poate de utilizat un sistem cu dou bare colectoare .

Fig. 20. Schema monofilar a ID-10 kV.

43

Bobinele de reactan dintre secii servesc pentru limitarea curenilor de s.c. Curentul
nominal al bobinei de reactan trebuie s corespund curentului de sarcin a seciei. La
fel putem meniona c n caz de oprire a unui generator sau de scoatere n repara ie a unei
bare colectoare consumatorii locali se alimenteaz de la generatoarele rmase n
funcionare. Consumatorii locali sunt conectai prin intermediul unei bobine de reactan
jumilat.
Avantajele:
- permite alimentarea consumatorilor de categoria 1 n regim permanent,
- funcionarea att separat ct i n paralel a barelor colectoare,
- fiabilitate ridicat,
- n caz de avarie centrala nu se v-a deconecta de la sistem n ntregime, dar numai
partea defectat.
Dezavantajele:
- numrul mare de separatoare, izolatoare, cabluri i ntreruptoare.
- construcia mai dificil.
Elaborarea schemei electrice de conexiune 150 kV.
La aceast tensiune de producere se folosesc ID cu dou sisteme de bare colectoare i
una de ocolire.

Fig. 21. Schema principal a ID-150 kV.


n regim normal de lucru schema se afl n starea urmtoare:
- Bara de ocolire fr tensiune O deconectat conexiunile sunt distribuite uniform ntre
sistemele de bare, iar separatoarele respective sunt nchise sau deschise .
O permite nlocuirea oricrui alt ntreruptor fr ntreruperea alimentrii conexiunii
respective,(la efectuarea manevrelor cupla longitudinal trebuie s fie conectat).
Avantajele:
- simpl i uor neleas,
- simplicitatea operaiunii cu separatoarele,

44

- ieftin,
- fiabilitate ridicat,
-

n caz de avarie numai un generator va fi deconectat iar consumatorii vor

fi alimentai n continuare.
Dezavantajele:
- n caz de avarie i de reparaie a unei secii consumatorii importani rmn fr
rezerv iar consumatorii simpli snt deconectai.
7.2 Alegerea schemei de conexiune i transformatoarelor pentru alimentarea
serviciilor proprii din centrala electric.
Elementele care sunt absolut necesare pentru o funcionare economic i sigur a
centralei electrice sunt:
- mecanismele antrenate de motoarele electrice i turbine cu abur,
- receptoarele electrice de toate tipurile,
- reelele electrice n cablu,
- transformatoarele cobortoare,
- sursele de energie independente de sistem,
- instalaiile de comand.
Toate acestea reprezint sistemul de servicii proprii a CE. Funcionarea normal a
CET este posibil numai n cazul funcionrii sigure a sistemului de SP.
Puterea activ consumat de sistemul de servicii proprii a unui CET pe crbune se
determin n felul urmtor PSP (5 7%) PnG .
n cazul nostru vom avea :
PSP (5 7%) PnG 0, 06 20 1, 2 MW ;

unde PnG puterea nominal a generatorului;


Puterea activ a SP sumar este:
PSP 3 PSP 4 1,
2 4,8 MW ;

Puterea aparent a SP se determin cu formula ;


S SP PSP cos 4,8 0,8 6 MVA;

45

Schema SP este prezentat n urmtoarea figur:

Fig.22 Schema SP a CET.


Transformatoarele din circuitul SP snt alese dup tensiune i curentul cerut.
U retelei 10.5 kV ;

S SP 1,5 MVA;
I cerut

S SP
1500

82, 47 A;
3 U retelei
3 10,5

Se alege transformatorul de tipul TM -1600/10.


Parametrii nominali ai transformatorului:
Tabelul 20
Tipul
TM-

Un1, kV

Un2, kV

Pmg kW

Ps.c. kW

I0 %

Us.c. %

1600/10

10.5

6.3

5.2

33.5

0.9

7.5

46

CONCLUZII
n aceast lucrarea a fost proiectat o central termoelectric cu puterea de 80MW.
Centrala electric este dotat cu patru generatoare de tip T-20-2 la tensiunea de
producere 10,5 kV. Energia este evacuat n sistem prin intermediul a dou
transformatoare de legtur cu sistemul TLS cu dou nfurri..
n capitolul 1 a fost elaborat schema de principiu a centralei, au fost construite i
prelucrate curbele de sarcin a consumatorilor locali i a liniilor de tensiune nalt, au fost
stabilite dou variante a schemei centralei, n care au fost alese i verificate
transformatorul de tip:-40000/150, pentru schema 1 i transformatorul de tip:
-25000/110, pentru schema 2. n urma calculelor tehnico-economice, unde a fost
folosit metoda CTA, schema 2 s-a dovedit a fi nerentabil. Deci calculele de mai departe
au fost efectuate pentru schema 1.
n capitolul 2 a fost efectuat calculul curenilor de s.c.trifazat, au fost alese aparatele
de comutaie i conductoarele din circuitul schemei. Efectund calculul curenilor de s.c.,
se observ c valorile obinute ale curenilor de s.c. sunt reale, ceea ce ne arat c
producerea energiei electrice la tensiunea de 10,5 kV este rentabil. Aparatele de
comutaie au fost verificate la stabilitatea electrodinamic i termic, iar conductoarele la
stabilitatea termic i mecanic.
n capitolul 3 s-a elaborat schema serviciilor proprii a centralei i schema de msurri
n toate circuitele centralei de asemenea s-a ales i s-a verificat clasa de precizie a TA de
i TV .
n capitolul 4 a fost elaborat schema de conexiune a ID-10,5 kV i au fost descrise
avantajele i dezavantajele ei.
Partea grafic a lucrrii const din o coal A1. i este prezentat schema electric
monofilar a centralei electrice .

47

BIBLIOGRAFIE

1. .., ... .
M: 1987.
2. .., ...
. M: 1989.
3. .. .. .
4. Arion Valentin, Codreanu Sergiu. Bazele calculului tehnico-economic al sistemelor de
transport i distribuie a energiei electrice. Chiinu UTM 1998.
5. .. .. .
M: 1990.

48