Sunteți pe pagina 1din 7

1.

1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per


IS:7098 (Part-I)
UN-ARMOURED CABLE

Crosssectional
area
(Sq MM)

Short Circuit
Current Rating for
1Sec.duration in K.
Amps

Normal Current Rating in Amps


Overall
Diameter
(mm)
Aluminums Conductor

Copper Conductor

Ground Duct

Air

Ground Duct

Air

48
62
81
99
117
138
168
204
230
265
295
340
390
450
500
555
625
690

45
61
83
115
135
170
210
255
300
342
385
450
519
605
700
809
935
1065

48
60
80
104
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780

45
57
77
106
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250

Aluminum
Copper
s

8
1cX4
1cX 6
1cX10
1cX16
1cX25
1cX 35
1cX50
1cX70
1cX 95
1cX120
1cX150
1cX185
1cX240
1cX300
1cX400
1cX 500
1cX 630
1cX800
1cX1000

9
10
11
12
13
15
16
18
20
22
24
27
30
33
36
40
47
51

45
62
80
90
110
125
155
185
210
230
260
300
335
380
430
485
530
570

47
59
78
102
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660

0.376
0.564
0.940
1.504
2.350
3.290
4.700
6.580
8.930
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

0.572
0.858
1.430
2.288
3.575
5.005
7.150
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00

1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per


IS:7098 (Part-I)
ARMOURED CABLE

Crosssectional
area
(Sq MM)

Normal Current Rating in Amps


Overall
Diameter
(mm)
Aluminums Conductor

1cX4
1cX 6
1cX10
1cX16
1cX25
1cX 35
1cX50
1cX70
1cX 95
1cX120
1cX150
1cX185
1cX240
1cX300
1cX400
1cX 500
1cX 630
1cX800
1cX1000

Short Circuit
Current Rating for
1Sec.duration in K.
Amps

10
11
12
13
14
15
17
19
22
24
25
28
30
33
38
41
46
51
56

Ground

45
59
76
99
117
138
168
204
230
265
295
340
390
450
500
555
625
690

Duct

45
62
80
90
110
125
155
185
210
230
260
300
335
380
430
485
530
570

Air

40
53
73
115
140
170
210
255
300
342
385
450
519
605
700
809
935
1065

Copper Conductor
Ground
48
60
80
104
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780

Duct
47
59
78
102
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660

Air
45
57
77
106
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250

Aluminum
Copper
s
0.376
0.56
0.94
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

0.572
0.858
1.43
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00

1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

UN-ARMOURED CABLE

Crosssectional
area
(Sq MM)

Normal Current Rating in Amps


Overall
Diameter
(mm)
Aluminums Conductor

2cX4
2cX 6
2cX10
2cX16
2cX25
2cX35
2cX50
2cX70
2cX95
2cX120
2cX150
2cX185
2cX240
2cX300
2cX400
2cX500
2cX630

Short Circuit
Current Rating for
1Sec.duration in K.
Amps

13
14
17
17
19
20
22
25
28
31
33
37
41
44
48
54
62

Ground
34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537

Duct
28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470

Air
30
40
53
70
99
117
140
176
221
258
294
339
402
461
542
624
723

Copper Conductor
Ground
44
55
74
94
120
145
170
210
250
285
315
355
410
460
520
580
680

Duct
37
47
61
78
100
120
145
175
210
240
270
300
350
390
440
480
575

Air
39
50
67
85
125
155
190
235
290
330
375
435
510
590
670
750
875

Aluminum
Copper
s
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)


Crosssectional
area
(Sq MM)

ARMOURED CABLE
Overall
Diameter
(mm)

Normal Current Rating in Amps

Short Circuit
Current Rating for
1Sec.duration in K.
Amps

Aluminums Conductor
2cX4
2cX 6
2cX10
2cX16
2cX25
2cX35
2cX50
2cX70
2cX95
2cX120
2cX150
2cX185
2cX240
2cX300
2cX400
2cX500
2cX630

15
16
18
19
21
23
25
28
31
34
37
40
45
49
52
60
66

Ground
34
43
57
78
95
116
140
170
200
225
255
285
325
370
0.33
0.34
0.36

Duct
28
37
48
61
80
94
110
140
165
185
210
235
270
305
435
481
537

Air
30
40
53
70
99
117
140
176
221
258
294
339
402
461
350
405
470

Copper Conductor
Ground
44
55
74
94
120
145
170
210
250
285
315
355
410
460
542
624
723

Duct
37
47
61
78
100
120
145
175
210
240
270
300
350
390
520
580
680

Air
39
50
67
85
125
155
190
235
290
330
375
435
510
590
440
480
575

Aluminum
Copper
s
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
670
750
875

0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.1
13.59
17.16
21.45
26.46
34.32
42.90
37.60
47.00
59.22

1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)


UN-ARMOURED CABLE

Crosssectional
area
(Sq MM)

Normal Current Rating in Amps


Overall
Diameter
(mm)
Aluminums Conductor

3cX 4
3cX 6
3cX 10
3cX 16

Short Circuit
Current Rating for
1Sec.duration in K.
Amps

14
16
18
18

Ground
34
43
57
78

Duct
28
37
48
61

Air
30
40
53
70

Copper Conductor
Ground
44
55
74
94

Duct
37
47
61
78

Air
39
50
67
85

Aluminum
Copper
s
0.376
0.564
0.940
1.50

0.572
0.858
1.430
2.29

3cX 25
3cX 35
3cX 50
3cX 70
3cX 95
3cX 120
3cX 150
3cX 185
3cX 240
3cX 300
3cX 400
3cX 500
3cX 630

21
22
25
30
32
35
39
43
49
53
59
66
73

95
116
140
170
200
225
255
285
325
370
435
481
537

80
94
110
140
165
185
210
235
270
305
350
405
470

99
117
140
176
221
258
294
339
402
461
542
624
723

120
145
170
210
250
285
315
355
410
460
520
580
680

100
120
145
175
210
240
270
300
350
390
440
480
575

125
155
190
235
290
330
375
435
510
590
670
750
875

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Three CORE AL/COPPER COND., PVC INSULATED CABLES As per


IS:1554 (Part-I)
ARMOURED CABLE

Crosssectional
area
(Sq MM)

Normal Current Rating in Amps


Overall
Diameter
(mm)
Aluminums Conductor

3cX 4
3cX 6
3cX 10
3cX 16
3cX 25
3cX 35
3cX 50
3cX 70
3cX 95
3cX 120

Short Circuit
Current Rating for
1Sec.duration in K.
Amps

18
19
20
20
23
25
29
32
35
39

Ground
34
43
57
78
95
116
140
170
200
225

Duct
28
37
48
61
80
94
110
140
165
185

Air
30
40
53
70
99
117
140
176
221
258

Copper Conductor
Ground
44
55
74
94
120
145
170
210
250
285

Duct
37
47
61
78
100
120
145
175
210
240

Air
39
50
67
85
125
155
190
235
290
330

Aluminum
Copper
s
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28

0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16

3cX 150
3cX 185
3cX 240
3cX 300
3cX 400
3cX 500
3cX 630

43
48
53
58
65
72
81

255
285
325
370
435
481
537

210
235
270
305
350
405
470

294
339
402
460
542
624
723

315
355
410
460
520
580
680

270
300
350
390
440
480
575

375
435
510
590
670
750
875

14.10
17.39
22.56
28.20
37.60
47.00
59.22

21.45
26.46
34.32
42.90
57.20
71.50
90.09

1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)


UN-ARMOURED CABLE

Crosssectional
area (Sq
MM)

Normal Current Rating in Amps


Overall
Diameter
(mm)
Aluminums Conductor

3.5X25
3.5X35
3.5X50
3.5X70
3.5X95
3.5X120
3.5X150
3.5X185
3.5X240

Short Circuit
Current Rating for
1Sec.duration in K.
Amps

22
24
27
31
34
38
43
46
52

Ground
95
116
140
170
200
225
255
285
325

Duct
80
94
110
140
165
185
210
235
270

Air
99
117
140
176
221
258
294
339
402

Copper Conductor
Ground
120
145
170
210
250
285
315
355
410

Duct
100
120
145
175
210
240
270
300
350

Air
125
155
190
235
290
330
375
435
510

Aluminum
Copper
s
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56

3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32

3.5X300
3.5X400
3.5X500
3.5X630

57
65
73
82

370
435
481
537

305
350
405
470

461
542
624
723

460
520
580
680

390
440
480
575

590
670
750
875

28.20
37.60
47.00
59.22

42.90
57.20
71.50
90.09

S-ar putea să vă placă și