SISTEMA DE CONTROL PARA

ALIMENTACIN AUXILIAR CON


GRUPO ELECTRGENO

AUTOR: Daniel Navas Sedeo


TITULACIN: Grado en Ingeniera Electrnica Industrial
ASIGNATURA: Electrotecnia Aplicada
CURSO: 2014-2015
FECHA: 7 de Enero de 2015
ESCUELA POLITCNICA SUPERIOR
UNIVERSIDAD DE CRDOBA

0. ndice
1. ObjetivosGenerales

1.1. Descripcin

1.2. Caractersticastcnicasdelsistemaysuscomponentes

1.2.1.ReddeAlimentacin

1.2.2.GrupoElectrgeno

1.2.3.Sistemadealimentacinininterrupida(SAI)

1.2.4.Envolventedelcuadrodecontrol

1.2.5.Contactores

1.2.6.Temporizadores

1.2.7.Conductores

1.2.8.Bornasdeconexin

1.2.9.Consideracionesgeneralesdelcableadodelcuadrodecontrol
1.2.10. Elementosdeseguridad

2. Objetivosfuncionales

2.1. Mododeregulacin

2.2. Cronogramadelautomatismo

3. Implementacindelmodelo

3.1. Clculodelaslneas

3.1.1.Previsindepotencias

3.1.2.LneaGeneraldeAlimentacin

3.1.3.DerivacinIndividual

3.1.4.Lneaauxiliar

3.1.5.Lnearespaldada

3.1.6.Lneaprotegida

3.2. Esquemaselctricos

3.3. Normasdeaplicacin

3.4. Elementosdeseguridad

3.4.1.Proteccincontracontactosdirectos

3.4.2.Proteccincontracontactosindirectos
3.4.3.Proteccincontrasobreintensidades

4. Configuraciones

4.1. Modosdefuncionamiento

4.2. Parmetrosdeentradaysalidadeusuario

5. Bibliografa

6. Planos

7. Fichastcnicas

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

1
1
2
2
2
2
3
3
3
4
4
5
5
5
5
5
6
6
6
6
7
7
8
9
10
10
11
11
11
12
12
12
13
13
14
21

1.

Objetivos Generales

1.1.

DESCRIPCIN

Se necesita disear el cuadro de control de un sistema de alimentacin auxiliar para una


instalacinelctricaquealimentardiversascargas.En elplano n1,puedeverseun croquis
funcionaldelsistema.
Elcuadrodecontroldiseadodeberrealizarlassiguientesfunciones:

Deber vigilar la permanencia de tensin en la red de alimentacin principal del


cuadrodeproteccinymandodelainstalacin.
Deber conmutar a la alimentacin auxiliar en caso de ausencia de tensin en la
alimentacinprincipal.Asmismo,seencargardearrancarungrupoelectrgenoque
suministrartensinalaalimentacinauxiliar.
Deberconmutaralaalimentacinprincipalencasoderecuperacindelatensinen
laredprincipaldealimentacin.Delmismomodo,deberapagarelgrupoelectrgeno
cuando el cuadro de mando y proteccin de la instalacin elctrica vaya a ser
alimentadoporlareddealimentacinprincipal.

Elcuadrodecontrolactuarconelsiguienteprocedimiento:sisedetectaquenohaytensin
en la red de alimentacin principal, desconectar el cuadro de proteccin y mando de dicha
red,tratardearrancarelgrupoelectrgenomedianteunpulsode2segundosenelquese
cerraruncontactosintensin.Sitraselprimerpulsonoarrancaelgrupo,darotropulso,y
ashastatresveces.Sitraslostrespulsos,elgruponohaconseguidoarrancarseconsiderar
quehayunfalloenelarranquedelgrupoynolointentardenuevo.Enelmomentoquese
detecte tensin en la lnea de alimentacin auxiliar, se conectar el cuadro de proteccin y
mando a dicha lnea. En el momento que se detecte tensin en la lnea de alimentacin
principal,sedesconectarelcuadrodeproteccinymandodelalneadealimentacinauxiliar
yseconectaralaprincipal,almismotiempo,seapagarelgrupoelectrgenopormediode
uncontactolibredetensin.
Enelplanon2puedeverseundiagramadelfuncionamientodelsistema.
Es importante sealar que el cuadro de control se disear de forma que sea imposible
alimentarelcuadrodeproteccinymandosimultneamentedesdelaredprincipalylaauxiliar
dealimentacin.Estoseharmedianteunjuegodecontactorescruzados.
El cuadro de control diseado ser alimentado por medio de una lnea protegida por un
sistemadealimentacinininterrumpido(SAI)paraasegurarquerealicesutrabajoenausencia
detensindelaredprincipal.

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

1.2.

CARACTERSTICAS TCNICAS DEL SISTEMA Y SUS


COMPONENTES

1.2.1.

Red de alimentacin

Elenlaboratoriosedisponedeunareddealimentacintrifsicamsneutrode400V,50Hz.En
nuestra prctica solamente usaremos la tensin de 230V entre fase y neutro, aunque en la
prcticaseutilizaparamentatrifsica.
1.2.2.

Grupo electrgeno

UnGrupoElectrgenoesunamquinacompuestapormotor,alternador,ypaneldecontrol,
que en su conjunto realizan conversin electromecnica de energa, es decir, transforma
energamecnicaenelctrica,atravsdeunmotordecombustininternaque,acopladoaun
alternador,entregaenergaelctrica.ElusodeGruposElectrgenosesbastanteamplio,yse
aplica fundamentalmente como una alternativa a la generacin de electricidad con la Red
Elctrica.
Para la lnea de alimentacin auxiliar, se utilizar un grupo electrgeno de gasolina con
arranqueelctricoadistanciamedianteuncontactolibredetensin(TerminalesGM1yGM2),
as mismo, la parada del grupo se realizar tambin mediante un contacto sin tensin
(TerminalesP1yP2).
CaractersticasdelGrupoelectrgeno:

GeneradorelctricodegasolinaGREENCUTmod.AV2000E.
Encendidomanualyelctrico.
Paradaadistanciamediantecontacto.
Dossalidasparaalimentacinmonofsica230V,50Hz.
Salidaadicionalde12V/8,3A.
SalidaestabilizadaporcondensadorARV.
Proteccindesobreintensidadycortocircuito.
Terminaldetomadetierra.
ProteccinclaseII.
Potenciamxima2200W.
Potencianominal2000W.
Pesode40Kg.
Dimensiones59x43x43cm.

1.2.3.

Sistema de alimentacin ininterrumpida (SAI)

Este dispositivo se encargar, mediante un sistema de bateras u otros elementos


almacenadoresdeenerga,deproporcionarporuntiempolimitadolatensindealimentacin
de la lnea protegida que alimenta al cuadro de control, asegurando una tensin de
alimentacinde230V,50Hzparaquedichocuadropuedadesempearsucometido.

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

Enlaprcticaqueserealizenellaboratorio,nosedisponadeesteelemento,sinembargo,
seranecesarioparauncasoreal.SesugiereunSAIconunapotenciadealmenos150VApara
asegurarlaalimentacindelosdispositivosdemando.
1.2.4.

Envolvente del cuadro de control

Laenvolventedelcuadrodecontrolesunarmariocompactoaptoparaexterior,deacerode
puertaciegaconmedidas1000x600x250mm.Enelinteriorseencuentralaplacademontajey
cuatro carriles DIN para los elementos. Para el alojamiento de los conductores de han
dispuestosuficientescanalizacionesdePVCdetamaotalquedispongandeunespaciolibre
dealmenosel20%parafuturasampliaciones,ynopudiendollegarenningnmomentoaun
llenado superior al 90% de su capacidad til. El paso de conductores hacia el exterior del
cuadro se hace mediante una placa de prensaestopas. Su funcin ser alojar todos los
elementos del cuadro de control de modo que queden protegidos de las inclemencias del
medio;asuvez,protegerdecontactosdirectoseindirectosunavezcerrado.
La envolvente tiene un grado de proteccin IP66 de acuerdo con IEC 60529, y un grado de
proteccinIK10conformeIEC62262.
El resto de caractersticas se pueden ver en la ficha tcnica del producto, aunque no tiene
porqucoincidirexactamenteconlaenvolventeutilizadaenlaprcticadelaboratorioaunque
seintentseleccionarunadecaractersticasparecidas.
1.2.5.

Contactores

Es un mecanismo cuya misin es la de cerrar unos contactos, para permitir el paso de la


corriente a travs de ellos. Esto ocurre cuando la bobina del contactor recibe corriente
elctrica, comportndose como electroimn y atrayendo dichos contactos. Normalmente
disponendecontactosauxiliaresquefacilitansuusoparaautomatismos.
Elautomatismodelcuadrodecontrolseharealizadopormediode5contactores(ademsde
2 temporizadores). Los dos contactores principales (KMG1 y KMG2) se utilizarn para
conmutardelalneadealimentacinprincipalalaauxiliaryviceversaenlapartedepotencia,
mientras que los 3 restantes (AUX1, AUX2 y AUX3), se utilizarn en la parte de mando
haciendoexclusivamenteusodesuscontactosauxiliares.
Se han utilizado contactores de la marca Schneider Electric modelo Telemecanique LC1D09,
soncontactoresquedisponende3polospreparadosparaunaintensidadasignadadeempleo
de 18A para categora de uso AC3. Disponen adems de 2 contactos auxiliares, uno
normalmenteabiertoyelotronormalmentecerrado.
Lafichatcnicapresentaelrestodecaractersticasdeloscontactores.
1.2.6.

Temporizadores

UntemporizadorelctricoesunDispositivoqueregulaunaoperacin,deformamomentnea
oporundeterminadoespaciodetiempotambinpodemosregularlaconexindesconexin
deuncircuitoelctricopasadountiempodesdequeselediodichaorden.Eltemporizadores

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

un tipo de rel auxiliar, con la diferencia sobre estos, que sus contactos no cambian de
posicininstantneamente.

Paraelcontroldelospulsosdearranquesehanutilizadodostemporizadores,unodeelloscon
funciones especiales, para la generacin de los pulsos de arranque. El temporizador con
funciones especiales (KT1), funcionar de modo que al alimentar su bobina, cerrar un
contacto de manera pulsante (2 segundos cerrado, 2 segundos abierto). Este contacto
alimentar la bobina de un contactor (AUX3), cuyo contacto auxiliar normalmente abierto,
cerrar los terminales de arranque del grupo (GM1 y GM2). El tren de pulsos cesar por la
causaquesedenprimerlugardelassiguientes;bienpordetectartensinenlalneaauxiliar
de alimentacin (grupo en funcionamiento), o bien por haber excedido el tiempo del
temporizador KT2. ste ltimo, contar un total de 10 segundos (la duracin de 3 pulsos en
estado alto), despus abrir el circuito de alimentacin de la bobina de KT1 con lo que
finalizareltrendepulsos.Enelesquemademandodelplanocorrespondienteseapreciala
lgicaexplicada.
Los temporizadores utilizados son de la marca OMRON modelo H3DS. En la ficha tcnica
puedenversetodaslascaractersticasdelosdispositivos.
1.2.7.

Conductores

Se utilizarn conductores unipolares con aislamiento termoplstico de 450/750V a base de


poliolefina (H07Z1KAS), no propagador de incendios y con emisin de humos y opacidad
reducida(Z1).Loscoloresdelosconductoresseguirnlasiguientetabla:
Color
Azulclaro
Negro
Rojo
Amarillo/Verde

Tipodecircuito
Neutrosdecircuitosdepotencia
Fasecircuitodepotencia
Circuitodemando
Tierra(Proteccin)

La seccin de los conductores ser la suficiente para no superar las intensidades mximas
admisiblesdecadacircuito,yquenoexistaunacadadetensinmayordel3%delatensin
nominal.Engeneral,enloscircuitosdemandoseutilizarnconductoresde1mm2deseccin,
mientrasqueparaloscircuitosdepotenciaseutilizarnconductoresde1,5mm2deseccin.La
justificacindeestasseccionessejustificarmsadelante.
1.2.8.

Bornas de conexin

Se utilizarn bornas de conexin para todo el cableado de entrada y salida del cuadro de
control.
SernbornasparacarrilDIN,deuninsimple(unaentradayunasalida)conunpasode5mm.
Tendrnconexinportornillo,yestarnpreparadasparatrabajar,almenos,aunatensinde
hasta0,6kVyunacorrientede20A.Cadabornaestarseparadadelaadyacenteporunaplaca
de separacin y aislamiento del mismo fabricante, de modo que se garantice un correcto
aislamientoelctrico.Secolocarunaplacaterminalenelladodelasbornasquenotengaotra
Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

adyacente. Las bornas correspondientes al circuito de control irn separadas de las


correspondientes al circuito de mando, agrupando las de cada circuito y facilitando as el
reconocimiento de las mismas. Adems, para mayor facilidad de reconocimiento visual, se
utilizarn bornas de color rojo para los conductores de mando, gris para los de potencia, y
amarillo/verde para los conductores de proteccin (tierra). Un ejemplo de bornas a utilizar
seranlasdelamarcaLegrand,serieViking3.Lacorrespondientefichatcnicaaportaelresto
decaractersticas.
1.2.9.

Consideraciones generales del cableado del cuadro de control

Paratodaslasconexionesseutilizarnbornasdepunteraadecuadasacadaconductorparala
prevencindeposiblesaflojamientosdelasmismas.
Paralasconexionesenparalelodedosconductoresseutilizarnbornasespecialesdiseadas
paratalfin.Nuncaseunirnmsdedosconductoresenunamismaborna.
Todoslosconductoresirnidentificadosdemaneraindelebleconlamismamarcaqueaparece
en los esquemas de conexionado. La marca se dispondr a ambos extremos de cada
conductor,enlugarvisible,yasegurandoqueningnconductorllevelamismamarcaqueotro
sinoestalmismopotencial.
1.2.10. Elementos de seguridad
Se dispondr de los elementos de seguridad adecuados con el fin de proteger equipos y
personas.
Esteapartadosedesarrollarmsadelante.

2.

Objetivos funcionales

2.1.

MODO DE REGULACIN

Laregulacindelcuadro,seharmediantelgicacableadayautomatismoselctricos,conun
sistema de control a 230V y 50Hz sobre un circuito de potencia monofsico de 230V y 50Hz
con una potencia mxima de 2,2 kW (esta limitacin la impone la potencia del grupo
electrgeno).Loselementosderegulacinsebasanencriteriosdeseguridadparamquinasy
usuarios.Nosecontemplalaoperacinmanualsobreelsistema,portantosiemprefuncionar
enmodoautomtico.

2.2.

CRONOGRAMA DEL AUTOMATISMO

Enelplanon3puedeverseuncronogramadelfuncionamientodelautomatismodelcuadro
decontrol.

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

3.

Implementacin del modelo

3.1.

CLCULOS DE LAS LNEAS

3.1.1.

Previsin de potencias

Paralarealizacindenuestrosclculosharemoslasiguienteprevisindepotencias:
Cargaslnearespaldada..1500W
Cuadrodemandoyproteccinarespaldar..1500W
Cargaslneaprotegida....100W
AUX2.48W
AUX3.48W
KT1...2W
KT2...2W
Cargaslneaauxiliar.1600W

Lneaprotegida+lnearespaldada...1600W
Potenciamximadelgrupoelectrgeno.2200W

Al carecer de datos de las cargas a las que alimentar el cuadro de mando y proteccin a
respaldar, tomaremos como elemento limitante la potencia aportada por el grupo
electrgeno. Segn el fabricante, es recomendable dimensionar el equipo considerando una
cargaconunconsumodel80%delapotencianominalaportadaporelgrupoparaasegurarel
buenfuncionamientodelmismo.Portanto,ypuestoqueelgrupotieneunapotencianominal
de 2000W, consideraremos unos consumos en la lnea auxiliar de 1600W, y por tanto un
consumode1400Wparaelcuadrodemandoyproteccinarespaldar.Cabedestacarquela
potencia consumida por las bobinas de los contactores no la facilita la ficha tcnica del
producto seleccionado, sin embargo el valor que se le ha asignado coincide con el aportado
por otros fabricantes de productos de similares caractersticas, siendo 20W para las bobinas
mantenidas,yentre38y48Wparalallamadaalasbobinas.Enelcasodelasbobinasdelos
temporizadores,siseconoceeldatoespecfico.
3.1.2.

Lnea General de Alimentacin

SegnlaICTBT14,laseccinmnimadelaLneaGeneraldeAlimentacinserde10mm2en
Cuy16mm2enaluminio.Ennuestrocasoaloptarporconductoresdecobre,instalaremosuna
seccinporfaseyneutrode10mm2.Estaseccinparaunainstalacinentubodesuperficie
empotradoenobraytipodeaislamientoXLPEnospermiteunaintensidadmximaadmisible
de 52A a una temperatura de 40C en el aire segn UNE 204605523. Esto es ms que
suficiente para nuestra aplicacin, y por tanto es innecesario realizar los clculos
correspondientes. Utilizaremos pues una manguera multiconductora con aislamiento de
0,6/1kVdepolietilenoreticulado(R)ycubiertaabasedepoliolefina(RZ1K),nopropagadorde
incendiosyconemisindehumosyopacidadreducida(Z1).

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

3.1.3.

Derivacin Individual

Segn ICTBT15, la seccin mnima de la Derivacin Individual ser de 6mm2 en Cu. Esta
seccincontipodeinstalacindetuboempotradoenparedesaislantesytipodeaislamiento
de Poliolefina admite una intensidad mxima de 27A a una temperatura de 40C en el aire
segn UNE 204605523. Esto es ms que suficiente para nuestra aplicacin, y por tanto es
innecesario realizar los clculos correspondientes. Utilizaremos pues una manguera
multiconductora con aislamiento termoplstico de 450/750V a base de poliolefina (H07Z1K
AS),nopropagadordeincendiosyconemisindehumosyopacidadreducida(Z1).
3.1.4.

Lnea auxiliar

Paraelclculodelalneaauxiliarsupondremosquetieneunalongitudde20metros,desdeel
lugardonde seencuentrael grupo electrgenohastaelpuntodeconsumo msalejado. Por
otrolado,comonoconocemoslaaplicacindelsistema,supondremosunacadamximade
tensin admisible en el conductor de un 3% ya que es la ms restrictiva para circuitos
interiores. De cara a estos clculos consideraremos un factor de potencia de 1, ya que una
carga resistiva pura nos situar en el caso ms desfavorable. Adems dimensionaremos esta
lneaconsiderandolapotenciamximadelgrupoelectrgenoparagarantizarlaseguridadan
estando ste en sobrecarga. El mtodo de instalacin, ser aislado en tubos de montaje
superficialyseutilizarnconductoresunipolaresconaislamientotermoplsticode450/750Va
base de poliolefina (H07Z1KAS), no propagador de incendios y con emisin de humos y
opacidadreducida(Z1).
Pretendemosrealizarlosclculosreglamentariosparalaseccindelosconductoresdelalnea
auxiliar.Laseccinelegidadebercumplirlossiguientescriterios:

Criteriodelaintensidadmximaadmisible.Lamximaintensidadquecircularporel
conductorser:
9,56

(Ec.1)

Segn la tabla A521bis de la norma UNE204605523, un conductor de 1,5mm2 en


lascondicionesquesehanespecificadopuedeadmitirunacorrientede15Aparauna
temperaturaenelairede40C,ycomosecompruebaenlaecuacin1,nuncapasarn
ms de 9,56A. Por tanto, un conductor de 1,5mm2 cumple el criterio de mxima
intensidadadmisible.Habrquecuidarsinembargoelnmerodecircuitosactivosque
pasanporlamismacanalizacin,nopudindosesuperarlos3circuitos,yaqueeneste
caso le sera de aplicacin un factor de correccin de 0,7 a la intensidad mxima
admisible,quedandoen10,5A.
Criterio de la cada de tensin. Como se explic anteriormente, se considerar una
cada de tensin mxima de un 3%, lo que para una tensin de suministro de 230V,
suponen 6,9V. Para el clculo de la seccin mnima segn el criterio de cada de
tensin se puede utilizar, como indica la gua tcnica de aplicacin del REBT, la
siguientefrmula:

1,15

(Ec.2)

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

Hemos considerado para un conductor de cobre y una temperatura estimada en el


mismode70C,unaconductividadde48m/mm2.
Por tanto segn estos clculos, un conductor de 1,5mm2 de seccin cumple con el
criteriodecadadetensin.
Criterio de la intensidad de cortocircuito. Este criterio, aunque es determinante en
instalacionesdealtaymediatensinnoloeseninstalacionesdebajatensinyaque
porunapartelaproteccionesdesobreintensidadlimitanladuracindelcortocircuito
a tiempos muy breves, y adems la impedancia de los cables hasta el punto de
cortocircuitolimitanlaintensidaddecortocircuito.

3.1.5.

Lnea respaldada

Paraelclculodelalnearespaldadasupondremosquetieneunalongitudde25metros.Por
otrolado,comonoconocemoslaaplicacindelsistema,supondremosunacadamximade
tensin admisible en el conductor de un 3% ya que es la ms restrictiva para circuitos
interiores. De cara a estos clculos consideraremos un factor de potencia de 1, ya que una
carga resistiva pura nos situar en el caso ms desfavorable. El mtodo de instalacin, ser
aisladoentubosdemontajesuperficialyseutilizarnconductoresunipolaresconaislamiento
termoplsticode450/750Vabasedepoliolefina(H07Z1KAS),nopropagadordeincendiosy
conemisindehumosyopacidadreducida(Z1).
Pretendemosrealizarlosclculosreglamentariosparalaseccindelosconductoresdelalnea
auxiliar.Laseccinelegidadebercumplirlossiguientescriterios:

Criteriodelaintensidadmximaadmisible.Lamximaintensidadquecircularporel
conductorser:
6,52

(Ec.3)

Segn la tabla A521bis de la norma UNE204605523, un conductor de 1,5mm2 en


lascondicionesquesehanespecificadopuedeadmitirunacorrientede15Aparauna
temperaturaenelairede40C,ycomosecompruebaenlaecuacin3,nuncapasarn
ms de 6,52A. Por tanto, un conductor de 1,5mm2 cumple el criterio de mxima
intensidadadmisible.Habrquecuidarsinembargoelnmerodecircuitosactivosque
pasanporlamismacanalizacin,nopudindosesuperarlos3circuitos,yaqueeneste
caso le sera de aplicacin un factor de correccin de 0,7 a la intensidad mxima
admisible,quedandoen10,5A.
Criterio de la cada de tensin. Como se explic anteriormente, se considerar una
cada de tensin mxima de un 3%, lo que para una tensin de suministro de 230V,
suponen 6,9V. Para el clculo de la seccin mnima segn el criterio de cada de
tensin se puede utilizar, como indica la gua tcnica de aplicacin del REBT, la
siguientefrmula:

0,98

(Ec.4)

Hemos considerado para un conductor de cobre y una temperatura estimada en el


mismode70C,unaconductividadde48m/mm2.
Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

Por tanto segn estos clculos, un conductor de 1,5mm2 de seccin cumple con el
criteriodecadadetensin.
Criterio de la intensidad de cortocircuito. Este criterio, aunque es determinante en
instalacionesdealtaymediatensinnoloeseninstalacionesdebajatensinyaque
porunapartelaproteccionesdesobreintensidadlimitanladuracindelcortocircuito
a tiempos muy breves, y adems la impedancia de los cables hasta el punto de
cortocircuitolimitanlaintensidaddecortocircuito.

3.1.6.

Lnea protegida

Para el clculo de la lnea protegida supondremos que tiene una longitud de 15 metros.
Supondremos una cada mxima de tensin admisible en el conductor de un 3%. De cara a
estosclculosconsideraremosunfactordepotenciade1,yaqueunacargaresistivapuranos
situar en el caso ms desfavorable. El mtodo de instalacin, ser aislado en tubos de
montaje superficial y se utilizarn conductores unipolares con aislamiento termoplstico de
450/750V a base de poliolefina (H07Z1KAS), no propagador de incendios y con emisin de
humosyopacidadreducida(Z1).
Pretendemosrealizarlosclculosreglamentariosparalaseccindelosconductoresdelalnea
auxiliar.Laseccinelegidadebercumplirlossiguientescriterios:

Criteriodelaintensidadmximaadmisible.Lamximaintensidadquecircularporel
conductorser:
0,43

(Ec.5)

Segn la tabla A521bis de la norma UNE204605523, un conductor de 1,5mm2 en


lascondicionesquesehanespecificadopuedeadmitirunacorrientede15Aparauna
temperaturaenelairede40C,ycomosecompruebaenlaecuacin5,nuncapasarn
ms de 0,43A. Por tanto, un conductor de 1,5mm2 cumple el criterio de mxima
intensidadadmisible.Habrquecuidarsinembargoelnmerodecircuitosactivosque
pasanporlamismacanalizacin,nopudindosesuperarlos3circuitos,yaqueeneste
caso le sera de aplicacin un factor de correccin de 0,7 a la intensidad mxima
admisible,quedandoen10,5A.
Criterio de la cada de tensin. Como se explic anteriormente, se considerar una
cada de tensin mxima de un 3%, lo que para una tensin de suministro de 230V,
suponen 6,9V. Para el clculo de la seccin mnima segn el criterio de cada de
tensin se puede utilizar, como indica la gua tcnica de aplicacin del REBT, la
siguientefrmula:

0,04

(Ec.6)

Hemos considerado para un conductor de cobre y una temperatura estimada en el


mismode70C,unaconductividadde48m/mm2.
Por tanto segn estos clculos, un conductor de 1,5mm2 de seccin cumple con el
criteriodecadadetensin.

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

Criterio de la intensidad de cortocircuito. Este criterio, aunque es determinante en


instalacionesdealtaymediatensinnoloeseninstalacionesdebajatensinyaque
porunapartelaproteccionesdesobreintensidadlimitanladuracindelcortocircuito
a tiempos muy breves, y adems la impedancia de los cables hasta el punto de
cortocircuitolimitanlaintensidaddecortocircuito.

3.2.

ESQUEMAS ELCTRICOS

Los esquema elctricos de potencia y mando, se muestran en los planos n5 y n6


respectivamente.Elesquemaunifilarpuedeverseenelplanon4.
Para el sistema de contactores cruzados que impidan la conexin simultnea de la lnea
principal y auxiliar, ser necesario disponer de contactos auxiliares extra de los contactores
KMG1yKMG2.

3.3.

NORMAS DE APLICACIN

Ademsdelasnormascitadasenelpresentedocumentoylascorrespondientesalascitadas
enlasdistintasfichastcnicas,serndeaplicacinlassiguientes:

NormainternacionalIEC61082:preparacindeladocumentacin.
IEC610821(diciembrede1991):Parte1:requerimientosgenerales
IEC610822(diciembrede1993):Parte2:orientacindelasfuncionesenlosesquemas.
IEC610823(diciembrede1993):Parte3:Esquemas,tablasylistasdeconexiones.
IEC610824(marzode1996):Parte4:Documentosdelocalizacineinstalacin.
Norma Europea EN 60617 aprobada por la CENELEC (Comit Europeo de Normalizacin
Electrotcnica)
UNEEN60617),SMBOLOSGRFICOSPARAESQUEMAS
EN 606172 (Junio de 1996): Parte 2: Elementos de smbolos, smbolos distintivos y otros
smbolosdeaplicacin
general.
EN606173(Juniode1996):Parte3:Conductoresydispositivosdeconexin.
EN606174(Juliode1996):Parte4:Componentespasivosbsicos.
EN606175(Juniode1996):Parte5:Semiconductoresytubosdeelectrones
EN 606176 (Junio de 1996): Parte 6: Produccin, transformacin y conversin de la energa
elctrica.
EN606177(Juniode1996):Parte7:Aparatosydispositivosdecontrolyproteccin.
EN 606178 (Junio de 1996): Parte 8: Aparatos de medida, lmparas y dispositivos de
sealizacin.
EN 606179 (Junio de 1996): Parte 9: Telecomunicaciones: Equipos de conmutacin y
perifricos.
EN6061710(Juniode1996):Parte10:Telecomunicaciones:Transmisin
EN6061711(Juniode1996):Parte11:Esquemasyplanosdeinstalacionesarquitectnicasy
topogrficas.
EN6061712(Diciembrede1997):Parte12:Elementoslgicosbinarios.
EN6061713(Febrerode1998):Parte13:Operadoresanalgicos.
Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

10

IEC60445(octubrede1999)Principiosfundamentalesydeseguridadparalainterfazhombre
mquina.
UNEEN604391:Conjuntosdeaparamentadebajatensin.
UNEEN60073:Principiosbsicosydeseguridadparainterfaceshombremquina,elmarcado
ylaidentificacin.
UNEEN 602041: Seguridad en las mquinas. Equipo elctrico en las mquinas. Parte 1:
Requisitosgenerales.
EN50081:Compatibilidadelectromagntica.Normasgenricasdeemisin.
EN 500822: Compatibilidad electromagntica. Normas genricas de inmunidad. Parte 2:
Entornoindustrial.
CEI60447:Interfazhombremquina:Principiosdemaniobra.

3.4.

ELEMENTOS DE SEGURIDAD

3.4.1.

Proteccin contra contactos directos

Los medios a utilizar para la proteccin contra contactos directos seguirn lo descrito en la
normaUNE20460441,yaplicaremoslossiguientes:

Proteccin por aislamiento de las partes activas. Las partes activas debern estar
recubiertasporunaislamientoquenopuedasereliminadomsquedestruyndolo.
Proteccinpormediodebarrerasoenvolventes.Laspartesactivasestarnsituadasen
el interior de envolventes con grado de proteccin segn norma UNE 20324, en
nuestrocaso,laenvolventedelcuadroelctrico,quedeberserfijadoadecuadamente
yserdeunarobustezydurabilidadadecuadas.
Proteccin complementaria por dispositivos de corriente diferencialresidual. Esta
medida es complementaria a las anteriores y no garantiza por si misma la total
proteccin.EsdeaplicacinenestesentidolanormaUNE61008.

Utilizaremos un interruptor automtico diferencial tetrapolar en cabecera, aguas


debajo del cajetn de previsin del ICP, de 25A y sensibilidad de 30mA de clase AC.
Deberserselectivo(CurvaS)ajustadoconuntiempodedisparosuperioralosquese
situarnaguasabajoparagarantizarlaselectividad.

Paralaslneasrespaldadayprotegida(aguasarribadelSAI),seutilizarninterruptores
automticosdiferencialesbipolaresde10A,sensibilidad30mA,claseACycurvaG.

3.4.2.

Proteccin contra contactos indirectos

Paraprotegercontraloscontactosindirectos,loharemosmedianteelcorteautomticodela
alimentacin. El objetivo ser, tras la aparicin de un fallo, limitar el tiempo de duracin de
una tensin de contacto de valor suficiente para causar un riesgo. Se utilizar por tanto un
esquemadeconexionesatierracoordinadamenteconlascaractersticasdelosdispositivosde
proteccin.SeguiremoslareferenciaquenosmarcalanormaUNE205721.

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

11

Utilizamos un esquema de conexiones a tierra TT en el que todas las masas de los equipos
elctricos protegidos por un mismo dispositivo de proteccin, se conectarn a una misma
tomadetierra,ydondesecumplirlaecuacin7:

(Ec.7)

DondeRAeslasumadelasresistenciasdelatomadetierraylosconductoresdeproteccinde
masas, Ia es la corriente diferencialresidual del interruptor automtico diferencial, y U es la
tensindecontactolmiteconvencional.
La seccin de los conductores de proteccin (tierra) sern las mismas que sus
correspondientesdefase,ascomoelrestodecaractersticas.
Como elementos de corte de la alimentacin, se utilizarn los interruptores automticos
diferencialesdescritosanteriormente.
3.4.3.

Proteccin contra sobreintensidades

Tanto para la proteccin de sobrecargas, como de cortocircuitos, se utilizarn interruptores


automticosmagnetotrmicosdecorteomnipolar,conunpoderdecorteadecuado.
Cada interruptor magnetotrmico, tendr una corriente nominal que no podr superar la
mxima corriente admisible para el conductor, por tanto se instalarn los siguientes
dispositivos:

En cabecera, aguas arriba del cajetn de previsin de ICP, se instalar un interruptor


magnetotrmicotetrapolardeintensidadnominal25A,curvaC,6kAparaunatensin
de400.
En la lnea protegida de alimentacin, antes y despus del SAI, se instalarn sendos
interruptoresmagnetotrmicosbipolaresdeintensidadnominal10A,curvaCypoder
decorte6kAparaunatensinde230V.

4.

Configuraciones

4.1.

MODOS DE FUNCIONAMIENTO

Stanby: El sistema recibe energa desde la lnea principal de alimentacin. El grupo


electrgenopermanecerapagado.
Fallodesuministro:Cuandolalneaprincipaldealimentacinsequedasintensin,el
sistemadesconectardelamisma,yarrancarelgrupoelectrgenomedianteuntren
depulsossobrelosterminalesGM1yGM2delgrupo.Unaveztengatensinlalnea
auxiliar,seconectarlalnearespaldadaalsuministrodelgrupo.
Recuperacindesuministro:Cuandolalneaprincipalrecuperelatensin,elsistema
apagarelgrupoelectrgenomedianteuncontactosobrelosterminalesdeparadadel
grupo,yvolveraconectarlalnearespaldadaalalneaprincipaldealimentacin.

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

12

4.2.

PARMETROS DE ENTRADA Y SALIDA DE USUARIO

El sistema diseado es totalmente automtico, y no contempla la manipulacin de los


elementosdelmismoporelusuario.

5.

Bibliografa

[1] BULLEJOS MARTN, David. Apuntes de Electrotecnia Aplicada. Tema 2. Incidentes y


proteccioneselctricas.EscuelaPolitcnicaSuperior.UniversidaddeCrdoba,2014.
[2] BULLEJOS MARTN, David. Apuntes de Electrotecnia Aplicada. Tema 3. Representacin
Normalizada de Circuitos Industriales. Escuela Politcnica Superior. Universidad de Crdoba,
2014.
[3] BULLEJOS MARTN, David. Apuntes de Electrotecnia Aplicada. Tema 3b. Normas de
Esquemas.EscuelaPolitcnicaSuperior.UniversidaddeCrdoba,2014.
[4] BULLEJOS MARTN, David. Apuntes de Electrotecnia Aplicada. Tema 4. Cuadros de
AparellajeyAutomatismos.EscuelaPolitcnicaSuperior.UniversidaddeCrdoba,2014.
[6]AENOR.InstalacionesElctricasenEdificios.UNE20460.Madrid:AENOR,2004.
[7] GOBIERNO de Espaa. Ministerio de Industria Energa y Turismo. REBT. Gua Tcnica de
AplicacinalReglamentoElectrotcnicodeBajaTensin[Enlnea].ActualizadaNoviembrede
2013. [Fecha de consulta: 7 de enero de 2015]. Disponible en:
http://www.f2i2.net/legislacionseguridadindustrial/rebt_guia.aspx

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

13

6.

Planos

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

14

7.

Fichas Tcnicas

Daniel Navas Sedeo. Sistema de Control para alimentacin auxiliar con Grupo Electrgeno

21

Caractersticas

NSYCRN106250

CRN 1000x600x250 una puerta ciega

PVR*: 361.887755102041 EUR


Principal
Estatus comercial

Comercializado

Gama de producto

Spacial CRN

Aplicacin

Multiuso

Tipo de producto o
componente

Armario compacto

Altura nominal de armario

1000 mm

Anchura nominal de armario

600 mm

Profundidad nominal de
armario

250 mm

Tipo de accesorio de
instalaci

Montaje mural

Concentrador de datos

Cierre 1
Puerta 1
Placa de prensaestopas 1
Cuerpo 1

Tipo de puerta

Plano

Tipo de placa de montaje

Sin placa de montaje

Complementario
Particularidad de variante

Lados hechos de una nica seccin doblada


Solda preta con perfil doble formando una rea selada y protegida

Nmero de puertas

1 cara frontal

6 mm inserto cuadrado macho

Reversible 120

Tipo de cierre

Cierre de doble barra 3 mm

Tipo de placa prens

Estndar

Accesibilidad para funcionamiento

Frontal

Piezas extrables

Placa de prensaestopas mediante tornillos


Puerta mediante bisagras

Material

Acero para cuerpo

Acabado de superficie

Polvo de eproxy-polister

Color

Gris RAL 7035

Normas

IEC 62208

Certificados de producto

CUL
UL

Entorno
Grado de proteccin IP

IP66 de acuerdo con IEC 60529

Grado de proteccin IK

IK10 de acuerdo con IEC 62262

Sostenibilidad de la oferta
Estado de la Oferta sostenible
RoHS

Producto Green Premium


Compliant - since 0940 - Schneider Electric declaration of conformity
cin de conformidad de Schneider Electric

REACh

Reference not containing SVHC above the threshold

Perfil ambiental del producto

Disponible

Instrucciones Fin de Vida del producto

No necesita operaciones de reciclaje especficas

07-ene-2015

Declara-

La informacin disponible en este documento contiene descripciones generales y/o caractersticas tcnicas de los productos adjuntos.
En razn de la evolucin de las normativas y del material, las caractersticas indicadas por el texto y las imgenes de este documento no nos comprometen hasta despus de una confirmacin por parte de nuestros servicios.
Est en el deber de cada usuario o integrador de efectuar un completo y apropiado anlisis de riesgos, evaluacin y testo de los productos con respecto a la aplicacin especfica o uso de los productos.
Schneider Electric Industries SAS ni sus filiales comerciales se responsabilizan de la incorrecta interpretacin de la informacin aqu contenida. *(C= A Consultar), Precios por 1 unidad. Los precios de las tarifas pueden sufrir variacin y, por tanto, el material ser siempre facturado a los precios y condicion

Ficha de producto

Caractersticas

LC1D186P7

TeSys D - Contactor - 3P AC-3 - <=440 V 18 A


- bobina 230 V CA
PVR*: 78.01 EUR

Principal

13-ene-2015

Estatus comercial

Comercializado

Gama

TeSys

Nombre del producto

TeSys D

Tipo de producto o
componente

Conector

Nombre del dispositivo

LC1D

Aplicacin de contactor

Control del motor


Carga resistiva

Categora de empleo

AC-1
AC-3

Nmero de polos

3P

Comp. contacto polo

3 NO

[Ue] Tensin aisgnada


de empleo

<= 300 V CC para circuito de alimentacin


<= 690 V CA 25...400 Hz para circuito de alimentacin

[Ie] Intensidad asignada de empleo

32 A (<= 60 C) en <= 440 V CA AC-1 para circuito


de alimentacin
18 A (<= 60 C) en <= 440 V CA AC-3 para circuito
de alimentacin

Potencia del motor en


kW

10 kW en 660...690 V CA 50/60 Hz
10 kW en 500 V CA 50/60 Hz
9 kW en 415...440 V CA 50/60 Hz
7.5 kW en 380...400 V CA 50/60 Hz
4 kW en 220...230 V CA 50/60 Hz

Potencia del motor en


CV

15 hp en 575/600 V CA 50/60 Hz para 3 fases motores


10 hp en 460/480 V CA 50/60 Hz para 3 fases motores
5 hp en 230/240 V CA 50/60 Hz para 3 fases motores
5 hp en 200/208 V CA 50/60 Hz para 3 fases motores
3 hp en 230/240 V CA 50/60 Hz para 1 fase motores
1 hp en 115 V CA 50/60 Hz para 1 fase motores

Control circuit type

CA 50/60 Hz

Tensin de circuito de
control

230 V CA 50/60 Hz

Composicin contacto
auxiliar

1 a + 1 NC

[Uimp] Tensin asignada de choque

6 kV de acuerdo con IEC 60947

Categora de sobretensin

III

[Ith] Intensidad trmica


convencional

32 A en <= 60 C para circuito de alimentacin


10 A en <= 60 C para circuito de sealizacin

Escuadra universal,

300 A en 440 V para circuito de alimentacin de


acuerdo con IEC 60947
250 A CC para circuito de sealizacin de acuerdo
con IEC 60947-5-1
140 A CA para circuito de sealizacin de acuerdo
con IEC 60947-5-1

Capacidad corte nominal

300 A en 440 V para circuito de alimentacin de


acuerdo con IEC 60947

La informacin disponible en este documento contiene descripciones generales y/o caractersticas tcnicas de los productos adjuntos.
En razn de la evolucin de las normativas y del material, las caractersticas indicadas por el texto y las imgenes de este documento no nos comprometen hasta despus de una confirmacin por parte de nuestros servicios.
Est en el deber de cada usuario o integrador de efectuar un completo y apropiado anlisis de riesgos, evaluacin y testo de los productos con respecto a la aplicacin especfica o uso de los productos.
Schneider Electric Industries SAS ni sus filiales comerciales se responsabilizan de la incorrecta interpretacin de la informacin aqu contenida. *(C= A Consultar), Precios por 1 unidad. Los precios de las tarifas pueden sufrir variacin y, por tanto, el material ser siempre facturado a los precios y condicion

Ficha de producto

[Icw] Intensidad asignada de corta duracin admisible

140 A 100 ms circuito de sealizacin


120 A 500 ms circuito de sealizacin
100 A 1 s circuito de sealizacin
84 A <= 40 C 1 min circuito de alimentacin
40 A <= 40 C 10 min circuito de alimentacin
240 A <= 40 C 1 s circuito de alimentacin
145 A <= 40 C 10 s circuito de alimentacin

Capacidad de fusible
asociado

35 A gG en <= 690 V coordinacin tipo 2 para circuito de alimentacin


50 A gG en <= 690 V coordinacin tipo 1 para circuito de alimentacin
10 A gG para circuito de sealizacin de acuerdo
con IEC 60947-5-1

Impedancia media

2.5 MOhm en 50 Hz - Ith 32 A para circuito de alimentacin

[Ui] Tensin asignada


de aislamiento

600 V para circuito de sealizacin certificaciones


UL
600 V para circuito de sealizacin certificaciones
CSA
690 V para circuito de sealizacin de acuerdo con
IEC 60947-1
600 V para circuito de alimentacin certificaciones
UL
600 V para circuito de alimentacin certificaciones
CSA
690 V para circuito de alimentacin de acuerdo con
IEC 60947-4-1

Endurancia elctrica

1 Mciclos 32 A AC-1 at Ue <= 440 V


1.65 Mciclos 18 A AC-3 at Ue <= 440 V

Potencia disipada por


polo

0.8 W AC-3
2.5 W AC-1

Cubierta protectora

Con

Soporte de montaje

Placa
Perfil

Normas

EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 No 14

Certificaciones

BV
CCC
CSA
DNV
GL
GOST
RINA
UL
LROS

Conexiones - terminales

Circuito de alimentacin : orejetas terminales de anillo - dimetro externo: 8 mm


Circuito de control : orejetas terminales de anillo dimetro externo: 8 mm

Par de apriete

Circuito de alimentacin : 1.7 N.m - sobre orejetas


terminales de anillo - con destornillador Philips n 2
screw : M3.5
Circuito de alimentacin : 1.7 N.m - sobre orejetas
terminales de anillo - con destornillador plano 8
screw : M3.5
Circuito de control : 1.7 N.m - sobre orejetas terminales de anillo - con destornillador Philips n 2
screw : M3.5
Circuito de control : 1.7 N.m - sobre orejetas terminales de anillo - con destornillador plano 6 screw :
M3.5

Horas de funcionamiento

4...19 ms apertura
12...22 ms cierre

Nivel de fiabilidad de
seguridad

B10d = 20000000 ciclos contactor con carga mecnica de acuerdo con EN/ISO 13849-1
B10d = 1369863 ciclos contactor con carga nominal
de acuerdo con EN/ISO 13849-1

Endurancia mecnica

15 Mcycles

Cadencia mxima

3600 cyc/h en <= 60 C

Complementario
Tecnologa de bobina

Modulo supresor no incorporado

Lmites tensin del circuito de control

0.85...1.1 Uc en 60 C operactiva 60 Hz
0.8...1.1 Uc en 60 C operactiva 50 Hz
0.3...0.6 Uc en 60 C desconexin 50/60 Hz

Compatibilidad con adaptadores

70 VA en 20 C (cos 0.75) 50 Hz
70 VA en 20 C (cos 0.75) 60 Hz

Trunking flexibles

7 VA en 20 C (cos 0.3) 50 Hz
7.5 VA en 20 C (cos 0.3) 60 Hz

Grabado placa

2...3 W en 50/60 Hz

Tipo de contactos auxiliares

Tipo contacto de espejo (1 NC) de acuerdo con IEC 60947-4-1


Tipo enlazado mecnicamente (1 a + 1 NC) de acuerdo con IEC 60947-5-1

Frecuencia del circuito de sealizacin

25...400 Hz

Corriente de conmutacin mnima

5 mA para circuito de sealizacin

Tensin de conmutacin mnima

17 V para circuito de sealizacin

Tiempo de no superposicin

1.5 ms en excitacin (entre o contacto a y NC)


1.5 ms en desexcitacin (entre o contacto a y NC)

Resistencia al aislamiento

> 10 MOhm para circuito de sealizacin

Entorno
Grado de proteccin IP

410 cara frontal de acuerdo con IEC 60529

Tratamiento de proteccin

TH de acuerdo con IEC 60068-2-30

Grado de contaminacin

Temperatura ambiente de trabajo

-5...60 C

Temperatura ambiente de almacenamiento

-60...80 C

Temperatura ambiente admisible alrededor del dispositivo

-40...70 C a Uc

Altitud mxima de funcionamiento

3000 m sin reduccin temperatura

Canalis cubierta

850 C de acuerdo con IEC 60695-2-1

Resistencia al fuego

V1 de acuerdo con UL 94

Robustez mecnica

Impactos conector cerrado 15 Gn for 11 ms


Impactos contactor abierto 10 Gn para 11 ms
Vibraciones conector cerrado 4 Gn, 5...300 Hz
Vibraciones contactor abierto 2 Gn, 5...300 Hz

Altura

77 mm

Anchura

45 mm

Profundidad

86 mm

Peso del producto

0.33 kg

Solid-state Multi-functional Timer

H3DS

DIN Track Mounted, Standard 17.5-mm Width Timer Range


A wide AC/DC power supply range (24 to 230 VAC/
24 to 48 VDC) reduces the number of timer models
kept in stock.
Eight operating modes (H3DS-M) and four
operating modes (H3DS-S) cover a wide range of
applications.
A wide time setting range of 0.10 s to 120 h.
Two LEDs indicate power and relay status
respectively.
Smart Dial/Selector-locking Mechanism: Prevents
the dials and selectors on the Timers front panel
from being inadvertently operated or being
operated without authorization. The lock can only
be unlocked and locked with an optional pen-type
Lock Key.
Screwless spring terminal type available.
Sticker provided for easy timer identification and
management.
Terminal clamp left open when delivered (screw
terminal type).
Finger protection terminal block to meet
VDE0106/P100.
Enables easy sequence checks through instantaneous outputs for a zero set value at any time
range.
Conforms to EN61812-1 and IEC60664-1
(VDE0110) 4 kV/2.
Conforms to EMC standards (EN50081-1 and
EN50082-2).

RC

Ordering Information
Supply
Supp
y voltage
o age

24 to 230 VAC (50/60Hz)/


24 to 48 VDC

Note:

Control
Co
o output
ou pu

Input
pu type
ype

Operating
Ope
a g mode
ode
(
t )
(see
note)

Model
Screw
terminal type

Screwless
spring
terminal type

Contact output:
SPDT

Voltage input

Eight multi-modes: A,
B, B2, C, D, E, G, J

H3DS-ML

H3DS-MLC

(time-limit output
SPDT))

No-input available

Four multi-modes: A,
B2, E, J

H3DS-SL

H3DS-SLC

Single mode: A

H3DS-AL

H3DS-ALC

The operating modes are as follows:


A: ON-delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/OFF-delay
D: SIgnal OFF-delay
E: Interval
G: Signal ON/OFF-delay
J: One shot

H3DS

H3DS
Model Number Legend
H3DS 1

L
2 3

1.

M: Multi-function type
S: Standard type
A: Single-function type

2.

L: Smart lock mechanism

3.

None:Screw terminal type


C:
Screwless spring terminal type

Accessories (Order Separately)


Lock Key

Y92S-38

Mounting
ou
g Track
ac

50 cm (l) x 7.3 mm (t)

PFP-50N

1 m (l) x 7.3 mm (t)

PFP-100N

1 m (l) x 16 mm (t)

PFP-100N2

End Plate

PFP-M

Spacer

PEP-S

Specifications
General
Item

H3DS-MLj

H3DS-SLj

H3DS-ALj

Operating mode

A: ON-delay (Signal or Power)


B: Flicker OFF start (Signal or Power)
B2: Flicker ON start (Signal or Power)
C: Signal ON/OFF-delay
D: Signal OFF-delay
E: Interval (Signal or Power)
G: Signal ON/OFF-delay
J: One-shot (Signal or Power)

A: ON-delay
B2: Flicker ON start
E: Interval
J: One-shot

Input type

Voltage input

---

Output type

Relay: SPDT

External
connections

Screw terminal, screwless spring terminal

Terminal block

Screw terminal type:


Clamps two 2.5-mm max. bar terminals without sleeves.
Screwless spring terminal type: Clamps two 1.5-mm max. bar terminals without sleeves.

Terminal screw
tightening torque

0.98 N S m max.

Mounting method

DIN track mounting (see note)

Attachment

Nameplate label

Approved standards

UL508, CSA 22.2 No.14


Conforms to EN61812-1, IEC60664-1 (VDE0110) 4 kV/2, VDE0106/P100
Conforms to IEC60947-5-1 (AC-13; 250 V 5 A/AC-14; 250 V 1 A/AC-15; 250 V 1 A/DC-13; 30 V 0.1 A/DC-14;
30 V 0.05 A)
Conforms to EN50081-1 and EN50082-2

Note:

A: ON-delay (fixed)

Can be mounted to DIN Track with a plate thickness of 1 to 2.5 mm.

Time Ranges
Time scale display

Time range

0.1 s

0.1 to 1.2 s

1s

1 to 12 s

0.1 m

0.1 to 1.2 min

1m

1 to 12 min

0.1 h

0.1 to 1.2 h

1h

1 to 12 h

10 h
Note:

10 to 120 h
When the time setting dial is set to 0 for any time scale, the output will operate instantaneously.

H3DS

H3DS
Ratings
Rated supply voltage
(see notes 1 and 2)

24 to 230 VAC (50/60 Hz)/24 to 48 VDC

Operating voltage range

85% to 110% of rated supply voltage

Power reset

Minimum power-off time: 0.1 s

Reset voltage
Power
consumption
p
(
t 3)
(see
note

2.4 VAC/DC max.


H3DS-MLj

AC: approx. 26.9 VA (1.8 W) at 230 VAC


DC: approx. 0.6 W at 24 VDC

H3DS-SLj

AC: approx. 26.5 VA (1.8 W) at 230 VAC


DC: approx. 0.6 W at 24 VDC

H3DS-ALj

AC: approx. 27.1 VA (1.8 W) at 230 VAC


DC: approx. 0.6 W at 24 VDC

Voltage input

Max. permissible capacitance between inputs lines (terminals B1 and A2): 2,000 pF
Load connectable in parallel with inputs (terminals B1 and A1).
H-level: 20.4 to 253 VAC/20.4 to 52.8 VDC
L-level: 0 to 2.4 VAC/DC

Control output

Contact output: 5 A at 250 VAC with resistive load (cos = 1)


5 A at 30 VDC with resistive load (cos = 1)

Ambient temperature

Operating:10C to 55C (with no icing)


Storage: 25C to 65C (with no icing)

Ambient humidity

Operating: 35% to 85%

Note:

1. DC ripple rate: 20% max.


2. Since an inrush current of 0.4 A will occur when using the power supply voltage at 24 VDC, pay careful attention when turning on or
off the power supply to the Timer with a solid-state output such as a sensor.
3. The power consumption is for mode A after the Timer counts the time-up time and for the AC input at 50 Hz. The power consumption
of the H3DS-ML includes the input circuit with the B1 and A1 terminals short-circuited.

H3DS

H3DS
Characteristics
Accuracy of operating time

1% max. of FS (1% 10 ms max. at 1.2-s range)

Setting error

10% 50 ms max. of FS

Signal input time

50 ms min.

Influence of voltage

0.5% max. of FS (0.5% 10 ms max. at 1.2-s range)

Influence of temperature

2% max. of FS (2%10 ms max. at 1.2-s range)

Insulation resistance

100 M min. at 500 VDC

Dielectric strength

Between current-carrying metal parts and exposed non-current-carrying metal parts:


2,000 VAC for 1 min.
Between control output terminals and operating circuit: 2,000 VAC for 1 min.
Between contacts not located next to each other: 1,000 VAC for 1 min.

Vibration resistance

Malfunction: 0.5-mm single amplitude at 10 to 55 Hz


Destruction: 0.75-mm single amplitude at 10 to 55 Hz

Shock resistance

Malfunction: 100 m/s2 3 times each in 6 directions


Destruction: 1,000 m/s2 3 times each in 6 directions

Impulse withstand voltage

3 kV (between power terminals)


4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)

Noise immunity

Square-wave noise generated by noise simulator (pulse width: 100 ns/1 s, 1-ns rise) 1.5 kV

Static immunity

Malfunction: 4 kV
Destruction: 8 kV

Life expectancy

Mechanical: 10 million operations min. (under no load at 1,800 operations/h)


Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
(see note)

EMC

(EMI):
Emission Enclosure:
Emission AC Mains:
Harmonic Current:
Voltage Fluctuation and Flickering:
(EMS):
Immunity ESD:

Case color

Light gray (5Y7/1)

Enclosure rating

IP30 (Terminal block: IP20)

Weight

100 g

Note:

EN50081-1
EN55022 class B (equivalent to EN55011 class B)
EN55022 class B (equivalent to EN55011 class B)
EN61000-3-2
EN61000-3-3
EN50082-2
EN61000-4-2:4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves:
ENV50140: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity RF-interference from Pulse-modulated Radio Waves:
ENV50204: 10 V/m (900 5 MHz) (level 3)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4:2 kV power line (level 3)
2 kV I/O signal line (level 4)

For reference:
A maximum current of 0.15 A can be switched at 125 VDC (cos=1).
A maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).

H3DS

H3DS

Nomenclature
H3DS-MLj/-SLj

Output indicator (orange)


(Lit while Timer output is ON.)
Set time window

Time setting dial (set time)


Lock for time setting dial

Time scale display window and


selector (select one from 1 s,
0.1 s, 1 h, 0.1 h, 10 h, 1 h, 1 m,
and 0.1 m)

Lock for time scale selector

Lock for operating mode selector


Operating mode display window
and selector (select the mode from
A, B, B2, C, D, E, G, and J for the
H3DS-ML, from A, B2, E, and J for
the H3DS-SL)

Attach the enclosed label


here as a nameplate.
(The label is attached to
the Timers DIN Track
hook section at the time
of shipment.)

Power-ON indicator (green)


(Lit while the power is ON.)

H3DS-ALj

Output indicator (orange)


(Lit while Timer output is ON.)
Set time window

Time setting dial (set time)


Lock for time setting dial

Time scale display window and


selector (select one from 1 s,
0.1 s, 1 h, 0.1 h, 10 h, 1 h, 1 m,
and 0.1 m)

Lock for time scale selector

Power-ON indicator (green)


(Lit while the power is ON.)

(Front View)

Operation
Block Diagram
H3DS-MLj
Zero setting
detection
circuit

AC (DC) input

Power supply
circuit

Start input

Oscillation
circuit

Time scale/
unit selectors

Counting
circuit

Input circuit

Operating
mode selector

Output circuit

Indicator
circuit

Power-ON Output
indicator
indicator

H3DS

H3DS
H3DS-SLj/-ALj
AC (DC) input

Power supply
circuit

Zero setting
detection
circuit

Oscillation
circuit

Time scale/
unit selectors

Counting
circuit

Operating
mode selector

Output circuit

Indicator
circuit

Power-ON Output
indicator
indicator

I/O Functions
Item

H3DS-MLj

H3DS-SLj/-ALj

Input

Start

Starts operation.

No input is available.

Output

Control output

Outputs are turned ON according to designated


output mode when preset value is reached.

Outputs are turned ON according to designated


output mode when preset value is reached.

Basic Operation
Setting of Selector
The selectors can be turned clockwise and counterclockwise to select the desired time scale, or operating mode.
Each selector has a snap mechanism that secures the selector at a
given position. Set the selector at a position at which it is secured.
Do not set it midway between two securing positions or a malfunction could result from improper setting.
Selection of Operating Mode (except for H3DS-AL)
The H3DS-ML/-SL can be set to any one of the operating modes A
to J. Turn the operating mode selector with a screwdriver until the
desired operating mode appears in the operating mode display window.
H3DS-ML (8 modes): A, B, B2, C, D, E, G, J (In order of appearance)
H3DS-SL (4 modes): A, E, B2, J, E, E, J, J (In order of appearance)
Note: Letters that appear more than once indicate exactly the
same operating mode.
Selection of Time Scale
The time scale is selected by turning the time scale selector. The
time scales will appear in the following order in the time scale display window on the left of the selector:
1 s, 0.1 s, 1 h, 0.1 h, 10 h, 1 h, 1 m, 0.1 m.
Note: The time scale 1h appears twice. Both instances indicate
exactly the same time scale.

Locking/Unlocking of Selectors and Time Setting Dial


The time setting dial, time scale selector, and operating mode selector can be locked using the Y92S-38 Lock Key, a special pen type
tool that is sold separately. To lock the dial or selectors, insert the
Lock Key in the keyhole to the lower right of the dial or selector and
turn it clockwise until the dial or selector is completely covered with
the red cover. To unlock, turn the Lock Key in the opposite direction.

Key hole

Time scale display


window and selector

Operating mode display


window and selector

H3DS

H3DS
Timing Chart
Note:

1. The minimum power reset time is 0.1 s and the minimum signal input time is 0.05 s.
2. The letter t in the timing charts stands for the set time and ta means that the period is less than the time set.

Operating
mode

Timing chart
t

A: ON-delay

ta

t
Basic operation

Power (A1 and A2)

Power

Start (B1 and A2)


(see note)

**

*
Start
Output relay: NC
15 and 16

t
Output

Output relay: NO
(output indicator)
15 and 18

For power-on operation, impose voltage to the


Start input. The Timer starts operating at the
moment the power is turned on.
Start input is invalid while the Timer is in operation.

**
Power indicator

B:
Flicker OFF
start

ta

ta
Basic operation

Power (A1 and A2)


Power
Start (B1 and A2)
(see note)

*
Start

**

Output relay: NC
15 and 16

Output
Output relay: NO
(output indicator)
15 and 18

For power-on operation, impose voltage to the


Start input. The Timer starts operating at the
moment the power is turned on.
Start input is invalid while the Timer is in operation.

**
Power indicator

B2:
Flicker ON
start

ta

ta

Power (A1 and A2)

Basic operation
Start (B1 and A2)
(see note)

Power
*
Start

Output relay: NC
15 and 16

Output

Output relay: NO
(output indicator)
15 and 18

For power-on operation, impose voltage to the


Start input. The Timer starts operating at the
moment the power is turned on.
Start input is invalid while the Timer is in operation.

**

Power indicator

C:
Signal
ON/OFFdelay

**

ta

ta

Power (A1 and A2)

Start (B1 and A2)


(see note)
Output relay: NC
15 and 16

Basic operation
Power
*

Output relay: NO
(output indicator)
15 and 18

Power indicator

Note:

10

Start
t

Output
*

Start input is invalid while the Timer is in operation.

The start input of the H3DS-MLj model is activated by applying a voltage to B1 and A2 terminals.
The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement).

H3DS

H3DS
Operating
mode
D:
Signal
OFF-delay

Timing chart
t

ta

ta

ta

Power (A1 and A2)

Basic operation
Start (B1 and A2)
(see note)
Power
Output relay: NC
15 and 16

*
Start
t

Output relay: NO
(output indicator)
15 and 18

Output
*

Start input is valid and re-triggerable while the


Timer is in operation.

Power indicator

E: Interval

ta

ta

Basic operation
Power (A1 and A2)
Power
Start (B1 and A2)
(see note)

*
Start

**

Output relay: NC
15 and 16

t
Output

Output relay: NO
(output indicator)
15 and 18

*
**

Power indicator

G:
Signal
ON/OFFdelay

Basic operation
Power (A1 and A2)

Power

Start (B1 and A2)


(see note)
Output relay: NC
15 and 16

*
Start
t

Output relay: NO
(output indicator)
15 and 18

ta

ta

Power (A1 and A2)

Power indicator

Note:

Start input is valid and re-triggerable while the


Timer is in operation.

Basic operation
Power

Start (B1 and A2)


(see note)
Output relay: NC
15 and 16
Output relay: NO
(output indicator)
15 and 18

Output

Power indicator

J:
One-shot
output
(ON delay)

For power-on operation, impose voltage to the


Start input. The Timer starts operating at the
moment the power is turned on.
Start input is valid and re-triggerable while the
Timer is in operation.

*
Start

Approx.
10.6 s
(fixed)

Approx.
10.6 s
(fixed)

Approx.
10.6 s
(fixed)

**

t
Output
*
**

Approx. 10.6 s
(fixed)

For power-on operation, impose voltage to the


Start input. The Timer starts operating at the
moment the power is turned on.
Start input is valid and re-triggerable while the
Timer is in operation.

The start input of the H3DS-MLj model is activated by applying a voltage to B1 and A2 terminals.
The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement).

11

H3DS

H3DS

Dimensions
Note:

All units are in millimeters unless otherwise indicated.

H3DS-MLj/-SLj/-ALj

Surface color:

Light gray 5Y7/1 (OMRON)

Installation
Terminal Arrangement
H3DS-MLj
A1

15

H3DS-SLj/-ALj

B1

A1

15

L
15

15

18

16

18

16

A2

(see note 1)

Note:

16

18

16

A2

(see note 1)

1. DC supply voltage does not require the designation of polarity.


2. The contact symbol for the H3DS is indicated with
contact for conventional timers.

12

18

because it offers multiple operating modes and is different from the delayed

H3DS

H3DS
Input Connections
The inputs of the H3DS-MLj are voltage (voltage imposition or open) inputs.
No-contact Input
(Connection to PNP output sensor.)

No-contact Input
(Connection to NPN output sensor.)

Contact Input

Sensor
Timer

Timer

(+)

A2

24 VDC

Timer

()
(+)
24 VDC
()

B1

A1

B1
Start

A1

A2

Operates with PNP transistor ON

A1

B1
Start
A2

Sensor

Operates with relay ON

Operates with NPN transistor ON

Voltage Input Signal Levels

No-contact
input

1. Transistor ON
Residual voltage: 1 V max.
(Voltage between terminals B1 and A2 must be more than
the rated H-level voltage (20.4 VDC min.).)
2. Transistor OFF
Leakage current: 0.01 mA max.
(Voltage between terminals B1 and A2 must be less than
the rated L-level voltage (2.4 VDC max.).)

Contact
input

Use contacts that can adequately switch 0.1 mA at each


voltage to be imposed. (When the contacts are ON or OFF,
voltage between terminals B1 and A2 must be within the
following ranges:
When contacts are ON: 20.4 to 253 VAC/20.4 to 52.8 VDC
When contacts are OFF: 0 to 2.4 VAC/DC

13

H3DS

H3DS

Accessories (Order Separately)


Note:

All units are in millimeters unless otherwise indicated.

Dimensions
Lock Key
Y92S-38

Mounting Track
PFP-100N, PFP-50N

PFP-100N2

16
7.30.15
4.5

4.5

15

25

25
10

Note:

25
1,000 (500)
(see note)

25
10

350.3

270.15

350.3

15

15 (5)
(see note)

25

25
10

25
1,000

27

25 15
10

29.2

1.5

The values shown in parentheses are for the


PFP-50N.

End Plate
PFP-M

Spacer
PFP-S
10
6.2

16
12

5
1.8

1
35.5 35.3

50

1.8

11.5

34.8

44.3

1.3
10 M4 x 8
pan head
screw

14

24

4.8

16.5

H3DS

H3DS

Precautions
Changing of Setting
NOTICE: Do not change the time scale or operating mode, while
the Timer is in operation or malfunction could result.

Switching Current vs. Ambient Temperature


(When Mounting Two or More H3DS Units Side-by-Side)
Mounting clearance:
50 mm min.

Power Supplies

Mounting
clearance: 10 mm
Mounting
clearance: 5 mm

70

Ambient temperature (C)

The H3DS Series is provided with a transformerless power supply


system. An electric shock may be received if the input terminal or
the output type selector switch is touched while power is being supplied.
Use the bar terminal for wiring the H3DS. Using a stranded-wire terminal may cause a short-circuit due to a stray wire entering into the
Timer.
Both AC and DC power supplies can be connected to the power input terminals without regarding polarity.
With the H3DS only, a DC power supply must be connected to the
power input terminals as designated according to the polarity of the
terminals.
A DC power supply can be connected if its ripple factor is 20% or
less and the mean voltage is within the rated operating voltage
range of the Timer.
Make sure that the voltage is applied within the specified range,
otherwise the internal elements of the Timer may be damaged.
Connect the power supply voltage through a relay or switch in such
a way that the voltage reaches a fixed value at once or the Timer
may not be reset or a timer error could result.
For the power supply of an input device of the H3DS-MLj, use an
isolating transformer, of which the primary and secondary windings
are mutually isolated and the secondary winding is not grounded.

60

Maximum range of
operating ambient
temperature

50

Mounting
clearance: 0 mm

40

30

Load current (A)

(Measurement Condition: Input voltage of 230 VAC)

Input/Output
Relationship between Input and Power Supply
Circuits (H3DS-MLj)
B1
AC/DC
power
supply

A1

A1
Power supply
circuit

Input circuit

B1
Power supply

H3DS-MLj

A2

Start
input

Rectifier circuit

A2

Circuit

Isolation transformer is required.

Installation
If the load current is continuously being supplied to the Timer for a
long period of time, be sure to provide the mounting clearance as
shown in the figure below. If used under the conditions other than
those specified below, the life of internal components may be shortened due to an excessive rise in the internal temperature.

Since the input circuit and the power supply circuit are configured
independently, the input circuit can be turned on or off irrespective of
the on/off state of the power supply.
It must be noted that a voltage equivalent to the power supply voltage is applied to the input circuit.
When connecting a relay or a transistor as an external signal input
device, pay attention to the following points to prevent short-circuiting due to a sneak current to the transformerless power supply.
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not
be different in phase or the terminals will be short-circuited to one
another (refer to the figures below).
Contact or transistor for
external input signal
A1

H3DS

H3DS

Incorrect

H3DS

DIN track
t

B1
H3DS-MLj

Power supply

A2
Short-circuit
current
A1

t
B1

H3DS-MLj

t: Mounting clearance (mm)


A2

15

H3DS

H3DS
Contact or transistor for
external input signal

Environment
A1

B1
H3DS-MLj

Correct

Power supply

A2
Short-circuit
current
A1
B1
H3DS-MLj

A2

The H3DS Series is provided with a transformerless power supply


system.

Input Wires

When using the Timer in an area with excess electronic noise, separate the Timer, wiring, and the equipment which generates the input
signals as far as possible from the noise sources. It is also recommended to shield the input signal wiring to prevent electronic interference.
Organic solvents (such as paint thinner), as well as very acidic or
basic solutions can damage the outer casing of the Timer.
Do not use the Timer in places where it is exposed to dust, corrosive
gas, or direct sunlight.
When storing the Timer, make sure that the ambient temperature
and humidity are within the rated values. Leave the Timer at room
temperature for at least three hours before using the Timer if it has
been stored at an ambient temperature of 10C or below.

Others
If the Timer is mounted on a control board, dismount the Timer from
the control board or short-circuit the circuitry of the power board before carrying out a voltage withstand test between the electric circuitry and non current-carrying metal part of the Timer, in order to
prevent the internal circuitry of the Timer from damage.

The input wires must be as short as possible. If the floating capacity


of wires exceeds 2,000 pF (approx. 17 m for cables with 120 pF/m),
the operation will be affected. Pay particular attention when using
shielded cables.

Precautions for EN61812-1 Conformance


The H3DS as a built-in timer conforms to EN61812-1 provided that
the following conditions are satisfied:
The output section of the H3DS is provided only with basic isolation.
To ensure reinforced isolation required by the EN61812-1, provide
supplementary basic isolation on the load side connected to the output.
The H3DS itself is designed according to the following:

Overvoltage category III


Pollution degree 2

On the above basis:


Operation parts on the front and bottom: Reinforced isolation
With clearance of 5.5 mm and creepage distance of 5.5 mm at
230 VAC
Output: Basic isolation
With clearance of 3 mm and creepage distance of 3 mm at
230 VAC

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.


To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. L098-E1-1A

In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation
Industrial Automation Company
Measuring and Supervisory Controls Department
28th Fl., Crystal Tower Bldg.,
1-2-27, Shiromi, Chuo-ku,
Osaka 540-6028 Japan
Tel: (81)6-6949-6035/Fax: (81)6-6949-6069

16

Printed in Japan
0600-3M (0200) (O)

EXZHELLENT XXI 1000 V


RZ1-K (AS)
Tensin 0,6/1 kV

NORMAS CONSTRUCTIVAS:

NACIONAL/EUROPEA

INTERNACIONAL

UNE 21123-4

UNE-EN
UNE-EN
UNE-EN
UNE-EN

IEC
IEC
IEC
IEC

60332-1-2
50266-2-4
50267
61034-2

CONSTRUCCIN:
1.-

CONDUCTOR:
Cobre flexible clase 5 para instalacin fija (-K).

1
2.-

AISLAMIENTO:
Polietileno reticulado (R).

3.-

CUBIERTA:

Poliolefina termoplstica ignfuga, libre de


halgenos (Z1).

3
APLICACIONES Y CARACTERSTICAS
PRINCIPALES:
La serie de cables EXZHELLENT XXI 1000 V, est constituida
por cables flexibles unipolares y multipolares de 600/1000 V,
correspondiendo su designacin tcnica a RZ1-K (AS).
A partir de la seccin de 50 mm2 inclusive se ofrece la
configuracin SECTORFLEX con conductor sectorial flexible
que, manteniendo idnticas prestaciones elctricas y los mismos terminales y accesorios convencionales que el cable circular, consigue un menor dimetro y peso del cable, incrementando significativamente su manejabilidad y facilidad de
instalacin.
Son cables especialmente indicados para ser instalados en
viviendas (lnea general de alimentacin y derivaciones individuales) segn indica el Reglamento de Baja Tensin en las
correspondientes ITC-BT-14 y 15, en los locales de pblica
concurrencia segn ITC-BT-28, as como en aquellos lugares
donde se pretenda elevar el grado de seguridad.
Los cables EXZHELLENT XXI 1000 V son productos certificados con la marca AENOR.
Es capaz de trabajar a muy baja temperatura (-40 C).
La temperatura mxima del conductor en servicio permanente es de 90 C.
40

60332-1-2
60332-3-24
60754
61034-2

EXZHELLENT XXI 1000 V


RZ1-K (AS)
Tensin 0,6/1 kV

CDIGO

SECCIN

DIMETRO

PESO

EXTERIOR

RADIO DE
CURVATURA

mm2

mm

kg/km

mm

1992106

1x1,5

5,7

50

25

1992107

1x2,5

6,1

60

1992108

1x4

6,7

1992109

1x6

1992110

INTENSIDAD

CAIDA DE TENSIN

AL AIRE(1) ENTERRADA(2) COS =0,8 COS =1


A

V/A.km

V/A.km

21

27

23,65

29,37

25

29

36

14,24

17,62

75

30

38

46

8,873

10,93

7,2

95

30

49

58

5,950

7,288

1x10

8,2

140

35

68

77

3,484

4,218

1992111

1x16

9,2

195

40

91

100

2,240

2,672

1992112

1x25

10,8

285

45

116

128

1,476

1,723

1992113

1x35

11,9

380

50

144

154

1,073

1,224

1992114

1x50

13,5

520

55

175

183

0,773

0,852

1992115

1x70

15,6

725

65

224

224

0,568

0,601

1992116

1x95

17,4

935

70

271

265

0,449

0,455

1992117

1x120

19,4

1.175

80

314

302

0,368

0,356

1992118

1x150

21,4

1.460

90

363

342

0,311

0,285

1992119

1x185

23,3

1.750

95

415

383

0,270

0,234

1992120

1x240

26,6

2.315

135

490

442

0,223

0,177

1992121

1x300

30,2

2.900

155

563

500

0,193

0,142

1992206

2x1,5

8,6

100

35

24

27

23,61

29,37

1992207

2x2,5

9,4

130

40

33

36

14,20

17,62

1992208

2x4

10,5

170

45

45

46

8,839

10,93

1992209

2x6

11,6

220

50

57

58

5,919

7,288

1992210

2x10

13,5

330

55

79

77

3,458

4,218

1992211

2x16

15,5

470

65

105

100

2,218

2,672

1992212

2x25

18,8

705

75

123

128

1,458

1,723

1992213

2x35

21,8

1.010

90

154

154

1,057

1,224

1998214

2x50

21,6

1.200

90

188

183

0,759

0,852

1998215

2x70

25,1

1.650

125

244

224

0,556

0,601

1998216

2x95

28,0

2.130

140

296

265

0,438

0,455

1998217

2x120

31,5

2.705

160

348

302

0,358

0,356

1998218

2x150

34,8

3.345

175

404

342

0,302

0,285

1998219

2x185

38,0

4.025

190

464

383

0,262

0,234

1998220

2x240

43,5

5.340

220

552

442

0,215

0,177

(1) Intensidades mximas admisibles al aire segn norma UNE 20460-5-523, tabla A.52-1 bis, mtodo de instalacin E para cables multipolares y segn
noma UNE 211435 para cables unipolares - Temperatura ambiente de 40 C
(2) Intensidades mximas admisibles enterrado segn norma UNE 20460-5-523, tabla A.52-2 bis, mtodo de instalacin D para cables multipolares y
segn noma UNE 211435 para cables unipolares - Temperatura del terreno de 25 C, profundidad de la instalacin 700 mm y resistividad trmica del
terreno 1,5 K.m/W
Nota: presentacin en bobina. Para presentacin en rollos, los cdigos empiezan por 1997

41

EXZHELLENT XXI 1000 V


RZ1-K (AS)
Tensin 0,6/1 kV

CDIGO

SECCIN DIMETRO

PESO

EXTERIOR

RADIO DE
CURVATURA

INTENSIDAD

CAIDA DE TENSIN

AL AIRE(1) ENTERRADA(2) COS =0,8 COS =1

1992306

mm2
3G1,5

mm
9,0

kg/km
115

mm
40

A
20

A
23

V/A.km
23,61

V/A.km
29,37

1992307

3G2,5

9,9

155

40

26

30

14,20

17,62

1992308

3G4

11,1

205

45

36

38

8,839

10,93

1992309

3G6

12,3

275

50

46

48

5,919

7,288

1992310

3G10

14,3

420

60

65

64

3,458

4,218

1992311

3G16

16,5

605

70

87

82

2,218

2,672

1992312

3x25

20,0

910

80

110

106

1,458

1,723

1992313

3x35

23,3

1.295

95

137

129

1,057

1,224

1998314

3x50

25,3

1.585

130

167

152

0,759

0,852

1998315

3x70

29,6

2.225

150

214

187

0,556

0,601

1998316

3x95

32,8

2.845

165

259

222

0,438

0,455

1998317

3x120

36,9

3.635

185

301

253

0,358

0,356

1998318

3x150

40,8

4.495

205

353

286

0,302

0,285

1998319

3x185

44,5

5.415

225

391

320

0,262

0,234

1998320

3x240

51,0

7.185

310

468

370

0,215

0,177

1992406

4G1,5

9,9

140

40

20

23

23,61

29,37

1992407

4G2,5

10,9

185

45

26

30

14,20

17,62

1992408

4G4

12,2

255

50

36

38

8,839

10,93

1992409

4G6

13,5

340

55

46

48

5,919

7,288

1992410

4G10

15,8

530

65

65

64

3,458

4,218

1992411

4G16

18,3

770

75

87

82

2,218

2,672

1992412

4x25

22,4

1.160

90

110

106

1,458

1,723

1992413

4x35

25,6

1.630

130

137

129

1,057

1,224

1998414

4x50

27,9

2.135

140

167

152

0,759

0,852

1998415

4x70

32,7

2.975

165

214

187

0,556

0,601

1998416

4x95

36,2

3.835

185

259

222

0,438

0,455

1998417

4x120

41,0

4.890

205

301

253

0,358

0,356

1998418

4x150

45,3

6.055

230

353

286

0,302

0,285

1998419

4x185

49,7

7.315

250

391

320

0,262

0,234

1998420

4x240

56,8

9.710

345

468

370

0,215

0,177

42

EXZHELLENT XXI 1000 V


RZ1-K (AS)
Tensin 0,6/1 kV

CDIGO

SECCIN DIMETRO

PESO

EXTERIOR

RADIO DE
CURVATURA

INTENSIDAD

CAIDA DE TENSIN

AL AIRE(1) ENTERRADA(2) COS =0,8 COS =1

1992506

mm2
5G1,5

mm
10,8

kg/km
170

mm
45

A
20

A
23

V/A.km
23,61

V/A.km
29,37

1992507

5G2,5

11,9

225

50

26

30

14,20

17,62

1992508

5G4

13,4

310

55

36

38

8,839

10,93

1992509

5G6

14,9

420

60

46

48

5,919

7,288

1992510

5G10

17,5

650

70

65

64

3,458

4,218

1992511

5G16

20,2

935

85

87

82

2,218

2,672

1992512

5G25

24,8

1.420

100

110

106

1,458

1,723

1992513

5G35

28,4

1.990

145

137

129

1,057

1,224

1992514

5G50

33,1

2.775

170

167

152

0,759

0,852

1992515

5G70

39,0

3.970

195

214

187

0,556

0,601

1992516

5G95

43,4

5.100

220

259

222

0,438

0,455

43

EXZHELLENT XXI 500 V - 750 V


ES 05Z1-K (AS) / H07Z1-K (AS)
Tensin 300/500 V 450/750 V

NORMAS CONSTRUCTIVAS:

NACIONAL/EUROPEA

INTERNACIONAL

UNE 211002

UNE-EN
UNE-EN
UNE-EN
UNE-EN

IEC
IEC
IEC
IEC

60332-1-2
50266-2-4
50267
61034-2

CONSTRUCCIN:
1.-

CONDUCTOR:
Cobre flexible clase 5 para instalacin fija (-K).

2.-

AISLAMIENTO:
Poliolefina termoplstica ignfuga, libre de
halgenos (Z1).

APLICACIONES Y CARACTERSTICAS
PRINCIPALES:
La serie de cables EXZHELLENT XXI, est constituida por
cables flexibles monopolares de 300/500 V en las secciones
de 0,5-0,75 y 1 mm2, correspondiendo su designacin a ES
05Z1-K (AS) y cables de 450/750 V para secciones superiores, correspondiendo a la designacin H07Z1-K (AS).
La serie EXZHELLENT XXI es el producto ms deslizante del
mercado, igualando e incluso superando las prestaciones
ofrecidas por la serie de cables GENLIS.
Esta condicin, conseguida mediante el innovador proceso
de aislamiento Speedy-Skin, le convierte en un producto
SUPERDESLIZANTE.
Cables de obligada instalacin en siguientes ITC del Reglamento de Baja Tensin:
ITC-BT-15

Derivaciones individuales

ITC-BT-28

Locales de pblica concurrencia

Es capaz de trabajar a muy baja temperatura (-40 C).


Los cables EXZHELLENT XXI 500 y 750 V son productos certificados con las marcas AENOR y AENOR <HAR> respectivamente.
La temperatura mxima del conductor en servicio permanente es de 70 C.
10

60332-1-2
60332-3-24
60754
61034-2

EXZHELLENT XXI 500 V


ES 05Z1-K (AS)
Tensin 300/500 V

CDIGO

SECCIN

DIMETRO
EXTERIOR

PESO

RADIO DE
CURVATURA

INTENSIDAD
AL AIRE (1)

CAIDA DE TENSIN
COS =0,8 COS =1

mm2

mm

kg/km

mm

V/A.km

V/A.km

1660103

1x0,5

2,1

10

15

65,94

82,27

1660104

1x0,75

2,3

15

15

44,05

54,92

1660105

1x1

2,5

15

15

33,10

41,24

(1) Intensidades mximas admisibles segn norma UNE 21176, Tabla 7 a) - Temperatura ambiente de 40 C
Nota: presentacin en cajas de 200 metros

EXZHELLENT XXI 750 V


H07Z1-K (AS)
Tensin 450/750 V
CDIGO

1656106
1656107
1656108
1656109
1656110
1656111
1656112
1656113
1656114
1657115
1657116
1657117
1657118
1657119
1657120
1657121

SECCIN

DIMETRO
EXTERIOR

PESO

RADIO DE
CURVATURA

INTENSIDAD
AL AIRE (1)

mm2

mm

kg/km

mm

1x1,5
1x2,5
1x4
1x6
1x10
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300

2,9
3,5
4,1
4,6
6,0
7,0
8,6
9,7
11,5
13,4
15,4
17,2
19,0
20,9
24,2
27,8

20
35
45
65
110
165
250
340
480
670
885
1.120
1.390
1.680
2.245
2.830

20
25
25
30
40
45
55
60
70
80
95
105
115
125
145
170

13
18
23
30
40
54
70
86
103
160
194
225
260
297
350
401

CAIDA DE TENSIN
COS =0,8 COS =1
V/A.km

V/A.km

22,16
13,33
8,302
5,561
3,255
2,090
1,377
0,999
0,720
0,528
0,419
0,342
0,290
0,252
0,208
0,181

27,56
16,54
10,26
6,839
3,958
2,508
1,616
1,148
0,800
0,564
0,427
0,334
0,267
0,220
0,166
0,133

(1) Intensidades mximas admisibles segn norma UNE 20460-5-523, tabla A.52-1 bis, mtodo de instalacin A1 para secciones hasta 50 mm2
y mtodo de instalacin B1 para secciones iguales o superiores a 70 mm2 - Temperatura ambiente de 40 C
Nota: los cdigos que empiezan por 1656 corresponden a la presentacin en cajas hasta 6 mm2 y presentacin en rollos a partir de
10 mm2 y hasta 50 mm2 inclusive. Para la presentacin en bobina los cdigos empiezan por 1657.

11

bornas de conexin con tornillo VikingTM 3

Q Caractersticas y dimensiones (mm)

Bornas para conductor de proteccin

Corriente (A)

UL

Ie

IEC

UL

20
30
50
60
85
115
20
30
30
200
30
50

20
30
50
60
85
115
20
30
30
200
30
50

(1) Bornas FTN

Ref.
0371 70/71/72/73

Ref. 0371 74/75

52.2
45.8

50.5

63
70.5
57
54.4

63
70.5

Terminales de desconexin

Ref. 0371 07/08/67/68

57
54.4

Ref. 0371 79

52.2
45.8

64.6
62

62.9
70.4

46.4
53.9

Ref. 0371 09/69

Ref. 0371 77/78

Ref. 0371 66

57.1
54.5

51.2
58.7

52.2
45.8

46.4
53.9

Ref. 0371 00/01/02/03/


20/21/30/31/60/61/62/ Ref.
63/77/78
0371 04/05/64/65

74.8
72.2

Tensin (V)

62.5
70

51.2
58.7

CSA

UL

IEC

0371 80
500
300
300
15
0371 81 o
250
250
250
6.3
0371 80 + 0375 15
0371 82
0371 83
0371 84
500
300
300
15
0371 85
0371 86
0371 87
250
250
250
10
IEC 60947-7-1/7-3, CSA no. 22-2 no. 158, UL 1059

CSA

15

6.3

6.3

15

15

10

10

2,5

Cortocircuito
Bornas
ensambladas
1.6 W/6.3 A
Pvk = 2 W
2,5 W
Pvk = 2.7 W

Ref.

Bornas
separadas
4 W / 6.3 A
Pvk = 4.75 W
4W
Pvk = 5 W

0371 81 o
0371 80 +
0375 15(1)
0371 87

Principales caractersticas:
Temperatura de utilizacin: - 30C a + 55C
Temperatura mxima de los materiales: + 85C

(1): Con o sin indicador de estado de fusible ref. 0375 25

Tensin de trabajo segn EN 60079-7:

Ref. 0371 80

Ref. 0371 81/82/83/85

71.2

Bornas de 1 nivel: 500 V


Bornas con 2 entradas - 2 salidas: 250 V
Bornas de 2 y 3 pisos: 250 V

12

12

10

Cortocircuito + sobrecarga
Bornas
Bornas
separadas
ensambladas
1.6 W/6.3 A
Pv = 1.65 W
1.6 W
Pv = 1.8 W
-

Ref. 0371 84/86

91.6

84.2

26.8

10

16

35

70

Corriente nominal
(A)

18

23

30

42

57

93

144

Declaracin de conformidad del componente para el cliente


disponible a peticin

Ref. 0371 87

65.5
73

65.5

71.2

26.8

52.3
59.8

90.6
83.1

2,5

46.4
53.9

26.8

Seccin del
conductor (mm2)

(1) Excepto para ref. 0371 76

UL

15

Seccin
nominal
CSA
UL
IEC
2
(mm ) (AWG) (AWG)

Potencia segn EN 60947-7-3


II 1 o 2 G o D Ex e/i/tD/iD II

Las bornas de conexin con tornillo conformes a este certicado son


bornas de conexin de 1, 2 y 3 pisos, y bornas para conductor de
proteccin con base metlica (1) y de plstico (ver lista detallada en
pg. 8)

20

Corriente (A)

Ref.
IEC

Homologados por ATEX:


LCIE 07 ATEX 0010 U-0081

Ref. 0371 76

54.5

46.4
53.9

CSA

UL

71.2

46.5
54

CSA

CSA

83.8
76.3

IEC

0371 00/20/30/60
27
24
0371 01/21/31/61
36
32
0371 02/62
48
41
800
600
600
0371 03/63
63
57
0371 04/64
85
76
0371 05/65
138
125
0371 07/67
27
24
0371 08/68
500
300
300
36
32
0371 09/69
36
32
0371 66
1000 600
600
213
192
0371 77
36
32
800
600
600
0371 78
48
41
Ref. 0371 51: ver bornas para sensores
IEC 60947-7-1, CSA n 22-2 n 158, UL 1059
Ie: Corriente nominal NF C 15100 tabla 52H, columna 4

Seccin
nominal
UL
IEC CSA
2
(mm ) (AWG) (AWG)
2,5
12
12
4
10
10
6
8
8
10
6
6
16
4
4
35
2
2
2,5
12
12
4
10
10
4
10
10
70
000
000
4
10
10
6
8
8

Seccin nominal

IEC (mm2) CSA (AWG) UL (AWG)


0371 70
2,5
12
12
0371 71
4
10
10
0371 72
6
8
8
800
600
600
10
6
6
0371 73(1)
(1)
0371 74
16
4
4
35
2
2
0371 75(1)
0371 76
35
0371 77
4
10
10
800
600
600
0371 78
6
8
8
0371 79
500
300
300
4
10
10
IEC 60947-7-1/7-2, CSA no. 22-2 no. 158, UL 1059
IEC

29.3
41.5

Tensin (V)
Ref.

Tensin (V)

Ref.

49
36.8

Poliamida V2 segn UL 94, 960C segn IEC EN 60695-2-11


Bornas de conexin

Bornas de funciones

Borna para accionador ref. 0371 52

Tensin (V)

Corriente (A)

Ref.
IEC

CSA

UL

IEC

CSA

UL

1
30

1
30

0371 53
250
0371 54
250
1
0371 55
500
300
300
1
0371 56 12 a 24 12 a 24 12 a 24
32
IEC 60947-7-1, CSA n 22-2 n 158, UL 1059

Ref. 0371 53/54

IEC
(mm2)
2,5
2,5
4
4

CSA
(AWG)
10
10

UL
(AWG)
10
10

Hacia los
accionadores
Seal
comn

Seal

Fase
Neutro

Automatizacin

Ref. 0371 55/56

71.2
65.9

Borna FNT ref. 0371 52

Seccin nominal

Peine de
interconexin
ref. 375 47

74.8
72.2
26.8

46.5
54

62.5
70

Bornas de desconexin para mediciones


Tensin (V)

Corriente (A)

Seccin nominal

Ref.
0371 92

IEC

CSA

UL

IEC

CSA

UL

800

24

CSA
UL
IEC
(mm2) (AWG) (AWG)
4
-

IEC EN 60947-7-1

Esquemas
Ref. 0371 53

Ref. 0371 92

Ref. 0371 55

73.2

62
69.5

Ref. 0371 54

Ref. 0371 56
+

Diodo para ref. 0371 54/55


- 1N4007 tipo 1A
- corriente continua = 1 A
- tensin inversa de cresta 1000 V
- corriente inversa 5 _A a 25C

Principio de cableado de las bornas de medicin ref. 0371 92


Circuito con ampermetro
Circuito con vatmetro

Bornas para sensores y accionadores FNT


Tensin (V)

Corriente (A)

Ref.
IEC

CSA

UL

Ie

IEC

CSA

0371 51
400
300
300
27
24
20
0371 52
IEC 60947-7-1/7-2, CSA n 22-2 n 158, UL 1059
Ie: Corriente nominal NF C 15100 tabla 52H, columna 4

UL
20

Seccin
nominal
CSA
UL
IEC
(mm2) (AWG) (AWG)
2,5

12

12

Ref. 0371 51/52

L1

Posicin
normal

84.5

Posicin
de prueba

Posicin de
cortocircuito

L2
L3

67.4
74.9

38.8

Por cada circuito:


2 Bornas de desconexin para mediciones Ref. 0371 92
4 Tomas de medicin para clavija de 4
mm Ref. 0375 77
1 Tapa terminal Ref. 0375 57
1 Derivacin con clavijas de 4 mm

Longitudes peladas (mm)


Principio de cableado
Borna para sensor ref. 0371 51
Sensores
Seal
Seal
Alimentacin (compartida)
Automatizacin
Peine de
interconexin
ref. 375 47
Alimentacin
oF-N

Paso de la borna
con tornillo (mm)
5
6
8
10
12
15
22

N
PE

Por cada circuito:


10 Bornas de desconexin para mediciones
Ref. 0371 92
12 Tomas de medicin para clavija de 4 mm
Ref. 0375 77
1 Tapa terminal Ref. 0375 57
3 Derivacin con clavijas de 4 mm

Conductor rgido o exible


6a8
10 a 12
13 a 17
14 a 18
15 a 22

Proteccin contra riesgos de incendio y pnico en


establecimientos de acceso pblico/Recomendacin
UTE C 12-201
Art. EL 3, deniciones: "Las instalaciones de seguridad son aquellas
que deben estar preparadas y puestas en servicio para asegurar la
evacuacin del pblico" o facilitar la intervencin de los equipos de
primeros auxilios. Art. EL 16, circuitos de alimentacin elctrica de
las instalaciones de seguridad seccin 1a: "los correspondientes
dispositivos de unin y derivacin y sus envolventes, excepto los
sistemas de impermeabilizacin, deben superar el ensayo con hilo
incandescente tal como se dene en la normativa en vigor, siendo la
temperatura del hilo incandescente de 960 C". Las bornas Viking 3
satisfacen el ensayo con hilo incandescente a 960 C segn la norma
IEC 60695-2-11

21

Caractersticas tcnicas del producto


CDC425M
Int. diferencial tipo AC, 4P, 25A, 30mA

Imagen similar (La imagen muestra


_CDC440M_)
Caractersticas tcnicas

Nmero de polos

4P

Corriente asignada nominal

25

Tensin asignada de empleo en alterna

230/400

Frecuencia asignada

50 Hz

Tipo de conexin

Jaula con tornillo

Seccin de conexin en cable flexible

16 mm

Salvo modificaciones tcnicas

Caractersticas tcnicas del producto


CDC728M
Int. diferencial tipo AC, 2P, 25A, 30mA

Imagen similar (La imagen muestra


_CDC748M_)
Caractersticas tcnicas

Nmero de polos

2P

Corriente asignada nominal

25

Corriente diferencial asignada

30 mA

Tipo de proteccin diferencial

AC

Tensin asignada de empleo en alterna

127/230

Frecuencia asignada

50 Hz

Tipo de conexin

Jaula con tornillo

Seccin de conexin en cable flexible

16 mm

Salvo modificaciones tcnicas

Caractersticas

18430

Interruptor C120H 4 polos 25 A curva B


PVR*: 278.512 EUR

Principal
Estatus comercial

Comercializado

Aplicacin

Distribucin

Gama de producto

Dardo Plus

Tipo de producto o
componente

Disyuntor

Nombre del dispositivo

C120H

Nmero de polos

4P

Nmero de polos protegidos

[In] corriente nominal

25 A en 30 C

Tipo de red

CA

Tipo de unidad de control

Trmico-magntico

Cdigo de curva de disparo ins

Poder de corte

15 kA Icu de acuerdo con EN/IEC 60947-2 - <= 500


V CC
30 kA Icu de acuerdo con EN/IEC 60947-2 230...400 V CA 50/60 Hz
15 kA Icu de acuerdo con EN/IEC 60947-2 400...415 V AC 50/60 Hz
10 kA Icu de acuerdo con EN/IEC 60947-2 - 440 V
AC 50/60 Hz
15000 A Icn de acuerdo con IEC 60898-1 230...400 V AC 50/60 Hz

Aptitud al seccionamiento

S de acuerdo con IEC 60947-2

Complementario
Frecuencia de la red

50/60 Hz

Lmite de enlace magntico

3...5 x In

[Ics] poder de corte en servicio

7.5 kA 50 % x Icu de acuerdo con EN/IEC 60947-2 - 400...415 V AC 50/60 Hz


15 kA 50 % x Icu de acuerdo con EN/IEC 60947-2 - 230...400 V AC 50/60 Hz
5 kA 50 % x Icu de acuerdo con EN/IEC 60947-2 - 440 V AC 50/60 Hz
7500 A 50 % x Icu de acuerdo con IEC 60898-1 - 230...400 V AC 50/60 Hz

1 tornillo

3 de acuerdo con IEC 60898-1

[Ui] Tensin asignada de aislamiento

500 V AC 50/60 Hz de acuerdo con EN/IEC 60947-2

[Uimp] Tensin asignada de choque

6 kV de acuerdo con EN/IEC 60947-2

Indicacin de contacto positivo

Tipo de control

Maneta

Sealizaciones en local

Indicacin encendido/apagado

Modo de montaje

Ajustable en clip

Soporte de montaje

Perfil DIN simtrico de 35 mm

Compatibilidad de juego de bar

Pasos de 9 mm

12

Altura

81 mm

Anchura

108 mm

Profundidad

73 mm

Peso del producto

0.82 kg

Endurancia mecnica

20000 ciclos

Endurancia elctrica

10000 ciclos de acuerdo con IEC 60947-2

Conexiones - terminales

Terminales de tipo tnel Flexible cableado(s) 1.5...35 mm max


Terminales de tipo tnel rgido cableado(s) 1...50 mm max

14-ene-2015

La informacin disponible en este documento contiene descripciones generales y/o caractersticas tcnicas de los productos adjuntos.
En razn de la evolucin de las normativas y del material, las caractersticas indicadas por el texto y las imgenes de este documento no nos comprometen hasta despus de una confirmacin por parte de nuestros servicios.
Est en el deber de cada usuario o integrador de efectuar un completo y apropiado anlisis de riesgos, evaluacin y testo de los productos con respecto a la aplicacin especfica o uso de los productos.
Schneider Electric Industries SAS ni sus filiales comerciales se responsabilizan de la incorrecta interpretacin de la informacin aqu contenida. *(C= A Consultar), Precios por 1 unidad. Los precios de las tarifas pueden sufrir variacin y, por tanto, el material ser siempre facturado a los precios y condicion

Ficha de producto

Longitud de pelado de cable

15 mm

Par de apriete

3.5 N.m

Proteccin de fugas a tierra

Bloque independiente

Entorno
Normas

EN/IEC 60947-2
IEC 60898-1

Certificados de producto

GOST

Etiquetas de calidad

NF

Grado de proteccin IP

IP20 de acuerdo con IEC 60529

Grado de contaminacin

3 de acuerdo con IEC 60947-2

Tropicalizacin

2 de acuerdo con IEC 60068-1

Humedad relativa

95 % 55 C

Altitud mxima de funcionamiento

2000 m

Temperatura ambiente de trabajo

-30...60 C

Temperatura ambiente de almacenamiento

-40...70 C

Caractersticas

A9K17210

Interruptor automtico magnetotrmico - iK60N


- 2P - 10 A - curva C

PVR*: 27.99275 EUR


Principal
Estatus comercial

Comercializado

Aplicacin

Distribucin

Gama

Acti 9

Tipo de producto o
componente

Disyuntor en miniatura

Nombre del producto

IK60

Nombre del dispositivo

IK60N

Nmero de polos

2P

Nmero de polos protegidos

[In] corriente nominal

10 A en 30 C

Tipo de red

CA

Tipo de unidad de control

Trmico-magntico

Cdigo de curva de disparo ins

Poder de corte

6000 A Icn de acuerdo con EN/IEC 60898-1 - 400 V


CA 50/60 Hz
6000 A Icn de acuerdo con EN/IEC 60898-1 - 230 V
CA 50/60 Hz

Aptitud al seccionamiento

S de acuerdo con EN/IEC 60898-1

Complementario
Frecuencia asignada de empleo

50/60 Hz

Lmite de enlace magntico

5...10 x In

[Ics] poder de corte en servicio

6000 A 100 % x Icu de acuerdo con EN/IEC 60898-1 - 400 V CA 50/60 Hz


6000 A 100 % x Icu de acuerdo con EN/IEC 60898-1 - 230 V CA 50/60 Hz

1 tornillo

3 de acuerdo con EN/IEC 60898-1

[Ui] Tensin asignada de aislamiento

440 V CA 50/60 Hz de acuerdo con EN/IEC 60898-1

[Uimp] Tensin asignada de choque

4 kV

Tipo de control

Maneta

Sealizaciones en local

Indicacin encendido/apagado

Modo de montaje

Ajustable en clip

Soporte de montaje

Carril DIN

Pasos de 9 mm

Altura

85 mm

Anchura

36 mm

Profundidad

78.5 mm

Peso del producto

200 g

Color

Blanco

Endurancia mecnica

20000 ciclos

Endurancia elctrica

10000 ciclos

Descripcin de las opciones de bloqueo

Dispositivo de cierre con candado

Conexiones - terminales

Terminal tipo tnel, arriba o abajo Flexible cableado(s) 1...16 mm max


Terminal tipo tnel, arriba o abajo rgido cableado(s) 1...25 mm max

Longitud de pelado de cable

14 mm arriba o abajo

13-ene-2015

La informacin disponible en este documento contiene descripciones generales y/o caractersticas tcnicas de los productos adjuntos.
En razn de la evolucin de las normativas y del material, las caractersticas indicadas por el texto y las imgenes de este documento no nos comprometen hasta despus de una confirmacin por parte de nuestros servicios.
Est en el deber de cada usuario o integrador de efectuar un completo y apropiado anlisis de riesgos, evaluacin y testo de los productos con respecto a la aplicacin especfica o uso de los productos.
Schneider Electric Industries SAS ni sus filiales comerciales se responsabilizan de la incorrecta interpretacin de la informacin aqu contenida. *(C= A Consultar), Precios por 1 unidad. Los precios de las tarifas pueden sufrir variacin y, por tanto, el material ser siempre facturado a los precios y condicion

Ficha de producto

Par de apriete

2 N.m arriba o abajo

Proteccin de fugas a tierra

Sin

Entorno
Normas

EN/IEC 60898-1

Certificaciones

Aenor

Grado de proteccin IP

IP20 de acuerdo con IEC 60529

Grado de contaminacin

2 de acuerdo con EN/IEC 60898-1

Categora de sobretensin

III

Temperatura ambiente de trabajo

-25...60 C

Temperatura ambiente de almacenamiento

-40...85 C

Sostenibilidad de la oferta
Estado de la Oferta sostenible
RoHS

Producto Green Premium


Compliant - since 1001 - Schneider Electric declaration of conformity
cin de conformidad de Schneider Electric

REACh

Reference not containing SVHC above the threshold

Perfil ambiental del producto

Disponible

Instrucciones Fin de Vida del producto

No necesita operaciones de reciclaje especficas

Descargar Perfil Medioambiental

Declara-