Sunteți pe pagina 1din 1

DAMAC TENORA (P027-DXB-2010)

Submittal/Reference No : MEP-065 dated 29 Dec 2014


Submittal Content
: Chilled water treatment system
Product
:
Manufacturer
: Cullingan international/Chilled water
treatment

Installer
:
_______________________________________________________________
SCL Engineers review comments:

1. No Objection for Cullingan as Chilled water treatment agency.


2. Provide details with drawing for calculation of system volume for
chemical dosing.
3. Provide dosing arrangement diagram with manual and dosing units as
per chilled water pump room layout.
4. Provide schematic drawing details of fill in, test drain points to cover
complete circuit.
5. Provide risk assessment and safety matrix to control hazard as listed in
the MSDS.
6. Disposal waste considerations must be provided for review before
application.
7. Warranty details to be provided.

SHANKLAND COX LIMITED


GF/RA/jm/10/12/2014

S-ar putea să vă placă și