Overload relay setting and calculation

Overload relay is the one of important device for motor control.It can prevent our motor from
overheat or winding burning due overload of ampere.
We need to setting the value of overload relay properly depend on our application and motor full load
ampere.If we setting low from FLA,it can cause motor trip c0ntinues and process not running
smoothly.
But if we setting to high from FLA,the overload relay cannot protect the motor if overload happen.It
can cause the motor failure or winding burns.So we must calculated and get a right setting for the
overload relay.

How to setting Overload Relay protection?


Basically to setting the overload value,we refer to this formula :
1) IB In IZ
IB = Anticipated operating current of the circuit
IZ = Current carrying capacity of conductor or cable or Motor
In = Rated current of protective device
2) I2 1,45 x IZ
Note:
IZ = Current carrying capacity of conductor or cable or Motor
For adjustable protective devices, In corresponds to the value set.
I2 = The current which causes tripping of the protective device under the conditions specified in the
equipment regulations (high test current).

Common practice

Normally for overload relay setting depend on FLA ( Full Load Ampere ) of motor.We can see at
the NAMEPLATE of motor.Normally setting for overload is 5% until 10 % more than FLA.
But it is depend on operation and functional of motor.For more detail setting,please refer manual
guide of motor from manufacture.
We also can setting overload relay value depend on value of service factor motor.Example if service
factor 1.15,we can setting 125% from FLA and if service factor is 1.0,we can setting 115% from FLA
of motor.

Manual and automatic reset.


Normally,overload relay have this 2 reset function selection.We can choose manual or automatic
reset after it trigger overload from motor.
I recommended for manual reset function because we can know when it trip and we can
troubleshooting the root cause for tripping issue.So after we found the root cause, we can reset back
the overload relay and can continue the operation.