Sunteți pe pagina 1din 28

PRACTICAL TRAINING

REPORT

SESSION 2012-16
Submitted To
Mr. Vikash Gupta
H.O.D.
(Electrical Engineering
Department)

Submitted By
Durgesh Maneshwar
ID- 2012UEE1168
Batch- E2

Department Of Electrical Engineering

ACKNOWLEDGEMENT
This summer training is of an immense academic record and value for the
student of any professional course and for the Engineering student who
have to be in the industry with the theoretical knowledge; this practical
experience gives an extra confidence in his performance.
With grateful heart I would like to remember the persons who have helped
me during the course of my internship program. I wish to place on record
my words of gratitude to Mr. Vikash Gupta , HoD , Department of
Electrical Engineering at Malaviya National Institute of Technology,
Jaipur for his efforts and for technical as well as moral support.
I would like to thanks the Mr. Anurag Vats (AEN), 132kv Hybrid GSS,
SMS Stadium , Jaipur that gave me the honour to complete my summer
training in their substation. I would like to thanks all the employees &
associates of 132kv Hybrid GSS, SMS Stadium , Jaipur who really
helped me in understanding all the functions and activities of the
Substation from time to time.
Lastly I would like to thank all those who helped me in any way in my
summer training.

CHAPTER 1

1.1 NEED OF 132 KV SUBSTATION


132KV Sub-Station forms an important link between Transmission network and Distribution network. It
has a vital Influence of reliability of service. Apart from ensuring efficient transmission and Distribution
of power, the sub-station configuration should be such that it enables easy maintenance of equipment
and minimum. interruptions in power Supply. Sub-Station is constructed as near as possible to the load
center. The voltage level of power transmission is decided on the quantum of power to be transmitted
to the load center.
This 132 KV hybrid GSS is one of the main power supply in Jaipur city.

1.2 SPECIFICATIONS OF SMS GSS

Total cost- 28.31 crore


Total capacity 2*50 MVA

1.3 Unique features of SMS hybrid GSS


Indias first hybrid grid substation where 145KV hybrid module and 36KV GIS is used.
A conventional outdoor substation requires 25000 sq. meters for 132KV grid but hybrid
substation was constructed only in 2100 sq. meter of land area.
Automatic/Scada system based on IEC 61850 standards.
Digital Communication System.

1.4 Equipments installed at GSS


Two Power Transformer of capacity 50 MVA
Lightning Arrester 132KV and 33KV
Wave trap
Relays
Isolator
Bus bars
PLCC
PASS
Capacitive voltage Transformer

1.5 FEEDERS
1.5.1 Incoming Feeders
132 KV Sanganer
132 KV Mansarovar
1.5.2 Outgoing Feeder
33kv Gautam Nagar
33kv Stadium
33kv Vidhansabha
33kv Secretariate
33kv Ramniwas Bagh
33kv Bisalpur
33kv Station

CHAPTER 2

2.1 Transformer
2.1.1 Power Transformer
Power Transformer is a static machine, which transforms the potential of alternating current at same
frequency. It means the transformer trans- forms the low voltage into high voltage and high voltage to
low voltage at same frequency. It works on the principle of static induction principle. When the energy is
transformed into a higher voltage, the transformer is called step up transformer but in case of other is
known as step down transformer.
The working principle of transformer is very simple. It depends upon Faraday's law of electromagnetic
induction. Actually, mutual induction between two or more winding is responsible for transformation
action in an electrical transformer.

Figure : Power Transformer

2.1.2 Current Transformer


A current transformer (CT) is used for measurement of alternating electric currents. Current
transformers, together with voltage (or potential) transformers (VT or PT), are known as instrument
transformers. When current in a circuit is too high to apply directly to measuring instruments, a current
transformer produces a reduced current accurately proportional to the current in the circuit, which can
be conveniently connected to measuring and recording instruments. A current transformer isolates the
measuring instruments from what may be very high voltage in the monitored circuit. Current
transformers are commonly used in metering and protective relays in the electrical power industry.

Figure :Current Transformer

Figure :Capicitor Voltage Transformer

2.1.3 Capacitive Voltage Transformer


A capacitor voltage transformer (CVT or CCVT), is a transformer used in power systems to step down
extra high voltage signals and provide a low voltage signal, for metering or operating a protective relay.

In its most basic form, the device consists of three parts: two capacitors across which the transmission
line signal is split, an inductive element to tune the device to the line frequency, and a voltage
transformer to isolate and further step down the voltage for the metering devices or protective relay.
In the conventional potential transformer we use the coupling capacitor but in CVT this is eliminated and
if we use conventional Potential Transformer in yard ,this is expensive due to the fact that the
transformer ratio is high and the size of PT is high than CVT of same capacity.Thats why CVTs are used in
substation.

2.2 CIRCUIT BREAKER


2.2.1 Introduction
A circuit breaker is an automatically operated electrical switch designed to protect an electrical circuit
from damage caused by overload or short circuit. Its basic function is to detect a fault condition and
interrupt current flow.

2.2.2 Working
The circuit breaker actually makes a physical separation in the current-carrying or conducting element
by inserting an insulating medium sufficient to prevent current from continuing to flow. In so doing, the
persistence of an arc across the gap is prevented. opened by drawing out an arc between contacts until
the arc can no longer support itself. The arc formed when The circuit is usually the contacts of a circuit
breaker move apart to interrupt of a circuit is a conductor made up of ionized particles of the insulating
materials. Whenever voltages and currents are large other forms of insulation are used in place or air to
extinguish the arc as quickly as possible.
Whenever fault occurs in the circuit breaker, relay connected to the current transformer CT actuates
and closes its contacts. Current flows from the battery in the trip circuit As soon as the trip coil of the
circuit breaker gets energized the circuit breaker operating mechanism is actuated and it operates for
the opening mechanism.
Different types of circuit breakers are explained in subsequent sections of this chapter.

2.2.3 Types of Circuit Breaker


Oil circuit breaker
Air circuit breaker
SF6 circuit breaker

Vacuum circuit breaker

2.2.4 SF6 Circuit Breaker


A circuit breaker in which the current carrying contacts operate in sulphur hexafluoride or SF6 gas is
known as an SF6 circuit breaker.
In 132KV SMS hybrid GSS only SF6 is used.

2.3 INSULATORS
2.3.1 Introduction
It is defined as An electrical insulator is a material whose internal electric charges do not flow freely,
and therefore make it impossible to conduct an electric current under the influence of an electric field.

Figure : Insulators

2.3.2 Need of the insulators


Electrical Insulator must be used in electrical system to prevent unwanted flow of current to the earth
from its supporting points. The insulator plays a vital role in electrical system. Electrical Insulator is a
very high resistive path through which practically no current can flow. In transmission and distribution
system, the overhead conductors are generally supported by supporting towers or poles. The towers
and poles both are properly grounded. So there must be insulator between tower or pole body and

current carrying conductors to prevent the flow of current from conductor to earth through the
grounded supporting towers or poles.
The main cause of failure of overhead line insulator, is flash over, occurs in between line and earth
during abnormal over voltage in the system. During this flash over, the huge heat produced by arcing,
causes puncher in insulator body. Viewing this phenomenon the materials used for electrical insulator,
has to posses some specific properties.

2.3.3 Properties of Insulating Material


For successful utilization, this material should have some specific properties as listed below1. It must be mechanically strong enough to carry tension and weight of conductors.
2. It must have very high dielectric strength to withstand the voltage stresses in High Voltage system.
3. It must possesses high Insulation Resistance to prevent leakage current to the earth.
4. The insulating material must be free from unwanted impurities.
5. It should not be porous.
6. There must not be any entrance on the surface of electrical insulator so that the moisture or gases
can enter in it.
7. There physical as well as electrical properties must be less effected by changing temperature.

2.3.4 Types of Insulators


There are mainly three types of insulator used as overhead insulator likewise
1. Pin Insulator
2. Suspension Insulator
3. Strain Insulator
4. Stray insulator
5. Shackle insulators

2.4 ISOLATOR
2.4.1 Introduction
Isolator is defined as Isolator is a manually operated mechanical switch which separates a part of the
electrical power system normally at off load condition.

2.4.2 Need of Isolators


Circuit breaker always trip the circuit but open contacts of breaker cannot be visible physically from
outside of the breaker and that is why it is recommended not to touch any electrical circuit just by
switching off the circuit breaker. So for better safety there must be some arrangement so that one can
see open condition of the section of the circuit before touching it. Isolator is a mechanical switch which
isolates a part of circuit from system as when required. Electrical isolators separate a part of the system
from rest for safe maintenance works.

2.4.3 Working

Isolator is located on both the sides of a circuit breaker. They are opened after the opening of CB and
are closed before the closing of CB. While doing maintenance on CBs, they are opened and earthing
switch is closed. They are always operated on no-load as they dont have arc extinguishing medium

Figure : Isolato

2.5 BUSBAR
2.5.1 Introduction
In electrical power distribution, a busbar is a metallic strip or bar (typically copper, brass or aluminium)
that conducts electricity within a switchboard, distribution board, substation, battery bank, or other
electrical apparatus. Its main purpose is to conduct a substantial current of electricity.
There are many different electrical bus system schemes available but selection of a particular scheme
depends upon the system voltage, position of substation in electrical power system, flexibility needed in
system and cost to be expensed.

2.5.3 Types of Busbars

Single Bus System


Single Bus System with Bus Sectionalizer
Double Bus System
Double Breaker Bus System

Main and Transfer Bus System


Double Bus System with Bypass Isolators
Ring Bus System

Figure : Busbars

2.6 LIGHTNING ARRESTER


2.6.1 Introduction
A lightning arrester is a device used on electrical power systems and telecommunications systems to
protect the insulation and conductors of the system from the damaging effects of lightning. The typical
lightning arrester has a high-voltage terminal and a ground terminal.
A lighting arrester is a piece of equipment that is designed to protect electrical systems and components
from damages that can be caused by surges of electricity. Such surges can be the result of lightning or
electrical switching and can be very dangerous, especially for power system equipment.
Different types of LAS are explained in subsequent sections of this chapter

2.6.2 Types of Lightning Arrester


Rod gap arrester
Horn gap arrester
Multigap arrester

Expulsion type arrester


Valve type arrester
General rating Recommendation for lightning arrester
1. 10kv rated lightning arrester- Arrester of this type are used in case of power station and
EHV substation
2. 5kA rated lightning arrester- Arrester of this capacity normally are used in case of high
voltage substations having system voltages as 66 kV or less.
3. 2.5 kA rated lightning Arrester- - Arrester of these ratings are used in case of system upto
11 KV.
4. 1.5 KA rated lightning Arrester- Arrester of these ratings are used in case of distribution
system.
Location of lightning arrester
1. Very close to the equipment to be protected and connected with shortest lead on both the
linesandground side to reduce the inductive effect of leads while discharging the surge current.
2. In order to ensure the protection of transformer windingsit is desirable to inter connect the
ground lead of the arresterwith the tank and also the neutral of secondary. This interconnection
reduces the stress imposed on the transformer windings by the surge current.

Figure : Lightning Arrester

2.7 PLCC

2.7.1 Introduction
Power Line Carrier Communication(PLCC), is an approach to utilize the existing power lines for the
transmission of information. In todays world every house and building has properly installed electricity
lines. Power Line Carrier Communication PLCC By using the existing AC power lines as a medium to
transfer the information, it becomes easy to connect the houses with a high speed network access point
without installing new wirings

2.7.2 Need of PLCC


Different communication technologies are being used for the transmission of information from one end
to another depending on the feasibility and needs. Some include Ethernet cables, fiber optics, wireless
transmission, satellite transmission, etc. A vast amount of information travels through the entire earth
every day and it creates an essential need for a transmission medium that is not only fast but
economically reasonable as well. One of the technologies that fit in the above stated criteria is PLCC..

2.7.3 Operation
The voice/data are mixed with radio frequency carrier (40-500kHz), amplified to a level of 10-80W RF
power and injected in to high voltage power
line using a suitable coupling capacitor. The power line
as a rigid long conductor parallel to ground, guides the carrier waves to travel along the transmission
line.

2.8 Wave trap


Wave Traps are used at sub-stations using Power Line Carrier Communication (PLCC). PLCC is used to
transmit communication and control information at a high frequency over the power lines. This reduces
need for a separate infra for communication between sub-stations.

Figure : PLCC and Wavetrap

CHAPTER 3

3.1 What is GIS?


A gas insulated substation is an electrical substation in which the major structures are contained in a
sealed environment with sulfur hexafluoride gas (SF6) as the insulating medium. Gas insulated
substations originated in Japan where the there a major need to develop technology that would allow
substations to be made as compact as possible.

3.2 why Gas Insulated Substations are


used ?
Gas Insulated Substations are used where there is space for providing the substation is expensive in
large cities and towns. In normal substation the clearances between the phase to phase and phase to
ground is very large. Due to this, large space is required for the normal or Air Insulated Substation (AIS).
But the dielectric strength of SF6 gas is higher compared to the air, the clearances required for phase to
phase and phase to ground for all equipments are quite lower. Hence, the overall size of each
equipment and the complete substation is reduced to about 10% of the conventional air insulated

substation

3.3 ADVANTAGES OF GIS TECHNOLOGY


1- Compactness. The space occupied by SF6 installation is only about 8 to 10 % of that a conventional
outdoor substation. High cost is partly compensated by saving in cost of space.
2- Choice of Mounting Site. Modular SF6 GIS can be tailor made to Suit the particular site requirements.
This results is saving of otherwise Expensive civil-foundation work. SF6 GIS can be suitably mounted
indoor on any floor or basement and SF6 Insulated Cables (GIC) can be taken through walls and
terminated through SF6 bushing or power cables.
3- Reduced Installation Time- The principle of building block construction (modular construction)
reduces the installation time to a few weeks. Each conventional substation requires several months for
installation. In SF6 substations, the time-consuming high cost galvanized steel structures are eliminated.
Heavy foundations for galvanized steel structures, Equipment support structures etc are eliminated. This

results in economy and reduced project execution time. Modules are factory assembled, tested and
dispatched with nominal SF6 gas. Site erection time is reduced to final assembly of modules.
4- Protection from pollution. The external moisture. Atmospheric Pollution, snow dust etc. have little
influence on SF6 insulated substation. All live parts are hermetically enclosed in the gas chamber & are,
thus, independent from environmental influences like rusting, ageing, atmospheric faults etc.
However, to facilitate installation and maintenance, the substations are generally housed inside a small
building.
5- Increased Safety. As the enclosures are at earth potential there is no possibility of accidental contact
by service personnel to live parts. Also continuous & robust mechanical interlocking systems ensure
maximum operating stability & operator safety.
6- Explosion-proof and Fire-proof installation. Oil Circuit Breakers and oil filled equipment are prone to
explosion. SF6 breakers and SF6 filled equipment are explosion proof and fire-proof.
7- Easy operation and long life
Operation of GIS is simple, user friendly and through safe mechanism. As all GIS is enclosed in sealed
chamber it provides long service life and low maintenance cost.

3.4 Why SF6 gas is used?


SF6 has excellent insulating property. SF6 has high electro-negativity. That means it has high affinity of
absorbing free electron. Whenever a free electron collides with the SF6 gas molecule, it is absorbed by
that gas molecule and forms a negative ion.
The attachment of electron with SF6 gas molecules may occur in two different ways,

These negative ions obviously much heavier than a free electron and therefore over all mobility of the
charged particle in the SF6 gas is much less as compared other common gases. We know that mobility of
charged particle is majorly responsible for conducting current through a gas.
Hence, for heavier and less mobile charged particles in SF6 gas, it acquires very high dielectric strength.
Not only the gas has a good dielectric strength but also it has the unique property of fast recombination
after the source energizing the spark is removed. The gas has also very good heat transfer property. Due
to its low gaseous viscosity (because of less molecular mobility) SF6 gas can efficiently transfer heat by
convection. So due to its high dielectric strength and high cooling effect SF6 gas is approximately 100
times more effective arc quenching media than air. Due to these unique properties of this gas SF6 circuit
breaker is used in complete range of medium voltage and high voltage electrical power system. These
circuit breakers are available for the voltage ranges from 33KV to 800KV and even more.

CHAPTER 4

3.1 WHAT IS PASS?


Here term Hybrid system refers to the combination of both conventional air insulated switchgear (AIS)
and newer SF6 metal clad insulated switchgear (GIS) which takes advantage of the two different
technologies.The hybrid switchgear solution uses already existing, tried and tested gas insulated
switching components but also a conventional and very reliable AIS bus to connect the various hybrid
modules. All the functions( except the ring type current transformer) are sealed in single SF6 gas
insulated housing.

Circuit breaker
Disconnectors
Earth switches
Cable sealing ends
Fast earthing switches
SF6 VTs or voltage sensors

Figure : PASS

3.2 Components of PASS


1. Gas density Control
Each PASS pole has a single gas compartment. Since the dielectric strength of the switchgear
and the breaking capacityof the SF6 circuit breaker depend on the density of SF6 gas, a gas
density relay is installed to control gas density and detect leakage.
2. Voltage Transformer
PASS can be equipped with a conventional GIS inductive voltage transformer.
3. Combined Disconnector/earth switch
PASS is equipped with combined disconnector/earthing switch. The mechanism has minimal
number of mechanical components and is intrinsically reliableand maintenance free. All
combinations are possible.
4. Current Transformer
PASS is equipped with a conventional transformer to meet the customers requirement. E.g.
for retrofitting. Several combination of cores for protection and measurement with different
load are available.

CHAPTER 4

4.1 What

Is

scada system

It is defined as -SCADA (supervisory control and data acquisition) is a system operating with coded
signals over communication channels so as to provide control of remote equipment (using typically one
communication channel per remote station) .
There is a SCADA system in the SMS Hybrid Substation based on IEC 61850 standard.

4.2 Need of SCADA system


Substations are a critical component for maintaining electrical supply and load control in low voltage,
medium voltage and high voltage electrical distribution networks. In order to ensure the proper
functioning of substations and related equipment such as line-mounted switches and capacitors, most
utilities use SCADA (supervisory control and data acquisition) systems to automate monitoring and
control.

4.3 Working
Electrical distribution systems involve many remote applications and sites, and monitoring and
controlling these sites has often been difficult. To solve this problem, utilities began installing remote
terminal/telemetry units (RTUs) at substations. Early RTUs were initially custom-made units, but later
versions relied on standard hardware such as programmable logic controllers (PLCs) or industrial PCs.
Intelligent electronic devices (IEDs) are a more recent technology development, and these devices are
now installed at most substations to some extent. These IEDs generally communicate with the
substation RTU.
Power distribution to various electrical loads at substations is controlled by switchgear feeders. Sensors
mounted on the switchgear collect various data on current, voltage, power and switchgear status. This
data is transferred to the RTU, which is in turn polled by a SCADA system.
The SCADA system consists of a master control station with one or more PC-based human machine
interfaces (HMIs). The SCADA system may also contain other secondary control stations with HMIs, and
large substations may also have local HMIs.
Operators view information on the HMIs to monitor and control substation operations and related
equipment.

CHAPTER 5

5.1 RELAY
Relay is a device which detects fault current and energizes trip circuit of circuit breaker. A relay is an
electrically operated switch.
Different Relay used
Current Relay
Voltage Relay
Power Relay
Directional Relay
Differential Relay
Distance Relay

Figure :Relay Panel in SMS hybrid GSS

5.2 TRANSFORMER PROTECTION

Buccholz relay protection


Differential protection
Pressure releasedevice(PRD)
Oil surge relay protection
Backup protection
WTP(winding temperature protection)
OTP(oil temperature protection)
Over flux Protection
Fire flighting Protection

5.3 protection for TRANSmission line


feeder
Differential backup protection
Differential relay protection
5.4 FIRE PROTECTION

Figure : FIRE Protection

CHAPTER 6

6.1 CONTROL ROOM


6.1.1 Introduction
At control room , remot control not only carry the appropriate mean s by which circuit breaker may be
open or close but also necessary indicating devices , indicating lamps, isolating switching, protective
relays, secondary circuit and wires are located here and most important No load Tap Changer for
transformer is available. There is a panel for synchronizing .
Different panels are located in different stages and on each panel control switch is provided on the
board. The control switches for each circuit breaker and isolators are provided on control panel. Color of
signals are synchronized as follows

Red- For circuit breaker or isolator is in closed position.


Green- For circuit Breaker is in open position
Amber-Indicate abnormal condition requiring action.

Supervisory control and data acquisition(SCADA)

For power system operation and control SCADA system is used which includes

Data collection system


Data transmission telemetric equipment
Data monitoring Equipment
Man/machine interface

Detail of SCADA has already explained in earlier chapter.

Operation
The operation in control room needs information regarding parameters and configuration according to
feeders. It has different units

Indicating system
Control Switches

Relay Section
Meter Section
Announcing Section
DC Supply system
Transformer control unit

Announcing Section
This section is always checked by shift incharge.If any fault or alarm swing or any abnormal condition
then type o fault is indicated on announcing box The most important section is transformer control
section, winding temperature indicator.
Tap position selector is situated on control panel. A control engineer controls the loading of various
lines,outgoing feeders, synchronizing the incoming lines with bus bars.
Control and relay panel
The arrangement of control and relay power is such that the indicating apparatus is clearly visible from
control space. These respective panels are provided

Control and indicating equipment


Relay and recording equipment

Indicating system
Indicating system is used to indicate total load, bus bar voltage indication of circuit breaker, isolator
position.
Relay section
Relay section indicate position of different realy at different feeder. Fault at any feeder is denoted by
corresponding relay that gives alarm signal.Master relay gives signal to trip coil of circuit breaker and
thus faulty feeder is disconnected from supply.

Figure 1 Control Room at 132KV SMS GSS

6.2 Battery Room


In GSS, DC supply is maintained for signaling remote position control. Alarm circuit etc. Direct current
can be obtained from 220 v 3 phase ac supply via rectifier and in event of ac failure , from fixed battery
which are kept charged in normal condition by rectifier supply.

Figure 2 Battery Room at 132KV SMS GSS

S-ar putea să vă placă și