Project Management Initials: Designer: Designer Checked: Checker

01

02

2750

03

3000

3250

04

2750

05

06

3000

3000

07

3000

08

2750

09
ALL DIMENSIONS ARE APPROXIMATE.
AECOM ARE NOT RESPONSIBLE FOR
ACCURACY OF DEMOLITION
DRAWINGS. FOR DISCUSSION ONLY.

NOTE:
CONSTRUCTING RETAINING WALL IN CLOSE
PROXIMITY TO EXISTING NEIGHBOURING
WALL TO BE REVIEWED WITH CONTRACTOR
SIZE AND LOCATION OF OPENINGS
IN STAIRCORE WALLS T.B.C.

RISK ELEMENT:
PILING BETWEEN EXISTING EXAMS HALL
AND CORN EXCHANGE WALL, 1.2m ZONE
FOR PILING RIG NOT ACHIEVABLE. MAY BE
POSSIBLE TO BREAKOUT SECTION OF
EXISTING EXAMS HALL WALL &
FOUNDATIONS TO ACHIEVE OFFSET.
CONTRACTOR TO CONSIDER TEMPORARY
WORKS REQUIRED TO ACHIEVE THIS.

VOID

B01

C
4

C
1

250

1200
C
1

200mm THICK INSITU


R.C UPSTAND

A
3000

C
4

C
1

3000

C
4
C
4

C
1

275

3000

C
1

C
1

STEP

3000

C
4

150
150

SSL 10.180 m

E
3000

275
C
1

C
1
C
1

VOID

B01

VOID
C
1

C
1

VOID

250mm THICK INSITU


R.C UPSTAND
TOC 10.205 m

150

250mm THICK INSITU


R.C UPSTAND

3000

C
4

B01

C
4

C
1

STEP

C
1

3000

275

150

SSL 10.180 m

B01

VOID

B01

C
1

150

C
1

C
1

150

EXISTING EXAM HALL STONE DOORWAY


TO BE RETAINED. DOORWAY ASSUMED
TO BE REBUILT IN FINAL POSITION.
B04

LOCAL BREAK OUT OF


EXISTING EXAMS HALL
WALL AND FOUNDATION
REQUIRED. TEMPORARY
WORKS REQUIRED.

3000

C
4

B04

3000

250mm THICK INSITU


R.C UPSTAND
TOC 10.205 m

150

250mm THICK INSITU


R.C UPSTAND
C
1

250mm THICK INSITU


R.C UPSTAND
C
1

C
4

STEP

B02

450x250x10.0 FABRICATED BOX SECTION


TOS 10.205 m

SSL +10.080 m

250mm THICK INSITU


R.C UPSTAND
TOC 10.205 m
EXAMS HALLS
Full extent of Exams Halls to be demolished
B01

250mm THICK INSITU


R.C UPSTAND

STEP

150 COMP

STEP
B01

TOC 10.205 m

LINE OF STEP IN
SLAB SOFFIT.

1200

SSL 10.180 m

150

TOC 10.205 m

VOID
C
1

B01

LIFT
SHAFT

VOID

450x250x10.0 FABRICATED BOX SECTION


TOS 10.205 m

C
1
C
1
C
1
C
1

150
C
1

250

250mm THICK INSITU


R.C UPSTAND
B02

1890
APPROX

250mm THICK INSITU


R.C UPSTAND
TOC 10.205 m

M
G BEA
CAPPIN

UP

SLAB EDGE PROJECTING TO CLOSE


GAP TO EXISTING ARTS SCHOOL WALL.
SLAB SUPPORTED ON RSA RESIN
FIXED TO EXISTING STRUCTURE.
SLAB TO BE COMPLETED AFTER
CLADDING HAS BEEN INSTALLED ON
THE WEST ELEVATION (T.B.C)

150

C
1

LIFT
SHAFT

.C
EEP R
x 900 D

OLD CAVENDISH EAST

B01

TOC 10.205 m

TOC 10.205 m

VOID

678

VOID

ART SCHOOL

SSL +10.055 m

E
900 WID

RAYLEIGH WING

250mm WIDE x 150mm HIGH RC UPSTAND

VOID FOR
STAIR
(BY OTHERS)

LINE OF STEP IN
SLAB SOFFIT.

B01

3000

SSL +10.055 m

C
1

B03

VOID FOR
STAIR
(BY OTHERS)

150

LINE OF STEP IN
SLAB SOFFIT.

300

300

B01

C
5

150

3000

300
TB01

C
5

C
5

300
C
5

C
5

300

C
5

C
5

300

C
5

2010

300

300

900 WIDE x 900 DEEP R.C CAPPING BEAM

NOTE:
DOUBLE HEIGHT INSITU R.C FEATURE
COLUMNS TO HAVE EXTRA FINE FINISH.

NOTE:
LARGE DEFLECTIONS OF TRANSFER BEAM
SUPPORTING MASONRY MAY NOT BE
ACCEPTABLE. BEAM DEPTH MAY SIGNIFICANTLY
INCREASE T.B.C AT NEXT STAGE.

REQUIRED EXTERNAL BUILDUP TO


BE ASSESSED AT NEXT STAGE. STEP
IN SLAB MAY BE REQUIRED.

NOTE:
WEIGHT AND DEFLECTION REQUIREMENTS OF
MOVEABLE PARTITIONS TO BE CONFIRMED.
SUPPORT REQUIREMENTS ALSO TO BE
REVIEWED AT NEXT STAGE.

00 - GROUND FLOOR DEMOLITION


Last Plotted: 03/07/2015 17:59:08
Filename: C:\Users\saundersj1\Desktop\NRB-ACM-XX-XX-M3-S (LOCAL).rvt

SCALE 1 : 100

Printed on _% Post-Consumer
Recycled Content Paper

These drawings are issued for background information only.


They cannot be used for any other purpose and must not be
relied upon for dimensional accuracy.
For all setting out dimensions, refer to the most current PDF
issued drawings.

This drawing has been prepared for the use of AECOMs client. It may not be used, modified, reproduced or relied upon by third parties, except as agreed by AECOM or as required by law. AECOM accepts no responsibility, and denies any liability whatsoever, to any party that uses or relies on this drawing without AECOMs express written consent. Do not scale this document. All measurements must be obtained from the stated dimensions.

ISO A0 841mm x 1189mm


Approved: Approver CAD: Author

PROJECT

NORTHERN
RANGE
BUILDINGS

CLIENT

UNIVERSITY
OF CAMBRIDGE
CONSULTANT
AECOM
36 Storey's Way
Cambridge, Cambridgeshire CB3 0DT
+44 (0) 1223 488000 tel
www.aecom.com

NOTES

ISSUE/REVISION

I/R

DATE

DESCRIPTION

KEY PLAN

PROJECT NUMBER

60321968
SHEET TITLE

GROUND FLOOR DEMOLITION


OVERLAY
SHEET NUMBER

SK-150703-001