Sunteți pe pagina 1din 32

Installation Instructions

EtherNet/IP Copper Tap


Catalog Number 1783-ETAP
Topic

Page

Important User Information

North American Hazardous Location Approval

European Hazardous Location Approval

Environment and Enclosure

Prevent Electrostatic Discharge

About the 1783-ETAP EtherNet/IP Tap

Module Components

Software Requirements

10

Install the Tap

11

Mount the Tap

11

Wire the Tap

13

Connect the Copper EtherNet Ports

15

Download the Tap Add-on Profile

16

Download the EDS File

17

Configure Internet Protocol Settings

18

Set the DIP Switches

20

Use the Web Interface

23

Status Indicators

24

Specifications

26

Additional Resources

30

2 EtherNet/IP Copper Tap

Important User Information


Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1 available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature/) describes some important differences between
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you identify
a hazard, avoid a hazard, and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor,
to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor,
to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the
product.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 3

North American Hazardous Location Approval


The following information applies
when operating this equipment in
hazardous locations.

Informations sur lutilisation de cet


quipement en environnements
dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are


suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with
markings on the rating nameplate indicating the
hazardous location temperature code. When
combining products within a system, the most
adverse temperature code (lowest "T" number) may
be used to help determine the overall temperature
code of the system. Combinations of equipment in
your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.

Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne


conviennent qu' une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dangereux et
non dangereux. Chaque produit est livr avec des
marquages sur sa plaque d'identification qui indiquent
le code de temprature pour les environnements
dangereux. Lorsque plusieurs produits sont combins
dans un systme, le code de temprature le plus
dfavorable (code de temprature le plus faible) peut
tre utilis pour dterminer le code de temprature
global du systme. Les combinaisons d'quipements
dans le systme sont sujettes inspection par les
autorits locales qualifies au moment de
l'installation.

WARNING:
Explosion Hazard

AVERTISSEMENT:
Risque dExplosion

Do not disconnect equipment


unless power has been removed
or the area is known to be
nonhazardous.
Do not disconnect connections to
this equipment unless power has
been removed or the area is
known to be nonhazardous.
Secure any external connections
that mate to this equipment by
using screws, sliding latches,
threaded connectors, or other
means provided with this product.
Substitution of components may
impair suitability for Class I,
Division 2.
If this product contains batteries,
they must only be changed in an
area known to be nonhazardous.

Couper le courant ou s'assurer que


l'environnement est class non
dangereux avant de dbrancher
l'quipement.
Couper le courant ou s'assurer que
l'environnement est class non
dangereux avant de dbrancher les
connecteurs. Fixer tous les
connecteurs externes relis cet
quipement l'aide de vis, loquets
coulissants, connecteurs filets ou
autres moyens fournis avec ce
produit.
La substitution de composants peut
rendre cet quipement inadapt
une utilisation en environnement de
Classe I, Division 2.
S'assurer que l'environnement est
class non dangereux avant de
changer les piles.

WARNING: An electrical arc can occur if you connect or disconnect the following:

Communication cable with power applied to this device or any device on the
network
Wiring while the field-side power is on
These actions could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

4 EtherNet/IP Copper Tap

European Hazardous Location Approval


The following applies when the product bears the Ex Marking:
This equipment is intended for use in potentially explosive atmospheres as defined by European Union
Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements
relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially
explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with
EN 60079-15 and EN 60079-0.1.
WARNING:

This equipment must be installed in an enclosure providing at least IP54 protection


when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by Rockwell
Automation.
Provision shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 40% when applied in Zone 2 environments.
Secure any external connections that mate to this equipment by using screws,
sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known
to be nonhazardous.

ATTENTION: This equipment is not resistant to sunlight or other sources of UV


radiation.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 5

Environment and Enclosure


ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at
altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR 11. Without appropriate precautions, there may be difficulties with
electromagnetic compatibility in residential and other environments due to conducted
and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions that will
be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable flame-retardant properties to
prevent or minimize the spread of flame, complying with a flame spread rating of 5VA,
V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:

Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation


publication 1770-4.1, for additional installation requirements.
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees
of protection provided by different types of enclosures.

Prevent Electrostatic Discharge


ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:

Touch a grounded object to discharge potential static.


Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

6 EtherNet/IP Copper Tap

About the 1783-ETAP EtherNet/IP Tap


The 1783-ETAP EtherNet/IP tap provides EtherNet/IP connectivity. Use the
tap to support these network topologies:
Linear
Star
Device-level ring (DLR)
The tap is configured by default to support linear, star, and ring (as a
non-supervisor ring node) topologies.
IMPORTANT

When setting up a DLR, refer to Device-level Ring (DLR)


Network Considerations on page 7 to avoid adversely impacting
your network.

Refer to the EtherNet/IP Embedded Switch Technology Application Guide,


publication ENET-AP005, for information on setting up EtherNet/IP network
topologies.

Linear and Star Network Considerations


When using the tap in a linear or star network, be sure that Ring Supervisor
mode is not enabled. By default, the tap is configured to be a non-supervisor ring
node.
IMPORTANT

For 1783-ETAP modules running firmware revision 2.001 or later,


DIP switch 3 is used for making the tap a ring supervisor in a DLR
network. To avoid adversely impacting communication in a linear
or star network, take these precautions:
Make sure switch 3 remains in the Off position. If switch 3 is
in the On position, the tap will be automatically enabled as a
ring supervisor.
Make sure the Ring Supervisor mode is not enabled in RSLinx
Classic communication software or RSLogix 5000
programming software. When switch 3 is in the Off position,
the programming software controls whether the tap is a ring
supervisor.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 7

Device-level Ring (DLR) Network Considerations


When using the tap in a DLR network, consider whether the tap will be a ring
supervisor. By default, the tap is configured to be a non-supervisor ring node.
Use one of these methods for controlling supervisor functionality:
Use RSLinx Classic communication software or RSLogix 5000
programming software to set the Ring Supervisor mode and other
supervisor-related parameters. This is the default method. If you choose
this option, follow the procedures outlined in the online help that
accompanies the software to enable Ring Supervisor mode.
Use the DIP switches to automatically enable Ring Supervisor mode
with the current supervisor-related parameters stored in the taps
memory .(1) Refer to Set the DIP Switches on page 20 for additional
information.
IMPORTANT

Use these precautions when setting up a DLR network:


Make sure at least one node is acting as supervisor before
connecting the last link of a DLR network and physically
closing the ring.
Do not connect nodes that do not support a DLR as members
of the ring.

(1)

Using switch 3 to control Ring Supervisor mode is supported only on 1783-ETAP modules running
firmware revision 2.001 or later.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

8 EtherNet/IP Copper Tap

Grounding Considerations
This product is intended to be mounted to a well-grounded mounting surface,
such as a metal pane or DIN rail.
ATTENTION: This product is grounded through the DIN rail to
chassis ground. Use zinc-plated yellow-chromate steel DIN rail to
assure proper grounding. The use of other DIN rail materials (for
example, aluminum or plastic) that can corrode, oxidize, or are
poor conductors, can result in improper or intermittent grounding.
Secure the DIN rail to mounting surface approximately every
200 mm (7.8 in.) and use end-anchors appropriately.
Refer to the Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1, for additional information.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 9

Module Components
2
1

10

9
8

7
6

5
Item

Description

Item

Description

DIP switches

Ports for connection to linear or ring


network
A: Port 1
B: Port 2

Top view

Front view

Side view

MAC ID label

DC connector

Device port on front panel

Bottom view

10

Status indicators

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

10 EtherNet/IP Copper Tap


By default, the individual ports on the tap auto-negotiate link speeds (10 Mbps
or 100 Mbps) and duplex (full or half ).
IMPORTANT

Configure the Ethernet port on the device you connect to a tap so


that it matches the taps speed and duplex settings.
Failure to make the speed and duplex settings of directly
connected devices match may result in higher error rates, or loss
of network connectivity.

Software Requirements
You must have these versions of software.
Software

Version

RSLinx Classic

2.56 or later

RSLogix 5000

17.01 or later
If you are using version 17.01, you need version 2.x of the add-on profile.
Download it from
http://www.rockwellautomation.com/support/downloads.html.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 11

Install the Tap


WARNING: For hazardous location applications, use the supplied
Phoenix MSTB 2.5/2-ST-5.08 power terminal block.
Follow these procedures to install the tap.
1. Mount the tap in one of these configurations:
Panel mount
DIN rail mount
2. Wire the tap.
3. Connect the copper Ethernet ports.
4. Download the tap Add-on Profile (AOP) if you are using RSLogix 5000
programming software version 17.01.
5. Download the EDS file for the tap.
6. Configure Internet Protocol settings.
7. Set the DIP switches.
This publication describes these steps in detail.

Mount the Tap


Install the tap on a DIN rail or panel mount the tap.
IMPORTANT

When mounting the tap, allow a minimum clearance between


product and adjacent equipment of 2.54 cm (1 in.) on all sides.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

12 EtherNet/IP Copper Tap

DIN Rail Mounting


To install the tap on a DIN rail, proceed as follows.
1. Mount your DIN rail.
2. Use a screwdriver to open the latch at the bottom of the tap.
3. Hook the latch over the DIN rail while holding the latch open with your
screwdriver.
4. Remove the screwdriver and push the latch to close.
The top figure shows using a screwdriver to open the latch so that you
can remove the tap from the DIN rail. The bottom figure shows the
latch at the bottom of the tap in the open position.

Panel Mounting
To panel mount a tap, proceed as follows.
1. Use the tap as a template and mark pilot holes on your panel.
2. Drill the pilot holes for M4 or #8 screws.
Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 13

Wire the Tap


WARNING: An electrical arc can occur if you connect or
disconnect the following:
Communication cable with power applied to this module or any
device on the network.
Wiring while the field-side power is on.
This could cause an explosion in hazardous location installations. Be
sure that power is removed or the area is nonhazardous before
proceeding.
ATTENTION: To comply with the CE Low Voltage Directive (LVD),
this equipment must be powered from a source compliant with
safety extra low voltage (SELV) or protected extra low voltage
(PELV).
To comply with UL restrictions, this equipment must be powered
from a source compliant with Class 2.
Provide DC power to the tap by using the DC connector at the bottom of the
tap.
WARNING: For hazardous location applications, use the supplied
Phoenix MSTB 2.5/2-ST-5.08 power terminal block.

ATTENTION: Do not wire more than two conductors on any


single terminal.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

14 EtherNet/IP Copper Tap


EtherNet/IP Copper Tap Terminals Description

2
3

Item

Description

Tap bottom

DC- (0V DC) terminal

DC+ (24V DC nom) terminal

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 15

Connect the Copper Ethernet Ports


Follow these steps to connect the copper Ethernet ports on the tap.
1. Locate the copper Ethernet RJ45 ports on the front and bottom of the
tap, as shown in the figure.

Item

Description

Device port on tap front panel

Ports on tap bottom for connection to the linear or ring network

2. Connect one end of an Ethernet cable to the front panel port used as a
device port.
3. Connect the other end of the Ethernet cable to the appropriate device in
your network.
4. Connect one end of an Ethernet cable to a port at the bottom of the tap
and connect the other end of the Ethernet cable to the linear or ring
network.
5. Repeat with the other port at the bottom of the tap if the port is used by
your network.
Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

16 EtherNet/IP Copper Tap


IMPORTANT

When setting up a DLR, refer to Device-level Ring (DLR) Network


Considerations on page 7 to avoid adversely impacting your
network.

Download the Tap Add-on Profile, RSLogix 5000 Software


Version 17.01 Only
If you are using RSLogix 5000 programming software, version 17.01, you need
version 2.x of the Add-on Profile (AOP). Follow these steps to download the
AOP.
1. Locate the tap AOP at
http://www.rockwellautomation.com/support/downloads.html.
IMPORTANT

You need a Rockwell Automation MySupport account to


download the AOP. If you do not have one, follow the steps on the
MySupport website to obtain an account.

2. Click the desired file to download it.


3. Enter your RSLogix 5000 programming software serial number and
click Qualify for Update.
4. Download and extract the zipped files to a temporary directory.
5. Shut down any instances of RSLogix 5000 programming software that
are currently running.
6. In the temporary directory, double-click the MPSetup.exe file and
follow the onscreen instructions to install the AOP.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 17

Download the EDS File


To use RSLinx Classic communication software to configure the tap, follow
these steps to download the EDS file for the tap.
1. Obtain the EDS file from
http://www.rockwellautomation.com/resources/eds/.
2. From the Network pull-down menu, choose the EtherNet/IP network.
3. From the Device Type pull-down, choose Communication Adapter.
4. In the Bulletin/catalog number field, type 1783-ETAP.
5. Click Search.
6. Click Download to download the EDS file for the tap.
7. Save the file to an appropriate location on your computer.
8. Use your configuration software to register the downloaded file.
a. If you are using RSLinx Classic communication software, use the
EDS Hardware Installation Tool.
b. Choose Start>All Programs>Rockwell Software>RSLinx>Tools.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

18 EtherNet/IP Copper Tap

Configure Internet Protocol Settings


Configure Internet Protocol (IP) settings, such as the IP address, in one of these
ways:
Use the taps default IP address of 169.254.1.1 by connecting the tap
directly to a computer. To establish communication between a computer
and the taps default IP address, you have the following options:
Enter a unique IP address in the local area connection properties for
your computer. The computers IP address must be on the same
subnet as the taps default IP address, such as 169.254.1.2.
Set up your computer to obtain its IP address automatically.
IMPORTANT

If the port on your PC that is connected to the tap is


configured to obtain its IP address automatically, expect
a wait time of up to two minutes before communication
is established after connecting the tap to a computer.
If two or more taps are connected to one another, and
each tap is using the default IP address, the computer is
only able to communicate with the tap to which it is
directly connected.

Use IP settings configured in RSLinx Classic communication software


or RSLogix 5000 programming software.
Acquire IP settings from a DHCP server.
Acquire IP settings from a BOOTP server.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 19


Use the DIP switches on the tap to select the configuration method to use for IP
settings. Refer to Set the DIP Switches on page 20.
TIP

After connecting with the out-of-box IP address or an address


obtained by using a DHCP server or a BOOTP server, RSLinx
Classic communication software or RSLogix 5000 programming
software may be used to configure a static IP address that will be
stored in nonvolatile memory.

Use the DHCP/BOOTP Server


If your network infrastructure does not provide DHCP/BOOT functionality,
you may download our DHCP/BOOTP server software to a personal computer
running a Microsoft Windows operating system. You can use this computer as
the DHCP/BOOTP server.
To set the network address by using the Rockwell Automation DHCP/BOOTP
server, follow these steps.
1. Access the DHCP/BOOTP utility at
http://www.ab.com/networks/ethernet/bootp.html.
2. Download the version 2.3.2 DHCP/BOOTP utility.
3. Extract the zipped files to a temporary directory.
4. In the temporary directory, double-click setup.exe to install the
DHCP/BOOTP utility.
5. Run the utility.
6. Refer to the following chart, which describes what happens next,
depending on whether DHCP/BOOTP is enabled on the tap.
If DHCP/BOOTP is

The tap

Enabled

Asks for an IP address from a DHCP/BOOTP server. Consult the


online help available in the BOOTP/DHCP application to
configure the server to provide the desired IP address for your
tap.

Not enabled

Uses the IP settings stored in nonvolatile memory. The default


IP address stored in memory is 169.254.1.1.
Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

20 EtherNet/IP Copper Tap

Set the DIP Switches


Use the DIP switches on the tap to do the following:
Specify the method for configuring Internet Protocol (IP) settings, such
as the IP address.
Enable the Ring Supervisor mode with its current parameters.
Restore the factory default settings.
Refer to the illustration to understand DIP switch On and Off positions.
Off On
Switch 3
Switch 2
Switch 1

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 21


Use this procedure to set the DIP switches.
1. Move the switches to the desired position, and then cycle power to the
tap.
IMPORTANT

The switch settings take effect only at powerup. The tap's


behavior will not be modified by switch changes until the tap is
power cycled.

Power-up Behavior

Switch 1

Switch 2

Switch 3

Internet
Protocol
settings

Uses the IP settings configured by


software(1)
or
Uses the default IP address of
169.254.1.1 if settings have not
been configured by software

Off

Off

The position
of switch 3
does not
affect IP
settings

Uses the IP settings acquired by a


BOOTP server

On

Off

Uses the IP settings acquired by a


DHCP server

Off

On

Enables Ring Supervisor mode with


the current supervisor-related
parameters(2)

The positions of
switches 1 and 2 do
not affect Ring
Supervisor mode

Ring
Supervisor
mode

Allows Ring Supervisor mode and


supervisor-related parameters to be
enabled and configured by software
Restores the factory default settings and then
suspends operation
(1)
(2)
(3)

On

On

On(3)

Off

On or Off

RSLinx Classic communication software or RSLogix 5000 programming software is required.


For information about supervisor-related parameters, refer to the EtherNet/IP Embedded Switch
Technology Application Guide, publication ENET-AP005.
Using switch 3 to control Ring Supervisor mode is supported only on 1783-ETAP modules running
firmware revision 2.001 or later.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

22 EtherNet/IP Copper Tap


2. Observe these guidelines on use of the DIP switches:
Out of the box, all three switches are in the Off position. In this
state, the tap is configured to be a non-supervisor ring node and will
respond to the default IP address of 169.254.1.1.
If your application does not require access to the taps diagnostic
information or configuration, no further action is required.
Otherwise, select alternate DIP switch settings or configure the tap
by using RSLinx Classic communication software or RSLogix 5000
programming software.
When a switch is pushed to the left, it is in the Off position.
When a switch is pushed to the right, it is in the On position.
To select BOOTP, move switch 1 to the On position and switch 2 to
the Off position.
To select DHCP, move switch 1 to the Off position and switch 2 to
the On position.
To enable Ring Supervisor mode with the current supervisor-related
parameters, move switch 3 to the On position.
To restore the factory default settings and suspend operation, move
both switch 1 and 2 to the On position. When both switch 1 and 2
are in the On position, the position of switch 3 is ignored.
When operation is suspended, the OK status indicator blinks red. To
resume normal operation, move the switches to the desired positions
and then cycle power to the tap.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 23

Use the Web Interface


The tap supports a Web interface that provides diagnostic read-only
information. Follow these steps to access the Web interface.
1. Connect a computer to any of the taps Ethernet ports.
2. Browse to the tap by entering the taps IP address (the out-of-the-box
default is 169.254.1.1) in your web browsers address bar.
TIP

If you configure the tap with an IP address, you can also access the
tap Web interface from any computer connected to the network.

3. Click Enter.
You see the 1783-ETAP tap page, which provides general information
about the tap.

4. In the left pane, click Diagnostics.


You see links to these pages:

Diagnostic Overview

Network Settings

Ethernet Statistics

Ring Statistics

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

24 EtherNet/IP Copper Tap


This web page

Contains information about

Diagnostic Overview

Network Settings

Network interface details, such as IP address and subnet


mask
Ethernet Interface configuration method
Ethernet port details

Ethernet Statistics

Ethernet counters
Ethernet port details
Error information

Ring Statistics

Ring supervisor, configuration, and fault details

Module resource utilization


Web server read and write hits
Module settings
Ring status
Network management features

Status Indicators

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 25


Indicator Description
Indicator
OK

LINK1,
LINK2

Status

Description

Off

Tap is not powered.

Flashing green

Tap is not configured.

Solid green

Tap is powered, configured, and operating correctly.

Flashing red

Recoverable fault, such as duplicate IP address or flash


update in progress, is detected.

Solid red

Unrecoverable fault detected.

Off

One of these conditions exists:


No link.
Port administratively disabled.
Port disabled because of rapid ring fault condition,
and this tap is the active ring supervisor (LINK 2).
Ring network has encountered a rare, partial network
fault, and this tap is the active supervisor (LINK 2).

Green

One of these conditions exists:


A 100 Mbps (full or half duplex) link exists.
The ring network is operating normally and this tap is
the active supervisor (LINK 2).

Flashing green

A 100 Mbps link exists and there is activity.

Solid yellow

One of these conditions exists:


A 10 Mbps (full or half duplex) link exists.
Ring network is operating normally, and this tap is the
active supervisor (LINK 2).

Flashing yellow

A 10 Mbps link exists and there is activity.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

26 EtherNet/IP Copper Tap

Specifications
Technical Specifications - 1783-ETAP
Attribute

1783-ETAP

Enclosure type rating

None (open-style)

Current consumption, max

125 mA @ 24V DC

DC power supply voltage rating

24V DC (20.4...27.6V DC)

Isolation voltage

30V (continuous), Basic Insulation Type, Network


channels to Power and Network channels to Network
channels
Type tested at 1250V DC for 60 s

Power consumption, max

3W

Power dissipation

3W

Wire size

Ethernet connections:
RJ45 connector according to IEC 60603-7, 2 or 4 pair
Category 5e minimum cable according to TIA 568-B.1 or
Category 5 cable according to ISO/IEC 24702
DC power connections:
One 0.333.3 mm2 (2212 AWG) or
two 0.331.3 mm2 (2216 AWG) solid or
stranded copper wire rated at 75 C (167 F) or greater,
1.2 mm (3/64 in.) insulation max

Torque

0.60.8 Nm (57 lbin) on power connectors

Dimensions (HxWxD), approx.


Wiring category

(1)

132 x 35 x 105 mm (5.16 x 1.36 x 4.13 in.)


1 - on power ports
2 - on communication ports

North American temp code

T5

IEC temp code

T5

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 27


Environmental Specifications - 1783-ETAP
Attribute

1783-ETAP

Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock)

-2570 C (-13158 F)

Temperature, surrounding air, max

70 C (158 F)

Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)

-4085 C (-40185 F)

Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp
Heat)

595% noncondensing

Voltage variation
IEC 61000-4-29

10 ms interruption on DC supply ports

Vibration
IEC 60068-2-6 (Test Fc, Operating)

5 g @ 10500 Hz

Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions
CISPR 11

Group 1, Class A

ESD immunity
IEC 61000-4-2

6 kV contact discharges
8 kV air discharges

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

28 EtherNet/IP Copper Tap


Environmental Specifications - 1783-ETAP
Attribute

1783-ETAP

Radiated RF immunity
IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from


802000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
1890 MHz
3V/m with 1 kHz sine-wave 80% AM from
20002700 MHz

EFT/B immunity
IEC 61000-4-4

4 kV at 5 kHz on power ports


3 kV at 5 kHz on communication ports

Surge transient immunity


IEC 61000-4-5

1 kV line-line (DM) and 2 kV line-earth


(CM) on power ports
2 kV line-earth (CM) on communication
ports

Conducted RF immunity
IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM


from 150 kHz80 MHz

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 29


Certifications - 1783-ETAP
Certification(1)

1783-ETAP

c-UL-us

UL Listed Industrial Control Equipment, certified for US


and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D
Hazardous Locations, certified for U.S. and Canada.
See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant


with:
EN 61326-1; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8,
Zone A and B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant


with:
EN 60079-15; Potentially Explosive Atmospheres,
Protection n
EN 60079-0; General Requirements
II 3 G Ex nA IIC T5X

EtherNet/IP

ODVA conformance tested to EtherNet/IP


specifications

(1)

When product is marked. See the Product Certification link at http://www.ab.com for Declarations of
Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

30 EtherNet/IP Copper Tap

Additional Resources
These documents contain additional information concerning related Rockwell
Automation products.
Resource

Description

EtherNet/IP Modules in Logix5000 Control


Systems User Manual, publication
ENET-UM001

Provides details about how to configure


your module.

EtherNet/IP Embedded Switch Technology


Application Guide, publication ENET-AP005

Provides information about using products


with embedded switch technology to
construct networks with linear and ring
topologies.

EtherNet/IP Industrial Protocol White Paper,


publication ENET-WP001

Describes how to implement services and


data objects on a TCP/UDP/IP based
Ethernet network.

Industrial Automation Wiring and Grounding


Guidelines, publication 1770-4.1

Provides general guidelines for installing a


Rockwell Automation industrial system.

Product Certifications website,


http://www.ab.com

Provides declarations of conformity,


certificates, and other certification details.

You can view or download publications at


http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Rockwell Automation distributor
or sales representative.

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

EtherNet/IP Copper Tap 31

Notes:

Rockwell Automation Publication 1783-IN007C-EN-P - April 2011

Rockwell Automation Support


Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs,
technical and application notes, sample code and links to software service packs, and a MySupport feature
that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
United States or Canada

1.440.646.3434

Outside United States or


Canada

Use the Worldwide Locator at


http://www.rockwellautomation.com/support/americas/phone_en.html, or
contact your local Rockwell Automation representative.

New Product Satisfaction Return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow
these procedures.

United States

Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete
the return process.

Outside United States

Please contact your local Rockwell Automation representative for the return
procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002, available at
http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Software, Rockwell Automation, CompactLogix, Compact I/O, RSLinx Classic, RSLogix 5000, and
TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

Publication 1783-IN007C-EN-P - April 2011


Supersedes Publication 1783-IN007B-EN-P - January 2010

PN-100146

Copyright 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

S-ar putea să vă placă și