AC VAV 350-750 mm VRV 450 mm RECESSED CHILLED BEAM 350-450 mm SURFACE CHILLED BEAM 250 mm CHILLED CEILINGS 250 mm
FAN COILS 450 mm
DUCTED AIR SYSTEM 450 mm AIR DUCT SHAFT SIZE 0.2 m2/m3/S 20mm DIA PIPE 100mmx100mm 25mm DIA PIPE 120mmx120mm 32mm DIA PIPE 130mmx130mm RISER DEPTH FROM SERVICES 690 mm FLOOR SPACE SERVICED BY VERTICAL SERVICE (RADIUS) 15-23 m aSPECT RATIO OF VERTICAL SERVICE DUCTS 2:1-4:1 TOTAL DUCT AREA AS % FLOOR AREA 2% SINLGE WATER COOLED LIQUID CHILLER 1500KW 10000Kg 3000KW 20000Kg 4500kw 30000Kg SINLGE AIR COOLED LIQUID CHILLER 500KW 6000Kg 000KW 11000Kg 500kw 14000Kg CENTRAL COOLING PLANT 125 W/m2 40w/m3 OR 0.5KW/KW DISTRIBUTED COOLING PLANT 140 W/m2 45w/m3 OR 0.78 KW/KW