ECG Engineering Consultants Group

PROJECT: NOZHA CITY CENTER

REV:

SUBJECT : ESTIMATE COOLING LOAD CALCULATIONS FOR GROUND FLOOR


SERIAL

DATE : MAY 2007

AREA

NO. OF

F.A PER

TOTAL F.A

COOLING

WATER

M2

PERSONS

PERSON

CFM

CAPACITY T.R.

GPM

ZONE NAME

T.R./M2

REV.

TOTAL

design data effected

CFM
F.A %

ONE A/C

CFM

NOTES
PER T.R

Lighting W/F2

EQ.KW

EQ.W/F2

LO-003

89.2

18

11

187

3.8

6.3

23.5

1962

10

273

517

4.5

0.9

1.0

TREATED F/A

LO-004

89.2

18

11

187

4.0

6.7

22.3

2068

273

517

4.5

0.9

1.0

TREATED F/A

LO-005

88.6

18

11

186

3.8

6.4

23.3

1966

271

517

4.5

0.9

1.0

TREATED F/A

LO-006

91.2

18

11

192

3.9

6.5

23.3

2024

279

517

4.5

1.0

1.0

TREATED F/A

LO-006A

52

10

11

109

2.2

3.7

23.3

1154

159

517

4.5

0.5

1.0

TREATED F/A

LO-007

28

11

59

1.2

2.0

23.3

621

86

517

4.5

0.3

1.0

TREATED F/A

LO-008

118.6

24

11

249

5.1

8.5

23.3

2632

363

517

4.5

1.2

1.0

TREATED F/A

LO-009

118.6

24

11

249

5.1

8.5

23.3

2632

363

517

4.5

1.2

1.0

TREATED F/A

LO-010

186.1

37

11

391

8.0

13.3

23.3

4129

569

517

4.5

1.9

1.0

TREATED F/A

10

LO-011

183

37

11

384

8.6

14.4

21.2

4463

560

517

4.5

1.9

1.0

TREATED F/A

11

LO-011A

192

38

11

403

9.1

15.1

21.2

4682

587

517

4.5

2.0

1.0

TREATED F/A

12

LO-012

174

35

11

365

8.2

13.7

21.2

4243

532

517

4.5

1.8

1.0

TREATED F/A

13

LO-013

159

32

11

334

7.5

12.5

21.2

3878

486

517

4.5

1.7

1.0

TREATED F/A

14

LO-014

127.5

26

11

268

6.0

10.0

21.2

3109

390

517

4.5

1.3

1.0

TREATED F/A

15

LO-015

77.5

16

11

163

3.7

6.1

21.2

1890

237

517

4.5

0.8

1.0

TREATED F/A

16

LO-016

135.5

27

11

285

6.5

10.8

21.0

3336

414

517

4.5

1.4

1.0

TREATED F/A

17

LO-017

129.5

26

11

272

6.2

10.3

21.0

3188

396

517

4.5

1.3

1.0

TREATED F/A

18

LO-018

128

26

11

269

6.1

10.2

21.0

3151

392

517

4.5

1.3

1.0

TREATED F/A

19

LO-019

129.5

26

11

272

6.2

10.3

21.0

3188

396

517

4.5

1.3

1.0

TREATED F/A

20

LO-020

106.5

21

11

224

5.1

8.5

21.0

2622

326

517

4.5

1.1

1.0

TREATED F/A

21

LO-021

123

25

11

258

5.9

9.8

21.0

3028

376

517

4.5

1.3

1.0

TREATED F/A

22

LO-022

84.1

17

11

177

4.0

6.7

21.0

2070

257

517

4.5

0.9

1.0

TREATED F/A

23

LO-023

167.3

33

11

351

8.0

13.3

21.0

4119

512

517

4.5

1.7

1.0

TREATED F/A

24

LO-024

172

34

11

361

8.2

13.7

21.0

4234

526

517

4.5

1.8

1.0

TREATED F/A

25

LO-025

201

40

11

422

9.6

16.0

21.0

4948

615

517

4.5

2.1

1.0

TREATED F/A

26

LO-026

85.2

17

11

179

3.7

6.2

22.8

1932

261

517

4.5

0.9

1.0

TREATED F/A

27

LO-027

124.5

25

11

261

5.9

9.9

21.0

3065

381

517

4.5

1.3

1.0

TREATED F/A

28

LO-028

161.5

32

11

339

7.7

12.8

21.0

3976

494

517

4.5

1.7

1.0

TREATED F/A

29

LO-029

167.4

33

11

352

8.0

13.3

21.0

4121

512

517

4.5

1.7

1.0

TREATED F/A

ECG Engineering Consultants Group


PROJECT: NOZHA CITY CENTER

REV:

SUBJECT : ESTIMATE COOLING LOAD CALCULATIONS FOR GROUND FLOOR


SERIAL

DATE : MAY 2007

AREA

NO. OF

F.A PER

TOTAL F.A

COOLING

WATER

M2

PERSONS

PERSON

CFM

CAPACITY T.R.

GPM

ZONE NAME

T.R./M2

REV.

TOTAL

design data effected

CFM
F.A %

ONE A/C

CFM

NOTES
PER T.R

Lighting W/F2

EQ.KW

EQ.W/F2

30

LO-030

128

26

11

269

5.4

9.1

23.5

2816

10

392

517

4.5

1.3

1.0

TREATED F/A

31

LO-030A

72.5

15

11

152

3.1

5.2

23.5

1595

10

222

517

4.5

0.8

1.0

TREATED F/A

32

LO-031

54.8

11

11

115

2.3

3.9

23.5

1206

10

168

517

4.5

0.6

1.0

TREATED F/A

33

LO-031A

57.6

12

11

121

2.5

4.1

23.5

1267

10

176

517

4.5

0.6

1.0

TREATED F/A

34

LO-032

56.8

11

11

119

2.4

4.0

23.5

1250

10

174

517

4.5

0.6

1.0

TREATED F/A

35

LO-033

149

30

11

313

6.3

10.6

23.5

3278

10

456

517

4.5

1.6

1.0

TREATED F/A

36

LO-034

152.3

30

11

320

6.5

10.8

23.5

3351

10

466

517

4.5

1.6

1.0

TREATED F/A

37

LO-035

152.3

30

11

320

6.5

10.8

23.5

3351

10

466

517

4.5

1.6

1.0

TREATED F/A

38

LO-036

143.5

29

11

301

6.1

10.2

23.5

3157

10

439

517

4.5

1.5

1.0

TREATED F/A

39

LO-037

81.5

16

11

171

3.5

5.8

23.5

1793

10

249

517

4.5

0.8

1.0

TREATED F/A

40

LO-038

156

31

11

328

6.6

11.1

23.5

3432

10

477

517

4.5

1.6

1.0

TREATED F/A

41

LO-039

151.5

30

11

318

6.4

10.8

23.5

3333

10

463

517

4.5

1.6

1.0

TREATED F/A

42

LO-040

56.4

11

11

118

2.4

4.0

23.5

1241

10

173

517

4.5

0.6

1.0

TREATED F/A

43

LO-041A

57.3

11

11

120

2.4

4.1

23.5

1261

10

175

517

4.5

0.6

1.0

TREATED F/A

44

LO-041

54.8

11

11

115

2.3

3.9

23.5

1206

10

168

517

4.5

0.6

1.0

TREATED F/A

45

LO-042

182.5

37

11

383

7.8

13.0

23.5

4015

10

558

517

4.5

1.9

1.0

TREATED F/A

46

LO-043

179

36

11

376

7.6

12.7

23.5

3938

10

548

517

4.5

1.9

1.0

TREATED F/A

47

LO-044

118.1

24

11

248

5.0

8.4

23.5

2598

10

361

517

4.5

1.2

1.0

TREATED F/A

48

LO-045

163.7

33

11

344

7.0

11.6

23.5

3601

10

501

517

4.5

1.7

1.0

TREATED F/A

49

LO-046

161.4

32

11

339

6.9

11.5

23.5

3551

10

494

517

4.5

1.7

1.0

TREATED F/A

50

LO-047

199

40

11

418

8.5

14.1

23.5

4378

10

609

517

4.5

2.1

1.0

TREATED F/A

51

LO-048

194.2

39

11

408

8.3

13.8

23.5

4272

10

594

517

4.5

2.0

1.0

TREATED F/A

52

LO-049

110.2

22

11

231

4.7

7.8

23.5

2424

10

337

517

4.5

1.1

1.0

TREATED F/A

53

LO-050

160.6

32

11

337

6.8

11.4

23.5

3533

10

491

517

4.5

1.7

1.0

TREATED F/A

54

LO-051

181.8

36

11

382

7.7

12.9

23.5

4000

10

556

517

4.5

1.9

1.0

TREATED F/A

55

LO-052

188.8

38

11

396

8.0

13.4

23.5

4154

10

578

517

4.5

2.0

1.0

TREATED F/A

56

LO-053

179.5

36

11

377

7.6

12.8

23.5

3949

10

549

517

4.5

1.9

1.0

TREATED F/A

57

LO-054

185

37

11

389

7.9

13.1

23.5

4070

10

566

517

4.5

1.9

1.0

TREATED F/A

58

LO-056

178.6

36

11

375

7.6

12.7

23.5

3929

10

546

517

4.5

1.9

1.0

TREATED F/A

59

LO-057

182

36

11

382

7.7

12.9

23.5

4004

10

557

517

4.5

1.9

1.0

TREATED F/A

60

LO-058

181.5

36

11

381

7.7

12.9

23.5

3993

10

555

517

4.5

1.9

1.0

TREATED F/A

61

TELECOM ROOM

36

11

76

1.7

2.9

21.0

771

10

110

450

0.6

1.5

TREATED F/A

62

FIRST AID

22

11

46

1.0

1.7

21.0

471

10

67

450

0.2

0.8

TREATED F/A

63

POLICE

12

11

25

0.6

1.0

21.0

257

10

37

450

0.1

0.8

TREATED F/A

64

ELEC

18

11

38

1.1

1.8

17.0

540

55

510

2.0

10.3

TREATED F/A

65

SERVICE LOBBY

67

13

11

141

2.6

4.3

26.0

1263

11

205

490

0.5

0.7

TREATED F/A

66

GARBAGE ROOM

0.2

0.4

27.0

89

18

400

0.1

0.8

TREATED F/A

360.0

601.1

8120.7

17,041

ECG Engineering Consultants Group


PROJECT: NOZHA CITY CENTER

REV:

SUBJECT : ESTIMATE COOLING LOAD CALCULATIONS FOR GROUND FLOOR


SERIAL

DATE : MAY 2007

AREA

NO. OF

F.A PER

TOTAL F.A

COOLING

WATER

M2

PERSONS

PERSON

CFM

CAPACITY T.R.

GPM

ZONE NAME

T.R./M2

REV.

TOTAL

design data effected

CFM
F.A %

ONE A/C

CFM

NOTES
PER T.R

Lighting W/F2

EQ.KW

EQ.W/F2

67

RO-01

372

266

20

5,314

38.0

63.4

9.8

8807

60

1138

232

4.0

1.0

68

RO-02

458

327

20

6,543

46.7

78.0

9.8

10842

60

1401

232

4.0

0.8

NORMAL F/A

69

ATM

52

20

20

2.3

3.8

23.0

1119

159

495

4.0

7.1

TREATED F/A

70

MO-01

966

193

11

2,029

46.7

77.9

20.7

15633

13

2955

335

4.5

10.0

1.0

NORMAL F/A

71

MO-02

1238

248

11

2,600

59.2

98.9

20.9

19725

13

3787

333

4.5

12.0

0.9

NORMAL F/A

72

MAIN ENTRANCE

310

31

12

372

10.0

16.7

31.0

3300

11

948

330

4.5

12.0

3.6

NORMAL F/A

73

HYPER MARKET

630.0

NORMAL F/A

0.0

74

CORRIDOR

3131

313

12

3,757

87.0

145.2

36.0

35311

11

11051

406

3.5

0.1

NORMAL F/A

75

SERVICE CORRIDOR

193

19

12

232

5.1

8.5

38.0

2062

11

568

406

1.0

0.5

NORMAL F/A

14840.7

37,907

1284.9

TOTAL FRESH AIR FOR GROUND FLOOR =

37,907

CFM

TOTAL TREATED FRESH AIR FOR GROUND FLOOR =

17,061

CFM

TOTAL LOAD TREATED FRESH AIR FOR GROUND FLOOR=

113.9

TR

TOTAL LOAD OF GROUND FLOOR WITH OUT F/A =

1,285

TR

TOTAL LOAD OF THE GROUND FLOOR TR =

1,399 TR