ModbusconfigurationexampleforanAllenBradleyMicrologix1400MestaAutomation
PLC
WPF
C#
Downloads
About
SubscribebyEmail SubscribetoRSS
Youarehere:Home>ModbusconfigurationexampleforanAllenBradleyMicrologix1400
ModbusconfigurationexampleforanAllenBradley
Micrologix1400
by Mesta on JUNE 19, 2012 in ALLEN BRADLEY, PLC
MOSTPOPULAR
Tweet
Like
Share
Share
ThelatestPLCAllenBradleyMicrologix1400isprovidedwithModbusTCPandRTU.Thisis
apowerfulfeatureandwiththispostiexplainhowtoenableandhowtouseit.
ToconfiguretheModbuscommunicationyouneedtoknowatleastthebasicinformation
aboutModbusprotocol.
RoboticCase
Packer
CallTodaytoDiscussYour
RoboticCasePackingNeeds!
(usuallyasupervisor)andasmanyslaveasyouwant.EveryslavehasaNodeaddress,so
themastercansendpackettoasingleslave.MasterdoesnothavetheNodeaddress.
The registers
Weusecookiestoensurethatwegiveyouthebestexperienceonourwebsite.If
youcontinuetousethissitewewillassumethatyouarehappywithit.
Youhave4typesofregisters:
Ok
FOLLOWMESTAAUTOMATION
2arereadonly(forbitsandintegers)
2arereadableandwritable(forbitsandintegers)
Booleanblockes.B3:
ReadOnlyregistersarecalledContacts.
Read/WriteregistersarecalledCoils.
Numericblockes.N7:
ReadOnlyregistersarecalledInputRegisters.
Read/WriteregistersarecalledHoldingRegisters.
MestaAutomation
59likes
LikePage
80
subscribers
Share
12
followers
RECENTPOSTS
http://www.mestaautomation.com/modbusconfigurationexampleforanallenbradleymicrologix1400/
1/7
26/09/2015
ModbusconfigurationexampleforanAllenBradleyMicrologix1400MestaAutomation
OxyPlot: a new open source chart
library for WPF
RECENTCOMMENTS
Importantnote:onceyouflagModbusTCPandsavetheconfiguration,youshouldpowerup
thePLCagain.
mesta
Hi Daniela, to get
started with simple
communication you can download
the sources
(https://goo.gl/LeZkbk) and...
Sep 20, 7:24 PM
jblee
Plc.DB1.cs :The following
code was added. PlcTag.cs :The
following code was added.
MainWindow.xaml.cs : The...
Sep 18, 10:26 AM
RoboticCase
Packer
CallTodaytoDiscussYour
RoboticCasePackingNeeds!
Block configuration:
CATEGORIES
C# (24)
Fonts (2)
Graphics (3)
PLC (29)
Scada (2)
WPF (33)
ARCHIVES
Withthisconfigurationihave:
B9:readonly
B10:r/w
N7:readonly
N15:r/w
2015 (1)
January (1)
2014 (3)
2013 (2)
2012 (26)
2011 (4)
2010 (1)
Expandedflag:thisflagpermittouse4moreNregisterscontigoustoN15inorderto
expandtheholdingregistersarea.
ToenableexpandedregistersyouneedtodeclareN15N16N17N18N19andtoset
alltheregisterswordsto256.
http://www.mestaautomation.com/modbusconfigurationexampleforanallenbradleymicrologix1400/
2/7
26/09/2015
ModbusconfigurationexampleforanAllenBradleyMicrologix1400MestaAutomation
Sample code
Youcandownloadasampleapplicationfromhere.
TheprogramhasbeentestedwiththeModbusTCPtesterthatyoucanfindat
http://www.codeproject.com/Articles/16260/ModbusTCPclass.
Tweet
Like
Share
Share
Related
PLCPCcommunicationwith
C#:aquickresumeabout
dataexchangelibraries
In"AllenBradley"
ModbuswithC#:libraries,
code,utilitiesandexamples
In"C#"
ResourcesforSiemensand
AllenBradleyPLCs:PLC
DEVwebsite
In"AllenBradley"
AllenBradley,Modbus,PLC,PLCprogramming
GitHub:GITGUItutorialtogetstartedwithgit
Dataexchangebetween2Controllogixusingproducedandconsumedtags.
mestaSeptember18,2012at21:26#
IwasrunningRsLogix500version8.40.00.
PleasenotethatModbusprotocolisavailableonlyonMicrologix1400Ser.B.
Micrologix1400Ser.AdoesntprovideModbuscommunication.
REPLY
http://www.mestaautomation.com/modbusconfigurationexampleforanallenbradleymicrologix1400/
3/7
26/09/2015
ModbusconfigurationexampleforanAllenBradleyMicrologix1400MestaAutomation
shridharNovember20,2013at07:05#
8.3rlater
REPLY
ducsiSeptember9,2013at12:35#
HelloMesta,
DoyouknowhowmanyclientconnectionsaMicrologix1400Ser.B.canhandle?
ItrytoconnecttoaPLCfroma2ndPCanditdoesnotwork.
REPLY
mestaSeptember9,2013at13:56#
ItdependsifitsModbusTCPorRTU.
ForModbusTCPiconnectedupto3computerstimeago,butinevertriedwith
more.
ForModbusRTUitdependsiftheMicrologisissetasmasterorslave.
REPLY
sarangSeptember17,2013at08:24#
Himesta,
IhaveMicrologix1400SerBPLC.IhavetoestablishacommunicationwithModbus
TCP&RTU.HowtouseRSLinxClassictoconfiguredriverforthesame?
REPLY
mestaSeptember17,2013at16:01#
RsLinxcantcommunicateinModbus,itusestheproprietaryprotocols
ofRA.
TheethernetportofMicrologixcancommunicatewith2or3protocols
simultaneously,andthesimilEthernet/IPisthedefault,andyoucanchoose
whatotherprotocolyouwanttocommunicatewith,inyourcaseModbus.
SowithRsLinxyousetEthernetDevices(notEthernet/IP,itwillnotwork)and
youcancommunicatewithRsLogix,whilewithyourapplicationsandotherplcs
youcommunicateinModbus.
REPLY
sarangOctober16,2013at10:07#
HiMesta,
WhataboutModbusRTU???WhatIamsupposedtoselectinRsLinxwhile
configuringML1400SerBthroughModbusRTU?Ihavedonechannel
configurationthroughRSLogix500.Butitisunabletoestablisha
communicationlink.
Kindlyrevertback.
REPLY
mestaOctober16,2013at12:25#
IdontrememberiftheserialportofMicrologixcantalk2
differentprotocols.Ifitdoes,thenyouhavetoselectDF1inRsLinx.If
itcancommunicateonlyModbusRTU,youhavetousetheotherserial
portorconnectthroughtheethernetport.
http://www.mestaautomation.com/modbusconfigurationexampleforanallenbradleymicrologix1400/
4/7
26/09/2015
ModbusconfigurationexampleforanAllenBradleyMicrologix1400MestaAutomation
krishnaSeptember19,2013at06:00#
HiMesta,
Iamannewbiein.net,basicallyfromPLC,SCADAdomain.
BigfanofADVHMI,Nowcansomeonesharemeaprojectwheretherealtimedata
fromPLCcanbeloggedtosqlserver.
Iwanttomakeascreenfordataandanotheroneforreports.
Doessomeonehavedonethisinadvancedhmi.
Thanks
Krishnamoorthy
REPLY
HectorQuirozOctober22,2013at17:37#
HelloMesta:
ImworkingwithwebserverembedonMicrologix1400PLCandRSLogix8.40.
ImonitoreddirectoryenabledandN7:0,(eg)
Usingcodes<ABDRTxxx)butonlyforreading,myquestionis:
IsthereanycodewithwhichIcannowwritetothatblock(N7:0)?
Thankyou.
REPLY
mestaOctober22,2013at19:11#
IhavenoexperienceofworkingwithembeddedwebserverofMicrologix
1400.IntheprojectsbasedonML1400wasusingEthernet/IP,OPCclientor
ModbusTCPprotocolswithallofthemiwasusingC#orANSICcompilers.
REPLY
shridharNovember20,2013at07:11#
HImesta
doyouhaveasamplerslogix500plcprogramformodbusTCP/IPcommunicationpls
sendmeonshridharhanamannavar@gmail.com
REPLY
mestaNovember20,2013at10:56#
Actuallyidonthaveaworkingsample,butyoucantestthatifyour
programworksbyusingtheModbusclientthatyoucanfindon
http://www.plcsimulator.org/
REPLY
RohanAugust18,2014at09:09#
Haveyougotsolutionforyourabovesaidquestion?iamworkingonthe
sameifyouhaveanydetailspleasesharewithmealso.
Thankx
REPLY
mestaAugust26,2014at10:56#
http://www.mestaautomation.com/modbusconfigurationexampleforanallenbradleymicrologix1400/
5/7
26/09/2015
ModbusconfigurationexampleforanAllenBradleyMicrologix1400MestaAutomation
ActuallyIdonthavethehardwareneededtomaketests,soicant
makeaprogramandassureyou100%itworks.Atthetimethati
wrotethearticle,iwasworkingonaprojectwheretheML1400was
connectedviaModbusTCPwithotherPLCsanditwasworking.
REPLY
RohanAugust18,2014at09:10#
Mymailaddressisrohan_984@yahoo.com
REPLY
padmarajApril25,2014at02:23#
Imake.Alltheconfigurationasyousaidbutthereisconnectiontimeoutbya
networkthismessageiscomingout
REPLY
padmarajApril25,2014at02:26#
IsthispossibletheChanel0makemodbusRTUandChanel1makemod
busTCPinsameplc
REPLY
AnonymousApril30,2014at16:52#
Mesta,samequestionaspdmaraj:isitpossibletousebothChannel0
(ModbusRTU)andChannel1(ModbusTCP)atthesametime?Mygoalisto
read/writedataonbothchannelsasIdohaveaRS485networkandthePLC
communicateswiththescadausingmodbusTCPTHANKS!
REPLY
mestaMay2,2014at13:22#
AccordingtoRsLogix,itseemsthatyoucanuseModbusRTUonchannel
0.AtleastinmyversionyoucansetModbusontheprotocolinsteadofDF1.
REPLY
PhillMcKieMay20,2014at11:28#
Hi,doyouhaveanyexamplesshowingtheuseofModbusRTUMaster?I
haveanAseries1400andImtryingtoconfigureaRTUmaster
REPLY
AnonymousFebruary11,2015at10:33#
hiiwanttotakeDeltaDTA4848TemperatureControllerDataonAllen
BrdleyML1400orML1100PLC..AnyBodycanpleasetellmethefullprocedure
REPLY
mestaFebruary14,2015at11:47#
Youhavetosetupmessages.Googleformicrologixmessagingmodbus,
thereareplentyofexamples.
http://www.mestaautomation.com/modbusconfigurationexampleforanallenbradleymicrologix1400/
6/7
26/09/2015
ModbusconfigurationexampleforanAllenBradleyMicrologix1400MestaAutomation
REPLY
JoeApril3,2015at19:19#
WhileusingaMicroLogix1400asaserialModbusRTUslaveIamnotableto
findthelocationofthediscreteinputs(contacts).Theyarenotshowingupinthe
1000119999rangeasdocumentationsuggested.Doyouhaveanyideas?Thanks.
REPLY
mestaApril7,2015at07:55#
Didyoutrytochecktheaddressfrom0000to9999?Becauseusually
thefirstnumberisthefunctionidentifier,and1meanscontactaddressarea.
Therearedifferentfunctionsforeachaddressarea(1234etc).
REPLY
SinghApril26,2015at10:09#
DEARALL,
iamfacingproblemtoaccessdataofmasibustemperaturescannerthroughmodbus
TCP/IPonML1400.IfanyoneofyouhavesampleapplicationofML1400
communicationwithanydeviceonmodbusTCP/IPpleasesendmeat
chauhan.singhraj@gmail.com
REPLY
kristopherMay8,2015at20:24#
Pleasehelpme!!!
howtosetuptheMl1400rev.bbymodbusTCPlikeaclient?
REPLY
mestaMay11,2015at19:22#
IfML1400hastoreadfromaModbusserver,youcandoitwith
messages.Itshouldntbedifficult,justrunasearchongoogle.
REPLY
Leave a Reply