IFMS TAG: CAR - Other carrier
Water ingress had damaged Eltek FP2 DC Power System.
Backplane is corroded. AC circuit breaker trips even when
rectifiers jacked out and DC load breakers isolated.
Please dispatch to VHA for rectification.
Reason: Field Access Device
From: Andy Wilkinson
Sent: Wednesday, 12 August 2015 1:18 AM
To: 'Vha, Flm (Nokia - Global)';
'venkidesh.bhaskaran@nsn.com'; 'bala.l.ext@nsn.com'
Cc: Muhammad Junaid; Chung Chan
Subject: Isolation for OVL:5651 INC000010994010 PR:12947219
Hi NSN,
I tried to upload this image to OVL however it is too large.
OVL back with VHA to action
Your tech Sonik Arora attended yesterday 25/08. He performed some testing, and a
pparantely found nothing wrong. Wanted Optus to check config. Issue still exists
. We have checked configs for this site and all settings are correct. Reset RFU
boards which carry these F4 frequencies and no change. Reset TMAs and no change.
Locked down L2300 onsite and no change. Checked neighbouring sites and no issue
s seen (no external interferer). Only things left are the feeders above the comb
iner and/or the antenna. Thanks