Sunteți pe pagina 1din 12

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

1. GENERAL DATA AND INFORMATION.


Panel No.
6L1B
Make
SIEMENS
Serial No
BF0710070
No of BO contacts BO31

Designation
Model No
Aux.volts
No of BIContacts

87L1-1/21-1/67N-1
7SD5221-5DB29-7HM7-2A
125 VDC
BI24

2. MECHANICAL CHECKS AND VISUAL INSPECTION.


ITEM
DESCRIPTION
1.
Inspect for any physical damage or defects.
2.
Verify connections as per approved drawing.
3.
Check tightness of all connections.
4.
Test switch / plug checked for correct function.

Yes
Yes
Yes
Yes

3. ELECTRICAL TESTS
FUNCTION TEST
ITEM
DESCRIPTION
1.
Case Earthing checked
2.
Indication checked
3.
Trip/Output contacts checked
4.
Binary input checked

Yes
Yes
Yes
Yes

REMARKS

REMARKS

4. METERING CHECK.
4.1 CURRENT INPUT CHECK:
Injected
Phase
CT Ratio Applied
Amps(A)
RN
1.00
800/1A

Displayed Primary
value (A)
799

1.00

800/1A

1.00

798

BN

1.00

800/1A

1.00

799

RN

0.50

800/1A

0.50

399

YN

0.50

800/1A

0.50

399

BN

0.50

800/1A

0.50

399

JAL INTL

N/A
N/A
N/A
N/A

Displayed
secondary value(A)
1.00

YN

Tested By

N/A
N/A
N/A
N/A

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

4.2 VOLTAGE INPUT CHECK:


Injected
Phase
Voltage(V)

PT Ratio Applied

Displayed
secondary value(V)

Displayed Primary
value (KV)

RN

66.40

115KV/115V

66.35

66.00

YN

66.40

115KV/115V

66.33

66.00

BN

66.40

115KV/115V

66.35

66.00

RN

33.20

115KV/115V

33.17

33.00

YN

33.20

115KV/115V

33.16

33.00

BN

33.20

115KV/115V

33.17

33.00

RY

115

115KV/115V

114.89

115.00

YB

115

115KV/115V

114.90

115.00

BR

115

115KV/115V

115.00

115.00

INPUT
RYB Frequency
RYB P
RYB Q
RYB S

INJECTED VALUE
3 ph nominal voltage
& Current with 0
degree Phase shift.
Voltage = 66.4 P-N
Current = 1A

RYB PF

EXPECTED VALUE
60HZ

DISPLAYED VALUE
60 .0HZ

159 MW

159.0 MW

0 MVAR

0.00 MVAR

159 MVA

159 MVA

1.00

1.00

Calculated :
P = 3 VI Cos
Q = 3 VI Sin
S = 3 VI
INPUT & OUTPUT FUNCTIONAL CHECK:
Tested By

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

BINARY
INPUT

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

CONTACTS

REMARKS

BINARY
OUTPUT

CONACTS

REMARKS

LED

REMARKS

BI 1

K17-K18

OK

BO 1

K5-K6

OK

OK

BI 2

J1-J2

OK

BO 2

K5-K7

OK

OK

BI 3

J3-J5

OK

BO 3

K5-K8

OK

OK

BI 4

J4-J5

OK

BO 4

K9-K10

OK

OK

BI 5

J6-J5

OK

BO 5

K11-K12

OK

OK

BI 6

J7-J8

OK

BO 6

K13-K14

OK

OK

BI 7

J9-J10

OK

BO 7

K15-K16

OK

OK

BI 8

J11-J12

OK

BO 8

R1-R5

OK

OK

BI 9

P17-P18

OK

BO 9

R2-R5

OK

OK

BI 10

N1-N2

OK

BO 10

R3-R5

OK

10

OK

BI 11

N3-N5

OK

BO 11

R4-R5

OK

11

OK

BI 12

N4-N5

OK

BO 12

R6-R5

OK

12

OK

BI 13

N6-N5

OK

BO 13

R7-R8

OK

13

OK

BI 14

N7-N8

OK

BO 14

R9-R10

OK

14

OK

BI 15

N9-N10

OK

BO 15

R11-R12

OK

BI 16

N11-N12

OK

BO 16

P3-P4

OK

BI 17

H17-H18

OK

BO 17

P6-P5

OK

BI 18

G1-G2

OK

BO 18

P7-P5

OK

BI 19

G3-G5

OK

BO 19

P8-P5

OK

BI 20

G4-G5

OK

BO 20

P9-P10

OK

BI 21

G6-G5

OK

BO 21

P11-P12

OK

BI 22

G7-G8

OK

BO 22

P13-P14

OK

BI 23

G9-G10

OK

BO 23

P15-P16

OK

BI 24

G11-G12

OK

BO24

H3-H4

OK

BO 25

H6-H5

OK

BO 26

H7-H5

OK

BO 27

H8-H5

OK

BO 28

H9-H10

OK

BO 29

H11-H12

OK

BO 30

H13-H14

OK

BO 31

H15-H16

OK

5. DIFFERENTIAL PROTECTION.
Tested By

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

Operating unit: 87L1: I diff>


Phase
Setting current(A)

Remarks: Pick up tolerance 5% of set value or 10mA


Pick up value (A)
Drop off value(A)
Remarks

0.3

0.317

0.164

OK

0.3

0.317

0.162

OK

0.3

0.317

0.164

OK

RY

0.3

0.317

0.164

OK

YB

0.3

0.316

0.162

OK

BR

0.3

0.316

0.162

OK

RYB

0.3

0.317

0.162

OK

5.1 Time measurement.


Phase
RN

SETTING CURRENT:2.50 x Is :2.50 x 0.3 =0.750 A


Setting
Measured time at
Tolerance
current(Is)
2.5xIs(m.sec)
0.3
28.4
Typical :29.0mse

YN

0.3

28.1

BN

0.3

28.7

RY

0.3

28.6

YB

0.3

28.0

BR

0.3

28.7

5.2 MEASUREMENTS FOR DIFF & BIAS CURRENT WITH LOCAL RELAY.
Measurements are made in % of Idiff.L1 set.
Tested By

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

I diff L1 set: 0.3


Phase

Inj.
amps

A
B
C
ABC

Local end measurement in % of I diff set.

Remote end measurement in % of I diff se

Idiff.
L1

I diff.
L2

I diff.
L3

I rest.
L1

I rest.
L2

I rest.
L3

3I0I
diff

I
diff
.L1

Idiff
.L2

I
diff
.L3

I
rest
. L1

I
rest
. L2

I
rest
. L3

3I0I
diff

1.0

99.6

0.00

0.00

31.9

31.4

31.4

99.5

99.5

0.00

0.00

31.6

31.3

31.4

99.5

1.0

0.00

99.6

0.00

31.3

32.1

31.6

99.6

0.00

99.5

0.00

31.4

32.4

31.4

99.4

1.0

0.00

0.00

99.7

31.3

31.6

31.6

99.6

0.00

0.00

99.6

31.3

31.4

32.4

99.7

1.0

99.7

99.6

99.6

32.1

32.1

31.9

0.00

99.3

99.5

99.6

32.1

32.5

32.4

0.00

Note :I diff = Vector sum of local +remote amps.


Bias =magnitude of I diff L1 set + errors in measurements.
5.3 RESTRAIN CHARECTERISTIC MEASUREMENT.
I Diff set: 1A
I bias: I diff set (Diff Characteristic Angle 45 deg.)
Local end
Remote injected
Phase
injected amps(A)
amps(A)
A
1
1.333

I Diff
Measured(%)
33.2

I Restrain
measured(%)
33.6

1.333

33.3

33.6

1.332

33.0

33.3

5.4 87 L2 second stage diff. I Diff.: >>


Set Amps: 1.0 A
Tested By

Injected amps : 2.5 x In=2.5 A


JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

Phase

PU Amps

Trip time (ms)

Tolerance

0.986

13.5

Pick up 5% or 10 mA.

0.987

13.4

0.985

13.7

6. DISTANCE PRORECTION:
ZONE AND TIME SETTINGS: RELAY CHARACTERISTICS (Quadrilateral)
Parameter

Z1

Z1B

Z2

Z3

Z4

Z5

Direction

Forward

Forward

Forward

Forward

Reverse

Non-directional

1.00

1.50

2.00

3.00

4.0

5.00

1.00

1.50

2.00

3.00

4.0

5.00

Re

1.00

1.50

2.00

3.00

4.0

5.00

Time (sec)

0.00

0.00

0.60

0.80

1.0

1.50

Set XE/XL:

1.0

RE/RL:1.0

R-resistive reaches for phase to phase Fault.


Re-resistive reach for phase to earth fault.
X-reactive reaches for phase to phase & phase to earth fault.

6.1 IMPEDENCE REACH TEST:


Sl.No.
Tested By

Description

Checked

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

Print out from freja attached

OK

6.2 OPERATING TIME TEST:


Sl.No.

Description

Checked

Print out from freja attached

OK

7. POWER SWING DETECTION:


1. Operation checked : OK
2. Blocking time measured using oscilographic recorder : 83 ms
8. DISTURBANCE RECORDER:
Checked event recording through DIGSI software: OK
9. FAULT LOCATER:
X=0.15 ohm/Km
Distance
25
50
75
100

Distance: 10.0 KM

Tolerance 2.5%
Measured distance(KM)
CN
AB
BC

Applied X
value

Expected
distance

AN

BN

0.375

2.5

2.5

2.5

2.5

2.5

0.750

5.0

5.0

5.0

5.0

1.125

7.5

7.5

7.5

1.500

10.0

10.0

10.0

CA

ABC

2.5

2.6

2.5

5.0

5.0

5.0

5.0

7.5

7.5

7.5

7.5

7.5

10.0

10.0

10.0

10.0

10.0

10.TELE PROTECTION SCHEME FOR DISTANCE PROTECTION:

Tested By

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

Permissive under reach scheme: (PUTT)


Set Z1=80% Z1B

Z1B=100%

Check CS with Z1.


Trip Logic ZIB x CR: OK
Trip Time With Out CR: 624 ms
Trip Time with CR: 21.6 ms
Permissive over reach scheme: POTT
Set: Z2=Z1B
Check Cs With Z2: OK
Trip Time With Out CR : 623.4 ms
Trip Time with CR: 21.9 ms
Blocking scheme:
Z3 reverse
CS with reverse zone: OK
Trip Time with CR :

635ms

Trip Time with out CR : 35.5 ms

11. RESIDUAL EARTH FAULT PROTECTION (DEF):


Angular measurement:
Tested By

Tolerance: 2

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

DIRECTION

SET VALUE

MEASURED
TRIPPING

MEASURED
BLOCKING

337.7 - 121.1

121.3-337.8

121.1 - 338.1

338 -121.1

=338
FORWARED

=122
= 338

REVERSE

= 122

Sensitivity check:
Characteristics: DEF forward
Measured Vo (Volts)
Set value Vo (Volts)
Pick up
Drop off

Measured Io (amp)
Pick up
Drop off

Set value Io (Amp)


0.5
1.0

0.504
1.006

0.474
0.946

2
5

2.01
5.01

TIME MEASUREMENT: set Io = 1.5 x Is= 1.5 A


Sl.no
1
2

Set time (sec)

Actual time(sec)

1.03

2.02

12. TELE PROTECTION SCHEME FOR DEF PROTECTION:


Directional comparison:

Tested By

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

1.86
4.66

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

Send logic : forward fault. : OK

Trip time with CR

: 26.9ms

Trip logic: forward fault +CR: OK

Trip time without CR: 1.02 Sec.

Week in feed: Trip and Echo Set V 25. Measured volts: OK


Blocking
Send logic: reverse Fault:

OK

Trip logic: Forward fault +NO CR:

Trip time with CR l: 1.02 Sec


OK

Trip time without CR: 26.1 ms

13. AUTOMATIC SWITCH ON TO FAULT FUNCTION:


Distance + CB close command.
Zone used for non directional Acceleration: non directional.
External activation of SOTF function: Z5+ CB close command.
Operating time : 39.4 ms
14. FUSE FAILURE SUPERVISION (ZERO SEQUENCE) FUNCTION:
Phase

Set 3U0>(Volts)

Pick up Volts

Set 3I0>(Amps)

Pick up(Amps)

36.35

0.101

36.39

30

0.101

0.1

36.40

0.101

Blocking of tripping zone in case of fuse fails in any phase: OK


15.1. BACK UP OVER CURRENT PROTECTION I>:
Phase

Set value I>


Tested By

Operate value(Amps)
PICK UP
DROP OFF

JAL INTL

Set time delay


(Sec)

Op.time at 1.5 x
Is (sec)

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

AN
BN
CN

1
1
1

0.999
1.000
0.998

0.933
0.934
0.928

3.0
3.0
3.0

3.03
3.03
3.03

Set time delay


(Sec)
5.0
5.0
5.0

Op.time at 1.5 x
Is (sec)
5.03
5.03
5.03

BACK UP OVER CURRENT PROTECTION I>>:


Phase

Set value I>

AN
BN
CN

1.0
1.0
1.0

Operate value(Amps)
PICK UP
DROP OFF
1.000
0.934
1.002
0.934
1.000
0.933

BACK UP OVER CURRENT PROTECTION I Inverse:


Normal Inverse
Phase

Set value I>

AN
BN
CN

1
1
1

Pickup value: Expected 10% set value above


Operate value(Amps)
Op.time at 3 x Is (sec)
Set time
delay
Actual
Expected
PICK UP
DROP OFF
(Sec)
time
time
1.100
1.027
0.50
3.15
3.18
1.101
1.028
0.50
3.15
3.18
1.100
1.026
0.50
3.15
3.18

Very Inverse
Operate value(Amps)
Phase

Set value I>

AN
BN
CN

1
1
1

PICK UP

DROP OFF

1.100
1.100
1.103

1.029
1.028
1.026

Set time
delay
(Sec)
0.50
0.50
0.50

Op.time at 3 x Is (sec)
Actual
Expected
time
time
3.37
3.375
3.37
3.375
3.37
3.375

Set time
delay
(Sec)

Op.time at 3 x Is (sec)
Actual
Expected
time
time

Extremely Inverse
Operate value(Amps)
Phase

Set value I>


Tested By

PICK UP

DROP OFF

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

JAL International

SITE INSPECTION AND TEST RECORD

Description 7SD522 LINE DIFF.RELAY

Sheet No:

&DISTANCE PROTECTION.

AN
BN
CN

0f

Customer

SEC-ERB

Customer Ref:

Site

115/34.5KV JUBAIL(44BC)S/S

Contract No :

1
1
1

1.100
1.100
1.100

1.027
1.027
1.026

0.50
0.50
0.50

5.0
5.0
5.0

5.0
5.0
5.0

Long time Inverse


Operate value(Amps)
Phase

Set value I>

AN
BN
CN

1
1
1

PICK UP

DROP OFF

1.102
1.100
1.100

1.027
1.025
1.026

Set time
delay
(Sec)
0.50
0.50
0.50

Op.time at 3 x Is (sec)
Actual
Expected
time
time
30.03
30.0
30.02
30.0
30.00
30.0

16. TEST EQUIPMENT USED:

1. Freja 300 relay test unit


2. FluKe-187 Multitester.
3. TOSHIBA laptop with DIGSI software.
4. DELL laptop with DIGSI SOFTWARE

Tested By

JAL INTL

Test Witnessed By SEC

Name: SENTHIL KUMAR.A

Name: Mr. MOEED

Sign:

Sign:

Date:

Date:

S-ar putea să vă placă și