Documente Academic
Documente Profesional
Documente Cultură
Project no :
Date :
Services :
Tittle :
Revision :
Mydin, Karamunting
5013-61
December-15
Electrical
Electrical Load
00
Area
Mall
Food Cour
M&E
Loading Area
Store
Hypermarket
Covered Carpark
Office
Chiller System
Cold Room
Area (m2)
Area (ft2)
4,510.07
48,546.00
903.67
9,727.00
648.00
6,975.00
646.98
6,964.00
1,945.67
20,943.00
5,098.98
54,885.00
1,912.04
20,581.00
248.05
2,670.00
15,913.45
171,291.00
Total Load (kW)
Group Diversity Factor (0.8 applied)
Total kVA
kW/m2
kW
Amp (A)
Essential Mode
0.10
0.10
0.03
0.06
0.03
0.10
0.03
0.03
-
451.01
90.37
19.44
38.82
58.37
509.90
57.36
7.44
670.00
243.90
739.65
148.20
31.88
63.66
95.73
836.23
94.07
12.20
1,098.80
400.00
135.30
27.11
19.44
11.65
17.51
152.97
17.21
7.44
0.00
243.90
1,902.70
3,120.43
632.53
2,496.35
1,522.16
1,790.78
790.66
2 No 1250KVA Transformer required
1 No of 1000 kVA Genset Required