Generator Circuit Breaker GT32 Troubleshot details

Initial checks:
Before starting stroking of the coils, we observed motor was starting for 1-2sec
in every 5min, we have switched off the motor supply and waited for the spring
to discharge at its maximum level, we noted that the spring is actually
discharging and has gone to maximum up to 16mm linear motion, after this rate
of discharge is very slow approx. 1mm/15-20min.
Cam operation checked and found working fine, as soon as spring discharged it
activates the cam switch and start the motor.

GT 32 MEASUREMENTS
Breaker open and spring charged
Measurement noted

9mm

Breaker closed and spring discharged charged[1/4]


Measurement noted

27mm

Breaker open and spring discharged charged[1/2]


Measurement noted

Breaker close and spring discharged charged[3/4]

47.5mm

Generator Circuit Breaker GT32 Troubleshot details


Measurement noted

62.5mm

Breaker open and spring fully discharged charged


Measurement noted

83mm

GT 21 MEASUREMENTS
Breaker open and spring fully charged
Measurement noted

9.3mm

PILOT OPERATING COIL


Y3trip
Y2trip
Y1close

1.5
1.5
1.5

COIL resistance noted


Average Y3/Y2/Y1

150.0 Ohms

Stroking of all the coils performed and observed for 1hour, no spring discharge noted and
no pump motor start noted.
Last pump counter noted is