Abstract
This document shows how to extend existing PTL items. The OMICRON Test Module NetSim will be used
for testing the power swing blocking function during stable power swings and the tripping function during
unstable swings.

OMICRON

Page 1 of 22

General information
OMICRON electronics GmbH including all international branch offices is henceforth referred to as
OMICRON.
The product information, specifications, and technical data embodied in this application note represent the
technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate and
entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be
present.
OMICRON translates this application note from the source language English into a number of other
languages. Any translation of this document is done for local requirements, and in the event of a dispute
between the English and a non-English version, the English version of this note shall govern.
All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming,
optical character recognition and/or storage in electronic data processing systems, requires the explicit
consent of OMICRON. Reprinting, wholly or in part, is not permitted.
OMICRON 2014. All rights reserved. This application note is a publication of OMICRON.

OMICRON 2014

Page 2 of 22

Content
1

Safety instructions .......................................................................................................................... 4

Introduction ..................................................................................................................................... 5

The Emergence of Power Swings and their Detection .................................................................. 6

The OMICRON Protection Testing Library (PTL) ........................................................................... 8


4.1

The Structure of the XRIO Converter ........................................................................................ 8

4.2

Using the Import Filter............................................................................................................... 8

Adding a NetSim Module for Power Swing Blocking ..................................................................... 9

Adding a NetSim Module for Power Swing Tripping ....................................................................15

Tips for Defining a Good Test Case ..............................................................................................17

Testing Power Swing Detection of ABB REL670 and Siemens 7SA631 ......................................18
8.1

Testing Power Swing Blocking of ABB REL670 ........................................................................18

8.2

Testing Power Swing Blocking and Tripping of Siemens 7SA631 .............................................19

List of Literature ...............................................................................................................................21

OMICRON 2014

Page 3 of 22

Safety instructions
This application note may only be used in combination with the relevant product manuals which contain all
safety instructions. The user is fully responsibility for any application that makes use of OMICRON products.
Instructions are always characterized by a symbol even if they are included to a safety instruction.
DANGER
Death or severe injury caused by high voltage or current if the respective
protective measures are not complied.
Carefully read and understand the content of this application note as well as
the manuals of the involved systems before starting its practical application.
Please contact OMICRON before you continue the process if you do not
understand the safety instructions, operating instructions, or parts of it.
Follow each instruction mentioned there especially the safety instructions
since this is the only way to avoid danger that can occur when working at
high voltage or high current systems.
Furthermore, only use the involved equipment according to its intended
purpose to guarantee a safe operation.
Existing national safety standards for accident prevention and
environmental protection may supplement the equipments manual.

Only experienced and competent professionals that are trained for working in high voltage or high current
environments may perform this application note. Additional the following qualifications are required:

authorized to work in environments of energy generation, transmission or distribution and familiar with
the approved operating practices in such environments.

familiar with the five safety rules.

good knowledge of the OMICRON CMC Test and Test Universe software.

OMICRON 2014

Page 4 of 22

Introduction
The OMICRON Protection Testing Library (PTL) provides predefined test plans (Protection Testing
Templates, PTTs) for testing a number of relays including distance protection devices. The respective PTL
item supports the test person in developing a high quality test for the main protection functions in a short
time. But for different reasons power swing detection is not implemented in the PTL. The aim of this
application note is to demonstrate how the OMICRON Test Module NetSim can be added to an existing PTT
to test this function. This is shown for the following three distance protection relays:
> AREVA P442
> ABB REL670
> SIEMENS 7SA631
NetSim will be used to simulate the transient processes in a power network during a power swing to analyze
the protection devices reaction. The whole protection system and not setting parameters is tested thereby.
This kind of testing is called system testing. It proofs whether the IED (Intelligent Electronic Device) will
protect the electrical equipment in the specific case, or not.

OMICRON 2014

Page 5 of 22

The Emergence of Power Swings and their Detection


During the normal operation of the electrical power network the actual load always equals the generation.
But caused by sudden load changes, switching operations or faults this balance can be disturbed. Because
of the inertia of all connected electrical machines and the slow control of the generation of active power
these events result in oscillations of voltages and currents. There are two possible scenarios:
1. The control devices are able to dampen the oscillations and the power system is equilibrated again. We
call that a stable power swing.
2. One or more generators fall out of step and loose synchronism to the remaining network. This is called an
unstable power swing.
During this process the installed distance protection relays measure impedances that can be similar to those
during three phase faults (see Figure 1). If the impedance is within a tripping zone for a long enough time,
the protection device will trip the circuit breaker to disconnect the electrical equipment. During the first case
tripping is not needed as no fault exists on the network and the disturbance will disappear by itself. To solve
the disturbance in the second case a few predefined connections within the network should break before the
whole network splits in separate subnetworks. To define these locations several considerations have to be
made. An activated power swing detection can prevent these non selective trips and thus possible blackouts
like the Northeast Blackout of 2003 in North America.

power swing
detection zone
tripping zone
line
impedance
stable power swing

unstable
power swing

Figure 1: Impedance trajectory during power swings

But how does the IED distinguish between a stable power swing, an unstable one and a fault? While the
impedance change during a power swing is rather slow the impedance vector jumps directly into the tripping
zone at a fault occurrence. At a stable power swing the measured impedance enters the zones from one
side, then turns around and leaves at the same side (see Figure 1). During an unstable power swing the
impedance crosses the X axis completely and leaves the zones on the other side.

OMICRON 2014

Page 6 of 22

The relay manufacturers developed different algorithms to decide which case is present. They all use one or
more of the following criteria:
> Power swing detection zone: As Figure 1 shows, a frame is drawn around the tripping zones or
the starting zones. If the impedance is calculated within this area for a given number of
measurement cycles, it is recognized as slowly changing and thus a power swing. Another
possibility is to determine the time the trajectory needs to move through this area. Position and
size of this frame are important parameters and can be set for some protection devices.
> Monotony: The movement direction in R and X is determined. During a power swing only one
direction is changing.
> Continuity: The measured impedance must be changing with at least a minimum value to
ensure, the trajectory is moving. Otherwise it cannot be a power swing.
> Regularity: The ratio of two successive changes of the measured impedances is below a limit
value. This ensures that the trajectory moves with constant or slowly changing speed, but not
performing rapid changes.
> Out of step detection: It is proved from which side the trajectory enters and leaves the out of
step detection zone (which can be the power swing detection zone or a similar one). Another
criterion is the direction of the impedance movement when crossing the line angle. Depending
on the setting of the IED it trips immediately or after a given number of turns.
Furthermore other criteria and exceptions to the listed ones are possible.
There are two different power swing functions in modern numerical relays:
> Power swing blocking: The whole distance protection or only assigned zones are blocked when
a power swing occurs.
> Power swing tripping: The relay trips after detecting an unstable power swing.

OMICRON 2014

Page 7 of 22

The OMICRON Protection Testing Library (PTL)


There are different sources for the PTL: It can be installed from the DVD or CDs that are shipped with the
CMC test set or it can be downloaded from the OMICRON customer area (www.omicron.at). In both cases it
is free of charge.
Each PTL item consists of several files:
> An *.xrio-file: This is the XRIO converter. It can be used as test object for every test module.
After entering the actual relay settings, the converter calculates the characteristics for the main
protection functions automatically.
> An *.occ-file: This is the PTT (Protection Test Template) and consists of several test modules to
test the main functions of the corresponding protection device. A test for power swing blocking
or tripping is always missing. The XRIO converter is already included as test object. Using the
PTT is the fastest way of using the PTL as only the relay settings and little other information
have to be entered in the test object.
> One or two *.pdf-files: These are the manuals for the PTL item. They contain important
information on how to use these files.

4.1

The Structure of the XRIO Converter


Each PTL XRIO converter is divided in five sections:
> Relay Parameter Section: This is a copy of the relay settings software. The actual settings of
the device have to be entered her either manually or with the help of an import filter (see chapter
0). Also the settings for the power swing detection are included, even if this function is not
supported by the PTT. They can be used to build a customized test for this function.
> Additional Information: This block contains few parameters which are needed to test the
device but are not part of the relay settings.
> RIOplus: This part is used for calculations to convert the relay specific parameters to values
valid for the RIO block and OMICRON Test Universe test modules. It is only visible if the
advanced view of the XRIO editor is active.
> Template Controller: This block is needed for the PTT. Only visible in advanced view.
> RIO: This block contains the resulting characteristics for most of the protection functions.
Nothing must be changed here, as the formulas for the automatic calculation would be
destroyed. In case of a distance protection the RIO function Distance contains the zones. They
will be used for testing the power swing detection.

4.2

Using the Import Filter


With the help of one of the OMICRON import filters the manual entry of settings may be omitted. Different
import filter for different manufacturers are available. With the import filter and the specific relay parameter
software export file, it is possible to import the relay settings automatically into the XRIO converter. Even if
the PTTs are normally not supporting power swing detection, the relay import filter will also work for these
settings.

OMICRON 2014

Page 8 of 22

Adding a NetSim Module for Power Swing Blocking


In the following the PTT for AREVA P441, P442 and P444 is used as an example. After installing this PTL
item the PTT is opened and the settings of the relay are entered in the converter.
For testing the power swing blocking function a NetSim module is inserted after the last distance protection
test, which is the SOTF (switch on to fault) test. At first the correct Test Case at the menu Parameters must
be selected (see Figure 2). There are three different power swing cases:
> Synchronous: A stable power swing is simulated. This one is selected here.
> Asynchronous, Multiple Turns: An unstable power swing is simulated with multiple pole slips.
> Asynchronous, With Fault: An unstable power swing is simulated with multiple pole slips.
Additionally a fault occurs at a predefined time.
The impedance view (Figure 3) shows, that the module is automatically using the impedance characteristic
data of the converter. Also the three trajectories of the phase to phase impedances are drawn. With the
default test settings entered in the test view (Figure 4) tabs the impedances will never reach the trip zones
and thus no power swing blocking can be tested. Therefore the according settings have to be adapted first.
Some further understanding of the data of the actual network and the physics behind the power swing is
needed.

Figure 2: Selection of the Test Case

OMICRON 2014

Page 9 of 22

Figure 3: Impedance view

Most of the parameters which have to be entered in the Test View do not correspond to the settings of the
protection function. Instead these are data about the network the IED is used on. By means of these data
the module will simulate the transient signals which occur during a power swing on this network. Not the
settings of the relay are tested, but its behavior under realistic conditions. Unfortunately some of the needed
network data are often not available in practice. Furthermore most of the networks have a variety of
switching states. This leads to many different combinations of test settings that have to be tested. But with
some considerations a good test case can be found. If there is no claim laid to test with real network data,
there is still the possibility to test the protection function with the standard values.
So let's go through the test views tabs and see, which effect on the test the individual settings have.
Fault
In this tab a Prefault and a Postfault time can be set. 100 ms are enough for both. The next two settings are
much more important for the test:
The Slip angle specifies the maximum asynchronicity. 180 are the theoretical limits for a stable power
swing. If the angle became even more, the machine would fall out of step, as its maximum torque was
exceeded. Less slip angle means less power swing and results in higher impedances. By entering the
maximum of -180 it is achieved that the relay measures impedances within the tripping zones. The negative
limit is chosen as this will create a power swing coming from the right what looks like a big load to the IED.
The protection device will thus be tested whether it is still working fine in such a difficult situation.

OMICRON 2014

Page 10 of 22

Figure 4: Test View with entered Fault settings

The Slip time defines the duration of the power swing. If this time is too short the trajectory might move to
fast and leave the tripping zones before the distance protection tripped. 500ms are a good value but after all
settings were entered it must be checked, that the trajectory stays within a tripping zone for a long enough
time.
Line
Here the LinkToXRIO function is used to define the lines parameters (see Figure 5). For the selected mode
Z and k the corresponding values are stored in the RIO block of the converter (see Figure 6). As they are
secondary values, this option must be selected in the View menu before linking otherwise they are
interpreted as primary values. The value for the grounding factor must be checked, as some PTL converters
use a grounding factor of zero and recalculate all zones to loop impedances. In that case the link must be
done to the corresponding parameter in the Relay Parameter Section. Changing the Mode might be needed.

Figure 5: Line settings

OMICRON 2014

Page 11 of 22

Figure 6: Linking the line settings

Sources
These data are characterizing the network. A user defined block called "System Data" is added to the XRIO
converter for some calculations (see Figure 8).
The Voltage and Frequency in this tab (Figure 7) can be linked to the nominal values in the RIO Device
block.
Delta V and Delta phi are both zero for the moment. Chapter 7 explains how these values can be used to
move the trajectory of the impedances.
For the impedance magnitudes and angles a user defined XRIO block shall be used. This block must be
added to the XRIO converter like shown in Figure 8 and is used to calculate the source impedances
, from the short circuit power , of the two connected sources. To calculate the parameters
Z1 source 1 and 2 equation (1) is implemented as a formula in XRIO.

, =

.,
,

,
,

(1)

In this equation , is the primary nominal line to line voltage. The four variables above and below the
right fraction line are the primary and secondary values of the installed current transformers or voltage
transformers. They are needed to convert the impedance value to a secondary value.
The results can be linked to the NetSim settings Zmag for source 1 and source 2. The angles can be
entered either directly in NetSim or as seen in Figure 7 and Figure 8 also linked to XRIO. In the converter
the angle is calculated from an R/X ratio of 10%, which is an approximation that can be made if the exact
values are not known. For this example 5000 MVA are used for both sources.
The grounding factor magnitudes and angles can normally be chosen as one and zero, if the exact values
are unknown.

OMICRON 2014

Page 12 of 22

Figure 7: The sources definition

Figure 8: The user defined block System Data in XRIO

Outputs
The primary and secondary values for the current transformers and voltage transformers can be linked to the
corresponding values in the RIO Device block (see Figure 9). This has only to be done for the location (A or
B) at which the relay is installed.

Figure 9: The output configuration

OMICRON 2014

Page 13 of 22

After all settings have been entered the impedance view shows the resulting power swing (see Figure 10).
As a next step, the trajectories are proved to remain in a tripping zone long enough to evoke a trip. As the
trajectories move into Z1 (TZ1 = 0 s) this zone will probably cause the trip. Depending on the movement
speed theoretically every other zone could trip first. To test the power swing blocking function at least one
zone must be found that would surely trip, if the function did not work probably. Therefore the cursors are
moved on the time axis to find the points where the trajectories enter and leave the zone. It is even more
exact not to take the borders of the zone but to use the tolerance lines. Now the time deviation can be read,
which is about 110 ms what is enough for the relay to trip. The proper operation of the power swing blocking
function can be tested with this power swing. If the time was too short the Slip Time (Fault settings) can be
increased.

Figure 10: Measuring the time the trajectory of the resulting power swing is within zone 1

After configuring the trip signal in the local hardware configuration three measurements for the phase
selective trip times can be defined. These time measurements start with the beginning of the power swing
and end with the trip signal for phase A, B or C. When testing the power swing blocking function, no trip is
expected at all, that's why no nominal values are entered. Therefore the assessment must be done
manually. The test was OK if no trip occurred. The Measurement View after a successful test is shown in
Figure 11.

Figure 11: Measurement View

OMICRON 2014

Page 14 of 22

Adding a NetSim Module for Power Swing Tripping


To test the power swing tripping function of the relay another NetSim module must be added, where
Power Swing / Asynchronous / Multiple Turns is selected as test case. The settings are very similar to those
from the power swing blocking test:
Power Swing
A Slip frequency (see Figure 12) of 1 Hz causes a slow enough movement through the impedance plane, to
possible cause a trip. The duration of each turn will be is 1 s and the trajectory will again move from right to
left through the impedance plane.
As the example relay is configured to block during the first turn and trip if a second one occurs, the
Number of turns should at least be two.

Figure 12: The Power Swing settings

Line, Sources and Outputs


These settings are exactly the same as for the power swing blocking test and can be seen in Figure 5,
Figure 7 and Figure 9.
The resulting impedance trajectory is shown in Figure 13. The time within zone 1 can be determined as
about 110 ms, what is long enough.

OMICRON 2014

Page 15 of 22

Figure 13: The resulting out of step power swing

Again measurements for the trip times are defined. Unlike during the power swing blocking test trips are now
expected in all three phases. Defining a nominal time is not possible, as it depends on the moment the relay
recognizes, that the power swing is an unstable one, which in turn depends on the algorithm of the IED. This
task is something completely different to measuring the trip time of a zone. The assessment again has to be
done manually. Figure 14 shows the result of this measurement: A trip time above 1 s signifies that the relay
tripped as supposed during the second turn. This can be verified with help of the signal view. Figure 15
clearly shows that all three trip signals occur during the second power swing. This is exactly how the IED
was meant to react. Thus the power swing tripping function could successfully be tested that way.

Figure 14: Measurement for the trip time

OMICRON 2014

Page 16 of 22

Figure 15: Signal view of an unstable power swing

Tips for Defining a Good Test Case


A good test case for a stable power swing is one with the turning point of the trajectory inside of zone 1. This
will ensure that the relay will trip if the power swing blocking function did not work probably.
If the real network data (i.e. the source impedances) are unknown, default values have to be used or
assumptions must be done.
If the resulting turning point is outside of all tripping zones there is a possibility to move it within the
impedance plane: By changing the value for Delta V (see Figure 7) the transfer of reactive power on the line
can be modeled. With Delta phi the active power transfer can be changed. This results in a movement of the
turning point like shown in Figure 16. A change of reactive power results in a movement in direction of the
line angle, a change of active power in a movement in 90 turned to it.
These two parameters can now be used to move the turning point from outside of the tripping characteristic
to the inside. Of course only realistic values should be used, that correspond to a power transfer that can
happen in reality. Nevertheless this function can still be tested by using unrealistic test values that do not
represent the connected network.

OMICRON 2014

Page 17 of 22

X
line impedance
-Delta V
-Delta phi
+Delta phi
+Delta V

line angle
R
Figure 16: Movement of the turning point depending on the power transport

Testing Power Swing Detection of ABB REL670 and Siemens 7SA631


Up to this point this application note describes how to test the power swing blocking and tripping of the
AREVA P442 relay. This chapter is therefore devoted to using the existing OMICRON NetSim modules to
test the same protection function in other relay types. This will be done with very few changes as no
parameter test but a system test was performed. Even if the line parameters and zone reaches will be the
same for these examples the distance characteristics will differ from relay to relay.

8.1

Testing Power Swing Blocking of ABB REL670


In the example settings of this IED only power swing blocking is included. A test for power swing tripping is
not needed.
The first step is to prepare the XRIO converter. As some settings of the NetSim module are linked to the
System Data block, this block must be copied to the REL670 converter. Therefore the Organize function
(XRIO editor advanced view) is used: The P442 converter is imported in the right window. Then the
System Data block is marked and moved to the appropriate place in the REL670 converter.
Now the NetSim module for power swing blocking is copied to the REL670 PTT. It will automatically use the
already imported System Data block of the converter. Depending on the wiring the local hardware
configuration might have to be adapted. Also the measurements are changed as only one general trip signal
exists in this example. As the parameters for the line are different to those in the P442 converter they have
to be adapted as seen in Figure 17. In the REL670 settings no grounding factor k is defined. That's why a
different Mode is chosen and the values are now linked to the R and X values of the positive and negative
sequence parameters of the line. These values are found in the settings for the fault locator. Please note,
that they are primary values and therefore the module must be configured to view primary values while
linking.

OMICRON 2014

Page 18 of 22

Figure 17: Defining the line for testing ABB REL670

The resulting impedance trajectory is shown in Figure 18. After checking its residence time in zone 1 the
module is ready for testing.

Figure 18: Power swing blocking test for ABB REL670

8.2

Testing Power Swing Blocking and Tripping of Siemens 7SA631


In the example settings for this relay power swing blocking and tripping are activated. It is configured to have
phase selective trip signals. Therefore both NetSim modules from the Areva P442 test can be copied to the
Siemens 7SA631 PTT. But before that the System Data block must be added to the converter like in the
previous chapter. The modules will now automatically use these values and also the distance characteristic
of the RIO block. Again the links for the line settings must be adapted to the new settings: Like in Figure 19 a

OMICRON 2014

Page 19 of 22

different mode must be selected. The R and X values can be taken from the RIOplus block under
ProtectedObject. The two ratios RE/R and XE/X are linked to the RIO distance function.
For testing power swing tripping the number of turns is changed, as the IED is meant to trip during the first
pole slip. Figure 20 shows the resulting trajectory. After checking its residence time within zone 1 the test
can be started.

Figure 19: Line settings for Siemens 7SA631

Figure 20: Testing of power swing tripping of Siemens 7SA631

OMICRON 2014

Page 20 of 22

List of Literature
[1] Michael Albert, Eugenio Carvalheira, Oliver Janke: PTL: A solid basis for building customized line
protection test standards, OMICRON IPTS 2009 (www.omicron.at)
[2] Dr. Peter Meinhardt, OMICRON electronics GmbH: Testing approaches for power swing blocking
function, OMICRON IPTS 2009 (www.omicron.at)
[3] Dr. Fred Steinhauser, OMICRON electronics GmbH: Testing of the Power Swing Blocking in
Distance Relays
[4] Dr. Yuchen Lu, Dr. Juergen Holbach, Laurie Martuscello, P.E., Edward Krizauskas, P.E.: Tests of
Distance Relay Performance on Stable and Unstable Power Swings Using Simulated Data of the
August 14th 2003 System Disturbance
[5] Jrg Blumschein, Matthias Kereit, Yilmaz Yelgin, SIEMENS: Erhhung der Netzstabilitt durch
zuverlssige Pendelerkennung, Tagungsbeitrag 4.1 OMICRON Anwendertagung 2009
(www.omicron.at)
[6] MiCOM P441/P442/P444 Numerical Distance Protection, Technical Manual
[7] Technical reference manual Line distance protection IED REL 670
[8] SIPROTEC DISTANZSCHUTZ 7SA6 MANUAL

OMICRON 2014

Page 21 of 22

Support
When you are working with our products we want to provide you with the greatest possible
benefits. If you need any support, we are here to assist you.

24/7 Technical Support Get Support


www.omicron.at/support
www.omicronusa.com/support
At our technical support hotline, you can reach well-educated technicians for all of your
questions. Around the clock competent and free of charge.
Make use of our 24/7 international technical support hotline:
Europe / Middle East / Africa
Americas
Asia-Pacific

+43 59495 4444


+1 713 830-4660
+852 3767 5500

+1 800-OMICRON

Additionally, on our website you can find our Service Center or Sales Partner closest
to you.

Customer Area Stay Informed


www.omicron.at/customer
www.omicronusa.com/customer
The Customer Area on our website is an international knowledge exchange platform.
Download the latest software updates for all our products and share your own experiences
in our user forum.
Browse through the knowledge library and find application notes, conference papers,
articles about daily working experiences, user manuals and much more.

OMICRON Academy Learn More


www.omicron.at/academy
www.omicronusa.com/academy
Learn more about your product in one of the training courses offered by the OMICRON
Academy.

S-ar putea să vă placă și