Sunteți pe pagina 1din 12

Mt.

Pleasant
Library
3160 16th Street, NW
Washington, DC 20010

Property Line

DRAWING NOTES: #

1. REMOVE ALL EXISTING PLUMBING FIXTURES, FAUCETS, SUPPORTS AND APPURTENANCES IN THIS
EXISTING TOILET ROOM.
2. REMOVE EXISTING DOMESTIC WATER SERVICE MAINS AS INDICATED.
3. REMOVE EXISTING SANITARY COMPLETELY BACK TO BUILDING SANITARY MAIN AT LOCATION 901 G Street, NW
INDICATED. Washington, DC 20001
4. REMOVE ALL EXISTING VENT PIPING TO PENETRATION THROUGH ROOF.
5. REMOVE ALL EXISTING GAS SERVICE PIPING BACK TO METER AS INDICATED. THE CONTRACTOR SHALL Architect
COORDINATE DEMOLITION OF EXISTING GAS SERVICE WITH GAS COMPANY.
6. REMOVE DISCONNECT AND REMOVE THE EXISTING GAS FIRED WATER HEATER AND ASSOCIATED WATER
AND GAS SERVICE PIPING AND VALVES.
7. EXISTING STORM DOWNSPOUT TO BE REMOVED.
8. EXISTING STORM RISER TO REMAIN.
8
1010 wisconsin avenue, nw
suite 405
washington, dc 20007
1 5
T 202.466.6116

M
F 202.466.6235

G
(E)
STORAGE
7
MEN'S 3 East 28th Street, 6th Floor
TOILET New York, NY 10016
T 212.696.0414

(E)
WOMEN'S (E) (E) Structural Engineer
TOILET

G
6 ReStl Designers, Inc.

G
2 1001 Connecticut Ave, NW, Suite 320
8 7

(E)
SECURITY Washington, DC 20036

(E)
1 T 202.452.1103
2
CLOS. F 202.452.1133

(E)
PLUMBING
JAN.

(E)
MEP Engineer
CLOS. 8

(E)

(E)
G
2 STORAGE &

(E)
BOILER ROOM

(E)
GROUNDSKEEPING

(E)
2

(E)
(E)
7061 Deepage Drive
3

(E)
STORAGE Columbia, MD 21045
SHELVING
STORAGE T 410.381.7100

(E)
ELEVATOR F 410.381.7110
SHAFT
PROJECTION Civil Engineer
2
ROOM AMT
1

(E)
STORAGE MACHINE 12750 Twinbrook Parkway
ROOM Rockville, MD 20852

ELEVATOR
T 301.881.2545
BASEMENT F 301.881.0814
LOBBY

(E)
LOBBY

(E)
Landscape Architect

(E)
2410 17th Street, NW, Suite 201
MEETING ROOM
Washington, DC 20009

T 202.588.5454
TO ACCESSIBLE F 202.588.5449
RAMP 8

(E)
(E)
REV DT ISSUED
STORAGE 5-29-09 SCHEMATIC DESIGN

MECHANICAL 7-17-09 DESIGN DEVELOPMENT


STORAGE 3
12-4-09 ISSUED FOR PERMIT

(E)
2
M

1 DEMOLITION TERRACE FLOOR PLAN- PLUMBING


DP0.01 SCALE: 1/8" = 1'-0"
I CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
DISTRICT OF COLUMBIA

Project No. 08002.10

Demolition
Terrace Floor Plan
- Plumbing

1' 0 4' 8' 12' 16'


N DP0.01
Printed: 11/11/08
© core group, pc 2008
GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179
Mt. Pleasant
Library
3160 16th Street, NW
Washington, DC 20010

Property Line

DRAWING NOTES: #
1. APPROXIMATE LOCATION OF EXISTING STORM DOWNSPOUTS.

901 G Street, NW
Washington, DC 20001

Architect

1010 wisconsin avenue, nw


suite 405
washington, dc 20007
T 202.466.6116
F 202.466.6235

3 East 28th Street, 6th Floor


New York, NY 10016
T 212.696.0414
Structural Engineer
ReStl Designers, Inc.
1 1001 Connecticut Ave, NW, Suite 320
Washington, DC 20036
T 202.452.1103
F 202.452.1133
MEP Engineer
1

7061 Deepage Drive


Columbia, MD 21045
T 410.381.7100
F 410.381.7110
Civil Engineer
AMT
12750 Twinbrook Parkway
Rockville, MD 20852
T 301.881.2545
F 301.881.0814
Landscape Architect

2410 17th Street, NW, Suite 201


Washington, DC 20009

T 202.588.5454
F 202.588.5449

1
REV DT ISSUED
5-29-09 SCHEMATIC DESIGN

7-17-09 DESIGN DEVELOPMENT


12-4-09 ISSUED FOR PERMIT

1-13-10 BID SET

1 1

1 DEMOLITION ROOF PLAN- PLUMBING


DP0.04 SCALE: 1/8" = 1'-0"
I CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
DISTRICT OF COLUMBIA

Project No. 08002.10

Demolition
Roof
- Plumbing

1' 0 4' 8' 12' 16'


N DP0.04
Printed: 11/11/08
© core group, pc 2008
GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179
GENERAL NOTES FIRE PROTECTION NOTES PLUMBING LEGEND Mt. Pleasant

07/20/09 - DESIGN DEVELOPMENT


PLUMBING ABBREVIATIONS
Library

05/29/09 - SCHEMATIC DESIGN

12/04/09 - ISSUED FOR PERMIT


SYMBOL ABRV. DESCRIPTION
1. ALL SPECIFICATIONS AND DRAWINGS, I.E. ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE 1. PROVIDE A COMPLETE FULLY AUTOMATIC SPRINKLER/STANDPIPE SYSTEM, HYDRAULICALLY
PROTECTION, AND ELECTRICAL, ARE COMPLIMENTARY AND MUST BE USED IN COMBINATION TO OBTAIN CALCULATED IN ACCORDANCE WITH NFPA AND ALL LOCAL CODES AND REGULATIONS OF THE AUTHORITY ABV ABOVE SAN., SANITARY PIPING
COMPLETE CONSTRUCTION INFORMATION. HAVING JURISDICTION. SPRINKLER PIPING LAYOUT AND SPRINKLER LOCATIONS SHOWN ON DRAWING FOR W. 3160 16th Street, NW
ADA AMERICANS W/ DISABLITIES ACT COMPLIANCE
INFORMATIONAL PURPOSES ONLY. ST STORM WATER PIPING Washington, DC 20010
PLUMBING SHEET INDEX 2. ANY INFORMATION CONFLICTS WITHIN THE SPECIFICATIONS AND/OR DRAWINGS SHALL BE BROUGHT TO AFF ABOVE FINISHED FLOOR ST
THE ARCHITECT'S ATTENTION. THE CONTRACTOR SHALL NOT PROCEED WITH ANY WORK UNTIL ALL 2. ALL FIRE PROTECTION EQUIPMENT, I.E. PIPING, VALVES, FITTINGS, ACCESSORIES, ETC., SHALL BE RATED AHJ AUTHORITY HAVING JURISDICTION ST/PD DUPLEX SUMP PUMP DISCHARGE
CONFLICTS ARE RESOLVED AND THE CLARIFYING INFORMATION IS ISSUED. FOR A MAXIMUM WORKING PRESSURE OF 175 PSI. ST/PD
DRAWING # SHEET TITLE APPROX APPROXIMATE
3. ALL SANITARY AND STORM SEWER PIPING LESS THAN 3" SHALL BE INSTALLED WITH A 1/4" PER FT. 3. ALL SPRINKLER PIPING SHALL BE INSTALLED SO THAT ALL PORTIONS CAN BE DRAINED BACK THROUGH ARCH ARCHITECT, ARCHITECTURAL V VENT PIPING
P0.01 PLUMBING DATA SHEET GRADE AND NOT LESS THAN 1/8" PER FT. GRADE FOR PIPING 3" AND LARGER UNLESS NOTED OR INDICATED A DRAIN VALVE.
OTHERWISE. PROVIDE CLEANOUTS ON ALL SEWER PIPING (HORIZONTAL AND VERTICAL) WHERE INDICATED BLDG BUILDING
P0.02 PLUMBING SCHEDULES PD PUMP DISCHARGE
AND/OR REQUIRED BY CODE. 4. ALL FIRE EQUIPMENT SHALL CONFORM TO LOCAL STANDARDS. PD
DP0.01 DEMOLITION TERRACE FLOOR PLAN- PLUMBING BLW BELOW
901 G Street, NW
DP0.02 DEMOLITION FIRST FLOOR PLAN- PLUMBING 4. COORDINATE ALL PIPING TO BE INSTALLED WITH ALL OTHER TRADES, I.E. MECHANICAL, FIRE 5. SPRINKLER SYSTEM ZONES SHALL BE COORDINATED WITH FIRE ALARM ZONES. BTU BRITISH THERMAL UNIT CW COLD WATER PIPING Washington, DC 20001
DP0.03 DEMOLITION SECOND FLOOR PLAN- PLUMBING PROTECTION, AND ELECTRICAL TO ENSURE THAT ALL PIPING SYSTEMS ARE INSTALLED ABOVE FINISHED BTUH BTU PER HOUR
DP0.04 DEMOLITION ROOF PLAN- PLUMBING CEILING OR IN A CONCEALED SPACE. ALL CEILING HEIGHTS INDICATED ON ARCHITECTURAL AND/OR 6. ALL CONTROL VALVES AND FLOW ALARM SWITCHES LOCATED ABOVE FINISHED CEILING SHALL BE Architect
CFH CUBIC FEET/HOUR NP NP NON POTABLE WATER
P1.01 TERRACE FLOOR PLAN- PLUMBING INTERIOR DESIGN DRAWINGS AS WELL AS MINIMUM CLEARANCES REQUIRED BY LOCAL CODES SHALL BE ACCESSIBLE AND HAVE NOTIFICATION MARKING TAG FOR THE INSPECTOR.
P1.02 FIRST FLOOR PLAN- PLUMBING MAINTAINED THROUGHOUT THE BUILDING. CI CAST IRON
7. ALL ELECTRICAL EQUIPMENT AND TELEPHONE ROOMS SHALL BE SPRINKLERED. HW HOT WATER PIPING
P1.03 SECOND FLOOR PLAN- PLUMBING CLG CEILING
5. ALL CUTTING, DRILLING, AND PATCHING OF WALLS, FLOORS, AND/OR STRUCTURAL MEMBERS FOR THE
P1.04 ROOF PLAN- PLUMBING FIRE PIPING PROTECTION
INSTALLATION OF PLUMBING SYSTEMS SHALL BE PROVIDED. STRUCTURAL COMPONENTS SHALL NOT BE 8. ELEVATOR MACHINE ROOM AND SHAFT: SPRINKLER CONTRACTOR SHALL PROVIDE HIGH TEMPERATURE COL COLUMN F
P2.01 PLUMBING RISER DIAGRAMS CUT, DRILLED, OR MODIFIED IN ANY WAY WITHOUT THE STRUCTURAL ENGINEER'S REVIEW AND PRIOR HEADS IN CONJUNCTION WITH HEAT/SMOKE DETECTION SYSTEM. CONTRACTOR SHALL COORDINATE F
P3.01 PLUMBING DETAILS APPROVAL. REQUIREMENTS WITH NFPA AND AUTHORITIES HAVING JURISDICTION, SUBJECT TO APPROVAL AND CONC CONCRETE
SP SPRINKLER PIPING 1010 wisconsin avenue, nw
SP1.01 TERRACE FLOOR PLAN- PROPOSED SPRINKLER LAYOUT ACCEPTANCE. CONT CONTINUATION SP suite 405
SP1.02 FIRST FLOOR PLAN- PROPOSED SPRINKLER LAYOUT 6. PIPING OR EQUIPMENT SHALL NOT BE SUPPORTED FROM STRUCTURAL MEMBER WITHOUT PRIOR REVIEW washington, dc 20007
AND APPROVAL FROM THE STRUCTURAL ENGINEER. 9. ALL FIRE EQUIPMENT THREADS SHALL CONFORM TO LOCAL STANDARDS. CWFU COLD WATER FIXTURE UNIT (E) EXISTING PIPING
SP1.03 SECOND FLOOR PLAN- PROPOSED SPRINKLER LAYOUT (E) T 202.466.6116
DEG DEGREE F 202.466.6235
7. ALL BACKFLOW PREVENTER ASSEMBLIES SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION. PIPE 10. TAMPER SWITCHES SHALL BE PROVIDED ON ALL FIRE PROTECTION SYSTEM CONTROL VALVES.
RELIEF OUTLET, IF APPLICABLE, SHALL DISCHARGE TO NEAREST FLOOR DRAIN. DO NOT INSTALL ABOVE ANNUNCIATE TAMPER SWITCHES IN ACCORDANCE WITH LOCAL CODES AND REGULATIONS. DFU DRAINAGE FIXTURE UNIT DEMO EXISTING PIPING TO BE REMOVED
FINISHED CEILING UNLESS NOTED OR INDICATED OTHERWISE. DIA DIAMETER
11. FLOW ALARM SWITCHES SHALL BE PROVIDED WHERE INDICATED ON PLANS AND/OR REQUIRED BY PIPE UP
8. PROVIDE FLOAT TYPE BACKWATER VALVE (SIZED FOR ANTICIPATED FLOW RATE) IN ALL OPEN SITE LOCAL CODES. ANNUNCIATE FLOW SWITCHES IN ACCORDANCE WITH LOCAL CODES AND REGULATIONS. DN DOWN
DRAINS AND FLOOR RECEPTORS RECEIVING A/C CONDENSATE, AND/OR CLEAR WATER WASTE SUCH AS DWG DRAWING PIPE DOWN 3 East 28th Street, 6th Floor
SPRINKLER FLOW TESTING. New York, NY 10016
EL ELEVATION
9. ALL PIPING SYSTEMS, VALVES, AND EQUIPMENT SHALL BE PROPERLY IDENTIFIED.
DEMOLITION NOTES: PIPE TEE DOWN T 212.696.0414
ELEC ELECTRICAL
Structural Engineer
10. ALL PLUMBING SHALL CONFORM TO ALL REQUIREMENTS OF THE LOCAL ENERGY CONSERVATION AND 1. FIELD VERIFY THE EXACT SIZES AND LOCATIONS OF ALL EXISTING PIPING PRIOR TO DEMOLITION OF ANY EXISTING ELEV ELEVATOR FCO CLEAN OUT, FLOOR
WORK. THE DEMOLITION WORK SHALL BE COORDINATED WITH THE NEW WORK OF ALL DIVISIONS TO ASSURE PROPER ReStl Designers, Inc.
PLUMBING CODES OF THE AUTHORITY HAVING JURISDICTION. F; ºF DEGREES FARENHEIT 1001 Connecticut Ave, NW, Suite 320
LIMITS OF DEMOLITION.
CO CLEAN OUT, EXPOSED Washington, DC 20036
11. HOT, COLD, AND RECIRCULATION WATER SUPPLY MAINS AND BRANCHES SHALL BE INSULATED IN FDC FIRE DEPARTMENT SIAMESE CONNECTION
2. REMOVE ALL EXISTING EQUIPMENT AND ASSOCIATED PIPING, WHETHER SPECIFICALLY INDICATED OR NOT, THAT IS T 202.452.1103
ACCORDANCE WITH THE LOCAL ENERGY CODE. NO LONGER REQUIRED. FFE FINISH FLOOR ELEVATION CAPPED PIPE F 202.452.1133
12. ALL PIPING, VALVES, AND ACCESSORIES SERVING EQUIPMENT SHALL BE INSTALLED TO ALLOW FIN FINISH MEP Engineer
3. REMOVE AND CAP EXISTING BRANCH PIPING, NO LONGER REQUIRED TO REMAIN AS PART OF AN ACTIVE SYSTEM, AT
SERVICING AND/OR REMOVAL WITHOUT DISCONNECTING ALL PIPING AND ACCESSORIES. THE APPROPRIATE MAIN. FLR FLOOR PIPE UNION

13. ALL VALVES SHALL HAVE THEIR NORMAL (IN OPERATION) POSITION IDENTIFIED, SUCH AS "NORMALLY FT FOOT OR FEET
4. ANY PIPING AND DUCTWORK WHICH MUST REMAIN AS PART OF AN ACTIVE SYSTEM AND IS IN CONFLICT WITH THE THERMOMETER
OPEN" OR "NORMALLY CLOSED." NEW LAYOUT SHALL BE RELOCATED AT NO ADDITIONAL COST OVER THE CONTRACT AMOUNT. GAL GALLON 7061 Deepage Drive
Columbia, MD 21045
14. EXPANSION LOOPS AND ANCHORS SHALL BE PROVIDED ON ALL PIPING SYSTEMS WHICH CROSS GPM GALLONS PER MINUTE PG PRESSURE GAUGE
5. EXISTING FIXTURES, EQUIPMENT AND PIPING REMOVED DURING CONSTRUCTION SHALL REMAIN THE PROPERTY OF
BUILDING EXPANSION JOINTS AND ALL HORIZONTAL PIPING LENGTHS EXCEEDING 100 FT. OR EACH HD HEAD T 410.381.7100
THE OWNER AND SHALL BE STORED, REMOVED FROM THE JOB SITE, OR DISPOSED OF AS DIRECTED BY THE OWNER'S F 410.381.7110
PORTION THEREOF. REPRESENTATIVE. BFP BACK FLOW PREVENTER
HORIZ HORIZONTAL
Civil Engineer
15. ALL NECESSARY EQUIPMENT SHALL BE PROVIDED ON ALL PIPING, UNIONS, VALVES, VACUUM 6. OPENINGS REMAINING IN WALLS/FLOORS AS A RESULT OF DEMOLITION SHALL BE SEALED WITH AN AIRTIGHT HP HORSEPOWER AMT
BREAKERS, STRAINERS, ETC. AS REQUIRED TO CONNECT EQUIPMENT AT LOCATION SHOWN, AND TO MAKE RPZ REDUCED PRESSURE ZONE ASSEMBLY
SHEET METAL CAP, UNLESS OTHERWISE NOTED ON THE DRAWINGS. HTR HEATER BACK FLOW PREVENTER 12750 Twinbrook Parkway
FULLY OPERABLE IN ACCORDANCE WITH ALL LOCAL CODES AND REGULATIONS. Rockville, MD 20852
7. WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, EXTREME CARE SHALL BE TAKEN TO PREVENT DAMAGE DURING HWFU HOT WATER FIXTURE UNIT BALL VALVE OR SHUTOFF VALVE
16. DRAINS AND CLEANOUTS SHALL BE INSTALLED AS SPECIFIED AND IN LOCATIONS SHOWN ON T 301.881.2545
THE REMOVAL AND REINSTALLATION. WHERE DAMAGE OCCURS,THE EQUIPMENT SHALL BE REPLACED OR REPAIRED (E) EXISTING
DRAWINGS. REFER TO THE DRAIN SCHEDULE, IF APPLICABLE. F 301.881.0814
TO THE SATISFACTION OF THE ARCHITECT, AND OWNERS REPRESENTATIVE AT NO ADDITIONAL COST OVER THE P&TRV PRESSURE AND/OR TEMPERATURE RELIEF VALVE
CONTRACT AMOUNT. IN. INCHES Landscape Architect
17. THESE DRAWINGS ARE SCHEMATIC AND ARE INTENDED TO CONVEY A FUNCTIONAL PLUMBING SYSTEM
AND TO DEPICT THE GENERAL LOCATION OF THE PLUMBING COMPONENTS. I.E. INVERT ELEVATION MIXING VALVE
8. CONTRACTOR SHALL PROVIDE ADD-ALTERNATIVE PRICE TO REMOVE AND REPLACE EXISTING INTERIOR STORM RISER
WITH NEW CAST IRON NO-HUB RISERS. REFER TO DRAWINGS FOR EXTENT OF ADD-ALTERNATIVE DEMOLITION WORK. KW KILOWATT 2410 17th Street, NW, Suite 201
18. THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF PLUMBING WORK WITH THE WORK OF Washington, DC 20009
LBS POUNDS PRV PRESSURE REDUCING VALVE
OTHER TRADES. MINOR DEVIATIONS FROM THE PLANS MAY BE MADE TO AVOID MINOR CONFLICTS. WHEN T 202.588.5454
MAJOR CONFLICTS ARE APPARENT, THE CONTRACT OFFICER SHALL BE ADVISED IMMEDIATELY AND MANUF. MANUFACTURER F 202.588.5449
AFFECTED WORK SHALL NOT BE CONSIDERED UNTIL THE CONFLICT HAS BEEN RESOLVED. DRAWING SYMBOLS CV CHECK VALVE
MAX MAXIMUM
19. THE CONTRACTOR SHALL VERIFY ALL VOLTAGE AND POWER REQUIREMENTS FOR ALL EQUIPMENT AND DETAIL # MIN MINIMUM CHECK VALVE WITH AUTO DRIP VALVE
X REV DT ISSUED
COORDINATE WITH THE CONTRACT DRAWINGS PRIOR TO ISSUANCE OF SHOP DRAWINGS AND PURCHASE
X X MTD MOUNTED 5-29-09 SCHEMATIC DESIGN
OF EQUIPMENT.
N.C. NORMALLY CLOSED OS&Y OS&Y VALVE 7-17-09 DESIGN DEVELOPMENT
20. ALL SYSTEMS SHALL BE CLEAN OF FOREIGN MATERIAL AND ROUGH SPOTS PRIOR TO BEING PLACED SHEET ORIGIN PLAN DETAIL 12-4-09 ISSUED FOR PERMIT
N.O. NORMALLY OPEN
IN SERVICE AND BEFORE OPERATIONAL TESTS ARE PERFORMED.x (DIFFERENT FLOOR) T.S. OS&Y VALVE WITH TAMPER SWITCH
SHEET REFERENCE N/A NOT APPLICABLE
21. INSTALLATION OF ALL EQUIPMENT AND THEIR ACCESSORIES SHALL BE PER MANUFACTURER'S FIRE DEPARTMENT SIAMESE CONNECTION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
PUBLISHED RECOMMENDATIONS. (FREE STANDING)
DETAIL # NO.; # NUMBER
22. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE PLUMBING SYSTEM SO AS TO FIRE PUMP TEST HEADER
X NP NON POTABLE
ENSURE QUIET OPERATION. NO VIBRATION OF SOUND SHALL BE TRANSMITTED TO THE BUILDING
STRUCTURE. THE DECISION OF THE CONTRACT OFFICER AS TO QUIETNESS OF THE SYSTEM AND X-X PLBG PLUMBING FLOW SWITCH
EQUIPMENT SHALL BE FINAL. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO CORRECT OR REPLACE PRESS PRESSURE
ANY NOISY SYSTEMS OR EQUIPMENT AS REQUIRED. SHEET REFERENCE PLAN DETAIL
PSI(G) POUNDS PER SQUARE INCH (GAGE) OSD OPEN SITE DRAIN
(IF TYPICAL FLOOR)
23. PROVIDE ACCESS DOORS AND/OR PANELS NECESSARY TO SERVICE ALL EQUIPMENT AND PSIA POUNDS PER SQUARE INCH ABSOLUTE
ACCESSORIES THAT REQUIRE SERVICE AND/OR MAINTENANCE AND ARE LOCATED ABOVE INACCESSIBLE FD FLOOR DRAIN
CEILINGS OR WALLS. ACCESS DOOR SIZES SHALL PERMIT FULL ACCESSIBILITY TO EQUIPMENT AND/OR SECTION # PVC POLYVINYL CHLORIDE
ACCESSORIES, BUT NOT LESS 18" X 18". ACCESS DOORS SHALL MATCH THE WALL OR CEILING RATING AT QTY QUANTITY RD ROOF DRAIN
THE LOCATION WHERE THEY ARE PLACED. X SECTION CUT
X-X RECIRC RECIRCULATION
24. ALL PIPING SHALL BE INSTALLED TIGHT TO UNDERSIDE OF STRUCTURAL CONSTRUCTION UNLESS AD/GD/TD AREA DRAIN/GARAGE DRAIN/TERRACE DRAIN
REQ'D REQUIRED
OTHERWISE NOTED. SHEET REFERENCE
RPM REVOLUTION PER MINUTE SA SHOCK ABSORBER
25. THE CONTRACTOR IS RESPONSIBLE FOR ALL ROUGH-IN, FINAL CONNECTIONS, AND PROPER ELEVATION # SQ. FT. SQUARE FOOT/FEET
INSTALLATION OF FIXTURES INCLUDING ASSOCIATED PIPING. MOUNT FAUCETS, SUPPLY ANY TRAPS,
VALVES, FITTINGS, VACUUM BREAKERS, PRESSURE GAUGES, OR PRESSURE REGULATORS FOR A TYP TYPICAL WH WALL HYDRANT- FREEZE PROOF
2
COMPLETE INSTALLATION WHICH MEETS THE APPLICABLE CODES. X 4 3 ELEVATION SYMBOL
1 V VOLTAGE
X-X X-X FDHV FIRE DEPARTMENT HOSE VALVE
26. ALL WORK ON THIS PROJECT SHALL BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES, WSFU WATER SUPPLY FIXTURE UNIT
REGULATIONS, AND THE AUTHORITY HAVING JURISDICTION. SHEET REFERENCE BWV BACK WATER VALVE I CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
27. PROVIDE TRAP PRIMER VALVES FOR ALL DRAINS WHICH REQUIRE A SOURCE OF WATER SUPPLY TO DISTRICT OF COLUMBIA

MAINTAIN TRAP SEAL. PRIMER VALVES SHALL BE CONNECTED TO THE NEAREST COLD WATER LINE 1 REVISION DELTA RISER DESIGNATIONS VTR VENT THRU ROOF
SERVING A FIXTURE.
S SANITARY RISER DESIGNATION
28. ALL PRODUCTS LOCATED WITHIN PLENUM AREAS, INCLUDING BUT NOT LIMITED TO INSULATION AND # I.E. I.E. INVERT ELEVATION
ADHESIVE SYSTEMS, SHALL HAVE A COMPOSITE FIRE HAZARD RATING NOT TO EXCEED 25 FLAME SPREAD REVISION CLOUD 08002.10
Project No.
AND 50 SMOKE DEVELOPED AS DETERMINED BY THE APPLICABLE UL OR ASTM STANDARD. F FIRE RISER DESIGNATION GAS COCK
#

# DRAWING NOTES W CONNECT TO EXISTING


DOMESTIC WATER RISER DESIGNATION
#
EXTENT OF DEMOLITION
Plumbing
Data Sheet
T1 HARDWIRE POWER CONVERTER FOR FLUSH VALVES

T2 HARDWIRE POWER CONVERTER FOR FAUCETS P0.01


Printed: 11/11/08
B BATTERY BACKUP MODULE FOR FLUSH VALVES © core group, pc 2008
ASE JOB# 0811_179
GENERAL NOTES:
Mt. Pleasant
A. REFER TO DATA SHEET FOR PLUMBING SYMBOLS AND ABBREVIATIONS.
Library
B. REFER TO RISER DIAGRAMS FOR ADDITIONAL SIZES OF UTILITIES AND PIPING.
3160 16th Street, NW
eF C. FOR PLUMBING FIXTURES AND EQUIPMENT REFER TO SCHEDULES ON DATA SHEET.
Washington, DC 20010
1 2 2.3 3 3.9 4 5 5.7 6 DRAWING NOTES: #

1. ENTIRE ATTIC SHALL BE FULLY SPRINKLERED BY A DRY PIPE SPRINKLER SYSTEM IN


ACCORDANCE WITH NFPA AND LOCAL CODES.
2. 4" STORM WATER PIPING CONNECTED AT BOTTOM OF ARCHITECTURAL ROOF GUTTER,
REFER TO DETAIL 3 ON ARCHITECTURAL DRAWING A8.31 FOR DETAIL.
3. 1" NON POTABLE WATER TO MECHANICAL COOLING TOWER. REFER TO MECHANICAL
eE DRAWINGS FOR CONTINUATION. COMPLETELY HEAT TRACE NON POTABLE WATER
901 G Street, NW
LINE ON ROOF UP TO 2' BELOW ROOF STRUCTURE, REFER TO ELECTRICAL DRAWINGS
Washington, DC 20001
3" OFD-1 3" OFD-1 3" OFD-1 FOR ELECTRICAL REQUIREMENTS.
(570 SQ. FT.) (400 SQ. FT.) (225 SQ. FT.) Architect
3" RD-1 3" RD-1 3" RD-1 eD
(570 SQ. FT.) (400 SQ. FT.) (225 SQ. FT.)
G

eC
1010 wisconsin avenue, nw
suite 405
3" VTR eB washington, dc 20007
ARCHITECTURAL ROOF GUTTER T 202.466.6116
REFER TO ARCHITECTURAL DWGS F 202.466.6235
FOR MORE DETAIL
F
eA
EXISTING DOWNSPOUT
E SEE NOTE 13 DWG P1.01
3" OFD-1
(300 SQ. FT.) 3 East 28th Street, 6th Floor
3" RD-1 New York, NY 10016
D
(300 SQ. FT.) T 212.696.0414
1" (NP)
Structural Engineer
WATER- DN 2
C.5 ReStl Designers, Inc.
3" OFD-1 1001 Connecticut Ave, NW, Suite 320
(570 SQ. FT.) 3 Washington, DC 20036
C
3" RD-1 T 202.452.1103
(570 SQ. FT.) F 202.452.1133
B
2 3" VTR MEP Engineer

2
A.7 Skyligh
t 7061 Deepage Drive
Columbia, MD 21045
A
T 410.381.7100
F 410.381.7110
eF
Civil Engineer
EXISTING DOWNSPOUT AMT
SEE NOTE 13 DWG P1.01 12750 Twinbrook Parkway
EXISTING DOWNSPOUT Rockville, MD 20852
SEE NOTE 13 DWG P1.01
T 301.881.2545
F 301.881.0814
Landscape Architect

2410 17th Street, NW, Suite 201


Washington, DC 20009
eE
T 202.588.5454
F 202.588.5449

1 REV DT ISSUED
eD 5-29-09 SCHEMATIC DESIGN

7-17-09 DESIGN DEVELOPMENT


12-4-09 ISSUED FOR PERMIT

eE.5

eC
e10
EXISTING DOWNSPOUT
eB SEE NOTE 13 DWG P1.01

3" VTR
e9

eA

EXISTING DOWNSPOUT EXISTING DOWNSPOUT


SEE NOTE 13 DWG P1.01 SEE NOTE 13 DWG P1.01
e8

e7
I CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND THAT I AM A
eC.1 DULY LICENSED ARCHITECT UNDER THE LAWS OF
DISTRICT OF COLUMBIA

Project No. 08002.10

1 ROOF PLAN- PLUMBING Roof Plan


P1.04 SCALE: 1/8" = 1'-0" - Plumbing

1' 0 4' 8' 12' 16'


N P1.04
Printed: 11/11/08
© core group, pc 2008
GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179
O S&Y VALVE W/ TO BUILDING SPRINKLER SYSTEM.
GAUGE TAMPER SWITCH (TYP) SEE RISER AND PLANS FOR
FIRE SERVICE FROM SIAMESE CONNECTION
DOUBLE CHECK
DETECTOR ASSEMBLY
FULL SIZE BY-PASS UNION (TYPICAL) Mt. Pleasant
GATE VALVE
(TYPICAL)
TO FIRE PUMP TEST HEADERS,
PROVIDE AUTO BALL DRIP Library
CHECK VALVE
(TYPICAL) 3160 16th Street, NW
Washington, DC 20010
SUMP VENT (FOR CONTINUATION JOCKEY PUMP FIRE PUMP
REFER TO FLOOR PLAN) DISCHARGE CASE RELIEF CONTROLLER
GAUGE VALVE
PUMP DISCHARGE (TYP OF 2) FOR 5 STRAINER JOCKEY
CONTINUATION REFER TO FLOOR PLAN PUMP
CHECK VALVE FLOOR CONTROLLER
GATE VALVE 6
CHECK VALVE (TYPICAL)
STEEL PIT COVER 8 ECCENTRIC CONCENTRIC 901 G Street, NW
REDUCER REDUCER Washington, DC 20001
CONCRETE PAD
FINISHED FLOOR= 0.00' (TYPICAL) 12" HOUSEKEEPING PAD SUCTION GAUGE
Architect
4 ELECTRIC FIRE PUMP DETAIL
INLET NO SCALE
P3.01
DISCHARGE
4 9 10
PRESSURE GAUGE (0 TO 250 PSI)
FOR CONTINUATION GUIDE RAILS O.S.&Y VALVE W/TAMPER SWITCH 1010 wisconsin avenue, nw
SEE FLOOR PLAN I.E. -3.0' 3 CHECK VALVE suite 405
MERCURY FLOAT SWITCH washington, dc 20007
NOTES: FLOW SWITCH TO FLOOR T 202.466.6116
1. HERMETIC NATURAL GAS BOOSTER PUMP. SPRINKLER F 202.466.6235
PUMP (TYP. OF 2) 7 SYSTEM
2. PRESSURE GAUGE (DISCHARGE).
2

7'-0"
3. PLUG VALVE.
2nd PUMP -ON (-3.5') PRE-CAST FIBERGLAS 4. NATURAL GAS DISCHARGE.
SUMP BASIN 5. FLEXIBLE GAS CONNECTION.
1
6. BRASS BALL VALVE. DRAIN RISER SIGHT GLASS
HIGH WATER ALARM (-4.0')
7. PRESSURE GAUGE (INLET). INSPECTOR'S 3 East 28th Street, 6th Floor
8. 6mm BALL VALVE. New York, NY 10016
1st PUMP- ON (-4.5') TEST VALVE
9. NEMA-12 CONTROL PANEL.
10. NEMA-4 JUNCTION BOX. T 212.696.0414
Structural Engineer
ReStl Designers, Inc.
1st PUMP SHUT-OFF (-5.5')
8 NATURAL GAS BOOSTER SYSTEM DETAIL DRAIN VALVE 1001 Connecticut Ave, NW, Suite 320
NO SCALE Washington, DC 20036
P3.01 UNION T 202.452.1103
BOTTOM OF BASIN (-7.0') F 202.452.1133
MEP Engineer

4'-0"
3 SPRINKLER FLOOR CONTROL VALVE ASSEMBLY DETAIL
P3.01 NO SCALE
NOTE: ALL SENDING AND CONTROL TUBING SHALL BE COPPER OR STAINLESS STEEL ONLY.
COMBINATION PRESSURE REGULATING VALVE (PRV) SHUT-OFF VALVE (TYP) 7061 Deepage Drive
4" x 2-1/2" x 2-1/2" Columbia, MD 21045
10 DUPLEX SUMP AND PUMP DETAIL (SP-2) & CHECK VALVE BY PUMP MANUFACTURER (TYP) FREESTANDING
P3.01 NO SCALE FLOW SWITCH (TYP) FIRE DEPARTMENT T 410.381.7100
HYDRO-PNEUMATIC TANK CONNECTION F 410.381.7110
WITH PRESSURE GAUGE Civil Engineer
AMT
GRADE OR 4" FIRE PIPING TO 12750 Twinbrook Parkway
CHECK VALVE (TYP)
PAVING FREESTANDING FDC Rockville, MD 20852
PUMP PUMP
CONTRACTOR TO CONNECT 4" FIRE PIPING T 301.881.2545
CONTROL PANEL AT THIS POINT FROM BUILDING F 301.881.0814
Landscape Architect

SKID BASE
OIL MINDER 1 2410 17th Street, NW, Suite 201
ELECTRICAL 4" HOUSE KEEPING PAD Washington, DC 20009
CONTROL OUTLET NIPC SUCTION
P1.01
6 3 T 202.588.5454
F 202.588.5449
POWER SUPPLY PRESSURE GAUGE (TYP) 4" FIRE PIPING TO
ANTI-VIBRATION PAD (TYP) 4" FIRE PIPING TO
3/4" AUTO BALL DRIP FREESTANDING FDC
FOR SYSTEM DRAIN FREESTANDING FDC
9 OIL-MINDER POWER 7 DOMESTIC WATER BOOSTER PUMP PACKAGE DETAIL GUARDIAN MODEL MINIMUM 4' COVER REV DT ISSUED
CABLE, PROBE CABLE, NO SCALE 6432 5-29-09 SCHEMATIC DESIGN
12 DETECTOR CHECK METER DETAIL 4 AND HIGH LIQUID
P3.01
7-17-09 DESIGN DEVELOPMENT
P3.01 NO SCALE 4" SCHED 40PVC CONDUIT ALARM CABLE,
12-4-09 ISSUED FOR PERMIT
WITH LONG RADIUS BENDS LENGTHS AS
REQUIRED, IN CONDUIT 1-13-10 BID SET
AVOID DIRECT INSTALLATION
TO PREVENT FOREIGN
ELECTRICAL FLOOR COLD WATER MATERIAL FROM ENTERING
OPEN GRATING THE PRIMER VALVE
ROOM SUPPLY LINE
WITH CUT-OUT FOR
DISCHARGE &
2 FREESTANDING FIRE DEPARTMENT CONNECTION DETAIL
P3.01 NO SCALE
ELECTRICAL
CONDUIT 5
ET-1

VACUUM
CW

RELIEF VALVE BREAKER


(TEMP./PRESS.)
TRAP PRIMER VALVE MINIMUM
HW

7 12" ABOVE FINISHED FLOOR.


THERMOMETER
1/2" SUPPLY TO
EWH-3 SAFE PAN FLOOR DRAINS NOTE:
ANGLE IRON
COMPRESSION FITTING
TRAP PRIMER ALL FOUNDATION DRAINAGE PIPING SHOWN ON PLUMBING
SUPPORT DRAWINGS IS FOR INFORMATIONAL PURPOSE ONLY.
WALL 2
ROUTE TO DRAIN 6 TRAP PRIMER DETAIL 2
P3.01 NO SCALE
TANK DRAIN 4" PVC FOUNTAIN DRAIN WITH 4" PVC WEEP GROUT WITH
PUMP ON-OFF PERFORATIONS AT BOTTOM OF WATER TIGHT SEALANT 4'-0" O.C.
OIL-MINDER FLOAT PIPE ONLY. PIPING SHALL BE COORDINATE WITH STRUCTURAL
WALL MOUNTED PROBE COLD WATER SERVICE WATER CLOSET INSTALLED LEVEL. BEAM. I CERTIFY THAT THESE DOCUMENTS WERE
STEEL ANGLE STOP UNDER LAVATORY COLD WATER FLUSH VALVE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
TANK SUPPORT 1 DISTRICT OF COLUMBIA
TO LAVATORY
ESCUTCHEON
ROUTE IN WALL

1) STANCOR MODEL SE-100 SUBMERSIBLE EFFLUENT PUMP 1HP. 115 VOLT, 3600 RPM, 2" DISCHARGE CONNECTION ESCUTCHEON 08002.10
2) STANCOR CHECK VALVE ESCUTCHEON Project No.

3) STANCOR OIL MINDER 115V, 1 PHASE CONTROL SYSTEM WITH OPTIONAL BUILT-IN AUDIBLE AND VISUAL ALARM WHEN 1/4" FERRULE X 1/2"
PUMP DOES NOT RUN DUE TO OIL IN PIT OR HIGH LIQUID CONDITION. PROVIDE SIILENCING BUTTON FOR AUDIBLE ALARM M.I.P. ADAPTOR
BUILT INTO PANEL. PANEL SHALL HAVE ADDITIONAL CONTACT FOR A REMOTE ALARM LOCATION. 1/4" FERRULE X 1/2"
TERMINATE WITH M.I.P. ADAPTOR 6" X 1/2" CHROME
2-INCH AIR GAP 4) WATERTIGHT SLEEVE NIPPLE AND ELL
5) PROVIDE BYPASS SHUTOFF VALVE AND HOSE BIB, TO TEMPORARILY PUMP LIQUIDS. HOSE BIB TO BE NORMALLY CLOSED,
SERVICE SINK AND VALVE TO BE NORMALLY OPEN.
EXTEND & CONNECT
EXTEND TO TRAP
WITH 1/4" TUBING I.E. 185.6' Plumbing Details
6) OIL MINDER POWER CABLE, PROBE, AND HIGH LIQUID ALARM CABLE

P3.01
7) HIGH LIQUID ALARM FLOAT WITH CLAMP DEVICE TO MOUNT TO PUMP DISCHARGE PIPING TO DRAIN PRIMER ESCUTCHEON
MS-1 8) PROVIDE A MINIMUM OF 5 FT. EXTRA OF EACH CABLE (SLACK) ROLLED AND CLAMPED TO THE DISCHARGE PIPE TO TAPPING WITH 1/4"
4" PVC (NO PERFORATIONS)
ALLOW FOR THE REMOVAL OF THE PUMP FROM THE PIT. SOFT COPPER TUBING
DISCHARGE TO
9) SEE PLANS FOR CONTINUATION OF DISCHARGE PIPING @ LAVATORY @ FLUSH VALVE FIXTURE REFER TO STRUCTURAL DETAIL
Printed: 11/11/08
© core group, pc 2008

11 WATER HEATER DETAIL (EWH-3) 9 ELEVATOR SUMP AND PUMP DETAIL (SP-1) 5 TRAP PRIMER PIPING DETAIL 1 1 FOUNDATION DRAINAGE DETAIL ASE JOB# 0811_179

NO SCALE P3.01 NO SCALE P3.01 NO SCALE P3.01 NO SCALE


P3.01
PLUMBING FIXTURE SCHEDULE
DESIGNATION FIXTURE TYPE C.W. H.W. WASTE MANUFACTURER MODEL NO. FAUCET / FLUSH VALVE ACCESSORIES REMARKS
WC-1 WATER CLOSET- FLUSH VALVE
WALL MOUNTED BARRIER-FREE
1" - 4" TOTO CT708 SLOAN- DUAL FLUSH
ECOS-8111-SF ( 1.6 GPF /1.1 GPF )
TOLIET SEAT- TOTO SC534 1, 2, 3, 4
Mt. Pleasant
WC-2 WATER CLOSET- FLUSH VALVE
WALL MOUNTED- CHILDREN'S
1" - 4" TOTO CT708 SLOAN- DUAL FLUSH
ECOS-8111-SF ( 1.6 GPF /1.1 GPF )
TOLIET SEAT- TOTO SC534 1, 2, 3, 4 Library
L-1 LAVATORY- 1/2" 1/2" 1 1/2" KOHLER SOHO SLOAN- OPTIMA SLOAN EAF-12 1, 2, 3, 5 3160 16th Street, NW
WALL MOUNTED BARRIER-FREE K-2084-L EAF-200-P-ISM ( 0.5 GPM ) PROVIDE PLUG-IN TRANSFORMER (T2) Washington, DC 20010
L-2 LAVATORY- 1/2" 1/2" 1 1/2" TOTO VERNICA SLOAN- OPTIMA SLOAN EAF-12 1, 2, 3, 5
UNDERCOUNTER BARRIER-FREE LT156 EAF-200-P-ISM ( 0.5 GPM ) PROVIDE PLUG-IN TRANSFORMER (T2)
SK-1 SINGLE COMPARTMENT SINK- 1/2" 1/2" 1 1/2" ELKAY DAYTON DELTA- TECK VANDAL RESISTANT FLOW CONTROL 1, 2, 3, 5
SELF RIMMING BARRIER-FREE GE12521L 29C2801 AERATOR ( 1.5 GPM )
U-1 URINAL- 3/4" - 2" SLOAN WEUS-1000.1301 SLOAN- OPTIMA TRANSFORMER (T1) SLOAN EL-154 1, 2, 4
ULTRA LOW FLOW -0.13 ES-S 186-0.13 ES-S (0.13 GPF)
U-2 URINAL- 3/4" - 2" SLOAN WEUS-1000.1301 SLOAN- OPTIMA TRANSFORMER (T1) SLOAN EL-154 1, 2, 3, 4
ULTRA LOW FLOW -0.13 ES-S 186-0.13 ES-S (0.13 GPF) 901 G Street, NW
MS-1 MOP SINK 3/4" 3/4" 3" ACORN TERRAZZO-WARE DELTA- TECK - 1, 2 Washington, DC 20001
TSH-24-KF24 29C2801 ( 2.2 GPM )
Architect
DF-1 DRINKING FOUNTAIN- 1/2" - 1 1/2" ELKAY EDFP217RAC 1, 2, 3
BARRIER-FREE
REMARKS:
1. PROVIDE ALL REQUIRED COMPONENTS FOR COMPLETE FIXTURE ROUGH-IN, I.E., SUPPLIES, STOPS, TRAPS, CARRIERS, GRID DRAINS, TAILPIECES, ETC. NOT ALL REQUIRED COMPONENTS ARE SPECIFIED ABOVE.
2. SEE PLANS & RISERS FOR VENT SIZES AND CONNECTIONS
3. FIXTURES SHALL BE ADA COMPLIANT. PROVIDED WITH ADA COMPLIANT ACCESSORIES. MOUNT ADA COMPLIANT. SEE ARCHITECTURAL PLAN FOR ELEVATIONS.
4. COORDINATE VALVE INSTALLATION WITH ADA GRAB BAR. VALVE SHALL BE LOCATED SO THAT GRAB BAR DOES NOT INTERFERE WITH USE OF VALVE. PROVIDE EXTENSION AS REQUIRED. 1010 wisconsin avenue, nw
suite 405
5. PROVIDE SKAL + GUARD INSULATING DEVICES ON EXPOSED UNDERCOUNTER PLUMBING. washington, dc 20007
T 202.466.6116
PUMP SCHEDULE F 202.466.6235

SYMBOL DESCRIPTION LOCATION BASIS OF DESIGN GPM FT OF HD HP RPM REMARKS

SP-1 ELEVATOR ELEVATOR PIT STANCOR 50 28 1 3600 1, 2


SUMP PUMPS ROOM 009 SE100A
3 East 28th Street, 6th Floor
SP-2 DUPLEX MECH 1, 2 New York, NY 10016
SUMP PUMPS ROOM 007
T 212.696.0414
DOMESTIC WATER DUPLEX MINI DOMESTIC FIRE PUMP BELL & GOSSET 40 GPM EA 40 2HP 3500 1, 2, 3
BOOSTER SYSTEM WATER BOOSTER PACKAGE ROOM EA20 EA Structural Engineer

FIRE IN-LINE FIRE PUMP FIRE PUMP PEERLESS 500 54 25 1450 1, 2 ReStl Designers, Inc.
PUMP ROOM 5PVF7 1001 Connecticut Ave, NW, Suite 320
Washington, DC 20036
JOCKEY REGENERATIVE FIRE PUMP MTH 5 60 1/2 3450 1, 2
T 202.452.1103
PUMP JOCKEY PUMP ROOM
F 202.452.1133
REMARKS:
1. REFER TO ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS. MEP Engineer

2. FOR ADDITIONAL INFORMATION REFER TO PLUMBING DETAIL SHEET.


3. SET PRESSURE REDUCING VALVE AT PUMP DISCHARGE TO MAXIMUM 75 PSI.
7061 Deepage Drive
WATER HEATER SCHEDULE Columbia, MD 21045

SYMBOL DESCRIPTION LOCATION MAKE/MODEL SIZE KW TEMPERATURE RISE REMARKS T 410.381.7100


F 410.381.7110
EWH-1 SINGLE POINT ELECTRIC TANKLESS MOUNT UNDER EEMAX - 4.1 56°F @ 0.5 GPM 1 Civil Engineer

WATER HEATER LAVATORY MODEL SP4208 AMT


EWH-2 THERMOSTATIC ELECTRIC TANKLESS MOUNT UNDER EEMAX - 8.3 57°F @ 1.0 GPM 1 12750 Twinbrook Parkway
Rockville, MD 20852
WATER HEATER LAVATORY MODEL EX8208T-ML
EWH-3 ELECTRIC TANK TYPE ABV. MOP AO. SMITH 20 GAL 4.5 18 GPH RECOVERY 1, 2 T 301.881.2545
WATER HEATER SINK MODEL DEL-20 NON-SIMULTANEAUS @ 100ºF RISE F 301.881.0814
REMARKS: Landscape Architect
1. REFER TO DETAIL SHEET FOR MORE INFORMATION.
2. PROVIDE EXPANSION TANK (ET-1) AMTROL MODEL ST-5. 2410 17th Street, NW, Suite 201
Washington, DC 20009

DRAIN SCHEDULE T 202.588.5454


F 202.588.5449
DESIGNATION FIXTURE TYPE MANUFACTURER MODEL NO. ACCESSORIES REMARKS
REV DT ISSUED
FD-1 FLOOR DRAIN- GENERAL MIFAB F1100 ~ 1 5-29-09 SCHEMATIC DESIGN
FD-2 FLOOR DRAIN- MECH. RMS. MIFAB F1100-X ~ 1
7-17-09 DESIGN DEVELOPMENT
OSD OPEN SITE DRAIN MIFAB F1100-DD - 1
12-4-09 ISSUED FOR PERMIT
AD AREA WAY DRAIN MIFAB R1100 - 1
TD TRENCH DRAIN MIFAB T1320-FL ~ 1
PD PROMENADE DRAIN MIFAB R1100-PJ ~ 1
RD-1 ROOF DRAIN- VEGETATED ROOF AREAS MIFAB F1830-P ~ 1
RD-2 ROOF DRAIN- GENERAL MIFAB R1200 ~ 1
OFD-1 OVERFLOW DRAIN- VEGETATED ROOF AREAS MIFAB F1840 ~ 1
OFD-2 OVERFLOW DRAIN- GENERAL MIFAB R1200-W ~ 1
SD SCUPPER DRAIN MIFAB R1320 ~ 1
REMARKS:
1. SEE PLANS & RISERS FOR VENT SIZES AND CONNECTIONS.
2. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS.
3. REFER TO PLUMBING PLANS FOR SIZES.

EQUIPMENT SCHEDULE
SYMBOL DESCRIPTION LOCATION MAKE/MODEL SIZE ELECTRICAL ACCESSORIES REMARKS
BFP-1 BACKFLOW PREVENTER- ROOM 023 WILKINS 3" - - 1
DOUBLE CHECK VALVE ASSEMBLY TERRACE LEVEL 350A
BFP-2 BACKFLOW PREVENTER- ROOM 023 WILKINS 4" - - 2
DOUBLE CHECK DETECTOR ASSEMBLY TERRACE LEVEL 350DA
BFP-3 BACKFLOW PREVENTER- REFER TO PLANS WATTS 1" - - -
REDUCED PRESSURE ZONE ASSEMBLY (AT MECH EQUIP) SERIES 009
BFP-4 BACKFLOW PREVENTER- AT ICEMAKER WATTS 1/2" - - -
IN-LINE DUAL CHECK CONNECTION SERIES 7
WH-1 NON-FREEZE VARIOUS ZURN 3/4" - COVER, VACUUM BREAKER - I CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND THAT I AM A
WALL HYDRANT REFER TO PLANS Z1300 BRONZE FINISH DULY LICENSED ARCHITECT UNDER THE LAWS OF
DISTRICT OF COLUMBIA
GPB-1 NATURAL GAS PRESSURE MECH SPENCER TURBINE - 1 HP - 3
BOOSTER SYSTEM ROOM 007 GL-050-3/4-R
GPR-1 GAS PRESSURE REGULATOR MECH RM 007 MAXITROL 210E 2x2 - 1/2" VENT TO EXTERIOR -
REMARKS:
1. MEETS REQUIREMENTS OF ASSE 1015. Project No. 08002.10
2. MEETS REQUIREMENTS OF ASSE 1048.
3. REFER TO DETAIL 8 ON THIS DRAWING FOR MORE INFORMATION. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL REQUIREMENTS.

COMMERCIAL - MINIMUM PIPE INSULATION THICKNESS (PER IPC & IECC) [1]
SERVICE WATER PIPE SIZES
HEATING NONCIRCULATING PIPING [2] CIRCULATING MAINS AND RUNOUTS Plumbing Schedules
TEMPERATURES ALL SIZES - 1ST 8 FEET UP TO 1 1/4" 1 1/2" TO 2" OVER 2"
170-180 ºF
140-169 ºF
100-139 ºF
1/2"
1/2"
1/2"
1"
1"
1"
1"
1"
1"
1"
1"
1"
P0.02
Printed: 11/11/08
NOTES:
© core group, pc 2008
1. CONDUCTIVITY OF INSULATION k = 0.27 BTU PER INCH/HxSQ.FTxºF - TABLE ADAPTED FROM IECC 2003 SECTION 804.5.
ASE JOB# 0811_179
2. NONCIRCULATING PIPING SERVED BY EQUIPMENT WITHOUT INTEGRAL HEAT TRAPS.
Mt. Pleasant
Library
3160 16th Street, NW
Washington, DC 20010

Property Line

DRAWING NOTES: #

1. REMOVE ALL EXISTING PLUMBING FIXTURES, FAUCETS, SUPPORTS, PIPING


AND APPURTENANCES IN THIS EXISTING TOILET ROOM.
2. EXISTING STORM DOWNSPOUT TO BE REMOVED.
3. EXISTING STORM RISER TO REMAIN. 901 G Street, NW
Washington, DC 20001

DN Architect

OPEN TO BELOW
UP

STORAGE
3
SHELVING UP 1010 wisconsin avenue, nw
1 suite 405
washington, dc 20007
T 202.466.6116
OPEN TO BELOW
F 202.466.6235

TOILET
MEZZANINE LEVEL
SPANISH
ROOM
2 DEMOLITION MEZZANINE FLOOR PLAN- PLUMBING REFERENC
E
UP

DP0.02 SCALE: 1/8" = 1'-0" 3 East 28th Street, 6th Floor


New York, NY 10016
2
T 212.696.0414
OFFICE
Structural Engineer
ReStl Designers, Inc.
3 2 1001 Connecticut Ave, NW, Suite 320
ELEC STAFF Washington, DC 20036
CLOSET ROOM
T 202.452.1103
F 202.452.1133
MEP Engineer

COMPUTERS
READING AREA 7061 Deepage Drive
STACKS Columbia, MD 21045
AREA 3
T 410.381.7100
F 410.381.7110
Civil Engineer
AMT
12750 Twinbrook Parkway
Rockville, MD 20852
FIRST FLOOR T 301.881.2545
LOBBY F 301.881.0814
ADULT
READING AREA
Landscape Architect

2410 17th Street, NW, Suite 201


Washington, DC 20009

T 202.588.5454
F 202.588.5449
3
REV DT ISSUED
5-29-09 SCHEMATIC DESIGN

7-17-09 DESIGN DEVELOPMENT


12-4-09 ISSUED FOR PERMIT

1 DEMOLITION FIRST FLOOR PLAN- PLUMBING


DP0.02 SCALE: 1/8" = 1'-0"
I CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
DISTRICT OF COLUMBIA

Project No. 08002.10

Demolition
First Floor Plan
- Plumbing

1' 0 4' 8' 12' 16'


N DP0.02
Printed: 11/11/08
© core group, pc 2008
GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179
eF
1 2 2.3 3 3.9 4 5 5.7 6 GENERAL NOTES:
A. REFER TO DATA SHEET FOR PLUMBING SYMBOLS AND ABBREVIATIONS.
B. REFER TO RISER DIAGRAMS FOR ADDITIONAL SIZES OF UTILITIES AND PIPING. Mt. Pleasant
C. FOR PLUMBING FIXTURES AND EQUIPMENT REFER TO SCHEDULES ON DATA SHEET.
Library
DRAWING NOTES: #
3160 16th Street, NW
eE 1.
PIPING BELOW SLAB. Washington, DC 20010
2.
PIPING ABOVE CEILING OR TIGHT TO UNDER SIDE OF STRUCTURE.
MAINTAIN MINIMUM 18" CLEARANCE 3.
PIPING ABOVE FLOOR SLAB IN PIPE CHASE OR WALL.
1 1/2" G 4.
FOR CONTINUATION REFER TO CIVIL DRAWINGS.
11
5.
RPZ- BACKFLOW PREVENTER BFP-3 FOR MECHANICAL EQUIPMENT. EXTEND FULL SIZE
(500 CFH) (TYP) GPB-1 eD DISCHARGE TO 4" OPEN SITE DRAIN.
P3.01 SP-2
MECH BOILERS 1/2" GPR-1 6. 4" FOUNDATION DRAINAGE CONNECTION BELOW SLAB. REFER TO STRUCTURAL
G 7 DRAWINGS FOR CONTINUATION. INVERT AT 3' BELOW FINISHED FLOOR.
7. 1" NON-POTABLE WATER SERVICE FOR MECHANICAL EQUIPMENT.
2" (1,000 CFH) 2" 8. PROVIDE ACCESS PANEL IN WALL OR PROVIDE ACCESS BELOW CABINET. 901 G Street, NW
9 eC 9. 1/2" GAS PRESSURE REGULATOR VENT THROUGH EXTERIOR WALL TO OUTSIDE.
1 6 Washington, DC 20001
7 10. NON-FREEZE WALL HYDRANT.
Elec. 11. OVERFLOW DRAIN THROUGH EXTERIOR WALL AND SPILL TO GRADE. Architect
4 12 G 3" V- UP 008 eB
4" FD-2 W 1 1/4" CW- UP 12. GAS METER BY LOCAL GAS COMPANY.

TP
2

M
5 BFP-3 13. CONTRACTOR SHALL PROVIDE ADD-ALTERNATIVE PRICE TO REPLACE EXISTING STORM

ST/PD
1" 2 2" 1 1/4"
Mech. 3" W 1" NP WATER- UP RISER WITH NEW CAST IRON NO-HUB RISER FROM THE ROOM DOWN TO THE POINT OF
007 G PD 2 2 TO COOLING TOWER TERMINATION.
F

PD
SP-1 eA 14. 1" RPZ DISCHARGE AND 2" SUMP PUMP DISCHARGE TO 4" OPEN SITE DRAIN. PROVIDE
14 L-2 TAILPIECE AND TERMINATE PIPE AT 45° SAW CUT ANGLE.
4" OSD L-2 WC-2 Elev.
E 11 MS-1 WC-2 009 15. SPRINKLER FLOOR CONTROL VALVE ASSEMBLY.
EWH-3 1010 wisconsin avenue, nw
L-2 2 16. EXTEND TO AUTOMATIC HYDRAULICALLY CALCULATED FULLY SPRINKLERED SYSTEM. suite 405
P3.01
WC-1 washington, dc 20007
Mop
3/4" Women's U-1 Men's L-2
D Sink
011 010 T 202.466.6116
4" WC-1 Garden F 202.466.6235
3" U-2
and Entry
Storage
C.5 1 6" ST- UP & DN 014
Trash
006 (4,315 SQ. FT.) 1
CO
Conf.
C 2" 4" 2" CW
012
2 3 East 28th Street, 6th Floor
3/4" 1 New York, NY 10016
B 6" ST 4 CW- UP ST/PD P1.01
T 212.696.0414
Hallway 1 4" SAN- UP 1 1/2" Lobby
005 1" CO 2" 013 3/4" Structural Engineer
4"

ST
CO 1/2" ReStl Designers, Inc.
A.7 ST 3/4"
1001 Connecticut Ave, NW, Suite 320
Stair
4" CO DF-1 2"
004 Washington, DC 20036
A 16 15 T 202.452.1103
1
2 F 202.452.1133
SP

eF CO 4" SAN- UP 2 MEP Engineer


Stair 4"
003 3/4" Info1
F 016 Adult Non-Fiction
1 015 EX 4" ST 3
(E) 7061 Deepage Drive
CO 13
(E) 4" ST 13 (E) 4" POWER CONVERTER POWER CONVERTER Columbia, MD 21045
2 8 8
F FOR (2) FAUCETS FOR (2) FAUCETS
4" F- UP T 410.381.7100
1
F 410.381.7110
CO 3"
Mech. T2 4" T2 1 1/4" Civil Engineer
2" L-2
002
(E) WH TO BE EWH-2
WC-2 WC-2
1 1/4" L-2 Elev.
AMT
12750 Twinbrook Parkway
eE REMOVED & 3 3" FD-1 Rockville, MD 20852
4" Stacks 10 REPLACED EWH-2 2"

TP
017 3/4" 2 4"
2" 3" T 301.881.2545
W 1" CW- UP 1" WITH NEW H-1 3 L-2
L-2 3" TP 3" FD-1 3" 3" 3 F 301.881.0814
1 3"
Landscape Architect

U-1
eD
Study
021 1
D
2 Women's WC-1 TP Men's3" CO
3"
2410 17th Street, NW, Suite 201
Young Adult e10 011
001
WC-1 4" 2" 010 1 Washington, DC 20009
U-2 3" FD-1 T 202.588.5454
2" 2 2"
Study C.53 3" 2" F 202.588.5449
eE.5 018
Study 4" T1 POWER CONVERTER
022 Comp./ 3/4" 8
(E) 4" ST 13 2" FOR (2) URINAL FV'S
eC Conf. REV DT ISSUED
020 e9 5-29-09 SCHEMATIC DESIGN
e10 4" 4" 4" 1 1/4"
F

2 2" CW- DN 7-17-09 DESIGN DEVELOPMENT


1 1 2"
CO (E) 4" SANITARY 12-4-09 ISSUED FOR PERMIT
eB Pump 1
Room 2 1 1/2" 4" 1-13-10 BID SET
4" 019
Study 2" Study e8
024 023 TO BE FIELD VERIFIED
F I.E. 185.6'
BY CIVIL ENGINEER e9
F
4
2 PART PLAN- TOILET ROOMS
eA P1.01 SCALE: 1/4" = 1'-0"
EX 4" ST
3" V- UP e7
13 6" FIRE TO FIRE PUMP
2" INCOMING DOMESTIC WATER 1 TEST HEADER, ROUTE
SERVICE, REFER TO CIVIL FOR FIRE PUMP ROOM e8 PIPING THROUGH CHASE
CONT. SET CENTERLINE OF 4 BELOW GRADE P1.01
INCOMING PIPE AT 195.90' IN STUDY ROOM
022 Comp./
F

6" INCOMING FIRE SERVICE


4
Conf.
F

REFER TO CIVIL FOR CONT. 4" FIRE TO FREE STANDING


SET CENTERLINE OF INCOMING FIRE DEPT SIAMESE CONNECTION,
2"
FIRE SERVICE PIPE AT 195.96'
e7
ROUTE PIPING THROUGH 020 4"
CHASE IN STUDY ROOM 4"
eC.1 6" F- UP TO FIRE DEPARTMENT
SIAMESE CONNECTION RAISED THRESHOLD TO PREVENT F
POSSIBLE WATER DAMAGE F
8" F- UP TO FIRE PUMP DOMESTIC WATER

TP
TEST HEADER BOOSTER PACKAGE BP-1 F 4"
4" Pump
PLUMBING CHASE
WITH FULL SIZE
Room
F
F 3" FD-2
019
I CERTIFY THAT THESE DOCUMENTS WERE
eA.5 ACCESS DOOR 3" FD-2 4" OS&Y WITH TAMPER SWITCH (TYP) PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
4" JOCKEY PUMP JP-1
Study 2" Study IN-LINE ELECTRIC FIRE PUMP FP-1
DISTRICT OF COLUMBIA

TP
e6
024 3" FD-2 023
F
e5.8
e5.7 F 08002.10
F FIRE PUMP & JOCK PUMP CONTROLLERS Project No.

e5.3
e5.2 eA.5 TP
e5 3" V- UP 6" BFP-2

e1 e2 e3 e4
2" BFP-1
Terrace Floor Plan
2" INCOMING DOMESTIC
1 PART PLAN- PUMP ROOM - Plumbing
WATER SERVICE 4"OSD P1.01 SCALE: 1/4" = 1'-0"
3 TERRACE FLOOR PLAN- PLUMBING
P1.01 SCALE: 1/8" = 1'-0"
6" INCOMING FIRE SERVICE

e5.2
e5.3
1' 0 2' 4' 6' 8' 1' 0 4' 8' 12' 16'
N P1.01
e5 Printed: 11/11/08
© core group, pc 2008
GRAPHIC SCALE 1/4" = 1'-0" GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179
eF
1 2 2.3 3 3.9 4 5 5.7 6

GENERAL NOTES: Mt. Pleasant


A. REFER TO DATA SHEET FOR PLUMBING SYMBOLS AND ABBREVIATIONS.
B. REFER TO RISER DIAGRAMS FOR ADDITIONAL SIZES OF UTILITIES AND PIPING. Library
C. FOR PLUMBING FIXTURES AND EQUIPMENT REFER TO SCHEDULES ON DATA SHEET.
3160 16th Street, NW
eE Washington, DC 20010
4" OVERFLOW PIPING THROUGH 3" OVERFLOW PIPING THROUGH DRAWING NOTES: #
EXTERIOR WALL & SPILL TO EXTERIOR WALL & SPILL TO 1. PIPING BELOW SLAB.
SPLASH BLOCK 18" ABOVE GRADE SPLASH BLOCK 18" ABOVE GRADE 2. PIPING ABOVE CEILING OR TIGHT TO UNDERSIDE OF STRUCTURE.
4" OFD- DN 3" OFD- DN eD 3. PIPING ABOVE FLOOR SLAB IN PIPE CHASE OR WALL.
(1,140 SQ.FT.) 4" SAN- UP (925 SQ.FT.) 4. SPRINKLER FLOOR CONTROL VALVE ASSEMBLY.
5. EXTEND TO AUTOMATIC HYDRAULICALLY CALCULATED FULLY SPRINKLERED SYSTEM.
G 6. INSTANTANEOUS WATER HEATER LOCATED ABOVE FLOOR IN MILLWORK OR CABINET.
CO RUN 1/2" COLD WATER TO WATER HEATER IN CABINET.
4" 901 G Street, NW
eC
2 Washington, DC 20001
3" V- UP
1 1/2" Storage
107 eB Architect

W 1" NP WATER- UP
1 1/4" CW- W 3 TO COOLING TOWER
F UP & DN 2
1 1/2" eA
Meeting 4" Elev.
Room 109
E 106 1010 wisconsin avenue, nw
IT
Closet suite 405
Vestibule washington, dc 20007
UP DOWN 112
D 108
T 202.466.6116
F 202.466.6235

C.5 Stair
Pantry 3/4" CW 111
105 FROM BELOW
C 4" SAN- DN SK-1 1/2" Entry
Hall
3 East 28th Street, 6th Floor
110 New York, NY 10016
B 4" SAN- UP
6 EWH-2 T 212.696.0414
Stair
104 1 3 6" ST- UP & DN Structural Engineer
(4,315 SQ. FT.) Open
A.7 above 4" ReStl Designers, Inc.
2 1001 Connecticut Ave, NW, Suite 320
UP Washington, DC 20036
A Workroom
113
T 202.452.1103
DOWN Open F 202.452.1133
4
eF above 4" SAN- DN MEP Engineer
Circulation
SP 114
Stair F CO
103 2 UP DOWN
2 5 7061 Deepage Drive
Stacks Columbia, MD 21045
115
F 4" F- UP & DN T 410.381.7100
1 F 410.381.7110
Civil Engineer
AMT
eE 12750 Twinbrook Parkway
Rockville, MD 20852
Display T 301.881.2545
W 1" CW- 116
F 301.881.0814
1 UP & DN
Landscape Architect

eD
2410 17th Street, NW, Suite 201
Stacks Washington, DC 20009
102
T 202.588.5454
eE.5 F 202.588.5449
Entry
Vestibule
117
eC REV DT ISSUED
5-29-09 SCHEMATIC DESIGN
e10
7-17-09 DESIGN DEVELOPMENT
3" V- UP & DN
eB 12-4-09 ISSUED FOR PERMIT
Exit 1-13-10 BID SET
Vestibule DOWN
101
DOWN
PORCH e9

eA

FREE STANDING FIRE PUMP TEST e8


HEADER 8" X 2 1/2" X 2 1/2" W/ F.D.
VALVES, CAPS & CHAINS (CHROME)

e7

eC.1 FREE STANDING FIRE


DEPARTMENT SIAMESE
CONNECTION 6" X 2 1/2" X 2 1/2"
W/ CAPS & CHAINS (CHROME)

eA.5 I CERTIFY THAT THESE DOCUMENTS WERE


PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
DISTRICT OF COLUMBIA

e6
e5.8
e5.7 08002.10
Project No.
e5.3
e5.2
e5
e1 e2 e3 e4 First Floor Plan
- Plumbing

1 FIRST FLOOR PLAN- PLUMBING 1' 0 4' 8' 12' 16'


N P1.02
Printed: 11/11/08
P1.02 SCALE: 1/8" = 1'-0" © core group, pc 2008
GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179
Mt. Pleasant
Library
3160 16th Street, NW
Washington, DC 20010

Property Line

DRAWING NOTES: #

1. DEMO ALL EXISTING PLUMBING FIXTURES, FAUCETS, SUPPORTS, PIPING AND


APPURTENANCES IN THIS EXISTING TOILET ROOM.
2. NOT USED.
3. EXISTING STORM RISER TO REMAIN. 901 G Street, NW
Washington, DC 20001

Architect

3
1010 wisconsin avenue, nw
suite 405
washington, dc 20007
T 202.466.6116
F 202.466.6235

1
STAFF
TOILET 3 East 28th Street, 6th Floor
New York, NY 10016
T 212.696.0414
CHILDREN'S STAFF Structural Engineer
TOILET LOUNGE ReStl Designers, Inc.
3 1001 Connecticut Ave, NW, Suite 320
Washington, DC 20036
FIRST-AID T 202.452.1103
ROOM F 202.452.1133
MEP Engineer

WORK ROOM
TEENAGER'S CHILDREN'S
AREA/ COMPUTERS STACK ROOM
7061 Deepage Drive
Columbia, MD 21045
3
T 410.381.7100
F 410.381.7110

LIBRARIAN Civil Engineer


AMT
12750 Twinbrook Parkway
Rockville, MD 20852
LOBBY ELEVATOR
LOBBY T 301.881.2545
F 301.881.0814
Landscape Architect

2410 17th Street, NW, Suite 201


MULTI-PURPOSE CHILDREN'S READING Washington, DC 20009
AREA EXHIBITS AREA
T 202.588.5454
F 202.588.5449
3
ALCOVE 2 REV DT ISSUED
5-29-09 SCHEMATIC DESIGN

7-17-09 DESIGN DEVELOPMENT


12-4-09 ISSUED FOR PERMIT

1-13-10 BID SET


ALCOVE 1

1 DEMOLITION SECOND FLOOR PLAN- PLUMBING


DP0.03 SCALE: 1/8" = 1'-0"
I CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF
DISTRICT OF COLUMBIA

Project No. 08002.10

Demolition
Second Floor Plan
- Plumbing

1' 0 4' 8' 12' 16'


N DP0.03
Printed: 11/11/08
© core group, pc 2008
GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179
3" VTR 3" VTR 3" VTR
ROOF ROOF

3" 3"
3"

Mt. Pleasant
3"
1 1/2" L-1
3"
3"
L-1 1 1/2" SK-1 1 1/2" Library
1 1/2" 3160 16th Street, NW
2"
2" WC-2 WC-2 1 1/2" Washington, DC 20010

SECOND FLOOR 4" FD-2 CO SECOND FLOOR


TP 4" 1 1/2"
4" 4"
4" (2 DFU) 1 1/2"
4" (7 DFU) CO
CO 4" (7 DFU) 4" 1 1/2"
4" SK-1 901 G Street, NW
4"
Washington, DC 20001
2" ELEVATOR PD FROM SP-1 Architect
TO 4" OPEN SITE DRAIN 2" VENT 2" (2 DFU)
3" 3" FROM SP-2
FIRST FLOOR 2" FIRST FLOOR
PD
4"
2"
3" 3"
3" 1 1/2" 1 1/2" 1010 wisconsin avenue, nw
FIELD VERIFY PRIOR TO START 1 1/2" 1 1/2" 2" suite 405
2" 1 1/2"

PD
OF ANY INSIDE SANITARY 2" 3" 3" 3" washington, dc 20007
DF-1 L-1 L-1 3" L-1 L-1 U-2 U-1
PIPING. REPORT TO ARCH/ T 202.466.6116
ENGINEER IF INV. EL. INSTALLED 3" (6 DFU) 1 1/2" 1 1/2" 2" (4 DFU) F 202.466.6235
4" (12 DFU) 4" 1 1/2" WC-1 WC-1 WC-2 WC-2
LOWER THAN ANTICIPATED. I.E. 185.6' 2" (2 DFU) 2" 4" (20 DFU)
(E) CO 4" OSD CO 1 1/2" (0.5 DFU) 3" 4" OSD MS-2 CO CO 4"
TERRACE FLOOR (E) CO 3" FD-2 3" FD-2 3" FD-2 3" FD-1 3" FD-1 4" FD-2 2" (2 DFU) 3" FD-1 CO TERRACE FLOOR
EXISTING 4" SANITARY 4" TP TP TP CO 2" TP 4" (10 DFU) TP 4" (16 DFU) 2" 2" 4" 4"
TP 4" 2" TP
SEWER LATERAL. REFER 4"
TO CIVIL DWG FOR CONT. 2" 4"
3 East 28th Street, 6th Floor
(E) 4" (49.5 DFU) 4" (49 DFU) 4" (40 DFU) 4" (9 DFU) 4" (34 DFU) 3" (2 DFU) 4" (6 DFU) 4" (2 DFU) 4" (9 DFU) 3" (2 DFU) 4" (14 DFU) 4" (9 DFU) New York, NY 10016
(E) 4" W 1" NON POTABLE WATER 4" (56.5 DFU) 4" (2 DFU) 4" (34 DFU)
(68.5 DFU) 3 TO MECH COOLING TOWER 5 SANITARY RISER DIAGRAM T 212.696.0414
NO SCALE W 1 1/4" (16 WSFU) W
P2.01 1" (12 WSFU) Structural Engineer
1 2
NP AIR CHAMBER AIR CHAMBER ReStl Designers, Inc.
ROOF ROOF 1001 Connecticut Ave, NW, Suite 320
1" NON POTABLE WATER Washington, DC 20036
TO MECH COOLING TOWER, T 202.452.1103
REFER TO MECH DWGS. 1" (12 WSFU) F 202.452.1133
1" 1 1/4" (16 WSFU) 3/4" (2 WSFU) 1" (12 WSFU)
PROVIDE HEAT TRACING ON
NON POTABLE WATER LINE MEP Engineer
1/2"
ON ROOF AND 2' FEET BELOW ROOF
EWH-2 EWH-1 WC-2 L-1 EWH-1
L-1 WC-2 L-1
TO ICE
MAKER 7061 Deepage Drive
Columbia, MD 21045
1/2" 1" 1/2" 1" 1/2" 1"
SECOND FLOOR BFP-4 SECOND FLOOR T 410.381.7100
F 410.381.7110
Civil Engineer
AMT
12750 Twinbrook Parkway
Rockville, MD 20852
T 301.881.2545
SK-1 EWH-2 F 301.881.0814
VACUUM RELIEF VALVE 1" (12 WSFU) Landscape Architect
COMPLY WITH ANZI Z21.22 2" (54 WSFU) 1 1/4" (16 WSFU) 1/2"
FIRST FLOOR 1" 1" 1" 2" (50 WSFU) 2" (69.25 WSFU) 2" (81.25 WSFU) FIRST FLOOR
2410 17th Street, NW, Suite 201
Washington, DC 20009
ET-1
1" NON POTABLE WATER T 202.588.5454
3/4" (2 WSFU) 2" (64 WSFU) 3/4" 3"
TO MECH BOILERS, REFER TO 3/4" (3 WSFU) 3/4" (4 WSFU) 2" (50 WSFU) F 202.588.5449
1 1/4" (20 WSFU) 2" (64 WSFU) 1/2" (0.25 WSFU) 2 1/2" 3"
MECH DWGS FOR CONT. EWH-3
1" 3/4" WC-1 3/4"
1" NON POTABLE WATER 11 (4 WSFU) EWH-2 (4 WSFU) EWH-2 3/4" REV DT
WC-2 DF-1 3" BFP-1 ISSUED
TO MECH CHILLER, REFER TO L-2 L-2 U-2 L-2 L-2
MECH DWGS FOR CONT. BFP-3 P3.01 SA 3/4" 5-29-09 SCHEMATIC DESIGN
MS-1 WC-2 U-1 WC-1 WH-1 7-17-09 DESIGN DEVELOPMENT
NP 3"
NP 1/2" 1/2" 1/2" 1/2" 12-4-09 ISSUED FOR PERMIT
TERRACE FLOOR 3" FD-2 3" TERRACE FLOOR
FULL SIZE DISCHARGE TO 1" 1 1/4" 1 1/2" 2"
4" OPEN SITE DRAIN 4 DOMESTIC WATER RISER DIAGRAM DOMESTIC WATER 2
3"
P2.01 NO SCALE 3" INCOMING DOMESTIC
BOOSTER PACKAGE P3.01
EXTEND TO HYDRAULIC SP (DRY) WATER SERVICE, REFER
F CALCULATED FULLY TO CIVIL DRAWINGS FOR
1 SPRINKLERED WET PIPE SYSTEM CONTINUATION
ROOF ROOF
EXTEND TO HYDRAULIC
SP DESIGNED SPRINKLER EXISTING DOWNSPOUT TO
DRY- PIPE SYSTEM IN ATTIC REMAIN REFER NOTE #13 DWG
F
P1.01.
DRY- PIPE VALVE AND COMPLETE
SYSTEM IN FACTORY MADE CABINET

DS
F

BY VICTAULIC OR APPROVED EQUAL 2


F

P3.01 (E) 4"


SECOND FLOOR SECOND FLOOR

EXTEND TO HYDRAULIC
SP CALCULATED FULLY
SPRINKLERED WET PIPE SYSTEM
FREE STANDING FIRE
DEPARTMENT
FREE STANDING SIAMESE CONNECTION
FIRE PUMP TEST HEADER 8 NATURAL GAS BOOSTER
F

FLANGED EXPANSION JOINT ON INLET AND


SYSTEM (GBP-1), REFER TO
DISCHARGE PIPING IN ACCORDANCE WITH P3.01
I CERTIFY THAT THESE DOCUMENTS WERE
RISER CONTROL VALVE DETAIL FOR MORE INFORMATION PREPARED OR APPROVED BY ME, AND THAT I AM A

2" ST/ PUMP DISCHARGE 2" VENT TO 1/2" GAS PRESSURE REDUCING SPECIFICATION. MANUAL BY-PASS PACKAGED DULY LICENSED ARCHITECT UNDER THE LAWS OF
AT THE BASE OF STAIR 003 JOCKEY PUMP JP-1 4" 4" 1/2" DISTRICT OF COLUMBIA
FIRST FLOOR TO 4" OPEN SITE DRAIN 3" VENT RISER VALVE VENT TO EXTERIOR AS PART OF GAS BOOSTER SYSTEM FIRST FLOOR
SP F F
2" (1,000 CFH) G G
F 3/4" AUTO BALL DRIP 2" 2" 1 1/2" (500 CFH)
EXTEND TO HYDRAULIC CALCULATED FULLY GAS METER, MAIN SHUT-OFF Project No. 08002.10

G
SPRINKLERED WET PIPE SYSTEM GUARDIAN MODEL 6432 AND PRESSURE REGULATOR 1 1/2" (500 CFH)
F

G
GAS COCK
ST/PD

BY LOCAL GAS COMPANY G


(E) 4" PROVIDE GAS BOOSTER SYSTEM
4" BFP-2 TO B-1 TO B-1 TO BOOST TO 14" W.C.
Plumbing
G
DS

MECH BOILER MECH BOILER MAINTAIN 18" CLEARANCE


4" BACK WATER VALVE
(500 CFH) (500 CFH) GPR-1
TERRACE FLOOR
3" FD-2 3" FD-2
4" M
TERRACE FLOOR
Riser Diagrams

F
3"
CONCENTRIC REDUCER
IN-LINE FIRE PUMP FP-1
ECCENTRIC REDUCER 6" TO FOUNDATION
G
INCOMING LOW PRESSURE GAS
SERVICE BY LOCAL GAS COMPANY REFER
NATURAL GAS CALCULATIONS BASED ON INTERNATIONAL FUEL GAS CODE:
SCHEDULE 40 METALLIC PIPING
P2.01
4" INLET PRESSURE = LESS THAN 2.0 PSI PRESSURE DROP = 0.3" W.C. Printed: 11/11/08
4" INCOMING FIRE DRAIN (BY OTHERS) TO CIVIL DRAWINGS FOR CONTINUATION EQUIVALENT LENGTH = 40' SPECIFIC GRAVITY= 0.60
SERVICE, REFER TO 3 FIRE PROTECTION RISER DIAGRAM 2 STORM WATER RISER DIAGRAM SP-2, DUPLEX SUMP (E) DOWNSPOUT CONNECTION TO TOTAL LOAD = 1,000 CFH
1 GAS RISER DIAGRAM © core group, pc 2008

CIVIL DRAWINGS FOR ASE JOB# 0811_179


P2.01 NO SCALE P2.01 NO SCALE PUMP PACKAGE REMAIN, REFER TO CIVIL DRAWINGS P2.01 NO SCALE
CONTINUATION FOR CONTINUATION
eF
1 2 2.3 3 3.9 4 5 5.7 6

GENERAL NOTES:
A. REFER TO DATA SHEET FOR PLUMBING SYMBOLS AND ABBREVIATIONS.
B. REFER TO RISER DIAGRAMS FOR ADDITIONAL SIZES OF UTILITIES AND PIPING. Mt. Pleasant
eE
C. FOR PLUMBING FIXTURES AND EQUIPMENT REFER TO SCHEDULES ON DATA SHEET.
Library
1 DRAWING NOTES: #
3" UP TO 3" OFD-1 1. PIPING BELOW SLAB. 3160 16th Street, NW
P1.03 (225 SQ. FT.) 2. PIPING ABOVE CEILING. Washington, DC 20010
EDGE OF
4" OFD- DN 3" ST UP TO 3" RD-1 3" OFD- DN CANOPY
BELOW eD 3. PIPING ABOVE FLOOR SLAB IN PIPE CHASE OR WALL.
(1,140 SQ.FT.) 4" SAN- DN (225 SQ. FT.) (925 SQ.FT.) 4. VICTAULIC FIRE-PAC DRY VALVE SPRINKLER CABINET. SIZE AIR COMPRESSOR
BASED ON MANUFACTURER'S RECOMMENDATIONS.
G Staff 5. SPRINKLER FLOOR CONTROL VALVE ASSEMBLY.
Bathroom 3" UP TO 3" OFD-1 3" UP TO 3" OFD-1
208
6. EXTEND TO AUTOMATIC HYDRAULICALLY CALCULATED FULLY SPRINKLERED SYSTEM.
(570 SQ. FT.) (400 SQ. FT.) 7. PROVIDE ICE MAKER OUTLET BOX BY OATEY OR APPROVED EQUAL.

D
3" eC

OF
Workroom WC-1 CO L-1 SK-1
8. PIPING, VALVE OR EQUIPMENT LOCATED ABOVE FLOOR IN MILLWORK OR CABINET.
207 OFD CO OFD
CO 4" CO 2 4" 3" V- UP 901 G Street, NW
Elevator TO 3" VTR Staff Lounge eB Washington, DC 20001
3" ST UP TO 3" RD-1 2
Control Closet ST ST 210
206 (570 SQ. FT.) Architect
3" ST UP TO 3" RD-1 W 1 1/4" 3"
2

(NP)
Roof (400 SQ. FT.) 2 CW- DN
F 4" ST- UP TO
Access 4" (2,245 SQ. FT.) eA
205 4" GUTTER
4" Elev. (750 SQ. FT.)

OFD
E 2 209

OFD

ST
ST
D 3" 4" 1010 wisconsin avenue, nw
Branch Elec. suite 405
Friends of ST 213
Manager 6" (2,815
the SQ. FT.)
Library washington, dc 20007
204 211
3" UP TO 3" OFD-1 T 202.466.6116
C.5 3" (NP) 4 F 202.466.6235
Strollers (300 SQ. FT.)
203 4" 1" 4" SAN- DN
2 3" ST UP TO 3" RD-1
C (750 SQ.FT.) 4" (750 SQ.FT.) 4" FD-2 Bathroom

ST
3" UP TO 3" OFD-1 (300 SQ. FT.)
(570 SQ. FT.) ST 215

B 1" NP WATER- UP W

TP
3" ST UP TO 3" RD-1 TO COOLING TOWER 3 Bridge Open
(570 SQ. FT.) 212 3 East 28th Street, 6th Floor
6" ST- DN below
Storage New York, NY 10016
DOWN
(4,315 SQ. FT.) 4" ST- UP TO
220
4" GUTTER

SP
A.7 T 212.696.0414

DR
(750 SQ. FT.) DOWN

Y
Structural Engineer

A 4" ST- UP TO 4" SP (DRY)- UP ReStl Designers, Inc.


4" GUTTER Workroom 1001 Connecticut Ave, NW, Suite 320
Open 214 TO ATTIC
(750 SQ. FT.) below
Washington, DC 20036
eF 4" T 202.452.1103
1" F 202.452.1133
SP
Stair 5 Info MEP Engineer
202 2 6 216 Children's

F
F Program
217

Ship's Ladder F 4" F- UP RAMP 7061 Deepage Drive


UP Columbia, MD 21045
to Attic 1 & DN Reading
218 T 410.381.7100
DOWN 1"
F 410.381.7110
eE Civil Engineer
UP AMT
12750 Twinbrook Parkway
W 1" CW- Rockville, MD 20852
1 UP & DN
Young
T 301.881.2545
Children F 301.881.0814
eD 219 U
P Landscape Architect

2410 17th Street, NW, Suite 201


Washington, DC 20009
eE.5
UP T 202.588.5454
4" SAN- DN F 202.588.5449
eC
Children's WC-2
Stacks e10
201 REV DT ISSUED
3" V- UP 3"
5-29-09 SCHEMATIC DESIGN
eB TO 3" UP
VTR
4" L-1 7-17-09 DESIGN DEVELOPMENT
T2 3" V- UP
Storage TO 3" VTR
12-4-09 ISSUED FOR PERMIT

3" V- DN
e9
220 1 1/2"
3 EWH-1 1-13-10 BID SET

POWER CONVERTER 1"


FOR FAUCETS
eA

e9
Alcove
221
e8
Alcove
eE
220
2 SECOND FLOOR PART PLAN- PLUMBING
SCALE: 1/4" = 1'-0"
e7 P1.03

eC.1

3.9 4 4" SAN- DN


1/2" H & CW
3 1 3
TO SK-1
1" 4" 2"
G

eA.5 CO L-1
T2
EWH-1 3/4" SK-1 I CERTIFY THAT THESE DOCUMENTS WERE
WC-2 REF 8 EWH-2 PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED ARCHITECT UNDER THE LAWS OF

e6 8 BFP-4
DISTRICT OF COLUMBIA

e5.8
e5.7
1/2" CW- TO
e5.3 7
1 1/4" ICEMAKER
e5.2 2 Project No. 08002.10
e5
3" V- UP TO 3"
Staff Lounge
e1 e2 e3 e4 VTR & 3" V- DN 210
Second Floor Plan
3 SECOND FLOOR PLAN- PLUMBING 1 RESTROOM & KITCHEN PART PLAN- PLUMBING - Plumbing
SCALE: 1/8" = 1'-0"

P1.03
P1.03 P1.03 SCALE: 1/4" = 1'-0"

N
1' 0 2' 4' 6' 8' 1' 0 4' 8' 12' 16'
Printed: 11/11/08
© core group, pc 2008
GRAPHIC SCALE 1/4" = 1'-0" GRAPHIC SCALE 1/8" = 1'-0"
ASE JOB# 0811_179