Parameter
Transformer rating
No Load KVAR for compensation
@ 5% of KVA
System Voltage
Loading Factor

Rating
40000

Factors
KVA

310

kW

2000

KVAR

0.7

PF

11000
85%

Total KVA Considering Load Factor

34000

KVA

27200

KW

0.8
0.99
14895
14900
12124.2
0.2
14900

PF
PF
kVAr
kVAr
V
%
kVAr

Savings In KVA
Previous KVA
Present KVA
Savings in KVA
Savings in Rs
Cable Losses Savings
Current Savings

PF
0.8
0.99
KVA
INR

Set
34000
27475
6525
1109293
35%

Line Current during PF @ initial PF

0.8

1785

0.99

1442

342

Total KW Considering Load Factor


and Power Factor
Present Power Factor
Target Power Factor
Kvar Required
Total Kvar Shall be Rounded to
Capacitor New Voltage
Reactor
Capacitor Bank
Savings

Line Current during PF @ Target


PF
Line Current Savings

Savings Snap Shot


KVA Savings
6525
INR Savings/month
1109293
Cable Loss Savings
35%
Current Savings
342

KVA
Rs
Percentage
Amperes

442.85714 kVA