FEATURES
DESCRIPT ION
Automatically
senses
mains
(utility) failure and starts the
backup generator.
557
AMF AND MAINS
PARALLEL
CONT ROLLER
Issue 2
AM 22/10/03
SPECIFICAT ION
DC Supply:
8V to 35V Continuous.
Cranking Dropouts:
Able to survive 0V for 50 mS,
providing supply was at least 10V
before dropout and supply recovers
to 5V. This is achieved without the
need for internal batteries.
Max. Operating Current:
513mA at 12V. 263mA at 24V.
Max. Standby Current:
370mA at 12V. 210mA at 24V.
Alternator Input Range:
15V(ph-N) to 277V(ph-N) AC
(+20%)
Alternator Input Frequency:
50Hz - 60Hz at rated engine speed
(Minimum: 15V AC Ph-N)
Magnetic Pick-up Voltage Input
Range:
+/- 0.5V to 70V Peak
Magnetic Input Frequency:
10,000Hz (max)
Mains Sensing Input Range:
15V(ph-N) to 277V(ph-N) AC
(+20%)
Mains Sensing Input Frequency:
50Hz - 60 Hz (Minimum: 15V AC
Ph-N)
Start Relay Output:
16 Amp DC at supply voltage.
Fuel Relay Output:
16 Amp DC at supply voltage.
Auxiliary Relay Outputs:
5 Amp DC at supply voltage.
Generator loading Relay Output:
8 Amp AC 250V.
Mains loading Relay Output:
8 Amp AC 250V
Charge Fail / Excitation Range:
0V to 35V
Operating Temperature Range:
-30C to +70C
Dimensions:
192mm x 144mm x 138mm
7.
6
x5.
7
x5.
5
CASE DIMENSIONS
144.0mm
(
5.
7
)
137mm
(
5.
4
)
155.0mm
110mm
7.
3
)
185.0mm (
(
4.
3
)
7.
6
)
192.0mm (
5.
5x7.
3
)
Panel Cut-out:138mmx185mm (
0.
3
)
7.5mm (
L2
L3
Current
Transformers
ALTERNATOR
MAINS
Generator
Contactor
Mains
Contactor
Electrical Interlock
29 34 33
25 26 27
32
31
36
35
Generator Loading
Relay
38
40 39
Mains Loading
Relay
42
43
44 45
18
19
FCC68 - 8 Way
1
20 21
22
24
9 10 11 12 13 14 15 16 17
23
30
4
Oil
Sender
810
Configuration
Temp
Sender
MPU
NOTE:When connected to a
completed Panel / Gen-set
Real-time diagnostic display
is available
5
6
7
8
9
Configurable inputs
To governor
To AVR