POWER SYSTEMS

TABLE DES MODIFICATIONS / MODIFICATIONS TABLE


REV
A

ETABLI

VERIFIE

APPROUVE

ESTABLISHED

CHECKED

APPROVED

MURUGIAH

DHS

VIKAS

HINLJR00BUA-ED00002/Rev A

DATE
19.7.10

MODIFICATIONS
FIRST ISSUE.

STAT.
GFE

Page 2

abcd

POWER SYSTEMS

CONTENTS
1

PURPOSE

REFERENCE DOCUMENT

2.1 REFERENCE STANDARDS

BASIC DATA

3.1 ENVIRONMENTAL CONDITIONS AND DESIGN CRITERIA


3.2 ELECTRICAL NETWORK DATA

5
5

TECHNICAL SPECIFICATION:

4.1 TYPE OF CABLE


4.2 INSTALLATION METHOD

5
6

CABLE SIZING METHOD

5.1 CURRENT CARRYING CAPACITY CRITERIA


5.2 SHORT CIRCUIT CRITERIA
5.3 VOLTAGE DROP CRITERIA

6
8
9

CIRCUIT BREAKER SELECTION

CALCULATION SHEET

ANNEXURE-I : CURRENT RATING, RESISTANCE & REACTANCE

10

ANNEUXRE-II : TEMPERATURE CORRECTION FACTOR

11

10

ANNEUXRE-III : GROUP RATING FACTORS

12

ATTACHMENT 1:

CALCULATION SHEETS (220V DC SYSTEM)

ATTACHMENT 2:

CALCULATION SHEETS (48V DC SYSTEM)

HINLJR00BUA-ED00002/Rev A

Page 3

abcd

POWER SYSTEMS

PURPOSE
The purpose of the document is to define the basis of calculation of 220V & 48V DC Power Cable
Sizes for all the DC Distribution boards.

2.1

REFERENCE DOCUMENT

HINLJR20BUA-FD00001: 220 V DC System Single Line Diagram

HINLJR20BUA-FE00001: 220 V DC System Design memorandum

HINLJR20BUA-ED00001: 220 V DC System Power Balance

HINLJR20BUD-FD00001: 48 V DC System Single Line Diagram

HINLJR20BUD-FE00001: 48 V DC System Design memorandum

HINLJR20BUD-ED00001: 48 V DC System Power Balance

REFERENCE STANDARDS

IEC 60364-4-43

Electrical Instalations of Building Protection Against Over Current

IEC 60364-5-52

Electrical Instalations of Building Selection and Erection of


Electrical Equipment Wiring System

IEC 60364-5-54

Selection and Erection of Electrical Equipment Earthing


Arrangements, Protective Conductors and Protective Bonding
Conductors

IEEE Std 241

Recommended Practice For Electrical Power System In Commercial


Building

IS 1554 - Part 1

PVC insulated (heavy duty) electric cables specification: For working


voltages upto and including 1 100 V

IS 7098 - Part 1

Cross-Linked Polyetelene Insulated thermoplastic sheathed cables


specification: For working voltages upto and including 1 100 V

HINLJR00BUA-ED00002/Rev A

Page 4

abcd

POWER SYSTEMS

3
3.1

BASIC DATA
ENVIRONMENTAL CONDITIONS AND DESIGN CRITERIA
In particular, the electrical and control equipment will be designed for the following ambient
conditions:

3.2

Pollution level

Level III as per IS

Altitude

<1000 Meter

Location of devices

Outdoor

Maximum ambient temperature

42 C

Minimum ambient temperature

12.5 C

Design ambient temperature for Electrical equipment

50 C

Relative humidity

40% approx at 42oC

Maximum humidity

85%

Seismic zone

Zone II as per IS 1893

ELECTRICAL NETWORK DATA


The equipment supplied shall be designed to operate under the following electrical environment:

4
4.1

Rated Voltage

220 V & 48V DC

Variation Range

10 %

Earthing Mode

Un-earthed

TECHNICAL SPECIFICATION:
TYPE OF CABLE
Insulation ..........................................................................XLPE
Core

..........................................................................Single / Multi core

Voltage grade .....................................................................1100V


Maximum normal operating temperature............................900C
Maximum short time operating temperature.......................2500C for 1sec.
Conductor Material .............................................................Al / Cu
HINLJR00BUA-ED00002/Rev A

Page 5

abcd

POWER SYSTEMS

4.2

INSTALLATION METHOD
Cable

..........................................................................Perforated Tray / Ladder Type

Single core cables ...............................................................Single layer laying with trefoil formation


[Refer Doc. HINLJR000BB FE00001]
Multi core cables.................................................................Multi layer laying (without exceeding the
90% height of cable tray) and Cable
surfaces are touching [Refer Doc.
HINLJR000BB FE00001]
Buried cables ......................................................................Multi layer laying and Cable surfaces are
touching
5

CABLE SIZING METHOD


Cable sizing and selection is based on the following criteria:-

5.1

Current carrying capacity under normal operating condition

Current carrying capacity under short-circuit condition and

Voltage drop

CURRENT CARRYING CAPACITY CRITERIA


The current carrying capacity of a cable de-rates due to
a)
b)

ambient temperature
accumulation of cable/installation of cable)

Such adaptation is done considering de-rating factors for ambient temperature and cable installation
as described hereunder:Iz
(Rated Capacity of cable)

In / Kd
(Required Capacity of Feeder)

Where
Iz

rated current of cable (Annexure-I)

Kd

cable current carrying capacity de-rating factor

Further Kd is calculated as
Kd

HINLJR00BUA-ED00002/Rev A

K x K2 x Kg
Page 6

abcd

POWER SYSTEMS

Where,
K

= correction factor for ambient temperature (Annexure-III)

K2

Sun exposition factor which is

For cable screened from sun rays

0.8

For cable exposed to air with black sheath

0.9

For cable exposed to air with light colour sheath

Cable installation de-rating factor (Annexure-IV)

Kg

The maximum permanent current (In) of a feeder is given as


In

Sn
U

Where Sn

Nominal apparent power of the feeder

System voltage (220V for 220V DC System)

Size of the cable selected shall ensure

I d Iz

Where Iz is the rated current carrying capacity of the cable (Refer Annexure-I).

5.1.1 AMBIENT TEMPERATURE CORRECTION FACTOR


Temperature correction factor for an ambient temperature equal to 500 C, will be
Kt

0.9 (Annexure-III)

5.1.2 SUN EXPOSITION FACTOR


Ks

Sun exposition factor which is

For cable screened from sun rays

0.8

For cable exposed to air with black sheath

0.9

For cable exposed to air with light colour sheath

HINLJR00BUA-ED00002/Rev A

Page 7

abcd

POWER SYSTEMS

5.1.3 GROUPING FACTOR


Multi core cables
As per the installation method adopted for multi core cables as per IEC 60364-5-52 (Annexure-IV),
the installation group rating factor shall be suitably selected.
Perforated trays, Laying configuration of 6 cables and 3 trays, Kg = 0.71
5.2

SHORT CIRCUIT CRITERIA


The minimum cable cross-sectional area S is selected such that the maximum thermal stress in the
cable during short circuit does not reach the maximum permissible limit. The selection criteria is
given as (IEC 60364-4-43)
K2 S2 I t
Where

i t

:-

Energy let-through of the associated circuit breaker (As per


breaker manufacturer data)

:=

Cable constant which is given as

Qc ( + 20)

ln (1 +

20

( f i )
( + i )

(IS 3043)

Where
Qc

Volumetric heat capacity of the conductor material in J/oC mm3


(See Annexure IV)

20

= Electrical resistivity of conducting material at 20oC in . mm. (See Annexure IV)

= Reciprocal of temperature coefficient of resistivity of the conducting material at


0oC
= Initial temperature of conductor in oC

= Final temperature of conductor in oC

Thus the value of cable constant


For XLPE copper cable, K = 143
For XLPE aluminium cable K =94

HINLJR00BUA-ED00002/Rev A

Page 8

abcd

POWER SYSTEMS

5.3

VOLTAGE DROP CRITERIA


The minimum cable cross-sectional area, S (in mm2) is calculated in such a way that the voltage drop
from the station service board / unit auxiliary board up to the consumer is less than or equal to 4%.
(IEC 60364-5-52)
Voltage drop
V

(2 x In x R x L) / 1000

Resistance of the cable in / Km, (Annexure-II)

In

Current in the feeder current A,

Length of cable in meter.

Where R

CIRCUIT BREAKER SELECTION


Circuit breakers rating is selected as per the connected load (i.e. maximum current in the feeder, In)
so as to confirm that the rated current of the circuit breaker is greater than the maximum permanent
load in the feeder.

1.

Thermal setting (Ith) of the circuit breaker/ current rating of CB is greater than or equal to
connected load, In.

2.

Icu with or without association with upstream breaker Icu Upstream Board.

CALCULATION SHEET
Please refer to Attachment 1.

HINLJR00BUA-ED00002/Rev A

Page 9

POWER SYSTEMS

abcd

ANNEXURE-I : CURRENT RATING, RESISTANCE & REACTANCE

HINLJR00BUA-ED00002/Rev A

Page 10

POWER SYSTEMS

abcd

ANNEUXRE-II : TEMPERATURE CORRECTION FACTOR

HINLJR00BUA-ED00002/Rev A

Page 11

POWER SYSTEMS

10

abcd

ANNEUXRE-III : GROUP RATING FACTORS

HINLJR00BUA-ED00002/Rev A

Page 12

POWER SYSTEMS

HINLJR00BUA-ED00002/Rev A

abcd

Page 13

ATTACHMENT 1 : CALCULATION SHEETS (220V DC POWER CABLES)

Sl. No. Rev

FROM EQUIPMENT

TO EQUIPMENT

DESIGNATION

DESIGNATION

LOAD
Consumption/O CURRENT IN
Voltage
utput Power
Amp
[V]
[W]
(In)

CABLE
TYPE

CABLE
RATED
LENGTH
No. OF SELECTED
CAPACITY RESISTANCE
RUNS CABLE SIZE
(m)
(/Km)
OF CABLE
mm2

(Iz)

Kt

Ks

Kg

REQUIRED PROTECTIVE
DEVICE
CAPACITY OF
Kd = (Kt x
FEEDER (A) RATING (A)
Ks x Kg)
(In / Kd)
(Ir)

K2S2
(kA2s)

LETPERMISSIBLE
THROUGH
VOLTAGE
(kA2s)
DROP (Vr)

RUNNING
VOLTAGE
DROP (Vpr)

BATTERY BANK 1

Positive Terminal

BATTERY TERMINAL BOX 1

220

300

XLPE-AL

1Cx500

693

0.082

18.062

0.9

0.78

0.702

427.35

400

2209

2.1

0.89

Negative Terminal

BATTERY TERMINAL BOX 1

220

300

XLPE-AL

1Cx500

693

0.082

18.062

0.9

0.78

0.702

427.35

400

2209

2.1

0.89

TERMINAL BOX 1

BATTERY CHARGER 1

220

300

XLPE-AL

1Cx500

1386

0.082

59.6328

0.9

0.78

0.702

427.35

400

2209

2.1

1.6

1.47

BATTERY CHARGER 1

220V MAIN DISTRIBUTION BOARD

220

300

XLPE-AL

1Cx500

1386

0.082

23.2758

0.9

0.78

0.702

427.35

400

2209

2.1

0.7

0.57

Positive Terminal

BATTERY TERMINAL BOX 2

220

300

XLPE-AL

1Cx500

693

0.082

18

0.9

0.71

0.639

469.48

400

2209

2.1

0.89

Negative Terminal

BATTERY TERMINAL BOX 2

220

300

XLPE-AL

1Cx500

693

0.082

18

0.9

0.71

0.639

469.48

400

2209

2.1

0.89

TERMINAL BOX 2

BATTERY CHARGER 2

220

300

XLPE-AL

1Cx500

1386

0.082

60

0.9

0.71

0.639

469.48

400

2209

2.1

1.6

1.47

BATTERY CHARGER 2

220V MAIN DISTRIBUTION BOARD

220

300

XLPE-AL

1Cx500

1386

0.082

23

0.9

0.71

0.639

469.48

400

2209

2.1

0.7

0.57

BATTERY BANK 2

DCDB Load Bus-1

DCDB Load Bus-1

EXCITATION PANEL UNIT 1

220

1200

5.45

XLPE-Cu

2Cx6

64

3.94

38

0.9

0.71

0.639

8.54

10

0.74

4.5

1.62

DCDB Load Bus-1

LUBRICATING SYSTEM STARTER UNIT 1

220

18500

84.09

XLPE-AL

2Cx95

542

0.409

111

0.9

0.71

0.639

131.60

125

79.74

0.7

4.5

3.81

LUBRICATING SYSTEM STARTER UNIT 1

LUBRICATING SYSTEM PUMP UNIT 1

220

18500

84.09

XLPE-AL

2Cx95

542

0.409

20

0.9

0.71

0.639

131.60

125

79.74

0.7

0.69

DCDB Load Bus-1

HP OIL INJECTION STARTER UNIT 1

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

111

0.9

0.71

0.639

53.35

63

43.30

4.5

4.27

HP OIL INJECTION STARTER UNIT 1

HP OIL INJECTION PUMP UNIT 1

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

20

0.9

0.71

0.639

53.35

63

43.30

0.77

DCDB Load Bus-1

GENERATOR BRAKING CUBICLE UNIT 1

220

200

0.91

XLPE-Cu

2Cx2.5

32

9.5

111

0.9

0.71

0.639

1.42

0.13

4.5

1.92

DCDB Load Bus-1

GENERATOR FIELD FLASHING UNIT 1

220

22000

100.00

XLPE-AL

2Cx95

271

0.409

38

0.9

0.71

0.639

156.49

200

79.74

0.85

4.5

3.08

DCDB Load Bus-1

MAIN GOVERNOR PANEL UNIT 1

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

64

0.9

0.71

0.639

2.13

0.13

4.5

1.65

DCDB Load Bus-1

LOCAL GOVERNOR PANEL UNIT 1

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

64

0.9

0.71

0.639

2.13

0.13

4.5

1.65

10

DCDB Load Bus-1

CONTROL AND PROTECTION BOARD UNIT 1

220

600

2.73

XLPE-Cu

2Cx6

64

3.94

64

0.9

0.71

0.639

4.27

0.74

4.5

1.37

11

DCDB Load Bus-1

GSU TRANSFORMER UNIT 1

220

55.5

0.25

XLPE-Cu

2Cx2.5

32

9.5

87

0.9

0.71

0.639

0.39

0.13

4.5

0.42

12

DCDB Load Bus-1

GSU TRANSFORMER UNIT 1 (Standby)

220

0.00

XLPE-AL

2Cx35

145

1.11

87

0.9

0.71

0.639

0.00

10.82

4.5

0.00

13

DCDB Load Bus-1

UNIT AUXILIARY BOARD 1

220

150

0.68

XLPE-Cu

2Cx2.5

32

9.5

44

0.9

0.71

0.639

1.07

0.13

4.5

0.57

14

DCDB Load Bus-1

EXCITATION PANEL UNIT 2

220

1200

5.45

XLPE-Cu

2Cx6

64

3.94

41

0.9

0.71

0.639

8.54

10

0.74

4.5

1.76

15

DCDB Load Bus-1

LUBRICATING SYSTEM STARTER UNIT 2

220

18500

84.09

XLPE-AL

2Cx70

442

0.565

89

0.9

0.71

0.639

131.60

125

43.30

0.7

4.5

4.25

16

LUBRICATING SYSTEM STARTER UNIT 2

LUBRICATING SYSTEM PUMP UNIT 2

220

18500

84.09

XLPE-AL

2Cx70

442

0.565

20

0.9

0.71

0.639

131.60

125

43.30

0.7

0.95

17

DCDB Load Bus-1

HP OIL INJECTION STARTER UNIT 2

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

89

0.9

0.71

0.639

53.35

63

43.30

4.5

3.44

18

HP OIL INJECTION STARTER UNIT 2

HP OIL INJECTION PUMP UNIT 2

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

20

0.9

0.71

0.639

53.35

63

43.30

0.77

19

DCDB Load Bus-1

GENERATOR BRAKING CUBICLE UNIT 2

220

200

0.91

XLPE-Cu

2Cx2.5

32

9.5

89

0.9

0.71

0.639

1.42

0.13

4.5

1.54

20

DCDB Load Bus-1

GENERATOR FIELD FLASHING UNIT 2

220

22000

100.00

XLPE-AL

2Cx95

271

0.409

41

0.9

0.71

0.639

156.49

200

79.74

0.85

4.5

3.36

21

DCDB Load Bus-1

MAIN GOVERNOR PANEL UNIT 2

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

55

0.9

0.71

0.639

2.13

0.13

4.5

1.42

22

DCDB Load Bus-1

LOCAL GOVERNOR PANEL UNIT 2

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

55

0.9

0.71

0.639

2.13

0.13

4.5

1.42

23

DCDB Load Bus-1

CONTROL AND PROTECTION BOARD UNIT 2

220

600

2.73

XLPE-AL

2Cx16

88

2.44

55

0.9

0.71

0.639

4.27

2.26

4.5

0.73

24

DCDB Load Bus-1

GSU TRANSFORMER UNIT 2

220

55.5

0.25

XLPE-Cu

2Cx2.5

32

9.5

80

0.9

0.71

0.639

0.39

0.13

4.5

0.38

25

DCDB Load Bus-1

GSU TRANSFORMER UNIT 2 (Standby)

220

0.00

XLPE-AL

2Cx25

117

1.53

80

0.9

0.71

0.639

0.00

5.52

4.5

0.00

26

DCDB Load Bus-1

UNIT AUXILIARY BOARD 2

220

150

0.68

XLPE-Cu

2Cx2.5

32

9.5

36

0.9

0.71

0.639

1.07

0.13

4.5

0.47

27

DCDB Load Bus-1

EXCITATION PANEL UNIT 3

220

1200

5.45

XLPE-Cu

2Cx4

51

5.9

47

0.9

0.71

0.639

8.54

10

0.33

4.5

3.04

28

DCDB Load Bus-1

LUBRICATING SYSTEM STARTER UNIT 3

220

18500

84.09

XLPE-AL

2Cx70

442

0.565

71

0.9

0.71

0.639

131.60

125

43.30

0.7

4.5

3.39

29

LUBRICATING SYSTEM STARTER UNIT 3

LUBRICATING SYSTEM PUMP UNIT 3

220

18500

84.09

XLPE-AL

2Cx70

442

0.565

20

0.9

0.71

0.639

131.60

125

43.30

0.7

0.95

30

DCDB Load Bus-1

HP OIL INJECTION STARTER UNIT 3

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

71

0.9

0.71

0.639

53.35

63

43.30

4.5

2.74

31

HP OIL INJECTION STARTER UNIT 3

HP OIL INJECTION PUMP UNIT 3

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

20

0.9

0.71

0.639

53.35

63

43.30

0.77

32

DCDB Load Bus-1

GENERATOR BRAKING CUBICLE UNIT 3

220

200

0.91

XLPE-Cu

2Cx2.5

32

9.5

71

0.9

0.71

0.639

1.42

0.13

4.5

1.23

33

DCDB Load Bus-1

GENERATOR FIELD FLASHING UNIT 3

220

22000

100.00

XLPE-AL

2Cx95

271

0.409

47

0.9

0.71

0.639

156.49

200

79.74

0.85

4.5

3.87

34

DCDB Load Bus-1

MAIN GOVERNOR PANEL UNIT 3

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

46

0.9

0.71

0.639

2.13

0.13

4.5

1.18

35

DCDB Load Bus-1

LOCAL GOVERNOR PANEL UNIT 3

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

46

0.9

0.71

0.639

2.13

0.13

4.5

1.18

36

DCDB Load Bus-1

CONTROL AND PROTECTION BOARD UNIT 3

220

600

2.73

XLPE-AL

2Cx16

88

2.44

46

0.9

0.71

0.639

4.27

2.26

4.5

0.61

37

DCDB Load Bus-1

GSU TRANSFORMER UNIT 3

220

55.5

0.25

XLPE-Cu

2Cx2.5

32

9.5

102

0.9

0.71

0.639

0.39

0.13

4.5

0.49

38

DCDB Load Bus-1

GSU TRANSFORMER UNIT 3 (Standby)

220

0.00

XLPE-AL

2Cx25

117

1.53

102

0.9

0.71

0.639

0.00

5.52

4.5

0.00

39

DCDB Load Bus-1

UNIT AUXILIARY BOARD 3

220

150

0.68

XLPE-Cu

2Cx2.5

32

9.5

30

0.9

0.71

0.639

1.07

0.13

4.5

0.39

40

DCDB Load Bus-1

SWITCHYARD SUB DISTRIBUTION BOARD LOAD BUS 1

220

5820

26.45

XLPE-AL

2Cx95A

542

0.41

329

0.9

0.71

0.639

41.40

100

79.74

0.5

4.5

3.57

41

DCDB Load Bus-1

STATION AUXILIARY CONTROL AND PROTECTION BOARD

220

260

1.18

XLPE-Cu

2Cx2.5

32

9.5

41

0.9

0.71

0.639

1.85

0.13

4.5

0.91
sheet 1 of 4

ATTACHMENT 1 : CALCULATION SHEETS (220V DC POWER CABLES)

Sl. No. Rev

FROM EQUIPMENT

TO EQUIPMENT

DESIGNATION

DESIGNATION

LOAD
Consumption/O CURRENT IN
Voltage
utput Power
Amp
[V]
[W]
(In)

CABLE
TYPE

CABLE
RATED
LENGTH
No. OF SELECTED
CAPACITY RESISTANCE
RUNS CABLE SIZE
(m)
(/Km)
OF CABLE
mm2

(Iz)

Kt

Ks

Kg

REQUIRED PROTECTIVE
DEVICE
CAPACITY OF
Kd = (Kt x
FEEDER (A) RATING (A)
Ks x Kg)
(In / Kd)
(Ir)

K2S2
(kA2s)

LETPERMISSIBLE
THROUGH
VOLTAGE
(kA2s)
DROP (Vr)

RUNNING
VOLTAGE
DROP (Vpr)

42

DCDB Load Bus-1

CONTROL AND PROTECTION BOARD UNIT 4

220

1400

6.36

XLPE-Cu

2Cx6

64

3.94

67

0.9

0.71

0.639

9.96

16

0.74

0.09

4.5

3.36

43

DCDB Load Bus-1

CONTROL AND PROTECTION BOARD UNIT 5

220

1400

6.36

XLPE-Cu

2Cx6

64

3.94

89

0.9

0.71

0.639

9.96

16

0.74

0.09

4.5

4.44

44

DCDB Load Bus-1

CONTROL AND PROTECTION BOARD UNIT 6

220

1400

6.36

XLPE-AL

2Cx16

88

2.44

110

0.9

0.71

0.639

9.96

16

2.26

0.09

4.5

3.42

45

DCDB Load Bus-1

INTAKE GATE / DAM CUBICLE

220

100

0.45

XLPE-Cu

2Cx2.5

32

9.5

56

0.9

0.71

0.639

0.71

0.13

4.5

0.49

46

DCDB Load Bus-1

MOSAIC MIMIC BOARD

220

125

0.57

XLPE-Cu

2Cx2.5

32

9.5

65

0.9

0.71

0.639

0.89

0.13

4.5

0.70

47

DCDB Load Bus-1

RESERVE BOARD - 1

220

500

2.27

XLPE-Cu

2Cx2.5

32

9.5

66

0.9

0.71

0.639

3.56

0.13

4.5

2.85

48

DCDB Load Bus-1

RESERVE BOARD - 2

220

500

2.27

XLPE-Cu

2Cx2.5

32

9.5

45

0.9

0.71

0.639

3.56

0.13

4.5

1.94

49

DCDB Load Bus-1

RESERVE BOARD - 3

220

500

2.27

XLPE-Cu

2Cx2.5

32

9.5

77

0.9

0.71

0.639

3.56

0.13

4.5

3.31

50

DCDB Load Bus-1

STATION AUXILIARY BOARD 1

220

150

0.68

XLPE-Cu

2Cx2.5

32

9.5

65

0.9

0.71

0.639

1.07

0.13

4.5

0.85

51

DCDB Load Bus-1

STATION AUXILIARY BOARD 2

220

150

0.68

XLPE-Cu

2Cx2.5

32

9.5

55

0.9

0.71

0.639

1.07

0.13

4.5

0.71

52

DCDB Load Bus-1

11kV GCB SWITCH BOARD FOR UNIT - 1

220

600

2.73

XLPE-AL

2Cx16

88

2.44

48

0.9

0.71

0.639

4.27

2.26

4.5

0.64

53

DCDB Load Bus-1

11kV GCB SWITCH BOARD FOR UNIT - 3

220

600

2.73

XLPE-AL

2Cx16

88

2.44

34

0.9

0.71

0.639

4.27

10

2.26

4.5

0.45

54

DCDB Load Bus-1

11kV GCB SWITCH BOARD FOR UNIT - 1

220

600

2.73

XLPE-AL

2Cx16

88

2.44

48

0.9

0.71

0.639

4.27

10

2.26

4.5

0.64

55

DCDB Load Bus-1

11kV GCB SWITCH BOARD FOR UNIT - 3

220

600

2.73

XLPE-AL

2Cx16

88

2.44

34

0.9

0.71

0.639

4.27

10

2.26

4.5

0.45

56

DCDB Load Bus-1

11kV LAVT PANEL FOR UNIT - 6

220

600

2.73

XLPE-Cu

2Cx4

51

5.9

117

0.9

0.71

0.639

4.27

10

0.33

4.5

3.76

57

DCDB Load Bus-1

GSU RTCC Panel UNIT - 1

220

200

0.91

XLPE-Cu

2Cx2.5

32

9.5

50

0.9

0.71

0.639

1.42

10

0.13

4.5

0.86

3.55

DCDB Load Bus-2

DCDB Load Bus-2

EXCITATION PANEL UNIT 4

220

1200

5.45

XLPE-Cu

2Cx4

51

5.9

55

0.9

0.71

0.639

8.54

10

0.33

4.5

DCDB Load Bus-2

LUBRICATING SYSTEM STARTER UNIT 4

220

18500

84.09

XLPE-AL

2Cx70

442

0.565

80

0.9

0.71

0.639

131.60

125

43.30

0.7

4.5

3.82

LUBRICATING SYSTEM STARTER UNIT 4

LUBRICATING SYSTEM PUMP UNIT 4

220

18500

84.09

XLPE-AL

2Cx70

442

0.565

20

0.9

0.71

0.639

131.60

125

43.30

0.7

0.95

DCDB Load Bus-2

HP OIL INJECTION STARTER UNIT 4

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

80

0.9

0.71

0.639

53.35

63

43.30

4.5

3.09

HP OIL INJECTION STARTER UNIT 4

HP OIL INJECTION PUMP UNIT 4

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

20

0.9

0.71

0.639

53.35

63

43.30

0.77

DCDB Load Bus-2

GENERATOR BRAKING CUBICLE UNIT 4

220

200

0.91

XLPE-Cu

2Cx2.5

32

9.5

80

0.9

0.71

0.639

1.42

0.13

4.5

1.39

DCDB Load Bus-2

GENERATOR FIELD FLASHING UNIT 4

220

22000

100.00

XLPE-AL

2Cx95

542

0.409

55

0.9

0.71

0.639

156.49

200

79.74

0.85

4.5

2.26

DCDB Load Bus-2

MAIN GOVERNOR PANEL UNIT 4

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

69

0.9

0.71

0.639

2.13

0.13

4.5

1.78

DCDB Load Bus-2

LOCAL GOVERNOR PANEL UNIT 4

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

69

0.9

0.71

0.639

2.13

0.13

4.5

1.78

10

DCDB Load Bus-2

CONTROL AND PROTECTION BOARD UNIT 4

220

600

2.73

XLPE-Cu

2Cx6

64

3.94

67

0.9

0.71

0.639

4.27

0.74

4.5

1.44

11

DCDB Load Bus-2

GSU TRANSFORMER UNIT 4

220

55.5

0.25

XLPE-Cu

2Cx2.5

32

9.5

124

0.9

0.71

0.639

0.39

0.13

4.5

0.59

12

DCDB Load Bus-2

GSU TRANSFORMER UNIT 4 (Standby)

220

0.00

XLPE-AL

2Cx25

117

1.53

124

0.9

0.71

0.639

0.00

5.52

4.5

0.00

13

DCDB Load Bus-2

UNIT AUXILIARY BOARD 4

220

150

0.68

XLPE-Cu

2Cx2.5

32

9.5

40

0.9

0.71

0.639

1.07

0.13

4.5

0.51

14

DCDB Load Bus-2

EXCITATION PANEL UNIT 5

220

1200

5.45

XLPE-Cu

2Cx6

64

3.94

94

0.9

0.71

0.639

8.54

10

0.74

4.5

4.03

15

DCDB Load Bus-2

LUBRICATING SYSTEM STARTER UNIT 5

220

18500

84.09

XLPE-AL

2Cx95

542

0.409

101

0.9

0.71

0.639

131.60

125

79.74

0.7

4.5

3.46

16

LUBRICATING SYSTEM STARTER UNIT 5

LUBRICATING SYSTEM PUMP UNIT 5

220

18500

84.09

XLPE-AL

2Cx70

442

0.565

20

0.9

0.71

0.639

131.60

125

43.30

0.7

0.95

17

DCDB Load Bus-2

HP OIL INJECTION STARTER UNIT 5

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

101

0.9

0.71

0.639

53.35

63

43.30

4.5

3.88

18

HP OIL INJECTION STARTER UNIT 5

HP OIL INJECTION PUMP UNIT 5

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

20

0.9

0.71

0.639

53.35

63

43.30

0.77

19

DCDB Load Bus-2

GENERATOR BRAKING CUBICLE UNIT 5

220

200

0.91

XLPE-Cu

2Cx2.5

32

9.5

101

0.9

0.71

0.639

1.42

0.13

4.5

1.74

20

DCDB Load Bus-2

GENERATOR FIELD FLASHING UNIT 5

220

22000

100.00

XLPE-AL

2Cx95

542

0.409

94

0.9

0.71

0.639

156.49

200

79.74

0.85

4.5

3.83

21

DCDB Load Bus-2

MAIN GOVERNOR PANEL UNIT 5

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

90

0.9

0.71

0.639

2.13

0.13

4.5

2.34

22

DCDB Load Bus-2

LOCAL GOVERNOR PANEL UNIT 5

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

90

0.9

0.71

0.639

2.13

0.13

4.5

2.34

23

DCDB Load Bus-2

CONTROL AND PROTECTION BOARD UNIT 5

220

600

2.73

XLPE-Cu

2Cx4

51

5.9

89

0.9

0.71

0.639

4.27

0.33

4.5

2.85

24

DCDB Load Bus-2

GSU TRANSFORMER UNIT 5

220

55.5

0.25

XLPE-Cu

2Cx2.5

32

9.5

145

0.9

0.71

0.639

0.39

0.13

4.5

0.70

25

DCDB Load Bus-2

GSU TRANSFORMER UNIT 5 (Standby)

220

0.00

XLPE-AL

2Cx25

117

1.53

145

0.9

0.71

0.639

0.00

5.52

4.5

0.00

26

DCDB Load Bus-2

UNIT AUXILIARY BOARD 5

220

150

0.68

XLPE-Cu

2Cx2.5

32

9.5

75

0.9

0.71

0.639

1.07

0.13

4.5

0.97

27

DCDB Load Bus-2

EXCITATION PANEL UNIT 6

220

1200

5.45

XLPE-Cu

2Cx6

64

3.94

97

0.9

0.71

0.639

8.54

10

0.74

4.5

4.17

28

DCDB Load Bus-2

LUBRICATING SYSTEM STARTER UNIT 6

220

18500

84.09

XLPE-AL

2Cx95

542

0.409

123

0.9

0.71

0.639

131.60

125

79.74

0.7

4.5

4.24

29

LUBRICATING SYSTEM STARTER UNIT 6

LUBRICATING SYSTEM PUMP UNIT 6

220

18500

84.09

XLPE-AL

2Cx70

442

0.565

20

0.9

0.71

0.639

131.60

125

43.30

0.7

0.95

30

DCDB Load Bus-2

HP OIL INJECTION STARTER UNIT 6

220

7500

34.09

XLPE-AL

2Cx95

271

0.409

123

0.9

0.71

0.639

53.35

63

79.74

4.5

3.44

31

HP OIL INJECTION STARTER UNIT 6

HP OIL INJECTION PUMP UNIT 6

220

7500

34.09

XLPE-AL

2Cx70

221

0.565

20

0.9

0.71

0.639

53.35

63

43.30

0.77

32

DCDB Load Bus-2

GENERATOR BRAKING CUBICLE UNIT 6

220

200

0.91

XLPE-Cu

2Cx2.5

32

9.5

123

0.9

0.71

0.639

1.42

0.13

4.5

2.13

33

DCDB Load Bus-2

GENERATOR FIELD FLASHING UNIT 6

220

22000

100.00

XLPE-AL

2Cx95

542

0.409

97

0.9

0.71

0.639

156.49

200

79.74

0.85

4.5

3.97

34

DCDB Load Bus-2

MAIN GOVERNOR PANEL UNIT 6

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

112

0.9

0.71

0.639

2.13

0.13

4.5

2.90

35

DCDB Load Bus-2

LOCAL GOVERNOR PANEL UNIT 6

220

300

1.36

XLPE-Cu

2Cx2.5

32

9.5

112

0.9

0.71

0.639

2.13

0.13

4.5

2.90

36

DCDB Load Bus-2

CONTROL AND PROTECTION BOARD UNIT 6

220

600

2.73

XLPE-Cu

2Cx4

51

5.9

110

0.9

0.71

0.639

4.27

0.33

4.5

3.54
sheet 2 of 4

ATTACHMENT 1 : CALCULATION SHEETS (220V DC POWER CABLES)

Sl. No. Rev

FROM EQUIPMENT

TO EQUIPMENT

DESIGNATION

DESIGNATION

LOAD
Consumption/O CURRENT IN
Voltage
utput Power
Amp
[V]
[W]
(In)

CABLE
TYPE

CABLE
RATED
LENGTH
No. OF SELECTED
CAPACITY RESISTANCE
RUNS CABLE SIZE
(m)
(/Km)
OF CABLE
mm2

(Iz)

Kt

Ks

Kg

REQUIRED PROTECTIVE
DEVICE
CAPACITY OF
Kd = (Kt x
FEEDER (A) RATING (A)
Ks x Kg)
(In / Kd)
(Ir)

K2S2
(kA2s)

LETPERMISSIBLE
THROUGH
VOLTAGE
(kA2s)
DROP (Vr)

RUNNING
VOLTAGE
DROP (Vpr)

37

DCDB Load Bus-2

GSU TRANSFORMER UNIT 6

220

55.5

0.25

XLPE-Cu

2Cx2.5

32

9.5

166

0.9

0.71

0.639

0.39

0.13

4.5

0.80

38

DCDB Load Bus-2

GSU TRANSFORMER UNIT 6 (Standby)

220

0.00

XLPE-AL

2Cx35

145

1.11

166

0.9

0.71

0.639

0.00

10.82

4.5

0.00

39

DCDB Load Bus-2

UNIT AUXILIARY BOARD 6

220

150

0.68

XLPE-Cu

2Cx2.5

32

9.5

83

0.9

0.71

0.639

1.07

0.13

4.5

1.07

40

DCDB Load Bus-2

SWITCHYARD SUB DISTRIBUTION BOARD LOAD BUS 2

220

5820

26.45

XLPE-AL

2Cx95A

542

0.41

329

0.9

0.71

0.639

41.40

100

79.74

0.5

4.5

3.57

41

DCDB Load Bus-2

STATION AUXILIARY CONTROL AND PROTECTION BOARD

220

260

1.18

XLPE-Cu

2Cx2.5

32

9.5

41

0.9

0.71

0.639

1.85

0.13

4.5

0.91

42

DCDB Load Bus-2

CONTROL AND PROTECTION BOARD UNIT 1

220

1400

6.36

XLPE-Cu

2Cx6

64

3.94

64

0.9

0.71

0.639

9.96

16

0.74

0.09

4.5

3.20

43

DCDB Load Bus-2

CONTROL AND PROTECTION BOARD UNIT 2

220

1400

6.36

XLPE-Cu

2Cx4

51

5.9

55

0.9

0.71

0.639

9.96

16

0.33

0.09

4.5

4.12

44

DCDB Load Bus-2

CONTROL AND PROTECTION BOARD UNIT 3

220

1400

6.36

XLPE-Cu

2Cx4

51

5.9

46

0.9

0.71

0.639

9.96

16

0.33

0.09

4.5

3.42

45

DCDB Load Bus-2

INTAKE GATE / DAM CUBICLE

220

100

0.45

XLPE-Cu

2Cx2.5

32

9.5

56

0.9

0.71

0.639

0.71

0.13

4.5

0.49

46

DCDB Load Bus-2

MOSAIC MIMIC BOARD

220

125

0.57

XLPE-Cu

2Cx2.5

32

9.5

65

0.9

0.71

0.639

0.89

0.13

4.5

0.70

47

DCDB Load Bus-2

11kV GCB SWITCH BOARD FOR UNIT - 5

220

600

2.73

XLPE-AL

2Cx16

88

2.44

55

0.9

0.71

0.639

4.27

10

2.26

4.5

0.73

48

DCDB Load Bus-2

11kV GCB SWITCH BOARD FOR UNIT - 5

220

600

2.73

XLPE-AL

2Cx16

88

2.44

55

0.9

0.71

0.639

4.27

10

2.26

4.5

0.73

49

DCDB Load Bus-2

11kV LAVT PANEL FOR UNIT - 2

220

600

2.73

XLPE-Cu

2Cx6

64

3.94

70

0.9

0.71

0.639

4.27

10

0.74

4.5

1.50

50

DCDB Load Bus-2

11kV LAVT PANEL FOR UNIT - 4

220

600

2.73

XLPE-Cu

2Cx6

64

3.94

74

0.9

0.71

0.639

4.27

10

0.74

4.5

1.59

51

DCDB Load Bus-2

GSU RTCC Panel UNIT - 1

220

200

0.91

XLPE-Cu

2Cx2.5

32

9.5

50

0.9

0.71

0.639

1.42

10

0.13

4.5

0.86

SWYD DCDB

DCDB bus-1

Unit-1 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

119

0.9

0.71

0.639

1.56

0.13

4.5

2.25

Unit-2 Bay Marshalling Kiosk

Unit-1 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

119

0.9

0.71

0.639

1.56

0.13

4.5

2.25

Unit-1 Bay Marshalling Kiosk

Unit-1 circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

Unit-1 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

Unit-1 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

DCDB bus-2

Unit-2 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

119

0.9

0.71

0.639

1.56

0.13

4.5

2.25

Unit-1 Bay Marshalling Kiosk

Unit-2 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

119

0.9

0.71

0.639

1.56

0.13

4.5

2.25

Unit-2 Bay Marshalling Kiosk

Unit-2 circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

18

0.9

0.71

0.639

1.56

0.13

4.5

0.34

Unit-2 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

10

Unit-2 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

11

DCDB bus-1

Unit-3 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

157

0.9

0.71

0.639

1.56

0.13

4.5

2.99

12

Unit-4 Bay Marshalling Kiosk

Unit-3 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

157

0.9

0.71

0.639

1.56

0.13

4.5

2.99

13

Unit-3 Bay Marshalling Kiosk

Unit-3 circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

14

Unit-3 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

15

Unit-3 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

16

DCDB bus-2

Unit-4 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

157

0.9

0.71

0.639

1.56

0.13

4.5

2.99

17

Unit-3 Bay Marshalling Kiosk

Unit-4 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

157

0.9

0.71

0.639

1.56

0.13

4.5

2.99

18

Unit-4 Bay Marshalling Kiosk

Unit-4 circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

18

0.9

0.71

0.639

1.56

0.13

4.5

0.34

19

Unit-4 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

20

Unit-4 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

21

DCDB bus-1

Unit-5 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

196

0.9

0.71

0.639

1.56

0.13

4.5

3.72

22

Unit-6 Bay Marshalling Kiosk

Unit-5 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

196

0.9

0.71

0.639

1.56

0.13

4.5

3.72

23

Unit-5 Bay Marshalling Kiosk

Unit-5 circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

18

0.9

0.71

0.639

1.56

0.13

4.5

0.34

24

Unit-5 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

25

Unit-5 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

26

DCDB bus-2

Unit-6 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

196

0.9

0.71

0.639

1.56

0.13

4.5

3.72

27

Unit-5 Bay Marshalling Kiosk

Unit-6 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

196

0.9

0.71

0.639

1.56

0.13

4.5

3.72

28

Unit-6 Bay Marshalling Kiosk

Unit-6 circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

18

0.9

0.71

0.639

1.56

0.13

4.5

0.34

29

Unit-6 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

30

Unit-6 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

31

Unit-6 Bay Marshalling Kiosk

IVT Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

51

0.9

0.71

0.639

1.56

0.13

4.5

0.97

32

Unit-6 Bay Marshalling Kiosk

IVT Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

70

0.9

0.71

0.639

1.56

0.13

4.5

1.33

33

DCDB bus-1

Bus coupler Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

109

0.9

0.71

0.639

1.56

0.13

4.5

2.07

34

Feeder-1 Bay Marshalling Kiosk

Bus coupler Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

109

0.9

0.71

0.639

1.56

0.13

4.5

2.07

35

Bus coupler Bay Marshalling Kiosk

Unit circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.63

36

Bus coupler Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

37

Bus coupler Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11
sheet 3 of 4

ATTACHMENT 1 : CALCULATION SHEETS (220V DC POWER CABLES)

Sl. No. Rev

FROM EQUIPMENT

TO EQUIPMENT

DESIGNATION

DESIGNATION

LOAD
Consumption/O CURRENT IN
Voltage
utput Power
Amp
[V]
[W]
(In)

CABLE
TYPE

CABLE
RATED
LENGTH
No. OF SELECTED
CAPACITY RESISTANCE
RUNS CABLE SIZE
(m)
(/Km)
OF CABLE
mm2

(Iz)

Kt

Ks

Kg

REQUIRED PROTECTIVE
DEVICE
CAPACITY OF
Kd = (Kt x
FEEDER (A) RATING (A)
Ks x Kg)
(In / Kd)
(Ir)

K2S2
(kA2s)

LETPERMISSIBLE
THROUGH
VOLTAGE
(kA2s)
DROP (Vr)

RUNNING
VOLTAGE
DROP (Vpr)

38

Bus coupler Bay Marshalling Kiosk

Line Isolator

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

50

0.9

0.71

0.639

1.56

0.13

4.5

39

DCDB bus-2

Feeder-1 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

109

0.9

0.71

0.639

1.56

0.13

4.5

0.95
2.07

40

Bus coupler Bay Marshalling Kiosk

Feeder-1 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

109

0.9

0.71

0.639

1.56

0.13

4.5

2.07

41

Feeder-1 Bay Marshalling Kiosk

Unit circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.63

42

Feeder-1 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

43

Feeder-1 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

44

Feeder-1 Bay Marshalling Kiosk

Line Isolator

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

50

0.9

0.71

0.639

1.56

0.13

4.5

0.95

45

DCDB bus-1

Feeder-2 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

148

0.9

0.71

0.639

1.56

0.13

4.5

2.80

46

Feeder-3 Bay Marshalling Kiosk

Feeder-2 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

148

0.9

0.71

0.639

1.56

0.13

4.5

2.80

47

Feeder-2 Bay Marshalling Kiosk

Unit circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.63

48

Feeder-2 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

49

Feeder-2 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

50

Feeder-2 Bay Marshalling Kiosk

Line Isolator

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

50

0.9

0.71

0.639

1.56

0.13

4.5

0.95

51

DCDB bus-2

Feeder-3 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

148

0.9

0.71

0.639

1.56

0.13

4.5

2.80

52

Feeder-2 Bay Marshalling Kiosk

Feeder-3 Bay Marshalling Kiosk

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

148

0.9

0.71

0.639

1.56

0.13

4.5

2.80

53

Feeder-3 Bay Marshalling Kiosk

Unit circuit breaker

220

220

1.00

XLPE-Cu

5Cx2.5A

28

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.63

54

Feeder-3 Bay Marshalling Kiosk

Bus Isolator -1

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

33

0.9

0.71

0.639

1.56

0.13

4.5

0.62

55

Feeder-3 Bay Marshalling Kiosk

Bus Isolator -2

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

58

0.9

0.71

0.639

1.56

0.13

4.5

1.11

56

Feeder-3 Bay Marshalling Kiosk

Line Isolator

220

220

1.00

XLPE-Cu

3Cx2.5A

30

9.5

50

0.9

0.71

0.639

1.56

0.13

4.5

0.95

sheet 4 of 4

ATTACHMENT 2 : CALCULATION SHEET (48V DC POWER CABLES)

FROM EQUIPMENT

TO EQUIPMENT

DESIGNATION

DESIGNATION

Voltage
[V]

Consumption/O
utput Power
[W]

LOAD CURRENT
IN Amp

CABLE
TYPE

RATED
CAPACITY OF
CABLE

CABLE
RESISTANCE
(/Km)

LENGTH
(m)

mm2

(Iz)

No. OF SELECTED
RUNS CABLE SIZE

(In)

Kt

Ks

Kg

Kd = (Kt x
Ks x Kg)

REQUIRED
CAPACITY OF
FEEDER (A)

PROTECTIVE
DEVICE RATING
(A)

(In / Kd)

(Ir)

K2S2
(kA2s)

PERMISSIBLE
LETVOLTAGE
THROUGH
DROP (Vr)
(kA2s)

RUNNING
VOLTAGE
DROP (Vpr)

BATTERY BANK 1
48 V BATTERY BANK
48 V BATTERY BANK
48 V BATTERY BANK

48 V DCDB
48 V DCDB
48 V DCDB

48
48
48

15
15
15

XLPE-AL
XLPE-AL
XLPE-AL

1
1
1

2Cx35
2Cx35
2Cx35

1.11
1.11
1.11

0.0783
0.0783
0.0783

20
20
20

0.9
0.9
0.9

1
1
1

0.71
0.71
0.71

0.639
0.639
0.639

23.47
23.47
23.47

80
80
80

10.82
10.82
10.82

0.51
0.51
0.51

0.92
0.92
0.92

0.68
0.68
0.68

48V DCDB
48 V DCDB
48 V DCDB
48 V DCDB
48 V DCDB

PLCC-1
PLCC-2
PLCC-3
PLCC4-Future

48
48
48
48

2.7
2.7
2.7

XLPE-AL
XLPE-AL
XLPE-AL

1
1
1

2Cx2.5
2Cx2.5
2Cx2.5

9.5
9.5
9.5

0.0985
0.0985
0.0985

16
16
16

0.9
0.9
0.9

1
1
1

0.71
0.71
0.71

0.639
0.639
0.639

4.23
4.23
4.23

16
16
16

10.82
10.82
10.82

0.099
0.099
0.099

1
1
1

0.84
0.84
0.84

sheet 1 of 1