Operational Measured Values: To check the operational measured values it

is necessary to inject a 3phase symmetrical current and voltage system (but with
different amplitudes) Inject current amplitudes of IA = 0.5Inom, IB = 0.4Inom,
IC = 0.3Inom (with balanced angles of 120) Inject voltage amplitudes of UAN
= 0.5Unom, UBN = 0.4Unom, UCN = 0.3Unom (with balanced angles of 120)
Depending on the protection / supervision settings the relay might pick up or
give an Alarm, but this does not affect the test (readings are possible to take)
The actual measurement values can be read via DIGSI or the relay display.