Sunteți pe pagina 1din 4

2/3/2016

CMUA

CMUA
ThecentralmonitoringunittypeA(CMUA)isacentralizedmonitoringunit.Itmonitorsthetemperatureofthe
fans,heaterassemblyunit(HAU),andcabinet.ACMUAcanbeusedinanAMP30H(Ver.B),RFC(Ver.B),
TMC11H(Ver.B),IBBS200D(Ver.B),orIBBS200T(Ver.B).

Exterior
ThefollowingfigureshowstheexteriorofaCMUA.
Figure1CMUA

Function
TheCMUAperformsthefollowingfunctions:
Automaticallyadjuststhetemperatureofcabinetswithdifferenttemperaturecontrolmodes.
ReservesportsforthreeBooleaninputstosupportBooleanalarmdetection,butdoesnotsupport
detectionofalarmsreportedbydevicesoutsidethecabinet.
ProvidesanelectroniclabelforRJ45portandrealizesthedetectionofcabinettypes.

Port
ThefollowingfigureshowstheportsonaCMUA.
Figure2PortsonaCMUA

ThefollowingtabledescribestheportsontheCMUA.
Table1PortsontheCMUA
No.
(1)

Silkscreen

Description
Inthe

IntheRFC,thisportisconnectedtothetemperature

http://127.0.0.1:52199/hedex/hdx.do?lib=31185825&v=12&id=&tocURL=resources%252fhert%252fbts3900a%252fbts3900a%252dhd%252fbta%252d1%252d013

1/4

2/3/2016

CMUA

(1)

(2)

Inthe
RFC:TEM
Inthe
IBBS200D
or
IBBS200T:
TEM_BAT
COM_OUT

IntheRFC,thisportisconnectedtothetemperature
sensorattheairintakeventofthecabinettoreceive
temperaturealarms.
IntheIBBS200D/IBBS200T,thisportisconnectedto
thebatterytemperaturesensorinthe
IBBS200D/IBBS200Ttoreceivebatterytemperature
alarms.
Cascadingportconnectedtoalowerleveldevice
IntheAPM30H,thisportisconnectedtothePMU.
IntheRFC,TMC11H,orIBBS200D/IBBS200T,thisport
isconnectedtothelowerlevelCMUA.

(3)

COM_IN

Cascadingportconnectedtoanupperleveldevice
IntheAPM30H,thisportisconnectedtotheBBU.
IntheRFCorTMC11H,thisportisconnectedtothe
BBUoranupperlevelCMUA.
IntheIBBS200DorIBBS200T,thisportisconnectedto
thePMUoranupperlevelCMUA.

(4)

ELU

ConnectedtotheElectronicLabelUnit(ELU)toreceiveELUrelated
alarms.

(5)

GATE

Connectedtothedoorstatussensortoreceivedoorstatusalarms.

(6)

IN0,IN1,andIN2

EachportprovidesoneextendedBooleansignalinput.

(7)

SMOKE

Connectedtothesmokesensortoreceivesmokealarms.

(8)

FAN_EXT

Connectedtotheouteraircirculationfaninthecabinetdoorto
receiveitsalarmsignals.

(9)

PWR

PortfeedingpowertotheCMUA

(10)

TEC

ConnectedtotheTECtoreceiveitsalarmsignals.

(11)

Inthe
APM30H,
TMC11H,
RFC,or
IBBS200D:
FAN1
Inthe
IBBS200T:
FAN_EXT

IntheAPM30HorTMC11H,thisportisconnectedto
thefansinthefanassembly.
IntheRFCorIBBS200D,thisportisconnectedtothe
rightfaninthefanassemblyorfanmountingframe.
IntheIBBS200T,thisportisconnectedtotheouterair
circulationfanontheTECandtoreceivealarmsignals
offansineachcabinet.

(12)

IntheRFC
or
IBBS200D:
FAN2
Inthe
IBBS200T:
FAN_INT

ConnectedtotheleftfaninthefanassemblyintheRFC
orIBBS200D.
IntheIBBS200T,itisconnectedtotheinnerair
circulationfanontheTECtoreceivealarmsignalsof
fansineachcabinet.

Indicator
ThetwoindicatorsontheCMUApanelindicatethestatusoftheCMUA.Thefollowingtabledescribestheir
meanings.

http://127.0.0.1:52199/hedex/hdx.do?lib=31185825&v=12&id=&tocURL=resources%252fhert%252fbts3900a%252fbts3900a%252dhd%252fbta%252d1%252d013

2/4

2/3/2016

CMUA

Table2IndicatorsontheCMUApanel
Silkscreen

Color

State

RUN

Green

Blinking(onfor1sandofffor Theboardisfunctionalandcommunicatingwithits
1s)
upperleveldeviceproperly.

ALM

Red

Meaning

Blinking(onfor0.125sand
offfor0.125s)

Theboardisfunctionalbutfailstocommunicatewith
itsupperleveldeviceformorethanoneminute.

Steadyonoroff

Theboardisfaulty(ifitisnotinthepoweroncheck
state).

Steadyoff

Noalarmisgenerated.

Steadyon

Analarmisgenerated,andtheboardneedstobe
replaced.

Blinking(onfor1sandofffor Analarmisgenerated,andthealarmmaybecaused
1s)
bythefaultinanassociatedboardorport.Therefore,
youneedtolocatethefaultbeforedetermining
whethertoreplacetheboard.

DIPSwitch
OntheCMUA,therearethreeDIPswitches,whichareSW1,SW2,andSW3.TheDIPswitchesareusedto
settheworkingmodeoftheCMUAaccordingtothecabinettype.Thefollowingfigureshowsthepositionsof
theDIPswitchesontheCMUA.
Figure3PositionsoftheDIPswitchesontheCMUA(planform)

Indifferenttypesofcabinets,theDIPswitchesontheCMUAaresetindifferentways,asshowninthe
followingfigure.
Figure4DIPswitchessettingoftheCMUAindifferenttypesofcabinets

http://127.0.0.1:52199/hedex/hdx.do?lib=31185825&v=12&id=&tocURL=resources%252fhert%252fbts3900a%252fbts3900a%252dhd%252fbta%252d1%252d013

3/4

2/3/2016

CMUA

NOTE:
Intheprecedingfigure,thesmallredboxindicatesconnectingtotheupperjumpercap.
HuaweiProprietaryandConfidential
CopyrightHuaweiTechnologiesCo.,Ltd.

http://127.0.0.1:52199/hedex/hdx.do?lib=31185825&v=12&id=&tocURL=resources%252fhert%252fbts3900a%252fbts3900a%252dhd%252fbta%252d1%252d013

4/4

S-ar putea să vă placă și